SUMMARY OF TEST

1) ALL Aggregates Gradation


Fine
Coarse Aggregates Blending
Aggregates Combine Specification as
SIEVE SIZE Grading per IS 383 table
(mm) (Crushed 20mm 10mm (Crushed sand)
20mm 10mm no.10
sand)
34% 19% 47% 100%
40.0 100.00 100.00 100.00 34.00 19.00 47.00 100.00 100
20.0 86.18 100.00 100.00 29.30 19.00 47.00 95.30 95 -100
10.0 0.88 97.20 100.00 0.30 18.47 47.00 65.77 -
4.75 0.64 6.95 99.60 0.22 1.32 46.81 48.35 30-50
2.36 0.00 0.95 61.20 0.00 0.18 28.76 28.94 -
1.180 0.00 0.00 35.60 0.00 0.00 16.73 16.73 -
0.600 0.00 0.00 24.60 0.00 0.00 11.56 11.56 10.-35
0.300 0.00 0.00 19.60 0.00 0.00 9.21 9.21 -
0.150 0.00 0.00 4.80 0.00 0.00 2.26 2.26 0-6
FM 7.12 5.95 3.55
2) The Tests Results of Coarse Aggregate (20mm & 10mm) - Pavanputra Crusher, Panchgaon

SI No. Description of the test Test Results Value Specified Limits Remarks

20 mm 0.79%
1 Water Absorption 5.00% IS 383 2016
10 mm 1.00%
20 mm 2.949 2.1-3.2 IS 383 2016
2 Specific Gravity
10 mm 2.936 2.1-3.2 IS 383 2016
3) The Tests Results of Fine Aggregate (Crushed sand) - Pavanputra Crusher, Panchgaon

SI No. Description of the test Test Results Value Specified Limits Remarks

1 Silt Content (75 Micron Passing) 9.00% 15% IS 383 2016


2 Water Absorption 3.31% - -
3 Specific Gravity 2.723 - -
4 Zone I - -
4) Physical Tests Results of Cement - Birla A1 OPC 53 Cement Confirming to IS:269-2015
Specified Limits
SI No. Description of the test Test Results Value (As per IS 269 Test Method
:2015)
1 Normal Consistency 27.00% - IS 4031 P-4

2 Initial Setting Time 95 Min. 30 Minutes IS 4031 P-5

3 Final Setting Time 205 Max. 600 Minutes IS 4031 P-5

4 Specific Gravity 3.168 - IS 4031 P-11

Compressive Strength 3 Days 29.94 Min. 27 Mpa


5 of Cement Motar 7 Days 39.69 Min. 37 Mpa IS 4031 P-6
Cubes 28 Days 59.68 Min. 53 Mpa

6 Fineness by Blain's Air 297.15 Min 225 m2/Kg IS 4031 P-2

5) The Tests Results of Chemical Admixture - Auramix 400

SI No. Description of the test Test Results Value Specified Limits Remarks

1 Specific Gravity 1.080 0.02±MTC IS Code-9103:1999


2 of 6
PROPORTION OF VOLUME OF COARSE AGGREGATE AND FINE AGGREGATE CONTENT

ADJUSTMENT as per Table no. 5 of IS10262:2019


CONDITION
Volume of Coarse Aggregate(%) Volume of Fine Aggregate(%) Zone I

volume for 0.32 W/c ratio 53.0 47.0

(0.5-0.32)0.01 say 0.64 or 64% volume of coarse


Note - = (0.6+0.036) = 0.636
0.05 aggregates

To avoid segregation of concrete during using pump or chute reducing 17% of Coarse aggregates.

Therefore % of coarse aggregates 64x0.83=53.12 say 53%

Calculation of Recommended mix no.1

A-03 TARGET STRENGTH FOR MIX PROPORTIONING

Characteristic Strength of Concrete = 50 N/mm2

Current Margin as per IS Code (1.65x5) = 8.25 N/mm2

Therefore, Target strength = 58.25 N/mm2

A-04 SELECTION OF WATER CEMENT RATIO

= 0.50
Maximum Water cement Ratio (As per IS456:2000)

Based on experience,Adopt water/cement ratio as = 0.32

0.32< 0.5 Hence O.K.

A-05 SELECTION OF WATER CONTENT - For 20mm Nominal size aggregate water content is -186kg/cum

for 150mm slump water content taken as 186+(12/100)x186 208.32 = Say 208 Kg/m3
By using chemical admixture and observed trial water content reduced by 30.77% at 0.7% dosage

Therefore water content taken


as (100-30.77)x208/100 = 144.00 Kgs/Cum

A-06 CALCULATION OF CEMENTITIOUS CONTENT

Adopted Water cement ratio = 0.32

Cementitious content = 144/0.32 = 450 Kgs/Cum

Minimum cement content (As per Project Requirement) = 450 Kgs/Cum

450 > 450 Hence O.K.

Therefore Cement Content = 450 Kgs/Cum

And Water Content = 144.0 Kgs/Cum

3 of 6
A-07 MIX CALCULATIONS

The mix calculations per unit volume of concrete shall be as follows:

Air content in concrete as per IS 10262: 2019 table no. 3 for 20mm aggregates- 1.0%

a) Volume of Concrete (1- 0.01) = 0.990 cum

b) Volume of Cement = Mass of Cement


x (1/1000)
Specific Gravity of Cement

= (450/3.168/1000)

= 0.1420 Cum

c) Volume of water Mass of water


x (1/1000)
Specific Gravity of water

= (144/1/1000)

= 0.144 cum

d) Volume of Chemical Admixture

percent 0.70% = 3.15 Kgs

by mass of cementitious material)


Mass of Chemical Admixture ######
x (1/1000)
Specific Gravity of admixture

= 0.0029 cum

e) Volume of all in aggregate

agg = [a - (b+c+d) ]

= 0.7011 cum

f) Mass of 20mm aggregate

= e x volume of Coarse aggregate x specific gravity of Coarse aggregate x 1000

= (0.7011x0.34x2.949x1000)

= 703 kgs

g) Mass of 10mm aggregate


= e x volume of Coarse aggregate x specific gravity of Coarse aggregate x 1000

= (0.7011x0.19x2.936x1000)

= 391 kgs

h) Mass of Fine aggregate (Crushed sand)


= e x volume of Fine aggregate x specific gravity of Fine aggregate x 1000

= (0.7011x2.723x0.47x1000)

= 897 kgs
4 of 6
A-08 Following quantities found after calculation with W/c correction .
Grade of concrete M50 Date of casting start 07-08-2021

Trials Mixes

materials Trial no.1 Trial no.2 Trial no.3 Trial no.4 Trial no.5

SSD Wt. SSD Wt. SSD Wt. SSD Wt. SSD Wt.

Cement 450 450 328 -

Crushed Sand 897 854 311

Aggregate20mm 703 740 733 -

Aggregate10mm 391 389 414 -

Water 144 149 176 -

Admixture 3.15 3.15 4.40 -

Total Density 2588 2583 2491 -

Observation Cohesive mix Cohesive mix Cohesive mix -

Slump (mm)
Initial Collapse Collapse 180 -

30min. 190 Collapse 130.00 -

60min. 160 170 100.00 -

90min. 145 155 70.00 -

Remark workable Workable Workable -

**W/C 0.32 0.33 0.44 -

Casting Dates 07-08-2021 10-08-2021 06-05-2021 -

7 days 14-08-2021 17-08-2021 13-05-2021 -


Testing
dates
28 days 04-09-2021 07-09-2021 03-06-2021 -

Average Compressive Strength of 3 Cube (N/mm2)


7 days 48.99 46.58 22.72 -

28 days 61.09 58.95 33.13 -

** Water Cement Ratio 5 of 6


A-09 PROPOSED MIX PROPORTIONS WITH WATER CORRECTION FOR SITE
In case of dry condition of aggregate, the excess amount of water required will be add of ssd materials

Ratio by wt of cement
SSD Weight Water Wt. of DRY(Corrected)
Ingredients
in Kg/cum absorption water Weight in Kg/cum
SSD Dry

Cement 450 - - 450 1.00 1.00

Crushed Sand 897 3.31% 29 869 1.99 1.93

Coarse aggre.(20mm) 703 0.79% 6 697 1.56 1.55

Coarse aggre. (10mm) 391 1.00% 4 387 0.87 0.86

Water 144 - - 182 0.32 0.40

Admixture 3.15 - - 3.15 0.01 0.007

Density 2588 2588

Note: - Aggregates should be used in saturated surface dry condition. If otherwise, when computing the requirement of
mixing water, allowance shall be made for the free (surface) moisture contributed by the fine and coarse aggregates. On the
other hand, if the aggregates are dry, the amount of mixing water should be increased by an amount equal to the moisture
likely to be absorbed by the aggregates. necessary adjustments are also required to be made in mass of aggregates. The
surface water and percent water absorption of aggregates shall be determined to IS: 2386.

A -10 Notes :-

1 This mix design based on 7 & 28 Days compressive strength of concrete cube test result, it is suggested to take plant mix trials & check Workability
of mix & required retention time.

2 This mix design only valid for sources of Coarse & fine Aggregates provided by customer with given cement and admixture brand.

3 This mix design is based on saturated surface dry condition of coarse and fine aggregates, water correction should be apply for site

surface moisture correction of fine and coarse aggregates to avoid extra water mixing & low quantity of material adding in mix.

4 Cement shoud be use in fresh condition as possible.

5 Workability of concrete mix should be adjust during temperature variation due to climate condition by adding or decreasing dosage

of admixture no extra water adding during mixing and at site, only some admixture adding during lossing of slump.

6 After received the report customer must be check or verify the mix by plant batch and take slump, making cube and check 7 ,28 days

strength if any type inconvenient found then please communicate to lab .

A-11 References - IS 269:2015 ,IS456 :2000,IS 10262: 2019,IS SP 23,IS383:2016,IS 2386(Part 1-5),IS 1199:2018

Checked by For Becquerel Industries Pvt. Ltd.

Mr. Sushant Mallick Mr Jeevan G. Ghime


Quality Head Authorized Signitory

6 of 6