Three Phase Inverter
INVERTERS
For Thailand
SE30K
12-20
YEAR
WARRANTY
Specifically designed to work with power optimizers
Fixed voltage inverter for superior efficiency Built-in module-level monitoring with Ethernet, wireless
(98.3%) and longer strings or cellular communication for full system visibility
Quick and easy inverter commissioning directly Advanced safety features - integrated arc fault
from a smartphone using the SolarEdge SetApp protection and optional rapid shutdown
Small, lightest in its class, and easy to install IP65 for outdoor and indoor installations
Integrated type 2 DC surge protection, to better Integrated DC Safety Unit - eliminates the need for
withstand surges caused by lightning or other external DC isolators
events
Future-proofed for SolarEdge energy storage
Optional RS485 and type 2 AC surge protection solutions
solaredge.com
Three Phase Inverter
For Thailand
SE30K
SE30K-THR0IXXXX
Applicable to inverters with part number
SE30K
OUTPUT
Rated AC Active Power Output 30000 W
Maximum AC Apparent Output Power 30000 VA
AC Output Voltage - Line to Line / Line to Neutral (Nominal) 380 / 220 ; 400 / 230 Vac
AC Output Voltage - Line to Line / Line to Neutral 304 - 437 / 176 - 253 ; 320 - 460 / 184 - 264.5 Vac
AC Frequency 50/60 ± 5% Hz
Maximum Continuous Output Current (per Phase) 48.25 Aac
AC Output Line Connections 3W + PE, 4W + PE
Utility Monitoring, Islanding Protection, Configurable Power
Yes
Factor, Country Configurable Thresholds
Total Harmonic Distortion <3 %
Power Factor Range +/-0.8 to 1
Maximum Residual Current Injection(1) 100 mA
INPUT
Maximum DC Power (Module STC) 45000 W
Transformer-less, Ungrounded Yes
Maximum Input Voltage DC+ to DC- 1000 Vdc
Operating Voltage Range 680-1000 Vdc
Maximum Input Current 48.25 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 167kΩ Sensitivity(2)
Maximum Inverter Efficiency 98,3 %
European Weighted Efficiency 98 %
Nighttime Power Consumption <4 W
ADDITIONAL FEATURES
Supported Communication Interfaces 2 x RS485, Ethernet, Wi-Fi (optional)(3), Cellular (optional)
Smart Energy Management Export Limitation
Inverter Commissioning With the SetApp mobile application using built-in Wi-Fi access point for local connection
Arc Fault Protection Integrated, User Configurable (According to UL1699B)
Rapid Shutdown Built-in(4) (Automatic upon AC Grid Disconnect)
RS485 Surge Protection Optional
DC Surge Protection Type II, field replaceable, integrated
AC Surge Protection Type II, field replaceable, integrated
DC SAFETY UNIT (OPTIONAL)
2-pole Disconnection 1000V / 48,25A
DC Fuses (Single Pole) Optional, 25A
Compliance UTE-C15-712-1
STANDARD COMPLIANCE
Safety IEC-62109, AS3100
VDE-AR-N-4105, AS-4777, EN50438, CEI-021, VDE 0126-1-1, CEI-016, EN50549-1, EN50549-2, VDE-AR-N-4110,
Grid Connection Standards (5)
TOR Erzeuger Typ A, G99, G99 (NI), VFR 2019
Emissions IEC61000-6-2, IEC61000-6-3 Class A, IEC61000-3-11, IEC61000-3-12
RoHS Yes
INSTALLATION SPECIFICATIONS
AC Output Gland Diameter / Line cross section / PE cross section Cable diameter 19-28 mm / 4 - 16 mm2 / 4 - 16 mm2
4 MC4 pairs
DC Input with Safety Unit (6)(7)
4 Strings: Gland: Cable outer diameter 5 - 10 mm / Wire cross section 2,5 - 16 mm2
Dimensions (H x W x D) 550 x 317 x 273 mm
Dimensions with Safety Unit (H x W x D) 819 x 317 x 300 (DC Gland) mm
Weight 32 kg
Weight with Safety Unit 36,5 kg
Operating Temperature Range -40 to +60(8) ˚C
Cooling Fan (user replaceable)
Noise < 62 dBA
Protection Rating IP65 - outdoor and indoor
Mounting Brackets provided
(1) If an external RCD is required, its trip value must be ≥ 100mA
(2) Where permitted by local regulations
(3) Wi-Fi connectivity requires connection of an additional Wi-Fi component, ordered separately. For more details ask your SolarEdge sales person or refer to: https://www.solaredge.com/products/communication
(4) Inverters with rapid shutdown part number: SExxK-xxRxxxxxx
(5) For all standards refer to Certifications category in Downloads page: http://www.solaredge.com/groups/support/downloads
(6) DC input is available with MC4 or Gland connectors under the inverter part number. For more information, contact SolarEdge
(7) Only MC4 connectors manufactured by Stäubli are approved for use
(8) For power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note.pdf
© SolarEdge Technologies, Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc.
All other trademarks mentioned herein are trademarks of their respective owners. Date: 10/2021 DS-000116-1.0-THA. Subject to change without notice.