Liebert CRV4 25 To 66 KW 380 & 460V Technical Manual May 23
Liebert CRV4 25 To 66 KW 380 & 460V Technical Manual May 23
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use, or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual
Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual
TABLE OF CONTENTS
1 Product Overview 1
1.1 Product Introduction 1
1.2 Product Appearance 1
1.3 Model Nomenclature 2
1.4 Main Components 3
1.5 Optional Components 4
2 Technical Parameters 7
2.1 Mechanical Parameters 7
2.1.1 Mechanical Parameters Of Indoor Unit 7
2.1.2 Positioning of Bottom and Top Plate Inlet and Outlet Access 7
2.2 Component Parameters 11
2.3 Performance Parameters 15
2.4 Electrical Performance 18
2.5 Noise Performance 18
3 Application Guidelines 19
3.1 Conditions of Use 19
3.1.1 Operating Environment 19
3.1.2 Storage Environment 19
3.2 General Layout 19
3.3 Cooling System Connection 22
3.3.1 Pipe Connection 23
3.3.2 Adding Extension Kits (On-site Installation) 27
3.3.3 Charging Refrigerant and Adding Lubricating Oil 30
3.3.4 Adding Lubricating Oil 30
3.4 Electrical Installation 31
3.5 Connecting the Control Cables 35
3.5.1 Water Underfloor Sensor 35
3.5.2 SIC Card 36
3.5.3 Remote Shutdown 36
3.5.4 Outdoor Unit Signal Control 36
3.5.5 Common Alarms 36
3.5.6 Connecting Extension Kit Solenoid Valve (Optional for On-site Installation) 36
3.5.7 Teamwork Control 36
3.6 Connecting Condensate Drainage Pipe on Indoor Unit 36
3.7 Connecting Humidifier Water Inlet Pipe 40
3.7.1 Connecting Electrode Humidifier Water Inlet Pipe 40
3.7.2 Connecting Wet Film Humidifier Water Inlet Pipe 41
3.8 Rack Temperature Sensors 42
i
ii
Appendix B: Alarm 85
Appendix C: Hazardous Substances 87
Appendix D: Circuit Diagram 89
Appendix D1 CR025 Circuit Diagram 90
Appendix D2 CR035 Circuit Diagram 91
Appendix D3 CR045 Circuit Diagram 92
Appendix D4 CR036 Circuit Diagram 93
Appendix D5 CR066 Circuit Diagram 94
iii
iv
1 Product Overview
This section describes the features, appearance, model description, main components, and optional components of the
Vertiv™ Liebert® CRV4 series air-cooled precision air conditioner (hereafter referred to as CRV4 or the unit).
The unit is suitable for installing between a row of high-density computer cabinets to form a "hot aisle-cold aisle"
configuration. The heat generated by the equipment enters the unit from the hot aisle, and is filtered, cooled, and then
returned to the cold aisle. The unit can be placed between the cabinets or at the end of a row of cabinets, as it is equipped
with air baffle and can easily adjust the air supply direction to the left, right or both sides.
CRV4 has all the functions of a standard precision air conditioner, including refrigeration, heating, humidification,
dehumidification, air filtration, condensate management, temperature control, alarm function, and data communication.
The standard model adopts air-cooled heat dissipation and can be used with a centralized LVC condenser or a new Liebert
PEX condenser according to different environmental conditions.
1 Product Overview 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
C R 0 3 6 R A 1 N 8 S 7 1 2 E 3 0 0 0 0 P V 0 4 0
3, 4, 025/ 035/
Cooling capacity Nominal cooling capacity, kW
5 036/045/066
0 None
11 Humidification S Electrode humidifier
W Wet film humidifier
S Standard display
12 Display
7 Global HMI 7-inch screen
0 None
13 Reheat
1 Electric heater (single-stage)
2 G4 (EU4) filter
14 Filtration
0 G4 (EU4) filter + filter clog switch
15 Coil and valves E Standard DX air- cooled coil, electronic expansion valve (EEV)
0 None
Mains disconnect switch high voltage
17 A Dual power supply (interlocking contactor)
options
T Dual power supply (ATS)
2 1 Product Overview
S SIC card
7 Unity card
20 Sensor 0 None
P Standard packaging
21 Packaging
C Packaging for ocean shipping
A None
22 Special requirements
V Condensate pump
0 Bottom piping
23 Piping
1 Top Piping
Compressor
The DC brushless compressor features low vibration, low noise, and high reliability. It is connected with suction and
discharge pipes with threaded connectors. It is convenient and easy to replace.
Evaporator
The evaporator uses high-efficiency, finned tube heat exchanger. It has a larger windward area and a smaller pressure drop.
The flow path is specially optimized to improve the utilization rate of the heat exchanger and ensure that the supply air
temperature is uniform. The surface is hydrophilic. There are condensate drainage pans in the middle and bottom of the
evaporator.
EEV
The EEV monitors temperature and pressure signals to provide accurate regulation of the refrigerant flow.
Humidifier
The unit can be equipped with electrode humidifier or wet film humidifier. CR025, CR035 and CR045 are equipped with
electrode humidifier as standard configuration. CR025, CR035 and CR045 can be configured with wet film humidifier.
CR036 and CR066 are equipped with wet film humidifier as standard configuration and cannot be installed with electrode
humidifier.
The electrode humidifier has a simple structure and is easy to disassemble and maintain. It has a short humidification time
and provides a large amount of humidification. The wet film humidifier is simple to control and has low water quality
requirements and low energy consumption.
1 Product Overview 3
Fan
EC fan provides high efficiency and saves energy and space. It is hot-swappable.
Electric Heater
PTC electric heater has fast heating speed and provides uniform heat. It is safe and reliable.
Sight Glass
Sight glass serves as the window of system circulation. Through it, you can observe the status of the refrigerant and detect
the water content of the system. When the water content exceeds the standard, the sight glass background color will
change.
Filter Drier
Filter drier can effectively remove the moisture present in the system, filter the impurities generated by the long-term
operation of the system, and ensure the normal operation of the system. It is connected to the air conditioner with threaded
connectors, making it easy to replace.
Display Screen
The unit is configured with 7-inch color screen or LCD screen. The user interface operation is simple. The multi-level
password protection can effectively prevent unauthorized operation. It also provides power failure auto-restoration and high
& low voltage protection functions. The operation status of the components are available on the respective menus. The
expert-level fault diagnosis system can automatically display the current fault information, facilitating easy maintenance. It
can store up to 1,000 historical event records.
Monitoring Card
Vertiv RDU-SIC monitoring card with RJ45 interface and USB interface:
4 1 Product Overview
• Use the web browser to monitor the smart devices and the environment data of the equipment room through
the web server function provided by the SIC card.
• Use the network management system (NMS) to monitor smart devices and computer room environment
through the SNMP agent function provided by the SIC card.
• Use the computer room management software (RDU-Manager) to monitor smart devices and computer room
environment through the TCP/IP interface provided by the SIC card.
• Use the centralized management software (Nform) to monitor smart devices through the Velocity Server
service function provided by the SIC card.
1 Product Overview 5
6 1 Product Overview
2 Technical Parameters
This section describes the technical parameters of CRV4.
2.1.2 Positioning of Bottom and Top Plate Inlet and Outlet Access
Positioning of Bottom Plate Inlet and Outlet Access
(Overlooking the bottom plate, from the rear door, the air return side)
2 Technical Parameters 7
8 2 Technical Parameters
Compressor air discharge pipe opening Ø16 Ø22 Ø22 Ø19 Ø22
Evaporator liquid inlet pipe opening Ø12.7 Ø16 Ø16 Ø16 Ø16
Wet film humidifier water inlet pipe ID9 x T3 ID9 x T3 ID9 x T3 ID9 x T3 ID9 x T3
Gravity condensate drainage pipe ID16 x T4 ID16 x T4 ID16 x T4 ID19 x T4.5 ID19 x T4.5
Electrode humidifier water inlet pipe connector 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread - -
2 Technical Parameters 9
Compressor air discharge pipe opening Ø16 Ø22 Ø22 Ø19 Ø22
Evaporator liquid inlet pipe opening Ø12.7 Ø16 Ø16 Ø16 Ø16
Humidifier water inlet pipe 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread
Pump condensate drainage pipe 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread
10 2 Technical Parameters
NOTE: To prevent cuts to the power cables, the protective holes for the cables are fitted with wire sheaths.
Type EC fan with external power module EC fan with external power module
Fan
Quantity 6 6
2 Technical Parameters 11
Type V-shape finned tube heat exchanger V-shape finned tube heat exchanger
Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card (optional)
Quantity The unit can be configured with at most 1pcs of monitoring card
Type EC fan with external power module EC fan with external power module
Fan
Quantity 8 8
Type V-shape finned tube heat exchanger V-shape finned tube heat exchanger
12 2 Technical Parameters
Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card
Quantity The unit can be configured with at most 1pcs of monitoring card
Type EC fan with external power module EC fan with external power module
Fan
Quantity 10 10
Type V-shape finned tube heat exchanger V-shape finned tube heat exchanger
Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card
Quantity The unit can be configured with at most 1pcs of monitoring card
2 Technical Parameters 13
Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card
Quantity The unit can be configured with at most 1pcs of monitoring card
14 2 Technical Parameters
Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card
Quantity The unit can be configured with at most 1pcs of monitoring card
40°C DB 20%RH
37°C DB 24%RH
2 Technical Parameters 15
35°C DB 26%RH
32°C DB 29%RH
30°C DB 34%RH
Note:
• The cooling capacity is the net cooling capacity value. All capacities are nominal; actual performance values may vary ±5% from nominal.
• The data in the table are rated data with standard G4 filter. Certain options or combinations of options may result in reduced airflow.
• For standard air volume, see Table 2-9
The maximum performance of CRV4 is the ultimate cooling capacity that the unit can achieve, and it is the highest
performance that can be achieved when the compressor and fan are increased to the highest speed. On the one hand, this
function is to enable the unit to quickly reduce the current high ambient temperature when it is turned on after the initial
installation, and on the other hand, it is to deal with the sudden high ambient temperature exceeding the design conditions
in the computer room and data center.
40°C DB 20%RH
16 2 Technical Parameters
37°C DB 24%RH
35°C DB 26%RH
32°C DB 29%RH
30°C DB 34%RH
Note
• The cooling capacity is the net cooling capacity value. All capacities are nominal; actual performance values may vary ±5% from nominal.
• The data in the table are rated data with standard G4 filter. Certain options or combinations of options may result in reduced airflow.
2 Technical Parameters 17
18 2 Technical Parameters
3 Application Guidelines
This section describes the conditions of use, general layout, refrigeration connections, electrical connections, water pipe
connections, and temperature sensors of CRV4.
Ambient temperature -20 °C to +45 °C. If a low ambient kit is configured, the lowest outdoor operation temperature
Outdoor
is -34 °C
Storage
Indoor, clean, no dust
environment
Ambient
-40 °C to +70 °C
temperature
Total transportation and storage time should not exceed six months; otherwise the performance of the system needs to be re-
Storage time
calibrated
3 Application Guidelines 19
7 Raised floor
20 3 Application Guidelines
NOTE: When the condenser is higher than the compressor, install a reverse bend on the gas pipe and liquid pipe of
the condenser to avoid the backflow of the liquid refrigerant when shutting down.
NOTE: When installing the reverse bend, ensure that the top bend of the reverse bend is higher than the highest row
of copper pipes of the condenser.
3 Application Guidelines 21
2 Oil trap (installing one oil trap at every 7.5 m vertical rise) 14 Schrader valve 3
22 3 Application Guidelines
NOTE: indicates the pipes that are laid on site (completed by technicians).
NOTE: Oil trap is not provided by Vertiv™. It is recommended to install it to ensure normal operation and convenient
maintenance.
NOTE: Solenoid valve and check valve are required when the equivalent pipe length is larger than 30 m.
