1.

Switch Fuse Unit ( 4 pieces )

Technical Specifications

Specification Specification Name Bid Requirement (Allowed Values)

RATI NGS Rated operational Voltage 415


(in Volt)

Rated frequency (in Hz) 50

Number of Pole 3 Pole and Neutral

Current rating (in Ampere) 63

Rated Insulation voltge (in 440


Volt)

Rated impulse withstand 3, 4, 6, 8, 12


voltage (in KV)

Rated short circuit breking 3


capacity, Minimum (in KA,
r.m.s.)
GENERI C Whether product ISI Marked 2 Or higher
(Select 2 for ISI Marked
product, Select 1 for Non
ISI Marked product

Switch Fue Unit contains Enclosure with door, Fuse units- Rewirable, Termina ls ,
Contactors, Operating handle, Pad locking
Utilisation category AC-22 A, AC-23 A

Warranty (in Years) 1

CONSTR UC TIO N Material of enclosure CRCA Sheet, 2 mm thick

Degree of protection IP54, IP55, IP20

Mechanical Endurance, 10000


Minimum (in No.of cycles)

Fixing accessories for Yes


mounting of enclolsures

FUSE UNIT Type of fuse Fuse Unit-Cylindrica l . DIN fuse-link

Additional Specification Parameters - Switch Fuse Unit ( 4 pieces )

1 / 11
Specification Parameter
TECHNICAL
Name

Conformity to the specification:


As per IS/IEC:60947-3: Pad Lock & Door interlock
Switch fuse unit contains:
* Bidders offering must also comply with the additiona l specification paramet ers mentioned above.

2.Switch Fuse Unit ( 7 pieces )

Technical Specifications

Specification Specification Name Requirement (Allowed Values)

RATI NGS Rated operational Voltage 415


(in Volt)

Rated frequency (in Hz) 50

Number of Pole 3 Pole and Neutral

Current rating (in Ampere) 100

Rated Insulation voltge (in 440


Volt)

Rated impulse withstand 3


voltage (in KV)

Rated short circuit breking 3


capacity, Minimum (in KA,
r.m.s.)

GENERI C Whether product ISI Marked 2 Or higher


(Select 2 for ISI Marked
product, Select 1 for Non
ISI Marked product

2 / 11
Specification Specification Name Requirement (Allowed Values)

Switch Fue Unit contains Contactors, Enclosure with door, Fuse units - Rewirable,
Operating handle, Termina ls
Utilisation category AC-23 A

Warranty (in Years) 1

CONSTR UC TIO N Material of enclosure CRCA Sheet, 2 mm thick

Degree of protection IP54

Mechanical Endurance, 10000


Minimum (in No.of cycles)

Fixing accessories for Yes


mounting of enclolsures

FUSE UNIT Type of fuse Fuse Unit-Cylindrica l . DIN fuse-link

Additional Specification Parameters - Switch Fuse Unit ( 7 pieces )


Specification Parameter
Requirement (Allowed Values)
Name

Conformity to the specification:


As per IS/IEC:60947-3: Pad Lock & Door interlock:
Switch fuse unit contains:
* offering must also comply with the additiona l specification parameters mentioned above.

3.Switch Fuse Unit ( 6 pieces)

3 / 11
Technical Specifications

Specification Specification Name Requirement (Allowed Values)

RATI NGS Rated operational Voltage 415


(in Volt)

Rated frequency (in Hz) 50

Number of Pole 3 Pole and Neutral

Current rating (in Ampere) 200

Rated Insulation voltge (in 440


Volt)

Rated impulse withstand 3, 4, 6, 8, 12


voltage (in KV)

Rated short circuit breking 3


capacity, Minimum (in KA,
r.m.s.)

GENERI C Whether product ISI Marked 2 Or higher


(Select 2 for ISI Marked
product, Select 1 for Non
ISI Marked product

Switch Fue Unit contains Enclosure with door, Fuse units- Rewirable, Termina ls ,
Contactors, Operating handle, Fuse units with fuse,
Handle/Shaft: Telescopic shaft for depth adjustm ent,
Pad locking, Auxiliary contact: 1C/O, Auxiliary
Contact: 1NO+1NC, Mounting: DIN RAIL Bolted, Phase
Barrier, Termina l shroud, Provided with external and
one internal earthing termination,, Separate neutral
link with provision of 16 sq.mm lug termination with
bolts, Phase separating barrier, Corner shields for
protection, Hinge type front door, Top and bottom
having removable gland plates of 3 mm thick, Wall
mounting structure with bolts and nuts, Gasket
Neoprene Rubber

Utilisation category AC-22 A, AC-23 A

Warranty (in Years) 2

CONSTR UC TIO N Material of enclosure CRCA Sheet, 2 mm thick

Degree of protection IP54, IP55, IP20

Mechanical Endurance, 10000


Minimum (in No.of cycles)

Fixing accessories for Yes


mounting of enclolsures

FUSE UNIT Type of fuse HRC Fuse Link

4 / 11
Additional Specification Parameters - Switch Fuse Unit ( 6 pieces )
Specification Parameter
Requirement (Allowed Values)
Name

Conformity to the specification:


As per IS/IEC:60947-3: Pad Lock & Door interlock:
Switch fuse unit contains:
* offering must also comply with the additiona l specification parameters mentioned above.

4.Switch Fuse Unit ( 3 pieces )

Technical Specifications

Specification Specification Name Requirement (Allowed Values)

Additional Specification Parameters - Switch Fuse Unit ( 3 pieces )


Specification Parameter
Requirement (Allowed Values)
Name

Conformity to the specification:


As per IS/IEC:60947-3: Pad Lock & Door interlock:
Switch fuse unit contains:
* offering must also comply with the additiona l specification paramet ers mentioned above.

5.Switch Fuse Unit ( 2 pieces )

Technical Specifications

Specification Specification Name Requirement (Allowed Values)

RATI NGS Rated operational Voltage 415


(in Volt)

Rated frequency (in Hz) 50

Number of Pole 3 Pole and Neutral

Current rating (in Ampere) 400

Rated Insulation voltge (in 690


Volt)

Rated impulse withstand 6


voltage (in KV)

Rated short circuit breking 80


capacity, Minimum (in KA,
r.m.s.)
5 / 11
GENERI C Whether product ISI Marked 2 Or higher
(Select 2 for ISI Marked
product, Select 1 for Non
ISI Marked product

Switch Fue Unit contains Enclosure with door, Termina ls , Contactors, Operat ing
handle, Fuse units with fuse, Handle/S ha ft: Telesc o pi c
shaft for depth adjustment, Pad locking

Utilisation category AC-23 A

Warranty (in Years) 1

CONSTR UC TIO N Material of enclosure CRCA Sheet, 2 mm thick

6 / 11
Specification Specification Name Requirement (Allowed Values)
Degree of protection IP54

Mechanical Endurance, 10000


Minimum (in No.of cycles)

Fixing accessories for No


mounting of enclolsures

FUSE UNIT Type of fuse Fuse Unit-Cylindrica l . DIN fuse-link

Additional Specification Parameters - Switch Fuse Unit ( 2 pieces )


Specification Parameter
Requirement (Allowed Values)
Name

Conformity to the specification:


As per IS/IEC:60947-3: Pad Lock & Door interlock
Switch fuse unit contains:
* offering must also comply with the additiona l specification parameters mentioned above.