0% found this document useful (0 votes)
34 views67 pages

2300 Closed Loop Mate (2300 CLM) Backup Controller: Product Manual 26331 (Revision A, 12/2009)

Uploaded by

nikolaymarkel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views67 pages

2300 Closed Loop Mate (2300 CLM) Backup Controller: Product Manual 26331 (Revision A, 12/2009)

Uploaded by

nikolaymarkel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 67

Product Manual 26331

(Revision A, 12/2009)
Original Instructions

2300 Closed Loop Mate (2300 CLM)


Backup Controller

8237-1132 (Ordinary Locations)


8237-1155 (Hazardous Locations)

Installation and Operation Manual


Read this entire manual and all other publications pertaining to the work to be
performed before installing, operating, or servicing this equipment.
Practice all plant and safety instructions and precautions.
General
Precautions Failure to follow instructions can cause personal injury and/or property damage.

This publication may have been revised or updated since this copy was produced.
To verify that you have the latest revision, check manual 26311 , Revision Status &
Distribution Restrictions of Woodward Technical Publications, on the publications
Revisions page of the Woodward website:
www.woodward.com/publications

The latest version of most publications is available on the publications page. If


your publication is not there, please contact your customer service representative
to get the latest copy.

Any unauthorized modifications to or use of this equipment outside its specified


mechanical, electrical, or other operating limits may cause personal injury and/or
property damage, including damage to the equipment. Any such unauthorized
Proper Use modifications: (i) constitute "misuse" and/or "negligence" within the meaning of
the product warranty thereby excluding warranty coverage for any resulting
damage, and (ii) invalidate product certifications or listings.

If the cover of this publication states "Translation of the Original Instructions"


please note:
The original source of this publication may have been updated since this
Translated translation was made. Be sure to check manual 26311 , Revision Status &
Publications Distribution Restrictions of Woodward Technical Publications, to verify whether
this translation is up to date. Out-of-date translations are marked with . Always
compare with the original for technical specifications and for proper and safe
installation and operation procedures.

Revisions—Changes in this publication since the last revision are indicated by a black line
alongside the text.

Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is
believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly
undertaken.
Manual 26331
Copyright © Woodward 2009
All Rights Reserved
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Contents

WARNINGS AND NOTICES ............................................................................III


ELECTROSTATIC DISCHARGE AWARENESS ................................................. IV
REGULATORY COMPLIANCE ........................................................................ V
CHAPTER 1. GENERAL INFORMATION ........................................................... 1
General Description ................................................................................................1
References .............................................................................................................2
CHAPTER 2. INSTALLATION.......................................................................... 3
Introduction .............................................................................................................3
Unpacking ...............................................................................................................3
Mounting Considerations ........................................................................................3
Electrical Connections ..........................................................................................10
CHAPTER 3. 2300 CLM MACHINE STATE ................................................... 17
2300 CLM State List .............................................................................................17
Watch Window Program .......................................................................................21
CHAPTER 4. SERVICE AND CONFIGURATION............................................... 26
Introduction ...........................................................................................................26
A**CONFIGURATION** .......................................................................................26
**SERVLINK CONFIRMATION** .........................................................................27
B**SPEED SETPOINTS** ....................................................................................28
C**GENERATOR APPLICATION** ......................................................................30
D**CALIBRATION** .............................................................................................31
E**MONITOR FUNC IN STATUS** ......................................................................33
F**RELAYS** ........................................................................................................34
G**ANALOG OUTPUT** ......................................................................................35
H**FORCE RELAYS**..........................................................................................36
I**REAL POWER SENSOR** ...............................................................................36
J**COMM PORT (MODBUS)** ............................................................................36
K**DISPLAY MENU** ...........................................................................................38
L**ALARMS** .......................................................................................................39
M**EMERGENCY START** .................................................................................40
N**MONITOR DI STATUS**.................................................................................41
O**SPEED PID** ..................................................................................................41
P**ACTUATOR TRANSFER** .............................................................................42
Q**TIME DELAY** ................................................................................................42
R**AUTO RAISE/LOWER** .................................................................................42
CHAPTER 5. COMMUNICATIONS ................................................................. 44
Modbus Communication .......................................................................................44
Modbus Communication Mode .............................................................................44
Port Adjustments ..................................................................................................45
For More Modbus Information ..............................................................................45
CHAPTER 6. SERVICE OPTIONS ................................................................. 46
Product Service Options .......................................................................................46
Woodward Factory Servicing Options ..................................................................47
Returning Equipment for Repair ...........................................................................47
Replacement Parts ...............................................................................................48
Engineering Services............................................................................................48
How to Contact Woodward ...................................................................................49
Technical Assistance ............................................................................................49

Woodward i
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Contents

APPENDIX A. MODBUS COMMUNICATION LIST ............................................50


APPENDIX B. SERVICE / CONFIGURE CHART ...............................................52
2300 CLM CONTROL SPECIFICATIONS .......................................................57
DECLARATIONS .........................................................................................58

Illustrations and Tables

Figure 2-1. 2300 CLM Outline Drawing (8237-1132) .............................................4


Figure 2-2. 2300 CLM Outline Drawing (8237-1155) .............................................4
Figure 2-3a. 2300 CLM Plant Wiring Diagram (sheet 1) ........................................5
Figure 2-3b. 2300 CLM Plant Wiring Diagram (sheet 2) ........................................6
Figure 2-3c. 2300 CLM Plant Wiring Diagram (notes) ...........................................7
Figure 2-3d. 2300 CLM Relays Wiring Diagram.....................................................8
Figure 2-3e. 2300 CLM Relays Wiring Diagram Notes ..........................................9
Figure 2-3f. 2300 CLM Relay Box Wiring Diagram (Actuator Relays) ...................9
Figure 2-3g. 2300 CLM Converter – for 20–160 or 20–200 mA Actuators ..........10
Figure 2-4. Installation of Wiring into Terminal .....................................................11
Figure 2-5. RS232 Pin assignments for Serial Communication Cable.................14
Figure 2-6. Typical RS-422 Communications Connections .................................15
Figure 2-7. RS-422 Terminator Locations ............................................................15
Figure 2-8. Preferred Multipoint Wiring Using Shielded Twisted-pair Cable with a
Separate Signal Ground Wire ..........................................................16
Figure 2-9. Alternate Multipoint Wiring Using Shielded Twisted-pair Cable without
a Separate Signal Ground Wire .......................................................16
Figure 3-1. Actuator Matching Criteria .................................................................19
Figure 3-2. Example of Application with Load Controllers ...................................20
Figure 3-3. Connection between PC and 2300 CLM............................................23
Figure 3-4. Setup ServLink Communication .........................................................24
Figure 3-5. Reading Control Information ..............................................................24
Figure 3-6. Watch Window Menu and Explore (Configure) ..................................25

Table 5-1. Modbus Modes ....................................................................................44


Table 5-2. Modbus Frame Definition ....................................................................45
Table 5-3. Modbus Function Codes .....................................................................45
Table 5-4. Port Adjustments .................................................................................45

ii Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Warnings and Notices


Important Definitions
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages that follow this
symbol to avoid possible injury or death.
 DANGER—Indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
 WARNING—Indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
 CAUTION—Indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.
 NOTICE—Indicates a hazard that could result in property damage only
(including damage to the control).
 IMPORTANT—Designates an operating tip or maintenance suggestion.

The engine, turbine, or other type of prime mover should be


equipped with an overspeed shutdown device to protect against
runaway or damage to the prime mover with possible personal injury,
Overspeed / loss of life, or property damage.
Overtemperature / The overspeed shutdown device must be totally independent of the
Overpressure prime mover control system. An overtemperature or overpressure
shutdown device may also be needed for safety, as appropriate.

The products described in this publication may present risks that


could lead to personal injury, loss of life, or property damage. Always
wear the appropriate personal protective equipment (PPE) for the job
Personal Protective at hand. Equipment that should be considered includes but is not
limited to:
Equipment
 Eye Protection
 Hearing Protection
 Hard Hat
 Gloves
 Safety Boots
 Respirator
Always read the proper Material Safety Data Sheet (MSDS) for any
working fluid(s) and comply with recommended safety equipment.

Be prepared to make an emergency shutdown when starting the


engine, turbine, or other type of prime mover, to protect against
runaway or overspeed with possible personal injury, loss of life, or
Start-up property damage.

On- and off-highway Mobile Applications: Unless Woodward's control


functions as the supervisory control, customer should install a
system totally independent of the prime mover control system that
Automotive monitors for supervisory control of engine (and takes appropriate
action if supervisory control is lost) to protect against loss of engine
Applications
control with possible personal injury, loss of life, or property damage.

Woodward iii
2300 CLM Closed Loop Mate Backup Controller Manual 26331

To prevent damage to a control system that uses an alternator or


battery-charging device, make sure the charging device is turned off
before disconnecting the battery from the system.
Battery Charging
Device

Electrostatic Discharge Awareness


Electronic controls contain static-sensitive parts. Observe the
following precautions to prevent damage to these parts:
 Discharge body static before handling the control (with power to
the control turned off, contact a grounded surface and maintain
Electrostatic contact while handling the control).
Precautions  Avoid all plastic, vinyl, and Styrofoam (except antistatic versions)
around printed circuit boards.
 Do not touch the components or conductors on a printed circuit
board with your hands or with conductive devices.
To prevent damage to electronic components caused by improper
handling, read and observe the precautions in Woodward manual
82715, Guide for Handling and Protection of Electronic Controls,
Printed Circuit Boards, and Modules.

Follow these precautions when working with or near the control.


1. Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as much
as possible because these do not store static electric charges as much as
synthetics.
2. Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:
 Do not touch any part of the PCB except the edges.
 Do not touch the electrical conductors, the connectors, or the
components with conductive devices or with your hands.
 When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.

iv Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Regulatory Compliance
General Installation and Operation Notes and Requirements:

The 2300 CLM is suitable for use in Class I, Division 2, Groups A, B, C, and D
per CSA for Canada and U.S. or non-hazardous locations only. These listings
are limited only to those units bearing the CSA agency identification and
hazardous location markings.

The 2300 CLM is suitable for use in Ordinary Locations per UL and CSA for
Canada and U.S. or non-hazardous locations only. These listings are limited only
to those units bearing the UL and CSA agency identification and ordinary location
markings.

Wiring must be in accordance with North American Class I, Division 2 wiring


methods as applicable, and in accordance with the authority having jurisdiction.

Connector J1 must not be used in hazardous locations.

The 2300 CLM shall be installed in a suitable enclosure. A local authority having
jurisdiction shall approve the final combination.

Connect the ground terminal to earth ground.

EXPLOSION HAZARD—Do not remove covers or connect/disconnect


electrical connectors unless power has been switched off or the area
is known to be non-hazardous.

Substitution of components may impair suitability for Class I,


Division 2, or Zone 2.

RISQUE D’EXPLOSION—Ne pas enlever les couvercles, ni


raccorder / débrancher les prises électriques, sans vous en
assurez auparavant que le système a bien été mis hors
tension; ou que vous vous situez bien dans une zone non
explosive.

La substitution de composants peut rendre ce matériel


inacceptable pour les emplacements de Classe I, Division 2,
ou Zone 2.

Woodward v
2300 CLM Closed Loop Mate Backup Controller Manual 26331

vi Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Chapter 1.
General Information

General Description
The 2300 Closed Loop Mate (2300 CLM) is a backup controller that can be used
with all types of applications (generators or mechanical loads) with engines or
turbines. The meaning of the term controller indicates that this product can
control the setpoints closed loop. It will not just keep the actuator at the same
position when the master speed control fails, but will control the speed or kW
setpoint with PID controller and will sustain the setpoint, changing the actuator
demand reacting to load changes.

The 2300 CLM assumes two states: Automatic Mode and Manual Mode.
 Automatic Mode: The main speed controller is not tripped and is controlling
the engine or turbine. The 2300 CLM is driving the actuator signal from the
main speed controller to the actuator. In this mode, the 2300 CLM is
monitoring both actuator current and the trip relay of the main speed
controller.
 Manual Mode: The 2300 CLM has detected a master speed control failure.
Because it has information about the actuator position and speed or kW, the
2300 CLM will start to control the prime mover at the same speed or kW
demand before the failure.

Since it is a controller, the 2300 CLM has discrete inputs to change (raise/lower)
the setpoints, It is possible to use 4–20 mA remote reference and also Modbus® *
Communications to change the setpoints.
*—Modbus is a trademark of Schneider Automation Inc.

If failure occurs on the main speed controller, a bumpless control transfer to the
2300 CLM will be done at the same setpoint sensed milliseconds before the
failure. This value will be used as the initial setpoint. While the problem with the
master speed control continues, the 2300 CLM PID will change the actuator
position based on load changes and will accept setpoint changes. When the
problem with the master speed has been eliminated, the 2300 CLM will use the
actuator demand matching criteria to return the control to master speed control.
This means that the 2300 CLM will be waiting for the actuator demand from the
main speed controller to reach the same value of the actuator demand that the
2300 CLM is using to control the speed/kW. When these values reach the same
value, control will automatically be transferred from Manual Mode to Automatic
Mode, without any disturbance.

When the driven load is a generator, the 2300 CLM can operate at island mode
(frequency control) or in droop mode when working in parallel to the grid or other
generator. It is possible to use actuator droop or kW droop. Usually actuator
droop is used in parallel mode at constant fuel/steam demand for each speed
setpoint and kW droop is used at constant kW demand with fuel/steam changes
for each kW setpoint. The CB Aux digital input will inform (when it is TRUE) to
operate at droop mode or frequency control (when it is FALSE).

This product can be used with mechanical loads or generators. Overspeed


Protection and Loss of MPU signal protection are active in order to have a safe
and stable control in manual mode. Other feature is that the Overspeed
Protection is active in both Manual Mode and Automatic Mode, improving the
system reliability.