The horizontal part of the pipe should be tilted downward after being led out of the compressor, and its inclination should
be at least 1:200 (5 mm should be lowered every 1 m). If the pipe is in an area affected by cooling equipment (or under a
raised floor), the pipe should be insulated.
The top and bottom plate of the unit have refrigeration pipe fittings and labels.
3 Application Guidelines 23
24 3 Application Guidelines
3 Application Guidelines 25
Considering the influence of pipe diameter on the pressure drop of the system, select the pip according to the
recommended size in Table 3.4.
Note: If the height difference is positive, the condenser is higher than the indoor unit. If the height difference is negative, the condenser is lower than the
indoor unit.
26 3 Application Guidelines
Pipe length Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe
10 m 19 12.7 19 16 22 16 19 16 25 19
20 m 19 16 22 16 25 19 22 16 25 19
30 m 22 16 25 16 28 19 25 16 28 22
40 m* 22 16 25 19 28 22 25 19 28 22
50 m* 22 19 25 22 28 22 25 19 32 25
Note:
• * indicates that a pipe extension kit needs to be added
• If the length of the pipe exceeds 50 m, consult Vertiv™
• If the outdoor ambient temperature is lower than -20 °C, the low ambient kit needs to be used. Please consult Vertiv™
When installing extension kits on site, in order to prevent pipeline exposure, it is recommended to install the check valve of
the extension kit on the outer engineering pipeline of the gas pipe, and install the solenoid valve body on the outer
engineering pipeline of the liquid pipe ball valve, the outside or bottom of the equipment.
During the installation process, you do not need to cut the pipeline of the indoor unit, but open the ball valve for maintaining
pressure and evacuating the system after the installation of the entire system. This avoids the moisture absorption of the
compressor lubricating oil and ensures the safety and life of the compressor. For electrical wiring of extension kits, see
Section 3.5.6.
3 Application Guidelines 27
• For the unit with bottom piping, the check valve can be installed on the gas pipe between the floor and the
ground under the indoor unit. For the unit with upper piping, the check valve can be installed on the gas pipe
above the indoor unit.
• Whether the unit is upper piping or bottom piping, the position of the check valve should be as close as
possible to the indoor unit.
• When welding the check valve, pay attention to the arrow on the valve body, which indicates the refrigerant
flow direction in the valve body. Make sure that the arrow is facing the condenser.
• For the unit with bottom piping, the solenoid valve can be installed near the floor and the ground under the
indoor unit. For the unit with upper piping, the solenoid valve can be installed near the indoor unit.
• Whether the unit is upper piping or bottom piping, the position of the solenoid valve should be as close as
possible to the indoor unit.
• The valve body and solenoid valve coil delivered to the site are separated. The valve body should be installed
on the refrigerant liquid pipe horizontally. Pay attention to the arrow on the valve body. The arrow indicates the
refrigerant flow direction in the valve body, and ensure that the arrow is facing the indoor unit.
• After welding the solenoid valve on the liquid pipe, install the coil. Remove the cover of the wiring terminals,
remove the cap by switching the slot in the middle, direct the cable through the cable hole in the cover, plug
the two terminals (black wire to pin 1 and brown wire to pin 2), reinstall the cap by switching the slot in the
middle, and reinstall the cover.
28 3 Application Guidelines
1 Wire connection base 3 Reinstalling the screw that was removed from the coil
Removing the cap by switching the slot in the middle, connecting the
2
wires, and reinstalling the cap
• Clip the coil of the valve body and press the coil tightly to ensure complete contact between the coil and valve
body. Please be noted to first install the spring provided with the valve onto the valve.
Item Description
2 Clipping the coil of the valve body and pressing the coil tightly
3 Application Guidelines 29
Inferior or counterfeit refrigerants will seriously damage the system. Please use refrigerants certified by Vertiv. If the use of
inferior refrigerants causes abnormal system failure or damage, Vertiv does not assume warranty responsibility. The
refrigerant brand certified by Vertiv is:
WARNING! Do not use inferior refrigerants. Vertiv does not assume warranty responsibility for any
consequences caused by inferior refrigerants.
The unit is charged in the factory with 2 bar nitrogen for shipping
Table 3.6 LSF Outdoor Unit Recommended Refrigerant Charge (Unit: kg)
Outdoor unit model LSF38 LSF42 LSF52 LSF62 LSF76 LSF85
Table 3.7 LVC Outdoor Unit Recommended Refrigerant Charge (Unit: kg)
Outdoor unit model LVC088 LVC106 LVC140 LVC152 LVC170
The recommended amount of refrigerant charge is calculated according to the following formula:
Recommended refrigerant charge (kg) = Recommended outdoor unit refrigerant charge + Recommended indoor unit
refrigerant charge + Recommended amount of refrigerant per unit length (kg/m) × Total length of liquid pipe (m)
Where Recommended amount of refrigerant per unit length (kg/m) is shown in the table below.
16 0.174 25 0.431
19 0.245 28 0.517
30 3 Application Guidelines
NOTE: CR025, CR045, CR036, and CR066 units use POE (32-3MAF) lubricating oil. CR035 uses PVE (FVC68D)
lubricating oil.
WARNING! Adding inferior lubricating oil or adding an incorrect type of lubricating oil can damage the
system. The quality issues caused by this are not covered by the warranty.
12.7
16
19 No need to add extra Recommended amount of additional charge of lubricating oil = Amount of refrigerant to add when the
22 lubricating oil pipe length exceeds 30 m × 10%
25
28
3 Application Guidelines 31
Figure 3.10 Electric Control Box (with Rear Door Opened at 120 Degrees)
CR025 NDM1-63C40/3 40
CR035 NDM1-63C50/3 50
CR045 NDM1-63C63/3 63
CR036 NDM1-63C40/4 40
CR066 NDM1-63C63/4 63
Connect the L1, L2, L3, N, and PE to corresponding terminals of the field power supply. Reserve a certain margin of the inlet
cable and fix it to the clips on the inner side of the unit.
For the cable model selection, refer to the rated full load current value (FLA) of the unit.
32 3 Application Guidelines
Figure 3.11 Cable Access on the Top Plate and Bottom Plate
3 Application Guidelines 33
34 3 Application Guidelines
70, 71 Outdoor unit control cable A2, B2, 12V, GND SIC card
75, 76 Common alarm A1, B1 Outdoor communication, for the unit with refrigeration pump or the EBM version
WARNING! Before connecting the control cable, take appropriate anti-static measures.
3 Application Guidelines 35
NOTE: When the 37 and 38 terminals are disconnected, the unit will shut down.
3.5.6 Connecting Extension Kit Solenoid Valve (Optional for On-site Installation)
The extension kit solenoid valve has two control cables. Connect them to the corresponding terminals on the control board.
For details on terminal number, see Appendix A.
To discharge the condensate from the bottom plate, route the discharge hose out of the gravity condensate drainage hole or
the pump condensate drainage hole, connect the hose with a connector, and then connect it to your drainage system.
To discharge the condensate from the top plate, the discharge copper pipe has been routed out of the top plate. You only
need to connect the copper pipe connector (1/2’’-BSP) to your drainage system.
To use only gravity drainage, route the discharge pipe (inner diameter: 16 mm) out of the gravity condensate drainage hole
and connect the pipe to your drainage system. To ensure that the condensate water can be discharged, set a water trap.
Note the following requirements:
• Use electroplated steel pipe, PVC, or polyethylene pipe with good flexibility as the water pipe.
36 3 Application Guidelines
2 Bracket 5 Minimum 20 cm
NOTE: Do not cut the bracket of the water trap. Otherwise, the water drainage will be affected.
NOTE: Before starting the unit, fill water to the water trap to avoid water from blowing out of the pan.
NOTE: To avoid leakage, use Teflon raw material belt between the drainage pipe and the connector.
NOTE: For the model with an electrode humidifier, because high-temperature water flows in the electrode humidifier,
you must use the water pipe with a heat resistance higher than 90°C.
NOTE: For the unit with condensate pump, the pump head should not exceed 5 m.
3 Application Guidelines 37
38 3 Application Guidelines
3 Application Guidelines 39
To supply water to the humidifier from the top plate, a pipe connector has been installed on the humidifier water inlet hole
on the top plate. Connect the connector to your drainage system.
The connection must be sealed to prevent water leakage, and the main line pressure range should be 100 kPa to 700 kPa.
Where the main pipe pressure may exceed 700 kPa, a pressure reducer should be installed. Where the main pipe pressure
is less than 100 kPa, there should be a collection tank and a water pump system.
NOTE: Some products may contain parts that are subject to local regulations
Figure 3.15 Bottom Piping for Electrode Humidifier Water Inlet Pipe
40 3 Application Guidelines
To supply water to the humidifier from the top plate, a pipe connector (1/2"-BSP) has been installed on the humidifier water
inlet hole on the top plate. Connect the connector to your drainage system.
The connection must be sealed to prevent water leakage, and the main line pressure range should be 100 kPa to 700 kPa.
Where the main pipe pressure may exceed 700 kPa, a pressure reducer should be installed. Where the main pipe pressure
is less than 100 kPa, there should be a collection tank and a water pump system.
NOTE: The field-supplied water pipe should be cleaned to prevent impurities from entering the humidifier.
3 Application Guidelines 41
42 3 Application Guidelines
Otherwise the device will not operate properly. Plug the connector of the rack temperature sensor into the TB3 connector.
After connecting the cable, route the cable from the top or bottom of the unit and connect the cable to the first sensor, then
from the first sensor to the second sensor, and so on, to form a connection chain. Secure the temperature sensor in front of
the hottest heat source in the rack and do not fix it in front of an empty slot. During operation, attach the magnet of each
sensor to the surface of the rack. The sensor should be fixed where there is most likely a lack of sufficient cold air.
The IRM-S02TH address settings for the rack temperature sensor are shown in Table 4.3 Application Guidelines on page 19
.
Item Description
3 Application Guidelines 43
Rack temperature 1 0 0 0 1 0 0 10
Rack temperature 2 0 0 0 1 0 1 11
Rack temperature 3 0 0 0 1 1 0 12
1: ON
0: OFF
Rack temperature 4 0 0 0 1 1 1 13
Rack temperature 5 0 0 1 0 0 0 20
Rack temperature 6 0 0 1 0 0 1 21
44 3 Application Guidelines
4.1 Features
The micro-controller has the following features:
• Monitors and displays the operation status of the air conditioner to keep the environment within the set range.
• Configured with a 7-inch color screen, which makes user interface operation simple.
• Provides a three-level password protection to effectively prevent unauthorized operation.
• Provides self-recovery upon power failure, high voltage and low voltage protection, phase loss and anti-phase
protection, etc.
• Allows users to accurately understand the main parameters and operating status of the system.
• Displays the measured temperature and humidity curves in real time.
• Displays the running time of critical components in real time.
• Provides expert-level fault diagnosis and displays the current fault information to facilitate maintenance
personnel in servicing and repair.
• Stores up to 1000 historical alarm records.
4.2 Appearance
When the screen is in black screen state, tap the screen, and the service hotline will be displayed. The service hotline will
disappear after 15 seconds.
The indicator is located under the screen. It has four colors and their indication is described in the table below.
Yellow Unit shuts down, or the display fails to communicate with the control board
4.3 Interface
4.3.1 Main Interface
After the boot is completed, the main interface is displayed, containing the menu button, date and time, unit address,
display address, and unlock button. The menu button cannot be tapped because it has not been unlocked. After tapping the
unlock button and inputting the correct password, the temperature and humidity setting button, curve button, unit address,
display address, and switch button will be displayed. Press and hold the power on/off button for at least two seconds to
toggle between the power on/off function.
