Siemens S7-200 Driver: © 2018 PTC Inc. All Rights Reserved
Siemens S7-200 Driver: © 2018 PTC Inc. All Rights Reserved
Table of Contents
Siemens S7-200 Driver 1
Table of Contents 2
Overview 3
Setup 4
Channel Properties 4
Channel Properties — General 5
Channel Properties — Serial Communications 6
Channel Properties — Write Optimizations 8
Channel Properties — Advanced 9
Channel Properties — Communication Serialization 10
Channel Properties - Master ID 11
Device Properties 11
Device Properties - General 11
Device Properties — Scan Mode 13
Device Properties — Timing 13
Device Properties — Auto-Demotion 14
Device Properties — Redundancy 15
Address Descriptions 17
S7-200 Addressing 17
Index 25
www. ptc.com
3 Siemens S7-200 Driver
CONTENTS
Overview
What is the Siemens S7-200 Driver?
Device Setup
How do I configure a device for use with this driver?
Address Descriptions
How do I address a data location on a Siemens S7-200 device?
Overview
The Siemens S7-200 Driver provides a reliable way to connect Siemens S7-200 devices to OPC Client
applications, including HMI, SCADA, Historian, MES, ERP, and countless custom applications. It is intended
for use with Siemens S7-200 devices, and supports a 10 or 11-bit setting for the PPI programming cable.
When using the 10-bit mode (specifically, the EM 241 Modem Module), the S7-200 PPM mode should be
selected. When using the 11-bit mode, the S7-200 model should be selected.
www. ptc.com
Siemens S7-200 Driver 4
Setup
The maximum number of supported channels is 256. The maximum number of devices supported per
channel is 127.
Ethernet Encapsulation
This driver supports Ethernet Encapsulation, which allows the driver to communicate with serial devices
attached to an Ethernet network using a terminal or device server. It may be invoked through the COM ID in
Channel Properties. For more information, refer to the main server's help documentation.
Communication Protocols
Point-to-Point (PPI) S7-200 Communications Protocol (11-bit mode).
Point-to-Point Modem (PPM) S7-200 Communications Protocol (10-bit mode).
The Siemens S7-200 Driver normally operates using the standard 11-bit PPI protocol. If the EM 241 modem
module is required, the S7-200 PPM model must be selected. This model allows the driver to operate in a 10-
bit mode that is compatible with many off-the-shelf modems. The 10-bit PPM mode can also be used directly
on the PLC's programming port. To enable 10-bit PPM mode, set the S7-200 programming cable to 10-bit
mode.
Flow Control
When using an RS232/RS485 converter, the type of flow control that is required depends on the needs of the
converter. Some converters do not require any flow control and others require RTS flow. Consult the
converter's documentation to determine its flow requirements. An RS485 converter that provides automatic
flow control is recommended.
Note: When using the manufacturer's supplied communications cable, it is sometimes necessary to
choose a flow control setting of RTS or RTS Always under the channel properties.
Supported Devices
Siemens S7-200 devices
Supported Cables
A special cable is required to communicate with the S7-200 PLC. The cable recommended by the
manufacturer should be used.
See Also: Device Properties
Channel Properties
This server supports the use of simultaneous multiple communications drivers. Each protocol or driver used
in a server project is called a channel. A server project may consist of many channels with the same
communications driver or with unique communications drivers. A channel acts as the basic building block of
an OPC link.
The properties associated with a channel are broken in to logical groupings. While some groups are specific
to a given driver or protocol, the following are the common groups:
www. ptc.com
5 Siemens S7-200 Driver
General
Ethernet or Serial Communications
Write Optimization
Advanced
Identification
Name: User-defined identity of this channel. In each server project, each channel name must be unique.
Although names can be up to 256 characters, some client applications have a limited display window when
browsing the OPC server's tag space. The channel name is part of the OPC browser information.
For information on reserved characters, refer to "How To... Properly Name a Channel, Device, Tag, and Tag
Group" in the server help.
