1900/65A General Purpose Equipment Monitor

Datasheet
Bently Nevada Machinery Condition Monitoring

Description
The 1900/65A General Purpose Equipment Monitor is
designed to continuously monitor and protect equipment that
is used in a variety of applications and industries. The
monitor’s low cost makes it an ideal solution for general-
purpose machines and processes that can benefit from
continuous monitoring and protection.

Inputs

The 1900/65A provides four transducer inputs and four


temperature inputs. Software can configure each transducer
input to support 2- and 3-wire accelerometers, velocity
sensors or proximity sensors. Each temperature input supports
Type E, J, K, and T thermocouples, and 2- or 3-wire RTDs.

Outputs

The 1900/65A provides six relay outputs, four 4-20 mA


recorder outputs, and a dedicated buffered output. The user
can use the 1900 Configuration software to configure the relay
contacts to open or close according to the OK, Alert and
Danger statuses of any channel or combination of channels,
and to provide data from any variable from any channel on any
recorder output. The dedicated buffer output can provide the
signal for each transducer input.
A Modbus Gateway option allows the monitor to provide
static variables, statuses, event list, time and date information
directly to any Modbus client, including Distributed Control
Systems (DCSs), Supervisory Control and Data Acquisition
(SCADA) systems, Programmable Logic Controllers (PLCs), or
System 1 software. The monitor uses an internal counter and a
Modbus client/master time reference to generate time and
date information. Users can upgrade monitors without the
Modbus Gateway by ordering the 1900/01 Communications
Upgrade (see the Ordering Information section). The 1900/65A

Document : 173401
Rev. T
1900/65A General Purpose Equipment Monitor
Datasheet
supports Modbus communications via Ethernet
and a software-configurable RS232/485 serial
port.

Configuration

The user defines monitor operation and the


Modbus Gateway register map by using
software running on a laptop or PC to create a
configuration file and download the file to the
monitor through the built-in Ethernet
connection. The 1900/65A permanently stores
configuration information in non-volatile
memory, and can upload this information to the
PC for changes.

Display Module

The 1900/65A supports an optional


display/keypad to view channel information or
make minor configuration changes. This allows
the 1900/65A to operate as a stand-alone
package. If desired, the user can mount the
display up to 75 metres (250 feet) from the
Monitor Module.

2/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
processes up to four variables per
channel.
Specifications Vibration Up to three bandpass filtered
amplitude measurements.

Inputs Acceleration Users can apply the acceleration


Enveloping enveloping algorithm to one
Acceleration or Reciprocating
Transducer Inputs Acceleration Variable.

Users can configure Channels 1 through 4 Bias Voltage Users may assign the value of the
transducer bias voltage to any of the
to accept input from acceleration, velocity variables.
or displacement transducers.
Configuration Options
Transducer Channel Types
Each variable is independently
Channel Types define the functionality configured with the following
for processing that will be applied to an options.
input signal and the kind of variables or
measurement values that will be derived Vibration l Peak or RMS
from this input. Channel Types also Variables l Metric or English
units
define the kind of sensor that must be l Filter corner
used. Transducer Channel Types include: frequencies
l Full scale range
l Acceleration or Reciprocating l Acceleration
Acceleration integrated to
l Velocity or Reciprocating Velocity velocity
l Radial Vibration (shaft vibration) Enveloped l Filter corner
l Thrust (shaft axial displacement) Variable frequencies
l Standard or
l Position
Enhanced
l Speed demodulation

Acceleration and Reciprocating Filters


Acceleration Channel Types
Vibration 0.5 Hz – 25 kHz configurable 4-pole high-
The Acceleration Channel Type and Variable pass, 4-pole low-pass
Reciprocating Acceleration Channel Type Enveloping
support two- and three-wire acceleration 25 Hz to 5 kHz, configurable 4-pole
High-Pass
sensors. The Reciprocating Acceleration Enveloping
channel type has timed OK channel defeat 125 Hz to 25 kHz, configurable 2-pole
Low-Pass
disabled. Enveloped
0.1 Hz min., but greater than Enveloped
Variable High-
Acceleration Variables and Pass
Variable low-pass 2-pole