In control mode, the text on the left side of the circle indicates the humidity control mode (air supply humidity control). The
text on the right indicates the temperature control mode (default air supply control mode, consistent with the compressor
control mode). The temperature value in the circle represents the measured temperature and humidity value (default air
supply temperature) in the current mode. The humidity value represents the theoretical air supply humidity. For the two
triangles on the circle, the left represents the supply air humidity set point, and the right represents the temperature set
point in the current mode. Tap the toggle button 1 to switch between the graph and the list display. Tap the setting button
to enter the temperature and humidity setting interface and to set the temperature and humidity.
Home
1 Tap this button to enter the home page and view the main data and status of the system
button
Menu
2 Tap this button to display the main menu page, through which you can access each submenu
button
Settings
3 Tap this button to enter the temperature and humidity setting page, where you can set system temperature and humidity
button
Curve Tap this button to enter the curve interface, where you can view the 0-48 hour curve of return air average temperature, remote
4
button average temperature, supply air average temperature, and supply air average humidity
Time
5 Displays the current time
display
Unit
6 Displays the unit address
address
Monitor
7 Displays the monitor address
address
On and When the host is in the shutdown state, tap this button for at least two seconds and the host will power on. When the host is in the running
8
off button state, tap this button for at least two seconds and the host will shut down
Tap this button to enter the password-input interface and then to enter the unlocked interface. After that, you can tap the menu icon
Unlock and set parameters
9
button
Tap this button again to enter the unlocked interface
Operating
10 Displays the operating status of the current unit (shutdown, operation, standby, locking, and communication interruption)
status
Toggle
11 Tap this button to switch between graphical display mode and list display mode
button 1
Toggle
12 Tap this button to switch between alarm data and sensor data
button 2
Control
13 Displays the setpoint of the unit and the environmental conditions of the equipment
mode
Status
14 Displays the running status of the current component
display
Alarm
15 Displays the current alarm and the time when it occurs
data
Sensor
* Displays the sensor data of the current component
data
1 The circle can be displayed in three colors: green, gray, and red
2 Measured supply air temperature value. It changes with the compressor's current control mode
Humidity setpoint. It changes in clockwise direction between the 30-150 angle in the polar coordinate. When the humidity setpoint is the minimum
3
value, it is at 30 degrees in the polar coordinate; when the humidity setpoint is the maximum value, it is at 150 degrees in the polar coordinate
Temperature setpoint. According to the range of temperature setpoint, it changes in counterclockwise direction between the 30-150 angle in the
polar coordinate. When the temperature setpoint is the maximum value, it is at 30 degrees in the polar coordinate; when the temperature setpoint is
5 the minimum value, it is at 150 degrees in the polar coordinate
Red The power-on status sensor data is not within the normal range or is an invalid value
Browse all menu information and set only temperature and humidity setpoints. Cannot set or
Level 1 Ordinary operators 1490
change other values
Maintenance
Level 2 - Browse all menu information and set all parameters except the display address
personnel
Manufacturer
Level 3 - -
technicians
If you enter the wrong password, you can only browse the homepage. Tap the ESC button to exit the password interface.
NOTE: If you do not type any password or enter the wrong password in the password interface, you can only view the
parameters and data of the unlocked interface, and you cannot view and change the menu parameters.
Home Displays operating status, operating data, alarm data, and sensor data
Operational Displays temperature and humidity information, External Static Pressure (ESP) information, switch status, power information,
information and teamwork information
Alarm message Displays system current alarms, historical alarms, and compressor driver alarms
Temperature
and humidity
settings Sets the temperature and humidity values
Sets alarm parameters, alarm properties, system settings, compressor settings, internal fan settings, ESP settings,
Parameter
communication settings, teamwork settings, time settings, display settings, parameter recovery, password settings, and data
settings
logging settings
Menu Temperature
Displays the return air temperature curve, return air humidity curve, supply air temperature curve, and remote temperature
and humidity
curve
curve
About Displays the controller hardware and software version number, and the software and hardware version number of the display
Settings Displays the temperature and humidity settings under the same menu
Curve Displays the temperature and humidity curve under the same menu
ESP Information
You can view the ESP parameters of the unit in real time (when the unit is equipped with a ESP sensor).
Switch Status
You can view the disconnection or closing status of switches such as high-voltage switches, remote shutdown switches, floor
overflow switches, and electrical heating fault switches.
Power Information
You can view three-phase voltage and frequency.
Teamwork Information
You can view the status of the teamwork message.
Current Alarm
You can view the current alarm status record and the specific alarm status information. The specific alarm status information
includes the serial number, start date time, end date time, and alarm content.
NOTE: The most recent alarm number is the smallest number. When multiple alarms occur, press the rightmost scroll
bar to scroll up or down the query.
NOTE: The current alarm record is automatically cleared when the system is powered down.
Historical Alarm
You can view the historical alarm information and the specific historical alarm information. The specific historical alarm
information includes the serial number, start date time, end date time, and alarm content.
NOTE: When multiple alarms occur, press the scroll bar on the right to scroll up or down to query.
NOTE: The alarm history can be saved up to 1000, and it is not cleared when the power is disconnected.
Temperature Setting
You can set values for return air temperature, remote temperature, supply air temperature , and temperature difference.
Humidity Setting
You can set the humidity value and ratio.
Alarm Setpoint
You can set parameters such as supply air high temperature, supply air low temperature, return air high temperature, return
air low temperature, and return air high humidity.
NOTE: It is not recommended to change the default values for alarm parameters. If necessary, operate under the
guidance of a trained professional.
Alarm Attribute
You can set enable or disable for the properties of the alarm such as the supply air high temperature alarm, supply air low
temperature alarm, return air high temperature alarm, and return air high humidity alarm.
System Setting
You can set the heating function, humidification function, and dehumidification function.
Compressor Setting
You can set the compressor control mode and the compressor proportional band.
ESP Setting
Figure 4.22 ESP Setting
Communication Setting
Figure 4.23 Communication Setting
Teamwork Setting
Figure 4.24 Teamwork Setting
Time Setting
Figure 4.25 Time Setting
Display Settings
Figure 4.26 Display Settings
Parameter Reset
Figure 4.27 Parameter Reset
Password Setting
Figure 4.28 Password Setting
5 Control Logic
The unit operation is fully automated, calculated and controlled by the microprocessor controller according to the user's
setpoint.
5.1 Cooling
5.1.1 Control Mode
The fan and compressor of CRV4 have different control modes according to application scenarios. A total of 11 combination
modes are available.
Supply air √ - -
Remote √ √ -
Return air √ √ √
Air pressure √ √ √
Temperature difference √ √ -
is a proportional requirement
5 Control Logic 67
Where:
is the temperature control output (with limit) at the time of the first sample.
After the unit is turned on and the fan is operating normally for 10s, the compressor is turned on according to demand.
The compressor performs a soft start at start-up, gradually ramps up to a preset speed, and completes the entire start-up
process, followed by dynamic output according to the current cooling demand.
When the unit has dehumidification needs, the compressor will increase the output on top of the current output.
When the compressor is turned off normally, it performs a soft shutdown, and it is turned off after gradually reducing to the
preset speed. The compressor will be turned off directly when a shutdown alarm is generated.
The start and stop of the compressor needs to meet the minimum operation and downtime.
68 5 Control Logic
When the unit is running alone, the fan shuts down if the compressor is locked or the unit is shut down.
When the unit is in group control, the fan is turned off when the standby unit or compressor is locked.
On the one hand, the suction pressure is not too high and exceeds the operating range of the compressor; on the other hand,
the suction pressure is not too low, and the heat exchanger is not frozen.
The electronic expansion valve has a MOP function that limits the evaporation pressure of the unit to below the preset value.
After entering the high temperature adjustment mode, the speed demand output of the fan and compressor uses the high
temperature demand of the supply air or the high temperature demand of the return air, whichever is greater, as the output.
The speed of the fan and compressor is linear between the rated speed and the maximum speed.
When the average humidity of the return air is invalid or the average humidity of the return air is ≥ 60%, the high
temperature adjustment is prohibited, and the return air humidity is effective, and the average humidity of the return air is ≤
50%.
The controller calculates the dew point temperature according to the return air temperature and humidity detection value,
calculates the theoretical supply air humidity from the dew point temperature and the supply air temperature set value, and
calculates the current supply air humidity from the dew point temperature and the current supply air temperature.
The panel shows the theoretical supply air humidity. The humidity demand is also calculated using the theoretical supply
air humidity.
5 Control Logic 69
If the compressor is in a shutdown state, the need for dehumidification cannot cause the compressor to start.
Every 24 hours, the dehumidification mode has a limited operating time, after which it can no longer enter the
dehumidification mode.
Dehumidification mode may trigger electric heating to turn on for temperature compensation.
If the temperature of the dehumidification mold is too low, the unit will automatically exit the dehumidification mode.
When the actual supply air humidity is already high, the unit will automatically exit the humidification mode.
70 5 Control Logic
5.3 Heating
5.3.1 Dehumidification Temperature Compensation
After the unit enters the dehumidification mode, the output of the compressor is additionally greater than the current
cooling demand, and if the temperature is too low (supply air or return air temperature, depending on the control mode), the
electric heating will be turned on for temperature compensation.
When the dehumidification mode ends or is aborted, the temperature compensation is stopped.
When the compressor runs at a low speed for a certain period of time (oil return cycle), the unit will enter the oil return
operation mode, the compressor rises to the preset oil return speed operation. After reaching the oil return running time, the
compressor exits the oil return operation mode.
The unit is also equipped with a high-water level switch. When a high water level alarm is detected, even if the water level
switch does not operate, the unit will also turn on the condensate pump.
Remote shutdown refers to the shutdown enable of the corresponding switch input.
Display board setting can set the panel shutdown and the monitoring shutdown to power-on.
In the presence of multiple shutdowns, the priority displayed is: remote shutdown→ panel shutdown→ monitoring
shutdown.
5 Control Logic 71
The power-on and -off state is saved when the unit is powered down.
Teamwork mode 0 0 2 2 -
Unit quantity 1 1 16 2 -
Polling cycle 0 0 8 2
Polly quantity 0 0 The smaller value of operating unit quantity and standby unit quantitiy 2 -
Unit address 1 0 15 2 -
NOTE: Group control mode: 0: standalone; 1: teamwork control of air conditioning unit; 2: RDU-A energy-saving
teamwork control.
NOTE: Polling period: 0: none; 1: Daily; 2: Monday; 3: Tuesday; 4: Wednesday; 5: Thursday; 6: Friday; 7: Saturday; 8:
Sunday. Set to 0 to disable the polling function.
Standby functions rotate on a daily basis (time can be set). Rotations are performed by an optional number. For example, in
the case of 4 units and 2 standby units, if the number of rotations is 1, the order of standby rotations is from 1-2 to 2-3 to 3-4.
If the number of rotations is 2, the alternate rotation sequence is 1-2 to 3-4.
If a certain operating unit in the group cannot be contacted or after the compressor locks or the high temperature alarm or
temperature sensor fails, a standby unit will be started, and all standby units will be started.
