DC Solar, 1.9 / 3.

3kV LV Cable and 33kV REV-0


MV Cable Specification
Ayana Renewable Power Pvt Ltd Page 3 of 15

DC Cables up to 10mm2

The section herein describes general specifications for DC cables up to and including 10mm2
cables that shall be used for PV module interconnection and string cabling up to the combiner
box.

Standards, Codes and Reference Documents


Cables shall be compliant to most recent standards and any latest amendments developed by the
IEC and EN for UV resistant DC cables for solar PV applications. Table 1‐1 indicates list of standards
to which DC cables should conform.
Table 1‐1: Applicable DC Cable Standards
Applicable DC Cable Standards
IEC 60228, class 5 Tinned fine copper strands
UL4703 Photovoltaic Wires
IEC 60332‐1 Fire performance
Tests on electric and optical fiber cables under fire conditions ‐
IEC 60332‐3‐24 Part 3‐24: Test for vertical flame spread of vertically‐mounted
bunched wires or cables ‐ Category C
Electric cables for photovoltaic systems with a voltage rating of 1.5
IEC 62930:2017
kV DC
IEC 61034 Smoke emission
IEC 60287 Electric cables – Calculation of the current rating
IEC 60216 Temperature index and service life of over 20 years
IEC 60754‐1 Halogen‐free
IEC 60811 Resistant to chemicals and oils
EN 50618:2014 Electric cables for photovoltaic systems
IEC 60228 Conductors of insulated cables
CSN EN 61 386‐24 Specifications of HDPE pipe
IEC 62548 Photovoltaic (PV) arrays – Design requirements

Cable Design
DC PV cables of size up to 10mm² should have following properties :
 Flexible Annealed Tinned Copper Conductor as per Class 5 of EN 60228.
 Insulation: Halogen free thermosetting, electron beam Cross‐linked Polyolefin
compound.
 Outer sheath: Halogen free, low smoke, Flame Retardant Black color, electron beam
Cross‐linked Polyolefin compound (XLPO), UV resisitant,anti‐termite and anti‐
rodent.
 Cables Operating temperature range shall be from ‐50°C to +120°C.