Driver: Selected protocol / driver for this channel. This property specifies the device driver that was selected
during channel creation. It is a disabled setting in the channel properties.
Note: With the server's online full-time operation, these properties can be changed at any time. This
includes changing the channel name to prevent clients from registering data with the server. If a client has
already acquired an item from the server before the channel name is changed, the items are unaffected. If,
after the channel name has been changed, the client application releases the item and attempts to re-
acquire using the old channel name, the item is not accepted. With this in mind, changes to the properties
should not be made once a large client application has been developed. Utilize the User Manager to prevent
operators from changing properties and restrict access rights to server features.
Diagnostics
Diagnostics Capture: When enabled, this option makes the channel's diagnostic information available to
OPC applications. Because the server's diagnostic features require a minimal amount of overhead
processing, it is recommended that they be utilized when needed and disabled when not. The default is
disabled.
Note: This property is not available if the driver does not support diagnostics.
For more information, refer to "Communication Diagnostics" in the server help.
www. ptc.com
Siemens S7-200 Driver 6
Note: With the server's online full-time operation, these properties can be changed at any time. Utilize
the User Manager to restrict access rights to server features, as changes made to these properties can
temporarily disrupt communications.
Connection Type
Physical Medium: Choose the type of hardware device for data communications. Options include COM
Port, None, Modem, and Ethernet Encapsulation. The default is COM Port.
l None: Select None to indicate there is no physical connection, which displays the Operation with no
Communications section.
l COM Port: Select Com Port to display and configure the Serial Port Settings section.
l Modem: Select Modem if phone lines are used for communications, which are configured in the
Modem Settings section.
l Ethernet Encap.: Select if Ethernet Encapsulation is used for communications, which displays the
Ethernet Settings section.
l Shared: Verify the connection is correctly identified as sharing the current configuration with another
channel. This is a read-only property.
COM ID: Specify the Communications ID to be used when communicating with devices assigned to the
channel. The valid range is 1 to 9991 to 16. The default is 1.
Baud Rate: Specify the baud rate to be used to configure the selected communications port.
Data Bits: Specify the number of data bits per data word. Options include 5, 6, 7, or 8.
www. ptc.com
7 Siemens S7-200 Driver
Parity: Specify the type of parity for the data. Options include Odd, Even, or None.
Stop Bits: Specify the number of stop bits per data word. Options include 1 or 2.
Flow Control: Select how the RTS and DTR control lines are utilized. Flow control is required to communicate
with some serial devices. Options are:
Tip: When using two-wire RS-485, "echoes" may occur on the communication lines. Since this
communication does not support echo suppression, it is recommended that echoes be disabled or a RS-485
converter be used.
Operational Behavior
l Report Comm. Errors: Enable or disable reporting of low-level communications errors. When
enabled, low-level errors are posted to the Event Log as they occur. When disabled, these same
errors are not posted even though normal request failures are. The default is Enable.
l Close Idle Connection: Choose to close the connection when there are no longer any tags being
referenced by a client on the channel. The default is Enable.
l Idle Time to Close: Specify the amount of time that the server waits once all tags have been
removed before closing the COM port. The default is 15 seconds.
Ethernet Settings
Note: Not all serial drivers support Ethernet Encapsulation. If this group does not appear, the functionality
is not supported.
Ethernet Encapsulation provides communication with serial devices connected to terminal servers on the
Ethernet network. A terminal server is essentially a virtual serial port that converts TCP/IP messages on the
Ethernet network to serial data. Once the message has been converted, users can connect standard devices
that support serial communications to the terminal server. The terminal server's serial port must be
properly configured to match the requirements of the serial device to which it is attached. For more
information, refer to "How To... Use Ethernet Encapsulation" in the server help.
www. ptc.com
Siemens S7-200 Driver 8
l Network Adapter: Indicate a network adapter to bind for Ethernet devices in this channel. Choose a
network adapter to bind to or allow the OS to select the default.