Reciprocating Acceleration Variables Enveloped


Greater than Enveloped Variable high-pass
Variable Low-
and less than Enveloping high-pass 4-pole
Acceleration Variables and Reciprocating Pass
Acceleration Variables are filtered and Bias Filter 0.01 Hz 1-pole low-pass
processed measurements from raw OK Filter 2.4 kHz 1-pole low-pass
transducer signals. The Acceleration
Channel Type and Reciprocating Full Scale Range
Acceleration Channel Type continuously
Vibration 20 to 500 m/s2 (2 to 50 g) peak

3/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
and RMS units
l Filter corner
20 to 500 m/s2 (2 to 50 g) peak frequencies
Enveloped
and RMS l Full-scale range
10 to 100 mm/s (0.4 to 4 in/s) l Velocity integrated
Integrated to displacement
peak and RMS
Bias Voltage -24 V
Filters
Accuracy Vibration 0.5 Hz to 5.5 kHz, configurable 8-pole high-
Variables pass, 4-pole low-pass
Vibration Variables ±1% of full scale range
Bias Filter 0.09 Hz 1-pole low-pass
Input Impedance OK Filter: 2.4 kHz 1-pole low-pass

3-wire Voltage Mode 10 kΩ Full Scale Range


Vibration 10 to 50 mm/s (0.5 to 2 in/s) peak and RMS
Integrated 100 to 500 μm (5 to 20 mils) peak to peak
Velocity and Reciprocating Bias Voltage -24 V
Velocity Channel Type
Accuracy
The Velocity Channel Type and
Reciprocating Velocity Channel Type Vibration Variables ±1% of full scale range
support two-wire and three-wire piezo-
velocity sensors. Input Impedance
Velocity Variables and Reciprocating 3-Wire Voltage Mode 10 kΩ
Velocity Variables
Velocity Variables and Reciprocating
Velocity Variables are filtered and Radial Vibration Channel Type
processed measurements from raw
The Radial Vibration Channel Type
transducer signals. The Velocity Channel
measures radial shaft motion using
Type and Reciprocating Velocity Channel
proximity sensors.
Type support up to four continuously
calculated variables per channel. Radial Vibration Variables
Up to three bandpass filtered amplitude Radial Vibration Variables are filtered and
Vibration
measurements.
processed measurements from raw
Users may assign the value of the transducer sensors. The Radial Vibration
Bias
transducer bias voltage to any of the
Voltage
variables.
Channel Type supports up to four
continuously calculated variables per
Configurable Options channel.

Up to three bandpass filtered amplitude


Each variable is independently Direct
measurements
configured with the following
Gap Gap voltage
options.
Up to three bandpass filtered amplitude
Vibration
Vibration l Peak or RMS measurements
Variables l Metric or English
Configurable Options

4/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
Each variable is independently configured transducer signals.
with the following options.
Position Axial position of shaft
Vibration Variables l Metric or English Gap Gap, voltage or position
units
l Filter corner
frequencies Configurable Options
l Number of filter
poles Each variable is independently configured
l Full-scale range with the following options.

Filters Position Variables Metric or English units


Full-scale range
Direct Filter 1 4 to 4000 Hz (240 to 240,000 RPM)
1 to 600 Hz (60 to 36,000 RPM) Filters
Direct Filter 2
Direct Filter: 1.2 Hz 1-pole low-pass
Direct Filter High-pass set by attack and decay,
Characteristics 1-pole low-pass Gap Filter 0.41 Hz 1-pole low-pass

Gap Filter 0.09 Hz 1-pole low-pass OK Filter: 2.4 kHz 1-pole low-pass

Vibration Variables 0.5 Hz to 4 kHz, configurable


Full Scale Range
1-, 2-, or 4-pole high-pass and low-pass,
configurable 1 to 4 mm (50 to 150 mils) span with adjustable
Position
OK Filter 2.4 kHz 1-pole low-pass zero position
Gap -24 V
Full Scale Range
Accuracy
Direct 100 to 500 μm (3 to 20 mils) peak-to-peak
Gap -24 V Position Variables ±1% of full-scale range

