1 Power System Components and Per Unit System
1 Power System Components and Per Unit System
Zaid Alhadrawi
4Th stage / Electrical Engineering Department / Kufa University
------------------------------------------------------------------------------------------------------------------------
Syllabus
Textbooks
References
1
Power System Analysis Lecturer: Dr. Zaid Alhadrawi
4Th stage / Electrical Engineering Department / Kufa University
------------------------------------------------------------------------------------------------------------------------
A single-line diagram of a power system shows the main connections and arrangements
of components. Power system networks are represented by single-line diagrams using
suitable symbols as shown in the figure below:
2
Power System Analysis Lecturer: Dr. Zaid Alhadrawi
4Th stage / Electrical Engineering Department / Kufa University
------------------------------------------------------------------------------------------------------------------------
Because of the large amount of power transmitted, kilowatts or megawatts and kilovolt-
ampere or megavolt-ampere are the common terms. However, these quantities as well
as amperes and ohms are often expressed as a percent or per unit of a base or reference
value specified for each.
In the per-unit system, all quantities are represented as a fraction of the base value:
For example
If we specify the base values of any two quantities, the base values of the remaining
two can be determined as shown in the following equations, usually, Sb and Vb are
specified.
𝑆1∅,𝐵
𝐼𝐵 =
𝑉𝐿𝑁,𝐵
𝑉𝐿𝑁,𝐵 (𝑉𝐿𝑁,𝐵 )2
𝑍𝐵 = =
𝐼𝐵 𝑆1∅,𝐵
3
Power System Analysis Lecturer: Dr. Zaid Alhadrawi
4Th stage / Electrical Engineering Department / Kufa University
------------------------------------------------------------------------------------------------------------------------
For 3 phase
𝑆3∅,𝐵
𝐼𝐵 =
√3𝑉𝐿𝐿,𝐵
𝑉𝐿𝐿,𝑏𝑎𝑠𝑒/√3 (𝑉𝐿𝐿,𝐵 )2
𝑍𝐵 = =
𝐼𝑏𝑎𝑠𝑒 𝑆3∅,𝐵
𝑉𝐵2 (20)2
𝑍𝐵 = = =8Ω
𝑆𝐵 50
𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 0.2
𝑋(𝑝. 𝑢) = = = 0.025 𝑝𝑢
𝑍𝐵 8
Example 2: A three phase transformer is rated 11/220 KV, 25 MVA with leakage
reactance measured from the low-tension side is 0.06 Ω. Determine leakage reactance
in per unit.
Solution: 𝑆𝐵 = 25 𝑀𝑉𝐴 𝑎𝑛𝑑 𝑉𝐵 = 11 𝐾𝑉
𝑉𝐵2 (11)2
𝑍𝐵 = = = 4.84 Ω
𝑆𝐵 25
𝑋 𝑎𝑐𝑡𝑢𝑎𝑙 0.06
𝑋(𝑝. 𝑢) = = = 0.0124 𝑝𝑢
𝑍𝐵 4.84
HW: Determine leakage reactance in per unit from high tension side.
4
Power System Analysis Lecturer: Dr. Zaid Alhadrawi
4Th stage / Electrical Engineering Department / Kufa University
------------------------------------------------------------------------------------------------------------------------
Changing of Base
The impedance of individual generators and transformers, as supplied by the
manufacturer, are generally in terms of percent or per-unit quantities based on their
own ratings. The impedance of transmission lines are usually expressed by their ohmic
values. For power system analysis, all impedances must be expressed in per unit on a
common system base. To accomplish this, an arbitrary base for apparent power is
selected; for example, 100 MVA. Then, the voltage bases must be selected. Once a
voltage base has been selected for a point in a system, the remaining voltage bases are
no longer independent; they are determined by the various transformer turns ratios.
