Liebert® CRV4 Series

Air-cooled Precision Air Conditioners


Technical Manual (Original Instructions)
Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

The information contained in this document is subject to change without notice


and may not be suitable for all applications. While every precaution has been
taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages result from
use of this information or for any errors or omissions.

Refer to local regulations and building codes relating to the application,


installation, and operation of this product. The consulting engineer, installer,
and/or end user is responsible for compliance with all applicable laws and
regulations relation to the application, installation, and operation of this
product.

The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use, or disclosure of
it without the written permission of Vertiv is strictly prohibited.

Names of companies and products are trademarks or registered trademarks of


the respective companies. Any questions regarding usage of trademark names
should be directed to the original manufacturer.

Technical Support Site


If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.

Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual
Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

TABLE OF CONTENTS

1 Product Overview 1
1.1 Product Introduction 1
1.2 Product Appearance 1
1.3 Model Nomenclature 2
1.4 Main Components 3
1.5 Optional Components 4
2 Technical Parameters 7
2.1 Mechanical Parameters 7
2.1.1 Mechanical Parameters Of Indoor Unit 7
2.1.2 Positioning of Bottom and Top Plate Inlet and Outlet Access 7
2.2 Component Parameters 11
2.3 Performance Parameters 15
2.4 Electrical Performance 18
2.5 Noise Performance 18
3 Application Guidelines 19
3.1 Conditions of Use 19
3.1.1 Operating Environment 19
3.1.2 Storage Environment 19
3.2 General Layout 19
3.3 Cooling System Connection 22
3.3.1 Pipe Connection 23
3.3.2 Adding Extension Kits (On-site Installation) 27
3.3.3 Charging Refrigerant and Adding Lubricating Oil 30
3.3.4 Adding Lubricating Oil 30
3.4 Electrical Installation 31
3.5 Connecting the Control Cables 35
3.5.1 Water Underfloor Sensor 35
3.5.2 SIC Card 36
3.5.3 Remote Shutdown 36
3.5.4 Outdoor Unit Signal Control 36
3.5.5 Common Alarms 36
3.5.6 Connecting Extension Kit Solenoid Valve (Optional for On-site Installation) 36
3.5.7 Teamwork Control 36
3.6 Connecting Condensate Drainage Pipe on Indoor Unit 36
3.7 Connecting Humidifier Water Inlet Pipe 40
3.7.1 Connecting Electrode Humidifier Water Inlet Pipe 40
3.7.2 Connecting Wet Film Humidifier Water Inlet Pipe 41
3.8 Rack Temperature Sensors 42
i

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

4 Display Screen Operation 45


4.1 Features 45
4.2 Appearance 45
4.3 Interface 46
4.3.1 Main Interface 46
4.3.2 Control Mode 48
4.3.3 Password Interface 49
4.4 Menu Structure 50
4.4.1 Main Menu 50
4.4.2 Operating Status 51
4.4.3 Alarm Information 54
4.4.4 Temperature and Humidity Setting 56
4.4.5 Parameter Setting 57
4.4.6 Temperature and Humidity Curve 64
4.4.7 Version Information 64
5 Control Logic 67
5.1 Cooling 67
5.1.1 Control Mode 67
5.1.2 Temperature Algorithm 67
5.1.3 Compressor Control 68
5.1.4 Fan Control 69
5.1.5 Electronic Expansion Valve Control 69
5.1.6 High Temperature Regulation 69
5.2 Humidity Control 69
5.2.1 Humidity Algorithm 69
5.2.2 Dehumidification Control 70
5.2.3 Humidification Control 70
5.3 Heating 71
5.3.1 Dehumidification Temperature Compensation 71
5.3.2 Separate Heating 71
5.4 Oil Return Operation 71
5.5 Condensate Pump Control 71
5.6 Shutdown Mode 71
5.6.1 Shutdown Types 71
5.6.2 Shutdown Logic 71
5.7 Teamwork Control 72
5.7.1 Teamwork Control Parameter 72
5.7.2 Typical Standby Features 72
5.8 Alarm Logic 73
Appendix A: Display Screen Menu Structure 83

ii

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Appendix B: Alarm 85
Appendix C: Hazardous Substances 87
Appendix D: Circuit Diagram 89
Appendix D1 CR025 Circuit Diagram 90
Appendix D2 CR035 Circuit Diagram 91
Appendix D3 CR045 Circuit Diagram 92
Appendix D4 CR036 Circuit Diagram 93
Appendix D5 CR066 Circuit Diagram 94

iii

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

This page intentionally left blank

iv

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

1 Product Overview
This section describes the features, appearance, model description, main components, and optional components of the
Vertiv™ Liebert® CRV4 series air-cooled precision air conditioner (hereafter referred to as CRV4 or the unit).

1.1 Product Introduction


CRV4 is a full-featured precise environmental control system for large, medium, and small computer rooms and modular
computer rooms with high heat density and energy-saving requirements. It provides a proper environment for process
equipment, communication equipment, and computers. CRV4 covers five cooling capacities: 25kW, 35kW, 36kW, 45kW, and
66kW. This variable capacity refrigeration system uses R410A environmentally friendly refrigerant.

The unit is suitable for installing between a row of high-density computer cabinets to form a "hot aisle-cold aisle"
configuration. The heat generated by the equipment enters the unit from the hot aisle, and is filtered, cooled, and then
returned to the cold aisle. The unit can be placed between the cabinets or at the end of a row of cabinets, as it is equipped
with air baffle and can easily adjust the air supply direction to the left, right or both sides.

CRV4 has all the functions of a standard precision air conditioner, including refrigeration, heating, humidification,
dehumidification, air filtration, condensate management, temperature control, alarm function, and data communication.

The standard model adopts air-cooled heat dissipation and can be used with a centralized LVC condenser or a new Liebert
PEX condenser according to different environmental conditions.

1.2 Product Appearance


Figure 1.1 Product Appearance

1 Product Overview 1

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

1.3 Model Nomenclature


The unit is named in 25 digits.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

C R 0 3 6 R A 1 N 8 S 7 1 2 E 3 0 0 0 0 P V 0 4 0

Digit Feature Value Description

1, 2 Product model CR CRV

3, 4, 025/ 035/
Cooling capacity Nominal cooling capacity, kW
5 036/045/066

R Horizontal airflow with baffle


6 Air supply type
H Horizontal airflow without baffle

A Air-cooled, cooling-only model (reheat and humidification are optional)


7 System type
P Refrigerant pump cooling

8 Fan type 1 EC fan

9 Power supply N 380-415 V, 50/60 Hz, 3 Ph + N + PE

Variable speed compressor, R410A refrigerant (single compressor single


8
10 System configuration circuit)
L
Single circuit, variable speed compressor, R410A refrigerant, single pump

0 None
11 Humidification S Electrode humidifier
W Wet film humidifier

S Standard display
12 Display
7 Global HMI 7-inch screen

0 None
13 Reheat
1 Electric heater (single-stage)

2 G4 (EU4) filter
14 Filtration
0 G4 (EU4) filter + filter clog switch

15 Coil and valves E Standard DX air- cooled coil, electronic expansion valve (EEV)

16 Appearance 3 EG7021 (black)

0 None
Mains disconnect switch high voltage
17 A Dual power supply (interlocking contactor)
options
T Dual power supply (ATS)

0 None, standard pipe, no low ambient kit


H Reheat and humidification lockout
18 Installation options L Air-cooled, long pipe > 30 m
C Low ambient kit
B Low ambient kit + long pipe

19 Monitoring 0 RS485 interface

2 1 Product Overview

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Digit Feature Value Description

S SIC card
7 Unity card

20 Sensor 0 None

P Standard packaging
21 Packaging
C Packaging for ocean shipping

A None
22 Special requirements
V Condensate pump

0 Bottom piping
23 Piping
1 Top Piping

24 Order special identifier 4 CRV4

0 Industry version - 1100 mm


25 Order special identifier 1 Telecom version
2 Industry version - 1200 mm

1.4 Main Components


The indoor unit of CRV4 includes DC brushless compressor, evaporator, EEV, humidifier, EC fan, electric heater, sight glass,
filter dryer, and display screen.

Compressor
The DC brushless compressor features low vibration, low noise, and high reliability. It is connected with suction and
discharge pipes with threaded connectors. It is convenient and easy to replace.

Evaporator
The evaporator uses high-efficiency, finned tube heat exchanger. It has a larger windward area and a smaller pressure drop.
The flow path is specially optimized to improve the utilization rate of the heat exchanger and ensure that the supply air
temperature is uniform. The surface is hydrophilic. There are condensate drainage pans in the middle and bottom of the
evaporator.

EEV
The EEV monitors temperature and pressure signals to provide accurate regulation of the refrigerant flow.

Humidifier
The unit can be equipped with electrode humidifier or wet film humidifier. CR025, CR035 and CR045 are equipped with
electrode humidifier as standard configuration. CR025, CR035 and CR045 can be configured with wet film humidifier.
CR036 and CR066 are equipped with wet film humidifier as standard configuration and cannot be installed with electrode
humidifier.

The electrode humidifier has a simple structure and is easy to disassemble and maintain. It has a short humidification time
and provides a large amount of humidification. The wet film humidifier is simple to control and has low water quality
requirements and low energy consumption.

1 Product Overview 3

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Fan
EC fan provides high efficiency and saves energy and space. It is hot-swappable.

Electric Heater
PTC electric heater has fast heating speed and provides uniform heat. It is safe and reliable.

Sight Glass
Sight glass serves as the window of system circulation. Through it, you can observe the status of the refrigerant and detect
the water content of the system. When the water content exceeds the standard, the sight glass background color will
change.

Filter Drier
Filter drier can effectively remove the moisture present in the system, filter the impurities generated by the long-term
operation of the system, and ensure the normal operation of the system. It is connected to the air conditioner with threaded
connectors, making it easy to replace.

Display Screen
The unit is configured with 7-inch color screen or LCD screen. The user interface operation is simple. The multi-level
password protection can effectively prevent unauthorized operation. It also provides power failure auto-restoration and high
& low voltage protection functions. The operation status of the components are available on the respective menus. The
expert-level fault diagnosis system can automatically display the current fault information, facilitating easy maintenance. It
can store up to 1,000 historical event records.

Remote Monitoring Software


The unit adopts the standard communication protocol (industry standard Modbus protocol) of the Ministry of Industry and
Information Technology of China. The unit communicates with the back end computer and is controlled by the back end
software via the RS485 interface.

1.5 Optional Components


Filter Differential Pressure Switch
It is used to detect the clogging of the filter screen and sends an alarm signal to the control board.

Water Leakage Detection Components


It is used to detect floor overflow and sends an alarm signal to the control board.

Remote Temperature Sensor Assembly


It is used to monitor the temperature of other equipment in the machine room, and the temperature can be used as the
control temperature of the unit.

Monitoring Card
Vertiv RDU-SIC monitoring card with RJ45 interface and USB interface:

4 1 Product Overview

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

• Use the web browser to monitor the smart devices and the environment data of the equipment room through
the web server function provided by the SIC card.
• Use the network management system (NMS) to monitor smart devices and computer room environment
through the SNMP agent function provided by the SIC card.
• Use the computer room management software (RDU-Manager) to monitor smart devices and computer room
environment through the TCP/IP interface provided by the SIC card.
• Use the centralized management software (Nform) to monitor smart devices through the Velocity Server
service function provided by the SIC card.

1 Product Overview 5

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

This page intentionally left blank

6 1 Product Overview

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

2 Technical Parameters
This section describes the technical parameters of CRV4.

2.1 Mechanical Parameters


2.1.1 Mechanical Parameters Of Indoor Unit
Figure 2.1 Mechanical Parameters of Indoor Unit

Table 2.1 Indoor Unit Dimensions and Weight


Model W×D×H mm Unit Weight kg

CR025RA1N8W712E30000PV040 300×1100×2000 (including leveling feet) 235

CR025RA1N8W712E30000PV042 300×1200×2000 (including leveling feet) 255

CR035RA1N8S712E30000PV040 600×1100×2000 (including leveling feet) 320

CR035RA1N8S712E30000PV042 600×1200×2000 (including leveling feet) 350

CR045RA1N8S712E30000PV040 600×1100×2000 (including leveling feet) 335

CR045RA1N8S712E30000PV042 600×1200×2000 (including leveling feet) 365

CR036RA1N8W712E30000PV040 300×1100×2000 (including leveling feet) 260

CR036RA1N8W712E30000PV042 300×1200×2000 (including leveling feet) 290

CR066RA1N8W712E30000PV040 600×1100×2000 (including leveling feet) 360

CR066RA1N8W712E30000PV042 600×1200×2000 (including leveling feet) 390

2.1.2 Positioning of Bottom and Top Plate Inlet and Outlet Access
Positioning of Bottom Plate Inlet and Outlet Access
(Overlooking the bottom plate, from the rear door, the air return side)

2 Technical Parameters 7

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 2.2 Positioning of Bottom Plate Inlet and Outlet Access

8 2 Technical Parameters

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 2.2 Bottom Plate Pipe Outlet Size (Unit: mm)


Model CR025 CR035 CR045 CR036 CR066

Compressor air discharge pipe opening Ø16 Ø22 Ø22 Ø19 Ø22

Evaporator liquid inlet pipe opening Ø12.7 Ø16 Ø16 Ø16 Ø16

Cable inlet hole Ø22 Ø36 Ø36 Ø22 Ø36

Wet film humidifier water inlet pipe ID9 x T3 ID9 x T3 ID9 x T3 ID9 x T3 ID9 x T3

Pump condensate drainage pipe ID9 x T3 ID9 x T3 ID9 x T3 ID9 x T3 ID9 x T3

Gravity condensate drainage pipe ID16 x T4 ID16 x T4 ID16 x T4 ID19 x T4.5 ID19 x T4.5

Electrode humidifier water inlet pipe connector 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread - -

Positioning of Top Plate Inlet and Outlet Access


Figure 2.3 Positioning of Top Plate Inlet and Outlet Access (Unit: mm)

2 Technical Parameters 9

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 2.3 Top Plate Pipe Outlet Size (Unit: mm)


Model CR025 CR035 CR045 CR036 CR066

Compressor air discharge pipe opening Ø16 Ø22 Ø22 Ø19 Ø22

Evaporator liquid inlet pipe opening Ø12.7 Ø16 Ø16 Ø16 Ø16

Cable inlet hole Ø22 Ø22 Ø22 Ø22 Ø22

Humidifier water inlet pipe 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread

Pump condensate drainage pipe 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread 1/2"-BSP thread

10 2 Technical Parameters

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 2.4 Air Supply on Unit Front Side

NOTE: To prevent cuts to the power cables, the protective holes for the cables are fitted with wire sheaths.

2.2 Component Parameters


Table 2.4 Component Parameters (CR025)
Unit model
Component
CR025RA1N8S712E30000PV040 CR025HA1N80S02E30000PV041

Type DC brushless scroll compressor DC brushless scroll compressor


Compressor
Quantity 1 1

Type EC fan with external power module EC fan with external power module
Fan
Quantity 6 6

2 Technical Parameters 11

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 2.4 Component Parameters (CR025) (continued)


Unit model
Component
CR025RA1N8S712E30000PV040 CR025HA1N80S02E30000PV041

Type Electronic expansion valve Electronic expansion valve


Expansion valve
Quantity 1 1

Type V-shape finned tube heat exchanger V-shape finned tube heat exchanger

Windward area (m2) 0.988 0.988


Evaporator coil
Rated windward speed (m/s) 1.46 1.46

Maximum windward speed (m/s) 1.55 1.55

Type One-stage electric heater, PTC None


Electrical heater
Heating power (kW) 3 None

Type Wet film humidifier None


Humidifier
Humidifying capacity (kg/h) 1.5 None

Air filter Grade G4 (EU4) G4 (EU4)

Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card (optional)
Quantity The unit can be configured with at most 1pcs of monitoring card

Condensate pump Head (m) 5 5

Air baffle Quantity Available None

Table 2.5 Component Parameters (CR035)


Unit model
Component
CR035RA1N 8S712E30000PV040 CR035HA1N- 80S02E30000PV041

Type DC brushless scroll compressor DC brushless scroll compressor


Compressor
Quantity 1 1

Type EC fan with external power module EC fan with external power module
Fan
Quantity 8 8

Type Electronic expansion valve Electronic expansion valve


Expansion valve
Quantity 1 1

Type V-shape finned tube heat exchanger V-shape finned tube heat exchanger

Windward area (m2) 1.27 1.27


Evaporator coil
Rated windward speed (m/s) 1.75 1.75

Maximum windward speed (m/s) 1.86 1.86

Type One stage electric heater, PTC None


Electrical heater
Heating power (kW) 6 None

12 2 Technical Parameters

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 2.5 Component Parameters (CR035) (continued)


Unit model
Component
CR035RA1N 8S712E30000PV040 CR035HA1N- 80S02E30000PV041

Type Electrode humidifier None


Humidifier
Humidifying capacity (kg/h) 1.5 None

Air filter Grade G4 (EU4) G4 (EU4)

Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card
Quantity The unit can be configured with at most 1pcs of monitoring card

Condensate pump Head (m) 5 5

Air baffle - Available None

Table 2.6 Component Parameters (CR045)


Unit model Unit model
Component
CR045RA1N8S712E30000PV040 CR045HA1N80S02E30000PV041

Type DC brushless scroll compressor DC brushless scroll compressor


Compressor
Quantity 1 1

Type EC fan with external power module EC fan with external power module
Fan
Quantity 10 10

Type Electronic expansion valve Electronic expansion valve


Expansion valve
Quantity 2 2

Type V-shape finned tube heat exchanger V-shape finned tube heat exchanger

Windward area (m2) 1.27 1.27


Evaporator coil
Rated windward speed (m/s) 2.08 2.08

Maximum windward speed (m/s) 2.23 2.23

Type One stage electric heater, PTC None


Electrical heater
Heating power (kW) 6 None

Type Electrode humidifier None


Humidifier
Humidifying capacity (kg/h) 1.5 None

Air filter Grade G4 (EU4) G4 (EU4)

Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card
Quantity The unit can be configured with at most 1pcs of monitoring card

Condensate pump Head (m) 5 5

Air baffle - Available None

2 Technical Parameters 13

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 2.7 Component Parameters (CR036)


Component
Component
CR036RA1N8W712E30000PV040

Type DC brushless scroll compressor


Compressor
Quantity 1

Type EC fan with external power module


Fan
Quantity 7

Type Electronic expansion valve


Expansion valve
Quantity 1

Type V-shape finned tube heat exchanger

Windward area (m2) 0.69


Evaporator coil
Rated windward speed (m/s) 2.53

Maximum windward speed (m/s) 2.58

Type One stage electric heater, PTC


Electrical heater
Heating power (kW) 3

Type Wet film humidifier


Humidifier
Humidifying capacity (kg/h) 1.5

Air filter Grade G4 (EU4)

Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card
Quantity The unit can be configured with at most 1pcs of monitoring card

Condensate pump Head (m) 5

Air baffle - Available

Table 2.8 Component Parameters (CR066)


Component
Component
CR066RA1N8W712E30000PV040

Type DC brushless scroll compressor


Compressor
Quantity 1

Type EC fan with external power module


Fan
Quantity 12

Type Electronic expansion valve


Expansion valve
Quantity 1

14 2 Technical Parameters

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 2.8 Component Parameters (CR066) (continued)


Component
Component
CR066RA1N8W712E30000PV040

Type V-shape finned tube heat exchanger

Windward area (m2) 1.34


Evaporator coil
Rated windward speed (m/s) 2.07

Maximum windward speed (m/s) 2.49

Type One stage electric heater, PTC


Electrical heater
Heating power (kW) 6

Type Wet film humidifier


Humidifier
Humidifying capacity (kg/h) 1.5

Air filter Grade G4 (EU4)

Type Vertiv RDU-SIC monitoring card, providing an RJ45 port and a USB port
Monitoring card
Quantity The unit can be configured with at most 1pcs of monitoring card

Condensate pump Head (m) 5

Air baffle - Available

2.3 Performance Parameters


CRV4 nominal performance is shown in the table below. Model selection can only be performed according to nominal
performance.

