2300 Closed Loop Mate (2300 CLM) Backup Controller: Product Manual 26331 (Revision A, 12/2009)
2300 Closed Loop Mate (2300 CLM) Backup Controller: Product Manual 26331 (Revision A, 12/2009)
(Revision A, 12/2009)
Original Instructions
This publication may have been revised or updated since this copy was produced.
To verify that you have the latest revision, check manual 26311 , Revision Status &
Distribution Restrictions of Woodward Technical Publications, on the publications
Revisions page of the Woodward website:
www.woodward.com/publications
Revisions—Changes in this publication since the last revision are indicated by a black line
alongside the text.
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is
believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly
undertaken.
Manual 26331
Copyright © Woodward 2009
All Rights Reserved
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Contents
Woodward i
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Contents
ii Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Woodward iii
2300 CLM Closed Loop Mate Backup Controller Manual 26331
iv Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Regulatory Compliance
General Installation and Operation Notes and Requirements:
The 2300 CLM is suitable for use in Class I, Division 2, Groups A, B, C, and D
per CSA for Canada and U.S. or non-hazardous locations only. These listings
are limited only to those units bearing the CSA agency identification and
hazardous location markings.
The 2300 CLM is suitable for use in Ordinary Locations per UL and CSA for
Canada and U.S. or non-hazardous locations only. These listings are limited only
to those units bearing the UL and CSA agency identification and ordinary location
markings.
The 2300 CLM shall be installed in a suitable enclosure. A local authority having
jurisdiction shall approve the final combination.
Woodward v
2300 CLM Closed Loop Mate Backup Controller Manual 26331
vi Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Chapter 1.
General Information
General Description
The 2300 Closed Loop Mate (2300 CLM) is a backup controller that can be used
with all types of applications (generators or mechanical loads) with engines or
turbines. The meaning of the term controller indicates that this product can
control the setpoints closed loop. It will not just keep the actuator at the same
position when the master speed control fails, but will control the speed or kW
setpoint with PID controller and will sustain the setpoint, changing the actuator
demand reacting to load changes.
The 2300 CLM assumes two states: Automatic Mode and Manual Mode.
Automatic Mode: The main speed controller is not tripped and is controlling
the engine or turbine. The 2300 CLM is driving the actuator signal from the
main speed controller to the actuator. In this mode, the 2300 CLM is
monitoring both actuator current and the trip relay of the main speed
controller.
Manual Mode: The 2300 CLM has detected a master speed control failure.
Because it has information about the actuator position and speed or kW, the
2300 CLM will start to control the prime mover at the same speed or kW
demand before the failure.
Since it is a controller, the 2300 CLM has discrete inputs to change (raise/lower)
the setpoints, It is possible to use 4–20 mA remote reference and also Modbus® *
Communications to change the setpoints.
*—Modbus is a trademark of Schneider Automation Inc.
If failure occurs on the main speed controller, a bumpless control transfer to the
2300 CLM will be done at the same setpoint sensed milliseconds before the
failure. This value will be used as the initial setpoint. While the problem with the
master speed control continues, the 2300 CLM PID will change the actuator
position based on load changes and will accept setpoint changes. When the
problem with the master speed has been eliminated, the 2300 CLM will use the
actuator demand matching criteria to return the control to master speed control.
This means that the 2300 CLM will be waiting for the actuator demand from the
main speed controller to reach the same value of the actuator demand that the
2300 CLM is using to control the speed/kW. When these values reach the same
value, control will automatically be transferred from Manual Mode to Automatic
Mode, without any disturbance.
When the driven load is a generator, the 2300 CLM can operate at island mode
(frequency control) or in droop mode when working in parallel to the grid or other
generator. It is possible to use actuator droop or kW droop. Usually actuator
droop is used in parallel mode at constant fuel/steam demand for each speed
setpoint and kW droop is used at constant kW demand with fuel/steam changes
for each kW setpoint. The CB Aux digital input will inform (when it is TRUE) to
operate at droop mode or frequency control (when it is FALSE).
Woodward 1
2300 CLM Closed Loop Mate Backup Controller Manual 26331
When a master speed control fails, the 2300 CLM will keep the same setpoint
and will provide setpoints changes. If it becomes necessary to switch off the
2300 CLM for any reason, or to remove and install it, this can be done easily
because there are relays to change the actuator connection directly to the master
speed control (see wiring diagram, Figure 2-3). In this case, the system will
operate in the same way as when the 2300 CLM is not installed.
Finally, when the master speed control is tripped/removed and an external trip
forces the prime mover to stop, the 2300 CLM will accept an emergency start
command, which has 3 setpoints, each one with its own rate and controlled
actuator opening ramp to start.
References
The following publications contain additional product or installation information on
Load Sharing and Speed Controls and related components. They can be
obtained from the Woodward website (www.woodward.com/publications) or
ordered from any Woodward office.
Manual Title
25070 Electronic Control Installation Guide
25195 Governing Fundamentals
82384 SPM-A Synchronizer
82510 Magnetic Pickups and Proximity Switches for Electronic Governors
82715 Guide for Handling and Protection of Electronic Controls, Printed
Circuit Boards, and Modules
Product
Spec Title
82383 SPM-A Synchronizer
82516 EG-3P/-6P/-10P Actuator
82575 EGB-1P/-2P Governor/Actuator
03202 Woodward Watch Window Standard
2 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Chapter 2.
Installation
Introduction
This chapter contains general installation instructions for the 2300 CLM control.
Power requirements, environmental precautions, and location considerations are
included to determine the best location for the control. Additional information
includes unpacking instructions, electrical connections, and an installation
checkout procedure.
Unpacking
Before handling the control, read the “Electrostatic Discharge Awareness”
information on page iv. Be careful when unpacking the electronic control. Check
the control for signs of damage such as bent or dented panels, scratches, and
loose or broken parts. If any damage is found, immediately notify the shipper.
