0% found this document useful (0 votes)
87 views19 pages

Fire Barrier Systems

Uploaded by

Persona Grata
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views19 pages

Fire Barrier Systems

Uploaded by

Persona Grata
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

Technical datasheet

FirePro Fire Barrier


Version 3.0 October 2023

FirePro ®

Fire Barrier
Preventing the spread of fire and inhibiting the
passage of smoke in concealed spaces
ROCKWOOL Fire Barrier is a dense stone wool roll with an integral wire mesh,
developed to prevent the spread of flames through concealed spaces, while also
inhibiting the transfer of heat and smoke.

• Patented ‘EasyFit’ fixing system offers fire resistance of up to an hour


• Alternative fixing method offers up to two hours’ resistance
• Provides airborne sound reduction
• Service penetration data available ROCKWOOL Fire Barrier
prevents the passage of fire and
inhibits the spread of smoke
within roof and ceiling voids.

Supported by an integral wire


mesh, Fire Barrier is suitable for
voids up to 10.5m in height.

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
FirePro Fire Barrier

APPLICATIONS
• Pitched roof voids
• Head of wall
• Concealed ceiling spaces
• Multiple substrates

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
2.
FirePro Fire Barrier

PERFORMANCE
Fire performance

Maximum Maximum
drop drop with
without additional
Rating support support Max Supporting
required frame frame width Integrity Insulation Install specification document
30 min 10.5m 30 15 Single 50mm layer FB, vertical joints butt
3m 20m 116911
cavity barrier - 60 15 jointed.

Single 60mm layer (plain or foil face) with a


30 min
6m N/A 20m 60 30 minimum 100mm overlapped and stitched 11970
fire barrier
joints on vertical joints*.
60 min
6m 20m 60 60 2 layers of 50mm back to back butt jointed 116912
fire barrier
10.5m with staggered vertical joints between the
90 min back to back layers.
3.5m 20m 90 90 51812
fire barrier
2 layers of 60mm (plain or foil face) butt
120 min
3.5m 9m 20m 120 120 jointed, incorporating a 40mm aircavity 44509
fire barrier
between the layers.

N.B. All extensions in drop height must incorporate a minimum 100mm overlap between the sections and stitched with
1.5mm galvanised wire.

*All stitching must be carried out using 0.9mm annealed and galvanised wire. Continuous wire stitching (100mm minimum)
or separate lengths of wire secured by twisting ends together. Wire must penetrate through thickness of barrier.

Acoustic performance
The correct use of Fire Barrier within structural cavities and voids will reduce the level of transmitted sound.

Room to room attenuation Rw dB

Typical lay-in grid suspended ceiling 30

Ceiling and 50mm ROCKWOOL Fire Barrier 42

Ceiling and 50mm ROCKWOOL Fire Barrier Foil Faced 44

Ceiling and 2x layers of 50mm ROCKWOOL Fire Barrier Foil Faced 50

Where plasterboard ceilings are used, add 2-3dB to above performances.


Note: Values quoted are approximate.

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
3.
FirePro Fire Barrier

PRODUCT INFORMATION
• One or two sided foil face options available.
• Wired mesh is available to both sides if required.

Thickness Length Width

50mm 3700mm 1000mm

60mm 3000mm 1000mm

STANDARDS AND APPROVALS


Certificate

Fire Barrier has been independently tested and assessed to BS 476: Part 22
by UKAS accredited laboratories.

They are third party approved for performance and quality by the Loss Prevention
Council Certification board (LPCB) and are listed in their Fire and Security ‘Red Book’ - certificate no. 022c.

The product has been authorised for use in LUL surface and sub-surface premises when installed in
accordance with this data sheet - please refer to the LUL Approved Product Register website
www.LU-apr.co.uk for specific details – LUL ref: 2230.

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
4.
FirePro Fire Barrier

INSTALLATION
½ hour cavity barrier
Figures 4-9 show typical details for Fire Barrier applied to a timber truss construction as a half hour cavity barrier within the roof
section, to satisfy the requirements of building Regulation B3 - (4) i.e. 30 minutes fire integrity and 15 minutes fire insulation.

If the truss is constructed from a minimum timber size of 35 to 49mm thick, both sides of all truss members/bracing require
protection from fire in order to minimise charring and retain strength. Figure 6 shows strips of 50mm Fire Barrier used on the
reverse side of the truss (for this purpose). Nail plate fixings may fail prematurely in fire unless protected (see Figure 9).

The ROCKWOOL
Fire Barrier ROCKWOOL
angle support
Fixing System
incorporates an
ROCKWOOL
angle support and clamping plate
clamping plate
(Up to one hour)

For fixing to timber, the ROCKWOOL clamping plate is used, compressing the barrier to the timber, fixed at 450mm centres
using No. 10 woodscrews.

To use the patented ROCKWOOL angle support system, bend tongues out to 90° and impale barrier onto them. The slotted
clamping plate is then fitted by pushing the tongues through the slots, these are then bent over the face of the clamping plate
completing the process.

Figure 4
Allow sufficient material
Fire Barrier to pack and stitch Fire
Barrier between rafters
traverse to rafters as shown

Tongues at max 450mm


centres

Continuous angle support


secured to underside of
each rafter with no 10
wood screws

RW clamping plate

Figure 5 RWA45
min 200mm
Half hour Tiled or slated roof

protection for
No. 10 wood screws at
timber truss maximum 450mm centres
construction RW clamping plate
50mm thick ROCKWOOL 50mm Fire
or more. Barrier tightly butt joined
and stitched (see Fig. 15)
Note: nail plate protection
required - see Figure 6 Minimum 50mm thick
timber trussed rafter
No. 10 wood screws at
maximum 450mm centres
Clamping plate

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
5.
FirePro Fire Barrier

Figure 6 RWA45
Half hour min 200mm
Tiled or slated roof
protection for
35-49mm thick timber
timber truss trussed rafter
construction 35
0.9mm wire stitching
to 49mm thick. to secure strips to main
barrier stitches typically
100mm long

No. 10 wood screws


(or large washer and
screws) at maximum
450mm centres
50mm Fire Barrier

Figure 7
Head of partition
ROCKWOOL Fire Barrier

RW clamping plate

No.10 wood screws at


max 450mm centres

Head plate

Ceiling board

Figure 8
Barrier fitted
transversely
to timber
joisted ceiling
Tongues fixed at max
300mm centres

Angle support fixed to


ceiling joists

Figure 9 25mm thick


ROCKWOOL
Nail plate BeamClad® fixed with
protection FirePro Glue and nailed,
or 50mm Fire Barrier
secured with screws and
large square washers.
300 Use 50mm nails for
BeamClad and 70mm
screws for Fire Barrier.

300

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
6.
FirePro Fire Barrier

For fixing to concrete soffits (Figure 10-12), the pre-punched angle support is fixed using Hilti DBZ or Ejot ECL 35 hammer set
anchors at max. 750mm centres. For fixing to steel purlins, use Hilti SMD 02Z (5.5 x 70mm) self-tapping screws at maximum
450mm centre.

Figure 10
Support angle fixed
50mm Fire to soffit at max 750mm
centres
Barrier fixed to
concrete soffit.

Angle support tangs fixed at


450mm centres
max 450mm

max 450mm

Figure 11
50mm Fire
Barrier running
across ribbed
soffit - Section RW clamping plate fixed
at 450mm centres

Angle support fixed


as Fig10

Barrier cut and packed


into troughs and wired
to prevent uncoiling

Figure 12
Alternative
fixing to flat s
offit or perimeter,
appropriate to
barriers with a 50mm Fire Barrier
compressed between
shallow drop soffit and clamping plate
at max 450mm centres

Hilti DBZ 6/4.5 or


Ejot ECL 35 hammer
set anchor

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
7.
FirePro Fire Barrier

60-30 Fire Barrier


If 30 minutes insulation is required, use 1 layer of 60mm plain or foil-faced fire barrier with 100mm vertical over lapped joints
(Figure 13 & 14). The barrier is otherwise fixed for timber construction as previously shown on Figures 4-9.