Table 2.9 Performance Parameters


Condensate temperature 45°C
Item
CR025 CR035 CR045 CR036 CR066

40°C DB 20%RH

Total cooling capacity (kW) 28.15 39.54 49.12 36.73 66.2

Sensible cooling capacity (kW) 28.03 38.75 46.73 36.73 66.2

Unit input power (kW) 6.75 9.22 12.27 10.8 22.35

Heat dissipation capacity (kW) 34.90 48.76 61.39 46.89 89.12

Air supply temperature (°C) 24.01 26.2 26.21 22.98 22.19

37°C DB 24%RH

Total cooling capacity (kW) 26.61 38.58 45.14 34.54 64.4

Sensible cooling capacity (kW) 26.45 37.67 43.83 34.54 64.4

Unit input power (kW) 6.72 9.2 12.12 10.64 22.10

Heat dissipation capacity (kW) 33.33 47.78 57.26 45.18 86.24

Air supply temperature (°C) 21.92 23.66 24.07 20.17 20.28

2 Technical Parameters 15

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 2.9 Performance Parameters (continued)


Condensate temperature 45°C
Item
CR025 CR035 CR045 CR036 CR066

35°C DB 26%RH

Total cooling capacity (kW) 25.48 37.4 43.92 33.4 62.9

Sensible cooling capacity (kW) 25.42 36.59 42.69 33.4 62.9

Unit input power (kW) 6.72 9.18 12.07 10.5 21.8

Heat dissipation capacity (kW) 32.20 46.58 55.99 43.9 85.3

Air supply temperature (°C) 20.61 22.05 22.51 19.5 19.0

32°C DB 29%RH

Total cooling capacity (kW) 24.13 35.64 41.38 32.2 60.2

Sensible cooling capacity (kW) 23.91 35.02 40.28 32.2 60.2

Unit input power (kW) 6.68 9.12 12.01 10.4 21.5

Heat dissipation capacity (kW) 30.81 44.76 53.39 43.3 81.5

Air supply temperature (°C) 18.59 19.81 20.27 18.5 18.1

30°C DB 34%RH

Total cooling capacity (kW) 22.51 34.01 39.83 31 58.0

Sensible cooling capacity (kW) 22.42 33.47 38.78 31 58.0

Unit input power (kW) 6.74 9.12 12.00 10.2 21.0

Heat dissipation capacity (kW) 29.25 43.13 51.83 41.6 79.7

Air supply temperature (°C) 17.69 18.39 18.81 17.4 17.3

Note:
• The cooling capacity is the net cooling capacity value. All capacities are nominal; actual performance values may vary ±5% from nominal.
• The data in the table are rated data with standard G4 filter. Certain options or combinations of options may result in reduced airflow.
• For standard air volume, see Table 2-9

The maximum performance of CRV4 is the ultimate cooling capacity that the unit can achieve, and it is the highest
performance that can be achieved when the compressor and fan are increased to the highest speed. On the one hand, this
function is to enable the unit to quickly reduce the current high ambient temperature when it is turned on after the initial
installation, and on the other hand, it is to deal with the sudden high ambient temperature exceeding the design conditions
in the computer room and data center.

Table 2.10 Maximum Performance


Condensate temperature 45°C
Item
CR025 CR035 CR045 CR036 CR066

40°C DB 20%RH

Total cooling capacity (kW) 30.64 42.54 51.15 38.16 67.78

Sensible cooling capacity (kW) 30.10 41.65 49.19 38.16 67.78

16 2 Technical Parameters

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 2.10 Maximum Performance (continued)


Condensate temperature 45°C
Item
CR025 CR035 CR045 CR036 CR066

Unit input power (kW) 8.05 10.67 13.64 11.54 23.89

Heat dissipation capacity (kW) 38.69 53.21 64.79 50.47 93.26

Air supply temperature (°C) 23..80 25.29 25.51 22.53 21.41

37°C DB 24%RH

Total cooling capacity (kW) 28.85 40.96 47.51 35.2 65.4

Sensible cooling capacity (kW) 28.67 40.25 46.21 35.2 65.4

Unit input power (kW) 7.82 10.58 13.40 11 23.33

Heat dissipation capacity (kW) 36.67 51.54 60.91 46.2 89.6

Air supply temperature (°C) 21.66 22.77 23.42 20.6 20.27

35°C DB 26%RH

Total cooling capacity (kW) 27.55 39.62 46.00 34.3 63.5

Sensible cooling capacity (kW) 27.37 38.88 44.86 34.3 63.5

Unit input power (kW) 7.83 10.55 13.34 10.9 22.8

Heat dissipation capacity (kW) 35.38 50.17 59.34 45.2 86.2

Air supply temperature (°C) 20.45 21.39 21.85 19.2 19.5

32°C DB 29%RH

Total cooling capacity (kW) 25.99 37.57 43.36 33.1 61.0

Sensible cooling capacity (kW) 25.82 37.01 42.23 33.1 61.0

Unit input power (kW) 7.78 10.45 13.27 10.7 22.5

Heat dissipation capacity (kW) 33.77 48.02 56.63 43.9 84.6

Air supply temperature (°C) 18.38 19.12 19.73 18.1 18.2

30°C DB 34%RH

Total cooling capacity (kW) 24.50 35.96 41.83 31.9 59.6

Sensible cooling capacity (kW) 24.22 35.45 40.75 31.9 59.6

Unit input power (kW) 7.75 10.45 13.22 10.3 22.1

Heat dissipation capacity (kW) 32.25 46.41 55.05 42.8 82.4

Air supply temperature (°C) 17.29 17.73 18.20 17.0 17.7

Note
• The cooling capacity is the net cooling capacity value. All capacities are nominal; actual performance values may vary ±5% from nominal.
• The data in the table are rated data with standard G4 filter. Certain options or combinations of options may result in reduced airflow.

2 Technical Parameters 17

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

2.4 Electrical Performance


Table 2.11 Full Load Current Value (Unit: A)
With single-stage electric With single-stage electric
FLA(A) Cooling-only model With electrode humidifier
heater heater and electrode humidifier

CR025 21.7 22.7 23.4 23.4

CR035 29.3 36.9 30.8 36.9

CR045 39.1 44.3 39.1 44.3

With single-stage electric With single-stage electric


FLA(A) Cooling-only model With wet film humidifier
heater heater and wet film humidifier

CR036 31.2 32.1 31.2 32.1

CR066 47.5 51 47.5 51

2.5 Noise Performance


Table 2.12 Noise Performance
Model Air volume (m3/h) Unit SPL (1m away from the unit front, dBA) Unit SPL (2m away from the unit front, dBA)

CR025 Rated air volume 5,200 81.5 78.4

CR035 Rated air volume 8,000 80.8 77.5

CR045 Rated air volume 9,500 82.2 80.5

CR036 Rated air volume 6,300 81.5 78.4

CR066 Rated air volume 12,000 83.0 80.4

Note: SPL is sound pressure level.

18 2 Technical Parameters

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

3 Application Guidelines
This section describes the conditions of use, general layout, refrigeration connections, electrical connections, water pipe
connections, and temperature sensors of CRV4.

3.1 Conditions of Use


3.1.1 Operating Environment
The operating environment should meet the requirements of GB4798.3-2007.

Table 3.1 Operating Environment Requirements


Item Requirement

Indoor 18 °C to 40 °C, 20% to 60% RH

Ambient temperature -20 °C to +45 °C. If a low ambient kit is configured, the lowest outdoor operation temperature
Outdoor
is -34 °C

Protection level (outdoor unit) IP20

Altitude <1000 m. Contact Vertiv™ if altitude is above 1000 m

Operation voltage range 380-400 V ± 10%, 50 / 60 Hz, 3 Ph + N + PE

3.1.2 Storage Environment


The storage environment should meet the requirements of GB4798.1-2005.

Table 3.2 Storage Environment Requirements


Item Requirement

Storage
Indoor, clean, no dust
environment

Ambient humidity < 95% RH

Ambient
-40 °C to +70 °C
temperature

Total transportation and storage time should not exceed six months; otherwise the performance of the system needs to be re-
Storage time
calibrated

3.2 General Layout


CRV4 adopts the air-cooled heat dissipation and is matched to a centralized LVC condenser or a new Liebert PEX
condenser.

3 Application Guidelines 19

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 3.1 System Installation Diagram (Condenser Higher Than Compressor)

Item Description Item Description

1 Maximum height 30 m 8 Humidifier water inlet pipe

2 Outdoor unit (condenser) 9 Condensate drainage pipe

3 Liquid pipe, away from direct sunlight 10 Floor

4 Oil trap 11 Insulated layer

5 Gas pipe needs to be tilted 12 Gap needs to be sealed

6 Indoor unit 13 Maximum height 7.5 m

7 Raised floor

20 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 3.2 System Installation Diagram (Condenser Lower Than Compressor)

Item Description Item Description

1 Outdoor unit (condenser) 5 Raised floor

2 Maximum height 8 m 6 Humidifier water inlet pipe

3 Gas pipe needs to be tilted 7 Condensate drainage pipe

4 Indoor unit 8 Liquid pipe needs to be tilted

NOTE: When the condenser is higher than the compressor, install a reverse bend on the gas pipe and liquid pipe of
the condenser to avoid the backflow of the liquid refrigerant when shutting down.

NOTE: When installing the reverse bend, ensure that the top bend of the reverse bend is higher than the highest row
of copper pipes of the condenser.

3 Application Guidelines 21

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

3.3 Cooling System Connection


Figure 3.3 System General Layout

Item Description Item Description

1 Condenser coil 13 Low pressure sensor

2 Oil trap (installing one oil trap at every 7.5 m vertical rise) 14 Schrader valve 3

3 Solenoid valve 15 Suction line

4 Ball valve 1 16 Variable speed compressor

5 Schrader valve 1 17 Discharge line

6 Filter drier 18 Discharge temperature sensor

7 Sight glass 19 High pressure sensor

8 EEV 20 Ball valve 2

9 Schrader valve 2 21 Check valve

10 Distribution board 22 Schrader valve 4

11 Evaporator coil 23 High pressure switch

12 Suction temperature sensor

NOTE: CR036/066 does not contain ball valves.

NOTE: indicates the pipeline provided by the manufacturer.

22 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

NOTE: indicates the pipes that are laid on site (completed by technicians).

NOTE: Oil trap is not provided by Vertiv™. It is recommended to install it to ensure normal operation and convenient
maintenance.

NOTE: Solenoid valve and check valve are required when the equivalent pipe length is larger than 30 m.

3.3.1 Pipe Connection


The indoor and outdoor units are connected by copper pipe welding. The indoor unit supports top piping and bottom
piping.

The horizontal part of the pipe should be tilted downward after being led out of the compressor, and its inclination should
be at least 1:200 (5 mm should be lowered every 1 m). If the pipe is in an area affected by cooling equipment (or under a
raised floor), the pipe should be insulated.

The top and bottom plate of the unit have refrigeration pipe fittings and labels.

Figure 3.4 Top Plate Connections

3 Application Guidelines 23

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

24 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 3.5 Bottom Plate Connections for Refrigeration

3 Application Guidelines 25

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Considering the influence of pipe diameter on the pressure drop of the system, select the pip according to the
recommended size in Table 3.4.

Table 3.3 Relative Position of the Indoor Unit and Condenser


Item Description

Maximum equivalent distance between indoor unit and condenser 50 m

Maximum vertical height difference between indoor unit and condenser -8 m to 30 m

Pipe diameter See Table 3.4


Requirement
Oil trap on vertical refrigerant pipe Installing one oil trap every 7.5m

Note: If the height difference is positive, the condenser is higher than the indoor unit. If the height difference is negative, the condenser is lower than the
indoor unit.

26 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 3.4 Recommended Size of the Pipe (Unit: mm)


Model CR025 CR035 CR045 CR036 CR066

Pipe length Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe

10 m 19 12.7 19 16 22 16 19 16 25 19

20 m 19 16 22 16 25 19 22 16 25 19

30 m 22 16 25 16 28 19 25 16 28 22

40 m* 22 16 25 19 28 22 25 19 28 22

50 m* 22 19 25 22 28 22 25 19 32 25

Note:
• * indicates that a pipe extension kit needs to be added
• If the length of the pipe exceeds 50 m, consult Vertiv™
• If the outdoor ambient temperature is lower than -20 °C, the low ambient kit needs to be used. Please consult Vertiv™

Table 3.5 Equivalent Length of Components


Equivalent length (m)
Liquid pipe outer diameter (inch)
90° bend 45° bend T-type three way

3/8 0.21 0.10 0.76

1/2 0.24 0.12 0.76

5/8 0.27 0.15 0.76

3/4 0.3 0.18 0.76

7/8 0.44 0.24 1.1

1-1/8 0.56 0.3 1.4

3.3.2 Adding Extension Kits (On-site Installation)


If the one-way equivalent length exceeds 30 m, or if the vertical height difference between the indoor unit and the outdoor
unit exceeds the value shown in Table 3.3, you need to add pipeline extension kits. The equivalent length of the
recommended line includes the calculated resistance losses due to bends. The equivalent length of the extension kits is
shown in Table 3.5. Select the kits according to the site situation.

When installing extension kits on site, in order to prevent pipeline exposure, it is recommended to install the check valve of
the extension kit on the outer engineering pipeline of the gas pipe, and install the solenoid valve body on the outer
engineering pipeline of the liquid pipe ball valve, the outside or bottom of the equipment.

During the installation process, you do not need to cut the pipeline of the indoor unit, but open the ball valve for maintaining
pressure and evacuating the system after the installation of the entire system. This avoids the moisture absorption of the
compressor lubricating oil and ensures the safety and life of the compressor. For electrical wiring of extension kits, see
Section 3.5.6.

3 Application Guidelines 27

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Notice on Installing Check Valve

• For the unit with bottom piping, the check valve can be installed on the gas pipe between the floor and the
ground under the indoor unit. For the unit with upper piping, the check valve can be installed on the gas pipe
above the indoor unit.
• Whether the unit is upper piping or bottom piping, the position of the check valve should be as close as
possible to the indoor unit.
• When welding the check valve, pay attention to the arrow on the valve body, which indicates the refrigerant
flow direction in the valve body. Make sure that the arrow is facing the condenser.

Figure 3.6 Discharge Check Valve Mounting Direction

Notice on Installing Solenoid Valve

• For the unit with bottom piping, the solenoid valve can be installed near the floor and the ground under the
indoor unit. For the unit with upper piping, the solenoid valve can be installed near the indoor unit.
• Whether the unit is upper piping or bottom piping, the position of the solenoid valve should be as close as
possible to the indoor unit.
• The valve body and solenoid valve coil delivered to the site are separated. The valve body should be installed
on the refrigerant liquid pipe horizontally. Pay attention to the arrow on the valve body. The arrow indicates the
refrigerant flow direction in the valve body, and ensure that the arrow is facing the indoor unit.

Figure 3.7 Horizontally Mounted Solenoid Valve

• After welding the solenoid valve on the liquid pipe, install the coil. Remove the cover of the wiring terminals,
remove the cap by switching the slot in the middle, direct the cable through the cable hole in the cover, plug
the two terminals (black wire to pin 1 and brown wire to pin 2), reinstall the cap by switching the slot in the
middle, and reinstall the cover.

28 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 3.8 Connecting Solenoid Valve Cable

Item Description Item Description

1 Wire connection base 3 Reinstalling the screw that was removed from the coil

Removing the cap by switching the slot in the middle, connecting the
2
wires, and reinstalling the cap

• Clip the coil of the valve body and press the coil tightly to ensure complete contact between the coil and valve
body. Please be noted to first install the spring provided with the valve onto the valve.

Figure 3.9 Fixing the Coil

Item Description

1 Installing the valve spring onto the valve

2 Clipping the coil of the valve body and pressing the coil tightly

3 Application Guidelines 29

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

3.3.3 Charging Refrigerant and Adding Lubricating Oil


Charging Refrigerant

Inferior or counterfeit refrigerants will seriously damage the system. Please use refrigerants certified by Vertiv. If the use of
inferior refrigerants causes abnormal system failure or damage, Vertiv does not assume warranty responsibility. The
refrigerant brand certified by Vertiv is:

WARNING! Do not use inferior refrigerants. Vertiv does not assume warranty responsibility for any
consequences caused by inferior refrigerants.

The unit is charged in the factory with 2 bar nitrogen for shipping

Table 3.6 LSF Outdoor Unit Recommended Refrigerant Charge (Unit: kg)
Outdoor unit model LSF38 LSF42 LSF52 LSF62 LSF76 LSF85

Recommended charge (kg) 3.93 4.12 5.12 5.86 6.72 7.9

Table 3.7 LVC Outdoor Unit Recommended Refrigerant Charge (Unit: kg)
Outdoor unit model LVC088 LVC106 LVC140 LVC152 LVC170

Recommended charge (kg) 4.12 5.12 5.86 6.72 7.90

Table 3.8 Indoor Unit Recommended Refrigerant Charge (Unit: kg)


Indoor unit model CR025 CR035 CR045 CR036 CR066

Standard charge (kg) 2.47 3.12 3.44 2.76 6.0

The recommended amount of refrigerant charge is calculated according to the following formula:

Recommended refrigerant charge (kg) = Recommended outdoor unit refrigerant charge + Recommended indoor unit
refrigerant charge + Recommended amount of refrigerant per unit length (kg/m) × Total length of liquid pipe (m)

Where Recommended amount of refrigerant per unit length (kg/m) is shown in the table below.

Table 3.9 Recommended Amount of Refrigerant per Unit Length


Liquid pipe outer diameter (mm) Amount of refrigerant per unit length (kg/m) Liquid pipe outer diameter (mm) Amount of refrigerant per unit length (kg/m)

12.7 0.107 22 0.321

16 0.174 25 0.431

19 0.245 28 0.517

3.3.4 Adding Lubricating Oil


Adding refrigerant will lead to the dilution of the lubricating oil in the system, affecting the lubrication and cooling effect of
the oil. Therefore it is necessary to add lubricating oil.

30 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

NOTE: CR025, CR045, CR036, and CR066 units use POE (32-3MAF) lubricating oil. CR035 uses PVE (FVC68D)
lubricating oil.

NOTE: For adding lubricating oil, please contact Vertiv™.

WARNING! Adding inferior lubricating oil or adding an incorrect type of lubricating oil can damage the
system. The quality issues caused by this are not covered by the warranty.

Table 3.10 Type of Lubricating Oil


Unit model Type of lubricating oil

CR025 POE (32-3MAF)

CR035 PVE (FVC68D)

CR045 POE (32-3MAF)

CR036 POE (32-3MAF)

CR066 POE (32-3MAF)

Table 3.11 Additional Charge of Lubricating Oil


Liquid pipe CR025, CR035, CR045, CR036, CR066
diameter mm Within 30 m > 30 m

12.7

16

19 No need to add extra Recommended amount of additional charge of lubricating oil = Amount of refrigerant to add when the
22 lubricating oil pipe length exceeds 30 m × 10%

25

28

3.4 Electrical Installation


Low-voltage components can be seen after opening the rear door of the unit. The labels of the components help distinguish
them.

3 Application Guidelines 31

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 3.10 Electric Control Box (with Rear Door Opened at 120 Degrees)

Table 3.12 Main Circuit Breaker Type


Unit model Main circuit breaker type Current (A)

CR025 NDM1-63C40/3 40

CR035 NDM1-63C50/3 50

CR045 NDM1-63C63/3 63

CR036 NDM1-63C40/4 40

CR066 NDM1-63C63/4 63

Connect the L1, L2, L3, N, and PE to corresponding terminals of the field power supply. Reserve a certain margin of the inlet
cable and fix it to the clips on the inner side of the unit.