Mounting Considerations
This product is intended for installation in a “closed electrical operating
area” or in an enclosed industrial control cabinet. Consider these
requirements when selecting the mounting location:
Adequate ventilation for cooling
Space for servicing and repair
Protection from direct exposure to water or to a condensation-prone
environment
Protection from high-voltage or high-current devices, or devices which
produce electromagnetic interference
Avoidance of vibration
Selection of a location that will provide an operating temperature range of
–40 to +70 °C (–40 to +158 °F)
The control must NOT be mounted on the engine or turbine.
Woodward 3
2300 CLM Closed Loop Mate Backup Controller Manual 26331
13.750
15.281 MAX
6.875
.750
6,626
9.125
4 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
NOT USED
ACTUATOR/HP OUTPUT
Woodward 5
2300 CLM Closed Loop Mate Backup Controller Manual 26331
RESET ALARMS
NOT USED
RESET ALARMS
NOT USED
CPU OK OUTPUT
CONFIGURABLE RELAY #2
6 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Woodward 7
2300 CLM Closed Loop Mate Backup Controller Manual 26331
8 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Figure 2-3f. 2300 CLM Relay Box Wiring Diagram (Actuator Relays)
Woodward 9
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Electrical Connections
All inputs and outputs are made through screwless spring-actuated terminal
blocks. For EMI reasons, it is recommend that all low-current wires be separated
from all high-current wire.
The spring clamp can be actuated using a standard 2.5 mm or 3/32 inch flat
bladed screwdriver. The terminal blocks accept wires from 0.08–4 mm² (27–12
AWG). Two 0.8 mm² (18 AWG) or three 0.5 mm² (20 AWG) wires can be easily
installed in each terminal. Wires for the fixed mounted power terminals should be
stripped 5–6 mm (0.22 inch) long.
10 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
The 2300 CLM is designed for shield termination to earth ground at the control. If
intervening terminal blocks are used in routing a signal, the shield should be
continued through the terminal block. If shield grounding is desired at the
terminal block, it should be ac coupled to earth. All other shield terminations
except at the control should be ac coupled to earth through a capacitor. A 1000
pF, 500 V capacitor is sufficient. The intent is to provide a low impedance path to
earth for the shield at frequencies of 150 kHz and up. Multiple direct connections
of a shield to earth risk high levels of current to flow within the shield (exception,
see note below on cabinet installations).
Shields can be grounded at both ends (2300 CLM and load) if the cable length is
sufficiently short (within a cabinet) to prevent ground loop current in the shield.
Woodward 11
2300 CLM Closed Loop Mate Backup Controller Manual 26331
The trip command from master speed control is connected in parallel (AND
Logic) to 2300 CLM. In this case, both master speed control and 2300 CLM must
receive this command when the trip action is needed.
12 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
A positive voltage on any discrete input terminal is sensed by the control as a
closed contact or “TRUE” state. With no voltage applied to a discrete input
terminal the control senses an open contact or “False” state.
For power loading reasons, it is recommended that the control’s internal 24 Vdc
not be used to power other external equipment.
Discrete inputs with cable lengths greater than 30 meters that are
used for critical functions, such as emergency stop, should not be
floated in either an on or off state. These inputs should be switched
to +24 Vdc or ground.
Actuator Output
Connect the unit’s actuator wires to the control’s actuator driver output on
terminals 13(+), 14(–), and 15(shield). This output’s current range is software
configurable and can be programmed to output a drive current of 20–160 mA, or
4–20 mA. Do not connect the shield wire to the actuator or any other point. Verify
that the output’s shield wire has continuity its entire distance to the actuator and
is insulated from all other conducting surfaces. The wiring diagram (Fig. 2-3c) will
show how this output is connected.
Actuator Input
This input receives the actuator/HP demand from the main speed controller
(terminals 19+ and 20-).
Remote Reference
This input is 4–20 mA type. It will accept a remote reference of speed or kW to
change these setpoints when the 2300 CLM is at manual mode.
With proper MPU, gear size and MPU-to-gear clearance, speed measurement
should be capable down to 100 Hz. Check the speed sensor for visible damage.
Standard MPU clearance is recommended to be between 0.25 and 1.0 mm
(0.010 and 0.040 inch) at the closest point. Make sure that the gear has less than
0.5 mm (0.020 inch) diametric run out. See manual 82510, Magnetic Pickups and
Proximity Switches for Electronic Governors.
Woodward 13
2300 CLM Closed Loop Mate Backup Controller Manual 26331
These discrete outputs are low-side drivers with a maximum output current of
160 mA. The discrete output drivers are isolated from the control’s internal power
supply (but not from each other) and are powered by an external +12 Vdc or +24
Vdc source connected at terminals 39(+) and 40(–) (refer to Figure 2-3 for plant
wiring information).
Communication Port
The control’s serial communications port is used to configure and service the
unit, as well as communicate to a Human Machine Interface (HMI) or plant
distributed control system (DCS).
RS-232
See Figure 2-5 for cable connection.
2301D-ST
14 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
RS-422
See Figure 2-6 for termination and cable connection example.
Termination
For RS-422, termination should be located at the receiver when one or more
transmitters are connected to a single receiver. When a single transmitter is
connected to one or more receiver, termination should be at the receiver farthest
from the transmitter. Figure 2-7 is an example.
Woodward 15
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Figure 2-8. Preferred Multipoint Wiring Using Shielded Twisted-pair Cable with a
Separate Signal Ground Wire
Figure 2-9. Alternate Multipoint Wiring Using Shielded Twisted-pair Cable without
a Separate Signal Ground Wire
16 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Chapter 3.
2300 CLM Machine State
The speed is below the threshold value programmed in the 2300 CLM. In this
situation, the control mode will be forced to automatically ignore whether the
main speed controller is tripped or not. This is a protection against loss of MPU
signal. If the 2300 CLM loses the MPU signal and the control mode is manual,
the mode will be forced to automatic. If the control mode is automatic it will be
kept in automatic mode even with the main speed controller tripped. If the
machine is being driven by the 2300 CLM at the time that the loss of MPU
occurs, a shutdown will be indicated on the 2300 CLM as a warning of MPU loss.
The trip relay AND the actuator demand from the master speed control do not
indicate a trip condition. The relay is closed and the actuator current is at the
programmed range.
