6000 Series

Power Operator
Installation and Instruction Manual
ASSA ABLOY 80-9360-1002-020 (08-13)

6020 1 3
(up to 110° 7
opening)

4
5 6
2
6030
(110° to 180°
opening)

5 8

Item No. Description


1 Motor (6000M) 5-3/8 (137)
2 Cover (6000COV) Min Ceiling
3 Control Inverter (6000IN)
4 Power Supply 24VDC (6000SUP)
5 Adjusting Tube and Shoe (6620-12)
6 Main Arm and Rod (6020-1W)
7 Closer Assembly (7500LAP)
8 Main Arm and Rod (6030-1W)

Tools required:
• Allen wrench set (inch) • Center punch
• Small flat blade screwdriver • Wire stripper
• Screwdriver (Phillips size 2) • #7 drill 1/4-20 tap (metal frame install)
• Tape ruler ! Ø3/8 drill (door sex bolt install)
• Power drill
Use screw pack and hardware provided to mount operator.
ETL certified; conforms to ANSI/UL standard
325 for automatic closing doors and UL10C
WARNING: To reduce the risk of injury to person, Positive Pressure Fire Test for Door Assemblies.
use this operator only with Pedestrian Swing doors. Certified to ANSI/BHMA A156.19 for Low Energy
For Indoor Use Only. Door Operators.
Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
General Information

Operation:

Your Low Energy Operator can be configured in three variations to meet the standards:
1. Push plates, Wave-to-open switches, etc. are available to activate the operator.
2. Push & Go can be enabled. In this mode, your door is pushed (or pulled) slowly 15° manually, and then
automatically opens to full open position.
3. Door can be used as a manual door. The door will work and act like a standard door closer, with or
without power, when pushed or pulled open manually. If Push & Go is enabled and door is opened
quickly, door will function as a manual door (energy save feature). Push plates are still active.
If desired, overhead presence devices can be provided for an extra level of protection. Consult local authority having
jurisdiction. These are not required by current ANSI/BHMA A156.19 standards.

Opening:

When an opening signal is received by the control unit, the door opens to the fully open position. The open position is
held by the motor and is adjustable from 0 to 30 seconds. If the door is obstructed while opening, the door will stop;
the operator will sense obstruction (obstruction time is adjustable from 0 to 5 seconds) and the door will close.

Note: Door must be visible by person operating activation switch(es). Auxiliary door stop (by others) required.

Closing:

When the hold open time has elapsed, the door closer will close the door automatically. The door will slow to low
speed at latch before it reaches the fully closed position. The door is kept closed by spring force of the closer. If the
door is obstructed while closing, the door will stop against the obstruction; the operator will sense obstruction and re-
open to fully open position after obstruction time has been reached. Once the hold open time has elapsed a second
time, the door closer will close the door automatically. If the door is obstructed during this second closing cycle, the
door will stop and rest against the obstruction using only the force of the closer spring. To reset, allow door to fully
close and re-activate push plates to test operation.

Extended Hold Open:

An optional feature to be used if door is desired to be held open for more than 30 seconds.

Set switch on end cap on the latch side of the operator to hold open. Door will immediately begin to open to the fully
open position. Once door is fully open, brake on end of motor energizes holding door in open position. To release
from hold open, if door is set up for executive operation (see page 15 for wiring instructions), door can be closed with
activation device. A pull on the door will also allow the unit to be taken out of hold open. Once door has closed, the
door will reopen to fully open position unless activation device is pressed or 3-position is changed from Hold Open
position.

Note: Door must be visible by person operating activation switch(es). Auxiliary door stop (by others) required.

! WARNING: Make sure that (120V, 60Hz) input power is turned off at facility’s main
circuit breaker before proceeding with installation.

Note: Flags included in this instruction sheet show a Pull side


installation instead of a Push side installation. Use video
segments for reference only.

For assistance, contact Norton Technical Product Support


at 800-438-1951 Ext 4706. ASSA ABLOY
3000 Highway 74 East • Monroe, NC 28112
Tel: 800-438-1951 Ext 4706 • Fax: 800-338-0965
www.nor tondoorcontrols.com

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. 80-9360-1002-020 (08-13)
ASSA ABLOY

Door Prep

Hollow Metal Door Frame Reinforcing Frame

Frame Reinforcing Door


Material 1/8"
Recommended Min. Required (3)
12 Ga. 12 Ga. 18 Ga.
.1046 .1046 .0478
(2.66) (2.66) (1.21) Templating is based on 1/8" gap between door and frame.
14 Ga. 10 Ga. 12 Ga.
.0747 .1343 .1046
(1.90) (3.41) (2.66) Notes:
16 Ga. 10 Ga. 12 Ga.
• All dimensions are given in inches.
.0598 .1343 .1046 • Thickness recommended for reinforcements in hollow metal doors
(1.52) (3.41) (2.66)
and frames is charted at the left of this page.
18 Ga. 8 Ga. 10 Ga. • Do not scale drawing.
.0478 .1644 .1343
(1.21) (4.18) (3.41) • This template information based upon use of 5" maximum width butt
hinges.
Fasteners for Frame: • Maximum frame reveal is 6-7/8" for both 6020 and 6030 units.
• 1/4-20 Machine screws for hollow • Before beginning the installation, verify that the door frame is properly
metal and aluminum. reinforced and is well anchored in the wall.
• No. 14x2-3/4 “ (70mm) long sheet • Unreinforced hollow metal frames and aluminum frames should be
metal screws for wood. prepared and fitted with 1/4-20 blind rivet nuts, furnished by others.
• Concealed electrical conduit and concealed switch or sensor wires
should be pulled to the frame before proceeding.

Technical Data
Input power: 120VAC, 60Hz Notes: Permanent wiring is to be employed as
Power consumption: .9 amps required by local codes.
Circuit breaker: Activation devices: push plates, access
3 amps
control, mats, touchless wall switches, etc.
Power supply: 24 V DC, max. 2.2 Amp.
Door width: 28 - 48" (71-122 cm) Maximum wire size is:
Door weight: 100-250 lb. (45-113 kg) 12AWG at terminals LINE and NEUTRAL
Door opening angle: up to 110° with reveal up to 3” (7.6 cm) max (120VAC; 60Hz) on Power Input Terminal
Hold open time: 0-30 seconds (A.D.A. 5 seconds min.) mounted on inside of end cap.
Indefinite for optional Extended Hold Open 14AWG at all other terminals.
Rate of operation shall not exceed 300 cycles of opening and closing per hour.

Standards
ETL Certified; conforms to ANSI/UL standard 325 for Americans with Disabilities Act (A.D.A.)
automatic closing doors and UL10C Positive Pressure Fire These door operators can be installed and adjusted to
Test for Door Assemblies . conform with A.D.A. regulations.

ANSI A156.19: ANSI A117.1:


These products are designed to conform to this specification These door controls permit door assemblies to
“for power assist and low energy power operated doors.” conform to the requirements of this specification “for
These products are designed to exceed all the requirements buildings and facilities - providing accessibility and
for the “Low Energy Power Operated Door.” usability for physically handicapper people.”

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 3 80-9360-1002-020 (08-13)
ASSA ABLOY

IMPORTANT INSTALLATION INSTRUCTIONS


1) READ AND FOLLOW ALL INSTALLATION 3) Remove, or make inoperative, all locks (unless
INSTRUCTIONS. mechanically and/or electrically interlocked to the
2) Install only on a properly operating and balanced door. A power unit) that are connected to the door before
door that is operating improperly could cause severe installing the operator.
injury. Have qualified service personnel make repairs to 4) Do not connect the door operator to the source
any hardware before installing the operator. power until instructed to do so.

1a Unpack Operator
A. Remove from box and unwrap operator. C. Carefully remove cardboard insert.
B. Remove (6) screws holding cover (save to D. Cut (2) large cable ties and separate back
be reused later) and remove cover. plate and closer sub-assembly.

Cable Tie

1b Initial Frame Holes


Left hand door illustrated. See page 24
for removable
A. Using template, locate and prepare holes in the frame. template.

B. Drill #7 and tap 1/4-20 Machine Screws or Self Drilling Screws (2 places).

21-5/16” 21-5/16”
1-7/8” 7/8”

Frame Rabbet Frame Rabbet


5/16” 5/16”

6020 6030
Edge of Frame
(up to 110° (110° to 180°
Edge of Frame
or C of Hinge opening) or C opening)
L L of Hinge

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 4 80-9360-1002-020 (08-13)
ASSA ABLOY

1c Initial Wall Prep


Blocking (supplied by others) is required for proper support Frame
of operator. Thickness is dependent upon Frame Return. Return
Material must comply with local codes.
A. For wood framing, screw blocking into wall studs. 4-7/8”
B. Lag anchoring required for masonry walls.
Left hand door
illustrated.

19-1/2” min 16-5/8” min


4-3/4” max 2-7/8” max

See page 24
for removable
template.
Edge of Frame
Edge of Frame
or C 6020 or C
L of Hinge
L of Hinge 6030

2a Back Plate Mounting


A. Install (2) 1/4-20 x 1” screws
into holes drilled in Step 1B.
Leave 1/8” gap between
bottom of screw head and
i frame.
B. i) Install Back Plate assembly
i ii over screws in Step 2A and
ii) slide Back Plate toward
ii
Latch edge of door.
C. Secure (2) screws.

2b For Concealed Wiring Only


A. Mark conduit holes using back plate as C. Drill (2) Ø7/8” holes.
template. D. Install conduit in frame, if desired.
B. Remove back plate. E. Reinstall back plate and secure (2) screws.
Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 5 80-9360-1002-020 (08-13)
ASSA ABLOY

3 Remaining Back Plate Screws

A. Drill #7 and tap 1/4-20 Machine


Screws or Self Drilling Screws (7
places).
B. Install (7) 1/4-20 x 1” screws into
Concealed holes drilled in Step 3A. Leave
Wiring Holes 1/4” gap between bottom of
“Closer” screw head of screws marked
Screws “Closer” and frame.
See page 24 C. Support between back plate and
for removable wall is required.
template.

4 Assembly Closer Sub-Assembly

i
i
ii From Closer
ii From Back
Sub-Assembly
Plate Assembly

A. i) Install Closer Sub-Assembly over screws in Step 3 with closer spring tube under
power supply and ii) slide Closer Sub-Assembly toward Hinge edge of door.
NOTE: Valves on door closer should be facing away from chain.
B. Secure screws for Closer Sub-Assembly from Step 3.
C. Secure top of Sub-Assembly to Blocking (for masonry, use anchors and spacers).
D. Connect wiring harnesses from Closer Sub-Assembly to Back Plate Assembly.
Connectors are keyed and only connect in one direction. Connectors will lock.

5 Attach Wiring Harness to Chain Guard

Using Cable Tie supplied in pack


with installation instructions, secure
wiring harness to loop on chain
guard just above the pinion.
Wiring Not To
Note: Wiring to be routed so it does Interfere with Wiring Harness
Route Along
not interfere with pulley, is out of Pulley Side of Chain
Cable Tie
door opening, and must route Guard
beside chain guard, not over at
motor area, for cover to fit properly.
Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 6 80-9360-1002-020 (08-13)
ASSA ABLOY

6 Prep Door for Shoe

DIM “A”

6020 13-1/8”

6030 10-3/8” Frame Rabbet 1-7/16”


1-11/16”
DIM “A”
A. Using template, locate and
prepare holes in door.
B. Drill 3/8” thru (2 places) for Edge of Frame
sex bolts. or C
L of Hinge See page 24
for removable
template.

7 Mount Adjusting Tube and Shoe Assembly on Door

A. Install sex bolts thru holes in


back side of door (2 places)
prepared in Step 6.
B. Orient shoe with short side of
shoe toward hinge as shown in
illustration. Install (2) 1/4-20 x Sex Bolts
5/8” screws thru shoe and into
sex bolts installed in Step 7A.

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 7 80-9360-1002-020 (08-13)
ASSA ABLOY

8 Assemble Arm to Pinion

A. i)Slide Adjusting Rod into Tube of Arm Slide and Main Arm
Tube Assembly. ii) Place square of Main Arm
onto pinion with pinion flat and arm marking as Adjusting
shown below. Rod
Arm Marking
ii
i
Pinion Flat

Arm Slide Tube

9 Secure Arm to Pinion

A. Attach arm with


provided screw.
B. Tighten arm screw with
7/16” wrench.

10 Secure Adjusting Rod and Arm Slide Tube


A. Rotate Main Arm away
from hinge until Adjusting
Rod and Arm Slide Tube
are perpendicular (at 90 90°
degrees) with the door.
B. Secure with forearm
screw.
Arm Slide Tube Main Arm

Adjusting Rod
Forearm Screw

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 8 80-9360-1002-020 (08-13)
ASSA ABLOY

11 Closer Spring Force Adjustment


Slowly increase closer power
until door closes consistently.
Stronger
+
NOTE: A closer set to the ADA
required 5 lbs opening force
may not be strong enough to
close the door due to latching
hardware, air pressure, or
frame issues.
-
Weaker

12 Mechanical Closer Adjustments


Closer Must function mechanically as a
standard door closer before applying any
"P" "B"
electrical power. Backcheck Backcheck
Position
Closing Speed Controls Stronger
• Valve "S" Controls Sweep Range from full
open to 5°.
• Valve "L" Controls Latch Range from 5° to
1/8"
Hex
Key 1/8"
Hex
+
Key
closed.

Opening Cycle
• Valve "B" controls the strength of
90°
-
Weaker
75°

cushioning in Backcheck Range. 75°


NEVER close this valve completely – it is not to
provide a positive stop.
• Valve "P" adjusts the angle that back-
check is felt in the open cycle.

"L"
Latch
"S" !
w
Slo er Sweep Do not remove valves
w from closer. Hydraulic
1/8"
Hex Slo er oil will escape.
Key 1/8"
Hex
Faster Key
Faster



!
Never Close
5° backcheck valve
Note: Valve location
S/D is not adjustable. completely

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 9 80-9360-1002-020 (08-13)
ASSA ABLOY

13 Incoming Power Connection

Incoming Power
120VAC
Insert
Low voltage /
Signal 24VDC Power
(Dry) Power Inputs

Insert
Contacts Outputs Line Neutral

Screw
Control Wiring Wire Driver
Surface Ground Screw & Push
Mounted (Green) Down
Conduit
Shown
Concealed
Conduit
Shown 3 4
Low voltage /
Incoming Power
Control Wiring
2 1
A. Pull wire thru Incoming Power conduit. 2) While pushing screw driver toward
B. Strip insulation back 3/8” on Hot and backplate, 3) insert stripped end of wire into
Common Incoming Power wires. terminal. Once wire inserted, 4) release screw
C. Using small flat blade screw driver, 1) insert driver. Tug on wire to confirm it is secured.
blade into small square below wire terminal. D. Attach ground wire to green ground screw.

14 Controller Interface

A. To power unit, flip switch on end cap furthest from the hinge Joystick
from “OFF” to “ON” position.
B. To scroll thru menu items, push up or down on joystick.
C. To change setting of a menu item, when cursor is on that
item, push joystick right to increase or left to decrease value.
D. To permanently accept changes to settings, scroll down to LCD
“Save Values” and press in on the joystick. NOTE: If power is Screen
turned off to the unit before “Save Values” has been accepted See Page 13 for Controller
to “Saved”, any changes made to that point will be lost. Adjustment Options.

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 10 80-9360-1002-020 (08-13)
ASSA ABLOY

15 Set Home and Open Positions

A. With door closed and 3-position switch on end A) B)

Home
of back plate in the “OFF” position, use joystick
to scroll down menu on LCD screen to “Home”.
B. Push in on joystick to activate menu feature.
Display changes to “Set Close Limit”.
C. Push in on joystick again, while door is still C)
closed, to set the Home or closed position.
Display changes to “Set Open Limit”.
D. Open door to desired open position and push
in on joystick again. Display changes to
“Closing to Home”. D)
E. Allow door to fully close again. Display E)
changes to “Home”.
F. Scroll to Save Values and push in on joystick to
permanently save open and closed positions.

16 Connect Accessories and Make Necessary Controller Adjustments

See Page 13 for Controller Adjustments


See Pages 14 - 20 for Accessory Wiring Instructions
See Page 21 for Troubleshooting Guide

17 Install Cover and Label


A. If using Surface Mount power input ONLY,
remove appropriate shaded area from cover,
see illustration below. Repaint cut edges as
necessary to prevent corrosion.
B. Place cover over unit and secure with (6) 6-32
screws taken out previously.
C. Attach label to cover as shown at right.
½ ½
Cover surface Clearance for
facing ceiling Strain Relief
7/8 ½ ½
Right Hand Left Hand
1-5/8 Door Door
2-7/8

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Page 9
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 11 80-9360-1002-000 (08-13)
ASSA ABLOY

General Electrical Information


Circuit Powered A. Power inputs at Power Input Connection and
Breaker Output Power Output Contacts must be made with
Contacts copper wire only.
B. Maximum wire size:
12 AWG at Power Input connection
14 AWG at all other terminals.
C. Power input at terminals LINE and NEUTRAL
Power must be 120VAC at 60 Hz (+10%, -15%).
On / Off D. Maximum current draw from auxiliary devices
Switch is 1.3 amps.
E. All wiring and connections use standard
wiring practice conforming with local wiring
codes.
Power F. Labeled fire or smoke barrier door
Input and Auxiliary assemblies require the 120VAC 60Hz
Basic Aux Dry power input be supplied through normally
Connection Contacts closed alarm contacts of the alarm
system / alarm panel.

IMPORTANT SAFETY INSTRUCTIONS - WARNING: To reduce the risk of severe injury or death

1) READ AND FOLLOW ALL INSTRUCTIONS. Failure to adjust the operator properly may
2) Never let children operate or play with door cause severe injury or death.
controls. Keep the remote control (where provided) 5) KEEP DOOR PROPERLY OPERATING. See
away from children. Door Manufacturer’s Owner’s Manual. An
3) Personnel should keep away from a moving door in improperly operating door could cause severe
motion. injury or death. Have a trained door systems
4) Test the door’s safety features at least once a technician make repairs.
month. After adjusting either the force or the limit 6) SAVE THESE INSTRUCTIONS.
of travel, retest the door operator’s safety features.

Controller Error Codes

Error Code Description


Short Circuit A short was sensed on the motor outputs
Power module reached 200°F or greater (too much load in too hot ambient
Temperature Trip condition)
Over Voltage Line Voltage has reached 145VAC or greater
Under Voltage Line Voltage has dropped below 80VAC
Aux 1 Stuck Activation device connected to Aux 1 is sending constant signal
Aux 2 Stuck Activation device connected to Aux 2 is sending constant signal
Aux 3 Stuck Activation device connected to Aux 3 is sending constant signal
No communication between top and bottom controller boards. Boards not
Comm Error functioning properly
Presense Detect Device connected to Presence Detect and was activated
Drive Disabled 3-position switch on end cap closest to latch is in "OFF" position

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 12 80-9360-1002-020 (08-13)
ASSA ABLOY

Controller Interface Description

Screen Display Adjustments Default Description


Mount: Push or Pull Pull Side of opening operator is mounted on
Turn on or off Push N Go feature.If On, a slight push or pull
Push: OFF or PushNGo Off of the door starts it automatically opening.
Obstruction Delay: the amount of time the operator will push
against an obstruction before closing if during an opening
0 - 5 sec in 1 sec cycle or reopening and trying to close again if during a
Obst Delay: increments 3s closing cycle.
0 - 30 sec in 1 sec
Hold Open: increments 6s Amount of time door will stay in full open position.
Open Speed: 0 - 100% in 1% increments 100 How fast the door opens to full open position.
How fast the motor returns to the home position. As Latch
and Sweep on the closer are adjusted, adjustments may be
needed for Close Speed to assure closer is not trying to
Close Speed: 0 - 100% in 1% increments 60 backdrive the motor.
Speed up or slow down door during last few degrees of
Slow Speed: 0 - 100% in 1% increments 55 opening.
Increase or decrease hold open force (when in "ON" position
only, not "H/O") to compensate for spring force, wind
Hold Speed: 0 - 100% in 1% increments 55 conditions, etc
Time before operator begins to open door. This is to allow
0 - 10 sec in 1 sec accessories time to function and not hinder the opening of
Start Delay: increments
OFF, 5 - 30 in 5 sec 0s the door.
Vestibule: increments Off Amount of delay for opening 2nd vestibule door
OFF, 3 - 45 in 3 sec
Latch Rtrct: increments Off Amount of time power is supplied to a latch retraction device.
Alarm Delay: OFF, 30 sec, 60 sec Off Used only for alarm accessories.
A2 input can be used for Alarm Delay or Input for door
mounted presence detector: Presence Off - door will not
Standard, Presence Off, reactivate; Presence On - door will reopen if presence
A2 Presence On Standard detected during closing cycle.
Cycles: not adjustable - Number of electrical cycles on the operator.
Number of full days electricity have been supplied to the
Days: not adjustable - operator.
Time it took for previous opening cycle to go from Home to
Open Time not adjustable - fully open position.
Time it took for previous closing cycle to go from fully open
Close Time not adjustable - position to Home.
Error code seen by controller. See below for Troubleshooting
Errors not adjustable - codes.
Used to set the Home position and the Fully Open positions
Home see Setting Open Position - of the operator.
Used to permanently add adjustments to controller's
Save Values Save Values or Saved - memory.

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 13 80-9360-1002-020 (08-13)
ASSA ABLOY
Factory Pre-Wiring of Connections

120VAC
Signal 24VDC Power
(Dry) Power Inputs
Contacts Outputs Line Neutral

NO
Com
NC
NO
Com
NC
+24
GND
Aux1
GND
Pres Det
GND
Aux2
GND
Door Toggle
GND
Aux1
Aux3
GND
Aux2
No Conn
Blow Open

Basic Wiring Diagrams Using Factory Pre-Wired Connection


Wall Switch, Card
Standard Function with Reader, Key Switch, etc.
(Normally Open
Switches Momentary dry contacts)
Ÿ Doors are normally
closed.

Contacts

Signal
(Dry)
Line Neutral

Ÿ Activating either switch


120VAC

Inputs
Power

Outputs
+

will open both doors.

24VDC
Power
Outputs
-

-
24VDC
Power

Door will close after hold

Line Neutral
+

120VAC
Inputs
Power
open time delay has
Contacts
Signal

-
(Dry)

expired.
Wall Switch, Card
Reader, Key Switch, etc.
(Normally Open
Momentary dry contacts)

Fail Secure Electric Strike 24VDC


Electric Strike
24VDC Wiring (Fail Secure)
Ÿ Doors are normally closed and + -
Line Neutral
120VAC

Inputs
Power

latched.
-
+

Ÿ Activating switch will unlock


Outputs
-
24VDC
Power

electric strike and door will


+
Contacts

automatically open. Door will


Signal
(Dry)

close after hold open time delay


Wall Switch, Card
has expired. Reader, Key Switch, etc.
Ÿ The door will remain locked (Normally Open
during power failure. Momentary dry contacts)

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 14 80-9360-1002-020 (08-13)
ASSA ABLOY
Fail Safe Electric Strike or Electromagnetic Lock 24VDC Wiring
Change Factory Pre-Wiring from Illustration A to Illustration B (more NO to NC)

A) B)

NO
Com
NC
NO
Com
NC
+24
GND

NO
Com
NC
NO
Com
NC
+24
GND
Fail Safe Electric Strike 24VDC
Wiring
24VDC
Ÿ Doors are normally closed and Electric Strike
latched. (Fail Secure) +
Ÿ Activating switch will unlock
Line Neutral
+ - -
120VAC

Inputs
Power

electric strike or mag lock and 24VDC


+

Electromagnetic
door will automatically open. Door
Outputs
-

Lock (Fail Safe)


24VDC
Power

will close after hold open time


+
Contacts
Signal
(Dry)

delay has expired.


Ÿ The door will remain unlocked
during power failure. Wall Switch, Card
Reader, Key Switch, etc.
Ÿ Current draw at Power Outputs not (Normally Open
to exceed 1.3 amps. Momentary dry contacts)

24VDC Electric Exit Device Wiring


Factory Pre-Wiring in Illustration is for this functionality.
NO
Com
NC
NO
Com
NC
+24
GND

24VDC Electric Exit Device


Wiring 24VDC Electric Exit Device

Ÿ Doors are normally closed and


Line Neutral

+
120VAC

Inputs
Power

latched. -
+

Ÿ Activating switch will energize exit


Outputs
-
24VDC
Power

device and door will automatically


Contacts
Signal
(Dry)

open. Exit device will stay


energized based on Latch Rtrct
Wall Switch, Card Reader,
setting. Door will close after hold Key Switch, etc.
open time delay has expired. (Normally Open
Ÿ Current draw at Power Outputs not Momentary dry contacts)
to exceed 1.3 amps.

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 15 80-9360-1002-020 (08-13)
ASSA ABLOY

Electric Dogging Exit Device Wiring


Change Factory Pre-Wiring from Illustration A to Illustration B (more NO to NC)

A) B)

NO
Com
NC
NO
Com
NC
+24
GND

NO
Com
NC
NO
Com
NC
+24
GND
Electric Dogging Exit Device Wiring
Ÿ Doors are normally closed and latched.
Ÿ Turning key switch ON will apply power to 24VDC Electric Dogging Exit
ON / OFF Device w/ Touch Bar Monitoring
the exit device. Key Switch (Yale and Corbin Russwin shown)
Ÿ The first depression on the device
+ Touch Bar Monitor Switch
touchpad will electrically dog the device -
Line Neutral
120VAC

for push/pull operation.


Inputs
Power

-
+

Ÿ The door will now open automatically


Outputs
-
24VDC
Power

when the wall switch is depressed.


+
Contacts

The device will relatch during a power


Signal

Ÿ
(Dry)

failure or when the key switch is turned off.


Ÿ The exit device allows egress at all times. Wall Switch, Card
The exit device allows egress during Reader, Key Switch, etc.
(Normally Open
power failures. Momentary dry contacts)
Ÿ Current draw at Power Outputs not to
exceed 1.3 amps.

Hard Wired Executive Function Wiring


Change Factory Pre-Wiring from Illustration A to Illustration B
A) B)
NO
Com
NC
NO
Com
NC
+24
GND
NO
Com
NC
NO
Com
NC
+24
GND

Aux1
GND
Pres Det
GND
Aux2
GND
Door Toggle
GND
Aux1
Aux3
Hard Wire Executive Function GND
Aux2
Ÿ Doors are normally closed. No Conn
Blow Open
Ÿ Activating switch will open door.
Line Neutral

Ÿ The door will remain in


120VAC

Inputs
Power

-
+

indefinite hold open until


Outputs
-
24VDC
Power

Wall Switch, Card


activating switch or is activated
+

Reader, Key Switch, etc.


Contacts
Signal

a second time causing the door


(Dry)

(Normally Open
Momentary dry
to close. contacts)

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 16 80-9360-1002-020 (08-13)
ASSA ABLOY
Electric Latch Retraction Exit Device Wiring
Change Factory Pre-Wiring from Illustration A to Illustration B

A) B)

NO
Com
NC
NO
Com
NC
+24
GND
NO
Com
NC
NO
Com
NC
+24
GND
Electric Latch Retraction Exit Controller - 120 VAC

781N
782N
Device Wiring 781N (Corbin
1/15 Russwin) or
-

Line Neutral
Ÿ Doors are normally closed and latched. 2/16 782N (Yale)
120VAC

Inputs
Power
Latch Retraction Exit Device

-
Ÿ Activating switch will retract exit device 7 8 +
+
Outputs Yale and Corbin
latch bolt and operator will open the door. -
24VDC
Power

+ Russwin shown
Ÿ The door will closer after hold open time
Contacts
Signal
(Dry)

delay has elapsed.


Ÿ Exit device allows egress at all times. Exit
Wall Switch, Card
device allows egress during power failure.
Reader, Key Switch, etc.
Ÿ Contact Tech Support for other devices or (Normally Open
manufacturer’s instructions. Momentary dry contacts)

Electric Latch Retraction Exit Device Wiring for Smoke Ventilation - Blow Open Function
Change Factory Pre-Wiring from Illustration A to Illustration B

A) B)
NO
Com
NC
NO
Com
NC
+24
GND

NO
Com
NC
NO
Com
NC
+24
GND
Aux1
GND
Pres Det
GND
Aux2
GND
Door Toggle
GND
Aux1
Electric Latch Retraction Exit Aux3
GND
Device Wiring - Blow Open Aux2
Ÿ Doors are normally closed and No Conn
Blow Open
latched. Controller - 120 VAC
781N
782N

Ÿ Fire Alarm activation will retract exit 781N (Corbin


device latch bolt and door operator 1/15 Russwin) or
-
Line Neutral

2/16 782N (Yale)


120VAC

will open door.


Inputs
Power

Latch Retraction Exit Device


-

Ÿ Door will remain open until the Fire 7 8 +


+

Yale and Corbin


Alarm System has been reset.
Outputs
-
24VDC
Power

Russwin shown
+

Ÿ Door Operator’s main power input


Contacts
Signal

must be wired into building’s back-up


(Dry)

power system. NOTE: This application


Ÿ Exit device allows egress at all times. must be approved by
Exit device allows egress during Fire Alarm System
local (AHJ) authority
(Dry Contacts Only) C NO
power failure. having jurisdiction.

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 17 80-9360-1002-020 (08-13)
ASSA ABLOY
Radio Frequency Standard Function Wiring (can be ordered pre-wired to this RF wiring)
If installing in the field, change Factory Pre-Wiring from Illustration A to Illustration B

A) B)

NO
Com
NC
NO
Com
NC
+24
GND

NO
Com
NC
NO
Com
NC
+24
GND
Radio Frequency Standard

12-24 V
AC/DC
COM
NO
NC
Function
Ÿ Doors are normally closed.
Ÿ Activating wireless switch or hand
Line Neutral
120VAC

Inputs
Power

held wireless transmitter will open


+

If installing RF
the door.
Outputs
-

in the field,
24VDC
Power

Ÿ The door will closer after hold open


+

attach receiver
Contacts

time delay has elapsed.


Signal

to bracket as
(Dry)

Ÿ Current draw at Power Outputs shown with


Velcro strips
not to exceed 1.3 amps. Optional second - + - +
supplied.
Low Energy
Line Neutral Outputs Contacts
Inputs Power (Dry)
Power 24VDC Signal
Power Operator 120VAC

Radio Frequency Executive Function Wiring


Change Factory Pre-Wiring from Illustration A to Illustration B

A) B)

NO
Com
NC
NO
Com
NC
+24
GND
NO
Com
NC
NO
Com
NC
+24
GND

Aux1
GND
Pres Det
GND
Aux2
GND
Door Toggle
GND
Radio Frequency Executive Aux1
Aux3
Function GND
12-24 V
AC/DC

Aux2
COM

Ÿ Doors are normally closed and


NO
NC

No Conn
Blow Open
latched.
Ÿ Activating wireless switch or hand
Line Neutral

held wireless transmitter will open


120VAC

Inputs
Power

the door.
+

If installing RF
in the field,
Outputs
-

Ÿ The door will remain in indefinite


24VDC
Power

attach receiver
hold open until wireless switch or
Contacts

to bracket as
Signal
(Dry)

hand held transmitter is activated a shown with


second time causing the door to Velcro strips
close. Optional second - + - +
supplied.
Low Energy
Line Neutral Outputs Contacts
Inputs

Current draw at Power Outputs


Power (Dry)

Ÿ Power Operator
Power
120VAC
24VDC Signal

not to exceed 1.3 amps.

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 18 80-9360-1002-020 (08-13)
ASSA ABLOY
585 Presence Detector and Door Mounted Presence Sensors Wiring
If installing in the field, change Factory Pre-Wiring from Illustration A to Illustration B
585 Presence
A) Presence Sensor Detector Mounted
(supplied by others) to / above

NO
Com
NC
NO
Com
NC
+24
GND
Mounted to Front / Frame
Back of Door

585 Presence Detector Wiring:


Ÿ Doors are normally closed.
Ÿ Activating switch will open the door.
Ÿ The door will closer after hold open
time delay has elapsed.
Ÿ If door is closed and 585 Presence B)
Detector senses something in the
opening, door will not open.
Ÿ If door is at open position and 585

NO
Com
NC
NO
Com
NC
+24
GND
Presence Detector senses
something in the opening, door will
not close.
Ÿ If using door mounted presence Aux1
sensors (supplied by others): GND
Ÿ If A2 is set to Presence Off, door Pres Det
will continue to open or close if GND
Aux2
presence is detected in the GND
opening. Door Toggle
Ÿ If A2 is set to Presence On, door GND
Aux1
will continue to open if presence Aux3
is detected. If door is closing and GND
presence is detected, door will Signal
(Dry)
24VDC
Power
120VAC
Power Aux2
Inputs
reopen for hold open time delay. Contacts Outputs Line Neutral No Conn
+ - + - Blow Open

NOTE: Presence Detector and/or


sensors CAN NOT be used to Aux1
GND
active opening cycle of door. Pres Det
GND
Aux2
7 IN + ------BLUE GND
6 IN - ------BROWN
5 NC Door Toggle
585 Presence 4 NO ------GREEN
------WHITE
GND
3 COM
Detector 2 PWR ------BLACK Aux1
1 PWR ------RED Aux3
GND
Aux2
No Conn
Blow Open

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

Front Back Back Front


Door Mounted
1... Presence Sensor

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 19 80-9360-1002-020 (08-13)
ASSA ABLOY
Vestibule Function Wiring

Using Factory Pre-Wiring

INSIDE DOOR

NO
Com
NC
NO
Com
NC
+24
GND
Inside Switch

Aux1
GND
Pres Det
GND
Aux2
Wall Switch, Card GND
Reader, Key Switch, etc. Door Toggle
(Normally Open GND
Momentary dry contacts) Aux1
Aux3
Vestibule Function Wiring GND
Aux2
Ÿ Doors are normally closed and latched.
No Conn
Ÿ Activating outside door switch will open the outside door. Blow Open
After the vestibule time delay has elapsed, a signal will be
sent to the inside door which will open. Activating the inside Wall Switch, Card
door switch will open the inside door. After the vestibule time Reader, Key Switch, etc.
delay has elapsed, a signal will be sent to the outside door (Normally Open
Momentary dry contacts)
which will open. Both doors will close when the hold open
time delay has elapsed.
Ÿ Activating the optional inside door switch located within the Optional Inside
corridor will open the inside door only. This door will re-close Corridor Switch
after the hold open delay has elapsed.
Ÿ Activating the optional outside door switch located within the
corridor will open the outside door only. This door will re-
close after the hold open delay has elapsed.

OUTSIDE
NO
Com
NC
NO
Com
NC
+24
GND

DOOR

Outside Switch Aux1


GND
Pres Det
GND
Aux2
GND
Door Toggle
Wall Switch, Card GND
Reader, Key Switch, etc. Aux1
(Normally Open Aux3
Momentary dry contacts) GND
Aux2
No Conn
Blow Open Optional Outside
Corridor Switch
Wall Switch, Card
Reader, Key Switch, etc.
(Normally Open
Momentary dry contacts)

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 20 80-9360-1002-020 (08-13)
ASSA ABLOY
Troubleshooting Guide
Issue Seen Solution
1) Adjust Latch and/or Sweep valves on closer clockwise or 2) Decrease Closing
Door closing too fast Speed on controller (see page 10)
1) Adjust Latch and/or Sweep valves on closer counterclockwise or 2) Increase
Door closing too slow Closing Speed on controller (see page 10)
1) Repeat Home process (see page 8), 2) Increase Obst Delay, 3) Adjust
Backcheck valve on closer counterclockwise, 4) Decrease spring force on closer
Door does not open to body (door myst still close in event of power failure (see page 7), or 5) Move
desired location Bumper Stop in track slightly toward hinge (see page 7)
1) Repeat Home process (see page 9), 2) Increase Obst Delay, 3) Adjust
Backcheck valve on closer counterclockwise, 4) Decrease spring force on closer
Door does not reach fully body (door must still close in event of power failure (see page 7), or 5) Move
opened position Bumper Stop in track sligh
Door opens and closes
repeatedly Change 3-position switch from H/O to On
Motor is driving in the Change Mount (Push / Pull) on controller, reset Home process (see page 8), and
wrong direction Save Values

When door reaches open


position, door drifts toward
closed position Increase Hold Speed on controller (see page 10) until door stops drifting
When door reaches open
position, door drifts further
open Decrease Hold Speed on controller (see page 10) until door stops drifting
When door reaches open
position, door bounces Decrease Slow Speed on controller (see page 10)
When signal is received, 1) Confirm latch devices are getting proper power, 2) Confirm latch devices are
operator tries to open door receiving power long enough to fully retract - adjust Latch Retraction on controller
before auxiliary (see page 10) as needed, 3) If latch device is not retracting fast enough, increase
components are unlatched / Start Delay on controller (see page 11) to assure latch device has had sufficient
retracted time to fully retract before operator starts opening door.
Values previously set on
controller are changed after Reset necessary values on controller (see page 10) and Save Values. Failure to
power removed from Save Values will result in changes to the controller being lost when power is
operator removed
Error message says "Short
Circuit" Turn off power to unit. Check wiring for short / cut.
Error message says "Over
Voltage" Check incoming power - line voltage has exceeded 145VAC
Error message says "Under
Voltage" Check incoming power - line voltage has dropped below 80VAC
Disconnect Aux 1, 2, or 3 inputs and confirm error message goes away. If so,
Error message says "Aux1, make sure input device is not stuck (sending contant signal). Controller has a 3
Aux 2, or Aux 3 Stuck" minute protection limit
Error message says
"Comm Error" Inverter must be replaced
Error message says
"Presense Detect" Unit has a presense detector attached and device has been activated
Error message says "Drive
Disabled" 3-position switch is in the "Off" position