Woodward 1
2300 CLM Closed Loop Mate Backup Controller Manual 26331
When a master speed control fails, the 2300 CLM will keep the same setpoint
and will provide setpoints changes. If it becomes necessary to switch off the
2300 CLM for any reason, or to remove and install it, this can be done easily
because there are relays to change the actuator connection directly to the master
speed control (see wiring diagram, Figure 2-3). In this case, the system will
operate in the same way as when the 2300 CLM is not installed.

Finally, when the master speed control is tripped/removed and an external trip
forces the prime mover to stop, the 2300 CLM will accept an emergency start
command, which has 3 setpoints, each one with its own rate and controlled
actuator opening ramp to start.

References
The following publications contain additional product or installation information on
Load Sharing and Speed Controls and related components. They can be
obtained from the Woodward website (www.woodward.com/publications) or
ordered from any Woodward office.

Manual Title
25070 Electronic Control Installation Guide
25195 Governing Fundamentals
82384 SPM-A Synchronizer
82510 Magnetic Pickups and Proximity Switches for Electronic Governors
82715 Guide for Handling and Protection of Electronic Controls, Printed
Circuit Boards, and Modules

Product
Spec Title
82383 SPM-A Synchronizer
82516 EG-3P/-6P/-10P Actuator
82575 EGB-1P/-2P Governor/Actuator
03202 Woodward Watch Window Standard

2 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Chapter 2.
Installation

Introduction
This chapter contains general installation instructions for the 2300 CLM control.
Power requirements, environmental precautions, and location considerations are
included to determine the best location for the control. Additional information
includes unpacking instructions, electrical connections, and an installation
checkout procedure.

Unpacking
Before handling the control, read the “Electrostatic Discharge Awareness”
information on page iv. Be careful when unpacking the electronic control. Check
the control for signs of damage such as bent or dented panels, scratches, and
loose or broken parts. If any damage is found, immediately notify the shipper.

Mounting Considerations
This product is intended for installation in a “closed electrical operating
area” or in an enclosed industrial control cabinet. Consider these
requirements when selecting the mounting location:
 Adequate ventilation for cooling
 Space for servicing and repair
 Protection from direct exposure to water or to a condensation-prone
environment
 Protection from high-voltage or high-current devices, or devices which
produce electromagnetic interference
 Avoidance of vibration
 Selection of a location that will provide an operating temperature range of
–40 to +70 °C (–40 to +158 °F)
 The control must NOT be mounted on the engine or turbine.

Woodward 3
2300 CLM Closed Loop Mate Backup Controller Manual 26331

13.750

15.281 MAX

6.875
.750

2300 CLO SED LO O PM ATE


BACK U P CO NTRO LLER
7,219 MAX

6,626

9.125

Figure 2-1. 2300 CLM Outline Drawing (8237-1132)

Figure 2-2. 2300 CLM Outline Drawing (8237-1155)


(Hazardous Locations, external cover installed)

4 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

NOT USED

ACTUATOR/HP OUTPUT

ANALOG OUTPUT (4-20 mA)

ACTUATOR/HP INPUT (4-20 mA)

REMOTE REFERENCE (4-20 mA)

SPEED SENSOR INPUT (1-30Vac RMS)

Figure 2-3a. 2300 CLM Plant Wiring Diagram (sheet 1)

Woodward 5
2300 CLM Closed Loop Mate Backup Controller Manual 26331

DISCRETE INPUTS WITH INTERNAL POWER SUPPLY

24 VDC POWER, USED WHEN


POWERING DISCRETE INPUTS

MAIN SPEED CONTROLLER TRIP RELAY STATUS

SYSTEM SHUTDOWN COMMAND

CLOSE FOR DROOP - GENERATORS

RAISE SPEED/KW LOAD

LOWER SPEED/KW LOAD DISCRETE INPUTS

FORCE TO AUTO/EMERGENCY START TRIGGER

RESET ALARMS

NOT USED

DISCRETE INPUTS WITH EXTERNAL POWER SUPPLY

NOT USED WHEN USING


EXTERNAL POWER SUPPLY

18-40 Vdc EXTERNAL POWER


SUPPLY INPUT
(100mA MAX AT 24 Vdc)

MAIN SPEED CONTROLLER TRIP RELAY STATUS

SYSTEM SHUTDOWN COMMAND

CLOSE FOR DROOP - GENERATORS

RAISE SPEED/KW LOAD

LOWER SPEED/KW LOAD DISCRETE INPUTS

FORCE TO AUTO/EMERGENCY START TRIGGER

RESET ALARMS

NOT USED

CPU OK OUTPUT

TRIP OUTPUT - ENERGIZES TO TRIP


DISCRETE OUTPUTS
SOLID STATE RELAY DRIVERS
CONFIGURABLE RELAY #1

CONFIGURABLE RELAY #2

Figure 2-3b. 2300 CLM Plant Wiring Diagram (sheet 2)

6 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Figure 2-3c. 2300 CLM Plant Wiring Diagram (notes)

Woodward 7
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Figure 2-3d. 2300 CLM Relays Wiring Diagram

8 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Figure 2-3e. 2300 CLM Relays Wiring Diagram Notes

Redundant Relay Wiring

Single Relay Wiring

Woodward reference for relays: P/N 1731-2065

Figure 2-3f. 2300 CLM Relay Box Wiring Diagram (Actuator Relays)

Woodward 9
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Figure 2-3g. 2300 CLM Converter – for 20–160 or 20–200 mA Actuators

Electrical Connections

Due to the hazardous location listings associated with this product,


proper wire type and wiring practices are critical to operation.

Do not connect any cable grounds to “instrument ground”, “control


ground”, or any non-earth ground system. Make all required
electrical connections based on the wiring diagrams.

All inputs and outputs are made through screwless spring-actuated terminal
blocks. For EMI reasons, it is recommend that all low-current wires be separated
from all high-current wire.

The spring clamp can be actuated using a standard 2.5 mm or 3/32 inch flat
bladed screwdriver. The terminal blocks accept wires from 0.08–4 mm² (27–12
AWG). Two 0.8 mm² (18 AWG) or three 0.5 mm² (20 AWG) wires can be easily
installed in each terminal. Wires for the fixed mounted power terminals should be
stripped 5–6 mm (0.22 inch) long.

10 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

It is recommended that stranded wire be used for connections to the


terminal block. Do not tin (solder) the wires that terminate at the
terminal blocks. The spring-loaded terminal blocks are designed to
flatten stranded wire and if those strands are tinned together, the
connection loses surface area and is degraded.

Shields and Grounding


An individual shield termination is provided at the terminal block for each of the
signals requiring shielding. All of these inputs should be wired using shielded,
twisted-pair wiring. The exposed wire length beyond the shield should be limited
to one 25 mm (1 inch). Relay outputs, contact inputs and power supply wiring do
not normally require shielding, but can be shielded if desired.

The 2300 CLM is designed for shield termination to earth ground at the control. If
intervening terminal blocks are used in routing a signal, the shield should be
continued through the terminal block. If shield grounding is desired at the
terminal block, it should be ac coupled to earth. All other shield terminations
except at the control should be ac coupled to earth through a capacitor. A 1000
pF, 500 V capacitor is sufficient. The intent is to provide a low impedance path to
earth for the shield at frequencies of 150 kHz and up. Multiple direct connections
of a shield to earth risk high levels of current to flow within the shield (exception,
see note below on cabinet installations).

Shields can be grounded at both ends (2300 CLM and load) if the cable length is
sufficiently short (within a cabinet) to prevent ground loop current in the shield.

Cabinet Installations: If the 2300 CLM is installed in a cabinet,


shielded I/O can be terminated directly to the cabinet (earth ground)
at the entry to the cabinet, as well as at the control.

For EMC reasons, it is recommend that all low-current wires be


separated from all high-current wires. Input Power ground terminal
should also be wired to earth ground.

Figure 2-4. Installation of Wiring into Terminal

Woodward 11
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Power Supply Connections


The 2300 CLM requires a voltage source of 18 to 40 Vdc, with a current capacity
of at least 900 mA for operating power. If a battery is used for operating power,
an alternator or other battery charging device is necessary to maintain a stable
supply voltage.

Connect 18–40 Vdc input power to terminals 45(+) and 46(–).

The 18–40 Vdc input power must be supplied from a power


supply/battery charger certified to IEC standard with SELV (Safety
Extra Low Voltage) classified output. The installer should properly
size wiring and fusing for the input power and PT/CT circuits.

Emergency Stop and External Trip


As indicated at Fig 2-3d all external trip conditions and the emergency stop
button must be wired to both master speed control and 2300 CLM.

The trip command from master speed control is connected in parallel (AND
Logic) to 2300 CLM. In this case, both master speed control and 2300 CLM must
receive this command when the trip action is needed.

Potential Transformer Connections


The control’s potential transformer inputs accept line-to-line voltages of 90 to 240
Vac (refer to the plant wiring diagram, Figure 2-3). Connect the potential
transformer secondary leads to the following terminals:
Phase A to Terminal 1
Phase B to Terminal 2
Phase C to Terminal 3

Current Transformer Connections


The control’s current transformer inputs accept a current range of 0 to 7.2 A
(refer to the plant wiring diagram, Figure 2-3). Connect the current transformer
leads to the following terminals:
Phase A to Terminals 4 & 5
Phase B to Terminals 6 & 7
Phase C to Terminals 8 & 9

Discrete Input Connections


In general, discrete inputs must change state for a minimum of 15 milliseconds for
the control to sense and register a change in state. All contact inputs accept dry
contacts. Contact wetting voltage is available through terminals 28 and 29. If
desired, an external 18-40 Vdc power source can be used for the circuit wetting
voltage. In this case terminal 30 (contact input common) must be connected to the
external power source’s negative common to establish a common reference point.
Each contact input pulls 3 mA when closed and requires at least 14 Vdc to
recognize a closure command. See Figure 2-3b for wiring information and see the
2300 CLM Control Specifications on the inside back cover for input specifications.

12 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
A positive voltage on any discrete input terminal is sensed by the control as a
closed contact or “TRUE” state. With no voltage applied to a discrete input
terminal the control senses an open contact or “False” state.

For power loading reasons, it is recommended that the control’s internal 24 Vdc
not be used to power other external equipment.

Discrete inputs with cable lengths greater than 30 meters that are
used for critical functions, such as emergency stop, should not be
floated in either an on or off state. These inputs should be switched
to +24 Vdc or ground.

Actuator Output
Connect the unit’s actuator wires to the control’s actuator driver output on
terminals 13(+), 14(–), and 15(shield). This output’s current range is software
configurable and can be programmed to output a drive current of 20–160 mA, or
4–20 mA. Do not connect the shield wire to the actuator or any other point. Verify
that the output’s shield wire has continuity its entire distance to the actuator and
is insulated from all other conducting surfaces. The wiring diagram (Fig. 2-3c) will
show how this output is connected.

Actuator Input
This input receives the actuator/HP demand from the main speed controller
(terminals 19+ and 20-).

Remote Reference
This input is 4–20 mA type. It will accept a remote reference of speed or kW to
change these setpoints when the 2300 CLM is at manual mode.

MPU Speed Sensor Input


To sense speed, the control accepts a signal from a passive magnetic pickup unit
(MPU) mounted off a gear connected or coupled to the turbine’s rotor. Connect
the MPU speed sensor to terminals 25, 26, and 27(shield). This input is limited to
a frequency range of 100–24 950 Hz and a voltage range of 1.7–35 Vac (it needs
the voltage above 2.7 Vac in case of a signal above 13 000 Hz). Verify that the
input’s shield wire has continuity its entire distance to the input sensor and is
insulated from all other conducting surfaces.

With proper MPU, gear size and MPU-to-gear clearance, speed measurement
should be capable down to 100 Hz. Check the speed sensor for visible damage.
Standard MPU clearance is recommended to be between 0.25 and 1.0 mm
(0.010 and 0.040 inch) at the closest point. Make sure that the gear has less than
0.5 mm (0.020 inch) diametric run out. See manual 82510, Magnetic Pickups and
Proximity Switches for Electronic Governors.

Woodward 13
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Relay Driver Outputs (Terminals 41–44)


The 2300 CLM has four discrete output driver channels, Terminals 41, 42, 43,
and 44.

These discrete outputs are low-side drivers with a maximum output current of
160 mA. The discrete output drivers are isolated from the control’s internal power
supply (but not from each other) and are powered by an external +12 Vdc or +24
Vdc source connected at terminals 39(+) and 40(–) (refer to Figure 2-3 for plant
wiring information).

Analog Output (4–20 mA)


Connect readout wiring to terminals 16(+), 17(–), and 18(shield) to use the
control’s 4–20 mA Analog Output.

The analog output can be programmed as readout of the following variables:


actual speed, speed reference to the PID, actuator input (mA), actuator output
(mA), PID output (%), remote reference (rpm), active power (kW).

Communication Port
The control’s serial communications port is used to configure and service the
unit, as well as communicate to a Human Machine Interface (HMI) or plant
distributed control system (DCS).

The communication port must be connected with an approved


jacketed serial communication cable. The connector must be
secured to the 2300 CLM to prevent contact with other circuits.

RS-232
See Figure 2-5 for cable connection.

2301D-ST

Figure 2-5. RS232 Pin assignments for Serial Communication Cable

14 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

RS-422
See Figure 2-6 for termination and cable connection example.

Figure 2-6. Typical RS-422 Communications Connections

Termination
For RS-422, termination should be located at the receiver when one or more
transmitters are connected to a single receiver. When a single transmitter is
connected to one or more receiver, termination should be at the receiver farthest
from the transmitter. Figure 2-7 is an example.