Accuracy Input Impedance


Vibration Variables ±1% of full-scale range Non-configurable 10 kΩ

Input Impedance Position Channel Type


Non-configurable 10 kΩ
The Position Channel Type measures
mechanical motion using proximity
sensors.
Thrust Channel Type Position Variables
The Thrust Channel Type measures axial Position Variables are filtered and
shaft motion using proximity sensors. processed measurements from raw
transducer signals.
Thrust Variables
Position Mechanical position
Thrust Variables are filtered and
processed measurements from raw Gap Gap, voltage or position

Configurable Options

5/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
Each variable is independently configured Speed 100 - 100,000 rpm
with the following options.
Events Per Revolution
Position Variables Metric or English units
Full- scale range EPR 0.001 to 1000

Filters Accuracy
Direct Filter 1.2 Hz 1-pole low-pass Speed Variables: ± 0.5 RPM + 0.015% of reading

Gap Filter 0.41 Hz 1-pole low-pass


Input Impedance
OK Filter 2.4 kHz 1-pole low-pass
Non-configurable 10 kΩ
Full Scale Range
1 to 28 mm (50 to 1100 mils) span with adjustable
Position
zero position. Temperature Inputs (Ch. 5 – 8)
Gap -24 V
Channels 5 through 8 support Type E, J, K,
Accuracy and T thermocouples, and 2- and 3-wire
RTDs.
Position Variables ±1% of full scale range
Temperature Variable
Input Impedance
Temperature variables are processed
Non-configurable 10 kΩ measurements from raw transducer
signals. The temperature channel type
processes one temperature variable per
channel.
Speed Channel Type Configurable Options
The Speed Channel Type measures speed
Each Variable is independently configured
using proximity sensors.
with the following options.
Speed Variables Units °C or °F
Speed Variables are filtered and
processed measurements from raw Filters
transducer signals.
Analog Filter 50 Hz 1-pole, low-pass
Speed Up to 4 speed measurements Digital Filter Notch filter will attenuate the first 5
orders of 50 Hz and 60 Hz (49 Hz to 61
Gap Gap, voltage Hz) by a minimum of 100 dB.

Configurable Options Full Scale Range


Each variable is independently configured Type E -200 to 1000 ºC (-328 to 1832 ºF)
with the following options:
Type J -210 to 1200 ºC (-346 to 2192 ºF
Gap Filter 0.09 Hz 1-pole low-pass Type K -200 to 1370 ºC (-328 to 2498 ºF)
OK Filter 2.4 kHz 1-pole low-pass Type T -200 to 400 ºC (-328 to 752 ºF)
10 Ω Cu
-200 to 260 ºC (-328 to 500 ºF)
Full Scale Range α=0.00427

6/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
120 Ω Ni or close contacts according to user-
-80 to 260 ºC (-112 to 500 ºF)
α=0.00672 defined logic statements. Logic
100 Ω Pt statements use the OK, Alert and Danger
-200 to 850 ºC (-328 to 1562 ºF)
α=0.00385: statuses of any channel, or combination of
100 Ω Pt channels as inputs.
-200 to 700 ºC (-328 to 1292 ºF)
α=0.00392:
Logical Operators
Accuracy
AND bypassed channels ignored
All ±1 °C (±1.8 °F) typical @ 25 °C (77 °F) True AND bypassed channels included
Thermocouple OR
±2.5 °C (±4.5 °F) maximum for
Types
thermocouple measurements over –100 °C
(148 °F) Logical Operands
±5 °C (±9 °F) maximum for thermocouple
measurements below –100 °C (-148 °F) Monitor Inhibit
3-Wire RTD ±1.5 °C (±2.7 °F) + 0.5 % full scale Monitor Not OK
(except 10 Ω
Cu) Monitor Danger
3-Wire RTD 10 ±3 °C (±5.4 °F) + 0.5 % full scale
Ω Cu Monitor Alert
2-wire RTDs have additional errors due to
Channel Not OK
2-wire RTD field wire resistance and variations in the
Types field wire resistance due to changes in
Channel Danger
ambient temperature.
Channel Alert
Input Impedance
Variable Danger
Thermocouple Inputs >1 MΩ
Variable Alert
Alarm Status Time Delays Maximum Operands
Position/ Vibration Inputs 50 per relay
Minimum 0.1 second
Relay Configuration
Maximum 60 seconds
Adjustment Resolution 0.1 second The following configuration options are
independent of the relay logic and can be
Temperature / Speed Inputs configured for each relay:

Minimum 1 second l Latching or non-latching


independent of alarm status
Maximum 60 seconds
Adjustment Resolution 0.1 second l Normally energized or normally de-
energized
Relays l Normally open and normally closed
via contacts
Relay Logic
The 1900/65A monitor has six relay Relay Specifications
outputs that users can program to open
Type

7/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
Single pole, double throw (SPDT) When configured for Trip Multiply short-
circuiting the Inhibit/Trip Multiply contact to
Contact Ratings RTN will increase Alert and Danger set points.
Minimum Switched Current 12Vdc/100mA When configured for Inhibit the Inhibit input
will inhibit (bypass or inactivate) Alert and
DC specifications (resistive load) Danger statuses. Short circuiting the INHIBIT
contact to INHIBIT RTN will:
Maximum Switched Current 5A
70W @ 24 Vdc l Set all Variable Danger Statuses to logic 0
Maximum Switched Power
10W @ 48 Vdc l Set all Variable Alert Statuses to logic 0
9W @ 60 Vdc l Set Bypass and Inhibit Statuses to logic 1
Maximum SwitchedVoltage 60 Vdc
Monitor Alarm Inhibit switch, and Monitor Trip
Multiply switch mapped in the Modbus Gateway will
AC specifications (resistive load) remotely inhibit Alert and Danger statuses or activate
Trip Multiply respectively.
Maximum Switched Current 5A
Maximum SwitchedPower 150 VA Electrical
Maximum SwitchedVoltage 30 Vac
Activate Inhibit 50 kΩ or less (shorted)
De-activate Inhibit 500 kΩ or greater (open)
Refer to Hazardous Area Special Considerations
Section for Relay specifications when used in
hazardous area applications.

Contact Life Reset


100,000 cycles @ 5 A, 250 Vac Use the Reset input to reset all latched
alarms and latched relays. If the condition
200,000 cycles @ 1 A, 24 Vdc
driving the status no longer exists, short-
circuiting the RESET contact to RESET RTN
Sealing will:
Epoxy
l Reset all latched Alert statuses
Insulation Resistance l Reset all latched Danger statuses
1000 MΩ minimum @ 500 Vdc l Reset all latched Not OK statuses
l Reset all latched relays
Writing a non-zero value to the Modbus register
Inhibit, Reset, and Trip Multiply Reset Latched Statuses mapped in the Modbus
Gateway will reset the monitor remotely.
Inputs
Electrical
Inhibit/Trip Multiply
Activate Reset 50 kΩ or less (shortened)
Users can use software to configure the
De-activate Reset 500 kΩ or greater (open)
Inhibit/Trip Multiply input as either Inhibit or
Trip Multiply.

Transducer Supplies

8/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
All outputs are short-circuit protected. cable)

Two-Wire Current Mode


Current Source 3.3 mA ± 5%
Monitor Module
Open Circuit Voltage 21 to 24 Vdc
Each input for channels 1 through 4 has a
Three-Wire Voltage Mode dedicated buffered output. The signal
does not have gain, and is not scaled.
Supply Voltage -24.02 Vdc to –23.47 Vdc
Each output is buffered to provided short
Maximum Rated Current 15 mA circuit and EMI protection.
Short Circuit Current 15.1 mA to 23.6 mA
Output Impedance 550 Ω
Bandwidth 40 kHz minimum

4-20 mA Interface
Number of
Four outputs, any of which may be Indicators
configured to provide data from any channel
Outputs
and any variable.
Monitor Module
Proportional 4 to 20 mA values are proportional to the
Value channel full-scale. Status Indicates when the monitor is functioning
Loop Supply LED properly.
18 to 36 Vdc
Voltage
Loop Display Module
600 Ω maximum
Resistance
Indicates when the monitor is functioning
Accuracy 2% over operating temperature range OK LED
properly.
Update Rate 100 mS
Alert LED Indicates an Alert condition.
Resolution 10 mA
Danger LED Indicates a Danger condition.
Clamp 2 mA ± 10% (configurable for Not OK and
Indicates that the monitor is in Bypass
Current Bypass) Bypass LED
mode.
Trip Multiply Indicates that the monitor is in Trip
LED Multiply mode.

Buffered Outputs Channel LED Indicates channel is active.