For the cable model selection, refer to the rated full load current value (FLA) of the unit.

32 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 3.11 Cable Access on the Top Plate and Bottom Plate

3 Application Guidelines 33

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

NOTE: The cable size should match local wiring rules

34 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

3.5 Connecting the Control Cables


Figure 3.12 Terminal Block (Enlarged View)

Terminal Description Terminal Description

51, 24 Water underfloor sensor 61, 62 CAN communication

37, 38 Remote power on/off 63, 64 Solenoid valve

70, 71 Outdoor unit control cable A2, B2, 12V, GND SIC card

75, 76 Common alarm A1, B1 Outdoor communication, for the unit with refrigeration pump or the EBM version

WARNING! Before connecting the control cable, take appropriate anti-static measures.

3.5.1 Water Underfloor Sensor


Water underfloor sensor is optional. If it is selected for the unit, connect one end of the sensor to terminal 51 of the terminal
block. Connect the other end to the common terminal of 24. Any number of sensors can be connected in parallel. Each unit
has only one water underfloor alarm.

3 Application Guidelines 35

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

3.5.2 SIC Card


SIC card is optional. If it is selected for the unit, connect the A, B, GND, and 12 terminals of the SIC card to the A2, B2, GND,
and 12V terminals of the terminal block respectively. The connection of Unity card is like SIC card. Details are shown in
Appendix A..

3.5.3 Remote Shutdown


The 37 and 38 terminals can be connected to the remote shutdown switch. The terminals are short circuited at the factory.
For connecting the remote shutdown device, you need to remove the short circuit.

NOTE: When the 37 and 38 terminals are disconnected, the unit will shut down.

3.5.4 Outdoor Unit Signal Control


The 70 and 71 terminals are the control signal terminals of the outdoor unit, and their switching state is the same as the
switching state of the compressor. Compressor speed control terminals can be connected to the control panel of the outdoor
unit, or they can be selected as not connected.

3.5.5 Common Alarms


Common alarms can be connected to the 75 and 76 terminals. The output is used to connect external alarm devices, such
as alarm lights. When a critical alarm occurs, the contacts are closed. This can be used to issue remote alarms to signal
building management systems or automatically dial paging systems. You need to provide power supply to the common
alarm system loop circuit.

For other terminal definitions, see Appendix A.

3.5.6 Connecting Extension Kit Solenoid Valve (Optional for On-site Installation)
The extension kit solenoid valve has two control cables. Connect them to the corresponding terminals on the control board.
For details on terminal number, see Appendix A.

3.5.7 Teamwork Control


When using the teamwork control function, you need to connect the communication line to the 61 and 62 terminals on the
TB2 terminal block.

3.6 Connecting Condensate Drainage Pipe on Indoor Unit


The condensate water from the humidifier and from the evaporator is gathered in the condensate pan and is then
discharged.

To discharge the condensate from the bottom plate, route the discharge hose out of the gravity condensate drainage hole or
the pump condensate drainage hole, connect the hose with a connector, and then connect it to your drainage system.

To discharge the condensate from the top plate, the discharge copper pipe has been routed out of the top plate. You only
need to connect the copper pipe connector (1/2’’-BSP) to your drainage system.

To use only gravity drainage, route the discharge pipe (inner diameter: 16 mm) out of the gravity condensate drainage hole
and connect the pipe to your drainage system. To ensure that the condensate water can be discharged, set a water trap.
Note the following requirements:

• Use electroplated steel pipe, PVC, or polyethylene pipe with good flexibility as the water pipe.

36 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

• Tilt the water pipe 2% along the draining direction.


• Set a water trap 30 cm under the condensate water pan. Place the water trap under the raised floor.
• Fill water into the water trap.

Figure 3.13 Water Trap

Item Description Item Description

1 Filling water to the water trap 4 Condensate pan

2 Bracket 5 Minimum 20 cm

3 Water trap 6 Minimum 10 cm

NOTE: Do not cut the bracket of the water trap. Otherwise, the water drainage will be affected.

NOTE: Before starting the unit, fill water to the water trap to avoid water from blowing out of the pan.

NOTE: To avoid leakage, use Teflon raw material belt between the drainage pipe and the connector.

NOTE: For the model with an electrode humidifier, because high-temperature water flows in the electrode humidifier,
you must use the water pipe with a heat resistance higher than 90°C.

NOTE: For the unit with condensate pump, the pump head should not exceed 5 m.

3 Application Guidelines 37

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 3.14 Discharging Condensate Water from Bottom Plate

38 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

3 Application Guidelines 39

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

3.7 Connecting Humidifier Water Inlet Pipe


3.7.1 Connecting Electrode Humidifier Water Inlet Pipe
To supply water to the humidifier from the bottom plate, route the hose (which is reserved inside the unit and has a
threaded connector) out of the water inlet hole on the bottom plate, and connect the hose to your drainage system using the
1/2"-BSP connector.

To supply water to the humidifier from the top plate, a pipe connector has been installed on the humidifier water inlet hole
on the top plate. Connect the connector to your drainage system.

The connection must be sealed to prevent water leakage, and the main line pressure range should be 100 kPa to 700 kPa.
Where the main pipe pressure may exceed 700 kPa, a pressure reducer should be installed. Where the main pipe pressure
is less than 100 kPa, there should be a collection tank and a water pump system.

Water quality requirements: conductivity between 125 and 1250 μs/cm.

NOTE: Some products may contain parts that are subject to local regulations

Figure 3.15 Bottom Piping for Electrode Humidifier Water Inlet Pipe

40 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

3.7.2 Connecting Wet Film Humidifier Water Inlet Pipe


To supply water to the humidifier from the bottom plate, route the hose (reserved inside the unit) out of the water inlet hole
on the bottom plate, and connect the hose to your drainage system.

To supply water to the humidifier from the top plate, a pipe connector (1/2"-BSP) has been installed on the humidifier water
inlet hole on the top plate. Connect the connector to your drainage system.

The connection must be sealed to prevent water leakage, and the main line pressure range should be 100 kPa to 700 kPa.
Where the main pipe pressure may exceed 700 kPa, a pressure reducer should be installed. Where the main pipe pressure
is less than 100 kPa, there should be a collection tank and a water pump system.

NOTE: The field-supplied water pipe should be cleaned to prevent impurities from entering the humidifier.

3 Application Guidelines 41

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 3.16 Connecting Wet Film Humidifier Water Inlet Pipe

3.8 Rack Temperature Sensors


Rack temperature sensor is optional. Each unit can be equipped with up to 6 rack temperature sensors. It is recommended
to place the sensor in front of the thermal load to obtain the most accurate temperature value. If the sensors are connected
in series, each sensor monitors the air temperature entering each rack device and the temperature values are used to
control the operation of the unit. The standard position of the sensor is 1.5 m high. Therefore, the sensor should be placed in
the position shown in the figure below.

42 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Otherwise the device will not operate properly. Plug the connector of the rack temperature sensor into the TB3 connector.
After connecting the cable, route the cable from the top or bottom of the unit and connect the cable to the first sensor, then
from the first sensor to the second sensor, and so on, to form a connection chain. Secure the temperature sensor in front of
the hottest heat source in the rack and do not fix it in front of an empty slot. During operation, attach the magnet of each
sensor to the surface of the rack. The sensor should be fixed where there is most likely a lack of sufficient cold air.

The IRM-S02TH address settings for the rack temperature sensor are shown in Table 4.3 Application Guidelines on page 19
.

Figure 3.17 Rack Temperature Sensor Position

Item Description

1 Rack temperature sensor

3 Application Guidelines 43

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 3.13 Rack Temperature Sensor IRM-S02TH Address Setting


Sensor 1 2 3 4 5 6 ID number

Rack temperature 1 0 0 0 1 0 0 10

Rack temperature 2 0 0 0 1 0 1 11

Rack temperature 3 0 0 0 1 1 0 12
1: ON
0: OFF
Rack temperature 4 0 0 0 1 1 1 13

Rack temperature 5 0 0 1 0 0 0 20

Rack temperature 6 0 0 1 0 0 1 21

44 3 Application Guidelines

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

4 Display Screen Operation


This section describes the appearance, features, control interface, and menu structure of the display screen.

4.1 Features
The micro-controller has the following features:

• Monitors and displays the operation status of the air conditioner to keep the environment within the set range.
• Configured with a 7-inch color screen, which makes user interface operation simple.
• Provides a three-level password protection to effectively prevent unauthorized operation.
• Provides self-recovery upon power failure, high voltage and low voltage protection, phase loss and anti-phase
protection, etc.
• Allows users to accurately understand the main parameters and operating status of the system.
• Displays the measured temperature and humidity curves in real time.
• Displays the running time of critical components in real time.
• Provides expert-level fault diagnosis and displays the current fault information to facilitate maintenance
personnel in servicing and repair.
• Stores up to 1000 historical alarm records.

4.2 Appearance
When the screen is in black screen state, tap the screen, and the service hotline will be displayed. The service hotline will
disappear after 15 seconds.

Figure 4.1 Color Screen Appearance

4 Display Screen Operation 45

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

The indicator is located under the screen. It has four colors and their indication is described in the table below.

Table 4.1 Indicator Color Description


Indicator Color Description

Blue Display is starting

Yellow Unit shuts down, or the display fails to communicate with the control board

Green Unit is running normally

Red An alarm occurs and the buzzer keeps generating sound

4.3 Interface
4.3.1 Main Interface
After the boot is completed, the main interface is displayed, containing the menu button, date and time, unit address,
display address, and unlock button. The menu button cannot be tapped because it has not been unlocked. After tapping the
unlock button and inputting the correct password, the temperature and humidity setting button, curve button, unit address,
display address, and switch button will be displayed. Press and hold the power on/off button for at least two seconds to
toggle between the power on/off function.

In control mode, the text on the left side of the circle indicates the humidity control mode (air supply humidity control). The
text on the right indicates the temperature control mode (default air supply control mode, consistent with the compressor
control mode). The temperature value in the circle represents the measured temperature and humidity value (default air
supply temperature) in the current mode. The humidity value represents the theoretical air supply humidity. For the two
triangles on the circle, the left represents the supply air humidity set point, and the right represents the temperature set
point in the current mode. Tap the toggle button 1 to switch between the graph and the list display. Tap the setting button
to enter the temperature and humidity setting interface and to set the temperature and humidity.

Figure 4.2 Main Interface (Unlocked)

46 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 4.2 Main Interface Description


Item Name Description

Home
1 Tap this button to enter the home page and view the main data and status of the system
button

Menu
2 Tap this button to display the main menu page, through which you can access each submenu
button

Settings
3 Tap this button to enter the temperature and humidity setting page, where you can set system temperature and humidity
button

Curve Tap this button to enter the curve interface, where you can view the 0-48 hour curve of return air average temperature, remote
4
button average temperature, supply air average temperature, and supply air average humidity

Time
5 Displays the current time
display

Unit
6 Displays the unit address
address

Monitor
7 Displays the monitor address
address

On and When the host is in the shutdown state, tap this button for at least two seconds and the host will power on. When the host is in the running
8
off button state, tap this button for at least two seconds and the host will shut down

Tap this button to enter the password-input interface and then to enter the unlocked interface. After that, you can tap the menu icon
Unlock and set parameters
9
button
Tap this button again to enter the unlocked interface

Operating
10 Displays the operating status of the current unit (shutdown, operation, standby, locking, and communication interruption)
status

Toggle
11 Tap this button to switch between graphical display mode and list display mode
button 1

Toggle
12 Tap this button to switch between alarm data and sensor data
button 2

Control
13 Displays the setpoint of the unit and the environmental conditions of the equipment
mode

Status
14 Displays the running status of the current component
display

Alarm
15 Displays the current alarm and the time when it occurs
data

Sensor
* Displays the sensor data of the current component
data

4 Display Screen Operation 47

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

4.3.2 Control Mode


The main interface is divided into three read-only states:

• Temperature control mode and humidity control mode


• Current control mode temperature value and theoretical air supply humidity value
• Temperature and humidity set value

Figure 4.3 Control Mode

Table 4.3 Control Mode Description


Item Description

1 The circle can be displayed in three colors: green, gray, and red

2 Measured supply air temperature value. It changes with the compressor's current control mode

Humidity setpoint. It changes in clockwise direction between the 30-150 angle in the polar coordinate. When the humidity setpoint is the minimum
3
value, it is at 30 degrees in the polar coordinate; when the humidity setpoint is the maximum value, it is at 150 degrees in the polar coordinate

4 Humidity control. By default, it is supply air humidity control

Temperature setpoint. According to the range of temperature setpoint, it changes in counterclockwise direction between the 30-150 angle in the
polar coordinate. When the temperature setpoint is the maximum value, it is at 30 degrees in the polar coordinate; when the temperature setpoint is
5 the minimum value, it is at 150 degrees in the polar coordinate

6 Theoretical supply air humidity value

7 Current compressor control mode. By default, it is supply air temperature control

8 represents the control state of the humidity displayed on the left

9 represents the control state of the temperature displayed on the right

48 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 4.4 Unit Status Color

Table 4.4 Unit Status Color Description


Color System state description

Red The power-on status sensor data is not within the normal range or is an invalid value

Grey The unit is in shutdown state or communication interruption state

Green The power-on state is within the normal range

4.3.3 Password Interface


Tap the Unlock button on the main interface to display the password interface.

Figure 4.5 Password Interface

4 Display Screen Operation 49

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

The password has three levels.

Table 4.5 Password Level


Password Initial
User Note
level password

Browse all menu information and set only temperature and humidity setpoints. Cannot set or
Level 1 Ordinary operators 1490
change other values

Maintenance
Level 2 - Browse all menu information and set all parameters except the display address
personnel

Manufacturer
Level 3 - -
technicians

If you enter the wrong password, you can only browse the homepage. Tap the ESC button to exit the password interface.

NOTE: If you do not type any password or enter the wrong password in the password interface, you can only view the
parameters and data of the unlocked interface, and you cannot view and change the menu parameters.

4.4 Menu Structure


4.4.1 Main Menu
After entering the correct password, the unlocked interface is displayed. For the specific menu structure, see Appendix B
Circuit Diagram on page 89 .

Figure 4.6 Main Menu

50 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 4.6 Menu Description


Menu item Description

Home Displays operating status, operating data, alarm data, and sensor data

Operational Displays temperature and humidity information, External Static Pressure (ESP) information, switch status, power information,
information and teamwork information

Alarm message Displays system current alarms, historical alarms, and compressor driver alarms

Temperature
and humidity
settings Sets the temperature and humidity values

Sets alarm parameters, alarm properties, system settings, compressor settings, internal fan settings, ESP settings,
Parameter
communication settings, teamwork settings, time settings, display settings, parameter recovery, password settings, and data
settings
logging settings
Menu Temperature
Displays the return air temperature curve, return air humidity curve, supply air temperature curve, and remote temperature
and humidity
curve
curve

About Displays the controller hardware and software version number, and the software and hardware version number of the display

Settings Displays the temperature and humidity settings under the same menu

Curve Displays the temperature and humidity curve under the same menu

4.4.2 Operating Status


Select operation information under the main menu to view temperature and humidity information, ESP information, power
supply information, and teamwork information.

Temperature and Humidity Information


You can view the temperature and humidity parameters of the unit in real time. This information includes return air
temperature and humidity, supply air temperature, remote temperature and other information. Press the rightmost scroll
bar to scroll up or down the query.

4 Display Screen Operation 51

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 4.7 Temperature and Humidity Information

ESP Information
You can view the ESP parameters of the unit in real time (when the unit is equipped with a ESP sensor).

Figure 4.8 ESP Information

Switch Status
You can view the disconnection or closing status of switches such as high-voltage switches, remote shutdown switches, floor
overflow switches, and electrical heating fault switches.

52 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 4.9 Switch Status

Power Information
You can view three-phase voltage and frequency.

Figure 4.10 Power Information

Teamwork Information
You can view the status of the teamwork message.

4 Display Screen Operation 53

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 4.11 Teamwork Information

4.4.3 Alarm Information


Select alarm information under the main menu to view current alarms, historical alarms, and compressor driver alarms.

Current Alarm
You can view the current alarm status record and the specific alarm status information. The specific alarm status information
includes the serial number, start date time, end date time, and alarm content.

Figure 4.12 Current Alarm

NOTE: The most recent alarm number is the smallest number. When multiple alarms occur, press the rightmost scroll
bar to scroll up or down the query.

54 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

NOTE: The current alarm record is automatically cleared when the system is powered down.

Historical Alarm
You can view the historical alarm information and the specific historical alarm information. The specific historical alarm
information includes the serial number, start date time, end date time, and alarm content.

Figure 4.13 Historical Alarm

NOTE: When multiple alarms occur, press the scroll bar on the right to scroll up or down to query.

NOTE: The alarm history can be saved up to 1000, and it is not cleared when the power is disconnected.

Compressor Driver Alarm


You can view the specific code of the compressor driver alarm.

4 Display Screen Operation 55

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 4.14 Compressor Driver Alarm

4.4.4 Temperature and Humidity Setting


Select temperature and humidity settings under the main menu to view temperature settings and humidity settings.

Temperature Setting
You can set values for return air temperature, remote temperature, supply air temperature , and temperature difference.

Figure 4.15 Temperature Setting

Humidity Setting
You can set the humidity value and ratio.

56 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 4.16 Humidity Setting

4.4.5 Parameter Setting


Select parameter settings under the main menu to view alarm parameters, alarm properties, system settings, compressor
settings, indoor fan settings, ESP settings, communication settings, teamwork settings, time settings, display settings,
parameter recovery, password settings, and data logging settings.

Alarm Setpoint
You can set parameters such as supply air high temperature, supply air low temperature, return air high temperature, return
air low temperature, and return air high humidity.

Figure 4.17 Alarm Setpoint

4 Display Screen Operation 57

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

NOTE: It is not recommended to change the default values for alarm parameters. If necessary, operate under the
guidance of a trained professional.

Alarm Attribute
You can set enable or disable for the properties of the alarm such as the supply air high temperature alarm, supply air low
temperature alarm, return air high temperature alarm, and return air high humidity alarm.

Figure 4.18 Alarm Attribute

System Setting
You can set the heating function, humidification function, and dehumidification function.

Figure 4.19 System Setting

58 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Compressor Setting
You can set the compressor control mode and the compressor proportional band.

Figure 4.20 Compressor Setting

Indoor Fan Setting


You can set the indoor fan control mode, indoor fan proportional band, the minimum speed, the maximum speed, and the
rated speed of the indoor fan.

4 Display Screen Operation 59

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 4.21 Indoor Fan Setting

ESP Setting
Figure 4.22 ESP Setting

60 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Communication Setting
Figure 4.23 Communication Setting

Teamwork Setting
Figure 4.24 Teamwork Setting

4 Display Screen Operation 61

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Time Setting
Figure 4.25 Time Setting

Display Settings
Figure 4.26 Display Settings

62 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Parameter Reset
Figure 4.27 Parameter Reset

Password Setting
Figure 4.28 Password Setting

4 Display Screen Operation 63

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Data Record Setting


Figure 4.29 Data Record Setting

4.4.6 Temperature and Humidity Curve


Select Temperature and Humidity Curve under the main menu to view the curve of return air temperature, return air
humidity, supply air temperature, and average air supply humidity of 0 to 48 hours.

Figure 4.30 Temperature and Humidity Curve

4.4.7 Version Information


You can see the hardware and software version numbers.

