PROVINCIAL ELECTRICITY AUTHORITY

SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.

PROTECTION AND RELAY DIVISION


115 kV. DISTANCE RELAY (21/21N) SETTING
SUBSTATION: APRIL BREAKER : APRIL1YB-01
FUNCTION : 21/21N, 67/67N, 25/79 MODEL NO.: SEL311L, SEL311C
Description Range Step parmeter setting
Identifier Labels (characters)
Relay Identifier (characters) 17 RELID APRIL
Terminal Identifier 39 TRMID APRIL1YB-01
Current and Potential Transformer Ratios
Phase (IA, IB, IC) Current Transformer Ratio 1–6000 CTR 1800

Phase (VA, VB, VC) Potential Transformer Ratio 1.00–10000.00 PTR 1000

Line Settings
Positive-sequence line impedance magnitude Z1MAG 5.86
Positive-sequence line impedance angle (degrees) 5.00–90.00 Z1ANG 81
Zero-sequence line impedance magnitude Z0MAG 23.42
Zero-sequence line impedance angle (degrees) 5.00–90.00 Z0ANG 81
Line length 0.10–999.00, unitless LL 12
Application Settings
Application 311C APP 311C
Distance Settings
Mho phase distance element zones N, 1–4, 1C–4C E21P 4
Mho ground distance element zones N, 1–4 E21MG N
Quadrilateral ground distance element zones E21XG 4
Instantaneous/Definite-Time Overcurrent Enable Settings
Phase element levels N, 1–3 E50P 3
Residual ground element levels N, 1–4 E50G 3
Negative-sequence element levels N, 1–4 E50Q N
Time-Overcurrent Enable Settings
Phase element Y, N E51P N
Residual ground element Y, N E51G N
Negative-sequence element Y, N E51Q N
Other Enable Settings
Directional control Y, AUTO E32 AUTO
Out-of-Step Y, N EOOS Y
Load encroachment Y, N ELOAD Y
Switch-onto-fault Y, N ESOTF Y
Voltage elements Y, N EVOLT Y
Synchronism check Y, N E25 Y
Frequency elements N, 1–6 E81 N
Fault location Y, N EFLOC Y
Loss-of-potential Y, Y1, N ELOP Y
Communications-assisted trip scheme N, DCB, POTT, DCUB1, DCUB2 ECOMM N
Reclosures N, 1–4 E79 1
Zone 1 extension Y, N EZ1EXT N
CCVT transient detection Y, N ECCVT N
SELogic® control equation Variable Timers N, 1–16 ESV 10
SELogic latch bits N, 1–16 ELAT 10
SELogic display points N, 1–16 EDP N
Demand Metering (THM = Thermal; ROL = Rolling) THM , ROL EDEM THM
Advanced settings Y, N EADVS Y
Mho Phase Distance Elements
Zone 1 (W) OFF, 0.05–64.00 W Z1P 4.98
Zone 2 (W) OFF, 0.05–64.00 W Z2P 21.36
Zone 3 (W) OFF, 0.05–64.00 W Z3P 55.46
Zone 4 (W) OFF, 0.05–64.00 W Z4P 0.75
Mho Phase Distance Fault Detector Settings
Zone 1 phase-to-phase current FD (A) 1–170.00 A 50PP1 1
ÝZone 2 phase-to-phase current FD (A) 1–170.00 A 50PP2 1
ÝZone 3 phase-to-phase current FD (A) 1–170.00 A 50PP3 1
ÝZone 4 phase-to-phase current FD (A) 1–170.00 A 50PP4 1
Mho Ground Distance Elements
Zone 1 (W) OFF, 0.05–64.00 W Z1MG 4.98
Zone 2 (W) OFF, 0.05–64.00 W Z2MG 21.36
Zone 3 (W) OFF, 0.05–64.00 W Z3MG 55.46

SETTING BY : DATED :
PROVINCIAL ELECTRICITY AUTHORITY
SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.

PROTECTION AND RELAY DIVISION


115 kV. DISTANCE RELAY (21/21N) SETTING
SUBSTATION: APRIL BREAKER : APRIL1YB-01
PROVINCE : 21/21N, 67/67N, 25/79 MODEL NO.: SEL311L, SEL311C
Description Range Step parmeter setting
Zone 4 (W) OFF, 0.05–64.00 W Z4MG 0.75
Quadrilateral Ground Distance Elements
Zone 1 reactance (W) OFF, 0.05–64.00 W XG1 4.91
Zone 2 reactance (W) OFF, 0.05–64.00 W XG2 21.09
Zone 3 reactance (W) OFF, 0.05–64.00 W XG3 54.76
Zone 4 reactance (W) OFF, 0.05–64.00 W XG4 0.74
Zone 1 resistance (W) OFF, 0.05–64.00 W RG1 72
Zone 2 resistance (W) OFF, 0.05–64.00 W RG2 72
Zone 3 resistance (W) OFF, 0.05–64.00 W RG3 72
Zone 4 resistance (W) OFF, 0.05–64.00 W RG4 72
ÝQuadrilateral ground polarizing quantity XGPOL I2
ÝNon-homogenous correction angle (degrees) TANG 0
Quadrilateral and Mho Ground Distance Fault Detector Settings
Zone 1 phase current FD (A) 0.5-100 A 50L1 0.3
ÝZone 2 phase current FD (A) 0.5-100 A 50L2 0.3
ÝZone 3 phase current FD (A) 0.5-100 A 50L3 0.3
ÝZone 4 phase current FD (A) 0.5-100 A 50L4 0.3
Zone 1 residual current FD (A) 0.5-100 A 50GZ1 0.3
ÝZone 2 residual current FD (A) 0.5-100 A 50GZ2 0.3
ÝZone 3 residual current FD (A) 0.5-100 A 50GZ3 0.3
ÝZone 4 residual current FD (A) 0.5-100 A 50GZ4 0.3
Zero Sequence Compensation (ZSC) Settings
Zone 1 ZSC factor magnitude k0M1 0.99986809241
Zone 1 ZSC factor angle (degrees) k0A1 0.00264069925
ÝZones 2, 3, and 4 ZSC factor magnitude k0M 0.99986809241
ÝZone 2, 3, and 4 ZSC factor angle (degrees) k0A 0.00264069925
Mho Phase Distance Element Time Delays
Zone 1 time delay (cycles) Z1PD 0
Zone 2 time delay (cycles) Z2PD 15
Zone 3 time delay (cycles) Z3PD 30
Zone 4 time delay (cycles) Z4PD 30
Quadrilateral and Mho Ground Distance Element Time Delays
Zone 1 time delay (cycles) Z1GD 0
Zone 2 time delay (cycles) Z2GD 15
Zone 3 time delay (cycles) Z3GD 30
Zone 4 time delay (cycles) Z4GD 30
Common Phase/Ground Distance Element Time Delay
Zone 1 time delay (cycles) Z1D 0
Zone 2 time delay (cycles) Z2D 15
Zone 3 time delay (cycles) Z3D 30
Zone 4 time delay (cycles) Z4D 30
Phase Inst./Def.-Time Overcurrent Elements
Level 1 (A) 50P1P 1800
Level 2 (A) 50P2P -
Level 3 (A) 50P3P -
Phase Definite-Time Overcurrent Element Time Delays
Level 1 (cycles) 0.00–16000.00 0.25 67P1D 25
Level 2 (cycles) 0.00–16000.00 0.25 67P2D -
Level 3 (cycles) 0.00–16000.00 0.25 67P3D -
Residual Ground Inst./Def.-Time Overcurrent Elements
Level 1 (A) OFF, 0.25–100.00 50G1P 1800
Level 2 (A) OFF, 0.25–100.00 50G2P -
Level 3 (A) OFF, 0.25–100.00 50G3P -
Level 4 (A) OFF, 0.25–100.00 50G4P -
Residual Ground Definite-Time Overcurrent Element Time Delay
Level 1 (cycles) 0.00–16000.00 0.25 67G1D 25
Level 2 (cycles) 0.00–16000.00 0.25 67G2D -
Level 3 (cycles) 0.00–16000.00 0.25 67G3D -
Level 4 (cycles) 0.00–16000.00 0.25 67G4D -
CTS Status
Negative-Sequence Inst./Def.-Time Overcurrent Elements
Level 1 (A) OFF, 0.25–100.00 50Q1P OFF

SETTING BY : DATED :
PROVINCIAL ELECTRICITY AUTHORITY
SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.

PROTECTION AND RELAY DIVISION


115 kV. DISTANCE RELAY (21/21N) SETTING
SUBSTATION: APRIL BREAKER : APRIL1YB-01
PROVINCE : 21/21N, 67/67N, 25/79 MODEL NO.: SEL311L, SEL311C
Description Range Step parmeter setting
Level 2 (A) OFF, 0.25–100.00 50Q2P OFF
Level 3 (A) OFF, 0.25–100.00 50Q3P OFF
Level 4 (A) OFF, 0.25–100.00 50Q4P OFF
Negative-Sequence Definite-Time Overcurrent Element Time Delay
Level 1 (cycles) 0.00–16000.00 0.25 67Q1D 0
Level 2 (cycles) 0.00–16000.00 0.25 67Q2D 0
Level 3 (cycles) 0.00–16000.00 0.25 67Q3D 0
Level 4 (cycles) 0.00–16000.00 0.25 67Q4D 0
Phase Time-Overcurrent Element
Pickup (A) OFF, 0.50–16.00 51PP OFF
Curve U1–U5, C1–C5 51PC -
Time Dial (U1–U5, C1–C5) 0.50–15.00, 0.05–1.00 51PTD -
Electromechanical Reset Y, N 51PRS -
Residual Ground Time-Overcurrent Element
Pickup (A) OFF, 0.50–16.00 51GP OFF
Curve U1–U5, C1–C5 51GC -
Time Dial (U1–U5, C1–C5) 0.50–15.00, 0.05–1.00 51GTD -
Electromechanical Reset Y, N 51GRS -
Negative-Sequence Time-Overcurrent Element
Pickup OFF, 0.50–16.00 51QP OFF
Pickup (A) U1–U5, C1–C5 51QC -
Curve 0.50–15.00, 0.05–1.00 51QTD -
Time Dial (U1–U5, C1–C5) Y, N 51QRS -
Electromechanical Reset
Block Zone 1 (Y, N) Y, N OOSB1 Y
Block Zone 2 (Y, N) Y, N OOSB2 N
Block Zone 3 (Y, N) Y, N OOSB3 N
Block Zone 4 (Y, N) Y, N OOSB4 N
Out-of-Step block time delay (cycles) 0.5–8000.0 OSBD 5
Enable Out-of-Step tripping N, I, O EOOST N
Out-of-Step trip delay (cycles) 0.5–8000 OSTD 0.5
Zone 6 reactance—Top (W) 0 to 96 X1T6 82.14
Zone 5 reactance—Top (W) 0 to 96 X1T5 71.19
Zone 6 resistance—Right (W) 0.05 to 70.00 R1R6 83.19
Zone 5 resistance—Right (W) 0.05 to 70.00 R1R5 72.10
ÝZone 6 reactance—Bottom (W) -96.00 to -0.05 X1B6 -82.14
ÝZone 5 reactance—Bottom (W) -96.00 to -0.05 X1B5 -71.19
ÝZone 6 resistance—Left (W) -70.00 to -0.05 R1L6 -83.19
ÝZone 5 resistance—Left (W) -70.00 to -0.05 R1L5 -72.10
Positive-Sequence current supervision (A) 1–100 50ABCP 1
Negative-Sequence current unblock delay (cycles) 0.5–120.0 UBD 2.5
ÝOut-of-Step angle change unblock rate 1–10 unitless UBOSBF 4
Load-Encroachment Elements
Forward load impedance (W) 0.05–64.00 ZLF 74
Reverse load impedance (W) 0.05–64.00 ZLR 74
Positive forward load angle (degrees) -90.00° to +90.00 PLAF 30
Negative forward load angle (degrees) +90.00° to +270.00 NLAF -30
Positive reverse load angle (degrees) +90.00° to +270.00 PLAR 150
Negative reverse load angle (degrees) NLAR 210
Zone/Level 3 and 4 Directional Control
Zone/Level 3 direction: (Forward, Reverse) F, R DIR3 F
Zone/Level 4 direction: (Forward, Reverse) F, R DIR4 R
Directional Elements
Ground directional element priority: Q, V, or I ORDER QVI
Forward directional Z2 threshold (W) -64.00–64.00 Z2F -
Reverse directional Z2 threshold (W) -64.00–64.00 Z2R -
Forward directional 3I2 pickup (A) 0.25–5.00 50QFP -
Reverse directional 3I2 pickup (A) 0.25–5.00 50QRP -
Positive-sequence current restraint factor, I2/I1 0.02–0.50, unitless a2 -
Zero-sequence current restraint factor, I2/I0 0.10–1.20, unitless k2 -
Forward directional 3I0 pickup (A) 0.25–5.00 50GFP -
Reverse directional 3I0 pickup (A) 0.25–5.00 50GRP -

SETTING BY : DATED :
PROVINCIAL ELECTRICITY AUTHORITY
SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.

