Phase (VA, VB, VC) Potential Transformer Ratio 1.00–10000.00 PTR 1000
Line Settings
Positive-sequence line impedance magnitude Z1MAG 5.86
Positive-sequence line impedance angle (degrees) 5.00–90.00 Z1ANG 81
Zero-sequence line impedance magnitude Z0MAG 23.42
Zero-sequence line impedance angle (degrees) 5.00–90.00 Z0ANG 81
Line length 0.10–999.00, unitless LL 12
Application Settings
Application 311C APP 311C
Distance Settings
Mho phase distance element zones N, 1–4, 1C–4C E21P 4
Mho ground distance element zones N, 1–4 E21MG N
Quadrilateral ground distance element zones E21XG 4
Instantaneous/Definite-Time Overcurrent Enable Settings
Phase element levels N, 1–3 E50P 3
Residual ground element levels N, 1–4 E50G 3
Negative-sequence element levels N, 1–4 E50Q N
Time-Overcurrent Enable Settings
Phase element Y, N E51P N
Residual ground element Y, N E51G N
Negative-sequence element Y, N E51Q N
Other Enable Settings
Directional control Y, AUTO E32 AUTO
Out-of-Step Y, N EOOS Y
Load encroachment Y, N ELOAD Y
Switch-onto-fault Y, N ESOTF Y
Voltage elements Y, N EVOLT Y
Synchronism check Y, N E25 Y
Frequency elements N, 1–6 E81 N
Fault location Y, N EFLOC Y
Loss-of-potential Y, Y1, N ELOP Y
Communications-assisted trip scheme N, DCB, POTT, DCUB1, DCUB2 ECOMM N
Reclosures N, 1–4 E79 1
Zone 1 extension Y, N EZ1EXT N
CCVT transient detection Y, N ECCVT N
SELogic® control equation Variable Timers N, 1–16 ESV 10
SELogic latch bits N, 1–16 ELAT 10
SELogic display points N, 1–16 EDP N
Demand Metering (THM = Thermal; ROL = Rolling) THM , ROL EDEM THM
Advanced settings Y, N EADVS Y
Mho Phase Distance Elements
Zone 1 (W) OFF, 0.05–64.00 W Z1P 4.98
Zone 2 (W) OFF, 0.05–64.00 W Z2P 21.36
Zone 3 (W) OFF, 0.05–64.00 W Z3P 55.46
Zone 4 (W) OFF, 0.05–64.00 W Z4P 0.75
Mho Phase Distance Fault Detector Settings
Zone 1 phase-to-phase current FD (A) 1–170.00 A 50PP1 1
ÝZone 2 phase-to-phase current FD (A) 1–170.00 A 50PP2 1
ÝZone 3 phase-to-phase current FD (A) 1–170.00 A 50PP3 1
ÝZone 4 phase-to-phase current FD (A) 1–170.00 A 50PP4 1
Mho Ground Distance Elements
Zone 1 (W) OFF, 0.05–64.00 W Z1MG 4.98
Zone 2 (W) OFF, 0.05–64.00 W Z2MG 21.36
Zone 3 (W) OFF, 0.05–64.00 W Z3MG 55.46
SETTING BY : DATED :
PROVINCIAL ELECTRICITY AUTHORITY
SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.
SETTING BY : DATED :
PROVINCIAL ELECTRICITY AUTHORITY
SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.
SETTING BY : DATED :
PROVINCIAL ELECTRICITY AUTHORITY
SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.
SETTING BY : DATED :
PROVINCIAL ELECTRICITY AUTHORITY
SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.
SETTING BY : DATED :
NAME VALUE Remark
SYSTEM DATA
Language English
Sys Fn Links 0
Description 21/21N, 67/67N, 25/79
Plant Reference APRIL
Serial Number
Frequency 50 Hz
CB CONTROL
CB Control by Opto+Local
Close Pulse Time 500 ms
Trip Pulse Time 500 ms
Man Close Delay 10 s
CB Healthy Time 5 s
Check Sync Time 5 s
Reset Lockout by CB Close
Man Close RstDelay 5 s
Single Pole A/R Disable
Three Pole A/R Enable
CB Status Input 52B 3 pole
CB Status Time 5 s
CONFIGURATION
Setting Group Select via Menu
Active Settings Visible
Setting Group 1 Enabled
Setting Group 2 Disabled
Setting Group 3 Disabled
Setting Group 4 Disabled
Distance Enabled
Directional E/F Enabled
Current Diff Disabled
Overcurrent Enabled
Neg Sequence O/C Disabled
Broken Conductor Disabled
Earth Fault Enabled
SEF/REF Prot'n Disabled
Residual O/V NVD Disabled
Thermal Overload Disabled
PowerSwing Block Enabled
Volt Protection Disabled
Freq Protection Disabled
df/dt Protection Disabled
CB Fail Enabled
Supervision Enabled
System Checks Enabled
Auto-Reclose Enabled
Input Labels Visible
CT & VT Ratio Visible
Record Control Visible
Distrurb Recorder Visible
Measure't Setup Visible
Comms Settings Visible
Comission Tests Visible
Setting Values Secondary
Control Inputs Visible
Ctrl I/P Config Visible
Ctrl IP Labels Visible
Direct Access Enabled
Function Key Visible
RP1 Read Only Disabled
NIC Read Only Disabled
LCD Contrast 11
NAME VALUE Remark
CT AND VT RATIOS
Main VT Primary 115 kV
Main VT Sec’y 115 V
C/S VT Primary 115 kV
C/S VT Secondary 115 V
Phase CT Primary 1800 A
Phase CT Sec’y 1 A
SEF CT Primary 1800 A
SEF CT Secondary 1 A
MComp CT Primary 1800 A
MComp CT Sec’y 1 A
C/S Input B-N
Main VT Location Bus
CT Polarity Standard
SEF CT Polarity Standard
M CT Polarity Standard
CS VT Ph Shift 0 deg
CS VT Mag 1
DISTURB RECORDER
Duration 5s
TriggerPosition 25%
TriggerMode Single
AnalogChannel1 VA
AnalogChannel2 VB
AnalogChannel3 VC
AnalogChannel4 V Checksync
AnalogChannel5 IA
AnalogChannel6 IB
AnalogChannel7 IC
AnalogChannel8 IN
DigitalInput1 Any Trip A
Input1Trigger Trigger L/H
DigitalInput2 Any Trip B
Input2Trigger Trigger L/H
DigitalInput3 Any Trip C
Input3Trigger Trigger L/H
DigitalInput4 Z1
Input4Trigger Trigger L/H
DigitalInput5 Z2
Input5Trigger Trigger L/H
DigitalInput6 Z3
Input6Trigger Trigger L/H
DigitalInput7 Z4
Input7Trigger Trigger L/H
DigitalInput8 I>1 trip
Input8Trigger Trigger L/H
DigitalInput9 IN>1 trip
Input9Trigger Trigger L/H
DigitalInput10 VT fail alarm
Input10Trigger Trigger L/H
DigitalInput11 tBF1 trip
Input11Trigger Trigger L/H
DigitalInput12 A/R Enable
Input12Trigger Trigger L/H
DigitalInput13 A/R Close
Input13Trigger Trigger L/H
DigitalInput14 I A/R 3P IN Pro.
Input14Trigger Trigger L/H
DigitalInput15 A/R Lockout
Input15Trigger Trigger L/H
DigitalInput16 CB Aux A
Input16Trigger Trigger L/H
DigitalInput17 CB Healthy
Input17Trigger Trigger L/H
DigitalInput18 Check Sync OK
Input18Trigger Trigger L/H
DigitalInput19 V< Line Dead
Input19Trigger Trigger L/H
DigitalInput20 V< Bus Dead
NAME VALUE Remark
Input20Trigger Trigger L/H
DigitalInput21 SOTF/TOR Trip
Input21Trigger Trigger L/H
DigitalInput22 Power Swing
Input22Trigger Trigger L/H
DigitalInput23 Not used
Input23Trigger Trigger L/H
DigitalInput24 Not used
Input24Trigger Trigger L/H
DigitalInput25 Not used
DigitalInput26 Not used
DigitalInput27 Not used
DigitalInput28 Not used
DigitalInput29 Not used
DigitalInput30 Not used
DigitalInput31 Not used
DigitalInput32 Not used
MEASURE’T SETUP
Local Values Primary
Remote Values Primary
Measurement Ref VA
Measurement Mode 0
Fix Dem Period 15 min
Roll Sub Period 30 min
Distance Unit Kilometres
Fault Location Distance
COMMISSION TESTS
Monitor Bit 1 1060
Monitor Bit 2 1062
Monitor Bit 3 1064
Monitor Bit 4 1066
Monitor Bit 5 1068
Monitor Bit 6 1070
Monitor Bit 7 1072
Monitor Bit 8 1074
CB MONITOR SETUP
Broken I^ 2.000-
I^ Maintenance Alarms Disabled
I^ Lockout Alarms Disabled
No CB Ops Maint Alarms Disabled
No CB Ops Lock Alarms Disabled
CB Time Maint Alarms Disabled
CB Time Lockout Alarms Disabled
Fault Freq Lock Alarms Disabled
Reset Lockout By CB Close
OPTO CONFIG.
Global normal V 110/125 V
Opto Filter Cntl 11111111111
Characteristic Standard 60%-80%
GROUP1
GROUP1 LINE PARAMETERS
Line Length 12.0 km
Line Impedance 5.86 Ohm
Line Angle 80.888 deg
kZN Res Comp 0.99987
kZN Angle 0.00264 deg
Mutual Comp Disable
Phase Sequence Standard ABC
Tripping Mode 3 Pole
Line Charging Y
GROUP1 DISTANCE SETUP
Setting Mode Advanced
Phase Chars. Quad
Zone 1 Ph Status Enable
NAME VALUE Remark
Zone 2 Ph Status Enable
Zone 3 Ph Status Enable
Zone 3 Offset Disable
Zone P Ph Status Disable
Zone 4 Ph Status Disable
Ground Chars. Quad
Zone 1 Gnd Stat. Enable
Zone 3 Gnd Stat. Enable
Zone 2 Gnd Stat. Enable
Zone 3 Gnd Offset Disable
Zone P Gnd Stat. Disable
Zone 4 Gnd Stat. Disable
Digital Filter Standard
CVT Filters Disabled
Load Blinders Disabled
Dist. Polarizing 1
Dir. Status Enabled
AidedDeltaStatus Disabled
Dir. Char Angle 60 deg
GROUP 1 DIST. ELEMENTS
Z1 Ph. Reach 4.98 Ohm
Z1 Ph. Angle 80.89 deg
R1 Ph. Resistive 29 Ohm
Z1 Tilt Top Line 0 deg
Z1 Sensit. Iph>1 250 mA
Z2 Ph. Reach 21.36 Ohm
Z2 Ph. Angle 81 deg
R2 Ph. Resistive 36 Ohm
Z2 Tilt Top Line 0 deg
Z2 Sensit. Iph>2 250 mA
Z3 Ph. Reach 55.46 Ohm Reverse
Z3 Ph. Angle 81 deg
R3 Ph. Resistive 45 Ohm
Z3 Tilt Top Line 0 deg
Z3 Sensit. Iph>3 250 mA
Z4 Ph. Reach 0.75 Ohm
Z4 Ph. Angle 81 deg
R4 Ph. Resistive 45 Ohm
Z4 Tilt Top Line 0 deg
Z4 Sensit. Iph>4 250 mA
Z1 Gnd. Reach 4.98 Ohm
Z1 Gnd. Angle 81 deg
Z1 Dynamic Tilt Disabled
Z1 Tilt Top Line 0 deg
kZN1 Res. Comp. 1.00
kZN1 Res. Angle 0 deg
R1 Gnd Resistive 72 Ohm
Z1 Sensit Ignd>1 150 mA
Z2 Gnd. Reach 21.36 Ohm
Z2 Gnd. Angle 81 deg
Z2 Dynamic Tilt Disabled
Z2 Tilt Top Line 0 deg
kZN2 Res. Comp. 0.99987
kZN2 Res. Angle 0.00264 deg
R2 Gnd Resistive 72 Ohm
Z2 Sensit Ignd>2 150 mA
Z3 Gnd. Reach 55.46 Ohm Reverse
Z3 Gnd. Angle 81 deg
Z3 Dynamic Tilt Disabled
Z3 Tilt Top Line 0 deg
kZN3 Res. Comp. 0.99987
kZN3 Res. Angle 0.00264 deg
R3 Gnd Resistive 72 Ohm
Z3 Sensit Ignd>3 150 mA
Z4 Gnd. Reach 0.75 Ohm
Z4 Gnd. Angle 81 deg
Z4 Dynamic Tilt Disabled
Z4 Tilt Top Line 0 deg
kZN4 Res. Comp. 0.99987
kZN4 Res. Angle 0.00264 deg
NAME VALUE Remark
R4 Gnd Resistive 72 Ohm
Z4 Sensit Ignd>4 150 mA
Mem Volt Dura 16
GROUP 1 SCHEME LOGIC
BasicScheme Mode Standard
Zone1 Tripping Phase And Ground
tZ1 Ph. Delay 0 s
tZ1 Gnd. Delay 0 s
Zone2 Tripping Phase And Ground
tZ2 Ph. Delay 300 s
tZ2 Gnd. Delay 300 s
Zone3 Tripping Phase And Ground
tZ3 Ph. Delay 600 s
tZ3 Gnd. Delay 600 s
ZoneP Tripping Phase And Ground
tZP Ph. Delay 600 s
tZP Gnd. Delay 600 s
Zone4 Tripping Phase And Ground
tZ4 Ph. Delay 600 s
tZ4 Gnd. Delay 600 s
Aid. 1 Selection POR Permissiver overreacch
Aid 1 Distance Phase And Ground
Aid.1 Dist. Dly 0 s
Aid. 2 Selection Disable
SOTF Status Enabled PoleDead
SOTF Delay 110 s
SOTF Tripping 011111 All Zone
TOR Status Enabled
TOR Tripping 000001 Zone 1
TOC Reset Delay 500
TOC Delay 200
Z1 Ext Scheme Disabled
LOL Scheme Disabled
GROUP 1 BACK UP I>
I > 1 Status Enable
I > 1 Function DT
I > 1 Directional Directional FWD
I > 1 Current Set 1800 A
I > 1 TMS 500 ms
I > 1 TReset 0 s
I > 2 Status Disable
I > 3 Status Disable
I > 4 Status Disable
I> Char Angle 30 Plain feeder
I> Blocking 001111 VTS Blk
GROUP 1 AIDED DEF
DEF Status Enabled
DEF Polarizing Zero Sequence
DEF Char. Angle -60 Transmission
DEF VNpol Set 1
DEF FWD Set 2E+06 mA
DEF REV Set 2E+06 mA
Virtual I Pol Enable
GROUP 1 POWER SWING BLK.
PSB Status Blocking
Zone 1 Ph. PSB Blocking
Zone 2 Ph. PSB Blocking
Zone 3 Ph. PSB Blocking
Zone P Ph. PSB Blocking
Zone 4 Ph. PSB Blocking
Zone 1 Gnd. PSB Blocking
Zone 2 Gnd. PSB Blocking
Zone 3 Gnd. PSB Blocking
Zone P Gnd. PSB Blocking
Zone 4 Gnd. PSB Blocking
WI Trip PSB Inhibit Trip
PSB Unblocking Disabled
PSB Reset Delay 200.0 ms
OST Mode OST Disabled
Slow Swing Disabled
NAME VALUE Remark
GROUP 1 CB FAIL & P.DEAD
CB Fail 1 Status Enabled
CB Fail 1 Timer 200.0 ms
CB Fail 2 Status Enabled
CBF Non I Rst I< Only
CBF Ext Reset I< Only
WI Prot Disabled Disabled
ExtTrip Only Ini Disabled
I< Current Set 300.00 mA
ISEF< Current 300.00 mA
V< 30.00 V
GROUP 1 SUPERVISION
VTS Mode Measured + MCB
VTS Status Blocking
VTS Reset Mode Auto
VTS Time Delay 5.000 s
VTS I> Inhibit 1.5 mA
VTS I2> Inhibit 50 mA
Inrush Detection Disabled
WI Inhibit Enabled
I0/I2 Setting 3
CTS Mode Disabled
GROUP 1 SYSTEM CHECKS
Live Line 53 V
Dead Line 20 V
Live Bus 53 V
Dead Bus 20 V
CS UV 53 V
CS OV 73 V
System Checks Enabled
CS Voltage Block V<
CS1 Status Enabled
CS1 Angle 25 deg
CS1 VDiff 13 V
CS1 Slip Ctrl Enabled
CS1 SlipFreq 200
CS2 Status Disabled
GROUP 1 AUTORECLOSE
AR Mode AR 3P
AR Shots 1
3P AR DT Shot 1 1 s
3PAR ReclaimTime 5 s
AR CBHealthyTime 5 s
AR CheckSyncTime 5 s
Z1 AR Initiate AR
Diff AR Initiate AR
Dist Aided AR Initiate AR
Z2T AR Block AR
Z3T AR Block AR
ZPT AR Block AR
Z4T AR Block AR
DEF Aided AR Block AR
Dir Aided AR Block AR
TOR AR Block AR
I>1 AR No Action
GROUP 1 INPUT LABELS
Opto Input 1 Opto Label 01 79 ON
Opto Input 2 Opto Label 02 52b
Opto Input 3 Opto Label 03 52b (Transfer bay)
Opto Input 4 Opto Label 04
Opto Input 5 Opto Label 05
Opto Input 6 Opto Label 06 MANUAL CLOSE
Opto Input 7 Opto Label 07
Opto Input 8 Opto Label 08
Opto Input 9 Opto Label 09
Opto Input 10 Opto Label 10
Opto Input 11 Opto Label 11
Opto Input 12 Opto Label 12
Opto Input 13 Opto Label 13
Opto Input 14 Opto Label 14
NAME VALUE Remark
Opto Input 15 Opto Label 15
Opto Input 16 Opto Label 16
GROUP 1 LED
LED 1 21/21N ZONE 1
LED 2 21/21N ZONE 2,3
LED 3 21/21N ZONE 4
LED 4 Power Swing
LED 5 SOTF/TOR Trip
LED 6 A/R Lockout
LED 7 A/R Close
LED 8 VT Fail
missiver overreacch
Subsation : APRIL Area : NE3 Date : 28-Oct-24 Remark :
Protection : APRIL Line to MAY Panel : APRIL1YB-01
Relay type : P443 APRIL MAY
Function : 21/21N, 67/67N, 25/79 12 km SD 20 km
CTR = 1800 / 1
VTR = 115000 / 115
CTR/VTR = 1.8 15 km SD
LL1 = 12 km Line type SD
LL2 (shortest line) = 15 km Line type SD JUNE
LL2 (longest line) = 20 km Line type SD
Max MVA = 320 MVA
Voltage = 115 kV Section2(shortest)
Pos. Seq. Resistance = 0.042936 Ohm/km 0.927 ohm_sec 0.042936 Ohm/km
Pos. Seq. Reactance = 0.2677 Ohm/km 5.78232 ohm_sec 0.2677 Ohm/km
Zero. Seq. Resistance = 0.17169 Ohm/km 3.7085 ohm_sec 0.17169 Ohm/km
Zero. Seq. Reactance = 1.0707 Ohm/km 23.1271 ohm_sec 1.0707 Ohm/km
Pos. Seq. Imp. = 0.2711 Ohm/km 5.85622 ohm_sec 0.2711 Ohm/km
Zero Seq. Imp. = 1.0844 Ohm/km 23.4226 ohm_sec 1.0844 Ohm/km
Pos. Line Imp. = 5.86 Ohm_sec 81 deg
Zero Line Imp. = 23.42 Ohm_sec 81 deg
Z1 = 85 % of LL1 R1 = 0.7883 X1 = 4.91497 Z1
= 4.98 Ohm_sec R0 = 3.15223 X0 = 19.6581 Z0
= 2.77 Ohm_pri R1 = 0.43795 X1 = 2.73054 Z1
R0 = 1.75124 X0 = 10.9211 Z0
tZ1 = 0 ms
Z2 = 100 % of LL1+ 50 %shortest LL2 I2/I1= 3.23514
= 21.36 Ohm_sec R1 = 1.50705 X1 = 9.39627 Z1
= 11.87 Ohm_pri R0 = 6.02632 X0= 37.5816 Z0
R1 = 0.83725 X1 = 5.22015 Z1
tZ2 = 300 ms R0 = 3.34796 X0 = 20.8787 Z0
Z3 = 100 % of LL1+ 120 %longest LL2 I2/I1= 3.23514
= 55.46 Ohm_sec R1 = 2.78225 X1 = 17.347 Z1
= 30.81 Ohm_pri R0 = 11.1255 X0= 69.3814 Z0
R1 = 1.5457 X1 = 9.6372 Z1
tZ3 = 600 ms R0 = 6.18084 X0 = 38.5452 Z0
Z4 = 15 % of Z1
= 0.75 Ohm_sec R1 = 0.11825 X1 = 0.73725 Z1
= 0.41 Ohm_pri R0 = 0.47283 X0= 2.94871 Z0
R1 = 0.06569 X1 = 0.40958 Z1
tZ4 600 ms R0 = 0.26269 X0 = 1.63817 Z0
K0 = 1.00
K0Ang = 0.00
Zmin = 41 Ohm_pri
= 74 Ohm_sec
Max Rph = 45 Ohm_sec 60% of minimun load imp.
R3ph-R4ph = 44.63 Ohm_sec max Rph
R2ph = 35.71 Ohm_sec 80% of R3ph-R4ph
R1ph = 28.57 Ohm_sec 80% of R2ph
Max RG = 40 Ohm_pri
R3G-R4G = 72 Ohm_sec 40 Ohm_pir All zone
R2G = 72 Ohm_sec 40 Ohm_pir All zone
R1G = 72 Ohm_sec 40 Ohm_pir All zone
Delta R = 13 Ohm_sec 30% of R3ph-R4ph
Delta X = 13 Ohm_sec 30% of R3ph-R4ph
Phase DOC = 1800 A 1
Time delay = 500 ms
Ground DOC = 1800 A 1
Time delay = 500 ms
Tele-Scheme = Basic
Tele Phase DOC = 1800 A 1
Tele-Time delay = 150 ms
Tele Ground DOC = 1800 A 1
Tele-Time delay = 150 ms
Live Volt = 53 80%Un
Dead Volt = 20 30%Un
Diff Volt = 13.3 20%Un
Diff Angle = 25
Diff Frequency = 200 mHz
Under Voltage = 53 80%Un
Over Volage = 73 110%Un
Update History
27-Sep-21 - Add P442, update Reclaim time 15 sec
29-Sep-21 - Set password CAL Sheet
19-Oct-21 - Add Summary page
15-Jan-22 - Fix display LL for Z4 and Auto select line imp.
22-Jan-22 - Add PSB for P442
11-Jun-22 - Fix ABB PSB
28-Aug-22 - Add ABB REL650 Version2
- Fix ABB RED670/Idmin following PEA criteria (CT rated)
- Fix ABB RED670/End Slope1 following Application Manual
- Fix ABB RED670/Slope section2 following Application Manual
- Fix ABB RED670/Slope section3 following Application Manual
- Fix Protecta/67N/Char. Angle from 60 deg. to 120 deg. (3U0 Pol. Ref.)
- Fix ABB REL650 V.1 FDPSPDIS/X1 from Sec. value to Pri. Value.
3-Sep-22 - แก้ไข Load Enchroachment : RLdFw รีเลย์ ABB ทุกรุ่น ไม่ให้เข้าไปใน
ข้อควรระวัง : ใช้ได้เฉพาะสายส่งสั้นเท่านั้น (<77km) หากสายส่งยาว
K0 Calculation
Z1/km = 0.042936+0.2677i
Z0/km = 0.17169+1.0707i
Z0-Z1 = 0.128754+0.803i
3Z1 = 0.128808+0.8031i
K0 = 0.999868091351552+4.60828175951498e-05i
JULY
SD
JUNE
Zone reach to km
= 4.97779 Z1 = 10.200 km
= 19.9092 Z2 = 19.500 km
= 2.76544 Z3 = 36.000 km
= 11.0607 Z4 = 1.530 km
= 9.51636
= 38.0617
= 5.28687
= 21.1454
38.0617
= 17.5687
= 70.2677
= 9.76037
= 39.0376
= 0.74667
= 2.98638
= 0.41482
= 1.6591
ห้เข้าไปใน zone operate เนื่องจากหากเกิดฟอลต์ SLG รีเลย์จะบล็อค
หากสายส่งยาว Heavy Load สามารถทำให้ zone operate ได้
PROVINCIAL ELECTRICITY AUTHORITY
APRIL1YB-01
Agile P443
GROUP 1 \DIST. ELEMENTS
Value Unit
4.978 Ohm
80.89 deg
300 mA
21.357 Ohm
80.888 deg
300 mA
55.460 Ohm
80.89 deg
300 mA
0.747 Ohm
80.888 deg
300 mA
4.978 Ohm
80.89 deg
Disabled
0.000 deg
1.000
0.003 deg
72.00 Ohm
100 mA
21.36 Ohm
80.89 deg
Disabled
0.000 deg
1.000
0.003 deg
72.00 Ohm
100 mA
55.460 Ohm
80.89 deg
Disabled
0.000 deg
1.000
0.003 deg
72.00 Ohm
100 mA
0.747 Ohm
80.89 deg
Disabled
0.000 deg
1.000
0.003 deg
72.000 Ohm
100.00 mA
16.00
GROUP 1 \SCHEME LOGIC
Value Unit
Standard
Phase And Ground
0.000 s
0.000 s
Phase And Ground
300.0 ms
300.0 ms
CIAL ELECTRICITY AUTHORITY
APRIL1YB-01
Agile P443
GROUP 1 \POWER SWING BLK.
Value Unit
Delay Unblock
Delay Unblock
Delay Unblock
Blocking
Delay Unblock
Delay Unblock
Delay Unblock
Delay Unblock
Inhibit Trip
Disabled
200.0 ms
OST Disabled
Disabled
GROUP 1 \CB FAIL & P.DEAD
Value Unit
1.00 A
20.00 mA
38.10 V
GROUP 1 \SUPERVISION
Value Unit
Measured + MCB
Blocking
Auto
5.000 s
1.50 A
50.00 mA
Disabled
Enabled
3.000
Disabled
Disabled
GROUP 1 \SYSTEM CHECKS
Value Unit
53 V
20 V
53 V
20 V
53 V
73 V
Enabled
V<
Enabled
25 deg
13 V
Enabled
200 mHz
Disabled
CIAL ELECTRICITY AUTHORITY
APRIL1YB-01
Agile P443