64 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 4.31 Version Information

4 Display Screen Operation 65

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

This page intentionally left blank

66 4 Display Screen Operation

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

5 Control Logic
The unit operation is fully automated, calculated and controlled by the microprocessor controller according to the user's
setpoint.

5.1 Cooling
5.1.1 Control Mode
The fan and compressor of CRV4 have different control modes according to application scenarios. A total of 11 combination
modes are available.

Table 5.1 Control Mode


Compressor
Supply air Remote Return air
Fan

Supply air √ - -

Remote √ √ -

Return air √ √ √

Air pressure √ √ √

Temperature difference √ √ -

5.1.2 Temperature Algorithm


Cooling requirement of fan and condenser is calculated according to the PID algorithm.

Figure 5.1 Temperature Proportional Band

PID algorithm with limit value:

is a proportional requirement

Proportional cooling requirement

Heating ratio requirements

5 Control Logic 67

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Where:

is the temperature control output (with limit) at the time of the first sample.

is the P action at the time of the first sampling (with limit).

is the I action at the time of the first sampling (with limit).

is the D action at the time of the first sampling (with limit).

is the temperature deviation rate at the time of the first sample.

is the temperature deviation rate at the time of the first sample.

is the temperature integration time parameter.

is the temperature differential time parameter.

is the sampling period. It is 1 second.

5.1.3 Compressor Control


Compressor Start and Stop
The starting and stopping points of the compressor are calculated proportionally according to the control mode selected
by the compressor.

After the unit is turned on and the fan is operating normally for 10s, the compressor is turned on according to demand.

The compressor performs a soft start at start-up, gradually ramps up to a preset speed, and completes the entire start-up
process, followed by dynamic output according to the current cooling demand.

When the unit has dehumidification needs, the compressor will increase the output on top of the current output.

When the compressor is turned off normally, it performs a soft shutdown, and it is turned off after gradually reducing to the
preset speed. The compressor will be turned off directly when a shutdown alarm is generated.

The start and stop of the compressor needs to meet the minimum operation and downtime.

Special Control of the Compressor


During operation, the compressor is limited by special controls such as high and low pressure regulation to ensure reliable
operation of the system.

68 5 Control Logic

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

5.1.4 Fan Control


Fan Start and Stop
After the unit is started, the fan will remain in operation and output proportionally according to the demand calculated by
cooling, humidification, or heating.

When the unit is running alone, the fan shuts down if the compressor is locked or the unit is shut down.

When the unit is in group control, the fan is turned off when the standby unit or compressor is locked.

Special Control of the Fan


When the fan is running, it is limited by the suction pressure of the unit.

On the one hand, the suction pressure is not too high and exceeds the operating range of the compressor; on the other hand,
the suction pressure is not too low, and the heat exchanger is not frozen.

5.1.5 Electronic Expansion Valve Control


The electronic expansion valve is automatically controlled by the controller according to the superheat set by the unit, and
it will be opened in advance before the compressor is opened to balance the differential pressure on the high- and low-
pressure sides.

The electronic expansion valve has a MOP function that limits the evaporation pressure of the unit to below the preset value.

5.1.6 High Temperature Regulation


When the supply air or return air temperature is too high, the unit enters the high temperature adjustment mode.

After entering the high temperature adjustment mode, the speed demand output of the fan and compressor uses the high
temperature demand of the supply air or the high temperature demand of the return air, whichever is greater, as the output.
The speed of the fan and compressor is linear between the rated speed and the maximum speed.

When the average humidity of the return air is invalid or the average humidity of the return air is ≥ 60%, the high
temperature adjustment is prohibited, and the return air humidity is effective, and the average humidity of the return air is ≤
50%.

5.2 Humidity Control


5.2.1 Humidity Algorithm
The humidity set point is the supply air humidity.

The controller calculates the dew point temperature according to the return air temperature and humidity detection value,
calculates the theoretical supply air humidity from the dew point temperature and the supply air temperature set value, and
calculates the current supply air humidity from the dew point temperature and the current supply air temperature.

The panel shows the theoretical supply air humidity. The humidity demand is also calculated using the theoretical supply
air humidity.

5 Control Logic 69

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Figure 5.2 Humidity Proportional Band

5.2.2 Dehumidification Control


When the compressor is in operation, the unit determines whether it needs to enter the dehumidification mode according to
the dehumidification demand.

If the compressor is in a shutdown state, the need for dehumidification cannot cause the compressor to start.

Every 24 hours, the dehumidification mode has a limited operating time, after which it can no longer enter the
dehumidification mode.

Dehumidification mode may trigger electric heating to turn on for temperature compensation.

If the temperature of the dehumidification mold is too low, the unit will automatically exit the dehumidification mode.

5.2.3 Humidification Control


The unit determines whether it needs to enter humidification mode according to the humidification demand.

When the actual supply air humidity is already high, the unit will automatically exit the humidification mode.

70 5 Control Logic

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

5.3 Heating
5.3.1 Dehumidification Temperature Compensation
After the unit enters the dehumidification mode, the output of the compressor is additionally greater than the current
cooling demand, and if the temperature is too low (supply air or return air temperature, depending on the control mode), the
electric heating will be turned on for temperature compensation.

When the dehumidification mode ends or is aborted, the temperature compensation is stopped.

5.3.2 Separate Heating


When the unit stops refrigeration and the ambient temperature is still particularly low, the electric heating will be turned on
separately to increase the temperature.

5.4 Oil Return Operation


When the heat load of the unit is low, the compressor will run at a low speed, which may cause difficulty in the compressor
oil return, so the unit will start the oil return operation.

When the compressor runs at a low speed for a certain period of time (oil return cycle), the unit will enter the oil return
operation mode, the compressor rises to the preset oil return speed operation. After reaching the oil return running time, the
compressor exits the oil return operation mode.

5.5 Condensate Pump Control


Under normal operating conditions, the condensate pump is controlled by a water level switch (water level detection plate)
in the water pan.

The unit is also equipped with a high-water level switch. When a high water level alarm is detected, even if the water level
switch does not operate, the unit will also turn on the condensate pump.

5.6 Shutdown Mode


5.6.1 Shutdown Types
The shutdown mode is divided into panel shutdown, monitoring shutdown, and remote shutdown.

Panel shutdown refers to the display board switch key setting.

Monitoring shutdown refers to communication shutdown through background monitoring.

Remote shutdown refers to the shutdown enable of the corresponding switch input.

5.6.2 Shutdown Logic


Panel shutdown, monitoring shutdown, remote shutdown are series relationships. Either one causes unit shutdown, and three
startups causes unit startup.

Display board setting can set the panel shutdown and the monitoring shutdown to power-on.

In the presence of multiple shutdowns, the priority displayed is: remote shutdown→ panel shutdown→ monitoring
shutdown.

5 Control Logic 71

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

The power-on and -off state is saved when the unit is powered down.

5.7 Teamwork Control


5.7.1 Teamwork Control Parameter
Table 5.2 Teamwork Primary Unit Parameter
Parameter Default value Lower limit Upper limit Password level Note

Teamwork mode 0 0 2 2 -

Unit quantity 1 1 16 2 -

Standby quantity 0 0 Unit quantity-1 2 -

Polling cycle 0 0 8 2

Polling at 12:00 0:00 2:00 2 -

Polly quantity 0 0 The smaller value of operating unit quantity and standby unit quantitiy 2 -

Table 5.3 Teamwork Secondary Unit Parameter


Parameter Default value Lower limit Upper limit Password level Note

Unit address 1 0 15 2 -

NOTE: Group control mode: 0: standalone; 1: teamwork control of air conditioning unit; 2: RDU-A energy-saving
teamwork control.

NOTE: Polling period: 0: none; 1: Daily; 2: Monday; 3: Tuesday; 4: Wednesday; 5: Thursday; 6: Friday; 7: Saturday; 8:
Sunday. Set to 0 to disable the polling function.

5.7.2 Typical Standby Features


One or several units can be set as standby, and the usual state of standby is shutdown (wind turbine).

Standby functions rotate on a daily basis (time can be set). Rotations are performed by an optional number. For example, in
the case of 4 units and 2 standby units, if the number of rotations is 1, the order of standby rotations is from 1-2 to 2-3 to 3-4.
If the number of rotations is 2, the alternate rotation sequence is 1-2 to 3-4.

If a certain operating unit in the group cannot be contacted or after the compressor locks or the high temperature alarm or
temperature sensor fails, a standby unit will be started, and all standby units will be started.

72 5 Control Logic

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

5.8 Alarm Logic


Table 5.4 Alarm Logic
No. Alarm name Conditions Action Clearance conditions Settings

The high-voltage sensor detects a


value greater than the alarm value, The exhaust pressure is
High voltage reaching the alarm delay time. The alarm is triggered and the less than 30 bar, reaching Allow/Abort
1
alarm compressor shuts down the alarm detection delay (default: Allow)
High voltage switch alarm value: 39bar
time
Sensor alarm value: 40 bar

The suction pressure is lower than the The exhaust pressure is


Low voltage alarm value, reaching the alarm The alarm is triggered and the higher than 5.5 bar, Allow/Abort
2 detection delay time.
alarm compressor shuts down reaching the alarm (default: Allow)
Sensor alarm value: 4.5 bar detection delay time

When the compressor is running, there The alarm is forcibly


High voltage The alarm is triggered. It is handled Allow/Abort/Close
3 are three times of abnormal high- cleared after 1h or when
abnormal alarm as high-voltage abnormal (default: Allow)
pressure adjustment within 1h the compressor is stopped

The exhaust temperature


is lower than the exhaust
When the compressor is running, the high temperature alarm
Exhaust high
discharge temperature is higher than The alarm is triggered and the value minus the return Allow/Abort
4 temperature
110°C, reaching the alarm detection compressor shuts down difference, reaching the (default: Allow)
alarm
delay time alarm detection delay time
or the corresponding
sensor fails

When the compressor is running, the


The alarm is automatically
Low exhaust exhaust superheat is below 10°C, The alarm is triggered and the Allow/Abort
5 cleared 30s after the
overheat alarm reaching the alarm detection delay compressor shuts down (default: Allow)
compressor shuts down
time

The maximum
temperature of the return
The maximum temperature of the
Return air high air is invalid or lower than
return air is effective and higher than Allow/Abort/Close
6 temperature The alarm is triggered the alarm value minus the
the alarm value, reaching the alarm (default: Allow)
alarm return difference, reaching
detection delay time
the alarm detection delay
time

The minimum temperature


The minimum temperature of the of the return air is invalid or
Return air low
return air is effective and lower than the higher than the alarm value Allow/Abort/Close
7 temperature The alarm is triggered
alarm value, reaching the alarm plus the return difference, (default: Close)
alarm
detection delay time reaching the alarm
detection delay time

The minimum temperature


The minimum temperature of the of the supply air is invalid or
Supply air low
supply air is effective and lower than The alarm is triggered. The cooling higher than the alarm Allow/Abort/Close
8 temperature
the alarm value, reaching the alarm function is stopped value plus the return (default: Allow)
alarm
detection delay time difference, reaching the
alarm detection delay time

5 Control Logic 73

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

The maximum
temperature of the supply
The maximum supply air temperature
Supply air high air is invalid or lower than
is effective and higher than the alarm Allow/Abort/Close
9 temperature The alarm is triggered the alarm value minus the
value, reaching the alarm detection (default: Allow)
alarm return difference, reaching
delay time
the alarm detection delay
time

The maximum humidity of


After the fan is turned on for 5 minutes,
the return air is invalid or
the maximum humidity of the return air
Return air high lower than the alarm value Allow/Abort/Close
10 is effective and higher than the alarm The alarm is triggered
humidity alarm minus the return (default: Allow)
value, reaching the alarm detection
difference, reaching the
delay time
alarm detection delay time

The minimum humidity of


After the fan is turned on for 5 minutes,
the return air is invalid or
the minimum humidity of the return air
Return air low higher than the alarm value Allow/Abort/Close
11 is effective and lower than the alarm The alarm is triggered
humidity alarm plus the return difference, (default: Allow)
value, reaching the alarm detection
reaching the alarm
delay time
detection delay time

The remote maximum


After the fan is turned on for 15 minutes,
temperature is invalid or
Remote high the remote maximum temperature is
lower than the alarm value Allow/Abort/Close
12 temperature effective and higher than the alarm The alarm is triggered
minus the return (default: Allow)
alarm value, reaching the alarm detection
difference, reaching the
delay time
alarm detection delay time

The remote minimum


After the compressor soft start is
temperature is invalid or
Remote low completed, the remote minimum
higher than the alarm value Allow/Abort/Close
13 temperature effective and lower than the alarm The alarm is triggered
plus the return difference, (default: Allow)
alarm value reaches the alarm detection
reaching the alarm
delay time
detection delay time

The remote maximum


After the fan is turned on for 15 minutes,
humidity is invalid or lower
the remote maximum humidity is
Remote high than the alarm value minus Allow/Abort/Close
14 effective and higher than the alarm The alarm is triggered
humidity alarm the return difference, (default: Allow)
value, reaching the alarm detection
reaching the alarm
delay time
detection delay time

The remote minimum


After the fan is turned on for 15 minutes,
humidity is invalid or higher
the remote minimum humidity is
Remote low than the alarm value plus Allow/Abort/Close
15 effective and below the alarm value, The alarm is triggered
humidity alarm the return difference, (default: Allow)
reaching the alarm detection delay
reaching the alarm
time
detection delay time

3 high-voltage alarms in 1 hour or high-


High voltage The alarm is triggered and The unit is powered on and Allow/Abort
16 voltage alarms without reset within 10
lock alarm thecompressor is locked reset (default: Allow)
minutes

3 low voltage alarms in 1 hour or low


Low voltage The alarm is triggered and The unit is powered on and Allow/Abort
17 voltage alarms without reset within 10
lock alarm thecompressor is locked reset (default: Allow)
minutes

74 5 Control Logic

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

Exhaust high
3 times exhaust high temperature The alarm is triggered and The unit is powered on and Allow/Abort
18 temperature
alarm within 24 hours thecompressor is locked reset (default: Allow)
lock alarm

Low exhaust
Three exhaust low temperature alarms The alarm is triggered and The unit is powered on and Allow/Abort
19 superheat lock
occur within 1 hour thecompressor is locked reset (default: Allow)
alarm

The alarm is triggered. There are


three ways to handle it and user can
Floor overflow The floor overflow switch is Allow/Abort/Close
20 The floor overflow opens and closes choose from: 1: alarm only, 2: stop
alarm disconnected (default: Allow)
humidification, dehumidification, 3:
shut down. The default is 2

The alarm is triggered and


High water The high water switch is Allow/Abort
21 High water switch closes humidification or dehumidification is
level alarm open (default: Allow)
stopped

Any of the following is met:


• The unit operates when
the airflow returns to
normal
The alarm is triggered and all
Airflow loss When the fan is operating normally, no • The fan is turned off Allow/Abort
22 equipment outside the fan
alarm airflow passes through the unit (default: Allow)
(excluding drain pump) is stopped • The airflow is lost,
detecting the temperature
sensor failure
• The return air
temperature sensor fails

The remote shutdown


Remote The remote shutdown switch does not The alarm is triggered and the Allow/Abort/Close
23 switch matches the set
shutdown alarm match the setting polarity system shuts down (default: Allow)
polarity

Return air The return air temperature


The return air temperature {n} exceeds
temperature {n} meets the detectable Allow/Abort/Close
24 the detectable range, reaching the The alarm is triggered
sensor {n} range and reaches the (default: Allow)
alarm detection delay time
failure alarm detection delay time

The return air humidity {n}


Return air The return air humidity {n} exceeds the
reaches the alarm Allow/Abort/Close
25 humidity sensor detectable range, reaching the alarm The alarm is triggered
detection delay time within (default: Allow)
{n} failure detection delay time
the detection range

Supply air The supply air temperature


The supply air temperature sensor {n}
temperature {n} reaches the alarm Allow/Abort/Close
26 exceeds the detectable range, reaching The alarm is triggered
sensor {n} detection delay time within (default: Allow)
the alarm detection delay time
failure the detection range

The supply air humidity {n}


Supply air The supply air humidity {n} exceeds
reaches the alarm Allow/Abort/Close
27 humidity sensor the detection range, reaching the alarm The alarm is triggered
detection delay time within (default: Allow)
{n} failure detection delay time
the detection range

Remote The remote temperature


The remote temperature {n} exceeds
temperature {n} reaches the alarm Allow/Abort/Close
28 the detection range, reaching the alarm The alarm is triggered
sensor {n} detection delay time in the (default: Allow)
detection delay time
failure detection range

5 Control Logic 75

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

Remote humidity {n}


Remote The remote humidity {n} exceeds the
reaches the alarm Allow/Abort/Close
29 humidity sensor detection range, reaching the alarm The alarm is triggered
detection delay time in the (default: Allow)
{n} failure detection delay time
detection range

High-pressure The high pressure exceeds the The alarm is triggered and MBV The high pressure reaches
Allow/Abort
30 pressure sensor detectable range, reaching the alarm opening is 100%, limiting access to the alarm detection delay
(default: Allow)
failure detection delay time the high-voltage restriction area time in the detection range

The electric heating fault


Electric heating Electric heating fault dry node alarm The alarm is triggered and the Allow/Abort/Close
31 stem node does not
fault alarm action electric heating is turned off (default: Allow)
perform the alarm action

The exhaust gas


Exhaust The exhaust temperature exceeds the
The alarm is triggered and the temperature reaches the Allow/Abort
32 temperature detectable range, reaching the alarm
compressor is forced to shut down alarm detection delay time (default: Allow)
sensor failure detection delay time
in the detection range

When the compressor


contactor is closed and the
When the compressor contactor is auxiliary normally-closed
The alarm is triggered and if an
Compressor closed and the auxiliary normally- contact is disconnected,
alarm that needs to shut down the
drive closed contact is disconnected, the the communication Allow/Abort
33 compressor occurs at the same
communication main control board and the compressor between the main control (default: Allow)
time, the compressor locks and
failure drive board lose communication for 10 board and the compressor
shuts down
seconds drive board normally
reaches the alarm
detection delay time

Compressor
The unit is powerd on or the
drive The compressor drive communication The alarm is triggered, and the Allow/Abort
34 alarm is cleared on the
communication failure lasts for 2 hours compressor locks and shuts down (default: Allow)
panel
fault lockout

Any of the following is met:


• Compressor contactor is
CP driver disconnected
The communication reads that the
protection U01 • The compressor
compression inverter hardware The alarm is triggered and the Allow/Abort
35 (inverter communication failure is
overcurrent fault reaches the alarm compressor shuts down immediately (default: Allow)
hardware detected
detection delay time
overcurrent)
• This compression
inverter hardware
overcurrent fault is cleared

Any of the following is met:


• Compressor contactor is
CP drive disconnected
The communication reads that the
protection U02
output of the compressor with a phase The alarm is triggered and the • The compressor Allow/Abort
36 (compressor
loss fault reaches the alarm detection compressor shuts down immediately communication failure is (default: Allow)
output phase
delay time detected
loss)
• Th compressor output
phase loss fault is cleared

The communication reads that the The alarm is triggered, the Any of the following is met:
CP overcurrent Allow/Abort
37 compressor overcurrent fault reaches compressor shuts down, and EEV is • Compressor contactor is (default: Allow)
reminder
the alarm detection delay time turned on to CP overcurrent opening disconnected

76 5 Control Logic

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

• The compressor
communication failure is
detected
• The compressor
overcurrent fault is cleared

Any of the following is met:


• Compressor contactor is
CP drive Three CP overcurrent reminders are The alarm is triggered, the disconnected
protection U03 generated in one hour or once for 30s, compressor shuts down • The compressor Allow/Abort
38
(compressor reaching the alarm detection delay immediately, and EEV is turned on to communication failure is (default: Allow)
overcurrent) time CP overcurrent opening detected
• The compressor
overcurrent fault is cleared