Specific drivers may display additional Ethernet Encapsulation properties. For more information, refer
to Channel Properties — Ethernet Encapsulation.
Modem Settings
l Modem: Specify the installed modem to be used for communications.
l Connect Timeout: Specify the amount of time to wait for connections to be established before
failing a read or write. The default is 60 seconds.
l Modem Properties: Configure the modem hardware. When clicked, it opens vendor-specific modem
properties.
l Auto-Dial: Enables the automatic dialing of entries in the Phonebook. The default is Disable. For
more information, refer to "Modem Auto-Dial" in the server help.
l Report Comm. Errors: Enable or disable reporting of low-level communications errors. When
enabled, low-level errors are posted to the Event Log as they occur. When disabled, these same
errors are not posted even though normal request failures are. The default is Enable.
l Close Idle Connection: Choose to close the modem connection when there are no longer any tags
being referenced by a client on the channel. The default is Enable.
l Idle Time to Close: Specify the amount of time that the server waits once all tags have been
removed before closing the modem connection. The default is 15 seconds.
Write Optimizations
Optimization Method: controls how write data is passed to the underlying communications driver. The
options are:
l Write All Values for All Tags: This option forces the server to attempt to write every value to the
controller. In this mode, the server continues to gather write requests and add them to the server's
internal write queue. The server processes the write queue and attempts to empty it by writing data
www. ptc.com
9 Siemens S7-200 Driver
to the device as quickly as possible. This mode ensures that everything written from the client
applications is sent to the target device. This mode should be selected if the write operation order or
the write item's content must uniquely be seen at the target device.
l Write Only Latest Value for Non-Boolean Tags: Many consecutive writes to the same value can
accumulate in the write queue due to the time required to actually send the data to the device. If the
server updates a write value that has already been placed in the write queue, far fewer writes are
needed to reach the same final output value. In this way, no extra writes accumulate in the server's
queue. When the user stops moving the slide switch, the value in the device is at the correct value at
virtually the same time. As the mode states, any value that is not a Boolean value is updated in the
server's internal write queue and sent to the device at the next possible opportunity. This can greatly
improve the application performance.
Note: This option does not attempt to optimize writes to Boolean values. It allows users to
optimize the operation of HMI data without causing problems with Boolean operations, such as a
momentary push button.
l Write Only Latest Value for All Tags: This option takes the theory behind the second optimization
mode and applies it to all tags. It is especially useful if the application only needs to send the latest
value to the device. This mode optimizes all writes by updating the tags currently in the write queue
before they are sent. This is the default mode.
Duty Cycle: is used to control the ratio of write to read operations. The ratio is always based on one read for
every one to ten writes. The duty cycle is set to ten by default, meaning that ten writes occur for each read
operation. Although the application is performing a large number of continuous writes, it must be ensured
that read data is still given time to process. A setting of one results in one read operation for every write
operation. If there are no write operations to perform, reads are processed continuously. This allows
optimization for applications with continuous writes versus a more balanced back and forth data flow.
Note: It is recommended that the application be characterized for compatibility with the write
optimization enhancements before being used in a production environment.
l Replace with Zero: This option allows a driver to replace non-normalized IEEE-754 floating point
values with zero before being transferred to clients.
l Unmodified: This option allows a driver to transfer IEEE-754 denormalized, normalized, non-
number, and infinity values to clients without any conversion or changes.
Note: This property is not available if the driver does not support floating point values or if it only supports
the option that is displayed. According to the channel's float normalization setting, only real-time driver tags
www. ptc.com
Siemens S7-200 Driver 10
(such as values and arrays) are subject to float normalization. For example, EFM data is not affected by this
setting.
For more information on the floating point values, refer to "How To ... Work with Non-Normalized Floating
Point Values" in the server help.
Inter-Device Delay: Specify the amount of time the communications channel waits to send new requests to
the next device after data is received from the current device on the same channel. Zero (0) disables the
delay.
Note: This property is not available for all drivers, models, and dependent settings.