Figure 2-7. RS-422 Terminator Locations

Grounding and Shielding


The RS-422 specifications state that a ground wire is needed if there is no other
ground path between units. The preferred method to do this is to include a
separate wire in the cable that connects the circuit grounds together. Connect the
shield to earth ground at one point only. The alternate way is to connect all circuit
grounds to the shield, and then connect the shield to earth ground at one point
only. If the latter method is used, and there are non-isolated nodes on the party
line, connect the shield to ground at a non-isolated node, not at an isolated node.
Figures 2-8 and 2-9 illustrate these cabling approaches.

Woodward 15
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Non-isolated nodes may not have a signal ground available. If signal


ground is not available, use the alternate wiring scheme in Figure 2-9
with the signal ground connection removed on those nodes only.

Figure 2-8. Preferred Multipoint Wiring Using Shielded Twisted-pair Cable with a
Separate Signal Ground Wire

The SG (signal ground) connection is not required if signal ground is


unavailable.

Figure 2-9. Alternate Multipoint Wiring Using Shielded Twisted-pair Cable without
a Separate Signal Ground Wire

16 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Chapter 3.
2300 CLM Machine State

2300 CLM State List


This chapter illustrates all control modes combinations when using the 2300 CLM
backup controller.

Automatic Mode (Controlled by Main Speed Controller)


The conditions below indicate all cases when Automatic Mode is active in the
2300 CLM. This state means that the actuator output is equal to the actuator
input.

The speed is below the threshold value programmed in the 2300 CLM. In this
situation, the control mode will be forced to automatically ignore whether the
main speed controller is tripped or not. This is a protection against loss of MPU
signal. If the 2300 CLM loses the MPU signal and the control mode is manual,
the mode will be forced to automatic. If the control mode is automatic it will be
kept in automatic mode even with the main speed controller tripped. If the
machine is being driven by the 2300 CLM at the time that the loss of MPU
occurs, a shutdown will be indicated on the 2300 CLM as a warning of MPU loss.

The trip relay AND the actuator demand from the master speed control do not
indicate a trip condition. The relay is closed and the actuator current is at the
programmed range.

Manual Mode (Controlled by 2300 CLM)


The 2300 CLM is controlling all loops. The setpoints can be changed and the
2300 CLM will be analyzing the conditions to return from manual to automatic
mode. The conditions to accept a manual mode are:
 The speed is greater than the threshold value
AND
 The trip relay from the main speed controller is open
OR
 The actuator current from the main speed controller is out of range

Emergency Start Sequence (Controlled by 2300 CLM)


In the situation when the main speed controller is tripped, and the prime mover
was stopped by an external trip, it will be necessary to re-start the prime mover
with the main speed controller not available. In this case, the 2300 CLM will
accept an Emergency Start Command. The conditions and sequence are listed
below:
 The prime mover is stopped and the main speed controller is tripped.
 Hold the force to auto mode (Digital Input F) at closed state for at least 5
seconds.
 The actuator will start to move from 0% to the maximum actuator position at
start sequence (configurable) using the actuator rate value (%/s; also
configurable).

Woodward 17
2300 CLM Closed Loop Mate Backup Controller Manual 26331
 If the sensed speed is greater than Override Speed, the actuator ramp is
disabled, the speed 2300 CLM PID will start to control the prime mover
speed at Start Speed Setpoint.
 If the actuator reaches maximum position at start sequence but the override
speed was not detected, automatically the actuator will return to 0% and an
other command to Emergency Start Sequence will be necessary.
 If an MPU signal is sensed, the PID will use the Start Speed Setpoint to
control the prime mover.
 Use the command Raise Speed/Load to Ramp from Start Speed to Low Idle
Speed (this ramp has a configurable rate).
 Use the command Raise Speed/Load after reaching Low Idle Speed to move
the setpoint to High Idle Speed (configurable rate).
 Use the Raise Speed/Load command to move from Hi-Idle to Sync/Rated
Speed using a configurable rate to finish the emergency start sequence.
 If there are conditions to transfer from manual mode to automatic mode, the
2300 CLM will accept to change to automatic mode during the start
sequence.

The Raise Command can be sent via Hardware, Modbus Comm, or


ServLink/Watch Window.

Digital input F shares the Force to Automatic Mode function and Emergency Start
Sequence function. These functions have an Exclusive OR logic. The conditions
that are permissive for one are inhibiting the other one and vice-versa.

CPU OK is ON, the 2300 CLM control mode is Automatic and no trip exists on
master speed control

The same actuator(s) current at the master speed control are being sent by the
2300 CLM to the actuator. The 2300 CLM will be monitoring the actuator current
and the trip relay state to change to Manual Mode.

CPU OK is OFF
Offline State. A 2300 CLM hardware failure was detected or it has no power
supply. In this case, the system will operate exactly at the same way when the
2300 CLM is not installed. The actuator relays provide this security action. No
transfer is possible, and no backup exists.

CPU OK is ON, the 2300 CLM control mode is Manual, and the main speed
controller is still tripped
The Speed/kW is active at 2300 CLM. It is possible to change setpoints (speed,
kW). The 2300 CLM is waiting for a valid state of main speed controller trip relay
and the actuator demand from main speed controller.

CPU OK is ON, the 2300 CLM control mode is Manual, and a trip state no
longer exists at the main speed controller (Master Ready to Start)
The 2300 CLM will understand that the problem with the main speed controller
was eliminated, and transferring to the main speed controller is possible. It
means that the trip relay at master is closed, its actuator current is not out of
range, and the 2300 CLM is controlling the loops. At this moment, the 2300 CLM
will be waiting for the actuator matching criteria to change to Automatic Mode.
This is the case when it waits until the actuator demand at main speed controller
becomes equal to the actuator demand from 2300 CLM PID to do the transfer. It
is a bumpless transfer mode because no speed/kW disturbance is sensed.

But if desired, after all the conditions described above, it is possible to bypass the
actuator matching criteria using the force to automatic mode command. In this
case, the control will be changed to manual mode and a speed/kW disturbance
will be sensed.
18 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Manual to Automatic Transfer Trend

Act. Demand

A B C
time
2300 CLM ACTUATOR DEMAND
MAIN SPEED CONTROLLER DEMAND

Figure 3-1. Actuator Matching Criteria

If a bumpless transfer is necessary to transfer the control from 2300 CLM to main
speed controller, consider the trend above.
 A trip at main speed controller was detected and the 2300 CLM is controlling
the prime mover.
 Time A: The main speed controller is still tripped.
 Time B: The main speed controller is operational, reset, and the actuator
current is at minimum.
 Time C: The actuator demand from main speed controller is increasing and
when it reaches the same value of actual position demand given by the 2300
CLM PID, the transfer to automatic mode will occur.

The actuator demand from main speed controller will increase if the
speed setpoint at main speed controller is greater than the actual
MPU measured value. If the controlled variable is the load (kW) the
same concept is applied to the kW demand. To provide this condition
use manual commands to raise the setpoint at main speed controller
or at load controller. The raise and lower pulses to the main speed
controller or to the load controller can be managed by the 2300 CLM
via two discrete outputs that can be configured for this purpose.

The 2300 CLM can indicate via digital output (configurable) when this condition
was reached (Time C). A digital output can be programmed as transfer indicator.
It will emit pulses with variable frequency If the difference between the actuator
input and the actuator output is big the pulses will have a slower frequency.
When this difference becomes small the pulses will have a faster frequency. This
indicator will only emit pulses when it’s in Manual mode and a run command was
set on the main speed controller.

If at time B a force to automatic mode command is sent to 2300 CLM, it will not
wait for the current criteria and the control will be transferred automatically to the
main speed controller (with disturbance).

Woodward 19
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Manual to Automatic Transfer Using Load Controllers


When the driven load is a generator and a Synchronizer/Load Controller is used
to synchronize the generator with the grid and to control the active power
(DSLC™, EGCP, GCP) some additional wiring is suggested. These
considerations are only valid for load controllers. Consider this wiring example:

HP

LOWER LOAD
RAISE LOAD

RAISE SPEED
MPU
2300 CLM
LOWER SPEED
TC

TP

SPEED BIAS MPU


Synch/Load Ctrl Master Spd Control
COM Gen Brk DI COM Gen Brk DI

NC contact. This relay must be energized when


Manual Mode is Active

Gen Breaker Status Gen Breaker Status

Figure 3-2. Example of Application with Load Controllers

Synchronizers and Load Controllers


Some conditions are presumed to be active:
 The Speed Bias is used to control the active power.
 The Gen Breaker status will determine if the speed control will accept the
speed bias signal or not.
 With the Gen Breaker Open, working at Manual Mode and it is possible to
transfer to Automatic Mode, do it before synchronization.
 With the Gen Breaker Closed and Manual Mode State but it is possible to
transfer to Automatic Mode, the commands Raise/Lower must be sent to
Load Controller. The Load Controller must be at Droop Mode (Manual
Mode).
 If the Gen Breaker status is open for the load controller and it is has a valid
TP and TC measurements, it will be operating at kW Droop Mode. This is the
reason to install a contact as shown to open the breaker contact for the load
controller when in manual mode. In this case, program one digital output at
2300 CLM for this function. If there are generators sharing the load, this
procedure will inform to the load-sharing network that this specific generator
is out of network control. It is being operated at manual mode.
 Commands to Raise/Lower Load at the Load Controller when in droop mode
can increase/decrease the speed bias value at the situation described above.

20 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
 When 2300 CLM is in manual mode and the Gen Breaker is Closed, the
speed bias can change the speed setpoint at the speed control, increasing
the active power (actuator output) with Load Controller in Droop Mode.
 Normally the Generator Breaker Status can determine if the load controller is
at Droop Mode or not. If the load controller cannot assume a droop state with
this condition, use the available way to change the control mode to droop in
function of the state of 2300 CLM (Auto Mode=Control ON, Manual
Mode=Droop).

The conditions above are valid for a generator operating synchronized with other
generators/grid. If the condition is a generator operating at island mode, be very
careful with these commands to increase load because an overfrequency can
occur if the increasing load pulses were sent many times.

If these all conditions are valid, use commands to increase the load at the load
controller. When the speed bias starts to increase, the actuator current will start
to increase at main speed controller and the transfer will occur at the same way
as described for speed controllers (mechanical Loads).

Synchronizers Only
In this case, the synchronizer will send pulses or analog signal to adjust the
generator frequency to the grid and will be waiting for synch window, dwell time,
slip window to close the generator breaker. After this, the main speed controller
will operate at droop mode (if in parallel mode), frequency control at island mode
or isolated bus frequency controller (2 or more generators in parallel mode and
out of the grid). If the system has this configuration, the pulses to raise
speed/load will be sent only to the speed control. If the generator is operating at
droop mode, it is indicated that it is in parallel with other generator in frequency
mode or in parallel with the grid. If it is operating at island mode, there is an
overfrequency possibility. Do not use a setpoint greater then 1% of synch. speed
to the generator in frequency control to transfer the control. No problems are
related to these commands to generators in droop mode.

Watch Window Program


Watch Window is the primary communications tool for Woodward controls that
support the ServLink protocol. Watch Window runs on a PC connected to the
control system through a serial communications port. The PC may be
permanently connected to the control or only as needed. The communications
server, ServLink I/O Server, is included in the same CD-ROM with the Watch
Window software.

An “inspector” provides a window for real-time monitoring and editing of all


control Configuration and Service Menu parameters and values. Custom
“inspectors” can easily be created and saved. Each window can display up to 28
lines of monitoring and tuning parameters without scrolling. The number with
scrolling is unlimited. Two windows can be open simultaneously to display up to
56 parameters without scrolling. Tunable values can be adjusted at the inspector
window. Watch Window communicates with the control through an RS-232 cable
connection to the comm. port configured as a point-to-point only ServLink Server.

Watch Window is a typical Windows application that provides a powerful and


intuitive interface. The menu structures are familiar to Windows users. Variable
navigation is provided through the Explorer window similar to Windows Explorer.

Woodward 21
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Watch Window performs these primary functions:
 Monitoring and Tuning of Control Variables—Watch Window presents
variables in a tabular format. The user chooses the variables to view. Multiple
pages of variables can be created, each with useful parameters for various
troubleshooting or tuning procedures. The user can toggle between pages
depending on the task being performed.
 Control Configuration and Set Point Management—Watch Window can
upload or download all tunable variables from the control system. This
feature allows a user (e.g., fleet owner, distributor, packager) to upload (and
save) all tunable parameters from one control and download the same
settings to other controls for similar turbine configurations.

Watch Window version 1.05 and higher, allows for automatic generation of
inspector sheets. Click on the Q icon (Quick Inspector) on the tool bar. A sheet
will automatically be created from each Service and Configure Header
programmed into the control. Multiple inspectors can be created to allow for
viewing more than one sheet at a time.

To enter the I/O Lock mode and enable a configure value to be entered,
click on the I/O Lock icon on the Tool Bar. Because the values set in Configure
are critical to turbine operation, it is not safe to operate the prime mover while
these parameters are being configured. In the Configure mode the control
outputs will be set to off state and the microprocessor will stop executing the
application code. The control will have to be reset to continue operation.

The Reset icon allows the microprocessor to store the configure


parameters, to return the outputs to their active state and to resume executing
the application software.

When the tuning or setting of parameters is complete, the values must be


saved in the control’s non-volatile memory. Go to the Tool Bar and click the
PROM icon for Save Values. The values will be saved in non-volatile memory
and will be unaffected by loss of power to the control.

If an application configuration has been previously saved to a *.CFG file,


the saved set of parameters can be loaded into the 2300 CLM as a group by
selecting the Load Application Settings icon.

To save the configuration to a file in the external computer for backup or


download later into another 2300 CLM, select the Save Application Settings icon.
All the tunable values presently set in the control will be saved to a file and can
be loaded into this 2300 CLM to reprogram it to the saved values or into another
2300 CLM at a later time.

22 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Install Watch Window Software


Woodward’s Watch Window Standard configuration and service tool may be
downloaded at no cost from the Woodward website (www.woodward.com). As
an alternative a Watch Window CD Install Kit may be purchased from the nearest
Woodward distributor. Once downloaded, select the kit’s Setup.exe program on
the computer on which you wish to install the Watch Window software program.
Please refer the product specification 03202 for detailed installation procedures.