Any of the following is met:


• Compressor contactor is
disconnected
CP Drive
The communication reads that the • The compressor
protection U04 The alarm is triggered and the Allow/Abort
39 input voltage phase loss fault reaches communication failure is
(input voltage compressor shuts down immediately (default: Allow)
the alarm detection delay time detected
phase out)
• The compressor input
voltage phase loss fault is
cleared

Any of the following is met:


• Compressor contactor is
disconnected
CP drive
The communication reads that the • The compressor
protection U05 The alarm is triggered and the Allow/Abort
40 voltage imbalance fault of this bus communication failure is
(bus voltage compressor shuts down immediately (default: Allow)
reaches the alarm detection delay time detected
unbalance)
• The compressor bus
voltage imbalance fault is
cleared

Any of the following is met:


• Compressor contactor is
CP drive disconnected
protection U06 The communication reads that the
(power overheating shutdown fault of this The alarm is triggered and the • The compressor Allow/Abort
41 communication failure is
component power component reaches the alarm compressor shuts down immediately (default: Allow)
overheating detection delay time detected
shutdown) • The compressor power
overheating shutdown fault
is cleared

Any of the following is met:


CP drive • Compressor contactor is
The communication reads that the
protection U07 The alarm is triggered and the disconnected Allow/Abort
42 motor stall fault reaches the alarm
(motor stand compressor shuts down immediately (default: Allow)
detection delay time • The compressor
rotation)
communication failure is
detected

5 Control Logic 77

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

• The compressor stall


fault is cleared

Any of the following is met:

The compressor contactor is closed • Compressor contactor is


CP drive and the time from the last contactor disconnected
protection U08 disconnection exceeds 120s, and the The alarm is triggered and the • The compressor Allow/Abort
43
(DC junction communication reads that the compressor shuts down immediately communication failure is (default: Allow)
overvoltage) compressor DC bus overvoltage fault detected
reaches the alarm detection delay time
• The compressor DC bus
overvoltage fault is cleared

Any of the following is met:


• Compressor contactor is
The compressor contactor is closed disconnected
CP drive and the time from the last contactor
protection U09 disconnection is more than 120s, and The alarm is triggered and the • The compressor Allow/Abort
44 communication failure is
(DC link the communication reads that the compressor shuts down immediately (default: Allow)
undervoltage) compressor DC bus undervoltage fault detected
reaches the alarm detection delay time • The compressor DC bus
undervoltage fault is
cleared

Any of the following is met:


• Compressor contactor is
disconnected
CP drive
The communication reads that the AC • The compressor
protection U10 The alarm is triggered and the Allow/Abort
45 input overvoltage fault reaches the communication failure is
(AC input compressor shuts down immediately (default: Allow)
alarm detection delay time detected
overvoltage)
• The compressor AC
input overvoltage fault is
cleared

• Compressor contactor is
disconnected
CP driver • The compressor
The communication reads that the AC
protection U11 The alarm is triggered and the communication failure is Allow/Abort
46 input undervoltage fault reaches the
(AC input compressor shuts down immediately detected (default: Allow)
alarm detection delay time
undervoltage)
• The compressor AC
input undervoltage fault is
cleared

CP drive
Allow/Abort
47 protection U12 Reserverd Reserverd Reserverd
(default: Allow)
(NA)

Any of the following is met:


• Compressor contactor is
CP drive The communication reads that the
The alarm is triggered and the disconnected Allow/Abort
48 protection U13 temperature sensor fault reaches the
compressor shuts down immediately (default: Allow)
(other faults) alarm detection delay time • The compressor
communication failure is
detected

78 5 Control Logic

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

• The temperature sensor


fault is cleared

Any of the following is met:


• Compressor contactor is
CP drive disconnected
The communication reads that the
protection U14 The alarm is triggered and the • The compressor Allow/Abort
49 temperature sensor fault reaches the
(temperature compressor shuts down immediately communication failure is (default: Allow)
alarm detection delay time
sensor fault) detected
• The temperature sensor
fault is cleared

Any of the following is met:


• Compressor contactor is
CP drive disconnected
The communication reads that the
protection U15 The alarm is triggered and the Allow/Abort
50 drive fan failure reaches the alarm • The compressor
(drive fan compressor shuts down immediately (default: Allow)
detection delay time communication failure is
failure)
detected
• The fan fault is cleared

Any of the following is met:


• Compressor contactor is
CP driver disconnected
protection U16
The communication reads that the • The compressor
(abnormal The alarm is triggered and the Allow/Abort
51 abnormal fault with the motherboard communication failure is
communication compressor shuts down immediately (default: Allow)
reaches the alarm detection delay time detected
with
motherboard) • The abnormal
communication with the
motherboard is cleared

Any of the CP drive protection U01 to


The unit is powerd on or the
U16 alarm is generated 3 times within 2 The alarm is triggered, and the Allow/Abort
52 CP drive lock alarm is cleared on the
hours, or once for 10 minutes, or 3 times compressor locks and shuts down (default: Allow)
panel
within 2 hours

The communication between the main The main control board


EEV The alarm is triggered and the
control board and the electronic communicates with the Allow/Abort
53 communication compressor shuts down
expansion valve is interrupted for 20 electronic expansion valve (default: Allow)
failure immediately.
seconds normally

The communication reads that the EEV


EEV drive communication
EEV drive driver 1 fault (parameter failure, An alarm is triggered and the Allow/Abort
54 fails or the EEV drive fault is
failure equipment failure) reaches the alarm compressor shuts down immediately (default: Allow)
cleared
detection delay time

Low pressure
The number of low-voltage sensor The alarm is triggered and the The unit is powerd on and Allow/Abort
55 sensor fault
failures in 1 hour reaches 3 times compressor is locked reset (default: Allow)
lockout

5 Control Logic 79

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

The alarm is triggered.


Humidification, dehumidification,
and heating is stopped. The fan
Fan detecting
outputs at rated speed under high
the The main control board and 10DI
temperature, cooling, humidification The main control board Allow/Abort
56 communication communication interruption reached
or heating regulation. The receives 10DI data (default: Allow)
fault of the 10s
compressor output outputs
board
according to demand, and the
compressor demand speed ≤ the
rated speed of the compressor

Any of the following is met:


• After the equipment startup delays,
the fan {n} fault alarm switch is
The alarm is triggered. The unit is
inconsistent with the set polarity, The alarm is not eliminated
cooling only (humidification,
reaching the alarm detection delay when the shutdown is
Fan {n} fault dehumidification, and heating are Allow/Abort
57 time stopped, and the alarm is
alarm stopped). The compressor shuts (default: Allow)
eliminated if handling is
• After the equipment startup delays, down immediately when the unit is
cooling
the fan {n} feedback frequency is less turned off
than 80% of the standard value,
reaching the alarm detection delay
time

Any of the following is met:


• The humidifier type is
none
Electrode humidifier: • The humidification type
Humidifier Electrode humidifier: the alarm is is wet film humidification Allow/Abort/Close
58 The humidifier fault switch closes,
failure alarm reaching the alarm detection delay triggered • When the humidification (default: Allow)
time type is electrode
humidification, the
humidifier fault switch is
turned off, reaching the
alarm detection delay time

The smoke sensor switch


The smoke sensor switch is inconsistent
matches the set polarity, Allow/Abort/Close
59 Smoke alarm with the set polarity, achieving alarm The alarm is triggered
reaching the alarm (default: Allow)
detection delay time
detection delay time

The fire sensor switch is


The polarity of the fire sensor switch is
The alarm is triggered and all consistent with the set Allow/Abort/Close
60 Fire alarm inconsistent with the setting, reaching
devices shut down immediately polarity, reaching the alarm (default: Allow)
the alarm detection delay time
detection delay time

The lightning protection


The lightning protection sensor switch is
sensor switch is consistent
inconsistent with the polarity of the Allow/Abort/Close
61 Lightning alarm The alarm is triggered with the setting model,
setting, reaching the alarm detection (default: Allow)
reaching the alarm
delay time
detection delay time

Custom 1 switch matches


Custom 1 switch is inconsistent with the
the set polarity, reaching Allow/Abort/Close
62 Custom 1 alarm set polarity reaching the alarm The alarm is triggered
the alarm detection delay (default: Allow)
detection delay time
time

80 5 Control Logic

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

Custom 2 switches match


Custom 2 switches are inconsistent with
Custom 2 the set polarity, reaching Allow/Abort/Close
63 the set polarity reaching the alarm The alarm is triggered
alarms the alarm detection delay (default: Allow)
detection delay time
time

The wind pressure {n}


Wind pressure The wind pressure {n} exceeds the
reaches the alarm Allow/Abort/Close
64 sensor {n} detection range, achieving the alarm The alarm is triggered
detection delay time in the (default: Allow)
failure detection delay time
detection range

The EEV driver


Faulty suction The main control board communicates communication fails
The alarm is triggered and the Allow/Abort
65 temperature with the electronic expansion valve and
compressor shuts down immediately It reads that the EEV fault is (default: Allow)
sensor reads this alarm
cleared

The main control board communicates


with the electronic expansion valve Any of the following is met:
normally. The second stage of the • Communication failure
compressor soft start is completed and
Low pressure The alarm is triggered and the • It reads that there is no Allow/Abort
66 exceeds the low pressure alarm start
sensor failure compressor shuts down immediately this alarm (default: Allow)
delay, and is not in the soft shutdown
state. The alarm is read or the pressure • The pressure value is
read exceeds the normal range. The within range
alarm is shielded in vacuum mode

The alarm is cleared


Power loss The unit is in operational condition, and Allow/Abort/Close
67 The alarm is triggered automatically after 10
alarm the power is lost and then restored (default: Allow)
seconds

Power supply The power input returns to


The alarm is triggered and all Allow/Abort/Close
68 phase loss The power input is out of phase normal, reaching the alarm
devices shut down immediately (default: Allow)
alarm detection delay time

The power input is lower


The power supply input voltage is
Power supply than the overvoltage alarm
higher than the overvoltage alarm The alarm is triggered and all Allow/Abort/Close
69 overvoltage value minus the return
value, reaching the alarm detection devices shut down immediately (default: Allow)
alarm difference, reaching the
delay time.
alarm detection delay time

The power supply is out of


When the power supply is not out of phase or the power input is
Power supply phase, the input voltage of the power higher than the
The alarm is triggered and all Allow/Abort/Close
70 undervoltage supply is lower than the undervoltage undervoltage alarm value
devices shut down immediately (default: Allow)
alarm alarm value, reaching the alarm plus the return difference,
detection delay time reaching the alarm
detection delay time

When the power supply is not out of


Power supply Power supply offset
phase, the power supply frequency The alarm is triggered and all Allow/Abort/Close
71 frequency recovery reaches alarm
offset reaches the alarm detection devices shut down immediately (default: Allow)
offset alarm detection delay time
delay time

When the power supply is not out of


Power supply inverting
Power supply phase, the power supply is inverted, The alarm is triggered and all Allow/Abort/Close
72 recovery reaches alarm
inverting alarm reaching the alarm detection delay devices shut down immediately (default: Close)
detection delay time
time

5 Control Logic 81

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Table 5.4 Alarm Logic (continued)


No. Alarm name Conditions Action Clearance conditions Settings

Duplicate The unit does not receive


teamwork The unit receives a data frame with the The alarm is triggered and all the same data frame as its Allow/Abort
73
control same address as itself devices shut down immediately own address again within (default: Allow)
addresses 60s

In teamwork control mode, the The alarm is triggered and the


Teamwork The secondary unit Allow/Abort
74 secondary unit does not receive data secondary unit operates in stand-
control host lost receives the host data (default: Allow)
from the host within 60 seconds alone mode

Teamwork
In teamwork control mode, the host The alarm is triggered and the host
control The secondary unit Allow/Abort
75 does not receive data from a secondary does not calculate the data of the
secondary unit receives the host data (default: Allow)
unit within 60 seconds secondary unit
lost

Any of the following is met:


• The fan closes, reaching
After the fan is started for 60s, the filter the alarm detection delay
Filter blockage Allow/Abort/Close
76 is opened and closed, reaching the The alarm is triggered and time
alarm (default: Allow)
alarm detection delay time
• The filter switch is
disconnected, reaching the
alarm detection delay time

Manually set the running


Filter
The filter running time reaches the filter time of the filter to clear Allow/Abort/Close
77 maintenance The alarm is triggered and
maintenance reminder value the filter, and the alarm is (default: Allow)
reminder
released

82 5 Control Logic

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Appendix A: Display Screen Menu Structure


Level 1 Menu Level 2 Menu Parameter

Theo Supply Hum, Current Supply Hum, Supply Temp Avg, Supply Temp1, Supply Temp2, Supply Temp3, Supply Hum1,
Temp/Hum Supply Hum2, Supply Hum3, Return Temp Avg, Return Temp1, Return Temp2, Return Temp3, Remote Temp Avg,
Information Remote Temp1, Remote Temp2, …, Remote Temp10, Remote Hum Avg, Remote Hum1, Remote Hum2, …, Remote
Hum10

ESP Information Unit ESP Avg, Unit ESP1, Unit ESP2

High Pressure Switch, Remote Shutdown Switch, Water Underfloor Switch, Heater Fail Switch, Humidifier Fail Switch, Cond
Run
Water Level Switch, Cond WOF Switch, Filter Clogged Switch, Custom1 Switch, Custom2 Switch, Dual Power Switch, Comp
Information Switch Status
Output, Indoor Fan1 Output, Indoor Fan2 Output, Outdoor Fan Output, Heater Output, Humidifier Output, Cond Pump
Output, LLSV Output, MBV Output, Spray Output, General Alarm Output

Power Phase A Voltage, Phase B Voltage, Phase C Voltage, Power Frequency, Phase A Current, Phase B Current, Phase C
Information Current, Phase A Power, Phase B Power, Phase C Power, Total Power, Total Active Energy

Teamwork
#00 Unit Status, #01 Unit Status, #02 Unit Status, ..., #15 Unit Status
Information

Alarm Status

Alarm Alarm History


Information
Comp Driver
Alarm

Temp/Hum Temp Setting Return Temp SP, Supply Temp SP, Remote Temp SP, Delta Temp SP
Setting Hum Setting Supply Hum SP, Hum Prop Band

83

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Level 1 Menu Level 2 Menu Parameter

Sup High Temp Alarm SP, Sup Low Temp Alarm SP, Rtn High Temp Alarm SP, Rtn Low Temp Alarm SP, Rtn High Hum
Alarm Setpoint Alarm SP, Rtn Low Hum Alarm SP, Rem High Temp Alarm SP, Rem Low Temp Alarm SP, Rem High Hum Alarm SP, Rem
Low Hum Alarm SP, Filter Maintenance Cycle, Wet Film Maintenance Cycle

Supply High Temp Alarm, Supply Low Temp Alarm, Return High Temp Alarm, Return Low Temp Alarm, Return High Hum
Alarm Attribute Alarm, Return Low Hum Alarm, Remote High Temp Alarm, Remote Low Temp Alarm, Remote High Hum Alarm, Remote
Low Hum Alarm

System Setting Heating Function, Humidifying Function, Dehumidifying Function

Compressor
Comp Control Mode, Comp Prop Band
Setting

Indoor Fan Indoor Fan Control Mode, Indoor Fan Prop Band, Indoor Fan Minimum Speed, Indoor Fan Standard Speed, Indoor Fan
Setting Maximum Speed

Humidifier
Humidifying Function, Humidifier Type, Wet Film First Fill Time, Wet Film Fill Time, Wet Film Fill Interval
Parameter Setting
Setting
ESP Setting ESP Setpoint

Communication
Monitor Protocol, Monitor Baudrate, Monitor Address
Setting

Teamwork Teamwork Mode, Units Quantity, Unit Address, Standby Quantity, Rotation Quantity, Rotate Daily,
Setting Rotation Cycle, Rotate At, Run Standby Delay, Manual Rotate

Time Setting Date Setting, Time Setting

Display Setting Display Language, Display Address

Parameter
Wet Film Maintenance Confirm, Filter Maintenance Confirm
Reset

Password
Level 1 Password, Level 2 Password, Deployment Startup Password, Deployment Required Password
Setting

Parameter Data Record


DataRecord Enable, DataRecord Cycle, DataRecord Interval
Setting Setting

Rtn Temp Avg

Rtn Hum Avg


Temp/Hum
Sup Temp Avg
Graph
Rem Temp Avg

Control
Software Model

Control
Software
Version
About
Display
Software Model

Display
Software
Version

84

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Appendix B: Alarm
High Pressure Alarm Smoke Alarm Remote Hum Sensor7 Failure Power Undervoltage

Low Pressure Alarm Fire Alarm Remote Hum Sensor8 Failure Power Freq Offset

Discharge High Temp Alarm SPD Failure Remote Hum Sensor9 Failure Power Phase Reverse

Discharge Low SH Alarm Remote Shutdown Alarm Remote Hum Sensor10 Failure Unit Address Repeat

High Pressure Lock Water Underfloor Alarm Airflow Temp Sensor Failure Primary Unit Loss

Low Pressure Lock Custom1 Alarm High Pressure Sensor Failure Secondary Unit Loss

Discharge High Temp Lock Custom2 Alarm Dsch Temp Sensor Failure Filter Maintenance

Discharge Low SH Lock Supply Temp Sensor1 Failure ESP Sensor1 Failure Filter Clogged Alarm

HP Abnormal Alarm Supply Temp Sensor2 Failure ESP Sensor2 Failure Secondary Power Feed Supply

LP Sensor Lock Supply Temp Sensor3 Failure Comp Driver Comm Failure Outdoor Fan Comm Failure

Supply High Temp Alarm Supply Hum Sensor1 Failure Comp Driver Comm Lock Outdoor Fan System Alarm

Supply Low Temp Alarm Supply Hum Sensor2 Failure Comp Driver Protect U01 Spray Comm Failure

Remote High Temp Alarm Supply Hum Sensor3 Failure Comp Driver Protect U02 Spray High Pressure Failure

Remote Low Temp Alarm Return Temp Sensor1 Failure Comp Driver Protect U03 Spray High Pressure Failure Lock

Remote High Hum Alarm Return Temp Sensor2 Failure Comp Driver Protect U04 Spray Low Pressure Failure

Remote Low Hum Alarm Return Temp Sensor3 Failure Comp Driver Protect U05 Spray Antifreeze Maintenance

Return High Temp Alarm Return Hum Sensor1 Failure Comp Driver Protect U06 10DI2 Comm Failure

Return Low Temp Alarm Return Hum Sensor2 Failure Comp Driver Protect U07 Fan11 Failure

Return High Hum Alarm Return Hum Sensor3 Failure Comp Driver Protect U08 Fan12 Failure

Return Low Hum Alarm Remote Temp Sensor1 Failure Comp Driver Protect U09 ATS Comm Failure

Loss Of Airflow Alarm Remote Temp Sensor2 Failure Comp Driver Protect U10 Power Meter Comm Failure

10DI1 Comm Failure Remote Temp Sensor3 Failure Comp Driver Protect U11 Wet Film Maintenance

Fan1 Failure Remote Temp Sensor4 Failure Comp Driver Protect U12 EEV Driver Device Failure

Fan2 Failure Remote Temp Sensor5 Failure Comp Driver Protect U13 Low Refrigerant

Fan3 Failure Remote Temp Sensor6 Failure Comp Driver Protect U14

Fan4 Failure Remote Temp Sensor7 Failure Comp Driver Protect U15

Fan5 Failure Remote Temp Sensor8 Failure Comp Driver Protect U16

Fan6 Failure Remote Temp Sensor9 Failure Comp Driver Lock

Fan7 Failure Remote Temp Sensor10 Failure EEV Driver Comm Failure

Fan8 Failure Remote Hum Sensor1 Failure EEV Driver Parameter Error

Fan9 Failure Remote Hum Sensor2 Failure Suction Temp Sensor Failure

Fan10 Failure Remote Hum Sensor3 Failure LP Sensor Failure

85

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Humidifier Failure Remote Hum Sensor4 Failure Power Loss

Cond WOF Alarm Remote Hum Sensor5 Failure Power Phase Loss

Heater Failure Remote Hum Sensor6 Failure Power Overvoltage

86

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Appendix C: Hazardous Substances


Harmful substance

Parts Polybromi- nated


Lead or Plumbum Mercury or Hexavalent Polybromi- nated
Cadmium (Cd) diphe- nyl ethers
(Pb) Hydrargum (Hg) chromium [Cr(VI)] biphe- nyls (PBB)
(PBDE)

Cabinet o o o o o o

Cooling fitting o o o o o o

Fan unit o o o o o o

Heating unit o o o o o o

Electric control unit x o o o o o

Display screen x o o o o o

Heat exchanger o o o o o o

Copper pipe o o o o o o

Cable o o o o o o

o indicates that the content of the hazardous substances in all the average quality materials of the part is within the limits specified in SJ/T-11363 - 2006
x indicates the content of the hazardous substances in at least one of the average quality materials of the part exceeds the limits specified in SJ/T-11363 -
2006

Vertiv™ is committed to the design and manufacture of environment-friendly products. It will reduce and eventually eliminate toxic and hazardous
substances in the products through unremitting efforts in research. However, limited by the current technical level, the following parts still contain
hazardous substance due to the lack of reliable substitute or mature solution.
The reason that some of the above parts contain Lead or Plumbum (Pb) is as follows: diode medium and high temperature solders contain lead; resistor
glass uranium contains lead (exemption); electronic ceramics contain lead (exemption)

About Environmental Protection Use Period: The Environmental Protection Use Period of the product is marked on the product. Under normal working
conditions and normal use of products observing relevant safety precautions, the hazardous substances in the product will not seriously affect the
environment, personnel safety or property in the Environmental Protection Use Period starting from the manufacturing date

Applicable product: Liebert® CRV4 series air-cooled precision air conditioners

87

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

This page intentionally left blank

88

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual

Appendix D: Circuit Diagram


• CR025 Circuit Diagram
• CR035 Circuit Diagram
• CR045 Circuit Diagram
• CR036 Circuit Diagram
• CR066 Circuit Diagram

89

Proprietary and Confidential ©2023 Vertiv Group Corp.