Display Liquid Crystal Display (LCD) with backlight
Display Module Dimensions
68.6 mm (2.7 in) wide x 35.6 mm (1.4 in)
high
A single buffered output on the Display
Module provides access to input Channels Power Requirements
1 through 4. The signal does not have
gain, and is not scaled. This output is Input Voltage Range 18 to 36 Vdc
buffered to provide short circuit and EMI
Operating Current 0.35 A typical, 1.0 A maximum
protection.
Operating Power 8.5 W typical, 14 W maximum
Output
550 Ω
Impedance
40 kHz minimum (Display Module
Bandwidth attached directly to Monitor)
8 kHz minimum (75 m (250 ft.) of

9/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Physical l Change bypass modes and setpoints on


the fly
l Display component for statuses and
Monitor Module variables
Dimensions (L x 196.9 mm x 149.4 mm x 74.4 mm (7.75 in l Display Hardware Identification and
W x H) x 5.88 in x 2.93 in) manufacturing information
Weight 0.77 kg (1.70 lb) l Context-specific help

Environmental
Display Module Temperature
Dimensions (L x 196.9 mm x 149.4 mm x 32.8 mm (7.75 in Operating -20 to +70 ºC (-4 to +158 ºF)
W x H) x 5.88 in x 1.29 in)
Storage -30 to +90 ºC (-22 to +194 ºF)
Weight 0.40 kg (0.89 lb)

Humidity
Mounting Operating 95% non-condensing, maximum

DIN Rail Storage 95% non-condensing, maximum


35 mm DIN rail
Option
Bulkhead Bulkhead mounting plate
Option
Weatherproof NEMA 4X/IP66 Fiberglass Housing with Supported Transducers
Enclosure window, 300.2 mm x 249.4 mm x 209.8 mm
Option (11.82 in x 9.82 in x 8.26 in) Bently Nevada
Channel Type
Transducer

Acceleration and Reciprocating 330400 Accelerometer


Acceleration
Configuration Software 330425 Accelerometer
190501 Velomitor
The 1900 Configuration Software package
Velocity and Reciprocating 330500 Velomitor
contains everything necessary to install,
configure, and maintain the 1900/65A monitor. Velocity 330525 Velomitor
330750 Velomitor
l Feature tools for installing and
troubleshooting 3300 5 & 8 mm
l Simple display to help with configuration Proximitor System
l Ability to browse network for 1900 3300 XL 8mm Proximitor
monitors System
l Network configuration 3300 XL 11mm
l Configuration for channels, variables, Proximitor System
setpoints, tag names, recorders and filters
Radial Vibration, Thrust, and 3300 XL NSv Proximitor
l Configuration for the optional Modbus
Speed System
Gateway
l Configuration for relays and relay voting 7200 5 & 8mm
logic Proximitor System
l Off-line configuration allowing use of 7200 11mm Proximitor
software when hardware is not available System
l Firmware upgrade function and 7200 14 mm Proximitor
diagnostics System

10/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
3300 5 & 8 mm
Proximitor System
3300 XL 8mm Proximitor
System
3300 XL 11mm
Proximitor System
3300 XL 25mm
Proximitor System
3300 XL 50mm
Position
Proximitor System
3300 XL NSv Proximitor
System
7200 5 & 8mm
Proximitor System
7200 11mm Proximitor
System
7200 14 mm Proximitor
System

The 1900/65A provides default configuration settings


for Bently Nevada transducers. The user can
configure the 1900/65A to accept other transducers.

11/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Hazardous Area
Compliance and Approvals
Certifications For the detailed listing of country and product specific
approvals, refer to the Approvals Quick Reference
Guide (108M1756) available from www.Bently.com.
FCC
This monitor is not certified for installation in
This device complies with part 15 of the Class 1 Div 1 locations, but it will support
FCC Rules. Operation is subject to the transducers installed in Div 1 locations via the
following two conditions: use of galvanic isolators and barriers. If galvanic
l This device may not cause harmful isolators are used, no change is necessary to the
interference. installation. A removable ground jumper allows
l This device must accept any the monitor to support zener barrier
interference received, including installations. Removing the jumper will
interference that may cause disconnect circuit common from chassis at the
undesired operation. monitor so that chassis can be connected at the
barrier.
EMC
CSA/NRTL/C
EN 61000-6-2: 2005
Ex/ AEx nA nC IIC Gc:
EN 61000-6-4: 2007 +A1:2001 Class I, Zone 2:
Class I, Division 2, Groups A, B, C,
EMC Directive 2014/30/EU and D
T4 @ -20°C [Ta [+70°C
Electrical Safety Vn = 18 to 36 Vdc @ Imax = 1A
per drawing 173089
EN 61010-1: 2010
LV Directive 2014/35/EU
ATEX/IECEx
ATEX
II 3 G
EN 60079-0: 2012 Ex nAC IIC T4 Gc
EN 60079-15: 2010
T4 @ Ta = -20°C [Ta [+70°C
ATEX Directive 2014/34/EU