Connect PC to 2300 CLM


The connection of a computer is only required for calibration and setup of the
2300 CLM on a prime mover (Figure 3-1). The computer and Watch Window
software program are not required or necessary for normal operation of the
control. The cable is a 9-pin female to 9-pin male, null modem cable.

2300

9-pin D sub
Connector

RS-232
Serial Cable

Note Book PC

Figure 3-3. Connection between PC and 2300 CLM

Apply Power to the 2300 CLM


At power-up, the 2300 CLM runs through its boot-up routine and performs a set
of initial diagnostics to verify CPU, memory and bus health. This boot-up routine
takes approximately 30 seconds to execute. During this time, the control’s red
status LED (located between terminals 27 and 28) should be on. When boot-up
is complete, the application program code begins running, the control outputs will
be enabled and system control will begin - the control’s red status LED will be
turned off and should remain off as long as the control is running.

Woodward 23
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Initial 2300 CLM Communications


Before communications can begin between the Watch Window program and a
control, a network definition file must be created. Once this network definition file
is created and saved, it never has to be recreated.

The 2300 CLM will be changing the protocol mode between Modbus and
ServLink Interface to check what mode is being requested. When a valid link is
detected, it will stop to switch the protocol mode. If Modbus is detected and fails,
it will re-start to check the link. If the ServLink Protocol has been detected, it is
necessary to use a command at Watch Window to leave this mode and re-start
to check the protocol mode, otherwise it will be locked at ServLink Mode.

To create a network definition file:


1. Open the Watch Window program’s associated ServLink server by Clicking
on Start > Programs > Woodward > ServLink Server.exe
2. Select the communications port the control is connected to
3. Select “Point-to-Point” communications
4. Select the a Baud Rate of 38400
5. Select the OK button

Figure 3-4. Setup ServLink Communication

At this point the ServLink Server program will establish control communications,
begin reading all control setting registers and create a lookup table for these
registers to expedite future control communications. Upon reading register
location information from the control the following Windows pop-up box will
appear. (This step can take several minutes to complete.)

Figure 3-5. Reading Control Information

24 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Once all control program registers have been read, the text “Dflt Control ID” will
appear within the ServLink program window and the network definition file can be
saved for future retrieval by the Watch Window program. If the network definition
file is not saved it will have to be re-created before computer-to-control
communications can be established again.

Start Watch Window Software


At this point, start the Watch Window software program by clicking on Start >
Programs > Woodward > Watch Window Standard.exe.

The Watch Window Menu bar, Explorer and Inspector will appear as shown in
Figure 3-4. Click on the icon (Quick Inspector) on the tool bar. Multiple sheets
will automatically be created from each Service and Configure Header
programmed into the control. Optionally, other inspectors can be created to allow
viewing of more than one sheet at a time.

Figure 3-6. Watch Window Menu and Explore (Configure)

Woodward 25
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Chapter 4.
Service and Configuration

Introduction
This chapter provides information about all service and configure which will be
found during the 2300 CLM configuration and adjustments

A**CONFIGURATION**
01 NUMBER OF TEETH *60 (1,500)
Enter the number of gear teeth seen by MPU.

02 TYPE OF ACTUATOR *2 (1,2)


This is an integer number that will change the hardware to 0–20 or 0–200 mA
actuator. Number 1 selects a 0–200 mA type and the number 2 selects a 0–20
mA type. This field is valid only for the speed control actuator (HP).
These values can be adjusted for 4–20 or 20–160 if it is necessary.

03 ACTUATOR RANGE
This field will inform using a message (string) the actuator output selected

04 ACT OUT (4–20 mA) LV *4 (0,8)


Actuator current for 0% of position demand, when configured for 0–20 mA
actuators. Program the minimum current value that the master speed control will
generate when it is not tripped and ready to start. Use ammeters at master speed
control to be sure about this value.

05 ACT OUT (4–20 mA) HV *20 (0,50)


Actuator current for 100% of position demand for 0–200 mA actuators. Program
here the maximum actuator value that the master speed control will generate
when it is not tripped and the actuator output is 100%. Use stroke actuator at
master speed control to know this current value.

06 ACT OUT (0–200 mA) LV *20 (15,24)


The same procedure of item 04, used for 0–200 mA actuators.

07 ACT OUT (0–200 mA) HV *160 (100,200)


The same procedure of item 05, used for 0–200 mA actuators.

08 ACT IN (4–20 mA) LV *4.0 (0.0, 8.0)


Must be entered here the same value obtained at Configure field number 04. At
most cases, the input actuator values must match the sent value via 2300 CLM
but it is possible to program different values for both cases, depending of the
application. This note can be applied to Config. Fields 9 to 11.

09 ACT IN (4–20 mA) HV *20.0 (15.0, 24.0)


Must be entered here the same value obtained at Configure field number 05
Additional considerations from field number 08 are valid.

10 ACT IN (0–200 mA) LV *20.0 (0.0, 50.0)


Must be entered here the same value obtained at Configure field number 06
Additional considerations from field number 08 are valid.

26 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
11 ACT IN (0–200 mA) HV *160.0 (100.0, 200.0)
Must be entered here the same value obtained at Configure field number 07
Additional considerations from field number 08 are valid.

12 GENERATOR APPLICATION? *FALSE (TRUE, FALSE)


If the load is a generator, set TRUE for this field. Otherwise leave it at FALSE
state. Generators and Mechanical Loads are processed with different actions in
each case.

13 OVERSPEED TRIP (RPM) *5000.0 (100.0, 15000.0)


Overspeed trip setpoint. When the MPU connected at 2300 CLM detects the
speed value programmed here or above, it will latch the trip relay, forcing the
primer move to stop. This protection is active in AUTO or MANUAL mode. Since
the actuator output is sent by 2300 CLM the prime mover will stop ignoring the
main speed controller state. If the main speed controller does not detect an
overspeed and the 2300 CLM has been detected this situation, it will latch the trip
state and the actuator output will be 0 mA until a reset command.

14 RATED kW *1000.0 (0.0, 1000000.0)


If the driven load is a generator, program here the maximum active power that
the generator can produce. If the application is a mechanical load, this field will
have no effect

15 REVERSE ACTUATOR? *FALSE (TRUE, FALSE)


A non-reverse actuator means that when the Speed PID increases it value, the
speed or kW increases its value too. Actuator 100% = maximum fuel/steam and
Actuator 0%=prime mover stopped. Otherwise the actuator decreases its position
to increase the speed/kW/fuel/steam demand. Program the same action of the
main speed controller.

16 ACTUATOR INPUT *1 (1,3)


This is an integer number that will change the hardware actuator input to 4–20,
20–160, or 20–200 mA. Number 1 selects a 4–20 mA actuator input, number 2
selects a 20–160 mA actuator input, and number 3 selects a 20–200 mA actuator
input. If a 20–160 or 20–200 mA actuator input is used, a converter must be used
in the actuator input pins of the 2300 CLM (see Figure 2-3g).

17 ACTUATOR INPUT
This field will inform using a message (string) the actuator input selected.

**SERVLINK CONFIRMATION**
01 SET TRUE TO LOCK SLINK *FALSE (TRUE, FALSE)
As soon as an entering in Watch Window is made is important to set this
parameter to TRUE so you can navigate on Watch Window. If it’s not done, when
a certain time expires (parameter 3 of this menu) the communication with Watch
Window will be lost.

02 SET TRUE TO EXIT SLINK *FALSE (TRUE, FALSE)


When all navigation on Watch Window is completed is possible to set this value
to exit Watch Window. By setting this value the communication will be lost after a
while (showed in parameter 4 of this menu). It’s not mandatory to set this value to
TRUE when it’s wanted to get out of Watch Window.

03 TIME TO ENABLE
This is the remaining time until the communication with Watch Window is lost. It’s
the remaining time to set TRUE to the parameter 1 of this menu.

Woodward 27
2300 CLM Closed Loop Mate Backup Controller Manual 26331
04 DISABLE TIMER
This is the remaining time until a communication is lost by setting the parameter
2 of this menu. When parameter 2 of this menu is set this parameter starts
counting down. When it reaches zero the communication with Watch Window is
lost.

B**SPEED SETPOINTS**
01 MINIMUM SPEED *1000.0 (100.0, 15000.0)
This is the minimum governor speed used when the 2300 CLM is at Manual
Mode.

02 MAXIMUM SPEED *4000.0 (100.0, 15000.0)


This is the maximum governor speed used when the 2300 CLM is at Manual
Mode.

03 4 mA SPEED *1000.0 (100.0, 15000.0)


This is the speed setpoint when 2300 CLM is at manual mode and the speed
setpoint is being controlled via 4–20 mA input (Speed for 4 mA value). This
setpoint control mode is obtained closing at same time Raise/Lower speed DI
and it can be done via Modbus Boolean write. This value must be higher than the
minimum speed.

04 20 mA SPEED *4000.0 (100.0, 15000.0)


This is the speed setpoint when 2300 CLM is at manual mode and the speed
setpoint is being controlled via 4–20 mA input (Speed for 20 mA value). This
setpoint control mode is obtained closing at same time Raise/Lower speed DI
and it can be done via Modbus Boolean write. This value must be lower than
maximum speed.

05 RAISE SPEED RATE *2.5 (0.1, 1000.0)


It is the speed setpoint increase rate for mechanical loads (RPM/S) when using
DI commands or Modbus (Raise/Lower commands). Modbus commands have a
programmable pulse time. See item B-11.

06 LOWER SPEED RATE *2.5 (0.1, 1000.0)


It is the speed setpoint decrease rate for mechanical loads (RPM/S) when using
DI commands or Modbus (Raise/Lower commands). Modbus commands have a
programmable pulse time. See item B-12.

07 REMOTE RATE *2.5 (0.1, 1000.0)


If both Raise/Lower DI are closed via Hardware or using a specific Modbus this
field will provide the speed setpoint change rate applied to the value received via
4–20 mA input. This parameter is applicable for mechanical loads.

08 MODBUS RATE *2.5 (0.1, 1000.0)


When the Modbus Communications are active, there is one Boolean write that
will activate the speed setpoint reference via an Analog Write. Then, the speed
setpoint will increase or decrease to reach the wrote value observing the rate
programmed here.

09 SPEED THRESHOLD *100.0 (100.0, 250.0)


Minimum Value Speed. Below this value, the software will understand a Loss of
MPU signal and only the Automatic Mode will be possible, ignoring the master
speed control state. In this case and with the master speed control in trip state,
the Emergency Start Sequence is available and permissive (the Emergency Start
Sequence will not be possible if it is solicited a stroke on the actuator or on the
analog output or if it’s wanted to force relays).
28 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
10 USE kW DROOP? *FALSE
When 2300 CLM is running at manual mode, the driven load has been
programmed for generator and the CB AUX input is TRUE, the software will
understand that the generator must be controlled in Droop Mode. The kW Droop
can be used only with TP and TC connected. If the software does not detect a
valid kW reading, automatically it will switch to actuator droop.

Lets imagine that the generator is working in parallel mode with the grid or other
turbine/engine. To program actuator droop (kW Droop=FALSE) means that the
valve/actuator will assume a fixed position and the kW can change. The actuator
droop is very useful when to control the fuel/steam demand has a high priority
because the software will ignore the kW changes caused by disturbances at
temperature, pressure, air, etc. Other situation is when is needed to have a
stable kW generation independently of the fuel/steam consumption. If this is
desired operational condition set true to kW Droop.

As a simple explanation, the actuator Droop provides a fixed valve/actuator


position and the Load (kW) can change. The kW Droop provides a fixed kW
value and the valve position can change.

11 MODBUS RAISE PULSE (s) *1.0 (0.1, 10.0)


Time delay at DCS systems can be a problem with these types of command. It is
not possible to assure that each pulse (TRUE TIME) will be always the same and
in most cases, these pulses have a low time delay (100–500 ms). To provide a
stable and predictive action, when the Modbus Boolean Write Command is used
to change the speed setpoint, the pulse time to the 2300 CLM speed setpoint
block will use a pulse with the time programmed here. It will provide a very
predictive response. In example, if the rate to raise speed is 2 RPM/S and the
MODBUS RAISE PULSE(s) is programmed for 0.5 s, when a Boolean Write
Command is sent to increase the speed/load, it does not matter if s this pulse
was sent during 0.1 s, 0.5 s, 2 s, 10 s. The internal pulse generated by the
software to move the setpoint will be the value programmed here. Using at this
example (Rate=2, Time Pulse=0.5 s) the speed setpoint will change exactly 1
RPM.
This pulse is activated with a state change from False to True. It means that after
each command, it is necessary to return to False and set to True again to
validate a new command. It is not state sensitive, it is a positive edge sensitive
command.

12 MODBUS LOWER PULSE (s) *1.0 (0.1, 10.0)


The same concept from field 11 to decrease the speed setpoint.

13 RECOVER RATE *10.0 (0.1, 1000.0)


This rate is used when the speed of the engine is below the minimum governor
speed (for mechanical loads) or below synchronous speed (for electrical loads)
and there is a problem in the main speed controller. At this point the control
changes to the 2300 CLM and the speed reference goes to the minimum
governor speed (for mechanical loads) or to the synchronous speed (for electrical
loads) at this rate.

Woodward 29
2300 CLM Closed Loop Mate Backup Controller Manual 26331

C**GENERATOR APPLICATION**
01 DROOP (%) *5.0 (0.0, 10.0)
This is the kW or Actuator Droop for generators applications. Used when the
generator is in parallel to the grid or other isochronous machine.

02 DROOP ADJUST (RPM) *15.0 (0.0, 100.0)


This is an additional adjust to make sure that at rated power the actuator will be
opened 100%. If it’s not wanted set it to zero.

03 RAISE LOAD RATE *10.0 (0.1, 1000.0)


Using DI commands or Modbus Commands, this is the Raise Load Rate that will
be applied to increase the Load. The pulse time for this application is the same of
Service B-11 when is has been sent via Modbus.

04 LOWER LOAD RATE *10.0 (0.1, 1000.0)


Using DI commands or Modbus Commands, this is the Lower Load Rate that will
be applied to decrease the Load. The pulse time for this application is the same
of Service B-11 when it has been sent via Modbus.

05 REMOTE LOAD RATE *10.0 (0.1, 1000.0)


Closing either Raise/Lower DI or Modbus BW the load reference will be
controlled via 4–20 mA input. The load change rate will be the value programmed
here.

06 MODBUS LOAD RATE *10.0 (0.1, 1000.0)


When using an analog write via Modbus to change the setpoint at manual mode,
the load reference sent via a Modbus Analog Write will move the setpoint at the
rate programmed here.

07 SYNCHRONOUS SPEED *1800.0 (100.0, 15000.0)


This is the synchronous speed of the generator. It depends of the frequency and
number of poles of generator and the gear. It is programmed in function of the
MPU signal. The MPU can be installed at the generator or at the prime mover, if
there is a gear installed.

08 USE MINIMUM BIAS? *TRUE (TRUE, FALSE)


When the transfer from the main speed controller occurs maybe it’s desired that
the engine absorbs a little more active power just to prevent reverse power in
case of a fail in the main speed controller occurs and the active power of the
engine is too low. This parameter says if it will be used a little increment on the
load when a transference from the main speed controller to the 2300 CLM
occurs.

09 MINIMUM BIAS (RPM) *5.0 (0.0,100.0)


This is the value incremented to speed reference when a transference from the
main speed controller to the 2300 CLM occurs to prevent reverse power on the
engine.

30 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

D**CALIBRATION**
01 ACTUATOR INPUT GAIN *1.0 (0.0, 10.0)
Use this field to match the actuator input current (measured) with the current
shown at field D-03. Use 3 or 4 test points to calibrate. Fields D-01 and D-02
works together. Adjust both at same time.

02 ACTUATOR INPUT OFFSET *0.0 (-100.0, 100.0)


With zero mA input the field D-03 must indicate 0 mA and use this field to provide
this value. It works with D-01 at same time and so, to have a correct adjustment
use 0%-50%-100% of actuator output obtained via main speed controller to have
a identical response of sensed current (D-03) in comparison of the current sent
by the master speed control.

03 ACT CURRENT SENSED (mA)


Indication only. It will inform the current that the 2300 CLM is reading and
processing. It must be exactly the same current sent by the master at any
position demand.

04 ANALOG INPUT GAIN *1.0 (0.0, 10.0)


Use this field to match the analog input current (measured) with the current
shown at field D-06. Use 3 or 4 test points to calibrate. Fields D-04 and D-05
works together. Adjust both at same time. It is necessary a milliamp generator to
send many points between 4–20 mA to calibrate this input.

05 ANALOG INPUT OFFSET *0.0 (-20.0, 20.0)


With zero mA input the field D-06 must indicate 0 mA and use this field to provide
this value. It works with D-04 at same time and so, to have a correct adjustment
use 0%-50%-100% at the input to have a identical response of sensed current
(D-06) in comparison of the current sent by current generator.

06 ANALOG INPUT SENSED (mA)


Indication only. This field must inform the same current at the 2300 CLM analog
input.

07 STROKE ACTUATOR? *FALSE (TRUE, FALSE)


If the prime mover is stopped and the 2300 CLM and the main speed controller
are tripped, set true to enable the actuator stroke for testing and calibration. Be
sure that the steam valve is shut off.

08 STROKE ENABLED
Will indicate if the stroke actuation is enabled or not.

09 ACTUATOR OUTPUT (mA)


This field indicates the actuator output demand at 2300 CLM measured in
milliamps.

10 ACTUATOR POSITION (%) * (0.0, 100.0)


With D-08 indicating TRUE, use this field to change the HP (ACT) position. The
conditions for stroking the actuator must be fulfilled (see parameter D-07),
otherwise this function will be automatically disabled.

Woodward 31
2300 CLM Closed Loop Mate Backup Controller Manual 26331
11 ACTUATOR OUTPUT GAIN *1.0 (0.01, 10.0)
This value is the multiplier applied at the block output. It is the multiplier for the
position demand received by the hardware driver. The calibration requires
adjusting the zero output value and the output scale. This value (gain) is used at
scale and the next one (D-12) is used to offset null. The actuator position is given
by the equation:

MA_OUT=POS_DEM*GAIN+OFFSET

POS_DEM is the input value at driver output (0-100%)

The current at the actuator input must be equal to the actuator output.

12 ACTUATOR OUTPUT OFFSET *0.0 (-20.0, 20.0)


It is used to adjust the min current output for zero input. If the input is 0% the
actuator output must generate the min current. Use this field to adjust the output
driver to this condition.
Keep in mind that both gain and offset can change the output. Use one and other
until adjust the output driver.

13 FORCE ANALOG OUT? *FALSE (TRUE, FALSE)


Set TRUE to manually change the output demand at the 4–20 mA output. Used
for calibration purposes. The conditions to stroke the analog output are the same
that the ones to stroke the actuator.

14 ANALOG FORCE ENABLED


Will indicate if the stroke actuation is enabled or not.

15 ANALOG OUT VALUE (%) *0.0 (0.0, 100.0)


Enter the desired position (0%=min current and 100%=max current). Only active
if D-14 is TRUE

16 ANALOG OUT GAIN *1.0 (0.01, 100.0)


Used to calibrate the output in function of the entered position.

17 ANALOG OUT OFFSET *0.0 (-100.0, 100.0)


Used together D-16 to provide a correct output (mA values) in function of the
desired output demand.

18 ANALOG OUT MIN CURRENT *4.0 (0.0, 20.0)


It is the current at 4–20 mA output when the desired position is 0%

19 ANALOG OUT MAX CURRENT *20.0 (0.0, 22.0)


The same concept of the field above, applied to 100%

32 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

E**MONITOR FUNC IN STATUS**


01 TRIP FROM SC
If this parameter is closed it means that there is a trip at main speed controller.
To work properly the digital input A must indicate a FALSE status in case of a trip
on the main controller.

02 2300 CLM TRIP


If this parameter is closed it means that no trip is being sent to 2300 CLM. In
case of a trip on the 2300 CLM this field will indicate FALSE.

03 CB AUX
It will indicate the direct state of digital input C. A true indication will inform that
the generator is at droop mode. It has no effect if the 2300 CLM was not
configured for generator application.

04 RAISE SPEED/LOAD
Indicates the state of digital input D (True=Closed, False=Open)

05 LOWER SPEED/LOAD
Indicates the state of digital input E (True=Closed, False=Open)

06 FORCE AUTO / EMERG START


Indicates the state of digital input F (True=Closed, False=Open).

This input has 2 functions. It is used to force the 2300 CLM to Automatic Mode.

If the prime mover is stopped, always will be at automatic mode. Other situation
is that the emergency start sequence is only possible with the prime mover
stopped. It can be seen that these two situations have a logic of XOR (exclusive
OR). The valid state for one automatically disables the other one. Since this, it
was implemented two functions for this input.

A) If the control mode is Manual and the trip relay from master speed control is
closed, it is possible to return the control from 2300 CLM to master speed
control without the actuator input x actuator output matching criteria. At the
same time it is impossible to do an emergency start sequence. While running
in manual mode, this input will force to automatic mode if the conditions
explained are valid.
B) If the prime mover is stopped (0 RPM) automatically the control mode will be
automatic. If the trip relay is open (master tripped) or the actuator current
from the master is out of range, one pulse of at least 5 seconds at this input
will start to open the actuator, at a programmed rate and until a programmed
maximum value. When the prime mover starts to run the 2300 CLM will
detect the speed threshold and will switch to manual mode and will continue
the start sequence until the rated/synch speed.

07 RESET
Indicates the state of digital input G (True=Closed, False=Open).
The alarm reset will eliminate any alarm or trip state:
 Loss of MPU Trip
 2300 CLM TRIP (External Trip)
 Overspeed trip.
 Analog Inputs, Load Sensor failed

Woodward 33
2300 CLM Closed Loop Mate Backup Controller Manual 26331

F**RELAYS**
01 CPU OK RELAY CLOSED
Indicates the state of digital output #1. It will be closed if the 2300 CLM has no
hardware problems but it can be switched off using a Modbus command, to
eliminate 2300 CLM from the actuator loop if this situation is desired.

02 TRIP RELAY CLOSED


An external trip command or overspeed trip occurred, indicated at digital output
#2. The actuator output will be 0 mA and it does not depend of the state or
actuator demand of main speed controller. To eliminate the trip condition and a
reset command must be used. It energizes to trip.

03 RELAY #3 CLOSED
Will indicate the state of programmable digital output #3

04 RELAY #3 FUNCTION *1 (1, 6)


This is a configurable relay and may have one of the four functions described on
the following item.

05 RELAY #3 PROG FOR


The options (1 up to 6) for digital output #3 are:

1) Auto/Man Indicator

Using this function, this digital output will be closed for Manual State and Open
for Automatic State.

2) OSC transfer Indicator

This is an oscillator that indicates how far the transfer from Manual to Automatic
is. When in Manual mode and the main speed controller is ready to control the
machine again this output starts to emit pulses with frequency proportional to the
difference between the actuator input (sent by the main speed controller) and the
actuator output (sent by the internal PID of the 2300 CLM). When this difference
is big the pulses have a slower frequency, when the difference is small the
frequency of the pulses is faster. When the transference is finished the output
doesn’t send pulses anymore.

03) Alarm/Event Indicator

To indicate what alarm is active (it can be more than one alarm) flashes will
indicate the alarm number. If there is more than one alarm, one pause between
the flashes will separate the alarms. Observing the number of flashes and the
pause between them, all alarms active will be indicated.

1 pulse = Manual Mode Active


2 pulses = Overspeed Trip
3 pulses = Modbus Link Failure
4 pulses = Remote Reference failed
5 pulses = Real Power Sensor Failed (Reverse Power)
6 pulses = Loss of MPU

04) Speed Switch

Programming for this function, the fields number 10 and 11 will determinate when
the digital output activates and de-activates in function of the actual speed
(MPU).

34 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
05) Auto Raise Setpoint

This function is used to program the configurable relay #3 to automatically send


raise speed pulses to the main speed controller to perform an automatic transfer
from Manual to Automatic Mode. See service menu R.

06) Auto Lower Setpoint

This function is used to program the configurable relay #3 to automatically send


lower speed pulses to the main speed controller to perform an automatic transfer
from Manual to Automatic Mode. See service menu R.

06 RELAY #4 CLOSED
Will indicate the state of programmable digital output #4.

07 RELAY #4 FUNCTION *1 (1, 6)


This is a configurable relay and may have the same functions of configurable
relay 4.

08 RELAY #4 PROG FOR


Will indicate the current selection for relay 4, with the functions explained on item
F-5.

09 LEVEL RLY SW ON *1000.0 (0.0, 15000.0)


Set the speed (MPU) that will turn on the relay output. Active if relay 03 is
programmed for level switch.

10 LEVEL RLY SW OFF *2000.0 (0.0, 15000.0)


Set the speed (MPU) that will turn off the relay output. Active if relay 04 is
programmed for level switch.

11 LEVEL SWITCH ON?


It indicates if the speed switch is activated.

G**ANALOG OUTPUT**
01 ANALOG OUTPUT SEL *1 (1, 8)
The options listed will be available at analog output (readout) with a programmed
range:
1) Actual Speed
2) Speed Reference
3) Actuator Input (mA)
4) Actuator Output (mA)
5) PID output (0-100%)
6) Remote Reference (Units)
7) Read kW
8) Absolute Actuator Difference Between Input and Output (%)

02 ANALOG OUTPUT USED FOR


It will indicate (string) the option selected and described at the field above.

03 4 mA VALUE *1000.0 (0.0, 30000.0)


The value that generates 4 mA output for the programmed readout.

04 20 mA VALUE *2000.0 (0.0, 30000.0)


The value that generates 20 mA output for the programmed readout.

Woodward 35
2300 CLM Closed Loop Mate Backup Controller Manual 26331

H**FORCE RELAYS**
01 FORCE OUTPUTS? *FALSE
Set true to force relays output. The only way to force relays is the prime mover is
stopped and the main speed controller and the 2300 CLM are tripped.

02 FORCE ENABLED
It will indicate if the force relays command was accepted or not.

03 DO#1 *FALSE
Used to turn on/off this relay output when in force mode.

04 DO#2 *FALSE
Used to turn on/off this relay output when in force mode.

05 DO#3 *FALSE
Used to turn on/off this relay output when in force mode.

06 DO#4 *FALSE
Used to turn on/off this relay output when in force mode.

I**REAL POWER SENSOR**


01 RPS GAIN *13.0 (5.0, 40.0)
For generators, adjust these values if kW droop is used and since this, TC and
TP are installed. Using one kW meter, adjust the gain value to have a correct
measurement of active power. It can be necessary to adjust offset and gain
together to have a correct calibration. The gain value must be used with some
load at generator.

02 RPS OFFSET *0.0 (-20.0, 20.0)


With voltages at TP and TC at zero adjust this field to 0 kW indication.

03 GENERATOR OUTPUT (kW)


Will reflect the active power read in function of the active power and the
adjustments above.

J**COMM PORT (MODBUS)**


01 PORT FAIL
Indicates a hardware fault of RS-232/RS-422 communication port.

02 LINK ERROR
Indicates that slave fails to answer a data request in specified number of time-out
seconds.

03 ERROR PERCENT
Error outputs reflect communication quality as a percentage by dividing the
number of exception error detected by the total number of communication
transactions. This essentially gives the number of message/packet errors
detected.