CR025 Circuit Diagram

单电源配置
8
J01-7 BL QF4-3
7 N
6 QF4-1
L3
J01-5 GR QF5-1 QF3-3
5 L2
交流检测板 J01
4
J01-3
QF3-1 L1

TB1-N
BR
ACM02A2 3 汇流排/Connection bars
2
1
J01-1 BK N N N N N
TB6 L1 L2 L3 PE
N N
电控盒接地点

TB1-N
J03 J02
Y/G J03 J29 J02-1
1 1 BK
1 2 3 4 5 6 7 8 L1 L2 L3
加湿器空开 1 3 变压器空开 1 3 电加热空开 1 3 5 压缩机空开 1 3 5
风机空开 1 3
空调室外机
Humidifier Transformer Heat Compressor
2 4 Fan breaker 2 4 2 4 6 2 4 6 TB2 Outdoor
电控盒接地点 breaker 2 4
breaker breaker breaker TB2-70
QF4 70

QF5-4

QF3-4
QF4-2
QF4-4
QF5-2

QF3-2
QF2 QF1

QF2-2
QF2-4

QF1-2
QF1-4
QF1-6
QF5 QF3 TB2-71
71

变压器TC
BR BL BR BL BK BK BK BK BK BK BK BK BK BK BK BK BR
CAN-L 1 2 3 4 5 6 7 8 Transformer TC

KM1-153
KM1-161
L

KM1-21
KM2-1
KM2-3
4

KM1-21

KM2-21
KR1-A1
KR1-13
KR1-31

KR2-A1
KR2-13
KM1-1
KM1-3
KM1-5
KM2-A1

KM1-A1

KM1-1
KM1-3
KM1-5

KM2-1
KM2-3
KM2-5

RD1-1

RD2-1
RD3-1

RD4-1
RD5-1
KM1-A1
CAN CAN-H J30 J31-1 TB1-0V TB1-0V BK TC-6

KM2-A1
H 1 BK 0V 3
J31 J31-2 BK
BK 电加热接触器 压缩机接触器
2 TC-2 1 3 5 21 1 3 5 21 153 161 13 31 13 31 1 3 5 21 1 3 5 21
TB1-24V
24V
TB1-24V BK TC-5 Heat A1 Compressor A1 KR1
A1
KR2
A1
KM1
A1 A1
KM2
RD1 RD2 RD3 RD4 RD5
TC-1 BK A2 RD1 RD2 RD3 RD4 RD5
TB2-62 J20-CANL J13-1 BK
contactor A2 2 4 6 22 contactor A2 2 4 6 22 154 162 A2 14 32 A2 14 32 A2 2 4 6 22 2 4 6 22
62 2 1

KM1-A2
KM2-A2

KM1-A2
显示屏

KM2-A2
KR1-A2
KR1-14
KR1-32

KR2-A2
KR2-14
KM2 KM1

KM1-22

KM2-22
KM1-2
KM1-4
KM1-6

KM2-2
KM2-4
KM2-6

RD1-2

RD2-2
RD3-2

RD4-2
RD5-2
KM1-154
KM1-162
TB2-61 J20 J13 J13-2

KM1-22
J20-CANH

KM2-2
KM2-4

KM1-2
KM1-4
KM1-6
61 1 2 BK

GHMI TB1-24V
24V BK BR BR BL BL BK BK
J18-1 BK
PWR-+ TB1-0V 1
+ 0V
PWR-- 2
PWR - J18-D06 BK 过电压抑制器
PWR-GND J18 3
J18-D07 BK Overvoltage
4
J18-D08 BK TB1-94 HPS HPS TB1-95 BK suppressor
5 94 95

N
高压开关
High Pressure Switch Y/G Y/G
485+
485-
压缩机
驱动器 电控盒接地点 电控盒接地点

J65-L
J65-N

J65-L
J65-N
7 4 2 3 1
KA2
J65 L N J65 L N Compressor

EH1-L
EH2-L
R48-1000 R48-1000
transducer

CAN

CAN
8
L3
6 5 电源模块 电源模块 BR BR
L2
24VDC J69 DC+ DC- J70 J69 DC+ DC- J70

QS1-1
QS1-3
QS1-5

QS2-1
QS2-3
QS2-5

QS1-1
QS1-3
QS1-5
L1
电源模块

PE1

PE1
PE2
N1

N2

N1
J69-DC+

J70-DC-

J69-DC+

J70-DC-
回风温湿度传感器 N
BL BL U V W PE 1 3 5 1 3 5 1 3 5
J1 J34 系统空开1 N1 PE1 N2 PE2 系统空开2 系统空开1 N1 PE1
Temp.and Humi.J1 J34
Main switch 1 2 4 6 2 4 6 Main switch 2 Main switch 1 2 4 6

EH1-N
EH2-N
sensor 冷凝水泵
Condensate 屏蔽 QS1 QS2 QS1
pump
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
选配件
Optional 24V 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~
输入电源1 输入电源2 输入电源1
TB2 POWER SUPPLY 1 POWER SUPPLY 2 POWER SUPPLY 1
控制板

KM3-1
KM3-3
KM3-A1
TB2-B2 BK J14-B 48V 48V GND GND 10V(1) 10V(1) 48V 48V GND GND 10V(2) 10V(2)
B B2 1
加湿接触器
RDU-SIC1 A A2
TB2-A2
TB2-GND
BR J14-A
2
J14 ACM05U1 J12
1
J12-12V
J12-GND
BK
BR
TB1-12V
TB1-GND
12V
A1
1 3 5 21
Humidifier TB4 48V 48V GND GND 10V(1)10V(1) 48V 48V GND GND 10V(2) 10V(2) TB5

T1
T2
T3
GND GND 2 GND
12 12V
TB2-12V A1 TB1-A1 A2 2 4 6 22 contactor 屏蔽
TB1-B1

KM3-A2
B1 KM3

KM3-2
KM3-4
压缩机1
Compressor1
BK BR 3~
J15-1 BR
1
J15 J15-2 BK 前门板接地 机柜接地
2
TB1-12V
TB1-GND

Y/G
12V GND
J16-1 BK
1
J16 J16-2 BR
2
后门板接地 机柜接地

RT1 J19-1 BK
BK J25-1 1
1 J19-2 BR 高压告警/High pressure alarm
送风温度传感器1/Delivery air probe1 BK J25-2 2
2 J19-3 BK
RT2 BK J25-3 J25 3
3 J19-4 BR J1-1 J1-2 高水位告警/High water alarm
送风温度传感器2/Delivery air probe2 BK J25-4 4
4 J19 J19-5 BK
5 选配件
J19-6 BK ST1-C ST1-NC ST2-C ST2-NC 电加热故障告警/Heat alarm
6 Optional 排水阀HDV
J19-7 BK TB2-51 51 BR
0V
地板溢水开关/Water under floor switch 选配件
7 BK
J19-8 BR TB2-24 24 1 2 电流互感器
8 Optional BR BR
BR BK 2
RT3 J8-1 BK
BK 1 BK 1
J21-1
M10-2
M10-1

M11-3
M11-2
排气温度传感器/Exhaust air probe J8-2 J8 BK M11-1 注水阀HFV

M7-3
M7-2
BK 1 选配件
TC2-1
TC2-2

2 J21-2 1 2 水位开关/Water line switch


BR
2 Optional
J21-3 BK 2 1 2 1 3 2 1 3 2 1 3 2
HP-5V J23-1 3 M3-2 BK BR BL
R 1 J21-4 BR 加湿告警/Humidifier alarm M6 M10 M11 M14 M7 2
HP-VIN J23-2 4 M3 M3-1 BK
高压传感器/High pressure sensor BR 2 J23 J21 J21-5 BK 1
HP-GND BK J23-3 5
水位开关/Water line switch 选配件
3 6
J21-6 BR 3 2
Optional CPY加湿控制器 2 M9-2 BK
J21-7 BK TB2-37 37 M9 M9-1 BK
7 1 CS LS
J21-8 BR TB2-38 38 1 2 远程开关机/Remote swith 电源 手操器 TLAN通迅 485通迅 外部控制端子
TB1-B1 BK J39-B 8 M8 J1 M12 M1 M2 M5
B1 1
J39
TC2-4

TB1-A1 J39-A
TC2-3

BR 1 2 1 2 1 2 3 1 2 3 4 5 6 7 1 2
A1 2
J28-1 BK TB1-24V 24V A E/B
1
M8-1
M8-2

M2-1
M2-2

M2-4
M2-5
M2-6

M5-1
M5-2
J28-2 BK KA1-A1 KA1-14 YE
2 加湿器
J28-3 BK TB2-75 75 A1 YE
3
J28-4 TB2-76 76 公共告警/Common alarm
4
J28-5
BR
BK TB1-24V 24V
A2
KA1-11
BK
BR
TB4 TB5
TB1-0V KA1-A2

J28 5
J28-6 BK TB2-63 63 Y1
6 XPE 选配件 BK
TB2-64 64 Y1 XPE
0: 加湿 加湿手动 NC
7 Optional COM BK
8 1: 手动排水 排水开关 BK 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2)
NO
液路电磁阀
TB1-0V

9 0V BK
Freon solenoid valve
10 BR
0V

BK

BK

BK

BK

BK

BK
R

R
Y1
TB1-0V Y1

BL

BL

BL

BL

BL

BL
0V

R
加湿电磁阀 风机1 风机2 风机3 风机4 风机5 风机6
Humidify solenoid valve
Fan1 Fan2 Fan3 Fan4 Fan5 Fan6

BR

BR

BR

BR

BR

BR
W

P
O

O
BR J38-1 GND
温度传感器
TH1 BK J38-2
1
2
J38 TB5 GND
B1 TB3 远程传感器1 远程传感器2 远程传感器3
A1
GND Remote sensor1 Remote sensor2 Remote sensor3
12V
R J43-1
1 电子膨胀阀控制器

GND
DI1
DI2
DI3

DI4
DI5
DI6
压力传感器 J43-2
2 J43 EEV controller
LPT BR J34-1 O
BK J43-3 1
3 J34-2 R 12V
2
Terminal block/端子排 J34 3
J34-3 YE 执行阀体 A
EEV A
TB1
GND
A1 10DI
J34-4 BK B1
J32 J33 4
TB1 TB2 TB3 5
J34-5 BR
1 2 1 2 3 4
6
J32-1
J32-2

J33-3
J33-4

0V 0V 0V 24V 24V 24V GND GND GND 12V 12V 12V 00 12 G10 10V A1 A1 A1 B1 B1 B1 94 95 N N N N N 51 24 37 38 70 71 75 76 A2 B2 12V GND 61 62 63 64

备注/Notes:
BR

BR
BK

BK

Factory supplied line voltage wiring/出厂线电压线路


配线色标/Wire color code:
Ethernet or CAN wiring/以太网或CAN线路
Factory supplied 24 volt wiring/出厂24V线路 BK-Black/黑色 P-Purple/紫色
BL-Blue/蓝色 R-Red/红色
Device own line/器件自带线
BR-Brown/棕色 YE-Yellow/黄色
Inline quick disconnect/线上快速对插端子
WH-White/白色 GR-Grey/灰色
Terminal block connector/线缆端子 Y/GN-Yellow green/黄绿色 24V 0V A1 B1
Naked crimping connector/裸压端子 O-Orange/橙色

Proprietary and Confidential ©2023 Vertiv Group Corp.


CR035 Circuit Diagram

单电源配置
8
J01-7 BL QF4-3 N
7
6 QF4-1 L3
J01-5 GR QF5-1 QF3-3
5 L2
交流检测板 J01
4
J01-3
QF3-1 L1

TB1-N
BR
ACM02A2 3 汇流排/Connection bars
2
1
J01-1 BK N N N N N
TB6 L1 L2 L3 PE
N N
电控盒接地点

TB1-N
J03 J02
Y/G J03 J29 J02-1
1 1 BK
1 2 3 4 5 6 7 8 L1 L2 L3
加湿器空开 1 3 变压器空开 1 3 电加热空开 1 3 5 压缩机空开 1 3 5
风机空开 1 3
空调室外机
Humidifier Transformer Heat Compressor
2 4 Fan breaker 2 4 2 4 6 2 4 6 TB2 Outdoor
电控盒接地点 breaker 2 4
breaker breaker breaker TB2-70
QF4 70

QF5-4

QF3-4
QF4-2
QF4-4
QF5-2

QF3-2
QF2 QF1

QF2-2
QF2-4

QF1-2
QF1-4
QF1-6
QF5 QF3 TB2-71
71

变压器TC
BR BL BR BL BK BK BK BK BK BK BK BK BK BK BK BK BR
1 2 3 4 5 6 7 8 Transformer TC

KM1-153
KM1-161
KM1-21
KM2-1
KM2-3
4

KM1-21

KM2-21
KR1-A1
KR1-13
KR1-31

KR2-A1
KR2-13
KM1-1
KM1-3
KM1-5
KM2-A1

KM1-A1

KM1-1
KM1-3
KM1-5

KM2-1
KM2-3
KM2-5

RD1-1

RD2-1
RD3-1

RD4-1
RD5-1
KM1-A1
J30 J31-1 TB1-0V TB1-0V BK TC-6

KM2-A1
1 BK 0V 3
J31 J31-2 BK
BK 电加热接触器 压缩机接触器
2 TC-2 1 3 5 21 1 3 5 21 153 161 13 31 13 31 1 3 5 21 1 3 5 21
L
CAN-L TB1-24V
24V
TB1-24V BK TC-5 Heat A1 Compressor A1 KR1
A1
KR2
A1
KM1
A1 A1
KM2
RD1 RD2 RD3 RD4 RD5
TC-1 BK RD1 RD2 RD3 RD4 RD5
CAN CAN-H contactor A2 contactor A2 A2 14 32 A2 14 32 A2 2 4 6 22 2 4 6 22 A2
H J13-1 2 4 6 22 2 4 6 22 154 162
1 BK

KM1-A2
KM2-A2

KM1-A2

KM2-A2
KR1-A2
KR1-14
KR1-32

KR2-A2
KR2-14
KM2 KM1

KM1-22

KM2-22
KM1-2
KM1-4
KM1-6

KM2-2
KM2-4
KM2-6

RD1-2

RD2-2
RD3-2

RD4-2
RD5-2
KM1-154
KM1-162
J13 J13-2

KM1-22
KM2-2
KM2-4

KM1-2
KM1-4
KM1-6
2 BK

TB2-62 J20-CANL
62 2 BK BR BR BL BL BK BK
显示屏 61
TB2-61 J20-CANH
1
J20
1
J18-1 BK
2
GHMI TB1-24V
24V
J18 3
J18-D06 BK 过电压抑制器
TB1-0V J18-D07 BK Overvoltage
PWR-+ 0V 4
+ J18-D08 BK TB1-94 HPS HPS TB1-95 BK suppressor
PWR-- 5 94 95
PWR -
PWR-GND 高压开关
N
High Pressure Switch Y/G Y/G
485+
485-
压缩机
驱动器 电控盒接地点 电控盒接地点

J65-L
J65-N

J65-L
J65-N
7 4 2 3 1
KA2
J65 L N J65 L N Compressor

EH1-L
EH2-L
EH3-L
EH4-L
R48-1000 R48-1000
transducer

CAN

CAN
8
L3
6 5 电源模块 电源模块 BR BR BR BR
L2
24VDC J69 DC+ DC- J70 J69 DC+ DC- J70

QS1-1
QS1-3
QS1-5
QS1-1
QS1-3
QS1-5

QS2-1
QS2-3
QS2-5
L1
电源模块

PE1
PE1

PE2

N1
N1

N2
J69-DC+

J70-DC-

J69-DC+

J70-DC-
回风温湿度传感器 N
BL BL BL BL U V W PE 1 3 5 1 3 5 1 3 5
J1 J34 系统空开1 N1 PE1 N2 PE2 系统空开2 系统空开1 N1 PE1
Temp.and Humi.J1 J34
Main switch 1 2 4 6 2 4 6 Main switch 2 Main switch 1 2 4 6

EH1-N
EH2-N
EH3-N
EH4-N
sensor 冷凝水泵
Condensate 屏蔽 QS1 QS2 QS1
pump
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
选配件
Optional 24V 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~
输入电源1 输入电源2 输入电源1
TB2 POWER SUPPLY 1 POWER SUPPLY 2 POWER SUPPLY 1
控制板

KM3-1
KM3-3
KM3-A1
TB2-B2 BK J14-B 48V 48V GND GND 10V(1) 10V(1) 48V 48V GND GND 10V(2) 10V(2)
B B2 1
加湿接触器
RDU-SIC1 A A2
TB2-A2
TB2-GND
BR J14-A
2
J14 ACM05U2 J12
1
J12-12V
J12-GND
BK
BR
TB1-12V
TB1-GND
12V
A1
1 3 5 21
Humidifier TB4 48V 48V GND GND 10V(1)10V(1) 48V 48V GND GND 10V(2)10V(2) TB5

T1
T2
T3
GND GND 2 GND
12 12V
TB2-12V A1 TB1-A1 A2 2 4 6 22 contactor 屏蔽
TB1-B1

KM3-A2
B1 KM3

KM3-2
KM3-4
压缩机1
Compressor1
BK BR 3~
J15-1 BR
1
J15 J15-2 BK 前门板接地 机柜接地
2
TB1-12V
TB1-GND