72 5 Control Logic
The maximum
temperature of the return
The maximum temperature of the
Return air high air is invalid or lower than
return air is effective and higher than Allow/Abort/Close
6 temperature The alarm is triggered the alarm value minus the
the alarm value, reaching the alarm (default: Allow)
alarm return difference, reaching
detection delay time
the alarm detection delay
time
5 Control Logic 73
The maximum
temperature of the supply
The maximum supply air temperature
Supply air high air is invalid or lower than
is effective and higher than the alarm Allow/Abort/Close
9 temperature The alarm is triggered the alarm value minus the
value, reaching the alarm detection (default: Allow)
alarm return difference, reaching
delay time
the alarm detection delay
time
74 5 Control Logic
Exhaust high
3 times exhaust high temperature The alarm is triggered and The unit is powered on and Allow/Abort
18 temperature
alarm within 24 hours thecompressor is locked reset (default: Allow)
lock alarm
Low exhaust
Three exhaust low temperature alarms The alarm is triggered and The unit is powered on and Allow/Abort
19 superheat lock
occur within 1 hour thecompressor is locked reset (default: Allow)
alarm
5 Control Logic 75
High-pressure The high pressure exceeds the The alarm is triggered and MBV The high pressure reaches
Allow/Abort
30 pressure sensor detectable range, reaching the alarm opening is 100%, limiting access to the alarm detection delay
(default: Allow)
failure detection delay time the high-voltage restriction area time in the detection range
Compressor
The unit is powerd on or the
drive The compressor drive communication The alarm is triggered, and the Allow/Abort
34 alarm is cleared on the
communication failure lasts for 2 hours compressor locks and shuts down (default: Allow)
panel
fault lockout
The communication reads that the The alarm is triggered, the Any of the following is met:
CP overcurrent Allow/Abort
37 compressor overcurrent fault reaches compressor shuts down, and EEV is • Compressor contactor is (default: Allow)
reminder
the alarm detection delay time turned on to CP overcurrent opening disconnected
76 5 Control Logic
• The compressor
communication failure is
detected
• The compressor
overcurrent fault is cleared
5 Control Logic 77
• Compressor contactor is
disconnected
CP driver • The compressor
The communication reads that the AC
protection U11 The alarm is triggered and the communication failure is Allow/Abort
46 input undervoltage fault reaches the
(AC input compressor shuts down immediately detected (default: Allow)
alarm detection delay time
undervoltage)
• The compressor AC
input undervoltage fault is
cleared
CP drive
Allow/Abort
47 protection U12 Reserverd Reserverd Reserverd
(default: Allow)
(NA)
78 5 Control Logic
Low pressure
The number of low-voltage sensor The alarm is triggered and the The unit is powerd on and Allow/Abort
55 sensor fault
failures in 1 hour reaches 3 times compressor is locked reset (default: Allow)
lockout
5 Control Logic 79
80 5 Control Logic
5 Control Logic 81
Teamwork
In teamwork control mode, the host The alarm is triggered and the host
control The secondary unit Allow/Abort
75 does not receive data from a secondary does not calculate the data of the
secondary unit receives the host data (default: Allow)
unit within 60 seconds secondary unit
lost
82 5 Control Logic
Theo Supply Hum, Current Supply Hum, Supply Temp Avg, Supply Temp1, Supply Temp2, Supply Temp3, Supply Hum1,
Temp/Hum Supply Hum2, Supply Hum3, Return Temp Avg, Return Temp1, Return Temp2, Return Temp3, Remote Temp Avg,
Information Remote Temp1, Remote Temp2, …, Remote Temp10, Remote Hum Avg, Remote Hum1, Remote Hum2, …, Remote
Hum10
High Pressure Switch, Remote Shutdown Switch, Water Underfloor Switch, Heater Fail Switch, Humidifier Fail Switch, Cond
Run
Water Level Switch, Cond WOF Switch, Filter Clogged Switch, Custom1 Switch, Custom2 Switch, Dual Power Switch, Comp
Information Switch Status
Output, Indoor Fan1 Output, Indoor Fan2 Output, Outdoor Fan Output, Heater Output, Humidifier Output, Cond Pump
Output, LLSV Output, MBV Output, Spray Output, General Alarm Output
Power Phase A Voltage, Phase B Voltage, Phase C Voltage, Power Frequency, Phase A Current, Phase B Current, Phase C
Information Current, Phase A Power, Phase B Power, Phase C Power, Total Power, Total Active Energy
Teamwork
#00 Unit Status, #01 Unit Status, #02 Unit Status, ..., #15 Unit Status
Information
Alarm Status
Temp/Hum Temp Setting Return Temp SP, Supply Temp SP, Remote Temp SP, Delta Temp SP
Setting Hum Setting Supply Hum SP, Hum Prop Band
83
Sup High Temp Alarm SP, Sup Low Temp Alarm SP, Rtn High Temp Alarm SP, Rtn Low Temp Alarm SP, Rtn High Hum
Alarm Setpoint Alarm SP, Rtn Low Hum Alarm SP, Rem High Temp Alarm SP, Rem Low Temp Alarm SP, Rem High Hum Alarm SP, Rem
Low Hum Alarm SP, Filter Maintenance Cycle, Wet Film Maintenance Cycle
Supply High Temp Alarm, Supply Low Temp Alarm, Return High Temp Alarm, Return Low Temp Alarm, Return High Hum
Alarm Attribute Alarm, Return Low Hum Alarm, Remote High Temp Alarm, Remote Low Temp Alarm, Remote High Hum Alarm, Remote
Low Hum Alarm
Compressor
Comp Control Mode, Comp Prop Band
Setting
Indoor Fan Indoor Fan Control Mode, Indoor Fan Prop Band, Indoor Fan Minimum Speed, Indoor Fan Standard Speed, Indoor Fan
Setting Maximum Speed
Humidifier
Humidifying Function, Humidifier Type, Wet Film First Fill Time, Wet Film Fill Time, Wet Film Fill Interval
Parameter Setting
Setting
ESP Setting ESP Setpoint
Communication
Monitor Protocol, Monitor Baudrate, Monitor Address
Setting
Teamwork Teamwork Mode, Units Quantity, Unit Address, Standby Quantity, Rotation Quantity, Rotate Daily,
Setting Rotation Cycle, Rotate At, Run Standby Delay, Manual Rotate
Parameter
Wet Film Maintenance Confirm, Filter Maintenance Confirm
Reset
Password
Level 1 Password, Level 2 Password, Deployment Startup Password, Deployment Required Password
Setting
Control
Software Model
Control
Software
Version
About
Display
Software Model
Display
Software
Version
84
Appendix B: Alarm
High Pressure Alarm Smoke Alarm Remote Hum Sensor7 Failure Power Undervoltage
Low Pressure Alarm Fire Alarm Remote Hum Sensor8 Failure Power Freq Offset
Discharge High Temp Alarm SPD Failure Remote Hum Sensor9 Failure Power Phase Reverse
Discharge Low SH Alarm Remote Shutdown Alarm Remote Hum Sensor10 Failure Unit Address Repeat
High Pressure Lock Water Underfloor Alarm Airflow Temp Sensor Failure Primary Unit Loss
Low Pressure Lock Custom1 Alarm High Pressure Sensor Failure Secondary Unit Loss
Discharge High Temp Lock Custom2 Alarm Dsch Temp Sensor Failure Filter Maintenance
Discharge Low SH Lock Supply Temp Sensor1 Failure ESP Sensor1 Failure Filter Clogged Alarm
HP Abnormal Alarm Supply Temp Sensor2 Failure ESP Sensor2 Failure Secondary Power Feed Supply
LP Sensor Lock Supply Temp Sensor3 Failure Comp Driver Comm Failure Outdoor Fan Comm Failure
Supply High Temp Alarm Supply Hum Sensor1 Failure Comp Driver Comm Lock Outdoor Fan System Alarm
Supply Low Temp Alarm Supply Hum Sensor2 Failure Comp Driver Protect U01 Spray Comm Failure
Remote High Temp Alarm Supply Hum Sensor3 Failure Comp Driver Protect U02 Spray High Pressure Failure
Remote Low Temp Alarm Return Temp Sensor1 Failure Comp Driver Protect U03 Spray High Pressure Failure Lock
Remote High Hum Alarm Return Temp Sensor2 Failure Comp Driver Protect U04 Spray Low Pressure Failure
Remote Low Hum Alarm Return Temp Sensor3 Failure Comp Driver Protect U05 Spray Antifreeze Maintenance
Return High Temp Alarm Return Hum Sensor1 Failure Comp Driver Protect U06 10DI2 Comm Failure
Return Low Temp Alarm Return Hum Sensor2 Failure Comp Driver Protect U07 Fan11 Failure
Return High Hum Alarm Return Hum Sensor3 Failure Comp Driver Protect U08 Fan12 Failure
Return Low Hum Alarm Remote Temp Sensor1 Failure Comp Driver Protect U09 ATS Comm Failure
Loss Of Airflow Alarm Remote Temp Sensor2 Failure Comp Driver Protect U10 Power Meter Comm Failure
10DI1 Comm Failure Remote Temp Sensor3 Failure Comp Driver Protect U11 Wet Film Maintenance
Fan1 Failure Remote Temp Sensor4 Failure Comp Driver Protect U12 EEV Driver Device Failure
Fan2 Failure Remote Temp Sensor5 Failure Comp Driver Protect U13 Low Refrigerant
Fan3 Failure Remote Temp Sensor6 Failure Comp Driver Protect U14
Fan4 Failure Remote Temp Sensor7 Failure Comp Driver Protect U15
Fan5 Failure Remote Temp Sensor8 Failure Comp Driver Protect U16
Fan7 Failure Remote Temp Sensor10 Failure EEV Driver Comm Failure
Fan8 Failure Remote Hum Sensor1 Failure EEV Driver Parameter Error
Fan9 Failure Remote Hum Sensor2 Failure Suction Temp Sensor Failure
85
Cond WOF Alarm Remote Hum Sensor5 Failure Power Phase Loss
86
Cabinet o o o o o o
Cooling fitting o o o o o o
Fan unit o o o o o o
Heating unit o o o o o o
Display screen x o o o o o
Heat exchanger o o o o o o
Copper pipe o o o o o o
Cable o o o o o o
o indicates that the content of the hazardous substances in all the average quality materials of the part is within the limits specified in SJ/T-11363 - 2006
x indicates the content of the hazardous substances in at least one of the average quality materials of the part exceeds the limits specified in SJ/T-11363 -
2006
Vertiv™ is committed to the design and manufacture of environment-friendly products. It will reduce and eventually eliminate toxic and hazardous
substances in the products through unremitting efforts in research. However, limited by the current technical level, the following parts still contain
hazardous substance due to the lack of reliable substitute or mature solution.