36 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
04 ERROR NUMBER
Error number outputs the code number of the communication/exception error that
occurred.

00 (No Error) = Error Free


01 (ILLEGAL FUNCTION) = Message function received is not an allowable
action for addressed slave. (Unsupported or illegal functional code)
02 (ILLEGAL DATA ADDRESS) = Address referenced in data field is not an
allowable address for the addressed slave location. (Master requested data,
which is not configured from slave)
03 (ILLEGAL DATA VALUE) = Amount of data requested from slave was too
large for slave to return a single response. Woodward maximum is 118 registers
09 (CHECKSUM ERROR) = Error in the checksum. Can indicate link quality
and/or noise problems.
10 GARBLED MESSAGE = Data received by the slave, but it is too short to be a
valid Modbus message/command

05 BAUD RATE *10 (1, 10)


Set the Baud Rate, which defines the transfer rate for port communications.
1=110
2=300
3=600
4=1200
5=1800
6=2400
7=4800
8=9600
9=19200
10=38400

06 BAUD RATE IS SET FOR


Show the selected Baud Rate.

07 DATA BITS *2 (1, 2)


Set the Data bits input defines the protocol for the number of data bits in the data
packets.
1=7
2=8

08 DATA BITS ARE SET FOR


Shows the selected data bits.

09 STOP BITS *1 (1, 3)


Set the Stop bits, which defines the number of stop bits for the communications
protocol. Stop bits specify the time that elapses between transmitted characters.
1=1 Stop Bit
2=2 Stop Bits
3=1.5 Stop Bit

10 STOP BITS ARE SET FOR


Show the selected stop bits setting

11 PARITY *1 (1, 3)
Set the Parity input defines protocol for the parity. If you selected 8 data bits
select “1” for none.
1=OFF (None)
2=ODD
3=EVEN

Woodward 37
2300 CLM Closed Loop Mate Backup Controller Manual 26331
12 PARITY IS SET FOR
Shows the parity setting.

13 DRIVER *1 (1, 2)
Set the driver input defines the type of driver output for this port.
1=RS-232
2=RS-422

14 DRIVER IS SET FOR


Shows the selected driver

15 TIME OUT (SEC) *4.0 (0.0, 100.0)


Set the Time-out Number of seconds input defines the Modbus link dead time
allowed before a link error occurs.

16 NETWORK ADDRESS *1 (1, 247)


Set the Network Address input defines the slave block address on the Modbus
network. The network address may depend on master device allowable
addresses.

17 kW MULTIPLIER *1.0 (0.01, 1000.0)


Modbus can indicate numbers from –32767 to +32678. The analog value read
via Modbus can be multiplied by this number to increase the definition.

18 ANALOG INPUT MULTIPLIER *1.0 (0.01, 1000.0)


The value of the analog input can be read via Modbus multiplied by this value.

19 ANALOG OUTPUT MULTIPLIER *100.0 (0.1, 1000.0)


The value of the analog output can be read via Modbus multiplied by this value.

20 ACTIVATE MODBUS TRIG *FALSE


Use this command (rising edge) to leave ServLink mode when use Modbus
comm was programmed TRUE, otherwise this mode will be locked and Modbus
comm will be blocked. If the field below (21) if false, this command is not
necessary because the ServLink mode will be always active. If you enter in
ServLink it’s mandatory to activate this parameter before trying to communicate
via Modbus, otherwise the Modbus communication will not be possible.

21 USE MODBUS COMM? *FALSE


Set true if Modbus comm will be used.

K**DISPLAY MENU**
01 AUTOMATIC MODE
Will indicate if the control mode is automatic or not.

02 SPEED SETPOINT
Actual speed setpoint. At automatic mode will be tracking the actual speed, in
manual mode is the setpoint at 2300 CLM control loop.

03 ACTUAL SPEED
Indicates the prime mover speed (RPM).

04 ACTUATOR INPUT (mA)


Indicates the actuator input in milliamps.

05 ACTUATOR OUTPUT (mA)


Indicates the actuator output in milliamps.
38 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
06 GENERATOR OUTPUT (kW)
Indicates the active power if the driven load is a generator.

07 ANALOG OUT (UNITS)


Reflects the analog output. The unit depends of the option chose for this readout.

08 REMOTE INPUT (RPM)


Indicates the remote speed reference.

09 SPEED REF (GEN)


With generators will indicate the virtual speed setpoint, that is the value before
droop calculations or the synchronous speed at frequency control mode (CB Aux
Open)

10 SPEED PID OUTPUT (%)


Indicates the speed PID output, when active at manual mode. At manual mode, it
is equal to proportional demand from the actuator input (tracking mode forced by
the automatic mode condition).

11 USING GAIN RATIO


If the PID error is greater than the programmed value for gain window, this field
will indicate if the Kp is being multiplied by the gain ratio value or not. It is a
Boolean indication (True or False).

12 PROP GAIN AT PID


Will indicate the effective gain at PID controller that is the programmed Kp value
multiplied by the gain ratio, when it is activated by a PID error greater than the
error window.

L**ALARMS**
01 EXTERNAL TRIP
Indicates if an external trip (2300 CLM tripped) is active. In this case the actuator
output will be 0 mA at manual or automatic mode. A reset command is
necessary.

02 OVERSPEED
An overspeed trip was detected. In this case, the actuator output is 0 mA. The
controller is blocked and must be reset.

03 4–20 mA INPUT FAIL


It was detected that the remote input is receiving a current out of range. This
input will be checked only if the remote reference is available.

04 LOAD SENSOR FAIL


Reverse Power Indication. Active for generators only.

05 LOSS OF MPU
Loss of MPU indication. This is active only if the loss of MPU occurs when in
control by 2300 CLM.

06 RESET ALARMS *FALSE


All alarms, when detected, are latched and will block the functions related to
them. It is necessary to eliminate the fail and reset. Modbus, DI, and Watch
Window can do that. In this case, it is possible to reset the alarms at this field.

Woodward 39
2300 CLM Closed Loop Mate Backup Controller Manual 26331

M**EMERGENCY START**
01 ACTUATOR RATE *5.0 (0.01, 100.0)
If the conditions below are true:
1) Prime mover stopped;
2) Main speed controller tripped;
3) Actuator or analog output stroke not active.

it is possible to use an emergency start sequence. In this case, this field will
determine the rate what the actuator position will be increased to re-start the
prime mover in emergency conditions.

Hold digital input F closed for more than 5 seconds, Modbus Command or
ServLink Trigger to start this sequence.

02 OVERRIDE SPEED (RPM) *500.0 (300.0, 1000.0)


The actuator position will be increased until the value programmed here is
sensed. Reaching this value, the PID will start to control the actuator and the
ramp will be stopped.

03 MAX ACT POS AT STRT (%) *20.0 (0.0, 100.0)


It is the maximum position for emergency start. If the actuator reaches this value
and the override speed was not reached, the actuator will return to 0% and a new
command to emergency start sequence must be sent.

04 START TRIGGER *FALSE


It is the start trigger for emergency start via Watch Window.

05 START SPEED *1000.0 (100.0, 15000.0)


It is the setpoint that the speed PID will use after detecting the override speed at
emergency start sequence (First Setpoint).

06 LOW IDLE SPEED *1200.0 (100.0, 15000.0)


It is the second setpoint used after reaching the start speed at the emergency
start sequence.

07 HI IDLE SPEED *1500.0 (100.0, 15000.0)


It is the third setpoint used after reaching the low idle speed

08 RATED/SYNC SPEED *1800.0 (1000.0, 15000.0)


It is the value of Rated or Synchronous Speed after reaching the Hi Idle Setpoint.
It is the last setpoint used by the emergency start sequence.

09 START-LOW IDLE RATE *20.0 (1.0, 1000.0)


It is the rate of setpoint change from Start Speed to Low Idle Speed.

10 LOW-HI IDLE RATE *20.0 (1.0, 1000.0)


It is the rate of setpoint change from Low Idle to High Idle Speed.

11 HI IDLE-RATED/SYNC RATE *20.0 (1.0, 1000.0)


It is the rate of setpoint change from Hi Idle to Rated/Synchronous Speed.

After reaching each setpoint, the start sequence will continue to the
next setpoint after receiving a Raise Speed (Digital Input or Modbus).
During this process is possible to transfer to master (Automatic
Mode) if the required conditions are active.

40 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

N**MONITOR DI STATUS**
01 DIGITAL INPUT #1
Indicates if digital input #1 is opened (FALSE) or closed (TRUE).

02 DIGITAL INPUT #2
Indicates if digital input #2 is opened (FALSE) or closed (TRUE).

03 DIGITAL INPUT #3
Indicates if digital input #3 is opened (FALSE) or closed (TRUE).

04 DIGITAL INPUT #4
Indicates if digital input #1 is opened (FALSE) or closed (TRUE).

05 DIGITAL INPUT #5
Indicates if digital input #5 is opened (FALSE) or closed (TRUE).

06 DIGITAL INPUT #6
Indicates if digital input #6 is opened (FALSE) or closed (TRUE).

07 DIGITAL INPUT #7
Indicates if digital input #7 is opened (FALSE) or closed (TRUE).

O**SPEED PID**
01 PROPORTIONAL GAIN *3.2 (0.01, 50.0)
Proportional Gain of 2300 CLM PID. It represents the amount of actuator action
in function of the error value.

02 INTEGRAL GAIN *0.5 (0.01, 50.0)


It is Integration Time. The integral value is the time during the error is integrated
and is responsible to eliminate the stationary error, but high values can impose a
delay at the response and the system will start to oscillate. This value is also
multiplied by proportional gain.

03 S_D_R *5.0 (0.01, 100.0)


Speed Derivation Ratio. The derivation is responsible by the predictive action of
controller. Values between 0.01 and 1 provide an input dominant action and
values between 1 and 100 provide a feedback dominant action. If PI controller is
desired, set 100 at this field

04 GAIN RATIO *1.0 (0.01, 10.0)


It is the value that will multiply the Proportional Gain when the speed error is
greater that error window.

05 ERROR WINDOW (RPM) *10.0 (0.0, 500.0)


When the difference of actual speed and speed setpoint is greater than this
value, the proportional gain at PID will be multiplied by the gain ratio value

All PID actions are only active in Manual Mode.

Woodward 41
2300 CLM Closed Loop Mate Backup Controller Manual 26331

P**ACTUATOR TRANSFER**
01 MAX ACT DIFF ON TRANSFR *1.0 (1.0, 5.0)
This is the maximum actuator difference between actuator input and output
allowed to perform an automatic transfer from the 2300 CLM and the main
controller.

02 ACT DLY ON AUTO TRANSFR *0.1 (0.05, 1.0)


This is the minimum time (in seconds) that the above parameter must be
maintained to perform an automatic transfer from the 2300 CLM and the main
controller.

03 MAX ACT DIFF ON FRC AUTO *5.0 (0.5, 30.0)


This is the maximum actuator difference between actuator input and output
allowed to perform a force to automatic mode command.

Q**TIME DELAY**
01 SELECT TIME DELAY (MPU) *4 (1, 7)
At the moment of the trip, the speed can change and it could be a problem to
keep the exact setpoint before the fail. Because this situation, it is possible to use
the sensed value from 0 up to 0.96 s before the fail, in intervals of 0.16 s. Set the
option at this field.

02 TIME DELAY FOR MPU


Will indicate the time delay at MPU. It means that if was programmed 0.16 s for
this delay, the speed value considered by the 2300 CLM will be the speed read
0.16 s before the fail has been detected.

03 SELECT TIME DELAY (ACT) *4 (1, 7)


The same concept of fields above applied to the actuator demand.

04 TIME DELAY FOR ACT/kW


Will indicate the time delay selected for this variable. It can be Act demand or kW
load depending of the droop mode selected.

R**AUTO RAISE/LOWER**
01 USE AUTO RAISE/LOWER? *FALSE
This item enables the auto raise/lower function. This function will manage the
raise/lower pulses to the main speed controller or the load controller in order to
help the transference from manual to automatic mode. If this parameter is set to
TRUE and the programmable relays #3 and #4 are programmed to Auto Raise
Setpoint and Auto Lower Setpoint there’s no need to increase /decrease the
speed/load setpoint in the main speed controller/load controller in order to
transfer the 2300 CLM from Manual mode to Automatic mode; the 2300 CLM will
do that job since the raise/lower outputs (programmable outputs #3 and #4) of
the 2300 CLM are tied to the raise/lower speed/load of the main speed
controller/load control.

42 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
02 DELAY FOR ACTION? *5.0 (0.0, 60.0)
After all the conditions of the auto raise/lower logic are fulfilled this parameter
defines the delay (in minutes) for the raise/lower pulses to start acting. The
conditions to start counting this delay are:
1) The control is in Manual Mode (controlled by the 2300 CLM)
2) There is no mere trip signal coming from the main speed controller.
3) The parameter 1 of this menu is set TRUE.

The definition of this parameter is important because some speed controllers


don’t do speed tracking when a start command is given and this time is used to
wait until the speed reference of the main speed controller is in the minimum
governor/synchronous value before start controlling the raise and lower
programmable relays.

03 AUTO RAISE/LOWER STATUS


This item shows the status of the auto raise/lower logic. It can show one of the
following four status:
1) Not active: the auto raise/lower logic conditions are not fulfilled.
2) Active – Raising Setpoint: the auto raise/lower logic is active and sending a
raise setpoint command.
3) Active – Lowering Setpoint: the auto raise/lower logic is active and sending a
lower setpoint command.
4) Active – Pause: the auto raise/lower logic is active but it’s sending neither a
raise nor a lower setpoint command.

04 ACTUATOR DERIV SETPOINT *0.5 (0.1, 5.0)


This parameter defines the rate of change of the actuator of the main speed
controller (in %/sec) that the auto raise/lower logic tries to control. A low value in
this parameter implies that the transference from Manual to Automatic Mode will
take more time, but the main speed controller speed/load setpoint will be just
slightly different from the speed/load setpoint of the 2300 CLM. A higher value of
this parameter implies that the transference from Manual to Automatic Mode will
take less time, but the difference between the main speed controller speed/load
and the 2300 CLM setpoint will be higher.