The term "virtual network" describes a collection of channels and associated devices that use the same
pipeline for communications. For example, the pipeline of an Ethernet radio is the master radio. All channels
using the same master radio associate with the same virtual network. Channels are allowed to communicate
each in turn, in a "round-robin" manner. By default, a channel can process one transaction before handing
communications off to another channel. A transaction can include one or more tags. If the controlling
channel contains a device that is not responding to a request, the channel cannot release control until the
transaction times out. This results in data update delays for the other channels in the virtual network.
Channel-Level Settings
Virtual Network This property specifies the channel's mode of communication serialization. Options
include None and Network 1 - Network 500. The default is None. Descriptions of the options are as follows:
Transactions per Cycle This property specifies the number of single blocked/non-blocked read/write
transactions that can occur on the channel. When a channel is given the opportunity to communicate, this
number of transactions attempted. The valid range is 1 to 99. The default is 1.
Global Settings
www. ptc.com
11 Siemens S7-200 Driver
l Network Mode: This property is used to control how channel communication is delegated. In Load
Balanced mode, each channel is given the opportunity to communicate in turn, one at a time. In
Priority mode, channels are given the opportunity to communicate according to the following rules
(highest to lowest priority):
l Channels with pending writes have the highest priority.
l Channels with pending explicit reads (through internal plug-ins or external client interfaces)
are prioritized based on the read's priority.
l Scanned reads and other periodic events (driver specific).
The default is Load Balanced and affects all virtual networks and channels.
Devices that rely on unsolicited responses should not be placed in a virtual network. In situations where
communications must be serialized, it is recommended that Auto-Demotion be enabled.
Due to differences in the way that drivers read and write data (such as in single, blocked, or non-blocked
transactions); the application's Transactions per cycle property may need to be adjusted. When doing so,
consider the following factors:
Master ID: Specify the node number used by the Siemens S7-200 Driver on the network. Each channel must
have a unique Master ID. The valid range is 0 to 126.
Device Properties
Device properties are organized into the following groups. Click on a link below for details about the settings
in that group.
General
Scan Mode
Communication Timeouts
Auto-Demotion
Redundancy
www. ptc.com
Siemens S7-200 Driver 12
Identification
Channel Assignment: User-defined name of the channel to which this device currently belongs.
ID Format: Select how the device identity is formatted. Options include Decimal, Octal, and Hex.
ID: the unique identity of the device for communication with the driver. The valid range is 0 to 126. Any
devices defined under this channel should not use an ID that conflicts with the Master ID.
Operating Mode
Data Collection: This property controls the device's active state. Although device communications are
enabled by default, this property can be used to disable a physical device. Communications are not
attempted when a device is disabled. From a client standpoint, the data is marked as invalid and write
operations are not accepted. This property can be changed at any time through this property or the device
system tags.
Simulated: This option places the device into Simulation Mode. In this mode, the driver does not attempt to
communicate with the physical device, but the server continues to return valid OPC data. Simulated stops
physical communications with the device, but allows OPC data to be returned to the OPC client as valid data.
While in Simulation Mode, the server treats all device data as reflective: whatever is written to the simulated
device is read back and each OPC item is treated individually. The item's memory map is based on the group
Update Rate. The data is not saved if the server removes the item (such as when the server is reinitialized).
The default is No.
Notes:
1. This System tag (_Simulated) is read only and cannot be written to for runtime protection. The System
tag allows this property to be monitored from the client.
www. ptc.com
13 Siemens S7-200 Driver
2. In Simulation mode, the item's memory map is based on client update rate(s) (Group Update Rate for
OPC clients or Scan Rate for native and DDE interfaces). This means that two clients that reference
the same item with different update rates return different data.
Simulation Mode is for test and simulation purposes only. It should never be used in a production
environment.
Scan Mode: specifies how tags in the device are scanned for updates sent to subscribing clients.
Descriptions of the options are:
l Respect Client-Specified Scan Rate: This mode uses the scan rate requested by the client.
l Request Data No Faster than Scan Rate: This mode specifies the maximum scan rate to be used.
The valid range is 10 to 99999990 milliseconds. The default is 1000 milliseconds.
Note: When the server has an active client and items for the device and the scan rate value is
increased, the changes take effect immediately. When the scan rate value is decreased, the changes
do not take effect until all client applications have been disconnected.
l Request All Data at Scan Rate: This mode forces tags to be scanned at the specified rate for
subscribed clients. The valid range is 10 to 99999990 milliseconds. The default is 1000 milliseconds.
l Do Not Scan, Demand Poll Only: This mode does not periodically poll tags that belong to the
device nor perform a read to get an item's initial value once it becomes active. It is the client's
responsibility to poll for updates, either by writing to the _DemandPoll tag or by issuing explicit device
reads for individual items. For more information, refer to "Device Demand Poll" in server help.
l Respect Tag-Specified Scan Rate: This mode forces static tags to be scanned at the rate specified
in their static configuration tag properties. Dynamic tags are scanned at the client-specified scan
rate.
Initial Updates from Cache: When enabled, this option allows the server to provide the first updates for
newly activated tag references from stored (cached) data. Cache updates can only be provided when the
new item reference shares the same address, scan rate, data type, client access, and scaling properties. A
device read is used for the initial update for the first client reference only. The default is disabled; any time a
client activates a tag reference the server attempts to read the initial value from the device.
www. ptc.com
Siemens S7-200 Driver 14
Communications Timeouts
Connect Timeout: This property (which is used primarily by Ethernet based drivers) controls the amount of
time required to establish a socket connection to a remote device. The device's connection time often takes
longer than normal communications requests to that same device. The valid range is 1 to 30 seconds. The
default is typically 3 seconds, but can vary depending on the driver's specific nature. If this setting is not
supported by the driver, it is disabled.
Note: Due to the nature of UDP connections, the connection timeout setting is not applicable when
communicating via UDP.
Request Timeout: This property specifies an interval used by all drivers to determine how long the driver
waits for a response from the target device to complete. The valid range is 50 to 9,999,999 milliseconds
(167.6667 minutes). The default is usually 1000 milliseconds, but can vary depending on the driver. The
default timeout for most serial drivers is based on a baud rate of 9600 baud or better. When using a driver
at lower baud rates, increase the timeout to compensate for the increased time required to acquire data.
Attempts Before Timeout: This property specifies how many times the driver issues a communications
request before considering the request to have failed and the device to be in error. The valid range is 1 to
10. The default is typically 3, but can vary depending on the driver's specific nature. The number of attempts
configured for an application depends largely on the communications environment. This property applies to
both connection attempts and request attempts.
Timing
Inter-Request Delay: This property specifies how long the driver waits before sending the next request to
the target device. It overrides the normal polling frequency of tags associated with the device, as well as
one-time reads and writes. This delay can be useful when dealing with devices with slow turnaround times
and in cases where network load is a concern. Configuring a delay for a device affects communications with
all other devices on the channel. It is recommended that users separate any device that requires an inter-
request delay to a separate channel if possible. Other communications properties (such as communication
serialization) can extend this delay. The valid range is 0 to 300,000 milliseconds; however, some drivers may
limit the maximum value due to a function of their particular design. The default is 0, which indicates no
delay between requests with the target device.
Note: Not all drivers support Inter-Request Delay. This setting does not appear if it is not available.
www. ptc.com
15 Siemens S7-200 Driver
reached, the driver re-attempts to communicate with the non-responsive device. If the device is responsive,
the device is placed on-scan; otherwise, it restarts its off-scan time period.
Demote on Failure: When enabled, the device is automatically taken off-scan until it is responding again.
Tip: Determine when a device is off-scan by monitoring its demoted state using the _AutoDemoted
system tag.
Timeouts to Demote: Specify how many successive cycles of request timeouts and retries occur before the
device is placed off-scan. The valid range is 1 to 30 successive failures. The default is 3.
Demotion Period: Indicate how long the device should be placed off-scan when the timeouts value is
reached. During this period, no read requests are sent to the device and all data associated with the read
requests are set to bad quality. When this period expires, the driver places the device on-scan and allows for
another attempt at communications. The valid range is 100 to 3600000 milliseconds. The default is 10000
milliseconds.
Discard Requests when Demoted: Select whether or not write requests should be attempted during the
off-scan period. Disable to always send write requests regardless of the demotion period. Enable to discard
writes; the server automatically fails any write request received from a client and does not post a message
to the Event Log.
www. ptc.com
Siemens S7-200 Driver 16
Data Description
Type
Boolean Single bit of a 16-bit value.*
Byte Unsigned 8-bit value.
The driver interprets two consecutive registers as a floating-point value by making the second
register the high word and the first register the low word.
String Null-terminated ASCII string
www. ptc.com
17 Siemens S7-200 Driver
Address Descriptions
Address specifications vary depending on the model in use. Select a link from the list below to obtain specific
address information for the model of interest.
S7-200 Addressing
S7-200 PPM Addressing
S7-200 Addressing
The S7-200 addressing format is the same as the S7-200 PPM addressing format. The model selection in
this case determines whether the driver is using PPI protocol (normal S7-200 Mode) or PPM (S7-200 in Point
to Point Modem) mode. In both cases, the addressing is the same.
The default data types for dynamically defined tags are shown in bold.
I00000.bb-I65535.bb Byte
I00000.bb-I65534.bb Boolean, Word, Short
I00000.bb-I65532.bb DWord, Long
Discrete Outputs Q00000-Q65535 Byte Read/Write
Q00000-Q65534 Word, Short
Q00000-Q65532 DWord, Long, Float
Q00000.bb-Q65535.bb Byte
Q00000.bb-Q65534.bb Boolean, Word, Short
Q00000.bb-Q65532.bb DWord, Long
Internal Memory M00000-M65535 Byte, Read/Write
M00000-M65534 Word, Short
M00000-M65532 DWord, Long, Float
M00000.bb-M65535.bb Byte
M00000.bb-M65534.bb Boolean, Word, Short
M00000.bb-M65532.bb DWord, Long
Special Memory SM00000-SM65535 Byte Read/Write
SM00000-SM65534 Word, Short
SM00000-SM65532 DWord, Long, Float
www. ptc.com
Siemens S7-200 Driver 18
*For Timer and Counter status bits, dot bit notation is not used. The status bit for timer 7 would be T7
declared as Boolean.
**For Analog Inputs and Outputs, the address must be even (AI0, AI2, AI4...). Analog Outputs (AQ) are Write
Only: there is no method for reading the value of Analog Outputs from the device. Write-only data types of
this driver return the last value written when read if an initial write to device has completed. If an initial write
has not completed, the driver returns a value of 0 when read. This only applies while a client is connected to
the server.
The actual number of addresses of each type depends on the Siemens S7-200 device in use. Each type does
not necessarily support an address of 0 to 65535. For address ranges, refer to the device's documentation.
Dynamic addresses with bit numbers in the range of 0-7 default to Byte; 8-15 default to Word; 16-31 defaults
to DWord. V Memory addresses with a bit number larger than 31 defaults to String. The following diagram
illustrates how the driver maps bits within the controller.
www. ptc.com
19 Siemens S7-200 Driver
Note: V30.10@bool, V30.2@byte, and V30.26@DWord all reference the same bit in the controller.
Arrays
Certain memory types (I, Q, M, SM, V, AI, and AQ) support an array operation. Boolean arrays are not
allowed at this time. To specify an array address, append [rows][cols] to the end of an address. If only [cols] is
specified, [rows] defaults to 1. With the array type, it is possible to read and write a block of 200 bytes at one
time.
The maximum array size for Word and Short types is 100, and for DWord, Long and Float types is 50. The
array size is determined by the multiplication of rows and cols.
