CONDUIT AND CABLE TRAY RECORD (to be completed by area only) ID E76001A
Description: Tag No:
P. O. No.: Module No.: Turnover System:
Contractor: Sub–System:
Work Package: Area/Unit:
Drawing #:
Item Description of Check Yes No N/A
Verify the following are in accordance with design documents and site ETP’s
01 Supports and Bracing
02 Grounding ( continuous 4/0 Green THNN bonded to each section )
03 Cable fill / spacing
04 Cable tie down
05 Barriers where required
06 Splice Plates
07 Wall penetrations / Sealing Methods
08 Tray Identification Labels installed
09 Expansion joints at 100 ft. intervals
10 Bonding jumpers where required
11 Cable Tray sized correctly
12 Indestructible cable tags at 100 ft. (30 m) intervals and on either side of a
penetration
13 Tray Covers installed where required
14 Tray Fireproofing installed where required
15 Conduit Bond Bushing / Bond Jumper
16 Tray protect-o-wire loop to Fire Relay Panel installed
17 Tray fittings and supports
18 Conduit clamps or connection to tray
Notes: