RFA - SD 028 RevB 11kV 400V Substation Single Line Diagram

Uploaded by

phamvietminh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Marks

Status Indication THIS DRAWING IS THE COPYRIGHT OF


Fault Indication
TAISEI CORPORATION AND MUST NOT
BE COPIED OR USED WITHOUT
Measuring
TAISEI CORPORATION PERMISSION.
Termination Work shall be out of scope Watt Hour
OUT OF SCOPE NOTES:
Existing Power Station
*Transferred to BMS (Mechanical Work).
1 11kV 3φ 3W
SCOPE OF WORK 3 4 EVT×3 B Generator for emergency Generator for emergency B
11000 110 190 1040kVA(Prime) 1040kVA(Prime)
PF×3 3 11000V 11000V
3 3
Synchronising Function: Buit-in Synchronising Function: Buit-in

G G
Main Station (External)
89R 89R
DS
36kV 600A
DS
36kV 600A
52S2
VCB
52S2
VCB
52S2
VCB
Earth Terminal Board
11kV 600A 11kV 600A 11kV 600A
RC 25kA RC 25kA RC 25kA
From
V,A,W,Wh,PF Energy Center 1F
Tr
CTT Multi Transformer Room
HV N/P 1F Generator Room DB-2 DB-2
52R 52R CTx3 Meter
LV ⑩

70sq
VCB VCB
36kV 600A 36kV 600A V,A,W,Wh,PF V,A,W,Wh,PF
RC 25kA RC 25kA CTT CTT Multi
CTT Multi
OCGR
CTx3
23 CTx3 Meter
24 CTx3 Meter

CTT CTT
CTx3 OVGR CTx3 OVGR

CT×3 CT×3
(Temp Alarm)
TIE TR
Cable size???

200sq
5000kVA

6sq

6sq
11kV/11kV 5 52G1 52G2

Auto Tap Changer


89R2
DS
DB-1 VCB
11kV 630A
VCB
11kV 630A
2 11kV E(TrN) E tp E tc
RC 25kA RC 25kA
600A <2Ω
VCT VCT RC 25kA
LAx3
To ET Panel 12kV VT x3 MCB
VTT VS
⑩ 10kA 4P10A
V

Inter Lock
12000/110V 0-15000V
U U
UVR-A1 OVR-A1


52R2
VCB
DB-1
11kV 630A
RC 25kA
Inter Lock

Omit Ampare Meter


Cable size???
CTT due to duplication.
CT x2 Multi
Meter V,A,W,Wh,PF
500/5A
25KA
B B
OCR
0.125sec CTT RFI 212 Question No.96
APFC NO. DESCRIPTION OF REVISION REV DATE
CT x2
VCB Panel No.19 has been omitted.
1 For Approval A 11.Dec.2019
1F Transformer Room
Inter Lock VCB rated current, Generator Capacity has been revised.
Ampare meter in No.6 has been omitted.
2 B 08.Feb.2020
Change Transformer Capacity of No. 25 and 39.
Omit HV Feeder Panel of No. 13 and 19.

DB-1 DB-1 DB-1 DB-1 DB-1 DB-2 DB-2 DB-2 DB-2 DB-2 DB-2
B 52BG
21 22
Additional Bus Bar 7 8 9 10 14 15 16 17 18 20 VCB
52B 52FG1 52FG2 52FG3 52FG4 11kV 630A
for Future Extension 52F1
VCB
52F2
VCB
52F3
VCB
52F4
VCB
52FG6
RC 25kA
VCB VCB VCB VCB VCB VCB
11kV 630A 11kV 630A 11kV 630A 11kV 630A 11kV 630A 11kV 630A 11kV 630A 11kV 630A 11kV 630A 11kV 630A
RC 25kA RC 25kA RC 25kA RC 25kA RC 25kA RC 25kA RC 25kA RC 25kA RC 25kA RC 25kA
EVT×3
(OFF with Fire Signal) (OFF with Fire Signal) (OFF with Fire Signal) (OFF with Fire Signal)
11000 110 190
V,A,W,Wh,PF V,A V,A,W,Wh,PF V,A,W,Wh,PF V,A,W,Wh,PF V,A,W,Wh,PF V,A,W,Wh,PF V,A,W,Wh,PF V,A,W,Wh,PF 3 3 3
CTT CTT CTT CTT CTT CTT CTT CTT CTT PF×3
Multi Multi Multi Multi Multi Multi Multi Multi Multi
CTx2 Meter CTx2 Meter CTx3 Meter CTx3 Meter CTx3 Meter CTx3 Meter CTx3 Meter CTx3 Meter CTx2 Meter