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 21 80-9360-1002-020 (08-13)
ASSA ABLOY
433MHz Receiver User’s Guide
Antenna Wire
ON ON ON ON
10s

10s

10s

10s
PUL TOG

PUL TOG

PUL TOG

PUL TOG
Blue LED
Red LED
0.5s

0.5s

0.5s

0.5s
1 2 1 2 1 2 1 2 Terminal
In Toggle Setting (1-ON), the 0.5 second 10 second Strip
Hold Time is inactive. Either Pulse Setting Pulse Setting
setting for #2 dip switch will
have the same result.
#1 Description Function Learn
OFF Pulse Relay Press the transmitter once and the relay will be active DIP Switch w/o Delay
momentarily. Button
Learn w/ Delay
ON Toggle Relay Press the transmitter once and the relay output is Delay Button Potentiometer
active indefinitely, press it again and the relay will de- (Time Adjustment)
energize indefinitely. Ÿ Always stop pedestrian traffic through the
doorway when performing tests that may
#2 Description Function result in unexpected reactions by the door.
OFF 0.5s Hold Time Relay will remain active 0.5 sec after loss of activation. Ÿ Ensure compliance with all applicable safety
ON 10s Hold Time Relay will remain active 10 sec after loss of activation. standards upon completion of installation.

R1 Hand-Held Configuration
1. Set dip switches to the receiver to the desired activation cycle (dip switch 1 - Toggle or Pulse and dip switch 2 - 0.5s or 10s
hold.
2. Press either Learn w/ Delay Button or Learn w/o Delay Button on the receiver depending on the activation requirements (if
delay learn is selected, adjust potentiometer to counterclockwise limit, 0 second delay). Red LED on receiver will flash. After
learn cycle is complete, adjust potentiometer to desired delay time (0 - 30 sec).
3. Depress transmitter button repeatedly until Blue LED on the receiver illuminates (indicating reception of signal from
transmitter).
NOTE: Repeat Steps 2 - 3 to program additional transmitters.
4. To test the system, depress transmitter button (Red LED on Transmitter will illuminate) and observe that the Blue LED
illuminates on the receiver. This indicates that the relay has been activated.

R2 Push Plate Configuration


1. Before beginning, it is easiest to have already prepared the installation of the push plate.
2. Connect the wires from the transmitter to the NO and COM contacts of the push plate’s switch.
3. Follow Steps 1 - 4 (Hand-Held Configuration); depress the push plate to activate the transmitter.
4. Attach the transmitter to the inside of the electrical box and complete the installation.

R3 Removing Transmitter Code(s)


Single Transmitter Code:
Ÿ Press both Delay and No Delay Buttons simultaneously until Red LED flashes once (approximately 1 second).
Ÿ Press transmitter button twice within 10 seconds and the transmitter code will be deleted.
All Transmitter Codes:
Ÿ Press and hold both Delay and No Delay Buttons simultaneously until Blue LED illuminates then release (approximately 10
seconds).

R4 Troubleshooting
Problem: The LED on my receiver is just flickering and I’m unable to program and/or it won’t work.
Solution: You have a push plate stuck or faulty transmitter. Disconnect each push plate until the LED goes out. If LED
does not go out, remove each transmitter battery until it does. Replace the appropriate transmitter.
Problem: Receiver intermittently doesn’t receive the transmitter(s) signal.
Solution: You may extend the receiver antenna wire only in multiples of 6-3/4” (171), i.e. 6.75 x 4 = 27” (686) of
extended antenna wire.
Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 22 80-9360-1002-020 (08-13)
ASSA ABLOY

This Page
Left Blank

Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. Page 23 80-9360-1002-020 (08-13)
30 3/8
6020 (762) (10)
(to 110° 1-7/8 27-7/8
(48) (708) 1-1/4
opening) (32)
21-5/16
(541) 5/8
1/2 3/8 4.0 13-1/4
(16) 5-3/8
(10) (102) (337)
(13)
Unit Height
Removable Template

Ÿ
Ÿ
Ÿ
Ÿ

5/16 Door
(8)
3/8 DIA.
13-1/8 1-11/16 1-7/16
Sex Nuts
(333) (43) (37) Frame
(2 Places)
Rabbet

Copyright © 2013 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Norton ® is a registered trademark of Yale Security Inc., an ASSA ABLOY Group company.
this application.

1/4-20 Machine Screws or Frame


No. 14 Wood Screws Stop/Soffit
Do not scale drawing.
Left hand door shown.

(7 Places)
7/8” For Concealed Wired

Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
cL Hinge or Pivot (23) Units Only (2 Places)

30 3/8
All dimensions given in inches (mm).

6030 (762) (10)


27-7/8

Page 24
(110° to 180° (708) 1-1/4
21-5/16 (32)
Maximum frame reveal is 6-7/8” (175 mm) for

opening) 7/8
(541)
(22)
5/8
1/2 3/8 4.0 13-1/4 (16) 5-3/8
(13) (10) (102) (337) Unit Height

5/16 Door
(8)
3/8 DIA.
10-3/8 1-11/16 1-7/16 Frame
Sex Nuts
(264) (43) (37) Rabbet
(2 Places)
1/4-20 Machine Screws or Frame
No. 14 Wood Screws 7/8” For Concealed Wired Stop/Soffit
(7 Places) (23) Units Only (2 Places)
cL Hinge or Pivot
ASSA ABLOY

80-9360-1002-020 (08-13)

You might also like