05 ACT DIFF HYSTERESIS *4.0 (1.0, 10.0)


This parameter defines the difference between the actuator input and the
actuator output of the 2300 CLM, expressed in %, at which the auto raise/lower
logic will invert its action. In other words, if the Actuator Deriv Setpoint is set to
0.5%/sec and the Act Diff Hysteresis is set to 4% then the control will try to
maintain 0.5%/sec as the rate of change of the actuator of the main speed
controller. If the actuator of the main speed controller becomes 4% higher than
the actuator output of the 2300 CLM and the transference doesn’t occur the
Actuator Deriv Setpoint changes to –0.5%/sec, so the main speed controller
actuator starts to lower in order to make the transference from Manual to
Automatic Mode. If the actuator of the main speed controller becomes 4% lower
than the actuator output of the 2300 CLM and the transference doesn’t occur the
Actuator Deriv Setpoint changes back to 0.5%/sec.

06 PULSE TIME (s) *1.5 (0.1, 10.0)


This parameter defines the pulse time, in seconds, of the raise or lower pulse for
the main speed controller or the load controller.

07 TIME BETWEEN PULSES (s) *1.5 (0.1, 10.0)


This parameter defines the time between pulses, in seconds, of the raise or lower
pulse for the main speed controller or the load controller.

Woodward 43
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Chapter 5.
Communications

Modbus Communication
The 2300 CLM control can communicate with plant distributed control systems or
CRT based operator control panels through one Modbus communication port.
The communication port support RS-232 and RS-422 communications using
RTU Modbus transmission protocols. Modbus utilizes a master/slave protocol.

This protocol determines how a communication network’s master and slave


devices establish and break contact, how a sender is identified, how messages
are exchanged, and how errors are detected.

Modbus Communication Mode


The 2300 CLM control supports two Modbus transmission modes. A mode
defines the individual units of information within a message and the numbering
system used to transmit the data. Only one mode per Modbus network is
allowed. The supported RTU (Remote Terminal Unit). These modes are defined
in the following table.

Characteristic RTU
Coding System 8-bit binary
Start Bits 1
Data Bits per Character 8
Parity none
Stop Bits 1
Baud Rate 110,300, 600, 1200, 1800, 2400, 4800, 9600, 19200,
or 38400
Error Checking CRC (Cyclical Redundancy Check)

Table 5-1. Modbus Modes

In the RTU mode, data is sent in 8-bit binary characters and transmitted in a
continuous stream.

The Modbus protocol allows one master and up to 247 slaves on a common
network. Each slave is assigned a fixed, unique device address in the range of 1
to 247. With the Modbus protocol, only the network master can initiate a
transaction. A transaction consists of a request from the master to a slave unit
and the slave’s response. The protocol and Modbus device number are set in the
Program Mode and can be adjusted in the Service Mode, if required.

The 2300 CLM control is programmed to function as a slave unit only. As a slave
unit, the 2300 CLM will only respond to a transaction request by a master device.
The 2300 CLM can directly communicate with a DCS or other Modbus supporting
device on a single communications link, or through a multi-dropped network. If
multi-dropping is used, up to 246 devices (2300 CLMs or other customer
devices) can be connected to one Master device on a single network. The control
address is programmed under the 2300 CLM’s communications block.

Each message to or from a master has a defined structure called the message
“frame”. A frame consists of the slave device address, a code defining the
requested data and error checking information (see Table 4-2).
44 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Beginning SLAVE Function DATA Error End of
of Frame Address Code Check Frame
Code

RTU 3-Char 1 Char 1 Char 8 bits 1 Char 3-Char


Dead 8 bits 8 bits Data per 8 bits Dead
Time Char Time

Table 5-2. Modbus Frame Definition

The Modbus function code tells the addressed slaves what function to perform.
Table 4-3 lists the function codes supported by this control.

Code Definition Reference Address


01 Read Digital Outputs 0XXXX
(Raise/Lower and Enable/Disable Commands)
02 Read Digital Inputs 1XXXX
(Status Indications / Alarms and Trips)
03 Read Analog Outputs 4XXXX
04 Read Analog Inputs 3XXXX
(Speed, Setpt, etc.)
05 Write Single Discrete Output 0XXXX
(Raise/Lower and Enable/Disable Commands)
08 Loopback Diagnostic Test N/A
(Subfunction 0 only)
15 Write Digital Outputs 0XXXX
16 Write Analog Outputs 4XXXX
Table 5-3. Modbus Function Codes

Port Adjustments
Before the 2300 CLM will communicate with the master device, the
communication parameters must be verified. These values are set from the
Service Mode.

Parameter Port Adjustment Range


Baud Rate 110 TO 38400
Data Bits 7 or 8
Stop Bits 1, 2 or 1.5
Parity NONE, ODD or EVEN
Receive Mode Line or Character
Flow OFF, XON/XOFF or CTR-RTS
Auto Echo OFF or ON
End Line LF, CR or CRLF
Ignore OFF or ON
Driver RS-232 or RS-422

Table 5-4. Port Adjustments

For More Modbus Information


Detailed information on the Modbus protocol is presented in “Reference Guide
PI-MBUS-300” published by AEC Corp./Modicon Inc. (formerly Gould Inc). To
implement your own source code, you must register with Modicon. Registration
includes purchasing document PI-MBUS-303 and signing a non-disclosure
agreement. You can register to use Modbus at your nearest Modicon field office. To
find the office nearest you, contact Modicon Technical Support at 1-800-468-5342.

Woodward 45
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Chapter 6.
Service Options

Product Service Options


If you are experiencing problems with the installation, or unsatisfactory
performance of a Woodward product, the following options are available:
 Consult the troubleshooting guide in the manual.
 Contact the manufacturer or packager of your system.
 Contact the Woodward Full Service Distributor serving your area.
 Contact Woodward technical assistance (see “How to Contact Woodward”
later in this chapter) and discuss your problem. In many cases, your
problem can be resolved over the phone. If not, you can select which course
of action to pursue based on the available services listed in this chapter.

OEM and Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the best
source for product service and support. Warranty service for Woodward products
shipped with an equipment system should also be handled through the OEM or
Packager. Please review your equipment system documentation for details.

Woodward Business Partner Support: Woodward works with and supports a


global network of independent business partners whose mission is to serve the
users of Woodward controls, as described here:
 A Full Service Distributor has the primary responsibility for sales, service,
system integration solutions, technical desk support, and aftermarket
marketing of standard Woodward products within a specific geographic area
and market segment.
 An Authorized Independent Service Facility (AISF) provides authorized
service that includes repairs, repair parts, and warranty service on Woodward's
behalf. Service (not new unit sales) is an AISF's primary mission.
 A Recognized Engine Retrofitter (RER) is an independent company that
does retrofits and upgrades on reciprocating gas engines and dual-fuel
conversions, and can provide the full line of Woodward systems and
components for the retrofits and overhauls, emission compliance upgrades,
long term service contracts, emergency repairs, etc.
 A Recognized Turbine Retrofitter (RTR) is an independent company that
does both steam and gas turbine control retrofits and upgrades globally, and
can provide the full line of Woodward systems and components for the
retrofits and overhauls, long term service contracts, emergency repairs, etc.

You can locate your nearest Woodward distributor, AISF, RER, or RTR on our
website at:
www.woodward.com/directory

46 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

Woodward Factory Servicing Options


The following factory options for servicing Woodward products are available
through your local Full-Service Distributor or the OEM or Packager of the
equipment system, based on the standard Woodward Product and Service
Warranty (5-01-1205) that is in effect at the time the product is originally shipped
from Woodward or a service is performed:
 Replacement/Exchange (24-hour service)
 Flat Rate Repair
 Flat Rate Remanufacture

Replacement/Exchange: Replacement/Exchange is a premium program


designed for the user who is in need of immediate service. It allows you to
request and receive a like-new replacement unit in minimum time (usually within
24 hours of the request), providing a suitable unit is available at the time of the
request, thereby minimizing costly downtime. This is a flat-rate program and
includes the full standard Woodward product warranty (Woodward Product and
Service Warranty 5-01-1205).

This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.

Charges for the Replacement/Exchange service are based on a flat rate plus
shipping expenses. You are invoiced the flat rate replacement/exchange charge
plus a core charge at the time the replacement unit is shipped. If the core (field
unit) is returned within 60 days, a credit for the core charge will be issued.

Flat Rate Repair: Flat Rate Repair is available for the majority of standard
products in the field. This program offers you repair service for your products with
the advantage of knowing in advance what the cost will be. All repair work carries
the standard Woodward service warranty (Woodward Product and Service
Warranty 5-01-1205) on replaced parts and labor.

Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option with the exception that the unit will be returned to you in “like-
new” condition and carry with it the full standard Woodward product warranty
(Woodward Product and Service Warranty 5-01-1205). This option is applicable
to mechanical products only.

Returning Equipment for Repair


If a control (or any part of an electronic control) is to be returned for repair,
please contact your Full-Service Distributor in advance to obtain Return
Authorization and shipping instructions.

When shipping the item(s), attach a tag with the following information:
 return authorization number;
 name and location where the control is installed;
 name and phone number of contact person;
 complete Woodward part number(s) and serial number(s);
 description of the problem;
 instructions describing the desired type of repair.

Woodward 47
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Packing a Control
Use the following materials when returning a complete control:
 protective caps on any connectors;
 antistatic protective bags on all electronic modules;
 packing materials that will not damage the surface of the unit;
 at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
 a packing carton with double walls;
 a strong tape around the outside of the carton for increased strength.

To prevent damage to electronic components caused by improper


handling, read and observe the precautions in Woodward manual
82715, Guide for Handling and Protection of Electronic Controls,
Printed Circuit Boards, and Modules.

Replacement Parts
When ordering replacement parts for controls, include the following information:
 the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
 the unit serial number, which is also on the nameplate.

Engineering Services
Woodward offers various Engineering Services for our products. For these services,
you can contact us by telephone, by email, or through the Woodward website.
 Technical Support
 Product Training
 Field Service

Technical Support is available from your equipment system supplier, your local Full-
Service Distributor, or from many of Woodward’s worldwide locations, depending
upon the product and application. This service can assist you with technical
questions or problem solving during the normal business hours of the Woodward
location you contact. Emergency assistance is also available during non-business
hours by phoning Woodward and stating the urgency of your problem.

Product Training is available as standard classes at many of our worldwide


locations. We also offer customized classes, which can be tailored to your needs
and can be held at one of our locations or at your site. This training, conducted
by experienced personnel, will assure that you will be able to maintain system
reliability and availability.

Field Service engineering on-site support is available, depending on the product


and location, from many of our worldwide locations or from one of our Full-
Service Distributors. The field engineers are experienced both on Woodward
products as well as on much of the non-Woodward equipment with which our
products interface.

For information on these services, please contact us via telephone, email us, or
use our website: www.woodward.com.

48 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller

How to Contact Woodward


For assistance, call one of the following Woodward facilities to obtain the address
and phone number of the facility nearest your location where you will be able to
get information and service.

Electrical Power Systems Engine Systems Turbine Systems


Facility---------------- Phone Number Facility---------------- Phone Number Facility---------------- Phone Number
Brazil ------------- +55 (19) 3708 4800 Brazil ------------- +55 (19) 3708 4800 Brazil ------------- +55 (19) 3708 4800
China ----------- +86 (512) 6762 6727 China ----------- +86 (512) 6762 6727 China ----------- +86 (512) 6762 6727
Germany--------- +49 (0) 21 52 14 51 Germany------- +49 (711) 78954-510 India --------------- +91 (129) 4097100
India --------------- +91 (129) 4097100 India --------------- +91 (129) 4097100 Japan -------------- +81 (43) 213-2191
Japan -------------- +81 (43) 213-2191 Japan -------------- +81 (43) 213-2191 Korea -------------- +82 (51) 636-7080
Korea -------------- +82 (51) 636-7080 Korea -------------- +82 (51) 636-7080 The Netherlands - +31 (23) 5661111
Poland--------------- +48 12 295 13 00 The Netherlands - +31 (23) 5661111 Poland--------------- +48 12 295 13 00
United States ---- +1 (970) 482-5811 United States ---- +1 (970) 482-5811 United States ---- +1 (970) 482-5811

You can also locate your nearest Woodward distributor or service facility on our
website at:
www.woodward.com/directory

Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information.
Please write it down here before phoning:

Your Name
Site Location
Phone Number
Fax Number
Engine/Turbine Model Number
Manufacturer
Number of Cylinders (if applicable)
Type of Fuel (gas, gaseous, steam, etc)
Rating
Application
Control/Governor #1
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
Control/Governor #2
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
Control/Governor #3
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number

If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.

Woodward 49
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Appendix A.
Modbus Communication List

Boolean Writes

Address Description
0:0001 Set digital input A (trip from main speed controller)
0:0002 Reset digital input A (trip from main speed controller)
0:0003 Set/reset digital input B (shutdown)
0:0004 Raise speed/kW command (pulse)
0:0005 Lower speed/kW command (pulse)
0:0006 Remote reference enable (generator or mechanical load)
0:0007 Emergency start trigger
0:0008 Turn off CPU OK relay
0:0009 Reset alarms
0:0010 Force to Automatic Mode
0:0011 Use Modbus Reference (generator or mechanical load)

Boolean Reads

Address Description
1:0001 Relay 01 state
1:0002 Relay 02 state
1:0003 Relay 03 state
1:0004 Relay 04 state
1:0005 Hardware input 01
1:0006 Hardware input 02
1:0007 Hardware input 03
1:0008 Hardware input 04
1:0009 Hardware input 05
1:0010 Hardware input 06
1:0011 Hardware input 07
1:0012 Manual Mode on
1:0013 At error window
1:0014 Trip from main speed controller
1:0015 2300 CLM shutdown
1:0016 CB Aux (Droop / Isochronous)
1:0017 Overspeed trip
1:0018 Actuator ramp at emergency start
1:0019 Remote reference fail
1:0020 Reverse power
1:0021 Raise speed/kW command
1:0022 Lower speed/kW command
1:0023 Loss of MPU trip
1:0024 Speed switch on?