The reason that some of the above parts contain Lead or Plumbum (Pb) is as follows: diode medium and high temperature solders contain lead; resistor
glass uranium contains lead (exemption); electronic ceramics contain lead (exemption)
About Environmental Protection Use Period: The Environmental Protection Use Period of the product is marked on the product. Under normal working
conditions and normal use of products observing relevant safety precautions, the hazardous substances in the product will not seriously affect the
environment, personnel safety or property in the Environmental Protection Use Period starting from the manufacturing date
87
88
89
单电源配置
8
J01-7 BL QF4-3
7 N
6 QF4-1
L3
J01-5 GR QF5-1 QF3-3
5 L2
交流检测板 J01
4
J01-3
QF3-1 L1
TB1-N
BR
ACM02A2 3 汇流排/Connection bars
2
1
J01-1 BK N N N N N
TB6 L1 L2 L3 PE
N N
电控盒接地点
TB1-N
J03 J02
Y/G J03 J29 J02-1
1 1 BK
1 2 3 4 5 6 7 8 L1 L2 L3
加湿器空开 1 3 变压器空开 1 3 电加热空开 1 3 5 压缩机空开 1 3 5
风机空开 1 3
空调室外机
Humidifier Transformer Heat Compressor
2 4 Fan breaker 2 4 2 4 6 2 4 6 TB2 Outdoor
电控盒接地点 breaker 2 4
breaker breaker breaker TB2-70
QF4 70
QF5-4
QF3-4
QF4-2
QF4-4
QF5-2
QF3-2
QF2 QF1
QF2-2
QF2-4
QF1-2
QF1-4
QF1-6
QF5 QF3 TB2-71
71
变压器TC
BR BL BR BL BK BK BK BK BK BK BK BK BK BK BK BK BR
CAN-L 1 2 3 4 5 6 7 8 Transformer TC
KM1-153
KM1-161
L
KM1-21
KM2-1
KM2-3
4
KM1-21
KM2-21
KR1-A1
KR1-13
KR1-31
KR2-A1
KR2-13
KM1-1
KM1-3
KM1-5
KM2-A1
KM1-A1
KM1-1
KM1-3
KM1-5
KM2-1
KM2-3
KM2-5
RD1-1
RD2-1
RD3-1
RD4-1
RD5-1
KM1-A1
CAN CAN-H J30 J31-1 TB1-0V TB1-0V BK TC-6
KM2-A1
H 1 BK 0V 3
J31 J31-2 BK
BK 电加热接触器 压缩机接触器
2 TC-2 1 3 5 21 1 3 5 21 153 161 13 31 13 31 1 3 5 21 1 3 5 21
TB1-24V
24V
TB1-24V BK TC-5 Heat A1 Compressor A1 KR1
A1
KR2
A1
KM1
A1 A1
KM2
RD1 RD2 RD3 RD4 RD5
TC-1 BK A2 RD1 RD2 RD3 RD4 RD5
TB2-62 J20-CANL J13-1 BK
contactor A2 2 4 6 22 contactor A2 2 4 6 22 154 162 A2 14 32 A2 14 32 A2 2 4 6 22 2 4 6 22
62 2 1
KM1-A2
KM2-A2
KM1-A2
显示屏
KM2-A2
KR1-A2
KR1-14
KR1-32
KR2-A2
KR2-14
KM2 KM1
KM1-22
KM2-22
KM1-2
KM1-4
KM1-6
KM2-2
KM2-4
KM2-6
RD1-2
RD2-2
RD3-2
RD4-2
RD5-2
KM1-154
KM1-162
TB2-61 J20 J13 J13-2
KM1-22
J20-CANH
KM2-2
KM2-4
KM1-2
KM1-4
KM1-6
61 1 2 BK
GHMI TB1-24V
24V BK BR BR BL BL BK BK
J18-1 BK
PWR-+ TB1-0V 1
+ 0V
PWR-- 2
PWR - J18-D06 BK 过电压抑制器
PWR-GND J18 3
J18-D07 BK Overvoltage
4
J18-D08 BK TB1-94 HPS HPS TB1-95 BK suppressor
5 94 95
N
高压开关
High Pressure Switch Y/G Y/G
485+
485-
压缩机
驱动器 电控盒接地点 电控盒接地点
J65-L
J65-N
J65-L
J65-N
7 4 2 3 1
KA2
J65 L N J65 L N Compressor
EH1-L
EH2-L
R48-1000 R48-1000
transducer
CAN
CAN
8
L3
6 5 电源模块 电源模块 BR BR
L2
24VDC J69 DC+ DC- J70 J69 DC+ DC- J70
QS1-1
QS1-3
QS1-5
QS2-1
QS2-3
QS2-5
QS1-1
QS1-3
QS1-5
L1
电源模块
PE1
PE1
PE2
N1
N2
N1
J69-DC+
J70-DC-
J69-DC+
J70-DC-
回风温湿度传感器 N
BL BL U V W PE 1 3 5 1 3 5 1 3 5
J1 J34 系统空开1 N1 PE1 N2 PE2 系统空开2 系统空开1 N1 PE1
Temp.and Humi.J1 J34
Main switch 1 2 4 6 2 4 6 Main switch 2 Main switch 1 2 4 6
EH1-N
EH2-N
sensor 冷凝水泵
Condensate 屏蔽 QS1 QS2 QS1
pump
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
选配件
Optional 24V 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~
输入电源1 输入电源2 输入电源1
TB2 POWER SUPPLY 1 POWER SUPPLY 2 POWER SUPPLY 1
控制板
KM3-1
KM3-3
KM3-A1
TB2-B2 BK J14-B 48V 48V GND GND 10V(1) 10V(1) 48V 48V GND GND 10V(2) 10V(2)
B B2 1
加湿接触器
RDU-SIC1 A A2
TB2-A2
TB2-GND
BR J14-A
2
J14 ACM05U1 J12
1
J12-12V
J12-GND
BK
BR
TB1-12V
TB1-GND
12V
A1
1 3 5 21
Humidifier TB4 48V 48V GND GND 10V(1)10V(1) 48V 48V GND GND 10V(2) 10V(2) TB5
T1
T2
T3
GND GND 2 GND
12 12V
TB2-12V A1 TB1-A1 A2 2 4 6 22 contactor 屏蔽
TB1-B1
KM3-A2
B1 KM3
KM3-2
KM3-4
压缩机1
Compressor1
BK BR 3~
J15-1 BR
1
J15 J15-2 BK 前门板接地 机柜接地
2
TB1-12V
TB1-GND
Y/G
12V GND
J16-1 BK
1
J16 J16-2 BR
2
后门板接地 机柜接地
RT1 J19-1 BK
BK J25-1 1
1 J19-2 BR 高压告警/High pressure alarm
送风温度传感器1/Delivery air probe1 BK J25-2 2
2 J19-3 BK
RT2 BK J25-3 J25 3
3 J19-4 BR J1-1 J1-2 高水位告警/High water alarm
送风温度传感器2/Delivery air probe2 BK J25-4 4
4 J19 J19-5 BK
5 选配件
J19-6 BK ST1-C ST1-NC ST2-C ST2-NC 电加热故障告警/Heat alarm
6 Optional 排水阀HDV
J19-7 BK TB2-51 51 BR
0V
地板溢水开关/Water under floor switch 选配件
7 BK
J19-8 BR TB2-24 24 1 2 电流互感器
8 Optional BR BR
BR BK 2
RT3 J8-1 BK
BK 1 BK 1
J21-1
M10-2
M10-1
M11-3
M11-2
排气温度传感器/Exhaust air probe J8-2 J8 BK M11-1 注水阀HFV
M7-3
M7-2
BK 1 选配件
TC2-1
TC2-2
TB1-A1 J39-A
TC2-3
BR 1 2 1 2 1 2 3 1 2 3 4 5 6 7 1 2
A1 2
J28-1 BK TB1-24V 24V A E/B
1
M8-1
M8-2
M2-1
M2-2
M2-4
M2-5
M2-6
M5-1
M5-2
J28-2 BK KA1-A1 KA1-14 YE
2 加湿器
J28-3 BK TB2-75 75 A1 YE
3
J28-4 TB2-76 76 公共告警/Common alarm
4
J28-5
BR
BK TB1-24V 24V
A2
KA1-11
BK
BR
TB4 TB5
TB1-0V KA1-A2
J28 5
J28-6 BK TB2-63 63 Y1
6 XPE 选配件 BK
TB2-64 64 Y1 XPE
0: 加湿 加湿手动 NC
7 Optional COM BK
8 1: 手动排水 排水开关 BK 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2)
NO
液路电磁阀
TB1-0V
9 0V BK
Freon solenoid valve
10 BR
0V
BK
BK
BK
BK
BK
BK
R
R
Y1
TB1-0V Y1
BL
BL
BL
BL
BL
BL
0V
R
加湿电磁阀 风机1 风机2 风机3 风机4 风机5 风机6
Humidify solenoid valve
Fan1 Fan2 Fan3 Fan4 Fan5 Fan6
BR
BR
BR
BR
BR
BR
W
P
O
O
BR J38-1 GND
温度传感器
TH1 BK J38-2
1
2
J38 TB5 GND
B1 TB3 远程传感器1 远程传感器2 远程传感器3
A1
GND Remote sensor1 Remote sensor2 Remote sensor3
12V
R J43-1
1 电子膨胀阀控制器
GND
DI1
DI2
DI3
DI4
DI5
DI6
压力传感器 J43-2
2 J43 EEV controller
LPT BR J34-1 O
BK J43-3 1
3 J34-2 R 12V
2
Terminal block/端子排 J34 3
J34-3 YE 执行阀体 A
EEV A
TB1
GND
A1 10DI
J34-4 BK B1
J32 J33 4
TB1 TB2 TB3 5
J34-5 BR
1 2 1 2 3 4
6
J32-1
J32-2
J33-3
J33-4
0V 0V 0V 24V 24V 24V GND GND GND 12V 12V 12V 00 12 G10 10V A1 A1 A1 B1 B1 B1 94 95 N N N N N 51 24 37 38 70 71 75 76 A2 B2 12V GND 61 62 63 64
备注/Notes:
BR
BR
BK
BK
单电源配置
8
J01-7 BL QF4-3 N
7
6 QF4-1 L3
J01-5 GR QF5-1 QF3-3
5 L2
交流检测板 J01
4
J01-3
QF3-1 L1
TB1-N
BR
ACM02A2 3 汇流排/Connection bars
2
1
J01-1 BK N N N N N
TB6 L1 L2 L3 PE
N N
电控盒接地点
TB1-N
J03 J02
Y/G J03 J29 J02-1
1 1 BK
1 2 3 4 5 6 7 8 L1 L2 L3
加湿器空开 1 3 变压器空开 1 3 电加热空开 1 3 5 压缩机空开 1 3 5
风机空开 1 3
空调室外机
Humidifier Transformer Heat Compressor
2 4 Fan breaker 2 4 2 4 6 2 4 6 TB2 Outdoor
电控盒接地点 breaker 2 4
breaker breaker breaker TB2-70
QF4 70
QF5-4
QF3-4
QF4-2
QF4-4
QF5-2
QF3-2
QF2 QF1
QF2-2
QF2-4
QF1-2
QF1-4
QF1-6
QF5 QF3 TB2-71
71
变压器TC
BR BL BR BL BK BK BK BK BK BK BK BK BK BK BK BK BR
1 2 3 4 5 6 7 8 Transformer TC
KM1-153
KM1-161
KM1-21
KM2-1
KM2-3
4
KM1-21
KM2-21
KR1-A1
KR1-13
KR1-31
KR2-A1
KR2-13
KM1-1
KM1-3
KM1-5
KM2-A1
KM1-A1
KM1-1
KM1-3
KM1-5
KM2-1
KM2-3
KM2-5
RD1-1
RD2-1
RD3-1
RD4-1
RD5-1