Woodward 17
2300 CLM Closed Loop Mate Backup Controller Manual 26331
If the sensed speed is greater than Override Speed, the actuator ramp is
disabled, the speed 2300 CLM PID will start to control the prime mover
speed at Start Speed Setpoint.
If the actuator reaches maximum position at start sequence but the override
speed was not detected, automatically the actuator will return to 0% and an
other command to Emergency Start Sequence will be necessary.
If an MPU signal is sensed, the PID will use the Start Speed Setpoint to
control the prime mover.
Use the command Raise Speed/Load to Ramp from Start Speed to Low Idle
Speed (this ramp has a configurable rate).
Use the command Raise Speed/Load after reaching Low Idle Speed to move
the setpoint to High Idle Speed (configurable rate).
Use the Raise Speed/Load command to move from Hi-Idle to Sync/Rated
Speed using a configurable rate to finish the emergency start sequence.
If there are conditions to transfer from manual mode to automatic mode, the
2300 CLM will accept to change to automatic mode during the start
sequence.
Digital input F shares the Force to Automatic Mode function and Emergency Start
Sequence function. These functions have an Exclusive OR logic. The conditions
that are permissive for one are inhibiting the other one and vice-versa.
CPU OK is ON, the 2300 CLM control mode is Automatic and no trip exists on
master speed control
The same actuator(s) current at the master speed control are being sent by the
2300 CLM to the actuator. The 2300 CLM will be monitoring the actuator current
and the trip relay state to change to Manual Mode.
CPU OK is OFF
Offline State. A 2300 CLM hardware failure was detected or it has no power
supply. In this case, the system will operate exactly at the same way when the
2300 CLM is not installed. The actuator relays provide this security action. No
transfer is possible, and no backup exists.
CPU OK is ON, the 2300 CLM control mode is Manual, and the main speed
controller is still tripped
The Speed/kW is active at 2300 CLM. It is possible to change setpoints (speed,
kW). The 2300 CLM is waiting for a valid state of main speed controller trip relay
and the actuator demand from main speed controller.
CPU OK is ON, the 2300 CLM control mode is Manual, and a trip state no
longer exists at the main speed controller (Master Ready to Start)
The 2300 CLM will understand that the problem with the main speed controller
was eliminated, and transferring to the main speed controller is possible. It
means that the trip relay at master is closed, its actuator current is not out of
range, and the 2300 CLM is controlling the loops. At this moment, the 2300 CLM
will be waiting for the actuator matching criteria to change to Automatic Mode.
This is the case when it waits until the actuator demand at main speed controller
becomes equal to the actuator demand from 2300 CLM PID to do the transfer. It
is a bumpless transfer mode because no speed/kW disturbance is sensed.
But if desired, after all the conditions described above, it is possible to bypass the
actuator matching criteria using the force to automatic mode command. In this
case, the control will be changed to manual mode and a speed/kW disturbance
will be sensed.
18 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Act. Demand
A B C
time
2300 CLM ACTUATOR DEMAND
MAIN SPEED CONTROLLER DEMAND
If a bumpless transfer is necessary to transfer the control from 2300 CLM to main
speed controller, consider the trend above.
A trip at main speed controller was detected and the 2300 CLM is controlling
the prime mover.
Time A: The main speed controller is still tripped.
Time B: The main speed controller is operational, reset, and the actuator
current is at minimum.
Time C: The actuator demand from main speed controller is increasing and
when it reaches the same value of actual position demand given by the 2300
CLM PID, the transfer to automatic mode will occur.
The actuator demand from main speed controller will increase if the
speed setpoint at main speed controller is greater than the actual
MPU measured value. If the controlled variable is the load (kW) the
same concept is applied to the kW demand. To provide this condition
use manual commands to raise the setpoint at main speed controller
or at load controller. The raise and lower pulses to the main speed
controller or to the load controller can be managed by the 2300 CLM
via two discrete outputs that can be configured for this purpose.
The 2300 CLM can indicate via digital output (configurable) when this condition
was reached (Time C). A digital output can be programmed as transfer indicator.
It will emit pulses with variable frequency If the difference between the actuator
input and the actuator output is big the pulses will have a slower frequency.
When this difference becomes small the pulses will have a faster frequency. This
indicator will only emit pulses when it’s in Manual mode and a run command was
set on the main speed controller.
If at time B a force to automatic mode command is sent to 2300 CLM, it will not
wait for the current criteria and the control will be transferred automatically to the
main speed controller (with disturbance).
Woodward 19
2300 CLM Closed Loop Mate Backup Controller Manual 26331
HP
LOWER LOAD
RAISE LOAD
RAISE SPEED
MPU
2300 CLM
LOWER SPEED
TC
TP
20 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
When 2300 CLM is in manual mode and the Gen Breaker is Closed, the
speed bias can change the speed setpoint at the speed control, increasing
the active power (actuator output) with Load Controller in Droop Mode.
Normally the Generator Breaker Status can determine if the load controller is
at Droop Mode or not. If the load controller cannot assume a droop state with
this condition, use the available way to change the control mode to droop in
function of the state of 2300 CLM (Auto Mode=Control ON, Manual
Mode=Droop).
The conditions above are valid for a generator operating synchronized with other
generators/grid. If the condition is a generator operating at island mode, be very
careful with these commands to increase load because an overfrequency can
occur if the increasing load pulses were sent many times.
If these all conditions are valid, use commands to increase the load at the load
controller. When the speed bias starts to increase, the actuator current will start
to increase at main speed controller and the transfer will occur at the same way
as described for speed controllers (mechanical Loads).
Synchronizers Only
In this case, the synchronizer will send pulses or analog signal to adjust the
generator frequency to the grid and will be waiting for synch window, dwell time,
slip window to close the generator breaker. After this, the main speed controller
will operate at droop mode (if in parallel mode), frequency control at island mode
or isolated bus frequency controller (2 or more generators in parallel mode and
out of the grid). If the system has this configuration, the pulses to raise
speed/load will be sent only to the speed control. If the generator is operating at
droop mode, it is indicated that it is in parallel with other generator in frequency
mode or in parallel with the grid. If it is operating at island mode, there is an
overfrequency possibility. Do not use a setpoint greater then 1% of synch. speed
to the generator in frequency control to transfer the control. No problems are
related to these commands to generators in droop mode.