50 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Analog Reads

Address Description Multiplier


3:0001 Speed setpoint (generators) 1.0
3:0002 Actual speed (rpm) 1.0
3:0003 Reference at PID 1.0
3:0004 Actuator input (mA) 100
3:0005 Actuator output (mA) 100
3:0006 Remote reference (rpm) *1.0 (0.01 1000)
3:0007 Analog output (mA) *1.0 (0.01 1000)
3:0008 kW load *1.0 (0.01 1000)
3:0009 PID output (0-100%) 100
3:0010 Mech setpoint ramp position 1
3:0011 Speed setpoint (mech loads) 1
3:0012 Main controller/2300 CLM 100
actuator difference (0-100%)
3:0013 Generator setpoint ramp position 1

Analog Writes

Address Description Multiplier


4:0001 Speed setpoint (mechanical loads) 1
4:0002 Speed setpoint (generators) 1

Woodward 51
2300 CLM Closed Loop Mate Backup Controller Manual 26331

Appendix B.
Service / Configure Chart

CONFIGURE PROGRAMMED DEFAULT TUNABLE RANGE


MENU VALUE VALUE MINIMUM MAXIMUM
A**CONFIGURATION**
01 Number of teeth 60 1 500
02 Type of actuator 2 1 2
03 Actuator range Monitor
04 Act out (4-20mA) LV 4 0 8
05 Act out (4-20mA) HV 20 0 50
06 Act out (0-200mA) LV 20 15 24
07 Act out (0-200mA) HV 160 100 200
08 Act in (4-20mA) LV 4 0 8
09 Act in (4-20mA) HV 20 0 50
10 Act in (0-200mA) LV 20 15 24
11 Act in (0-200mA) HV 160 100 200
12 Generator application? FALSE FALSE TRUE
13 Overspeed trip (rpm) 5000 100 15000
14 Rated kW 1000 0 1000000
15 Reverse actuator? FALSE FALSE TRUE

SERVICE PROGRAMMED DEFAULT TUNABLE RANGE


MENU VALUE VALUE MINIMUM MAXIMUM
**SERVLINK CONFIRMATION**
01 Set true to lock slink FALSE FALSE TRUE
02 Set true to exit slink FALSE FALSE TRUE
03 Time to enable Monitor
04 Disable timer Monitor

B**SPEED SETPOINTS**
01 Minimum speed 1000 100 15000
02 Maximum speed 4000 100 15000
03 4mA speed 1000 100 15000
04 20mA speed 4000 100 15000
05 Raise speed rate 2.5 0.1 1000
06 Lower speed rate 2.5 0.1 1000
07 Remote rate 2.5 0.1 1000
08 Modbus rate 2.5 0.1 1000
09 Speed threshold 100 100 250
10 Use kW droop? FALSE FALSE TRUE
11 Mdbus raise pulse (s) 1 0.1 10
12 Mdbus lower pulse (s) 1 0.1 10
13 Recover Rate 10 0.1 1000

52 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
SERVICE PROGRAMMED DEFAULT TUNABLE RANGE
MENU VALUE VALUE MINIMUM MAXIMUM
C**GENERATOR APPLICATION**
01 Droop (%) 5 0 10
02 Droop adjust (rpm) 15 0 100
03 Raise load rate 10 0.1 1000
04 Lower load rate 10 0.1 1000
05 Remote load rate 10 0.1 1000
06 Modbus load rate 10 0.1 1000
07 Synchronous speed 1800 100 15000
08 Use minimum bias? TRUE FALSE TRUE
09 Minimum bias (rpm) 5 0 100

D**CALIBRATION**
01 Actuator input gain 1 0 10
02 Actuator input offset 0 -100 100
03 Act current sensed (mA) Monitor
04 Analog input gain 1 0 10
05 Analog input offset 0 -20 20
06 Analog input sensed (mA) Monitor
07 Stroke actuator? FALSE FALSE TRUE
08 Stroke enabled Monitor
09 Actuator output (mA) Monitor
10 Actuator position (%) 0 0 100
11 Actuator output gain 1 0.01 10
12 Actuator output offset 0 -20 20
13 Force analog out? FALSE FALSE TRUE
14 Analog force enabled Monitor
15 Analog out value (%) 0 0 100
16 Analog out gain 1 0.01 100
17 Analog out offset 0 -100 100
18 Analog out min current 4 0 20
19 Analog out max current 20 0 22

E**MONITOR FUNC IN STATUS**


01 Trip from SC Monitor
02 2300 CLM trip Monitor
03 CB_Aux Monitor
04 Raise speed/load Monitor
05 Lower speed/load Monitor
06 Force auto / emerg start Monitor
07 Reset Monitor

Woodward 53
2300 CLM Closed Loop Mate Backup Controller Manual 26331
SERVICE PROGRAMMED DEFAULT TUNABLE RANGE
MENU VALUE VALUE MINIMUM MAXIMUM
F**RELAYS**
01 CPU OK relay closed Monitor
02 Trip relay closed Monitor
03 Relay #3 closed Monitor
04 Relay #3 function 1 1 6
05 Relay #3 prog for Monitor
06 Relay #4 closed Monitor
07 Relay #4 function 1 1 6
08 Relay #4 prog for Monitor
09 Level rly sw on 2000 0 15000
10 Level rly sw off 1000 0 15000
11 Level switch on? Monitor

G**ANALOG OUTPUT**
01 Analog output sel 1 1 7
02 Analog output used for Monitor
03 4mA value 1000 0 30000
04 20mA value 1000 0 30000

H**FORCE RELAYS**
01 Force outputs? FALSE FALSE TRUE
02 Force enabled Monitor
03 DO#1 FALSE FALSE TRUE
04 DO#2 FALSE FALSE TRUE
05 DO#3 FALSE FALSE TRUE
06 DO#4 FALSE FALSE TRUE

I**REAL POWER SENSOR**


01 RPS gain 13 5 40
02 RPS offset 0 -20 20
03 Generator output (kW) Monitor

54 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
SERVICE PROGRAMMED DEFAULT TUNABLE RANGE
MENU VALUE VALUE MINIMUM MAXIMUM
J**COMM PORT (MODBUS)**
01 Port fail Monitor
02 Link error Monitor
03 Error percent Monitor
04 Error number Monitor
05 Baud rate 10 1 10
06 Baud rate is set for Monitor
07 Data bits 2 1 2
08 Data bits are set for Monitor
09 Stop bits 1 1 3
10 Stop bits are set for Monitor
11 Parity 1 1 3
12 Parity is set for Monitor
13 Driver 1 1 2
14 Driver is set for Monitor
15 Time out (sec) 4 1 10
16 Network address 1 1 247
17 kW multiplier 1 0.01 1000
18 Analog in multiplier 1 0.01 1000
19 Analog out multiplier 1 0.01 1000
20 Activate modbus trig FALSE FALSE TRUE
21 Use modbus comm? TRUE FALSE TRUE

K**DISPLAY MENU**
01 Automatic Mode Monitor
02 Speed setpoint Monitor
03 Actual speed Monitor
04 Actuator input (mA) Monitor
05 Actuator output (mA) Monitor
06 Generator output (kW) Monitor
07 Analog out (units) Monitor
08 Remote input (rpm) Monitor
09 Speed ref gen Monitor
10 Speed PID output (%) Monitor
11 Using gain ratio Monitor
12 Prop gain at PID Monitor

L**ALARMS**
01 External trip Monitor
02 Overspeed Monitor
03 4-20mA input fail Monitor
04 Load sensor fail Monitor
05 Loss of MPU Monitor
06 Reset alarms FALSE FALSE TRUE

Woodward 55
2300 CLM Closed Loop Mate Backup Controller Manual 26331
SERVICE PROGRAMMED DEFAULT TUNABLE RANGE
MENU VALUE VALUE MINIMUM MAXIMUM
M**EMERGENCY START**
01 Actuator rate 5 0.01 100
02 Override speed (rpm) 500 300 1000
03 Max act pos at strt (%) 20 0 100
04 Start trigger FALSE FALSE TRUE
05 Start speed 1000 100 15000
06 Low idle speed 1200 100 15000
07 High idle speed 1500 100 15000
08 Rated/sync speed 1800 1000 15000
09 Start-low idle rate 20 1 1000
10 Low-high idle rate 20 1 1000
11 Hi idle-rated/sync rate 20 1 1000

N**MONITOR DI STATUS**
01 Digital Input #1 Monitor
02 Digital Input #2 Monitor
03 Digital Input #3 Monitor
04 Digital Input #4 Monitor
05 Digital Input #5 Monitor
06 Digital Input #6 Monitor
07 Digital Input #7 Monitor

O**SPEED PID**
01 Proportional gain 3.2 0.01 50
02 Integral gain 0.5 0.01 50
03 S_D_R 5 0.01 100
04 Gain ratio 1 0.01 10
05 Error window (rpm) 10 0 500

P**TRANSFER ACTUATOR**
01 Max Act difference on transfer 0.5 0.1 5
02 Act delay on auto transfer 0.1 0.05 1
03 Max Act difference on ForceAuto 5 0.5 30

Q**TIME DELAY**
01 Select time delay (MPU) 4 1 7
02 Time delay for MPU Monitor
03 Select time delay (ACT) 4 1 7
04 Time delay for ACT/kW Monitor

R**AUTO RAISE/LOWER**
01 Use Auto Raise/Lower?
02 Delay for Action
03 Auto Raise/Lower Status Monitor
04 Actuator Deriv Setpoint 0.5 0.1 5
05 Act Diff Hysteresis 4 1 10
06 Pulse Time (s) 1.5 0.1 10
07 Time Between Pulses (s) 1.5 0.1 10

56 Woodward
2300 CLM Control Specifications
Woodward Part Numbers:
8237-1132 2300 CLM certified for ordinary locations
8237-1155 2300 CLM certified for hazardous locations
8923-932 Watch Window Installation

Power Supply Rating 18–40 Vdc (SELV)


Power Consumption less than or equal 20 W nominal
Input Supply Voltage Input Supply Current
18 V 589 mA
24 V (nominal) 431 mA
32 V 319.6 mA
Inrush Current 7 A for 0.1 ms (low-voltage model)
Inrush Current 22 A for 15 ms (high-voltage model)
Steady State Speed Band ±0.25% of rated speed
Magnetic Pickup 100–24 950 Hz (900–20000 rpm)
Discrete Inputs (8) 3 mA at 24 Vdc, impedance approximately 5.2 kΩ
Analog Input #1, #2 4–20 mA
SPM-A Input ±2.5 Vdc, externally powered
Analog Output #1 4–20 or 20–200 mA to actuator, software configurable
Analog Output #2 4–20 mA to monitor, internally powered
Discrete Outputs (4) configured to provide various level switches or conditions, power by
external +12 Vdc or +24 Vdc source, max output current 200 mA
Discrete Output Ratings Low-side drivers with overvoltage protection, 200 mA maximum
Communication Port (J2) RS-232, RS-422, 9-pin connector, 1200 to 38 400 baud, full duplex
Ambient Operating Temperature –40 to +70 °C (–40 to +158 °F)
Storage Temperature –40 to +105 °C (–40 to +221 °F)
Humidity 95% at +20 to +55 °C (+68 to +131 °F)
Lloyd’s Register of Shipping Test Specification No. 1, 1996, Humidity Test 1
Mechanical Vibration Lloyd’s Register of Shipping Test Specification No. 1, 1996, Vibration Test 2
(5-25 Hz, ± 1.6 mm; 25-100 Hz, 4.0g)
Mechanical Shock US MIL-STD 810C, Method 516.2, Procedure I (basic design test),
Procedure II (transit drop test, packaged), Procedure V (bench handling)
Equipment Classification 1 (grounded equipment)

Regulatory Compliance
European Compliance for CE Mark:
EMC Directive Declared to 89/336/EEC COUNCIL DIRECTIVE of 03 May 1989 on the
approximation of the laws of the member states relating to electromagnetic
compatibility.
Low Voltage Directive Declared to the 73/23/EEC COUNCIL DIRECTIVE of 19 February 1973 on
the harmonization of the laws of the Member States relating to electrical
equipment designed for use within certain voltage limits.

Marine Compliance:
Bureau Veritas BV Rules Part C, June 2000
Germanischer Lloyd Additional Rules and Guidelines, Part 1, 2001
Lloyd’s Register of Shipping Type Approval System, Test Specification Number 1, 2002
NOTE These certifications apply to specific models only.

North American Compliance:


CSA: CSA Certified for Class I, Division 2, Groups A, B, C, D, T4 at 70 °C
Ambient. For use in Canada and the United States
Certificate 1150575
This listing is limited only to those units bearing the CSA agency identification and hazardous location markings.
CSA: CSA Certified for Ordinary Locations. For use in Canada and the United
States
Certificate 1150575
UL: UL Listed for Ordinary Locations. For use in Canada and the United States.
UL File E97763
NOTE Wiring must be in accordance with applicable electric codes with the
authority having jurisdiction.
Declarations
We appreciate your comments about the content of our publications.
Send comments to: [email protected]

Please reference publication 26331A.

PO Box 1519, Fort Collins CO 80522-1519, USA


1000 East Drake Road, Fort Collins CO 80525, USA
Phone +1 (970) 482-5811  Fax +1 (970) 498-3058

Email and Website—www.woodward.com

Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and
other authorized service and sales facilities throughout the world.
Complete address / phone / fax / email information for all locations is available on our website.

You might also like