KM1-A1
J30 J31-1 TB1-0V TB1-0V BK TC-6
KM2-A1
1 BK 0V 3
J31 J31-2 BK
BK 电加热接触器 压缩机接触器
2 TC-2 1 3 5 21 1 3 5 21 153 161 13 31 13 31 1 3 5 21 1 3 5 21
L
CAN-L TB1-24V
24V
TB1-24V BK TC-5 Heat A1 Compressor A1 KR1
A1
KR2
A1
KM1
A1 A1
KM2
RD1 RD2 RD3 RD4 RD5
TC-1 BK RD1 RD2 RD3 RD4 RD5
CAN CAN-H contactor A2 contactor A2 A2 14 32 A2 14 32 A2 2 4 6 22 2 4 6 22 A2
H J13-1 2 4 6 22 2 4 6 22 154 162
1 BK
KM1-A2
KM2-A2
KM1-A2
KM2-A2
KR1-A2
KR1-14
KR1-32
KR2-A2
KR2-14
KM2 KM1
KM1-22
KM2-22
KM1-2
KM1-4
KM1-6
KM2-2
KM2-4
KM2-6
RD1-2
RD2-2
RD3-2
RD4-2
RD5-2
KM1-154
KM1-162
J13 J13-2
KM1-22
KM2-2
KM2-4
KM1-2
KM1-4
KM1-6
2 BK
TB2-62 J20-CANL
62 2 BK BR BR BL BL BK BK
显示屏 61
TB2-61 J20-CANH
1
J20
1
J18-1 BK
2
GHMI TB1-24V
24V
J18 3
J18-D06 BK 过电压抑制器
TB1-0V J18-D07 BK Overvoltage
PWR-+ 0V 4
+ J18-D08 BK TB1-94 HPS HPS TB1-95 BK suppressor
PWR-- 5 94 95
PWR -
PWR-GND 高压开关
N
High Pressure Switch Y/G Y/G
485+
485-
压缩机
驱动器 电控盒接地点 电控盒接地点
J65-L
J65-N
J65-L
J65-N
7 4 2 3 1
KA2
J65 L N J65 L N Compressor
EH1-L
EH2-L
EH3-L
EH4-L
R48-1000 R48-1000
transducer
CAN
CAN
8
L3
6 5 电源模块 电源模块 BR BR BR BR
L2
24VDC J69 DC+ DC- J70 J69 DC+ DC- J70
QS1-1
QS1-3
QS1-5
QS1-1
QS1-3
QS1-5
QS2-1
QS2-3
QS2-5
L1
电源模块
PE1
PE1
PE2
N1
N1
N2
J69-DC+
J70-DC-
J69-DC+
J70-DC-
回风温湿度传感器 N
BL BL BL BL U V W PE 1 3 5 1 3 5 1 3 5
J1 J34 系统空开1 N1 PE1 N2 PE2 系统空开2 系统空开1 N1 PE1
Temp.and Humi.J1 J34
Main switch 1 2 4 6 2 4 6 Main switch 2 Main switch 1 2 4 6
EH1-N
EH2-N
EH3-N
EH4-N
sensor 冷凝水泵
Condensate 屏蔽 QS1 QS2 QS1
pump
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
选配件
Optional 24V 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~
输入电源1 输入电源2 输入电源1
TB2 POWER SUPPLY 1 POWER SUPPLY 2 POWER SUPPLY 1
控制板
KM3-1
KM3-3
KM3-A1
TB2-B2 BK J14-B 48V 48V GND GND 10V(1) 10V(1) 48V 48V GND GND 10V(2) 10V(2)
B B2 1
加湿接触器
RDU-SIC1 A A2
TB2-A2
TB2-GND
BR J14-A
2
J14 ACM05U2 J12
1
J12-12V
J12-GND
BK
BR
TB1-12V
TB1-GND
12V
A1
1 3 5 21
Humidifier TB4 48V 48V GND GND 10V(1)10V(1) 48V 48V GND GND 10V(2)10V(2) TB5
T1
T2
T3
GND GND 2 GND
12 12V
TB2-12V A1 TB1-A1 A2 2 4 6 22 contactor 屏蔽
TB1-B1
KM3-A2
B1 KM3
KM3-2
KM3-4
压缩机1
Compressor1
BK BR 3~
J15-1 BR
1
J15 J15-2 BK 前门板接地 机柜接地
2
TB1-12V
TB1-GND
Y/G
12V GND
J16-1 BK
1
J16 J16-2 BR
2
后门板接地 机柜接地
RT1 J19-1 BK
BK J25-1 1
1 J19-2 BR 高压告警/High pressure alarm
送风温度传感器1/Delivery air probe1 BK J25-2 2
2 J19-3 BK
RT2 BK J25-3 J25 3
3 J19-4 BR J1-1 J1-2 高水位告警/High water alarm
送风温度传感器2/Delivery air probe2 BK J25-4 4
4 J19 J19-5 BK
5 选配件
J19-6 BK ST1-C ST1-NC ST2-C ST2-NC ST3-C ST3-NC ST4-C ST4-NC 电加热故障告警/Heat alarm
6 Optional 排水阀HDV
J19-7 BK TB2-51 51 BR
7 选配件 0V BK
J19-8 BR TB2-24 24 1 2 地板溢水开关/Water under floor switch 电流互感器
8 Optional BR BR
BR BK 2
RT3 J8-1 BK
BK 1 BK 1
J21-1
M10-2
M10-1
M11-3
M11-2
M11-1
M7-3
M7-2
BK 1 选配件
TC2-1
TC2-2
1 2 1 2 1 2 3 1 2 3 4 5 6 7 1 2
TB1-B1 BK J39-B J28-1 BK TB1-24V 24V
B1 1 1 A E/B
M8-1
M8-2
M2-1
M2-2
M2-4
M2-5
M2-6
M5-1
M5-2
J28 5
J28-6 BK TB2-63 63 Y1
6 XPE 选配件 BK
TB2-64 64 Y1 XPE
0: 加湿 加湿手动 NC
7 Optional COM BK
8 1: 手动排水 排水开关 BK
NO
液路电磁阀
TB1-0V
9 BK
10
Freon solenoid valve 0V
BR TB4 TB5
0V
48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2)
Y1
TB1-0V Y1
0V
加湿电磁阀
Humidify solenoid valve
BK
BK
BK
BK
BK
BK
BK
BK
R
R
BL
BL
BL
BL
BL
BL
BL
BL
R
R
风机1 风机2 风机3 风机4 风机5 风机6 风机7 风机8
Fan1 Fan2 Fan3 Fan4 Fan5 Fan6 Fan7 Fan8
BR J38-1
温度传感器 1
TH1 BK J38-2 J38
BR
BR
BR
BR
BR
BR
BR
BR
2
W
P
B1 TB3 远程传感器1 远程传感器2 远程传感器3
A1
Remote sensor1 Remote sensor2 Remote sensor3
O
O
GND
GND
12V
R J43-1 电子膨胀阀控制器
TB5 GND
1
压力传感器 J43-2
2 J43 EEV controller
LPT BR J34-1 O
BK J43-3 1
3 J34-2 R
2
Terminal block/端子排 J34 3
J34-3 YE 执行阀体 A
EEV A
J34-4 BK
GND
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
J32 J33 4
TB1 TB2 TB3 5
J34-5 BR
1 2 1 2 3 4 12V
6 TB1
GND
10DI
J32-1
J32-2
J33-3
J33-4
A1
0V 0V 0V 24V 24V 24V GND GND GND 12V 12V 12V 00 12 G10 10V A1 A1 A1 B1 B1 B1 94 95 N N N N N 51 24 37 38 70 71 75 76 A2 B2 12V GND 61 62 63 64 B1
备注/Notes:
BR
BR
BK
BK
单电源配置
8
J01-7 BL QF4-3 N
7
6 QF4-1 L3
J01-5 GR QF5-1 QF3-3 L2
5
交流检测板 J01
4
J01-3
QF3-1 L1
TB1-N
BR
ACM02A2 3
2
1
J01-1 BK N N N N N
TB6 L1 L2 L3 PE
N N
电控盒接地点
TB1-N
J03 J02
Y/G J03 J29 J02-1
1 1 BK
1 2 3 4 5 6 7 8 L1 L2 L3
HUMIDIFIER 1 3 TRANSFORMER 1 3 HEAT 1 3 5 COMPRESSOR 1 3 5
FAN BREAKER 1 3
空调室外机
BREAKER BREAKER BREAKER BREAKER
2 4 QF4 2 4 2 4 6 2 4 6 TB2 Outdoor
电控盒接地点 QF5 2 4 QF3 QF2 QF1 TB2-70
70
QF5-4
QF3-4
QF4-2
QF4-4
QF5-2
QF3-2
QF2-2
QF2-4
QF1-2
QF1-4
QF1-6
TB2-71
71
TRANSFORMER TC BR BL BR BL BK BK BK BK BK BK BK BK BK BK BK BK BR
1 2 3 4 5 6 7 8
KM1-153
KM1-161
KM2-A1
KM1-21
KM1-A1
KM2-1
KM2-3
4
KMA-21
KMB-21
KAC-A1
KAC-13
KAC-31
KAD-A1
KAD-13
KM1-1
KM1-3
KM1-5
L CAN-L
KMA-1
KMA-3
KMA-5
KMB-1
KMB-3
KMB-5
RD1-1
RD2-1
RD3-1
RD4-1
RD5-1
KMA-A1
J30 J31-1 TB1-0V TB1-0V BK TC-6
KMB-A1
BK
1 0V 3 BK HEAT COMPRESSOR
H CAN-H
CAN J31 J31-2 BK
2 TC-2 1 3 5 21 1 3 5 21 153 161 13 31 13 31 1 3 5 21 1 3 5 21
TB1-24V
24V
TB1-24V BK TC-5 CONTACTOR A1 CONTACTOR A1
KAC
A1
KAD
A1
KMA
A1 A1
KMB
RD1 RD2 RD3 RD4 RD5
TC-1 BK
J13-1
KM2 A2 2 4 6 22 KM1 A2 2 4 6 22 154 162 A2 14 32 A2 14 32 A2 2 4 6 22 2 4 6 22 A2 RD1 RD2 RD3 RD4 RD5
BK
GHMI 1
KMA-A2
KMB-A2
KAC-A2
KAC-14
KAC-32
KAD-A2
KAD-14
KMA-22
KMB-22
KMA-2
KMA-4
KMA-6
KMB-2
KMB-4
KMB-6
RD1-2
RD2-2
RD3-2
RD4-2
RD5-2
KM1-154
KM1-162
KM2-A2
62 TB2-62 BR J20-CANL 2 J13 J13-2
KM1-A2
KM1-22
KM2-2
KM2-4
BK
KM1-2
KM1-4
KM1-6
2
61 TB2-61 BK J20-CANH 1 J20
DISPLAY BK BR BR BL BL BK BK BK BK BK
J18-1 BK
1
+ PWR-+ TB1-24V 24V 2
J18-D06 BK
PWR -
PWR-- TB1-0V 0V J18 3 OVERVOLTAGE
J18-D07 BK
PWR-GND 4 SUPPRESSOR
J18-D08 BK TB1-94 HPS HPS TB1-95 BK
5 94 95
HIGH PRESSURE SWITCH
N Y/G
Y/G
BK 24V
电控盒接地点
J65-L
J65-N
J65-L
J65-N
PE 电控盒接地点
KM3-A1
KM3-1
KM3-3
7 4 2 3 1 J65 L N J65 L N
KA2 L1 L2 L3
EH1-L
EH2-L
EH3-L
EH4-L
8 A1
1 3 5 21 HUMIDIFIER R48-1000 R48-1000
CAN
CAN
6 5
A2 2 4 6 22
CONTACTOR POWER SUPPLY POWER SUPPLY
BR BR BR BR COMPRESSOR
KM3
QS1-1
QS1-3
QS1-5
BK BR BL J69 DC+ DC- J70 J69 DC+ DC- J70
INVERTER
QS1-1
QS1-3
QS1-5
QS2-1
QS2-3
QS2-5
PE1
KM3-A2
N1
KM3-2
KM3-4
PE1
PE2
N1
N2
RETURN AIR A1 TB1-A1
J69-DC+
J70-DC-
J69-DC+
J70-DC-
J1 J34 N 485+ 1 3 5
J16
J1 B1 TB1-B1
J34 1 3 5 1 3 5
24VDC BL BL BL BL 485-
系统空开1 系统空开2 系统空开1 N1 PE1
T&TH SENSOR ADAPTER
Main switch 1 2 4 6
N1 PE1
2 4 6
N2 PE2
Main switch 2 Main switch 1 2 4 6
EH1-N
EH2-N
EH3-N
EH4-N
U V W PE
QS1 QS2 QS1
