Product datasheet
Specifications
MicroLogic 5.0X control unit,
MasterPact MTZ2/MTZ3, drawout
circuit breakers, LSI protections
LV848499
Main
Range MasterPacT
Device short name MicroLogic 5.0 X
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Control unit
Device application Equipment protection, monitoring and control
Circuit breaker application Distribution IEC standard
Range compatibility MasterPact MTZ2 circuit breaker
MasterPact MTZ3 circuit breaker
Poles 3P
4P
Protected poles description 3P 3d
4P 3d
4P 3d + N/2
4P 4d
4P 3d + OSN
[Ue] rated operational voltage 690 V AC, +/- 10 %
Network type AC
Network frequency 50/60 Hz
Trip unit technology Electronic
Trip unit protection functions LSI
Protection type Overload protection (long time) conforming to ANSI 49
Instantaneous short-circuit protection conforming to ANSI 50
Short time short-circuit protection conforming to ANSI 51
Trip unit rating 400 A
630 A
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
5000 A
6300 A
Complementary
mounting mode Drawout
Neutral protection setting 1 x Ir (4P 4d)
0.5 x Ir (4P 3d + N/2)
1.6 x Ir (4P 3d + OSN)
No protection (4P 3d)
[Ir] long time pick-up adjustment 0.4...1 x In adjustable in step of 1 A
range
26 Sept 2024 1
Long time delay adjustment type Adjustable in step of 0.5 s
[tr] long-time delay adjustment 12.5…600 s at 1.5 x Ir
range 0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
thermal memory Yes
[Isd] short-time pick-up 1.5...10 x Ir adjustable in step of 0.5 x Ir with embedded HMI
adjustment range 1.5...10 x Ir adjustable in step of 0.1 x Ir with Ecoreach software or MasterPact MTZ
mobile app
Short-time delay adjustment type Adjustable
[tsd] short-time delay adjustment 0.1…0.4 s I²t=on
range 0…0.4 s I²t=off
Instantaneous pick-up adjustment Adjustable
type Ii
[Ii] instantaneous pick-up 2...15 x In adjustable in step of 0.5 x In with embedded HMI
adjustment range 2...15 x In adjustable in step of 0.1 x In with Ecoreach software or MasterPact MTZ
mobile app
Ii enable on/off
[li mode] instantaneous delay 0 ms in fast
adjustment range 20 ms in standard
Zone selective interlocking ZSI With
Network and machine diagnosis System (HMI) health state overview: circuit breaker health state
type Contacts state: circuit breaker health state
MicroLogic service life: circuit breaker health state
Tripping cause indication: circuit breaker tripping cause
Identification card: diagnostic data
Configured alarms synthesis: diagnostic data
Monitored function: diagnostic data
Operation: diagnostic data
MicroLogic test: test
Protection test: test
Selectivity test: test
Trip context information: crisis management
Operation: advanced diagnostic
Breaker service life: circuit breaker health state
Type of measurement Power meter
Energy management Measurement ,active, reactive and apparent energy
Measurement ,electrical network
Measurement ,energy
Metering type Current I1, I2, I3, Iavg RMS
Neutral current IN RMS
Ground fault current Ig RMS
Voltage V12, V23, V31, VLLavg RMS
Voltage V1N, V2N, V3N, VLNavg RMS
Active power P, P1, P2, P3 total
Reactive power Q, Q1, Q2, Q3 total
Apparent power S, S1, S2, S3 total
Power factor
Active energy Ep IN/OUT/tot
Reactive energy Eq IN/OUT/tot
Apparent energy Es IN/OUT/tot
Demand current I1, I2, I3, In, Iavg
Demand power P, Q, S
Frequency
Phase sequence
Earth leakage current
Total current harmonic distortion THD (I)
Total voltage harmonic distortion THD (V)
Unbalance current
Unbalance voltage
Measurement voltage 208…828 V AC 50/60 Hz phase to phase
120…480 V AC 50/60 Hz phase to neutral
Frequency measurement range 40…70 Hz
2 26 Sept 2024
Measurement accuracy Current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A
Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 0.5 % 40...4000 x 1.2 A
Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 0.5 % 80...6300 x 1.2 A
Neutral current IN: +/- 1 %
Ground fault current Ig: +/- 5 %
Voltage V12, V23, V31, VLLavg: +/- 0.5 % 208...690 x 1.2 V
Voltage V1N, V2N, V3N, VLNavg: +/- 0.5 % 120...400 x 1.2 V
Active power P, P1, P2, P3, Pdemand: +/- 1 %
Reactive power Q, Q1, Q2, Q3, Qdemand: +/- 2 %
Apparent power S, S1, S2, S3, Sdemand: +/- 1 %
Power factor: +/- 2 %
Active energy Ep IN/OUT/tot: +/- 1 %
Reactive energy Ep IN/OUT/tot: +/- 2 %
Apparent energy Es IN/OUT/tot: +/- 1 %
Frequency: +/- 0.005 Hz
Earth leakage current: +/- 10 %
Unbalance current: +/- 0.5 %
Accuracy class Class 5: total current harmonic distortion THD (I)
Class 0.5: unbalance voltage
Class 1: active and reactive energy by pulse counting (+/- W.h, +/- VAR.h)
Class 2: total voltage harmonic distortion THD (V)
Display type LCD display - 128 x 96 pixels
Communication port protocol Bluetooth 4.0 LE peer to peer 30 kbit/s
NFC peer to peer conforming to ISO 15963
USB peer to peer 115 kbauds
Data recording Event logs
Data logs
Time stamping
Alarm logs
Min/max of instantaneous values
Maintenance logs
Environment
Standards EN/IEC 60947-2
EN/IEC 60947-1
EN/IEC 60255-1
EN/IEC 60092-202
EN/IEC 61010-1
mounting location Indoor use only
Environmental characteristic Wet location not approved for use conforming to IEC 61010-1
Electromagnetic compatibility Electrostatic discharge immunity test conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Conducted and radiated emissions A conforming to CISPR 22
Overvoltage category IV conforming to IEC 61010-1
Measurement category Category IV conforming to IEC 61010-2-30
Pollution degree 3 conforming to IEC 60947-1
Ambient air temperature for -25…70 °C (operating)
operation -35 °C (for start-up of product)
Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
Operating altitude <= 2000 m without derating
<= 4000 m with operational voltage derating 600 V AC
<= 5000 m with operational voltage derating 560 V AC
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 6.7 cm
26 Sept 2024 3
Package 1 Width 7.9 cm
Package 1 Length 21.6 cm
Package 1 Weight 369.0 g
Contractual warranty
Warranty 18 months
4 26 Sept 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Well-being performance
Mercury Free
Rohs Exemption Information Yes
Pvc Free
Halogen Free Plastic Parts Product
Certifications & Standards
Reach Regulation REACh Declaration
Eu Rohs Directive Compliant with Exemptions
China Rohs Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
26 Sept 2024 5