RoHS Special Considerations


RoHS Directive 2011/65/EU l Hazardous area installations require
relay contact voltages below 30 Vac
Maritime rms, or 30 Vdc to minimize hazard.
l Hazardous area installations require
ABS 2009 Steel Vessels Rules
relay contact amperages below 5
1-1-4/7.7,4-8-3/1.11.1,4-9-7/13 Amps DC, or AC to minimize hazard.

12/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet
00 None
01 Modbus communicationsw

Ordering Information
For a detailed listing of country- and product-
specific approvals, refer to the Approvals Quick
Reference Guide (document 108M1756) available
from www.bently.com.

1900/65A General Purpose


Equipment Monitor
1900/65A-AA-BB-CC-DD-EE

A: Power Option
00 18 to 36 Vdc
00 110 to 220 Vac @ 50 to 60 Hz (external supply)
B: Display Option
00 No display
01 Attached display (no cable) Figure 1: DIN Rail Mount
02 Display with 10’ PVC cable
03 Display with 10’ unassembled PVC cable
04 Display with 10’ TEF cable
05 Display with 10’ unassembled TEF cable
C: Mounting Option
00 None
01 DIN rail mount
02 Bulkhead Mount
Fiberglass NEMA 4X/IP66 WP housing with window
03
in door
1900/55 replacement kit (See "1900/65A General
04
Purpose Equipment Monitor" above)*
ProTIM Housing, Wiring and Mounting
07 HardwareSee "ProTIM Housing Dimensions" on
page 21
Figure 2: Bulkhead Mount
* Uses existing 1900/55 weather-proof housing
and requires power option A01 (110/220 Vac to
24 Vdc external power supply)

D: Approvals Options
00 None
01 Multiple approvals

See Hazardous Areas Approvals section for specific


certifications. Maritime approvals included with all
approval options.

E: Communications Option

13/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

1900/01 – 1900/65A General


Communications Monitor,
Communications Upgrade
1900/01-AA-BB-CC-DD

A: Order Type Option


01 New order (CD, key, and binder)
98 Replacement licenses (key)
99 Configuration Software only (CD)
B: Communications Option
01 Modbus comm.
C: License Key Type Option
Figure 3: NEMA 4X/IP66 WP Housing 00 None
01 USB license key
D: License Key Type Option
XX Total Licenses (1 to 99)

Figure 4: 1900/55 Replacement Kit

14/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Graphs and Figures


Note: All dimensions shown in millimeters (inches) except as noted.

Figure 1: Monitor Module Dimensions

15/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Figure 2: Display Module Dimensions

16/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Figure 3: Combined Dimensions

17/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Figure 4: Weatherproof Housing Dimensions

18/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Figure 5: Weatherproof Door Drill Pattern

19/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Figure 6: Weatherproof Door Dimensions

20/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Figure 7: ProTIM Housing Dimensions

21/22 173401 Rev. T


1900/65A General Purpose Equipment Monitor
Datasheet

Copyright 2019 Baker Hughes, a GE company, LLC ("BHGE") All rights reserved.
Bently Nevada, Orbit Logo, Proximitor, Velomitor and System 1 are registered trademarks of BHGE in
the United States and other countries. All product and company names are trademarks of their
respective holders. Use of the trademarks does not imply any affiliation with or endorsement by the
respective holders. This product may be covered by one or more patents, please see Bently.com/legal
for current status. The information contained in this document is subject to change without prior
notice.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1.775.782.3611 Bently.com

22/22 173401 Rev. T