CONDENSATE L1 L2 L3 N PE
L1 L2 L3 N PE L1 L2 L3 N PE
PUMP BK R BL Y/G 屏蔽
380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60HZ 3N~
OPTIONAL
输入电源1 输入电源2 输入电源1
10V(1) 10V(1) 48V 48V GND GND 10V(2)10V(2) 48V 48V GND GND POWER SUPPLY 1
控制板 TB4 10V(1) 10V(1) 48V 48V GND GND 10V(2)10V(2) 48V 48V GND GND
TB5 PE POWER SUPPLY 1 POWER SUPPLY 2
TB2
L1
L2
L3
PE
B B2 TB2-B2 BK J14-B 1 ACM05U2 J12
1
J12-12V
J12-GND
BK TB1-12V
TB1-GND
12V
J14-A 2 J14 BR
A A2 TB2-A2 BR 2 GND
屏蔽
RDU-SIC COMPRESSOR
ZPV096
12V 12V TB2-12V
GND TB2-GND
J15-1 BR
GND 1
J15 J15-2 BK 前门板接地 机柜接地
BR BK 2
TB1-GND
TB1-12V
Y/G
J16-1 BK
1
GND 12V J16 J16-2 BR
2
后门板接地 机柜接地
J19-1 BK
1
J19-2 BR 高压告警/High pressure alarm
2
J19-3 BK
3
J19-4 BR J1-1 J1-2 高水位告警/High water alarm
4
J19 J19-5 BK
5 选配件
B1 TB2-B1 BK J22-B 1 6
J19-6
J19-7
BK
BK
ST1-C
TB2-51 51
ST1-NC ST2-C ST2-NC ST3-C ST3-NC ST4-C ST4-NC 电加热故障告警/Heat alarm
Optional
BR 排水阀HDV TB4 TB5
OPTIONAL TB2-A1 BR J22-A 2 J22 7 选配件 0V BK
A1 J19-8 BR TB2-24 24 1 2 地板溢水开关/Water under floor switch 电流互感器
8 Optional BR BR
BR BK 2 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2)
BK
BK 1
J21-1
M10-2
M10-1
M11-3
M11-2
M11-1
BK 注水阀HFV
M7-3
M7-2
1 选配件
TC2-1
TC2-2
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
2 1
R
J21 J21-5 BK
SAS2 BK J25-3 J25 5 选配件
3 J21-6 BR 3 2 浮球开关/FLOAT LEVER SWITCH CPY加湿控制器 M9-2 BK
SUPPLY AIR SENSOR 2 BK J25-4 6 Optional 2
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
4 J21-7 BK TB2-37 37 M9 M9-1 BK
R
7 1 CS LS
J21-8 BR TB2-38 38 1 2 远程开关机/Remote swith 电源 手操器 TLAN通迅 485通迅 外部控制端子
8 M8 J1 M12 M1 M2 M5 风机1 风机2 风机3 风机4 风机5 风机6 风机7 风机8 风机9 风机10
TC2-4
TC2-3
1 2 1 2 1 2 3 1 2 3 4 5 6 7 1 2
J28-1 BK TB1-24V 24V
Fan1 Fan2 Fan3 Fan4 Fan5 Fan6 Fan7 Fan8 Fan9 Fan10
A E/B
1
M8-1
M8-2
M2-1
M2-2
M2-4
M2-5
M2-6
M5-1
M5-2
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BK TB2-75 75 A1 YE
P
DISCHARGE TEMPERATURE SENSOR BK J8-2 J8 3
COMMON ALARM
2 J28-4 BR TB2-76 76 BK
4 A2
J28-5 BK TB1-24V 24V KA1-11 BR
TB1-0V KA1-A2
O
J28 5
J28-6 BK TB2-63 63 Y1 GND
6
7 TB2-64 64 Y1
XPE XPE 选配件
Optional 0: 加湿 加湿手动 NC COM
BK
BK TB5 GND
8 1: 手动排水 排水开关 BK
NO
TB1-0V
DI10
GND
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
HUMIDITY SOLENOID VALVE
TB3
J38 REMOTE TEMP
J38 10DI SENSOR *
A1 B1
J34-1 O
TB1-B1
TB1-A1
1 1
J34-2 R
2 2
J39-A BR J33-3 3 J33 3
J34-3 YE
2 J34 J34-4 BK
J39 BK J33-4 4 EEV A
1 J39-B 4
J34-5 BR
5
6
6
BK
BR
0V 0V 0V 24V 24V 24V GND GND GND 12V 12V 12V 00 12 G10 10V A1 A1 A1 B1 B1 B1 94 95 N N N N N 51 24 37 38 70 71 75 76 A2 B2 12V GND 61 62 63 64
备注/Notes:
TB1-24V
TB1-0V
8
J01-7 BL N
7
6 L3
交流检测板 5
J01-5 GR
L2
J01
ACM02A2 4
3
J01-3 BR
L1
2 TB6 L1 L2 L3 PE
J01-1 BK N
1 N N N N
PE
J03 J29 J02
Y/G J03 J02-1 BK L1 L2 L3
1 1 2 3 4 5 6 7 8 1 变压器空开 风机空开 电加热空开 压缩机空开
1 3 1 3 HEATER 1 3 5 COMPRESSOR 1 3 5 室外机空调
TRANSFORMER FAN
BREAKER 2 4 2 4 BREAKER 2 4 6 BREAKER 2 4 6 TB2 OUTDOOR
PE
BREAKER
QF2 QF1 TB2-70
QF4-2
QF4-4
QF3
QF3-4
QF3-2
QF4 70
QF2-2
QF2-4
QF1-2
QF1-4
QF1-6
TB2-71
6A 16A 10A 25A 71
变压器TC
TRANSFORMER TC BK BK BK BK BK BK BK BK
BK BK BR BL
KAC-A1
KAC-13
KAC-31
KMA-A1
KMA-01
KMB-01
KMB-A1
KAD-A1
KAD-13
1 2 3 4 5 6 7 8 100VA
KM2-A1
RD1-2
RD2-2
RD3-2
RD4-2
RD5-2
KMA-1
KMA-3
KMA-5
KMA-7
KMB-1
KMB-3
KMB-5
KMB-7
KM1-A1
KM1-21
KM1-153
KM1-161
KM2-1
KM2-3
KM1-1
KM1-3
KM1-5
J30 J31-1 BK TB1-0V 0V TB1-0V BK TC-6
4 电加热接触器 压缩机接触器
3
J31 1 J31-2 BK BK HEATER COMPRESSOR
2 TC-2 1 3 5 21 1 3 5 21 153 161 A1 13 31 A1 13 31 A1 1 3 5 7 01 1 3 5 7 01 A1 RD1 RD2 RD3 RD4 RD5
TB1-24V 24V TB1-24V BK TC-5
TC-1 BK CONTACTOR A1 CONTACTOR A1 KAC KAD KMA KMB
A2 14 32 A2 14 32 A2 2 4 6 8 02 2 4 6 8 02 A2 RD1 RD2 RD3 RD4 RD5
J13-1 BK KM2 A2 2 4 6 22 KM1 A2 2 4 6 22 154 162
J13 1 J13-2
KAC-A2
KAC-14
KAC-32
KAD-A2
KAD-14
KMA-A2
KMA-02
KMB-02
KMB-A2
KM1-154
KM1-162
RD1-1
RD2-1
RD3-1
RD4-1
RD5-1
9A 25A
KMA-2
KMA-4
KMA-6
KMA-8
KMB-2
KMB-4
KMB-6
KMB-8
KM2-A2
BK
KM1-A2
KM1-22
KM2-2
KM2-4
KM1-2
KM1-4
KM1-6
2
CAN-L
L J18-1 BK BK BR BR BL BK BK BK BK BK
CAN CAN-H 1
H
2
J18 3 J18-D06 BK 过电压抑制器
显示屏 OVERVOLTAGE
TB2-62 BR J20-CANL 4 J18-D07 BK
SUPPRESSOR
GHMI 62
61
TB2-61 BK J20-CANH
2
1 J20
5 J18-D08 BK TB1-94 94 HPS HPS 95 TB1-95 BK
高压开关
DISPLAY HIGH PRESSURE SWITCH N Y/G Y/G
PWR-+ TB1-24V 24V BK
+
PWR-- TB1-0V PE
PWR - 0V PE
PWR-GND 4 2 3 1
7 L1 L2 L3
KA1
J1-L
J1-N
8
EH1-L
EH2-L
PE 6 5
压缩机驱动
BK BR BL J16 COMPRESSOR
QS1-1
QS1-3
QS1-5
QS1-7
QS2-1
QS2-3
QS2-5
QS2-7
J1 L N
QS1-1
QS1-3
QS1-5
QS1-7
BR BR TB1-A1
A1 485+
PE
N
PE
R48-2000E3 485- INVERTER
PE
TB1-B1
24VDC B1 主空开1 主空开2
主空开 1 3 5 7 1 3 5 7
J12-V12 BK TB1-12V 12V
电源模块 电源模块 MAIN BREAK
1 3 5 7
MAIN BREAK 1 PE PE MAIN BREAK 2
J12 1 J12-GND BR U V W PE PE
TB1-GND GND J21 DC+ DC- J11 BL BL 2 4 6 8 QS1 2 4 6 8 2 4 6 8 QS2
2 QS1
冷凝水泵
BK R BL Y/G 屏蔽 40A 40A 40A
EH1-N
EH2-N
CONDENSATE
PUMP
J21-DC+
J11-DC-
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
回风温湿度传感器 选配件
输入电源1 输入电源2
OPTIONAL 输入电源
RETURN AIR J1
J1 J34
J34
控制板 PE
POWER POWER 1 POWER 2
T1
T2
T3
PE
T&TH SENSOR ACM05U15
压缩机 屏蔽
COMPRESSOR
ZPV050
1
J19-1 BK
J19-2 BR 高压告警/HIGH PRESSURE ALARM
2
3
J19-3 BK
J19-4 BR J1-1 J1-2 高水位告警/HIGH WATER ALARM
4
J19 J19-5 BK
5
TB2 6 J19-6 BK ST1-C ST1-NC ST2-C ST2-NC 电加热告警/HEAT ALARM
TB2-51 51
B B2 TB2-B2 BK J14-B 1 7
J19-7 BK
J1-1 J1-2
J14 J19-8 BR TB2-24 24 地板溢水开关/WATER UNDER FLOOR SWITCH OPTIONAL
A A2 TB2-A2 BR J14-A 2 8
RDU-SIC
J16-1 BK
12V 12V TB2-12V J16 1 J16-2
GND GND TB2-GND 2 BR
OPTIONAL BR BK
TB-48V
TB-GND
FAN1-PWM TB-10V
TB-48V
TB-GND
Y PWM FAN2-PWM TB-10V
TB-48V
TB-GND
Y PWM FAN3-PWM TB-10V
TB-48V
TB-GND
Y PWM FAN4-PWM TB-10V
TB-48V
TB-GND
Y PWM FAN5-PWM TB-10V
TB-48V
TB-GND
Y PWM FAN6-PWM TB-10V
TB-48V
TB-GND
Y PWM FAN7-PWM TB-10V
TB1-GND
TB1-12V
J21-1 BK
1
J21-2 BR C NO 滤网压差开关/FILTER CLOGGED SWITCH OPTIONAL
FAN1-L
FAN1-N
FAN2-L
FAN2-N
FAN3-L
FAN3-N
FAN4-L
FAN4-N
FAN5-L
FAN5-N
FAN6-L
FAN6-N
FAN7-L
FAN7-N
GND 12V 2
3
4
J21 J21-5 BK
FAN1-FG
FAN2-FG
FAN3-FG
FAN4-FG
FAN5-FG
FAN6-FG
FAN7-FG
BL FG
BL FG
BL FG
BL FG
BL FG
BL FG
5
+
BL -
+
BK -
+
BK -
+
BK -
+
BK -
+
BK -
+
BK -
J1-1 J1-2 OPTIONAL
P C
W T
J21-6 BR 浮球开关/FLOAT LEVER SWITCH
TB2-B1 BK J22-B 1 6
R
B1 J21-7 BK TB2-37 37
A1 TB2-A1 BR J22-A 2 J22 7
J21-8 BR TB2-38 38 远程开关机/REMOTE SHUTDOWN DEVICE
8
FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 FAN7
SAS1 BK J25-1 1
J28-1 BK TB1-24V 24V Y/G Y/G Y/G Y/G Y/G Y/G Y/G
送风温度传感器1 1
BK J25-2 J28-2 BK Y1-1 加湿电磁阀
