1MRK506311-SUS C en Line Distance Protection REL670 1.2 650 1.1 ANSI
1MRK506311-SUS C en Line Distance Protection REL670 1.2 650 1.1 ANSI
2
REL670 IEDs provide both customized and pre-configured rilateral and mho impedance characteristics. This enables
solutions. The pre-configured IED is capable of being used coordination with existing distance protection schemes in any
on single pole breaker, or multi-breaker arrangements with power network.
single or three-phase tripping. If needed, the pre-configured
IEDs can be adapted to meet your power system’s specific The distance protection is further enhanced with load en-
requirements. With the customized REL670 IEDs you have the croachment adaption, which increases the ability to detect
freedom to completely adapt the functionality according to high resistive faults on heavily loaded lines. This is especially
your needs. useful in sub-transmission networks where high line load
needs to be allowed while high resistive faults need to be
REL650 – your best choice for sub-transmission detected and cleared. The unique load current compensation
applications in zone one prevents overreaching during resistive faults and
REL650 offers optimum ‘off-the-shelf’, ready-made application high power transfer on the line. Furthermore, an integrated
solutions for protection of single breaker connected power lines power swing detection function prevents unwanted operation
and cables. The type tested variants are delivered equipped during power system oscillations caused by disconnection of
and configured with complete protection functionality, and with parallel lines, heavy loads or tripping of large generators.
default parameters for easy handling of products – from order-
ing, engineering and commissioning to reliable operation. Versatile overcurrent functions provide additional back-up
protection. The thermal overload protection will trip the line
The 650 series IEDs introduce a number of innovations, such at overload situations to prevent more severe fault conse-
as a significantly reduced number of parameter settings and quences.
extended IED HMI functionality including 15 dynamic three-
color-indication LEDs per page, on up to three pages, and Breaker failure protection allows high speed back-up tripping
configurable push-button shortcuts for different actions. In of surrounding breakers and re-tripping of the own breaker,
the 650 series IEDs, most basic parameters are set before for instance, to avoid operational mistakes during testing.
delivery from the factory. You only need to set the parameters This is essential in substations with high short circuit power
specific to your application. The parameters related to line infeed, which require local back-up protection. The distance
distance protection are mostly set as primary ohms, which directional ground fault overcurrent and directional negative
significantly reduce the need to re-calculate the current and sequence overcurrent functions can communicate with the
voltage values. This allows the IEDs to be quickly taken into remote end in any communication scheme.
operation. The application manual includes setting examples
to support the protection engineer. The auto-reclosing functionality increases operation security
and is an effective way to restore the network after arcing
Extensive protection for lines and cables faults. In REL670 and REL650, auto-reclosing can be made
REL670 and REL650 provide protection of power lines and using synchro-check to eliminate the risk of unwanted reclos-
cables with high sensitivity and low CT requirements. Measure- ing during unfavourable circumstances.
ments and setting of all five zones with several setting groups
are realized completely independently to ensure high reliability. In addition to the wide range of overcurrent protection func-
The distance protection function is available with both quad- tions, REL670 and REL650 provide a negative sequence
3
Designed for IEC 61850
4
Application examples
Relion® 670 series IEDs support IEC 62439 standard redun-
X
dant communications on the station bus. The solution from
ABB utilizes the IEC 62439-3 standardized Parallel Redundan-
cy Protocol (PRP). PRP improves the communication system
reliability and features a unique capability of zero seconds’
recovery time in case of communication failures. This means
that there will be no interruption in communication if one link
fails as the other link instantaneously takes over the communi-
cation. As a result, there is no data lost when communication
R
failures have occurred.
5
REL670 Technology summary:
Features Monitoring
• Fully IEC 61850 compliant • Disturbance recorder
• Control, monitoring and protection integrated in one IED - 100 disturbances
• Extensive self-supervision including analog channels - 40 analog channels 30 physical and 10 derived
• Six independent parameter setting groups - 96 binary channels
• Large HMI for visualization of single line diagrams • Event list for 1000 events
• Ethernet interface for fast and easy communication with PC • Disturbance report
• Signal matrix for easy configuration of binary and analog signals • Event and trip value recorders
• User management and authority handling • Fault locator
• Event counters
Pre-configured solutions
• Supervision of AC and mA input quantities
• Pre-configured and type-tested solutions including default settings for
• Small and large HMI in local language
ring bus or 1 1/2 circuit breaker arrangements with selective single or
• LED indications with 6 red and 9 yellow LEDs
three phase tripping.
Metering
Most important protection functions
• U, I, P, Q, S, f, and cosϕ
• Distance protection
• Differential voltage per zone
- 5 zone full-scheme high-speed line distance protection with quadri-
• AC input quantities with accuracy better than 0.5%
lateral, Mho- or series compensation characteristics, and with
• Inputs for mA measuring
scheme communication logic and load encroachment discrimination
• Energy metering function for energy statistics
- Selective phase selection and automatic switch on to fault logic
• Pulse counting support for energy metering
- Current reversal and weak end infeed logic
- Power swing detection and blocking Control functions
- Phase preference logic • Apparatus control for 8 or 15 apparatus
- Pole slip protection • Ready to use interlocking modules for different switchgear
• High impedance differential protection for tee-feeders arrangements
• Current • Several alternatives for reservation functionality
- Instantaneous phase- and residual over-current protection • Synchronizing, synchro-check and energizing check
- Four-step phase- and residual directional over-current protection • Auto-recloser
with definite and inverse time characteristics • Versatile switch with two positions
- Four-step directional negative sequence overcurrent protection • Selector switch with up to 32 positions
- Directional residual over-current protection with scheme
Communication
communication logic
• IEC 61850-8-1 including GOOSE messaging
- Sensitive directional ground fault protection
• IEC 61850-9-2 LE Process bus
- Broken conductor
• Individually supervised redundant station bus with zero seconds
- Thermal overload protection
recovery time
- Breaker failure protection
• IEC 60870-5-103
- Stub protection
• DNP 3.0 slave protocol
- Pole discordance protection
• LON
• Power functions
• SPA
- Directional under- and over power protection
• Remote end communication for transfer of 192 binary signals
• Voltage
- Two step phase- and residual over-voltage protection with definite Setting, configuration and disturbance handling
and inverse time characteristics • Protection and Control IED Manager PCM600
- Two step under-voltage protection with definite and inverse time
Hardware
characteristics
• 1/1 x 19”, 3/4 x 19” or 1/2 x 19” 6U height case selected
- Overexcitation
according
- Loss of voltage
to the number of required I/O modules
• Power system supervision
• Power supply modules from 24 to 250 V DC ± 20%
- Loss of voltage check configured based on under-voltage protection
• TRM module with measurement transformers
- Dead line detection included in fuse failure supervision and switch
• ADM module
on to fault logic
• Up to 14 I/O modules in 1/1 x 19” case
• Secondary system supervision
• Binary input module, 30 mA and 50 mA, with 16 inputs
- Fuse failure supervision
• Binary output module with 24 outputs
- Current circuit supervision
• Static binary output module with 12 outputs (6 static)
• Frequency functions
• Binary input/output module, 30 mA and 50 mA, with 8 inputs and
- Over- and under-frequency protection
12 outputs
- Rate-of-change frequency protection
• mA input module with 6 transducer channels
• Multipurpose function
• Accurate time-synchronization through GTM, GPS time module,
- General current and voltage protection
SNTP, DNP 3.0, or IRIG-B-module
Logic • Remote end data communication modules for C37.94, X21 and
• Tripping logic G.703/G.703E1
• Trip matrix logic • COMBITEST test switch module
• Configurable logic blocks
Technical details are available in the REL670 Product Guide.