Woodward 21
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Watch Window performs these primary functions:
Monitoring and Tuning of Control Variables—Watch Window presents
variables in a tabular format. The user chooses the variables to view. Multiple
pages of variables can be created, each with useful parameters for various
troubleshooting or tuning procedures. The user can toggle between pages
depending on the task being performed.
Control Configuration and Set Point Management—Watch Window can
upload or download all tunable variables from the control system. This
feature allows a user (e.g., fleet owner, distributor, packager) to upload (and
save) all tunable parameters from one control and download the same
settings to other controls for similar turbine configurations.
Watch Window version 1.05 and higher, allows for automatic generation of
inspector sheets. Click on the Q icon (Quick Inspector) on the tool bar. A sheet
will automatically be created from each Service and Configure Header
programmed into the control. Multiple inspectors can be created to allow for
viewing more than one sheet at a time.
To enter the I/O Lock mode and enable a configure value to be entered,
click on the I/O Lock icon on the Tool Bar. Because the values set in Configure
are critical to turbine operation, it is not safe to operate the prime mover while
these parameters are being configured. In the Configure mode the control
outputs will be set to off state and the microprocessor will stop executing the
application code. The control will have to be reset to continue operation.
22 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
2300
9-pin D sub
Connector
RS-232
Serial Cable
Note Book PC
Woodward 23
2300 CLM Closed Loop Mate Backup Controller Manual 26331
The 2300 CLM will be changing the protocol mode between Modbus and
ServLink Interface to check what mode is being requested. When a valid link is
detected, it will stop to switch the protocol mode. If Modbus is detected and fails,
it will re-start to check the link. If the ServLink Protocol has been detected, it is
necessary to use a command at Watch Window to leave this mode and re-start
to check the protocol mode, otherwise it will be locked at ServLink Mode.
At this point the ServLink Server program will establish control communications,
begin reading all control setting registers and create a lookup table for these
registers to expedite future control communications. Upon reading register
location information from the control the following Windows pop-up box will
appear. (This step can take several minutes to complete.)
24 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Once all control program registers have been read, the text “Dflt Control ID” will
appear within the ServLink program window and the network definition file can be
saved for future retrieval by the Watch Window program. If the network definition
file is not saved it will have to be re-created before computer-to-control
communications can be established again.
The Watch Window Menu bar, Explorer and Inspector will appear as shown in
Figure 3-4. Click on the icon (Quick Inspector) on the tool bar. Multiple sheets
will automatically be created from each Service and Configure Header
programmed into the control. Optionally, other inspectors can be created to allow
viewing of more than one sheet at a time.
Woodward 25
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Chapter 4.
Service and Configuration
Introduction
This chapter provides information about all service and configure which will be
found during the 2300 CLM configuration and adjustments
A**CONFIGURATION**
01 NUMBER OF TEETH *60 (1,500)
Enter the number of gear teeth seen by MPU.
03 ACTUATOR RANGE
This field will inform using a message (string) the actuator output selected
26 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
11 ACT IN (0–200 mA) HV *160.0 (100.0, 200.0)
Must be entered here the same value obtained at Configure field number 07
Additional considerations from field number 08 are valid.
17 ACTUATOR INPUT
This field will inform using a message (string) the actuator input selected.
**SERVLINK CONFIRMATION**
01 SET TRUE TO LOCK SLINK *FALSE (TRUE, FALSE)
As soon as an entering in Watch Window is made is important to set this
parameter to TRUE so you can navigate on Watch Window. If it’s not done, when
a certain time expires (parameter 3 of this menu) the communication with Watch
Window will be lost.
03 TIME TO ENABLE
This is the remaining time until the communication with Watch Window is lost. It’s
the remaining time to set TRUE to the parameter 1 of this menu.
Woodward 27
2300 CLM Closed Loop Mate Backup Controller Manual 26331
04 DISABLE TIMER
This is the remaining time until a communication is lost by setting the parameter
2 of this menu. When parameter 2 of this menu is set this parameter starts
counting down. When it reaches zero the communication with Watch Window is
lost.
B**SPEED SETPOINTS**
01 MINIMUM SPEED *1000.0 (100.0, 15000.0)
This is the minimum governor speed used when the 2300 CLM is at Manual
Mode.
Lets imagine that the generator is working in parallel mode with the grid or other
turbine/engine. To program actuator droop (kW Droop=FALSE) means that the
valve/actuator will assume a fixed position and the kW can change. The actuator
droop is very useful when to control the fuel/steam demand has a high priority
because the software will ignore the kW changes caused by disturbances at
temperature, pressure, air, etc. Other situation is when is needed to have a
stable kW generation independently of the fuel/steam consumption. If this is
desired operational condition set true to kW Droop.
Woodward 29
2300 CLM Closed Loop Mate Backup Controller Manual 26331
C**GENERATOR APPLICATION**
01 DROOP (%) *5.0 (0.0, 10.0)
This is the kW or Actuator Droop for generators applications. Used when the
generator is in parallel to the grid or other isochronous machine.
30 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
D**CALIBRATION**
01 ACTUATOR INPUT GAIN *1.0 (0.0, 10.0)
Use this field to match the actuator input current (measured) with the current
shown at field D-03. Use 3 or 4 test points to calibrate. Fields D-01 and D-02
works together. Adjust both at same time.
08 STROKE ENABLED
Will indicate if the stroke actuation is enabled or not.
Woodward 31
2300 CLM Closed Loop Mate Backup Controller Manual 26331
11 ACTUATOR OUTPUT GAIN *1.0 (0.01, 10.0)
This value is the multiplier applied at the block output. It is the multiplier for the
position demand received by the hardware driver. The calibration requires
adjusting the zero output value and the output scale. This value (gain) is used at
scale and the next one (D-12) is used to offset null. The actuator position is given
by the equation:
MA_OUT=POS_DEM*GAIN+OFFSET
The current at the actuator input must be equal to the actuator output.
32 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
03 CB AUX
It will indicate the direct state of digital input C. A true indication will inform that
the generator is at droop mode. It has no effect if the 2300 CLM was not
configured for generator application.
04 RAISE SPEED/LOAD
Indicates the state of digital input D (True=Closed, False=Open)
05 LOWER SPEED/LOAD
Indicates the state of digital input E (True=Closed, False=Open)
This input has 2 functions. It is used to force the 2300 CLM to Automatic Mode.
If the prime mover is stopped, always will be at automatic mode. Other situation
is that the emergency start sequence is only possible with the prime mover
stopped. It can be seen that these two situations have a logic of XOR (exclusive
OR). The valid state for one automatically disables the other one. Since this, it
was implemented two functions for this input.
A) If the control mode is Manual and the trip relay from master speed control is
closed, it is possible to return the control from 2300 CLM to master speed
control without the actuator input x actuator output matching criteria. At the
same time it is impossible to do an emergency start sequence. While running
in manual mode, this input will force to automatic mode if the conditions
explained are valid.
B) If the prime mover is stopped (0 RPM) automatically the control mode will be
automatic. If the trip relay is open (master tripped) or the actuator current
from the master is out of range, one pulse of at least 5 seconds at this input
will start to open the actuator, at a programmed rate and until a programmed
maximum value. When the prime mover starts to run the 2300 CLM will
detect the speed threshold and will switch to manual mode and will continue
the start sequence until the rated/synch speed.
07 RESET
Indicates the state of digital input G (True=Closed, False=Open).
The alarm reset will eliminate any alarm or trip state:
Loss of MPU Trip
2300 CLM TRIP (External Trip)
Overspeed trip.
Analog Inputs, Load Sensor failed
Woodward 33
2300 CLM Closed Loop Mate Backup Controller Manual 26331
F**RELAYS**
01 CPU OK RELAY CLOSED
Indicates the state of digital output #1. It will be closed if the 2300 CLM has no
hardware problems but it can be switched off using a Modbus command, to
eliminate 2300 CLM from the actuator loop if this situation is desired.
03 RELAY #3 CLOSED
Will indicate the state of programmable digital output #3
1) Auto/Man Indicator
Using this function, this digital output will be closed for Manual State and Open
for Automatic State.
This is an oscillator that indicates how far the transfer from Manual to Automatic
is. When in Manual mode and the main speed controller is ready to control the
machine again this output starts to emit pulses with frequency proportional to the
difference between the actuator input (sent by the main speed controller) and the
actuator output (sent by the internal PID of the 2300 CLM). When this difference
is big the pulses have a slower frequency, when the difference is small the
frequency of the pulses is faster. When the transference is finished the output
doesn’t send pulses anymore.
To indicate what alarm is active (it can be more than one alarm) flashes will
indicate the alarm number. If there is more than one alarm, one pause between
the flashes will separate the alarms. Observing the number of flashes and the
pause between them, all alarms active will be indicated.
Programming for this function, the fields number 10 and 11 will determinate when
the digital output activates and de-activates in function of the actual speed
(MPU).
34 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
05) Auto Raise Setpoint
06 RELAY #4 CLOSED
Will indicate the state of programmable digital output #4.
G**ANALOG OUTPUT**
01 ANALOG OUTPUT SEL *1 (1, 8)
The options listed will be available at analog output (readout) with a programmed
range:
1) Actual Speed
2) Speed Reference
3) Actuator Input (mA)
4) Actuator Output (mA)
5) PID output (0-100%)
6) Remote Reference (Units)
7) Read kW
8) Absolute Actuator Difference Between Input and Output (%)
Woodward 35
2300 CLM Closed Loop Mate Backup Controller Manual 26331
H**FORCE RELAYS**
01 FORCE OUTPUTS? *FALSE
Set true to force relays output. The only way to force relays is the prime mover is
stopped and the main speed controller and the 2300 CLM are tripped.
02 FORCE ENABLED
It will indicate if the force relays command was accepted or not.
03 DO#1 *FALSE
Used to turn on/off this relay output when in force mode.
04 DO#2 *FALSE
Used to turn on/off this relay output when in force mode.
05 DO#3 *FALSE
Used to turn on/off this relay output when in force mode.
06 DO#4 *FALSE
Used to turn on/off this relay output when in force mode.
02 LINK ERROR
Indicates that slave fails to answer a data request in specified number of time-out
seconds.
03 ERROR PERCENT
Error outputs reflect communication quality as a percentage by dividing the
number of exception error detected by the total number of communication
transactions. This essentially gives the number of message/packet errors
detected.
36 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
04 ERROR NUMBER
Error number outputs the code number of the communication/exception error that
occurred.
11 PARITY *1 (1, 3)
Set the Parity input defines protocol for the parity. If you selected 8 data bits
select “1” for none.
1=OFF (None)
2=ODD
3=EVEN
Woodward 37
2300 CLM Closed Loop Mate Backup Controller Manual 26331
12 PARITY IS SET FOR
Shows the parity setting.
13 DRIVER *1 (1, 2)
Set the driver input defines the type of driver output for this port.
1=RS-232
2=RS-422
K**DISPLAY MENU**
01 AUTOMATIC MODE
Will indicate if the control mode is automatic or not.
02 SPEED SETPOINT
Actual speed setpoint. At automatic mode will be tracking the actual speed, in
manual mode is the setpoint at 2300 CLM control loop.
03 ACTUAL SPEED
Indicates the prime mover speed (RPM).
L**ALARMS**
01 EXTERNAL TRIP
Indicates if an external trip (2300 CLM tripped) is active. In this case the actuator
output will be 0 mA at manual or automatic mode. A reset command is
necessary.
02 OVERSPEED
An overspeed trip was detected. In this case, the actuator output is 0 mA. The
controller is blocked and must be reset.
05 LOSS OF MPU
Loss of MPU indication. This is active only if the loss of MPU occurs when in
control by 2300 CLM.
Woodward 39
2300 CLM Closed Loop Mate Backup Controller Manual 26331
M**EMERGENCY START**
01 ACTUATOR RATE *5.0 (0.01, 100.0)
If the conditions below are true:
1) Prime mover stopped;
2) Main speed controller tripped;
3) Actuator or analog output stroke not active.
it is possible to use an emergency start sequence. In this case, this field will
determine the rate what the actuator position will be increased to re-start the
prime mover in emergency conditions.
Hold digital input F closed for more than 5 seconds, Modbus Command or
ServLink Trigger to start this sequence.
After reaching each setpoint, the start sequence will continue to the
next setpoint after receiving a Raise Speed (Digital Input or Modbus).
During this process is possible to transfer to master (Automatic
Mode) if the required conditions are active.
40 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
N**MONITOR DI STATUS**
01 DIGITAL INPUT #1
Indicates if digital input #1 is opened (FALSE) or closed (TRUE).
02 DIGITAL INPUT #2
Indicates if digital input #2 is opened (FALSE) or closed (TRUE).
03 DIGITAL INPUT #3
Indicates if digital input #3 is opened (FALSE) or closed (TRUE).
04 DIGITAL INPUT #4
Indicates if digital input #1 is opened (FALSE) or closed (TRUE).
05 DIGITAL INPUT #5
Indicates if digital input #5 is opened (FALSE) or closed (TRUE).
06 DIGITAL INPUT #6
Indicates if digital input #6 is opened (FALSE) or closed (TRUE).
07 DIGITAL INPUT #7
Indicates if digital input #7 is opened (FALSE) or closed (TRUE).
O**SPEED PID**
01 PROPORTIONAL GAIN *3.2 (0.01, 50.0)
Proportional Gain of 2300 CLM PID. It represents the amount of actuator action
in function of the error value.
Woodward 41
2300 CLM Closed Loop Mate Backup Controller Manual 26331
P**ACTUATOR TRANSFER**
01 MAX ACT DIFF ON TRANSFR *1.0 (1.0, 5.0)
This is the maximum actuator difference between actuator input and output
allowed to perform an automatic transfer from the 2300 CLM and the main
controller.
Q**TIME DELAY**
01 SELECT TIME DELAY (MPU) *4 (1, 7)
At the moment of the trip, the speed can change and it could be a problem to
keep the exact setpoint before the fail. Because this situation, it is possible to use
the sensed value from 0 up to 0.96 s before the fail, in intervals of 0.16 s. Set the
option at this field.
R**AUTO RAISE/LOWER**
01 USE AUTO RAISE/LOWER? *FALSE
This item enables the auto raise/lower function. This function will manage the
raise/lower pulses to the main speed controller or the load controller in order to
help the transference from manual to automatic mode. If this parameter is set to
TRUE and the programmable relays #3 and #4 are programmed to Auto Raise
Setpoint and Auto Lower Setpoint there’s no need to increase /decrease the
speed/load setpoint in the main speed controller/load controller in order to
transfer the 2300 CLM from Manual mode to Automatic mode; the 2300 CLM will
do that job since the raise/lower outputs (programmable outputs #3 and #4) of
the 2300 CLM are tied to the raise/lower speed/load of the main speed
controller/load control.
42 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
02 DELAY FOR ACTION? *5.0 (0.0, 60.0)
After all the conditions of the auto raise/lower logic are fulfilled this parameter
defines the delay (in minutes) for the raise/lower pulses to start acting. The
conditions to start counting this delay are:
1) The control is in Manual Mode (controlled by the 2300 CLM)
2) There is no mere trip signal coming from the main speed controller.
3) The parameter 1 of this menu is set TRUE.
Woodward 43
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Chapter 5.
Communications
Modbus Communication
The 2300 CLM control can communicate with plant distributed control systems or
CRT based operator control panels through one Modbus communication port.
The communication port support RS-232 and RS-422 communications using
RTU Modbus transmission protocols. Modbus utilizes a master/slave protocol.
Characteristic RTU
Coding System 8-bit binary
Start Bits 1
Data Bits per Character 8
Parity none
Stop Bits 1
Baud Rate 110,300, 600, 1200, 1800, 2400, 4800, 9600, 19200,
or 38400
Error Checking CRC (Cyclical Redundancy Check)
In the RTU mode, data is sent in 8-bit binary characters and transmitted in a
continuous stream.
The Modbus protocol allows one master and up to 247 slaves on a common
network. Each slave is assigned a fixed, unique device address in the range of 1
to 247. With the Modbus protocol, only the network master can initiate a
transaction. A transaction consists of a request from the master to a slave unit
and the slave’s response. The protocol and Modbus device number are set in the
Program Mode and can be adjusted in the Service Mode, if required.
The 2300 CLM control is programmed to function as a slave unit only. As a slave
unit, the 2300 CLM will only respond to a transaction request by a master device.
The 2300 CLM can directly communicate with a DCS or other Modbus supporting
device on a single communications link, or through a multi-dropped network. If
multi-dropping is used, up to 246 devices (2300 CLMs or other customer
devices) can be connected to one Master device on a single network. The control
address is programmed under the 2300 CLM’s communications block.
Each message to or from a master has a defined structure called the message
“frame”. A frame consists of the slave device address, a code defining the
requested data and error checking information (see Table 4-2).
44 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Beginning SLAVE Function DATA Error End of
of Frame Address Code Check Frame
Code
The Modbus function code tells the addressed slaves what function to perform.
Table 4-3 lists the function codes supported by this control.
Port Adjustments
Before the 2300 CLM will communicate with the master device, the
communication parameters must be verified. These values are set from the
Service Mode.
Woodward 45
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Chapter 6.
Service Options
OEM and Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the best
source for product service and support. Warranty service for Woodward products
shipped with an equipment system should also be handled through the OEM or
Packager. Please review your equipment system documentation for details.
You can locate your nearest Woodward distributor, AISF, RER, or RTR on our
website at:
www.woodward.com/directory
46 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.