SUPPLY AIR SENSOR 1 2 2
SAS2 BK J25-3 3
J25 3
J28-3 BK TB2-75 75 公共告警 0V TB1-0V Y1-2 HUMIDIFY SOLENOID VALVE GND GND GND GND GND GND GND
送风温度传感器2 J28-4 BR TB2-76 76
SUPPLY AIR SENSOR 2 BK J25-4 4 4 COMMON ALARM
J28 5 J28-5 BK TB1-24V 24V
J28-6 BK TB2-63 63 Y1 液路电磁阀
6
TB2-64 64 Y1 XPE OPTIONAL
DI1
DI2
DI3
DI4
DI5
DI6
DI7
7 FREON SOLENOID VALVE
8
TB1-0V
DTS 9
排气温度传感器 BK J8-1 1 10
DISCHARGE TEMPERATURE SENSOR BK J8-2 J8
2 0V
D1 D2 D3 D4 D5 D6 D7 D8 TB3 远程温度传感器
J38 10DI-J1 10DI-J2
J38 REMOTE TEMP
HP-5V R J23-1 1 10DI CARD SENSOR *
高压传感器 HP-VIN BR J23-2 2 J23
HIGH PRESSURE TRANSDUCER HP-GND BK J23-3 3
A1 B1
J34-1 O
TB1-B1
TB1-A1
1 1
J34-2 R
2 2
BK BR J33-3 3 J33 J34-3 YE
2 J39-A J34
3
J34-4 BK
执行阀体A
J39
1 J39-B BR BK J33-4 4 4
J34-5 BR
EEV A
5
6
吸气温度传感器
STS
BR
BK
J38-1 1
J38-2 2 J38
电子膨胀阀控制器
SUCTION TEMPERATURE SENSOR
STS EEV CONTROLLER
TERMINAL BLOCK/端子排 J32
LP-5V R J43-1 1
TB1 低压传感器 LPT LP-GND BR J43-2 2
J43
1 2
LOW PRESSURE TRANSDUCER LP-VIN BK J43-3 3
TB2 TB3
J32-1
J32-2
备注/Notes: 24V 0V
Factory supplied line voltage wiring/出厂线电压线路
配线色标/Wire color code:
Ethernet or CAN wiring/以太网或CAN线路
Factory supplied 24 volt wiring/出厂24V线路 BK-Black/黑色
BL-Blue/蓝色
Device own line/器件自带线
BR-Brown/棕色
Inline quick disconnect/线上快速对插端子
WH-White/白色
Terminal block connector/线缆端子 Y/GN-Yellow green/黄绿色
Naked crimping connector/裸压端子 O-Orange/橙色
P-Purple/紫色
R-Red/红色
YE-Yellow/黄色
GR-Grey/灰色
8
7 J01-7 BL N
6 L3
交流检测板 5 J01-5 GR L2
J01
ACM02A2 4
J01-3 BR
L1
TB1-N
TB1-N
TB1-N
TB1-N
TB1-N
TB1-N
3
2 TB6 L1 L2 L3 PE
1 J01-1 BK N N N N N N
PE
J03 J29 J02
Y/G J03 1 1
J02-1 BK
1 2 3 4 5 6 7 8 L1 L2 L3
变压器空开 1 3 风机空开 1 3 电加热空开 1 3 5 压缩机空开 1 3 5 室外机空调
TRANSFORMER FAN HEATER COMPRESSOR OUTDOOR
2 4 BREAKER 2 4 6 BREAKER 2 4 6 TB2
PE BREAKER BREAKER 2 4 TB2-70
70
QF2 QF1
QF3-4
QF4-2
QF4-4
QF3-2
QF3
QF2-2
QF2-4
QF1-2
QF1-4
QF1-6
QF4 TB2-71
71
6A 25A 20A 32A
变压器TC
TRANSFORMER TC BK BK BK BK BK BK BK BK
100VA BK BK BR BL
KAC-A1
KAC-13
KAC-31
KMA-A1
KMA-01
KMB-01
KMB-A1
1 2 3 4 5 6 7 8
KAD-A1
KAD-13
KM1-161
RD1-2
RD2-2
RD3-2
RD4-2
RD5-2
KMA-1
KMA-3
KMA-5
KMA-7
KMB-1
KMB-3
KMB-5
KMB-7
KM1-21
KM1-153
KM2-1
KM2-3
KM2-A1
KM1-A1
KM1-1
KM1-3
KM1-5
TB1-0V TB1-0V BK TC-6 4
J30
1 J31-1 BK 0V 3 BK
电加热接触器 压缩机接触器
J31
L CAN-L 2 J31-2 BK
TB1-24V 24V TB1-24V BK TC-5 TC-2 HEATER 1 3 5 21 COMPRESSOR
A1
1 3 5 21 153 161 A1 13 31 A1 13 31 A1 1 3 5 7 01 1 3 5 7 01 A1 RD1 RD2 RD3 RD4 RD5
H CAN-H
CAN A1 KAC KAD KMA KMB
TC-1 BK CONTACTOR CONTACTOR A2 14 32 A2 14 32 A2 2 4 6 8 02 2 4 6 8 02 A2 RD1 RD2 RD3 RD4 RD5
A2 2 4 6 22 A2 2 4 6 22 154 162
1 J13-1 BK KM2 KM1
KAC-A2
KAC-14
KAC-32
KAD-A2
KAD-14
KMA-A2
KMA-02
KMB-02
KMB-A2
KM1-154
KM2-A2
RD1-1
RD2-1
RD3-1
RD4-1
RD5-1
KM1-162
KMA-2
KMA-4
KMA-6
KMA-8
KMB-2
KMB-4
KMB-6
KMB-8
J13
KM1-A2
2 J13-2 BK
KM1-22
KM2-2
KM2-4
显示屏 9A 32A
KM1-2
KM1-4
KM1-6
62 TB2-62 BR J20-CANL 2
TB2-61 BK J20-CANH 1 J20
GHMI 61
1 J18-1 BK BK BR BR BL BL BK BK BK BK BK
DISPLAY 2
过电压抑制器
+ PWR-+ TB1-24V 24V J18 3 J18-D06 BK
OVERVOLTAGE
PWR -
PWR-- TB1-0V 0V 4 J18-D07 BK
TB1-94 94 HPS HPS SUPPRESSOR
PWR-GND 5 J18-D08 BK 95 TB1-95 BK
高压开关
N
HIGH PRESSURE SWITCH Y/G Y/G
BK
PE PE
J1-1L
J1-1N
J1-2L
J1-2N
PE
7 4 2 3 1 L1 L2 L3
EH1-L
EH2-L
EH3-L
EH4-L
KA1 J41 J41
CAN
CAN
8 J1 L N L N J1
6 5 BR BR BR BR 压缩机驱动
R48-2000E3 R48-2000E3 J16
QS1-1
QS1-3
QS1-5
QS1-7
QS2-1
QS2-3
QS2-5
QS2-7
QS1-1
QS1-3
QS1-5
QS1-7
BK BR BL
电源模块 电源模块 A1 TB1-A1
COMPRESSOR
PE
PE
回风温湿度传感器
PE
485+
N B1 TB1-B1 485- INVERTER 主空开 主空开1 1 3 5 7 1 3 5 7 主空开2
J1 J34 24VDC J21 DC+ DC- J11 J21 DC+ DC- J11 BL BL BL BL 1 3 5 7
MAIN BREAK MAIN BREAK 1 PE PE MAIN BREAK 2
RETURN AIR J1 J34 电源模块
U V W PE QS1 2 4 6 8
PE
QS1 2 4 6 8 2 4 6 8 QS2
EH1-N
EH2-N
EH3-N
EH4-N
J21-DC1+
J11-DC1-
J21-DC2+
J11-DC2-
T&TH SENSOR 63A 63A 63A
冷凝水泵
CONDENSATE BK R BL Y/G 屏蔽
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
PUMP
L1
L2
L3
PE
10V(1) 10V(1) 48V 48V GND GND 10V(2)10V(2) 48V 48V GND GND 压缩机
TB4 10V(1) 10V(1) 48V 48V GND GND 10V(2)10V(2) 48V 48V GND GND
TB5 COMPRESSOR
屏蔽
ZPV096
TB2
B B2 TB2-B2 BK J14-B 1 1 J15-1 BR
J15
A A2 TB2-A2 BR J14-A 2 J14 2 J15-2 BK
RDU-SIC 1 J16-1 BK
J16
2 J16-2 BR
12V 12V TB2-12V
GND GND TB2-GND 1 J19-1 BK
BR BK J19-2 BR 高压告警/HIGH PRESSURE ALARM
2
3 J19-3 BK
TB1-GND
TB1-12V
BK J22-B 1 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2)
B1 TB2-B1 J21-1 BK
J22-A 2 J22 1
A1 TB2-A1 BR J21-2 BR C NO 滤网压差开关/FILTER CLOGGED SWITCH OPTIONAL
2
3
4
J21 J21-5 BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
5
R
R
SAS1 BK J25-1 J21-6 BR J1-1 J1-2 浮球开关/FLOAT LEVER SWITCH OPTIONAL
送风温度传感器1 1 6
SUPPLY AIR SENSOR 1 BK J25-2 7 J21-7 BK TB2-37 37
2
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
J21-8 BR TB2-38 38 远程开关机/REMOTE SHUTDOWN DEVICE
R
R
SAS2 BK J25-3 J25 8
送风温度传感器2 3
SUPPLY AIR SENSOR 2 BK J25-4 4
1 J28-1 BK TB1-24V 24V FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 FAN7 FAN8 FAN9 FAN10 FAN11 FAN12
2 J28-2 BK Y1-1 加湿电磁阀
3 J28-3 BK TB2-75 75 公共告警 0V TB1-0V Y1-2 HUMIDIFY SOLENOID VALVE
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
J28-4 BR TB2-76 76 COMMON ALARM
W
P
4
DTS BK J8-1 5 J28-5 BK TB1-24V 24V
排气温度传感器 1 J28 J28-6 BK TB2-63 63 Y1
O
O
DISCHARGE TEMPERATURE SENSOR BK J8-2 J8 6 液路电磁阀 TB5
2 TB2-64 64 Y1 XPE
7 FREON SOLENOID VALVE
8 GND
TB1-0V
9
10
0V
HP-5V R J23-1 1
DI10
DI11
DI12
高压传感器
GND
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
HP-VIN BR J23-2 2 J23
HIGH PRESSURE TRANSDUCER HP-GND BK J23-3 3 TB3
1#10DI-1 1#10DI-2 2#10DI-1 2#10DI-2
远程温度传感器
J38
J38 1#10DI CARD 2#10DI CARD REMOTE TEMP
SENSOR *
A1 B1
J34-1 O
TB1-B1
TB1-A1
1 1
J34-2 R
2 2
J39-A BR J33-3 3 J33 3
J34-3 YE
2 J34 执行阀体A
J39 BK J33-4 4 J34-4 BK
1 J39-B 4
J34-5 BR
EEV A
5
6
吸气温度传感器
STS
BR
BK
J38-1 1
J38-2 2 J38
电子膨胀阀控制器
SUCTION TEMPERATURE SENSOR
STS EEV CONTROLLER
J32
LP-5V R J43-1 1
1 2
低压传感器 LP-VIN BR J43-2 2
LPT J43
LOW PRESSURE TRANSDUCER LP-GND BK J43-3 3
J32-1
J32-2
TERMINAL BLOCK/端子排
BK
BR
TB1
TB2 TB3
TB1-24V
TB1-0V
备注/Notes:
Factory supplied line voltage wiring/出厂线电压线路
配线色标/Wire color code:
Ethernet or CAN wiring/以太网或CAN线路
Factory supplied 24 volt wiring/出厂24V线路 BK-Black/黑色 P-Purple/紫色
BL-Blue/蓝色 R-Red/红色
Device own line/器件自带线
BR-Brown/棕色 YE-Yellow/黄色
Inline quick disconnect/线上快速对插端子
WH-White/白色 GR-Grey/灰色
Terminal block connector/线缆端子 Y/GN-Yellow green/黄绿色
Naked crimping connector/裸压端子 O-Orange/橙色
Version 1.6