PROTECTION AND RELAY DIVISION


115 kV. DISTANCE RELAY (21/21N) SETTING
SUBSTATION: APRIL BREAKER : APRIL1YB-01
PROVINCE : 21/21N, 67/67N, 25/79 MODEL NO.: SEL311L, SEL311C
Description Range Step parmeter setting
Positive-sequence current restraint factor, I0/I1 0.02–0.50, unitless a0 -
Forward directional Z0 threshold (W) -64.00–64.00 Z0F -
Reverse directional Z0 threshold (W) -64.00–64.00 Z0R -
Voltage Elements
Phase undervoltage pickup (V secondary) OFF, 0.0–150.0 27P OFF
Phase overvoltage pickup (V secondary) 59P
Zero-sequence (3V0) overvoltage pickup (V secondary) OFF, 0.0–150.0 59N1P OFF
Zero-sequence (3V0) overvoltage pickup (V secondary) OFF, 0.0–150.0 59N2P OFF
Negative-sequence (V2) overvoltage pickup (V secondary) OFF, 0.0–100.0 59QP OFF
Positive-sequence (V1) overvoltage pickup (V secondary) OFF, 0.0–150.0 59V1P OFF
Channel VS undervoltage pickup (V secondary) OFF, 0.0–150.0 27SP OFF
Channel VS overvoltage pickup (V secondary) OFF, 0.0–150.0 59SP OFF
Phase-to-phase undervoltage pickup (V secondary) OFF, 0.0–260.0 27PP OFF
Phase-to-phase overvoltage pickup (V secondary) OFF, 0.0–260.0 59PP OFF
Synchronism Check Elements
Voltage window—low threshold (V secondary) OFF, 0.0–260.0 25VLO 53
Voltage window—high threshold (V secondary) OFF, 0.0–260.0 25VHI 80
Maximum slip frequency (Hz) 0.005–0.500 25SF 0.2
Maximum angle 1 0.00°–80.00° 25ANG1 25
Maximum angle 2 0.00°–80.00° 25ANG2 25
Synchronizing phase VA, VB, VC, VAB, VBC, VAC SYNCP VB
Breaker close time for angle compensation (cycles) OFF, 1.00–60.00 0.25 TCLOSD 3
Frequency Elements
Phase undervoltage block 27B81P
Level 1 pickup (Hz) OFF, 41.00–65.00 81D1P OFF
Level 1 time delay (cycles) 2.00–16000.00 0.25 81D1D 50
Level 2 pickup (Hz) OFF, 41.00–65.00 81D2P OFF
Level 2 time delay (cycles) 2.00–16000.00 0.25 81D2D 50
Level 3 pickup (Hz) OFF, 41.00–65.00 81D3P OFF
Level 3 time delay (cycles) 2.00–16000.00 0.25 81D3D 50
Level 4 pickup (Hz) OFF, 41.00–65.00 81D4P OFF
Level 4 time delay (cycles) 2.00–16000.00 0.25 81D4D 50
Level 5 pickup (Hz) OFF, 41.00–65.00 81D5P OFF
Level 5 time delay (cycles) 2.00–16000.00 0.25 81D5D 50
Level 6 pickup (Hz) OFF, 41.00–65.00 81D6P OFF
Level 6 time delay (cycles) 2.00–16000.00 0.25 81D6D 50
Reclosing Relay
Open interval 1 time (cycles) 0.00–999999.00 0.25 79OI1 50
Open interval 2 time (cycles) 0.00–999999.00 0.25 79OI2 50
Open interval 3 time (cycles) 0.00–999999.00 0.25 79OI3 50
Open interval 4 time (cycles) 0.00–999999.00 0.25 79OI4 50
Reset time from reclose cycle (cycles) 0.00–999999.00 0.25 79RSD 250
Reset time from lockout (cycles) 0.00–999999.00 0.25 79RSLD 500
Reclose supervision time limit (cycles) OFF, 0.00–999999.00 0.25 79CLSD 500
Switch-Onto-Fault
Close enable time delay (cycle) OFF, 0.00–16000.00 0.25 CLOEND OFF
52A enable time delay (cycle) OFF, 0.00–16000.00 0.25 52AEND 5500
SOTF duration (cycles) 0.50–16000.00 0.25 SOTFD 25
POTT Trip Scheme Settings
Zone (level) 3 reverse block time delay (cycles) 0.00–16000.00 0.25 Z3RBD
Echo block time delay (cycles) OFF, 0.00–16000.00 0.25 EBLKD
Echo time delay pickup (cycles) OFF, 0.00–16000.00 0.25 ETDPU
Echo duration time delay 0.00–16000.00 0.25 EDURD
Weak-infeed enable Y, N EWFC
WIF phase-to-phase undervoltage (V secondary) 0.0–260.0 27PPW
WIF zero-sequence (3V0) overvoltage (V secondary) 0.0–150.0 59NW
Additional DCUB Trip Scheme Settings
Guard present security time delay (cycles) 0.00–16000.00 0.25 GARD1D
DCUB disabling time delay (cycles) 0.25–16000.00 0.25 UBDURD
DCUB duration time delay (cycles) 0.25–16000.00 0.25 UBEND
DCB Trip Scheme Settings
Zone (level) 3 reverse pickup time delay (cycles) 0.00–16000.00 0.25 Z3XPU

SETTING BY : DATED :
PROVINCIAL ELECTRICITY AUTHORITY
SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.

PROTECTION AND RELAY DIVISION


115 kV. DISTANCE RELAY (21/21N) SETTING
SUBSTATION: APRIL BREAKER : APRIL1YB-01
PROVINCE : 21/21N, 67/67N, 25/79 MODEL NO.: SEL311L, SEL311C
Description Range Step parmeter setting
Zone (level) 3 reverse dropout extension (cycles) 0.00–16000.00 0.25 Z3XD
Block trip receive extension (cycles) 0.00–16000.00 0.25 BTXD
Zone 2 distance short delay (cycles) 0.00–16000.00 0.25 21SD
Level 2 overcurrent short delay (cycles) 0.00–16000.00 0.25 67SD
Zone 1 Extension Scheme Settings
Zone 1 extension delay time (0.00–16000.00 cycles) 0.00–16000.00 Z1EXTD
Zone 1 distance multiplier 1.00–4.00 Z1EXTM
Demand Metering Settings
Time constant (minutes) 5, 10, 15, 30, 60 DMTC
Phase pickup (A secondary) OFF, 0.50–16.00 PDEMP
Residual ground pickup (A secondary) OFF, 0.50–16.00 GDEMP
Negative-sequence pickup (A secondary) OFF, 0.50–16.00 QDEMP
Other Settings
Minimum trip duration time (cycles) 4.00–16000.00 0.25 TDURD
Close failure time delay (cycles) 0.00–16000.00 0.25 CFD
Three-pole open time delay (cycles) 0.00–60.00 0.25 3POD
Open pole option 52, 27 OPO
Three-pole open undervoltage (V secondary) 0.0–150.0 27PO
Load detection phase pickup (A) OFF, 0.25–100.00 50LP
SELogic Control Equation Variable Timers
SV1 Pickup Time (cycles) 0.00–999999.00 0.25 SV1PU
SV1 Dropout Time (cycles) 0.00–999999.00 0.25 SV1DO
SV2 Pickup Time (cycles) 0.00–999999.00 0.25 SV2PU
SV2 Dropout Time (cycles) 0.00–999999.00 0.25 SV2DO
SV3 Pickup Time (cycles) 0.00–999999.00 0.25 SV3PU
SV3 Dropout Time (cycles) 0.00–999999.00 0.25 SV3DO
SV4 Pickup Time (cycles) 0.00–999999.00 0.25 SV4PU
SV4 Dropout Time (cycles) 0.00–999999.00 0.25 SV4DO
SV5 Pickup Time (cycles) 0.00–999999.00 0.25 SV5PU
SV5 Dropout Time (cycles) 0.00–999999.00 0.25 SV5DO
SV6 Pickup Time (cycles) 0.00–999999.00 0.25 SV6PU
SV6 Dropout Time (cycles) 0.00–999999.00 0.25 SV6DO
SV7 Pickup Time (cycles) 0.00–16000.00 0.25 SV7PU
SV7 Dropout Time (cycles) 0.00–16000.00 0.25 SV7DO
SV8 Pickup Time (cycles) 0.00–16000.00 0.25 SV8PU
SV8 Dropout Time (cycles) 0.00–16000.00 0.25 SV8DO
SV9 Pickup Time (cycles) 0.00–16000.00 0.25 SV9PU
SV9 Dropout Time (cycles) 0.00–16000.00 0.25 SV9DO
SV10 Pickup Time (cycles) 0.00–16000.00 0.25 SV10PU
SV10 Dropout Time (cycles) 0.00–16000.00 0.25 SV10DO
SV11 Pickup Time (cycles) 0.00–16000.00 0.25 SV11PU
SV11 Dropout Time (cycles) 0.00–16000.00 0.25 SV11DO
SV12 Pickup Time (cycles) 0.00–16000.00 0.25 SV12PU
SV12 Dropout Time (cycles) 0.00–16000.00 0.25 SV12DO
SV13 Pickup Time (cycles) 0.00–16000.00 0.25 SV13PU
SV13 Dropout Time (cycles) 0.00–16000.00 0.25 SV13DO
SV14 Pickup Time (cycles) 0.00–16000.00 0.25 SV14PU
SV14 Dropout Time (cycles) 0.00–16000.00 0.25 SV14DO
SV15 Pickup Time (cycles) 0.00–16000.00 0.25 SV15PU
SV15 Dropout Time (cycles) 0.00–16000.00 0.25 SV15DO
SV16 Pickup Time (cycles) 0.00–16000.00 0.25 SV16PU
SV16 Dropout Time (cycles) 0.00–16000.00 0.25 SV16DO
Trip Logic Equations
Direct trip conditions TR
Communications-assisted trip conditions TRCOMM
Switch-onto-fault trip conditions TRSOTF
Direct transfer trip conditions DTT
Unlatch trip conditions ULTR
Communications-Assisted Trip Scheme Input Equations
Permissive trip 1 (used for ECOMM = POTT, DCUB1, or DCUB2) PT1
Loss-of-guard 1 (used for ECOMM = DCUB1 or DCUB2) LOG1
Loss of guard 2 (used for ECOMM = DCUB2) LOG2
Block trip (used for ECOMM = DCB) BT

SETTING BY : DATED :
NAME VALUE Remark
SYSTEM DATA
Language English
Sys Fn Links 0
Description 21/21N, 67/67N, 25/79
Plant Reference APRIL
Serial Number
Frequency 50 Hz

CB CONTROL
CB Control by Opto+Local
Close Pulse Time 500 ms
Trip Pulse Time 500 ms
Man Close Delay 10 s
CB Healthy Time 5 s
Check Sync Time 5 s
Reset Lockout by CB Close
Man Close RstDelay 5 s
Single Pole A/R Disable
Three Pole A/R Enable
CB Status Input 52B 3 pole
CB Status Time 5 s

DATE AND TIME


Battery Alarm Enabled
Local Time Enable Fixed
Local Time Offset 420 min
DST Enable Disable

CONFIGURATION
Setting Group Select via Menu
Active Settings Visible
Setting Group 1 Enabled
Setting Group 2 Disabled
Setting Group 3 Disabled
Setting Group 4 Disabled
Distance Enabled
Directional E/F Enabled
Current Diff Disabled
Overcurrent Enabled
Neg Sequence O/C Disabled
Broken Conductor Disabled
Earth Fault Enabled
SEF/REF Prot'n Disabled
Residual O/V NVD Disabled
Thermal Overload Disabled
PowerSwing Block Enabled
Volt Protection Disabled
Freq Protection Disabled
df/dt Protection Disabled
CB Fail Enabled
Supervision Enabled
System Checks Enabled
Auto-Reclose Enabled
Input Labels Visible
CT & VT Ratio Visible
Record Control Visible
Distrurb Recorder Visible
Measure't Setup Visible
Comms Settings Visible
Comission Tests Visible
Setting Values Secondary
Control Inputs Visible
Ctrl I/P Config Visible
Ctrl IP Labels Visible
Direct Access Enabled
Function Key Visible
RP1 Read Only Disabled
NIC Read Only Disabled
LCD Contrast 11
NAME VALUE Remark
CT AND VT RATIOS
Main VT Primary 115 kV
Main VT Sec’y 115 V
C/S VT Primary 115 kV
C/S VT Secondary 115 V
Phase CT Primary 1800 A
Phase CT Sec’y 1 A
SEF CT Primary 1800 A
SEF CT Secondary 1 A
MComp CT Primary 1800 A
MComp CT Sec’y 1 A
C/S Input B-N
Main VT Location Bus
CT Polarity Standard
SEF CT Polarity Standard
M CT Polarity Standard
CS VT Ph Shift 0 deg
CS VT Mag 1

DISTURB RECORDER
Duration 5s
TriggerPosition 25%
TriggerMode Single
AnalogChannel1 VA
AnalogChannel2 VB
AnalogChannel3 VC
AnalogChannel4 V Checksync
AnalogChannel5 IA
AnalogChannel6 IB
AnalogChannel7 IC
AnalogChannel8 IN
DigitalInput1 Any Trip A
Input1Trigger Trigger L/H
DigitalInput2 Any Trip B
Input2Trigger Trigger L/H
DigitalInput3 Any Trip C
Input3Trigger Trigger L/H
DigitalInput4 Z1
Input4Trigger Trigger L/H
DigitalInput5 Z2
Input5Trigger Trigger L/H
DigitalInput6 Z3
Input6Trigger Trigger L/H
DigitalInput7 Z4
Input7Trigger Trigger L/H
DigitalInput8 I>1 trip
Input8Trigger Trigger L/H
DigitalInput9 IN>1 trip
Input9Trigger Trigger L/H
DigitalInput10 VT fail alarm
Input10Trigger Trigger L/H
DigitalInput11 tBF1 trip
Input11Trigger Trigger L/H
DigitalInput12 A/R Enable
Input12Trigger Trigger L/H
DigitalInput13 A/R Close
Input13Trigger Trigger L/H
DigitalInput14 I A/R 3P IN Pro.
Input14Trigger Trigger L/H
DigitalInput15 A/R Lockout
Input15Trigger Trigger L/H
DigitalInput16 CB Aux A
Input16Trigger Trigger L/H
DigitalInput17 CB Healthy
Input17Trigger Trigger L/H
DigitalInput18 Check Sync OK
Input18Trigger Trigger L/H
DigitalInput19 V< Line Dead
Input19Trigger Trigger L/H
DigitalInput20 V< Bus Dead
NAME VALUE Remark
Input20Trigger Trigger L/H
DigitalInput21 SOTF/TOR Trip
Input21Trigger Trigger L/H
DigitalInput22 Power Swing
Input22Trigger Trigger L/H
DigitalInput23 Not used
Input23Trigger Trigger L/H
DigitalInput24 Not used
Input24Trigger Trigger L/H
DigitalInput25 Not used
DigitalInput26 Not used
DigitalInput27 Not used
DigitalInput28 Not used
DigitalInput29 Not used
DigitalInput30 Not used
DigitalInput31 Not used
DigitalInput32 Not used

MEASURE’T SETUP
Local Values Primary
Remote Values Primary
Measurement Ref VA
Measurement Mode 0
Fix Dem Period 15 min
Roll Sub Period 30 min
Distance Unit Kilometres
Fault Location Distance

COMMISSION TESTS
Monitor Bit 1 1060
Monitor Bit 2 1062
Monitor Bit 3 1064
Monitor Bit 4 1066
Monitor Bit 5 1068
Monitor Bit 6 1070
Monitor Bit 7 1072
Monitor Bit 8 1074

CB MONITOR SETUP
Broken I^ 2.000-
I^ Maintenance Alarms Disabled
I^ Lockout Alarms Disabled
No CB Ops Maint Alarms Disabled
No CB Ops Lock Alarms Disabled
CB Time Maint Alarms Disabled
CB Time Lockout Alarms Disabled
Fault Freq Lock Alarms Disabled
Reset Lockout By CB Close

OPTO CONFIG.
Global normal V 110/125 V
Opto Filter Cntl 11111111111
Characteristic Standard 60%-80%

GROUP1
GROUP1 LINE PARAMETERS
Line Length 12.0 km
Line Impedance 5.86 Ohm
Line Angle 80.888 deg
kZN Res Comp 0.99987
kZN Angle 0.00264 deg
Mutual Comp Disable
Phase Sequence Standard ABC
Tripping Mode 3 Pole
Line Charging Y
GROUP1 DISTANCE SETUP
Setting Mode Advanced
Phase Chars. Quad
Zone 1 Ph Status Enable
NAME VALUE Remark
Zone 2 Ph Status Enable
Zone 3 Ph Status Enable
Zone 3 Offset Disable
Zone P Ph Status Disable
Zone 4 Ph Status Disable
Ground Chars. Quad
Zone 1 Gnd Stat. Enable
Zone 3 Gnd Stat. Enable
Zone 2 Gnd Stat. Enable
Zone 3 Gnd Offset Disable
Zone P Gnd Stat. Disable
Zone 4 Gnd Stat. Disable
Digital Filter Standard
CVT Filters Disabled
Load Blinders Disabled
Dist. Polarizing 1
Dir. Status Enabled
AidedDeltaStatus Disabled
Dir. Char Angle 60 deg
GROUP 1 DIST. ELEMENTS
Z1 Ph. Reach 4.98 Ohm
Z1 Ph. Angle 80.89 deg
R1 Ph. Resistive 29 Ohm
Z1 Tilt Top Line 0 deg
Z1 Sensit. Iph>1 250 mA
Z2 Ph. Reach 21.36 Ohm
Z2 Ph. Angle 81 deg
R2 Ph. Resistive 36 Ohm
Z2 Tilt Top Line 0 deg
Z2 Sensit. Iph>2 250 mA
Z3 Ph. Reach 55.46 Ohm Reverse
Z3 Ph. Angle 81 deg
R3 Ph. Resistive 45 Ohm
Z3 Tilt Top Line 0 deg
Z3 Sensit. Iph>3 250 mA
Z4 Ph. Reach 0.75 Ohm
Z4 Ph. Angle 81 deg
R4 Ph. Resistive 45 Ohm
Z4 Tilt Top Line 0 deg
Z4 Sensit. Iph>4 250 mA
Z1 Gnd. Reach 4.98 Ohm
Z1 Gnd. Angle 81 deg
Z1 Dynamic Tilt Disabled
Z1 Tilt Top Line 0 deg
kZN1 Res. Comp. 1.00
kZN1 Res. Angle 0 deg
R1 Gnd Resistive 72 Ohm
Z1 Sensit Ignd>1 150 mA
Z2 Gnd. Reach 21.36 Ohm
Z2 Gnd. Angle 81 deg
Z2 Dynamic Tilt Disabled
Z2 Tilt Top Line 0 deg
kZN2 Res. Comp. 0.99987
kZN2 Res. Angle 0.00264 deg
R2 Gnd Resistive 72 Ohm
Z2 Sensit Ignd>2 150 mA
Z3 Gnd. Reach 55.46 Ohm Reverse
Z3 Gnd. Angle 81 deg
Z3 Dynamic Tilt Disabled
Z3 Tilt Top Line 0 deg
kZN3 Res. Comp. 0.99987
kZN3 Res. Angle 0.00264 deg
R3 Gnd Resistive 72 Ohm
Z3 Sensit Ignd>3 150 mA
Z4 Gnd. Reach 0.75 Ohm
Z4 Gnd. Angle 81 deg
Z4 Dynamic Tilt Disabled
Z4 Tilt Top Line 0 deg
kZN4 Res. Comp. 0.99987
kZN4 Res. Angle 0.00264 deg
NAME VALUE Remark
R4 Gnd Resistive 72 Ohm
Z4 Sensit Ignd>4 150 mA
Mem Volt Dura 16
GROUP 1 SCHEME LOGIC
BasicScheme Mode Standard
Zone1 Tripping Phase And Ground
tZ1 Ph. Delay 0 s
tZ1 Gnd. Delay 0 s
Zone2 Tripping Phase And Ground
tZ2 Ph. Delay 300 s
tZ2 Gnd. Delay 300 s
Zone3 Tripping Phase And Ground
tZ3 Ph. Delay 600 s
tZ3 Gnd. Delay 600 s
ZoneP Tripping Phase And Ground
tZP Ph. Delay 600 s
tZP Gnd. Delay 600 s
Zone4 Tripping Phase And Ground
tZ4 Ph. Delay 600 s
tZ4 Gnd. Delay 600 s
Aid. 1 Selection POR Permissiver overreacch
Aid 1 Distance Phase And Ground
Aid.1 Dist. Dly 0 s
Aid. 2 Selection Disable
SOTF Status Enabled PoleDead
SOTF Delay 110 s
SOTF Tripping 011111 All Zone
TOR Status Enabled
TOR Tripping 000001 Zone 1
TOC Reset Delay 500
TOC Delay 200
Z1 Ext Scheme Disabled
LOL Scheme Disabled
GROUP 1 BACK UP I>
I > 1 Status Enable
I > 1 Function DT
I > 1 Directional Directional FWD
I > 1 Current Set 1800 A
I > 1 TMS 500 ms
I > 1 TReset 0 s
I > 2 Status Disable
I > 3 Status Disable
I > 4 Status Disable
I> Char Angle 30 Plain feeder
I> Blocking 001111 VTS Blk
GROUP 1 AIDED DEF
DEF Status Enabled
DEF Polarizing Zero Sequence
DEF Char. Angle -60 Transmission
DEF VNpol Set 1
DEF FWD Set 2E+06 mA
DEF REV Set 2E+06 mA
Virtual I Pol Enable
GROUP 1 POWER SWING BLK.
PSB Status Blocking
Zone 1 Ph. PSB Blocking
Zone 2 Ph. PSB Blocking
Zone 3 Ph. PSB Blocking
Zone P Ph. PSB Blocking
Zone 4 Ph. PSB Blocking
Zone 1 Gnd. PSB Blocking
Zone 2 Gnd. PSB Blocking
Zone 3 Gnd. PSB Blocking
Zone P Gnd. PSB Blocking
Zone 4 Gnd. PSB Blocking
WI Trip PSB Inhibit Trip
PSB Unblocking Disabled
PSB Reset Delay 200.0 ms
OST Mode OST Disabled
Slow Swing Disabled
NAME VALUE Remark
GROUP 1 CB FAIL & P.DEAD
CB Fail 1 Status Enabled
CB Fail 1 Timer 200.0 ms
CB Fail 2 Status Enabled
CBF Non I Rst I< Only
CBF Ext Reset I< Only
WI Prot Disabled Disabled
ExtTrip Only Ini Disabled
I< Current Set 300.00 mA
ISEF< Current 300.00 mA
V< 30.00 V
GROUP 1 SUPERVISION
VTS Mode Measured + MCB
VTS Status Blocking
VTS Reset Mode Auto
VTS Time Delay 5.000 s
VTS I> Inhibit 1.5 mA
VTS I2> Inhibit 50 mA
Inrush Detection Disabled
WI Inhibit Enabled
I0/I2 Setting 3
CTS Mode Disabled
GROUP 1 SYSTEM CHECKS
Live Line 53 V
Dead Line 20 V
Live Bus 53 V
Dead Bus 20 V
CS UV 53 V
CS OV 73 V
System Checks Enabled
CS Voltage Block V<
CS1 Status Enabled
CS1 Angle 25 deg
CS1 VDiff 13 V
CS1 Slip Ctrl Enabled
CS1 SlipFreq 200
CS2 Status Disabled
GROUP 1 AUTORECLOSE
AR Mode AR 3P
AR Shots 1
3P AR DT Shot 1 1 s
3PAR ReclaimTime 5 s
AR CBHealthyTime 5 s
AR CheckSyncTime 5 s
Z1 AR Initiate AR
Diff AR Initiate AR
Dist Aided AR Initiate AR
Z2T AR Block AR
Z3T AR Block AR
ZPT AR Block AR
Z4T AR Block AR
DEF Aided AR Block AR
Dir Aided AR Block AR
TOR AR Block AR
I>1 AR No Action
GROUP 1 INPUT LABELS
Opto Input 1 Opto Label 01 79 ON
Opto Input 2 Opto Label 02 52b
Opto Input 3 Opto Label 03 52b (Transfer bay)
Opto Input 4 Opto Label 04
Opto Input 5 Opto Label 05
Opto Input 6 Opto Label 06 MANUAL CLOSE
Opto Input 7 Opto Label 07
Opto Input 8 Opto Label 08
Opto Input 9 Opto Label 09
Opto Input 10 Opto Label 10
Opto Input 11 Opto Label 11
Opto Input 12 Opto Label 12
Opto Input 13 Opto Label 13
Opto Input 14 Opto Label 14
NAME VALUE Remark
Opto Input 15 Opto Label 15
Opto Input 16 Opto Label 16

GROUP 1 OUTPUT LABELS


Relay 1 Relay Label 01 DIST. PHASE A
Relay 2 Relay Label 02 DIST. PHASE B
Relay 3 Relay Label 03 DIST. PHASE C
Relay 4 Relay Label 04 DIST. ZONE 1
Relay 5 Relay Label 05 DIST. ZONE 1
Relay 6 Relay Label 06 DIST. ZONE 2
Relay 7 Relay Label 07 DIST. ZONE 2
Relay 8 Relay Label 08 DIST. PHASE N
Relay 9 Relay Label 09 DIST. ZONE 1
Relay 10 Relay Label 10 DIST. ZONE 2
Relay 11 Relay Label 11 LOSS OF PT
Relay 12 Relay Label 12 A/R INPROGRESS
Relay 13 Relay Label 13 50BF OPERATED
Relay 14 Relay Label 14 RECLOSE LOCKOUT
Relay 15 Relay Label 15 DIST. ZONE 3
Relay 16 Relay Label 16 DIST. ZONE 4
Relay 17 Relay Label 17 POWER SWING BLOCK
Relay 18 Relay Label 18 A/R INPROGRESS
Relay 19 Relay Label 19 DIST. OPERATED
Relay 20 Relay Label 20 SOFT
Relay 21 Relay Label 21 A/R CLOSE

GROUP 1 LED
LED 1 21/21N ZONE 1
LED 2 21/21N ZONE 2,3
LED 3 21/21N ZONE 4
LED 4 Power Swing
LED 5 SOTF/TOR Trip
LED 6 A/R Lockout
LED 7 A/R Close
LED 8 VT Fail
missiver overreacch
Subsation : APRIL Area : NE3 Date : 28-Oct-24 Remark :
Protection : APRIL Line to MAY Panel : APRIL1YB-01
Relay type : P443 APRIL MAY
Function : 21/21N, 67/67N, 25/79 12 km SD 20 km
CTR = 1800 / 1
VTR = 115000 / 115
CTR/VTR = 1.8 15 km SD
LL1 = 12 km Line type SD
LL2 (shortest line) = 15 km Line type SD JUNE
LL2 (longest line) = 20 km Line type SD
Max MVA = 320 MVA
Voltage = 115 kV Section2(shortest)
Pos. Seq. Resistance = 0.042936 Ohm/km 0.927 ohm_sec 0.042936 Ohm/km
Pos. Seq. Reactance = 0.2677 Ohm/km 5.78232 ohm_sec 0.2677 Ohm/km
Zero. Seq. Resistance = 0.17169 Ohm/km 3.7085 ohm_sec 0.17169 Ohm/km
Zero. Seq. Reactance = 1.0707 Ohm/km 23.1271 ohm_sec 1.0707 Ohm/km
Pos. Seq. Imp. = 0.2711 Ohm/km 5.85622 ohm_sec 0.2711 Ohm/km
Zero Seq. Imp. = 1.0844 Ohm/km 23.4226 ohm_sec 1.0844 Ohm/km
Pos. Line Imp. = 5.86 Ohm_sec 81 deg
Zero Line Imp. = 23.42 Ohm_sec 81 deg
Z1 = 85 % of LL1 R1 = 0.7883 X1 = 4.91497 Z1
= 4.98 Ohm_sec R0 = 3.15223 X0 = 19.6581 Z0
= 2.77 Ohm_pri R1 = 0.43795 X1 = 2.73054 Z1
R0 = 1.75124 X0 = 10.9211 Z0
tZ1 = 0 ms
Z2 = 100 % of LL1+ 50 %shortest LL2 I2/I1= 3.23514
= 21.36 Ohm_sec R1 = 1.50705 X1 = 9.39627 Z1
= 11.87 Ohm_pri R0 = 6.02632 X0= 37.5816 Z0
R1 = 0.83725 X1 = 5.22015 Z1
tZ2 = 300 ms R0 = 3.34796 X0 = 20.8787 Z0
Z3 = 100 % of LL1+ 120 %longest LL2 I2/I1= 3.23514
= 55.46 Ohm_sec R1 = 2.78225 X1 = 17.347 Z1
= 30.81 Ohm_pri R0 = 11.1255 X0= 69.3814 Z0
R1 = 1.5457 X1 = 9.6372 Z1
tZ3 = 600 ms R0 = 6.18084 X0 = 38.5452 Z0
Z4 = 15 % of Z1
= 0.75 Ohm_sec R1 = 0.11825 X1 = 0.73725 Z1
= 0.41 Ohm_pri R0 = 0.47283 X0= 2.94871 Z0
R1 = 0.06569 X1 = 0.40958 Z1
tZ4 600 ms R0 = 0.26269 X0 = 1.63817 Z0
K0 = 1.00
K0Ang = 0.00
Zmin = 41 Ohm_pri
= 74 Ohm_sec
Max Rph = 45 Ohm_sec 60% of minimun load imp.
R3ph-R4ph = 44.63 Ohm_sec max Rph
R2ph = 35.71 Ohm_sec 80% of R3ph-R4ph
R1ph = 28.57 Ohm_sec 80% of R2ph
Max RG = 40 Ohm_pri
R3G-R4G = 72 Ohm_sec 40 Ohm_pir All zone
R2G = 72 Ohm_sec 40 Ohm_pir All zone
R1G = 72 Ohm_sec 40 Ohm_pir All zone
Delta R = 13 Ohm_sec 30% of R3ph-R4ph
Delta X = 13 Ohm_sec 30% of R3ph-R4ph
Phase DOC = 1800 A 1
Time delay = 500 ms
Ground DOC = 1800 A 1
Time delay = 500 ms
Tele-Scheme = Basic
Tele Phase DOC = 1800 A 1
Tele-Time delay = 150 ms
Tele Ground DOC = 1800 A 1
Tele-Time delay = 150 ms
Live Volt = 53 80%Un
Dead Volt = 20 30%Un
Diff Volt = 13.3 20%Un
Diff Angle = 25
Diff Frequency = 200 mHz
Under Voltage = 53 80%Un
Over Volage = 73 110%Un

**DO NOT MODIFY ANYTHING ON THIS SHEET!!!

This EXCEL spreadsheet was developed by:

Protection System Engineering Section


Protection and Relay Division
Provincial Electricity Authority
(+66)02-5909576

Update History
27-Sep-21 - Add P442, update Reclaim time 15 sec
29-Sep-21 - Set password CAL Sheet
19-Oct-21 - Add Summary page
15-Jan-22 - Fix display LL for Z4 and Auto select line imp.
22-Jan-22 - Add PSB for P442
11-Jun-22 - Fix ABB PSB
28-Aug-22 - Add ABB REL650 Version2
- Fix ABB RED670/Idmin following PEA criteria (CT rated)
- Fix ABB RED670/End Slope1 following Application Manual
- Fix ABB RED670/Slope section2 following Application Manual
- Fix ABB RED670/Slope section3 following Application Manual
- Fix Protecta/67N/Char. Angle from 60 deg. to 120 deg. (3U0 Pol. Ref.)
- Fix ABB REL650 V.1 FDPSPDIS/X1 from Sec. value to Pri. Value.
3-Sep-22 - แก้ไข Load Enchroachment : RLdFw รีเลย์ ABB ทุกรุ่น ไม่ให้เข้าไปใน
ข้อควรระวัง : ใช้ได้เฉพาะสายส่งสั้นเท่านั้น (<77km) หากสายส่งยาว

K0 Calculation
Z1/km = 0.042936+0.2677i
Z0/km = 0.17169+1.0707i
Z0-Z1 = 0.128754+0.803i
3Z1 = 0.128808+0.8031i
K0 = 0.999868091351552+4.60828175951498e-05i
JULY
SD

JUNE

ion2(shortest) Section2(longest) Transmission Line Parameter


Ohm/km 0.042936 Ohm/km SD SS
Ohm/km 0.2677 Ohm/km R1 0.042936 0.085811
Ohm/km 0.17169 Ohm/km X1 0.2677 0.36204
Ohm/km 1.0707 Ohm/km R0 0.17169 0.2789
Ohm/km 0.2711 Ohm/km X0 1.0707 1.1766
Ohm/km 1.0844 Ohm/km

Zone reach to km
= 4.97779 Z1 = 10.200 km
= 19.9092 Z2 = 19.500 km
= 2.76544 Z3 = 36.000 km
= 11.0607 Z4 = 1.530 km

= 9.51636
= 38.0617
= 5.28687
= 21.1454
38.0617
= 17.5687
= 70.2677
= 9.76037
= 39.0376

= 0.74667
= 2.98638
= 0.41482
= 1.6591
ห้เข้าไปใน zone operate เนื่องจากหากเกิดฟอลต์ SLG รีเลย์จะบล็อค
หากสายส่งยาว Heavy Load สามารถทำให้ zone operate ได้
PROVINCIAL ELECTRICITY AUTHORITY

SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.

PROTECTION AND RELAY DIVISION

115 kV. DISTANCE RELAY (21/21N) SETTING

SUBSTATION: APRIL BREAKER :

FUNCTION: 21/21N, 67/67N, 25/79 MODEL NO.:


CT AND VT RATIOS GROUP 1 \DIST. ELEMENTS
Number Settings Value Unit Number Settings
0A.01 Main VT Primary 115 kV 32.01 PHASE DISTANCE
0A.02 Main VT Sec'y 115 V 32.02 Z1 Ph. Reach
0A.03 CS VT Primary 115 kV 32.03 Z1 Ph. Angle
0A.04 CS VT Secondary 115 V 32.09 Z1 Sensit. Iph>1
0A.07 Phase CT Primary 1800 A 32.10 Z2 Ph. Reach
0A.08 Phase CT Sec'y 1 A 32.11 Z2 Ph. Angle
0A.0B SEF CT Primary 1800 A 32.17 Z2 Sensit. Iph>2
0A.0C SEF CT Secondary 1 A 32.20 Z3 Ph. Reach
0A.0D MComp CT Primary 1800 A 32.21 Z3 Ph. Angle
0A.0E MComp CT Sec'y 1 A 32.28 Z3 Sensit. Iph>3
0A.0F CS Input BN 32.40 Z4 Ph. Reach
0A.10 Main VT Location Bus 32.41 Z4 Ph. Angle
0A.11 CT Polarity Standard 32.46 Z4 Sensit. Iph>4
0A.13 SEF CT Polarity Standard 32.50 GROUND DISTANCE
0A.14 M CT Polarity Standard 32.51 Z1 Gnd. Reach
0A.21 CS VT Ph Shift 0 deg 32.52 Z1 Gnd. Angle
0A.22 CS VT Mag 1 32.53 Z1 Dynamic Tilt
GROUP 1 \LINE PARAMETERS 32.54 Z1 Tilt Top Line
Number Settings Value Unit 32.55 kZN1 Res. Comp.
30.01 Line Length 12.000 Km 32.56 kZN1 Res. Angle
30.03 Line Impedance 5.856 Ohm 32.59 R1 Gnd Resistive
30.04 Line Angle 80.89 deg 32.5B Z1 Sensit Ignd>1
30.05 kZN Res Comp 1.000 32.60 Z2 Gnd. Reach
30.06 kZN Res Angle 0.003 deg 32.61 Z2 Gnd. Angle
30.07 Mutual Comp Disabled 32.63 Z2 Dynamic Tilt
30.0B Phase Sequence Standard ABC 32.64 Z2 Tilt Top Line
30.0C Tripping Mode 3 Pole 32.65 kZN2 Res. Comp.
30.10 Line Charging Y 2.00 mS 32.66 kZN2 Res. Angle
GROUP 1 \DISTANCE SETUP 32.69 R2 Gnd Resistive
Number Settings Value Unit 32.6B Z2 Sensit Ignd>2
31.0C Setting Mode Advanced 32.70 Z3 Gnd. Reach
31.10 PHASE DISTANCE 32.71 Z3 Gnd. Angle
31.11 Phase Chars. Mho 32.73 Z3 Dynamic Tilt
31.20 Zone 1 Ph Status Enabled 32.74 Z3 Tilt Top Line
31.30 Zone 2 Ph Status Enabled 32.75 kZN3 Res. Comp.
31.40 Zone 3 Ph Status Enabled 32.76 kZN3 Res. Angle
31.42 Zone 3 Ph Dir. Forward 32.79 R3 Gnd Resistive
31.50 Zone P Ph Status Disabled 32.7C Z3 Sensit Ignd>3
31.60 Zone 4 Ph Status Enabled 32.90 Z4 Gnd. Reach
31.70 GROUND DISTANCE 32.91 Z4 Gnd. Angle
31.71 Ground Chars. Quad 32.93 Z4 Dynamic Tilt
31.80 Zone 1 Gnd Stat. Enabled 32.94 Z4 Tilt Top Line
31.90 Zone 2 Gnd Stat. Enabled 32.95 kZN4 Res. Comp.
31.A0 Zone 3 Gnd Stat. Enabled 32.96 kZN4 Res. Angle
31.A2 Zone 3 Gnd Dir. Forward 32.99 R4 Gnd Resistive
31.B0 Zone P Gnd Stat. Disabled 32.9B Z4 Sensit Ignd>4
31.C0 Zone 4 Gnd Stat. Enabled 32.B0 Mem Volt Dura
31.D0 Digital Filter Standard GROUP 1 \SCHEME LOGIC
31.D1 CVT Filters Disabled Number Settings
31.D3 Load Blinders Disabled 34.01 BASIC SCHEME
31.D4 Z< Blinder Imp 36.886 Ohm 34.02 BasicScheme Mode
31.D5 Load/B Angle 45.00 34.08 Zone1 Tripping
31.D6 Load Blinder V< 46 V 34.09 tZ1 Ph. Delay
31.D7 Dist. Polarizing 1.000 34.0A tZ1 Gnd. Delay
31.E0 DELTADIRECTIONAL 34.10 Zone2 Tripping
31.E1 Dir. Status Disabled 34.11 tZ2 Ph. Delay
31.F0 DIST STUB BUS 34.12 tZ2 Gnd. Delay
31.F1 Dist Stub Bus Disabled
PROVINCIAL ELECTRICITY AUTHORITY

SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.

PROTECTION AND RELAY DIVISION

115 kV. DISTANCE RELAY (21/21N) SETTING

SUBSTATION: APRIL BREAKER :

FUNCTION: 21/21N, 67/67N, 25/79 MODEL NO.:


GROUP 1 \SCHEME LOGIC GROUP 1 \POWER SWING BLK.
Number Settings Value Unit Number Settings
34.18 Zone3 Tripping Phase And Ground 3D.07 Zone 3 Ph. PSB
34.19 tZ3 Ph. Delay 600.0 ms 3D.09 Zone P Ph. PSB
34.1A tZ3 Gnd. Delay 600.0 ms 3D.0B Zone 4 Ph. PSB
34.20 ZoneP Tripping Phase And Ground 3D.0D Zone 1 Gnd. PSB
34.21 tZP Ph. Delay 400.0 ms 3D.0F Zone 2 Gnd. PSB
34.22 tZP Gnd. Delay 400.0 ms 3D.11 Zone 3 Gnd. PSB
34.28 Zone4 Tripping Phase And Ground 3D.13 Zone P Gnd. PSB
34.29 tZ4 Ph. Delay 600.0 ms 3D.15 Zone 4 Gnd. PSB
34.2A tZ4 Gnd. Delay 600.0 ms 3D.16 WI Trip PSB
34.40 AIDED SCHEME 1 3D.20 PSB Unblocking
34.41 Aid. 1 Selection Disabled 3D.22 PSB Reset Delay
34.60 AIDED SCHEME 2 3D.23 OST Mode
34.61 Aid. 2 Selection Disabled 3D.40 Slow Swing
34.80 TRIP ON CLOSE GROUP 1 \CB FAIL & P.DEAD
34.81 SOTF Status Enabled PoleDead Number Settings
34.82 SOTF Delay 10.00 s 45.0A UNDER CURRENT
34.83 SOTF Tripping 000111 45.0B I< Current Set
34.84 TOR Status Enabled 45.0D ISEF< Current
34.85 TOR Tripping 000111 45.0E POLEDEAD VOLTAGE
34.86 TOC Reset Delay 500.0 ms 45.10 V<
34.88 TOC Delay 200.0 ms GROUP 1 \SUPERVISION
34.B0 Z1 EXTENSION Number Settings
34.B1 Z1 Ext Scheme Disabled 46.01 VTS Mode
34.C0 LOSS OF LOAD 46.02 VTS Status
34.C1 LOL Scheme Disabled 46.03 VTS Reset Mode
GROUP 1 \OVERCURRENT 46.04 VTS Time Delay
Number Settings Value Unit 46.05 VTS I> Inhibit
35.01 I>1 Status Enabled 46.06 VTS I2> Inhibit
35.02 I>1 Function DT 46.0E Inrush Detection
35.03 I>1 Directional Directional Fwd 46.10 WEAK INFEED BLK
35.04 I>1 Current Set 1.000 A 46.11 WI Inhibit
35.05 I>1 Time Delay 500.0 ms 46.12 I0/I2 Setting
35.09 I>1 tRESET 0.000 s 46.20 ISEF HARM. BLOCK
35.0A I>2 Status Disabled 46.21 ISEF>2nd Detect.
35.13 I>3 Status Disabled 46.30 CT SUPERVISION
35.18 I>4 Status Disabled 46.31 CTS Mode
35.1C I> Char Angle 30.00 deg GROUP 1 \SYSTEM CHECKS
35.1D I> Blocking 001111 Number Settings
GROUP 1 \EARTH FAULT 48.14 VOLTAGE MONITORS
Number Settings Value Unit 48.85 Live Line
38.01 IN>1 Status Enabled 48.86 Dead Line
38.25 IN>1 Function DT 48.87 Live Bus
38.26 IN>1 Directional Directional Fwd 48.88 Dead Bus
38.29 IN>1 Current Set 1.000 A 48.8B CS UV
38.2C IN>1 Time Delay 500.0 ms 48.8C CS OV
38.33 IN>1 tRESET 0.000 s 48.8D System Checks
38.35 IN>2 Status Disabled 48.8E CS Voltage Block
38.46 IN>3 Status Disabled 48.8F CS1 Status
38.4D IN>4 Status Disabled 48.90 CS1 Angle
38.54 IN> Blocking 001111 48.91 CS1 VDiff
38.55 IN> DIRECTIONAL 48.92 CS1 Slip Ctrl
38.56 IN> Char Angle -60.00 deg 48.93 CS1 SlipFreq
38.57 IN> Polarisation Zero Sequence 48.94 CS2 Status
38.59 IN> VNpol Set 1.000 V
GROUP 1 \POWER SWING BLK.
Number Settings Value Unit
3D.01 PSB Status Blocking
3D.03 Zone 1 Ph. PSB Blocking
3D.05 Zone 2 Ph. PSB Delay Unblock
PROVINCIAL ELECTRICITY AUTHORITY

SUBSTATION AND POWER SYSTEM MAINTENANCE DEPT.

PROTECTION AND RELAY DIVISION

115 kV. DISTANCE RELAY (21/21N) SETTING

SUBSTATION: APRIL BREAKER :

FUNCTION: 21/21N, 67/67N, 25/79 MODEL NO.:


GROUP 1 \AUTORECLOSE
Number Settings Value Unit
49.51 AR Mode AR Opto
49.59 AR Shots 1
49.5A AR Skip Shot 1 Disabled
49.5C Multi Phase AR Allow Autoclose
49.5D Discrim Time 100.0 ms
49.60 CB IS Time 5.000 s
49.61 CB IS MemoryTime 500.0 ms
49.62 DT Start by Prot Protection Reset
49.63 3PDTStart WhenLD Disabled
49.64 DTStart by CB Op Disabled
49.67 SP AR Dead Time 500.0 ms ms
49.68 3P AR DT Shot 1 1.000 s
49.69 3P AR DT Shot 2 60.00 s
49.6A 3P AR DT Shot 3 60.00 s
49.6B 3P AR DT Shot 4 60.00 s
49.6D SPAR ReclaimTime 60.00 s
49.6E 3PAR ReclaimTime 15.000 s
49.6F AR CBHealthyTime 5.000 s
49.70 AR CheckSyncTime 10.00 s
49.72 Z1 AR Initiate AR
49.74 Dist Aided AR Initiate AR
49.75 Z2T AR Block AR
49.76 Z3T AR Block AR
49.77 ZPT AR Block AR
49.78 Z4T AR Block AR
49.7B TOR AR Block AR
49.7C I>1 AR No Action
49.80 IN>1 AR No Action
49.A5 AR SYS CHECKS
49.A6 CB SC all Enabled
49.A7 CB SC Shot 1 Enabled
49.A8 CB SC ClsNoDly Disabled
49.A9 CB SC CS1 Enabled
49.AA CB SC CS2 Disabled
49.AB CB SC DLLB Enabled
49.AC CB SC LLDB Enabled
49.AD CB SC DLDB Disabled
CIAL ELECTRICITY AUTHORITY

D POWER SYSTEM MAINTENANCE DEPT.

ECTION AND RELAY DIVISION

STANCE RELAY (21/21N) SETTING

APRIL1YB-01

Agile P443
GROUP 1 \DIST. ELEMENTS
Value Unit

4.978 Ohm
80.89 deg
300 mA
21.357 Ohm
80.888 deg
300 mA
55.460 Ohm
80.89 deg
300 mA
0.747 Ohm
80.888 deg
300 mA

4.978 Ohm
80.89 deg
Disabled
0.000 deg
1.000
0.003 deg
72.00 Ohm
100 mA
21.36 Ohm
80.89 deg
Disabled
0.000 deg
1.000
0.003 deg
72.00 Ohm
100 mA
55.460 Ohm
80.89 deg
Disabled
0.000 deg
1.000
0.003 deg
72.00 Ohm
100 mA
0.747 Ohm
80.89 deg
Disabled
0.000 deg
1.000
0.003 deg
72.000 Ohm
100.00 mA
16.00
GROUP 1 \SCHEME LOGIC
Value Unit

Standard
Phase And Ground
0.000 s
0.000 s
Phase And Ground
300.0 ms
300.0 ms
CIAL ELECTRICITY AUTHORITY

D POWER SYSTEM MAINTENANCE DEPT.

ECTION AND RELAY DIVISION

STANCE RELAY (21/21N) SETTING

APRIL1YB-01

Agile P443
GROUP 1 \POWER SWING BLK.
Value Unit
Delay Unblock
Delay Unblock
Delay Unblock
Blocking
Delay Unblock
Delay Unblock
Delay Unblock
Delay Unblock
Inhibit Trip
Disabled
200.0 ms
OST Disabled
Disabled
GROUP 1 \CB FAIL & P.DEAD
Value Unit

1.00 A
20.00 mA

38.10 V
GROUP 1 \SUPERVISION
Value Unit
Measured + MCB
Blocking
Auto
5.000 s
1.50 A
50.00 mA
Disabled

Enabled
3.000

Disabled

Disabled
GROUP 1 \SYSTEM CHECKS
Value Unit

53 V
20 V
53 V
20 V
53 V
73 V
Enabled
V<
Enabled
25 deg
13 V
Enabled
200 mHz
Disabled
CIAL ELECTRICITY AUTHORITY

D POWER SYSTEM MAINTENANCE DEPT.

ECTION AND RELAY DIVISION

STANCE RELAY (21/21N) SETTING

APRIL1YB-01

Agile P443