Charges for the Replacement/Exchange service are based on a flat rate plus
shipping expenses. You are invoiced the flat rate replacement/exchange charge
plus a core charge at the time the replacement unit is shipped. If the core (field
unit) is returned within 60 days, a credit for the core charge will be issued.
Flat Rate Repair: Flat Rate Repair is available for the majority of standard
products in the field. This program offers you repair service for your products with
the advantage of knowing in advance what the cost will be. All repair work carries
the standard Woodward service warranty (Woodward Product and Service
Warranty 5-01-1205) on replaced parts and labor.
Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option with the exception that the unit will be returned to you in “like-
new” condition and carry with it the full standard Woodward product warranty
(Woodward Product and Service Warranty 5-01-1205). This option is applicable
to mechanical products only.
When shipping the item(s), attach a tag with the following information:
return authorization number;
name and location where the control is installed;
name and phone number of contact person;
complete Woodward part number(s) and serial number(s);
description of the problem;
instructions describing the desired type of repair.
Woodward 47
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Packing a Control
Use the following materials when returning a complete control:
protective caps on any connectors;
antistatic protective bags on all electronic modules;
packing materials that will not damage the surface of the unit;
at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
a packing carton with double walls;
a strong tape around the outside of the carton for increased strength.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
the unit serial number, which is also on the nameplate.
Engineering Services
Woodward offers various Engineering Services for our products. For these services,
you can contact us by telephone, by email, or through the Woodward website.
Technical Support
Product Training
Field Service
Technical Support is available from your equipment system supplier, your local Full-
Service Distributor, or from many of Woodward’s worldwide locations, depending
upon the product and application. This service can assist you with technical
questions or problem solving during the normal business hours of the Woodward
location you contact. Emergency assistance is also available during non-business
hours by phoning Woodward and stating the urgency of your problem.
For information on these services, please contact us via telephone, email us, or
use our website: www.woodward.com.
48 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
You can also locate your nearest Woodward distributor or service facility on our
website at:
www.woodward.com/directory
Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information.
Please write it down here before phoning:
Your Name
Site Location
Phone Number
Fax Number
Engine/Turbine Model Number
Manufacturer
Number of Cylinders (if applicable)
Type of Fuel (gas, gaseous, steam, etc)
Rating
Application
Control/Governor #1
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
Control/Governor #2
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
Control/Governor #3
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
Woodward 49
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Appendix A.
Modbus Communication List
Boolean Writes
Address Description
0:0001 Set digital input A (trip from main speed controller)
0:0002 Reset digital input A (trip from main speed controller)
0:0003 Set/reset digital input B (shutdown)
0:0004 Raise speed/kW command (pulse)
0:0005 Lower speed/kW command (pulse)
0:0006 Remote reference enable (generator or mechanical load)
0:0007 Emergency start trigger
0:0008 Turn off CPU OK relay
0:0009 Reset alarms
0:0010 Force to Automatic Mode
0:0011 Use Modbus Reference (generator or mechanical load)
Boolean Reads
Address Description
1:0001 Relay 01 state
1:0002 Relay 02 state
1:0003 Relay 03 state
1:0004 Relay 04 state
1:0005 Hardware input 01
1:0006 Hardware input 02
1:0007 Hardware input 03
1:0008 Hardware input 04
1:0009 Hardware input 05
1:0010 Hardware input 06
1:0011 Hardware input 07
1:0012 Manual Mode on
1:0013 At error window
1:0014 Trip from main speed controller
1:0015 2300 CLM shutdown
1:0016 CB Aux (Droop / Isochronous)
1:0017 Overspeed trip
1:0018 Actuator ramp at emergency start
1:0019 Remote reference fail
1:0020 Reverse power
1:0021 Raise speed/kW command
1:0022 Lower speed/kW command
1:0023 Loss of MPU trip
1:0024 Speed switch on?
50 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
Analog Reads
Analog Writes
Woodward 51
2300 CLM Closed Loop Mate Backup Controller Manual 26331
Appendix B.
Service / Configure Chart
B**SPEED SETPOINTS**
01 Minimum speed 1000 100 15000
02 Maximum speed 4000 100 15000
03 4mA speed 1000 100 15000
04 20mA speed 4000 100 15000
05 Raise speed rate 2.5 0.1 1000
06 Lower speed rate 2.5 0.1 1000
07 Remote rate 2.5 0.1 1000
08 Modbus rate 2.5 0.1 1000
09 Speed threshold 100 100 250
10 Use kW droop? FALSE FALSE TRUE
11 Mdbus raise pulse (s) 1 0.1 10
12 Mdbus lower pulse (s) 1 0.1 10
13 Recover Rate 10 0.1 1000
52 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
SERVICE PROGRAMMED DEFAULT TUNABLE RANGE
MENU VALUE VALUE MINIMUM MAXIMUM
C**GENERATOR APPLICATION**
01 Droop (%) 5 0 10
02 Droop adjust (rpm) 15 0 100