Y/G
12V GND
J16-1 BK
1
J16 J16-2 BR
2
后门板接地 机柜接地

RT1 J19-1 BK
BK J25-1 1
1 J19-2 BR 高压告警/High pressure alarm
送风温度传感器1/Delivery air probe1 BK J25-2 2
2 J19-3 BK
RT2 BK J25-3 J25 3
3 J19-4 BR J1-1 J1-2 高水位告警/High water alarm
送风温度传感器2/Delivery air probe2 BK J25-4 4
4 J19 J19-5 BK
5 选配件
J19-6 BK ST1-C ST1-NC ST2-C ST2-NC ST3-C ST3-NC ST4-C ST4-NC 电加热故障告警/Heat alarm
6 Optional 排水阀HDV
J19-7 BK TB2-51 51 BR
7 选配件 0V BK
J19-8 BR TB2-24 24 1 2 地板溢水开关/Water under floor switch 电流互感器
8 Optional BR BR
BR BK 2
RT3 J8-1 BK
BK 1 BK 1
J21-1
M10-2
M10-1

M11-3
M11-2
M11-1

排气温度传感器/Exhaust air probe J8-2 J8 BK 注水阀HFV

M7-3
M7-2
BK 1 选配件
TC2-1
TC2-2

2 J21-2 1 2 水位开关/Water line switch


BR
2 Optional
J21-3 BK 2 1 2 1 3 2 1 3 2 1 3 2
HP-5V J23-1 3 M3-2 BK BR BL
R 1 J21-4 BR 加湿告警/Humidifier alarm M6 M10 M11 M14 M7 2
HP-VIN J23-2 4 M3 M3-1 BK
高压传感器/High pressure sensor BR 2 J23 J21 J21-5 BK 1
HP-GND BK J23-3 5
水位开关/Water line switch 选配件
3 6
J21-6 BR 3 2
Optional CPY加湿控制器 2 M9-2 BK
J21-7 BK TB2-37 37 M9 M9-1 BK
7 1 CS LS
J21-8 BR TB2-38 38 1 2 远程开关机/Remote swith 电源 手操器 TLAN通迅 485通迅 外部控制端子
8 M8 J1 M12 M1 M2 M5
TC2-4
TC2-3

1 2 1 2 1 2 3 1 2 3 4 5 6 7 1 2
TB1-B1 BK J39-B J28-1 BK TB1-24V 24V
B1 1 1 A E/B
M8-1
M8-2

M2-1
M2-2

M2-4
M2-5
M2-6

M5-1
M5-2

TB1-A1 BR J39-A J39 J28-2 BK KA1-A1 KA1-14 YE


A1 2 2
J28-3 BK TB2-75 75 A1 YE
加湿器
3
J28-4 BR TB2-76 76 公共告警/Common alarm A2 BK
4
J28-5 BK TB1-24V 24V KA1-11 BR
TB1-0V KA1-A2

J28 5
J28-6 BK TB2-63 63 Y1
6 XPE 选配件 BK
TB2-64 64 Y1 XPE
0: 加湿 加湿手动 NC
7 Optional COM BK
8 1: 手动排水 排水开关 BK
NO
液路电磁阀
TB1-0V

9 BK
10
Freon solenoid valve 0V
BR TB4 TB5
0V

48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2)

Y1
TB1-0V Y1
0V
加湿电磁阀
Humidify solenoid valve

BK

BK

BK

BK

BK

BK

BK

BK
R

R
BL

BL

BL

BL

BL

BL

BL

BL
R

R
风机1 风机2 风机3 风机4 风机5 风机6 风机7 风机8
Fan1 Fan2 Fan3 Fan4 Fan5 Fan6 Fan7 Fan8
BR J38-1
温度传感器 1
TH1 BK J38-2 J38

BR

BR

BR

BR

BR

BR

BR

BR
2
W

P
B1 TB3 远程传感器1 远程传感器2 远程传感器3
A1
Remote sensor1 Remote sensor2 Remote sensor3
O

O
GND
GND
12V
R J43-1 电子膨胀阀控制器
TB5 GND
1
压力传感器 J43-2
2 J43 EEV controller
LPT BR J34-1 O
BK J43-3 1
3 J34-2 R
2
Terminal block/端子排 J34 3
J34-3 YE 执行阀体 A
EEV A
J34-4 BK

GND
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
J32 J33 4
TB1 TB2 TB3 5
J34-5 BR
1 2 1 2 3 4 12V
6 TB1
GND
10DI
J32-1
J32-2

J33-3
J33-4

A1
0V 0V 0V 24V 24V 24V GND GND GND 12V 12V 12V 00 12 G10 10V A1 A1 A1 B1 B1 B1 94 95 N N N N N 51 24 37 38 70 71 75 76 A2 B2 12V GND 61 62 63 64 B1

备注/Notes:
BR

BR
BK

BK

Factory supplied line voltage wiring/出厂线电压线路


配线色标/Wire color code:
Ethernet or CAN wiring/以太网或CAN线路
Factory supplied 24 volt wiring/出厂24V线路 BK-Black/黑色 P-Purple/紫色
BL-Blue/蓝色 R-Red/红色
Device own line/器件自带线
BR-Brown/棕色 YE-Yellow/黄色
Inline quick disconnect/线上快速对插端子
WH-White/白色 GR-Grey/灰色
Terminal block connector/线缆端子 Y/GN-Yellow green/黄绿色 24V 0V A1 B1
Naked crimping connector/裸压端子 O-Orange/橙色

Proprietary and Confidential ©2023 Vertiv Group Corp.


CR045 Circuit Diagram

单电源配置
8
J01-7 BL QF4-3 N
7
6 QF4-1 L3
J01-5 GR QF5-1 QF3-3 L2
5
交流检测板 J01
4
J01-3
QF3-1 L1

TB1-N
BR
ACM02A2 3
2
1
J01-1 BK N N N N N
TB6 L1 L2 L3 PE
N N
电控盒接地点

TB1-N
J03 J02
Y/G J03 J29 J02-1
1 1 BK
1 2 3 4 5 6 7 8 L1 L2 L3
HUMIDIFIER 1 3 TRANSFORMER 1 3 HEAT 1 3 5 COMPRESSOR 1 3 5
FAN BREAKER 1 3
空调室外机
BREAKER BREAKER BREAKER BREAKER
2 4 QF4 2 4 2 4 6 2 4 6 TB2 Outdoor
电控盒接地点 QF5 2 4 QF3 QF2 QF1 TB2-70
70

QF5-4

QF3-4
QF4-2
QF4-4
QF5-2

QF3-2

QF2-2
QF2-4

QF1-2
QF1-4
QF1-6
TB2-71
71

TRANSFORMER TC BR BL BR BL BK BK BK BK BK BK BK BK BK BK BK BK BR
1 2 3 4 5 6 7 8

KM1-153
KM1-161
KM2-A1

KM1-21
KM1-A1
KM2-1
KM2-3
4

KMA-21

KMB-21
KAC-A1
KAC-13
KAC-31

KAD-A1
KAD-13
KM1-1
KM1-3
KM1-5
L CAN-L

KMA-1
KMA-3
KMA-5

KMB-1
KMB-3
KMB-5

RD1-1

RD2-1
RD3-1

RD4-1
RD5-1
KMA-A1
J30 J31-1 TB1-0V TB1-0V BK TC-6

KMB-A1
BK
1 0V 3 BK HEAT COMPRESSOR
H CAN-H
CAN J31 J31-2 BK
2 TC-2 1 3 5 21 1 3 5 21 153 161 13 31 13 31 1 3 5 21 1 3 5 21
TB1-24V
24V
TB1-24V BK TC-5 CONTACTOR A1 CONTACTOR A1
KAC
A1
KAD
A1
KMA
A1 A1
KMB
RD1 RD2 RD3 RD4 RD5
TC-1 BK
J13-1
KM2 A2 2 4 6 22 KM1 A2 2 4 6 22 154 162 A2 14 32 A2 14 32 A2 2 4 6 22 2 4 6 22 A2 RD1 RD2 RD3 RD4 RD5
BK
GHMI 1

KMA-A2

KMB-A2
KAC-A2
KAC-14
KAC-32

KAD-A2
KAD-14

KMA-22

KMB-22
KMA-2
KMA-4
KMA-6

KMB-2
KMB-4
KMB-6

RD1-2

RD2-2
RD3-2

RD4-2
RD5-2
KM1-154
KM1-162
KM2-A2
62 TB2-62 BR J20-CANL 2 J13 J13-2

KM1-A2

KM1-22
KM2-2
KM2-4
BK

KM1-2
KM1-4
KM1-6
2
61 TB2-61 BK J20-CANH 1 J20
DISPLAY BK BR BR BL BL BK BK BK BK BK
J18-1 BK
1
+ PWR-+ TB1-24V 24V 2
J18-D06 BK
PWR -
PWR-- TB1-0V 0V J18 3 OVERVOLTAGE
J18-D07 BK
PWR-GND 4 SUPPRESSOR
J18-D08 BK TB1-94 HPS HPS TB1-95 BK
5 94 95
HIGH PRESSURE SWITCH
N Y/G
Y/G
BK 24V
电控盒接地点

J65-L
J65-N

J65-L
J65-N
PE 电控盒接地点

KM3-A1
KM3-1
KM3-3
7 4 2 3 1 J65 L N J65 L N
KA2 L1 L2 L3

EH1-L
EH2-L
EH3-L
EH4-L
8 A1
1 3 5 21 HUMIDIFIER R48-1000 R48-1000

CAN

CAN
6 5
A2 2 4 6 22
CONTACTOR POWER SUPPLY POWER SUPPLY
BR BR BR BR COMPRESSOR
KM3

QS1-1
QS1-3
QS1-5
BK BR BL J69 DC+ DC- J70 J69 DC+ DC- J70
INVERTER

QS1-1
QS1-3
QS1-5

QS2-1
QS2-3
QS2-5

PE1
KM3-A2

N1
KM3-2
KM3-4

PE1

PE2
N1

N2
RETURN AIR A1 TB1-A1

J69-DC+

J70-DC-

J69-DC+

J70-DC-
J1 J34 N 485+ 1 3 5
J16
J1 B1 TB1-B1
J34 1 3 5 1 3 5
24VDC BL BL BL BL 485-
系统空开1 系统空开2 系统空开1 N1 PE1
T&TH SENSOR ADAPTER
Main switch 1 2 4 6
N1 PE1
2 4 6
N2 PE2
Main switch 2 Main switch 1 2 4 6

EH1-N
EH2-N
EH3-N
EH4-N
U V W PE
QS1 QS2 QS1
CONDENSATE L1 L2 L3 N PE
L1 L2 L3 N PE L1 L2 L3 N PE
PUMP BK R BL Y/G 屏蔽
380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60Hz 3N~ 380V~415V 50Hz/60HZ 3N~
OPTIONAL
输入电源1 输入电源2 输入电源1
10V(1) 10V(1) 48V 48V GND GND 10V(2)10V(2) 48V 48V GND GND POWER SUPPLY 1
控制板 TB4 10V(1) 10V(1) 48V 48V GND GND 10V(2)10V(2) 48V 48V GND GND
TB5 PE POWER SUPPLY 1 POWER SUPPLY 2
TB2

L1
L2
L3

PE
B B2 TB2-B2 BK J14-B 1 ACM05U2 J12
1
J12-12V
J12-GND
BK TB1-12V
TB1-GND
12V
J14-A 2 J14 BR
A A2 TB2-A2 BR 2 GND
屏蔽
RDU-SIC COMPRESSOR
ZPV096
12V 12V TB2-12V
GND TB2-GND
J15-1 BR
GND 1
J15 J15-2 BK 前门板接地 机柜接地
BR BK 2
TB1-GND
TB1-12V

Y/G

J16-1 BK
1
GND 12V J16 J16-2 BR
2
后门板接地 机柜接地

J19-1 BK
1
J19-2 BR 高压告警/High pressure alarm
2
J19-3 BK
3
J19-4 BR J1-1 J1-2 高水位告警/High water alarm
4
J19 J19-5 BK
5 选配件
B1 TB2-B1 BK J22-B 1 6
J19-6
J19-7
BK
BK
ST1-C

TB2-51 51
ST1-NC ST2-C ST2-NC ST3-C ST3-NC ST4-C ST4-NC 电加热故障告警/Heat alarm
Optional
BR 排水阀HDV TB4 TB5
OPTIONAL TB2-A1 BR J22-A 2 J22 7 选配件 0V BK
A1 J19-8 BR TB2-24 24 1 2 地板溢水开关/Water under floor switch 电流互感器
8 Optional BR BR
BR BK 2 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2)
BK
BK 1
J21-1
M10-2
M10-1

M11-3
M11-2
M11-1

BK 注水阀HFV

M7-3
M7-2
1 选配件
TC2-1
TC2-2

J21-2 BR 1 2 水位开关/Water line switch


2 Optional
SAS1 J21-3 BK 2 1 2 1 3 2 1 3 2 1 3 2
BK J25-1 1 3
2 M3-2 BK BR BL
SUPPLY AIR SENSOR 1 J21-4 BR 加湿告警/Humidifier alarm M6 M10 M11 M14 M7
BK J25-2 4 M3 M3-1 BK

BK

BK

BK

BK

BK

BK

BK

BK

BK

BK
2 1

R
J21 J21-5 BK
SAS2 BK J25-3 J25 5 选配件
3 J21-6 BR 3 2 浮球开关/FLOAT LEVER SWITCH CPY加湿控制器 M9-2 BK
SUPPLY AIR SENSOR 2 BK J25-4 6 Optional 2

BL

BL

BL

BL

BL

BL

BL

BL

BL

BL
4 J21-7 BK TB2-37 37 M9 M9-1 BK

R
7 1 CS LS
J21-8 BR TB2-38 38 1 2 远程开关机/Remote swith 电源 手操器 TLAN通迅 485通迅 外部控制端子
8 M8 J1 M12 M1 M2 M5 风机1 风机2 风机3 风机4 风机5 风机6 风机7 风机8 风机9 风机10
TC2-4
TC2-3

1 2 1 2 1 2 3 1 2 3 4 5 6 7 1 2
J28-1 BK TB1-24V 24V
Fan1 Fan2 Fan3 Fan4 Fan5 Fan6 Fan7 Fan8 Fan9 Fan10
A E/B
1
M8-1
M8-2

M2-1
M2-2

M2-4
M2-5
M2-6

M5-1
M5-2

J28-2 BK KA1-A1 KA1-14 YE


DTS BK J8-1 2 加湿器
1 J28-3

BR

BR

BR

BR

BR

BR

BR

BR

BR

BR
BK TB2-75 75 A1 YE

P
DISCHARGE TEMPERATURE SENSOR BK J8-2 J8 3
COMMON ALARM
2 J28-4 BR TB2-76 76 BK
4 A2
J28-5 BK TB1-24V 24V KA1-11 BR
TB1-0V KA1-A2

O
J28 5
J28-6 BK TB2-63 63 Y1 GND
6
7 TB2-64 64 Y1
XPE XPE 选配件
Optional 0: 加湿 加湿手动 NC COM
BK
BK TB5 GND
8 1: 手动排水 排水开关 BK
NO
TB1-0V

9 FREON SOLENOID VALVE 0V BK


HP-5V R J23-1 1 10 BR
HP-VIN Y1
BR J23-2 2 J23
HIGH PRESSURE TRANSDUCER 0V
0V
TB1-0V Y1
HP-GND BK J23-3 3

DI10
GND
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
HUMIDITY SOLENOID VALVE
TB3
J38 REMOTE TEMP
J38 10DI SENSOR *
A1 B1
J34-1 O
TB1-B1
TB1-A1

1 1
J34-2 R
2 2
J39-A BR J33-3 3 J33 3
J34-3 YE
2 J34 J34-4 BK
J39 BK J33-4 4 EEV A
1 J39-B 4
J34-5 BR
5
6

BR J38-1 1 EEV CONTROLLER


SUCTION TEMPERATURE SENSOR STS BK J38-2 2 J38
STS
1
J35-1 O
2
J35-2 R
J32
Terminal block/端子排 LP-5V R J43-1 1
1 2
J35
3
4
J35-3
J35-4
YE
BK EEV B
LP-GND BR J43-2 2 J35-5 BR
LOW PRESSURE TRANSDUCER LPT J43 5
TB1 TB2 TB3 LP-VIN BK J43-3 3
J32-1
J32-2

6
BK
BR

0V 0V 0V 24V 24V 24V GND GND GND 12V 12V 12V 00 12 G10 10V A1 A1 A1 B1 B1 B1 94 95 N N N N N 51 24 37 38 70 71 75 76 A2 B2 12V GND 61 62 63 64

备注/Notes:
TB1-24V
TB1-0V

Factory supplied line voltage wiring/出厂线电压线路


配线色标/Wire color code:
Ethernet or CAN wiring/以太网或CAN线路 24V 0V
Factory supplied 24 volt wiring/出厂24V线路 BK-Black/黑色 P-Purple/紫色
BL-Blue/蓝色 R-Red/红色
Device own line/器件自带线
BR-Brown/棕色 YE-Yellow/黄色
Inline quick disconnect/线上快速对插端子
WH-White/白色 GR-Grey/灰色
Terminal block connector/线缆端子 Y/GN-Yellow green/黄绿色
Naked crimping connector/裸压端子 O-Orange/橙色

Proprietary and Confidential ©2023 Vertiv Group Corp.