Figure 13

min 100mm

Figure 14

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
8.
FirePro Fire Barrier

Common details
Extended drops
ROCKWOOL 50mm Fire Barrier single and double layers, can be extended from a 3.5m drop to a maximum 6m drop by fixing
an additional 2.5m section, stitched with overlapped joints as per Figure 16. For additional guidance and drops in excess of
6m, please refer to Figure 31 and associated guidance.

Wire stitching of butt joints in ROCKWOOL Fire Barrier


Adjacent barriers must be closely butt jointed, or overlapped, and through stitched with 0.9mm galvanised annealed wire
(see Figure 15). It is essential that the barrier provides a good seal at its head, perimeter and at all joints. Where the barrier
abuts a profile such as a trapezoidal deck, the material must be cut to suit and secured to fire stop the gap (see Figure 17).
For extended drops, 1.5mm diameter galvanised and annealed wire is used (see Figure 16).

Figure 15

100mm typical

Figure 16

min 100mm 100mm typical

Figure 17 Fire Barrier cut and


pushed up into profile as
fire stopping

max Angle or clamping plate


max 450mm
450mm fixing Fire Barrier to purlin
with self tapping screws
at 450mm centres (Hilti
SMD 02Z 5.5 x 70mm)

Adjacent Barriers butt


jointed and wired tightly
together as Fig15

Fire Barrier draped over


suspended ceiling and
wired to grid, min 100mm
lap. If not wired, overlap
is min 150mm

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
9.
FirePro Fire Barrier

Penetration details
It is regarded as good practice to adequately support or reinforce services penetrating compartment walls and cavity
barriers, to prevent displacement. It is recommended that such supports should be no greater than 500mm from each face
of the Fire Barrier.

To maintain the integrity of the barrier when penetrated by services with a high melting point (such as steel or copper pipes,
beams or trusses) the barrier is first cut locally to accommodate the service or structural member and then re-stitched as
neatly as possible. The penetration is then lightly sleeved each side of the barrier to a minimum length of 300mm, using the
same barrier material. Each sleeve should be securely stitched to the main barrier to produce a tight seal and prevent future
detachment (see Figures 18 and 19). Where access is only available from one side, the double seal solution may be replaced
by a single ‘collar’ detail - please contact our Technical Fire Team for further advice.

If the penetrating service is manufactured from a low melting point material such as plastic or aluminium, then sleeving should
be extended to at least 1000mm either side of the barrier.

This guidance applies to services such as pipes, sheathed cables and conduits, including those carried on steel trays.

For protected steel ductwork with a tested fire resistance performance (stability, integrity and insulation) at least the same as
the Fire Barrier, 300mm sleeves should be applied either side of the main barrier, as for high melting point services above.

For information on achieving fire protection to steel ductwork, please refer to the ROCKWOOL Fire Duct System data sheet.

For non-fire protected ductwork, or that with a fire resistance performance less than the barrier, two sleeves should be applied
to each side of the barrier, an inner sleeve of 1000mm and an outer sleeve of 300mm. All sleeves should be stitched to the
main barrier.

The duct should also include an independently supported fire damper, located in the line of the main barrier. Reference should
also be made to Approved Document B of England & Wales Building Regulations - Volume 1, Requirement B3, Section 7 and
Volume 2, Requirements B3, Section 10.

Figure 18

Sleeves wire stitched


1m min through main barrier

300mm min
Fire barrier material
backing

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
10.
FirePro Fire Barrier

Figure 19

Sleeves to be stitched to
main barrier

Off-cuts of Fire Barrier


to be packed tightly into
purlin void

1 hour Fire Barrier


The unique, patented ROCKWOOL support angle and clamping plate is used to fasten two 50mm Fire Barrier curtains with
one support angle without the need for a cavity.

The ROCKWOOL support angle has tongues that are pushed out from opposite sides at 300mm max. centres. A layer of
Fire Barrier is impaled onto the tongues on each side, with joints staggered, then fixed in place using ROCKWOOL clamping
plates. The clamping plates are secured by bending the support angle tongues.

Note that the wire-reinforced sides should face outwards.

Figure 20

Concrete soffit

Fire Barrier support angle

Hilti DBZ 6/4.5 or Ejot


ECL 35 hammer set
anchor at max 750mm
centres

Two layers of 50mm


Fire Barrier with joints
staggered

Figure 21

Clamping plate

Screw system at max


450mm centres

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
11.
FirePro Fire Barrier

Figure 22

Clamping plate

Hilti hammer screws at


max. 450mm centres

Figure 23 Concrete soffit

Support angle fixed to


soffit at max 750mm
centres
300mm
300mm max Clamping plate fixed at
max
300mm centres

Two layers of 50mm


Rockwool Fire Barrier,
vertical joints staggered
and stitched and clamped
to head of wall

Suspended ceiling

Fire-resisting wall

Fixing to timber structure (1 hour)


When a 1 hour Fire Barrier is supported on structural timber (for example a trussed rafter), and the thickness of timber is
35-49mm, one layer of 60mm ROCKWOOL Fire Barrier must be placed on each side of the timber (see Figure 24).
Where timber thickness is 50mm or greater, 2 layers of 50mm Fire Barrier are sufficient.

Figure 24 Fill space between battens


with 300mm wide RWA45

RW clamping plate
No.10 wood screws at
maximum 450mm centres
35mm thick timber
trussed rafter
60mm ROCKWOOL Fire
Barrier tightly butt joined
and stitched (see Fig.15)
1 hour fire rated ceiling
Clamping plate
No.10 wood screws at
maximum 450mm centres

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
12.
FirePro Fire Barrier

1.5 & 2 hour Fire Barrier


1.5 hour Fire Barrier
The 1.5 hour solution requires 2 layers of 50mm Fire Barrier with staggered joints fixed as Figures 25-27. Note that wire
reinforced faces should face outwards.

Figure 25 Concrete soffit


2mm tested angle fixed
to soffit at max 750mm
150mm
300mm max centres (see Fig. 26).
300mm max
max
Clamped at max 300mm
centres with M6 bolts
and nuts

Two layers of 50mm


ROCKWOOL Fire Barrier,
vertical joints staggered
and stitched

Suspended ceiling

Fire-resisting wall

Figure 26 Concrete soffit

2mm tested angle fixed


to soffit at max 750mm
centres
M8 expanding bolt
anchors at max. 750mm
centres

M6 bolts and nuts


staggered each side

2mm tested punched


strap
Two layers of 50mm Fire
Barrier with vertical joints
staggered

Figure 27

2mm tested punched


strap

Hilti HUS universal Screw


System max. 300mm
centres

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
13.
FirePro Fire Barrier

2 hour Fire Barrier


The 2-hour solution (see Figures 28-30) requires two layers of 60mm Fire Barrier with staggered vertical joints, separated by a
nominal 40mm air space. The base or perimeter to which the barrier is fixed must be capable of remaining in place for 2 hours.

Figure 28 Concrete soffit


2mm tested angle fixed
to soffit at max 750mm
centres (see Fig. 29).
2mm tested strap
clamped at max 300mm
centres with M6 bolts
and nuts
Two layers of foil-faced, wire
reinforced 60mm Fire Barrier,
with foil outwards, vertical
joins, staggered and stitched.
40mm air space between the
two layers

Suspended ceiling
Fire-resisting wall

Figure 29

2mm tested angle fixed


to soffit at max 750mm
centres

M8 expanding bolt
anchors at max. 750mm
centres
2mm punched strap

M6 bolts and nuts

Figure 30
Two layers of foil-
faced Fire Barrier

2mm punched
strap and universal
Screw System max.
300mm centres

2mm punched
strap

Ceiling

Angle and strap for 1.5 and 2 hour Fire Barrier


The following specification for slotted angles and straps is suitable for supporting ROCKWOOL Fire Barrier for 1.5 and 2
hours when tested to BS 476: Part 22. Slotted angles (62 x 41 x 2mm) and straps (38 x 2mm) manufactured from mild steel
conforming to BS 1449: Part 1.1: 1991 and cold reduced to provide a minimum of 0.2% proof stress of 417 Mpa (27 tons/ in2)
and conforming to BS 4345: 1968 (1986) - Specification for slotted angles (inc. flat strap).

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
14.
FirePro Fire Barrier

OTHER INSTALLATION INFORMATION


General design considerations
A cavity fire barrier must be designed to restrict the passage of both hot smoke and flames for the minimum specified period,
as listed in Approved Document B in support of the Building Regulations. In addition, it must be fixed in such a way that:

• It will remain effective in the event of structural movement


• There are no gaps where it abuts other elements of construction
• It complies with the requirements of Approved Document B of the Building Regulations

Extended drops
For periods of up to 60 minutes, ROCKWOOL Fire Barrier can be used for extended void heights between 3.5 and 6m without
the need for a supported frame - see Figure 16 for joining barriers with overlap. For periods of up to 90 minutes, this drop
height can be increased to 10.5m (9m for 120 minutes), by the use of a simple frame system constructed from slotted angles
and straps (see Figure 31).

Further details are available from ROCKWOOL Technical Solutions Team.

Fire barriers and dampers


Where ROCKWOOL Fire Barrier is installed in conjunction with fire dampers, the dampers must be supported independently of
the fire barrier. HVCA or ASFP publications may be helpful.

Access through barriers


Where regular access is required through the barriers for maintenance purposes etc, this should be achieved by the inclusion
of an independently supported fire rated door set and frame. Fire Barrier should be clamped to the door frame with the RW
clamping plate and appropriate fixings at 450mm centres.

Figure 31

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
15.
FirePro Fire Barrier

ROCKWOOL ancillaries
ROCKWOOL Fire Barrier support angle and clamping plate are specially manufactured for ROCKWOOL.

Clamping Plate:
3m x 40mm, 10 lengths per pack

Fire Barrier Support Angles:


3m x 34mm x 75mm, 10 lengths per pack

Proprietary fixings
All steel hammer set expansion anchors for soffit fixings are available from Hilti, or Ejot. For perimeter fixings to concrete or
masonry, use Hilti HUS Universal Screw system. For fixings to timber, use standard No. 10 steel wood screws 100mm long.

Durability
For durability, we recommend that the finish should be capable of withstanding at least 200 hours salt spray and 400 hours
humidity corrosion resistance testing to BS 3990: Part F. Slotted angles and straps conforming to this specification are available
from the following suppliers: JB Products Tel: 01384 240234 Link 51 Tel: 01952 682251 Romstor Tel: 01442 242261
If other hardware is used to support the barriers, we recommend that the respective specifier, supplier or installer should be
certain that the chosen fixing system has been both tested and approved, for the required period of fire resistance and drop
height.

Packaging of Fire Barrier


Shrink wrapped in polyethylene

Handling
ROCKWOOL Fire Barrier is easy to handle and cut to shape. The product should be stored indoors or under a weatherproof
covering.

Maintenance
Once installed ROCKWOOL Fire Barrier should require no maintenance. It should be ensured during routine inspections that
the product has not been damaged or disturbed.

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
16.
FirePro Fire Barrier

SPECIFICATION CLAUSES
ROCKWOOL Fire Barrier is associated with the following NBS clauses:

K10: Gypsum board dry linings/partitions/ceilings

530 – Cavity fire barriers within partitions/wall linings

545 – Cavity fire barriers within suspended ceilings

KK40: Demountable suspended ceilings

287 – cavity barriers

425 – Installing cavity barriers

431 – Installing sound barriers

P10: Sundry insulation/proofing work

410 – Flexible cavity barriers

430 – Wired mineral wool small cavity barriers

440 – Fire protection

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
17.
FirePro Fire Barrier

BUILDING SAFETY AND PRODUCT USE

LEGAL NOTICES
General safety requirements – Building Safety Act 2022

ROCKWOOL Limited is committed to supporting specifiers, resellers and users of ROCKWOOL products for the full life cycle
of the product to comply with the obligations and responsibilities set out in the Building Safety Act 2022. With regard to the
general safety requirements of the Act, ROCKWOOL Limited cannot control or foresee every situation where its products might
be used. We therefore strongly advise that specifiers, resellers and users contact us where use of ROCKWOOL products is
contemplated in applications different from those explicitly described in the latest, relevant ROCKWOOL product datasheets;
especially in applications that can be reasonably foreseen as critical to safety.

ROCKWOOL Limited reserves the right to amend the specification of its products without notice. Changes to the ROCKWOOL
manufacturing process, or to pertinent regulations, may be reflected in changes to tested and certified product performance.
Whilst ROCKWOOL Limited endeavours to keep its publications up to date, readers will appreciate that between publications
there may be pertinent changes in the law or other developments affecting the accuracy of the information contained in our
publications.

ROCKWOOL Limited does not accept responsibility for the consequences of using (including testing or certifying) its products
in applications different from those explicitly described in the relevant ROCKWOOL product datasheets. Expert advice should
be sought, and ROCKWOOL Limited should be contacted, where such different use is contemplated, or where the extent of
any use described by ROCKWOOL Limited is in doubt.

The ROCKWOOL Trademark Trademarks Photography and illustrations


ROCKWOOL - our trademark
®
Registered trademarks of the The product illustrations are the property
ROCKWOOL Group include but are not of ROCKWOOL Limited and have been
The ROCKWOOL trademark was
limited to: created for indicative purposes only.
initially registered in Denmark as a
logo mark back in 1936. In 1937, it ROCKWOOL®, RockClose®, RainScreen Unless indicated below, the
was accompanied with a word mark Duo Slab®, HardRock®, RockFloor® photography and illustrations used
registration; a registration which is now Flexi®, RockFall®, FirePro®, DuctRock®, in this guide are the property of
extended to more than 60 countries BeamClad®, NyRock® ROCKWOOL Limited. We reserve all
around the world. rights to the usage of these images.
© ROCKWOOL 2023.
The ROCKWOOL trademark is one All rights reserved. If you require permission to use
of the most important assets of the ROCKWOOL images, you must apply for
ROCKWOOL Group, and is therefore a Usage Agreement.
well-protected and defended by
To apply, write to:
ROCKWOOL throughout the world.
[email protected]
If you require permission to use the
ROCKWOOL logo for your business,
advertising or promotion, you
must apply for a Trade Mark Usage
Agreement.
To apply, write to:
[email protected]

HEALTH & SAFETY


A Material Safety Data Sheet is available and can be downloaded from www.rockwool.com/uk to assist in the preparation of
risk assessments, as required by the Control of Substances Hazardous to Health Regulations (COSHH)

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
18.
FirePro Fire Barrier

ROCKWOOL stone wool -


safe to install and live alongside
There are no hazardous classifications associated with stone wool insulation manufactured by ROCKWOOL-UK
according to EU REACH and UK REACH regulations on health and the environment.
ROCKWOOL safe use instruction sheets and material safety data sheets (where applicable) can be downloaded here.

Sustainability Environment
ROCKWOOL products are used to enrich modern ROCKWOOL takes a fact-based, auditable
living, creating safer, healthier and more climate- approach to documenting our progress in
resilient communities. maximising our products’ positive impact and
minimising the effect our operations have on the
We transform abundant, natural volcanic rock into
environment, backed by third-party references
stone wool insulation products that are used to
and methodologies. Further details can be found
reduce energy demand, lower fuel bills and help
online in our annual sustainability report.
address society’s climate change challenges.
Our high-tech production process uses filters,
ROCKWOOL stone wool insulation is recyclable
pre-heaters, after-burners and other cleaning and
and can be transformed into new ROCKWOOL
collection systems that help to reduce the effects of
products. Please contact us for details of how we
our manufacturing operations on the environment.
can work together to recycle waste ROCKWOOL
stone wool material that may be generated during ROCKWOOL stone wool insulation does not
on-site installation. contain (and has never contained) gases that have
ozone depletion potential (ODP) or global warming
Our annual sustainability reports, which set out
potential (GWP).
progress against our sustainability goals, and
further details of the positive impacts of using our
products can be found on our website.

Pencoed, Bridgend CF35 6NY


For more information visit rockwool.com/uk Tel: (+44) 1656 862 621 • [email protected]
19.

You might also like