03 Raise load rate 10 0.1 1000
04 Lower load rate 10 0.1 1000
05 Remote load rate 10 0.1 1000
06 Modbus load rate 10 0.1 1000
07 Synchronous speed 1800 100 15000
08 Use minimum bias? TRUE FALSE TRUE
09 Minimum bias (rpm) 5 0 100
D**CALIBRATION**
01 Actuator input gain 1 0 10
02 Actuator input offset 0 -100 100
03 Act current sensed (mA) Monitor
04 Analog input gain 1 0 10
05 Analog input offset 0 -20 20
06 Analog input sensed (mA) Monitor
07 Stroke actuator? FALSE FALSE TRUE
08 Stroke enabled Monitor
09 Actuator output (mA) Monitor
10 Actuator position (%) 0 0 100
11 Actuator output gain 1 0.01 10
12 Actuator output offset 0 -20 20
13 Force analog out? FALSE FALSE TRUE
14 Analog force enabled Monitor
15 Analog out value (%) 0 0 100
16 Analog out gain 1 0.01 100
17 Analog out offset 0 -100 100
18 Analog out min current 4 0 20
19 Analog out max current 20 0 22
Woodward 53
2300 CLM Closed Loop Mate Backup Controller Manual 26331
SERVICE PROGRAMMED DEFAULT TUNABLE RANGE
MENU VALUE VALUE MINIMUM MAXIMUM
F**RELAYS**
01 CPU OK relay closed Monitor
02 Trip relay closed Monitor
03 Relay #3 closed Monitor
04 Relay #3 function 1 1 6
05 Relay #3 prog for Monitor
06 Relay #4 closed Monitor
07 Relay #4 function 1 1 6
08 Relay #4 prog for Monitor
09 Level rly sw on 2000 0 15000
10 Level rly sw off 1000 0 15000
11 Level switch on? Monitor
G**ANALOG OUTPUT**
01 Analog output sel 1 1 7
02 Analog output used for Monitor
03 4mA value 1000 0 30000
04 20mA value 1000 0 30000
H**FORCE RELAYS**
01 Force outputs? FALSE FALSE TRUE
02 Force enabled Monitor
03 DO#1 FALSE FALSE TRUE
04 DO#2 FALSE FALSE TRUE
05 DO#3 FALSE FALSE TRUE
06 DO#4 FALSE FALSE TRUE
54 Woodward
Manual 26331 2300 CLM Closed Loop Mate Backup Controller
SERVICE PROGRAMMED DEFAULT TUNABLE RANGE
MENU VALUE VALUE MINIMUM MAXIMUM
J**COMM PORT (MODBUS)**
01 Port fail Monitor
02 Link error Monitor
03 Error percent Monitor
04 Error number Monitor
05 Baud rate 10 1 10
06 Baud rate is set for Monitor
07 Data bits 2 1 2
08 Data bits are set for Monitor
09 Stop bits 1 1 3
10 Stop bits are set for Monitor
11 Parity 1 1 3
12 Parity is set for Monitor
13 Driver 1 1 2
14 Driver is set for Monitor
15 Time out (sec) 4 1 10
16 Network address 1 1 247
17 kW multiplier 1 0.01 1000
18 Analog in multiplier 1 0.01 1000
19 Analog out multiplier 1 0.01 1000
20 Activate modbus trig FALSE FALSE TRUE
21 Use modbus comm? TRUE FALSE TRUE
K**DISPLAY MENU**
01 Automatic Mode Monitor
02 Speed setpoint Monitor
03 Actual speed Monitor
04 Actuator input (mA) Monitor
05 Actuator output (mA) Monitor
06 Generator output (kW) Monitor
07 Analog out (units) Monitor
08 Remote input (rpm) Monitor
09 Speed ref gen Monitor
10 Speed PID output (%) Monitor
11 Using gain ratio Monitor
12 Prop gain at PID Monitor
L**ALARMS**
01 External trip Monitor
02 Overspeed Monitor
03 4-20mA input fail Monitor
04 Load sensor fail Monitor
05 Loss of MPU Monitor
06 Reset alarms FALSE FALSE TRUE
Woodward 55
2300 CLM Closed Loop Mate Backup Controller Manual 26331
SERVICE PROGRAMMED DEFAULT TUNABLE RANGE
MENU VALUE VALUE MINIMUM MAXIMUM
M**EMERGENCY START**
01 Actuator rate 5 0.01 100
02 Override speed (rpm) 500 300 1000
03 Max act pos at strt (%) 20 0 100
04 Start trigger FALSE FALSE TRUE
05 Start speed 1000 100 15000
06 Low idle speed 1200 100 15000
07 High idle speed 1500 100 15000
08 Rated/sync speed 1800 1000 15000
09 Start-low idle rate 20 1 1000
10 Low-high idle rate 20 1 1000
11 Hi idle-rated/sync rate 20 1 1000
N**MONITOR DI STATUS**
01 Digital Input #1 Monitor
02 Digital Input #2 Monitor
03 Digital Input #3 Monitor
04 Digital Input #4 Monitor
05 Digital Input #5 Monitor
06 Digital Input #6 Monitor
07 Digital Input #7 Monitor
O**SPEED PID**
01 Proportional gain 3.2 0.01 50
02 Integral gain 0.5 0.01 50
03 S_D_R 5 0.01 100
04 Gain ratio 1 0.01 10
05 Error window (rpm) 10 0 500
P**TRANSFER ACTUATOR**
01 Max Act difference on transfer 0.5 0.1 5
02 Act delay on auto transfer 0.1 0.05 1
03 Max Act difference on ForceAuto 5 0.5 30
Q**TIME DELAY**
01 Select time delay (MPU) 4 1 7
02 Time delay for MPU Monitor
03 Select time delay (ACT) 4 1 7
04 Time delay for ACT/kW Monitor
R**AUTO RAISE/LOWER**
01 Use Auto Raise/Lower?
02 Delay for Action
03 Auto Raise/Lower Status Monitor
04 Actuator Deriv Setpoint 0.5 0.1 5
05 Act Diff Hysteresis 4 1 10
06 Pulse Time (s) 1.5 0.1 10
07 Time Between Pulses (s) 1.5 0.1 10
56 Woodward
2300 CLM Control Specifications
Woodward Part Numbers:
8237-1132 2300 CLM certified for ordinary locations
8237-1155 2300 CLM certified for hazardous locations
8923-932 Watch Window Installation
Regulatory Compliance
European Compliance for CE Mark:
EMC Directive Declared to 89/336/EEC COUNCIL DIRECTIVE of 03 May 1989 on the
approximation of the laws of the member states relating to electromagnetic
compatibility.
Low Voltage Directive Declared to the 73/23/EEC COUNCIL DIRECTIVE of 19 February 1973 on
the harmonization of the laws of the Member States relating to electrical
equipment designed for use within certain voltage limits.
Marine Compliance:
Bureau Veritas BV Rules Part C, June 2000
Germanischer Lloyd Additional Rules and Guidelines, Part 1, 2001
Lloyd’s Register of Shipping Type Approval System, Test Specification Number 1, 2002
NOTE These certifications apply to specific models only.
Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and
other authorized service and sales facilities throughout the world.
Complete address / phone / fax / email information for all locations is available on our website.