CR036 Circuit Diagram

双电源配置/DUAL POWER SUPPLY OPTIONAL

8
J01-7 BL N
7
6 L3
交流检测板 5
J01-5 GR
L2
J01
ACM02A2 4
3
J01-3 BR
L1

2 TB6 L1 L2 L3 PE
J01-1 BK N
1 N N N N
PE
J03 J29 J02
Y/G J03 J02-1 BK L1 L2 L3
1 1 2 3 4 5 6 7 8 1 变压器空开 风机空开 电加热空开 压缩机空开
1 3 1 3 HEATER 1 3 5 COMPRESSOR 1 3 5 室外机空调
TRANSFORMER FAN
BREAKER 2 4 2 4 BREAKER 2 4 6 BREAKER 2 4 6 TB2 OUTDOOR
PE
BREAKER
QF2 QF1 TB2-70

QF4-2
QF4-4
QF3

QF3-4
QF3-2
QF4 70

QF2-2
QF2-4

QF1-2
QF1-4
QF1-6
TB2-71
6A 16A 10A 25A 71
变压器TC
TRANSFORMER TC BK BK BK BK BK BK BK BK
BK BK BR BL

KAC-A1
KAC-13
KAC-31

KMA-A1

KMA-01

KMB-01
KMB-A1
KAD-A1
KAD-13
1 2 3 4 5 6 7 8 100VA

KM2-A1

RD1-2
RD2-2
RD3-2
RD4-2
RD5-2
KMA-1
KMA-3
KMA-5
KMA-7

KMB-1
KMB-3
KMB-5
KMB-7
KM1-A1

KM1-21
KM1-153
KM1-161
KM2-1
KM2-3

KM1-1
KM1-3
KM1-5
J30 J31-1 BK TB1-0V 0V TB1-0V BK TC-6
4 电加热接触器 压缩机接触器
3
J31 1 J31-2 BK BK HEATER COMPRESSOR
2 TC-2 1 3 5 21 1 3 5 21 153 161 A1 13 31 A1 13 31 A1 1 3 5 7 01 1 3 5 7 01 A1 RD1 RD2 RD3 RD4 RD5
TB1-24V 24V TB1-24V BK TC-5
TC-1 BK CONTACTOR A1 CONTACTOR A1 KAC KAD KMA KMB
A2 14 32 A2 14 32 A2 2 4 6 8 02 2 4 6 8 02 A2 RD1 RD2 RD3 RD4 RD5
J13-1 BK KM2 A2 2 4 6 22 KM1 A2 2 4 6 22 154 162
J13 1 J13-2

KAC-A2
KAC-14
KAC-32

KAD-A2
KAD-14

KMA-A2

KMA-02

KMB-02
KMB-A2
KM1-154
KM1-162

RD1-1
RD2-1
RD3-1
RD4-1
RD5-1
9A 25A

KMA-2
KMA-4
KMA-6
KMA-8

KMB-2
KMB-4
KMB-6
KMB-8
KM2-A2
BK

KM1-A2

KM1-22
KM2-2
KM2-4

KM1-2
KM1-4
KM1-6
2
CAN-L
L J18-1 BK BK BR BR BL BK BK BK BK BK
CAN CAN-H 1
H
2
J18 3 J18-D06 BK 过电压抑制器
显示屏 OVERVOLTAGE
TB2-62 BR J20-CANL 4 J18-D07 BK
SUPPRESSOR
GHMI 62
61
TB2-61 BK J20-CANH
2
1 J20
5 J18-D08 BK TB1-94 94 HPS HPS 95 TB1-95 BK
高压开关
DISPLAY HIGH PRESSURE SWITCH N Y/G Y/G
PWR-+ TB1-24V 24V BK
+
PWR-- TB1-0V PE
PWR - 0V PE
PWR-GND 4 2 3 1
7 L1 L2 L3
KA1

J1-L
J1-N
8

EH1-L

EH2-L
PE 6 5
压缩机驱动
BK BR BL J16 COMPRESSOR

QS1-1
QS1-3
QS1-5
QS1-7

QS2-1
QS2-3
QS2-5
QS2-7
J1 L N

QS1-1
QS1-3
QS1-5
QS1-7
BR BR TB1-A1
A1 485+

PE
N

PE
R48-2000E3 485- INVERTER

PE
TB1-B1
24VDC B1 主空开1 主空开2
主空开 1 3 5 7 1 3 5 7
J12-V12 BK TB1-12V 12V
电源模块 电源模块 MAIN BREAK
1 3 5 7
MAIN BREAK 1 PE PE MAIN BREAK 2
J12 1 J12-GND BR U V W PE PE
TB1-GND GND J21 DC+ DC- J11 BL BL 2 4 6 8 QS1 2 4 6 8 2 4 6 8 QS2
2 QS1
冷凝水泵
BK R BL Y/G 屏蔽 40A 40A 40A

EH1-N

EH2-N
CONDENSATE
PUMP

J21-DC+
J11-DC-
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
回风温湿度传感器 选配件
输入电源1 输入电源2
OPTIONAL 输入电源
RETURN AIR J1
J1 J34
J34
控制板 PE
POWER POWER 1 POWER 2

T1
T2
T3

PE
T&TH SENSOR ACM05U15
压缩机 屏蔽
COMPRESSOR
ZPV050
1
J19-1 BK
J19-2 BR 高压告警/HIGH PRESSURE ALARM
2
3
J19-3 BK
J19-4 BR J1-1 J1-2 高水位告警/HIGH WATER ALARM
4
J19 J19-5 BK
5
TB2 6 J19-6 BK ST1-C ST1-NC ST2-C ST2-NC 电加热告警/HEAT ALARM
TB2-51 51
B B2 TB2-B2 BK J14-B 1 7
J19-7 BK
J1-1 J1-2
J14 J19-8 BR TB2-24 24 地板溢水开关/WATER UNDER FLOOR SWITCH OPTIONAL
A A2 TB2-A2 BR J14-A 2 8
RDU-SIC
J16-1 BK
12V 12V TB2-12V J16 1 J16-2
GND GND TB2-GND 2 BR
OPTIONAL BR BK

TB-48V
TB-GND
FAN1-PWM TB-10V

TB-48V
TB-GND
Y PWM FAN2-PWM TB-10V

TB-48V
TB-GND
Y PWM FAN3-PWM TB-10V

TB-48V
TB-GND
Y PWM FAN4-PWM TB-10V

TB-48V
TB-GND
Y PWM FAN5-PWM TB-10V

TB-48V
TB-GND
Y PWM FAN6-PWM TB-10V

TB-48V
TB-GND
Y PWM FAN7-PWM TB-10V
TB1-GND
TB1-12V

J21-1 BK
1
J21-2 BR C NO 滤网压差开关/FILTER CLOGGED SWITCH OPTIONAL

FAN1-L
FAN1-N

FAN2-L
FAN2-N

FAN3-L
FAN3-N

FAN4-L
FAN4-N

FAN5-L
FAN5-N

FAN6-L
FAN6-N

FAN7-L
FAN7-N
GND 12V 2
3
4
J21 J21-5 BK

FAN1-FG

FAN2-FG

FAN3-FG

FAN4-FG

FAN5-FG

FAN6-FG

FAN7-FG
BL FG

BL FG

BL FG

BL FG

BL FG

BL FG
5

+
BL -

+
BK -

+
BK -

+
BK -

+
BK -

+
BK -

+
BK -
J1-1 J1-2 OPTIONAL

P C
W T
J21-6 BR 浮球开关/FLOAT LEVER SWITCH
TB2-B1 BK J22-B 1 6

R
B1 J21-7 BK TB2-37 37
A1 TB2-A1 BR J22-A 2 J22 7
J21-8 BR TB2-38 38 远程开关机/REMOTE SHUTDOWN DEVICE
8
FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 FAN7
SAS1 BK J25-1 1
J28-1 BK TB1-24V 24V Y/G Y/G Y/G Y/G Y/G Y/G Y/G
送风温度传感器1 1
BK J25-2 J28-2 BK Y1-1 加湿电磁阀
SUPPLY AIR SENSOR 1 2 2
SAS2 BK J25-3 3
J25 3
J28-3 BK TB2-75 75 公共告警 0V TB1-0V Y1-2 HUMIDIFY SOLENOID VALVE GND GND GND GND GND GND GND
送风温度传感器2 J28-4 BR TB2-76 76
SUPPLY AIR SENSOR 2 BK J25-4 4 4 COMMON ALARM
J28 5 J28-5 BK TB1-24V 24V
J28-6 BK TB2-63 63 Y1 液路电磁阀
6
TB2-64 64 Y1 XPE OPTIONAL

DI1
DI2
DI3
DI4

DI5
DI6
DI7
7 FREON SOLENOID VALVE
8
TB1-0V

DTS 9
排气温度传感器 BK J8-1 1 10
DISCHARGE TEMPERATURE SENSOR BK J8-2 J8
2 0V

D1 D2 D3 D4 D5 D6 D7 D8 TB3 远程温度传感器
J38 10DI-J1 10DI-J2
J38 REMOTE TEMP
HP-5V R J23-1 1 10DI CARD SENSOR *
高压传感器 HP-VIN BR J23-2 2 J23
HIGH PRESSURE TRANSDUCER HP-GND BK J23-3 3

A1 B1
J34-1 O
TB1-B1
TB1-A1

1 1
J34-2 R
2 2
BK BR J33-3 3 J33 J34-3 YE
2 J39-A J34
3
J34-4 BK
执行阀体A
J39
1 J39-B BR BK J33-4 4 4
J34-5 BR
EEV A
5
6

吸气温度传感器
STS
BR
BK
J38-1 1
J38-2 2 J38
电子膨胀阀控制器
SUCTION TEMPERATURE SENSOR
STS EEV CONTROLLER
TERMINAL BLOCK/端子排 J32
LP-5V R J43-1 1
TB1 低压传感器 LPT LP-GND BR J43-2 2
J43
1 2
LOW PRESSURE TRANSDUCER LP-VIN BK J43-3 3
TB2 TB3
J32-1
J32-2

24V 24V 24V 12V 12V B1 B1 B1 95


N N N N N 0V 0V 0V GND GND A1 A1 A1 94
BK
BR

N N N N N 0V 0V 0V GND GND A1 A1 A1 94 51 24 37 38 70 71 75 76 A1 B1 A2 B2 12V GND 61 62 63 64


24V 24V 24V 12V 12V B1 B1 B1 95
TB1-24V
TB1-0V

备注/Notes: 24V 0V
Factory supplied line voltage wiring/出厂线电压线路
配线色标/Wire color code:
Ethernet or CAN wiring/以太网或CAN线路
Factory supplied 24 volt wiring/出厂24V线路 BK-Black/黑色
BL-Blue/蓝色
Device own line/器件自带线
BR-Brown/棕色
Inline quick disconnect/线上快速对插端子
WH-White/白色
Terminal block connector/线缆端子 Y/GN-Yellow green/黄绿色
Naked crimping connector/裸压端子 O-Orange/橙色
P-Purple/紫色
R-Red/红色
YE-Yellow/黄色
GR-Grey/灰色

Proprietary and Confidential ©2023 Vertiv Group Corp.


CR066 Circuit Diagram

双电源配置/DUAL POWER SUPPLY OPTIONAL

8
7 J01-7 BL N
6 L3
交流检测板 5 J01-5 GR L2
J01
ACM02A2 4
J01-3 BR
L1

TB1-N
TB1-N
TB1-N

TB1-N

TB1-N
TB1-N
3
2 TB6 L1 L2 L3 PE
1 J01-1 BK N N N N N N
PE
J03 J29 J02
Y/G J03 1 1
J02-1 BK
1 2 3 4 5 6 7 8 L1 L2 L3
变压器空开 1 3 风机空开 1 3 电加热空开 1 3 5 压缩机空开 1 3 5 室外机空调
TRANSFORMER FAN HEATER COMPRESSOR OUTDOOR
2 4 BREAKER 2 4 6 BREAKER 2 4 6 TB2
PE BREAKER BREAKER 2 4 TB2-70
70
QF2 QF1

QF3-4

QF4-2
QF4-4
QF3-2
QF3

QF2-2
QF2-4

QF1-2
QF1-4
QF1-6
QF4 TB2-71
71
6A 25A 20A 32A
变压器TC
TRANSFORMER TC BK BK BK BK BK BK BK BK
100VA BK BK BR BL

KAC-A1
KAC-13
KAC-31

KMA-A1

KMA-01

KMB-01
KMB-A1
1 2 3 4 5 6 7 8

KAD-A1
KAD-13
KM1-161

RD1-2
RD2-2
RD3-2
RD4-2
RD5-2
KMA-1
KMA-3
KMA-5
KMA-7

KMB-1
KMB-3
KMB-5
KMB-7
KM1-21
KM1-153
KM2-1
KM2-3
KM2-A1

KM1-A1
KM1-1
KM1-3
KM1-5
TB1-0V TB1-0V BK TC-6 4
J30
1 J31-1 BK 0V 3 BK
电加热接触器 压缩机接触器
J31
L CAN-L 2 J31-2 BK
TB1-24V 24V TB1-24V BK TC-5 TC-2 HEATER 1 3 5 21 COMPRESSOR
A1
1 3 5 21 153 161 A1 13 31 A1 13 31 A1 1 3 5 7 01 1 3 5 7 01 A1 RD1 RD2 RD3 RD4 RD5
H CAN-H
CAN A1 KAC KAD KMA KMB
TC-1 BK CONTACTOR CONTACTOR A2 14 32 A2 14 32 A2 2 4 6 8 02 2 4 6 8 02 A2 RD1 RD2 RD3 RD4 RD5
A2 2 4 6 22 A2 2 4 6 22 154 162
1 J13-1 BK KM2 KM1

KAC-A2
KAC-14
KAC-32

KAD-A2
KAD-14

KMA-A2

KMA-02

KMB-02
KMB-A2
KM1-154
KM2-A2

RD1-1
RD2-1
RD3-1
RD4-1
RD5-1
KM1-162

KMA-2
KMA-4
KMA-6
KMA-8

KMB-2
KMB-4
KMB-6
KMB-8
J13

KM1-A2
2 J13-2 BK

KM1-22
KM2-2
KM2-4
显示屏 9A 32A

KM1-2
KM1-4
KM1-6
62 TB2-62 BR J20-CANL 2
TB2-61 BK J20-CANH 1 J20
GHMI 61
1 J18-1 BK BK BR BR BL BL BK BK BK BK BK
DISPLAY 2
过电压抑制器
+ PWR-+ TB1-24V 24V J18 3 J18-D06 BK
OVERVOLTAGE
PWR -
PWR-- TB1-0V 0V 4 J18-D07 BK
TB1-94 94 HPS HPS SUPPRESSOR
PWR-GND 5 J18-D08 BK 95 TB1-95 BK
高压开关
N
HIGH PRESSURE SWITCH Y/G Y/G
BK
PE PE

J1-1L
J1-1N

J1-2L
J1-2N
PE
7 4 2 3 1 L1 L2 L3

EH1-L
EH2-L
EH3-L
EH4-L
KA1 J41 J41

CAN

CAN
8 J1 L N L N J1
6 5 BR BR BR BR 压缩机驱动
R48-2000E3 R48-2000E3 J16

QS1-1
QS1-3
QS1-5
QS1-7

QS2-1
QS2-3
QS2-5
QS2-7
QS1-1
QS1-3
QS1-5
QS1-7
BK BR BL
电源模块 电源模块 A1 TB1-A1
COMPRESSOR

PE

PE
回风温湿度传感器

PE
485+
N B1 TB1-B1 485- INVERTER 主空开 主空开1 1 3 5 7 1 3 5 7 主空开2
J1 J34 24VDC J21 DC+ DC- J11 J21 DC+ DC- J11 BL BL BL BL 1 3 5 7
MAIN BREAK MAIN BREAK 1 PE PE MAIN BREAK 2
RETURN AIR J1 J34 电源模块
U V W PE QS1 2 4 6 8
PE
QS1 2 4 6 8 2 4 6 8 QS2

EH1-N
EH2-N
EH3-N
EH4-N
J21-DC1+
J11-DC1-

J21-DC2+
J11-DC2-
T&TH SENSOR 63A 63A 63A
冷凝水泵
CONDENSATE BK R BL Y/G 屏蔽
L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE
PUMP

选配件 输入电源 输入电源1 输入电源2


控制板 OPTIONAL POWER POWER 1 POWER 2
1 J12-12V BK TB1-12V 12V PE
ACM05U15 J12
2 J12-GND BR TB1-GND GND

L1
L2
L3

PE
10V(1) 10V(1) 48V 48V GND GND 10V(2)10V(2) 48V 48V GND GND 压缩机
TB4 10V(1) 10V(1) 48V 48V GND GND 10V(2)10V(2) 48V 48V GND GND
TB5 COMPRESSOR
屏蔽

ZPV096
TB2
B B2 TB2-B2 BK J14-B 1 1 J15-1 BR
J15
A A2 TB2-A2 BR J14-A 2 J14 2 J15-2 BK

RDU-SIC 1 J16-1 BK
J16
2 J16-2 BR
12V 12V TB2-12V
GND GND TB2-GND 1 J19-1 BK
BR BK J19-2 BR 高压告警/HIGH PRESSURE ALARM
2
3 J19-3 BK
TB1-GND
TB1-12V

J19-4 BR J1-1 J1-2 高水位告警/HIGH WATER ALARM


4
J19 J19-5 BK
5
GND 12V J19-6 BK ST1-C ST1-NC ST2-C ST2-NC ST3-C ST3-NC ST4-C ST4-NC 电加热告警/HEAT ALARM OPTIONAL
6
7 J19-7 BK TB2-51 51 TB4 TB5
J19-8 BR TB2-24 24 1 2 地板溢水开关/WATER UNDER FLOOR SWITCH OPTIONAL
8

BK J22-B 1 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(1) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2) 48V GND 10V(2)
B1 TB2-B1 J21-1 BK
J22-A 2 J22 1
A1 TB2-A1 BR J21-2 BR C NO 滤网压差开关/FILTER CLOGGED SWITCH OPTIONAL
2
3
4
J21 J21-5 BK
BK

BK

BK

BK

BK

BK

BK

BK

BK

BK

BK

BK
5
R

R
SAS1 BK J25-1 J21-6 BR J1-1 J1-2 浮球开关/FLOAT LEVER SWITCH OPTIONAL
送风温度传感器1 1 6
SUPPLY AIR SENSOR 1 BK J25-2 7 J21-7 BK TB2-37 37
2
BL

BL

BL

BL

BL

BL

BL

BL

BL

BL

BL

BL
J21-8 BR TB2-38 38 远程开关机/REMOTE SHUTDOWN DEVICE
R

R
SAS2 BK J25-3 J25 8
送风温度传感器2 3
SUPPLY AIR SENSOR 2 BK J25-4 4
1 J28-1 BK TB1-24V 24V FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 FAN7 FAN8 FAN9 FAN10 FAN11 FAN12
2 J28-2 BK Y1-1 加湿电磁阀
3 J28-3 BK TB2-75 75 公共告警 0V TB1-0V Y1-2 HUMIDIFY SOLENOID VALVE
BR

BR

BR

BR

BR

BR

BR

BR

BR

BR

BR

BR
J28-4 BR TB2-76 76 COMMON ALARM
W

P
4
DTS BK J8-1 5 J28-5 BK TB1-24V 24V
排气温度传感器 1 J28 J28-6 BK TB2-63 63 Y1
O

O
DISCHARGE TEMPERATURE SENSOR BK J8-2 J8 6 液路电磁阀 TB5
2 TB2-64 64 Y1 XPE
7 FREON SOLENOID VALVE
8 GND
TB1-0V

9
10
0V
HP-5V R J23-1 1

DI10

DI11
DI12
高压传感器

GND
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
HP-VIN BR J23-2 2 J23
HIGH PRESSURE TRANSDUCER HP-GND BK J23-3 3 TB3
1#10DI-1 1#10DI-2 2#10DI-1 2#10DI-2
远程温度传感器
J38
J38 1#10DI CARD 2#10DI CARD REMOTE TEMP
SENSOR *

A1 B1
J34-1 O
TB1-B1
TB1-A1

1 1
J34-2 R
2 2
J39-A BR J33-3 3 J33 3
J34-3 YE
2 J34 执行阀体A
J39 BK J33-4 4 J34-4 BK
1 J39-B 4
J34-5 BR
EEV A
5
6

吸气温度传感器
STS
BR
BK
J38-1 1
J38-2 2 J38
电子膨胀阀控制器
SUCTION TEMPERATURE SENSOR
STS EEV CONTROLLER

J32
LP-5V R J43-1 1
1 2
低压传感器 LP-VIN BR J43-2 2
LPT J43
LOW PRESSURE TRANSDUCER LP-GND BK J43-3 3
J32-1
J32-2

TERMINAL BLOCK/端子排
BK
BR

TB1
TB2 TB3
TB1-24V
TB1-0V

24V 24V 24V 12V 12V B1 B1 B1 95


N N N N N 0V 0V 0V GND GND A1 A1 A1 94
24V 0V
N N N N N 0V 0V 0V GND GND A1 A1 A1 94 51 24 37 38 70 71 75 76 A1 B1 A2 B2 12V GND 61 62 63 64
24V 24V 24V 12V 12V B1 B1 B1 95

备注/Notes:
Factory supplied line voltage wiring/出厂线电压线路
配线色标/Wire color code:
Ethernet or CAN wiring/以太网或CAN线路
Factory supplied 24 volt wiring/出厂24V线路 BK-Black/黑色 P-Purple/紫色
BL-Blue/蓝色 R-Red/红色
Device own line/器件自带线
BR-Brown/棕色 YE-Yellow/黄色
Inline quick disconnect/线上快速对插端子
WH-White/白色 GR-Grey/灰色
Terminal block connector/线缆端子 Y/GN-Yellow green/黄绿色
Naked crimping connector/裸压端子 O-Orange/橙色

Proprietary and Confidential ©2023 Vertiv Group Corp.


Vertiv™ Liebert® CRV4 Series Air-cooled Precision Air Conditioners Technical Manual
© 2023 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All
other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has
been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages
resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at
Vertiv’s sole discretion upon notice.

Version 1.6