𝑜𝑙𝑑
Let 𝑍𝑝.𝑢 be the per-unit impedance on the power base 𝑆𝐵𝑜𝑙𝑑 and the voltage
base 𝑉𝐵𝑜𝑙𝑑 , which is expressed by
𝑜𝑙𝑑 .𝑍 𝑜𝑙𝑑
𝑍𝑝.𝑢
𝑜𝑙𝑑 𝑜𝑙𝑑
𝑍𝑎𝑐𝑡𝑢𝑎𝑙 = 𝑍𝑝.𝑢 . 𝑍𝐵 = 𝑛𝑒𝑤
𝑍𝑝.𝑢 . 𝑍𝐵𝑛𝑒𝑤 𝑛𝑒𝑤
𝑍𝑝.𝑢 = 𝑛𝑒𝑤
𝐵
𝑍𝐵
2
𝑛𝑒𝑤 𝑜𝑙𝑑
𝑉𝐵𝑜𝑙𝑑 𝑆𝐵𝑛𝑒𝑤
𝑍𝑝.𝑢 = 𝑍𝑝.𝑢 ( 𝑜𝑙𝑑 ) ( 𝑜𝑙𝑑 )
𝑉𝐵 𝑆𝐵
Example 3: the reactance of a generator designated x" is given as 0.25 per unit based
on the generator's nameplate rating of 18 KV , 500 MVA the base for calculations is
20 K V, 100 MVA. Find x" on the new base.
Solution:
18 2 100
x"(pu)new = 0.25 ∗ ( ) ( ) = 0.0405 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡
20 500
1 T2
T1 T.L.
2
GG1 M
G1
110
𝑉𝑏𝑎𝑠𝑒,2 = 𝑉𝑏𝑎𝑠𝑒,1 = 110 𝐾𝑉 𝑅𝑒𝑔𝑖𝑜𝑛 2
13.8
13.8
𝑉𝑏𝑎𝑠𝑒,3 = 𝑉𝑏𝑎𝑠𝑒,2 = 13.8 𝐾𝑉 𝑅𝑒𝑔𝑖𝑜𝑛 3
110
2
𝑉𝐿𝐿,𝑏𝑎𝑠𝑒 1 (13.8 𝐾𝑉)2
𝑍𝑏𝑎𝑠𝑒,1 = = = 1.904 Ω 𝑅𝑒𝑔𝑖𝑜𝑛 1
𝑆3∅,𝑏𝑎𝑠𝑒 100 𝑀𝑉𝐴
2
𝑉𝐿𝐿,𝑏𝑎𝑠𝑒2 (110 𝐾𝑉)2
𝑍𝑏𝑎𝑠𝑒,2 = = = 121 Ω 𝑅𝑒𝑔𝑖𝑜𝑛 2
𝑆3∅,𝑏𝑎𝑠𝑒 100 𝑀𝑉𝐴
2
𝑉𝐿𝐿,𝑏𝑎𝑠𝑒3 (13.8 𝐾𝑉)2
𝑍𝑏𝑎𝑠𝑒,3 = = = 1.904 Ω 𝑅𝑒𝑔𝑖𝑜𝑛 3
𝑆3∅,𝑏𝑎𝑠𝑒 100 𝑀𝑉𝐴
The impedances of G1 and T1 are specified per per-unit on a base of 13.8 kV and 100
MVA, which is the same as the system base in Region 1.
15
𝑅𝑙𝑖𝑛𝑒 = = 0.124 𝑝𝑢
121
75
𝑋𝑙𝑖𝑛𝑒 = = 0.62 𝑝𝑢
121
The impedance of T2
𝑜𝑙𝑑 2
𝑛𝑒𝑤 𝑜𝑙𝑑
𝑉𝑏𝑎𝑠𝑒 𝑆𝑛𝑒𝑤
𝑍𝑝.𝑢 = 𝑍𝑝.𝑢 ( 𝑜𝑙𝑑 ) ( )
𝑉𝑛𝑒𝑤 𝑆𝑜𝑙𝑑
𝑛𝑒𝑤
13.8 2 100
𝑅𝑝.𝑢 = 0.01 ( ) ( ) = 0.02 𝑝𝑢
13.8 50
𝑛𝑒𝑤
13.8 2 100
𝑋𝑝.𝑢 = 0.05 ( ) ( ) = 0.1 𝑝𝑢
13.8 50
7
Power System Analysis Lecturer: Dr. Zaid Alhadrawi
4Th stage / Electrical Engineering Department / Kufa University
------------------------------------------------------------------------------------------------------------------------
𝑛𝑒𝑤
13.8 2 100
𝑅𝑝.𝑢 = 0.1 ( ) ( ) = 0.2 𝑝𝑢
13.8 50
𝑛𝑒𝑤
13.8 2 100
𝑋𝑝.𝑢 = 1.1 ( ) ( ) = 2.2 𝑝𝑢
13.8 50
SOLVED PROBLEMS
HOMEWORKS