Note: The maximum array size also depends on the maximum block size of the device being used.
Examples
1. To read and write an array of 10 Variable Memory Float values starting with V10, declare an address as
follows: V10 [1][10]. Choose Float for the data type.
Note: This array reads and writes values to registers V10, V14, V18, V22 ... V46.
2. To read and write to bit 23 of Internal Memory Long M20, declare an address as follows: M20.23. Choose
Long for the data type.
Strings
The driver allows for variable length strings to be stored in Variable Memory locations. The bit number
specifies the string length (1-211) in characters. String data that is sent to the device, but is smaller in length
than the string character count (bit number), is null terminated. String data that meets or exceeds the
character length is truncated to the character count and sent to the device without a null terminator.
To read and write a string starting at V5 for a length of 10 characters, declare an address as follows: V5.10.
Choose string for the data type.
Notes:
2. Not all devices support up to 211 character requests in a single transaction. To determine the
maximum number of characters that can be requested in a transaction, consult the device's
documentation. This value is the largest string the driver can Read/Write to and from the device.
www. ptc.com
Siemens S7-200 Driver 20
Caution: When modifying Word, Short, DWord, Long and Float types remember that each address starts
at a byte offset within the device. Therefore, Words V0 and V1 overlap at byte 1. Writing to V0 modifies the
value held in V1. Similarly, DWord, Long, and Float types can also overlap. It is recommended that these
memory types be used so that overlapping does not occur. As an example, when using DWords, use V0, V4,
V8, and so on to prevent overlapping bytes.
The default data types for dynamically defined tags are shown in bold.
I00000.bb-I65535.bb Byte
I00000.bb-I65534.bb Boolean, Word, Short
I00000.bb-I65532.bb DWord, Long
Discrete Outputs Q00000-Q65535 Byte Read/Write
Q00000-Q65534 Word, Short
Q00000-Q65532 DWord, Long, Float
Q00000.bb-Q65535.bb Byte
Q00000.bb-Q65534.bb Boolean, Word, Short
Q00000.bb-Q65532.bb DWord, Long
Internal Memory M00000-M65535 Byte Read/Write
M00000-M65534 Word, Short
M00000-M65532 DWord, Long, Float
M00000.bb-M65535.bb Byte
M00000.bb-M65534.bb Boolean, Word, Short
M00000.bb-M65532.bb DWord, Long
Special Memory SM00000-SM65535 Byte Read/Write
SM00000-SM65534 Word, Short
SM00000-SM65532 DWord, Long, Float
www. ptc.com
21 Siemens S7-200 Driver
*For Timer and Counter status bits, dot bit notation is not used. The status bit for timer 7 would be "T7"
declared as Boolean.
**For Analog Inputs and Outputs the address must be even (AI0, AI2, AI4...). Analog Outputs (AQ) are Write
Only: there is no method for reading the value of Analog Outputs from the device. Write Only types in this
driver returns the last value written when read if an initial write to device has completed. If an initial write
has not completed, the driver returns a value of 0 when read. This only applies while a client is connected to
the server.
The actual number of addresses of each type depends on the Siemens S7-200 device in use. Each type does
not necessarily support an address of 0 to 65535. For address ranges, refer to the device documentation.
Dynamic addresses with bit numbers in the range of 0-7 defaults to Byte; 8-15 defaults to Word; 16-31
defaults to DWord. V Memory addresses with a bit number larger than 31 defaults to String. The following
diagram illustrates how the driver maps bits within the controller.
www. ptc.com
Siemens S7-200 Driver 22
Note: V30.10@bool, V30.2@byte, and V30.26@DWord all reference the same bit in the controller.
Arrays
In addition to the address formats listed above, certain memory types (I, Q, M, SM, V, AI, AQ) support an
array operation. Boolean arrays are not allowed at this time. To specify an array address, append [rows][cols]
to the end of an address. If only [cols] is specified, [rows] defaults to 1. With the array type, it is possible to
read and write a block of 200 bytes at one time.
The maximum array size for Word and Short types is 100, and for DWord, Long and Float types is 50. The
array size is determined by the multiplication of rows and cols.
Note: The maximum array size also depends on the maximum block size of the device being used.
Examples
1. To read and write an array of 10 Variable Memory Float values starting with V10, declare an address as
follows:
V10 [1][10]. Choose Float for the data type. This array reads and writes values to registers V10, V14, V18,
V22 ... V46.
2. To read and write to bit 23 of Internal Memory Long M20, declare an address as follows: M20.23. Choose
Long for the data type.
Strings
The driver allows for variable length strings to be stored in Variable Memory locations. The bit number
specifies the string length (1-211) in characters. String data that is sent to the device, but is smaller in length
than the string character count (bit number) is null terminated. String data that meets or exceeds the
character length is truncated to the character count and sent to the device without a null terminator.
To read and write a string starting at V5 for a length of 10 characters, declare an address as follows: V5.10.
Choose string for the data type.
Notes:
2. Not all devices support up to 211 character requests in a single transaction. To determine the
maximum number of characters that can be requested in a transaction, refer to the device
documentation. This value is the largest string the driver can Read/Write to and from the device.
www. ptc.com
23 Siemens S7-200 Driver
When modifying Word, Short, DWord, Long and Float types remember that each address starts at a byte
offset within the device. Therefore, Words V0 and V1 overlap at byte 1. Writing to V0 modifies the value held
in V1. Similarly, DWord, Long, and Float types can also overlap. It is recommended that these memory types
be used so that overlapping does not occur. For example, when using DWords, use V0, V4, V8 ... and so on, to
prevent overlapping bytes.
www. ptc.com
Siemens S7-200 Driver 24
Possible Cause:
An attempt has been made to reference a block of memory that contains at least one non-existent location
in the specified device.
Possible Solution:
Verify that the tags assigned to addresses are within the specified range on the device and eliminate any
that reference invalid locations.
www. ptc.com
25 Siemens S7-200 Driver
Index
Address Descriptions 17
Analog Inputs 18, 21
Analog Outputs 18, 21
Arrays 19, 22
Attempts Before Timeout 14
Block may have addresses out of range. | Block start address = '<address>', Block size = <count>
(bytes). 24
Boolean 16
Byte 16
Channel Assignment 12
Channel Properties 4
Communication Protocols 4
Communications Timeouts 13-14
Connect Timeout 14
Counter Current Values 18, 21
Counter Status Bits 18, 21
Data Collection 12
Data Types Description 16
Demote on Failure 15
Demotion Period 15
Device Properties 11
Device Properties — Auto-Demotion 14
Discard Requests when Demoted 15
Discrete Inputs 17, 20
Discrete Outputs 17, 20
www. ptc.com
Siemens S7-200 Driver 26
Float 16
Flow Control 4
Framing 24
Hardware 24
High Speed Counters 18, 21
I/O 24
ID 12
ID Format 12
Identification 11
Initial Updates from Cache 13
Inter-Request Delay 14
Internal Memory 17, 20
Long 16
Master ID 11
www. ptc.com
27 Siemens S7-200 Driver
Model 12
Network 4
OPC Client 3
Overrun 24
Overview 3
Parity 24
Point-to-Point (PPI) 4
Point-to-Point Modem (PPM) 4
PPI programming cable 3
Redundancy 15
Request All Data at Scan Rate 13
Request Data No Faster than Scan Rate 13
Request Timeout 14
Respect Client-Specified Scan Rate 13
Respect Tag-Specified Scan Rate 13
RS232 4
RS485 4
RX buffer overrun 24
S7-200 Addressing 17
S7-200 PPM Addressing 20
Scan Mode 13
Setup 4
Short 16
www. ptc.com
Siemens S7-200 Driver 28
Timeouts to Demote 15
Timer Current Values 18, 21
Timer Status Bits 18, 21
TX buffer 24
Unsigned 16
Word 16
www. ptc.com