CTT CTT CTT CTT CTT CTT CTT CTT CTT


CTx2 CTx2 CTx3 OCGR CTx3 OCGR CTx3 OCGR CTx3 OCGR CTx3 OCGR CTx3 OCGR CTx2

Project:

Cable size??? B New Yangon Specialist Hospital


29 GF~2F 41 3F~6F 35 37 39 GF~2F 43 3F~6F Additional Bus Bar for Future Extension The Corner of Min Ye' Kyaw Swar Road And
DB-3 (Temp Alarm) For Medical Use For Medical Use DB-3 (Temp Alarm)
For General Use For General Use For General Use For General Use Pyay Road,Yangon Division
GC GC 3φ4WTR
3φ4WTR
B (500kVA) (500kVA) GC GC 300kVA
1500kVA B (750kVA) (750kVA)
25 R11000V/415V/240V RFI 212 Question No.93 (750kVA) (300kVA) 27 R11000V/415V/240V

Manual Tap Changer


RFI 212 Question No.95 Manual Tap Changer
Consultant:
Dry Type
Change Transformer Capacity from 750kVA to 1500kVA VCB Panel No.11 has been omitted. B Dry Type

RFI 212 Question No.96 RFI 212 Question No.94


CTT
B
VCB Panel No.13 has been omitted. Change Transformer Capacity
from 300kVA to 750kVA
CTT
YAMASHITA SEKKEI INC.
ZCT
RFI 198 Question 90 ZCT ARCHITECTS, ENGINEERS & CONSULTANTS

To ET Panel LBS can be omitted because there is VCB. To ET Panel


① ①

DB-3 EFx3 DB-3 EFx3


(5A)
(5A) CTx2
CTx2
26 2500A/5A Multi 28
400A/5A Multi
Contractor:
Meter
V,A,W,Wh To 1F Transformer Room Meter
V,A,W,Wh
1F Electrical
Common Alarm
Common Alarm
Over Demand To
Room Earth Terminal Board Over Demand Shunt Trip with Fire Signal
Breaker Trip Breaker Trip
Leakage Main Station Leakage
Tr Tr
(External)
HV N/P N/P Ge Ge The Tokyo Enterprise Building,
100sq

LV SPD ① ② N/P N/P


70sq

100sq No.32 , Pyay Road, 6 1/2 miles,

100sq
Hlaing Township ,Yangon ,Myanmar
PF C 7.5A PF C 7.5A PF C 7.5A PF C 7.5A Tel: (95)1 654838 , 514862 , 527103

kVA

kVA

kVA

kVA

kVA

kVA
40kA 40kA 40kA 40kA
kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

30.0

11.0
Sub Contractor:
50.0

3.25

3.7

2.9
VMC 400A VMC 400A VMC 400A VMC 400A
118

8.1

130

130

130

130

130

130


SR SR SR SR Yurtec Corporation

225 AF 125 AT

100 AF 75 AT

50 AF 30 AT

50 AF 20 AT

SPARE 225 AF 225 AT

SPARE 225 AF 225 AT


400 AF 300 AT

50 AF 30 AT

400 AF 300 AT

400 AF 300 AT

400 AF 300 AT

400 AF 300 AT

400 AF 300 AT

400 AF 300 AT

225 AF 125 AT

50 AF 30 AT

SPARE 225 AF 225 AT

SPARE 225 AF 225 AT

L=6% L=6% L=6% L=6% Myanmar Office


I5=55% I5=55% I5=55% I5=55%
100sq

100sq

Jockey Pump
14sq

35sq

35sq

6sq

6sq

SC

Fire Pump

Fire Pump
SC SC SC
500kvar 500kvar 300kvar 200kvar

E(ACD) E(LA) E(TrN) E(TrN) E(GeN) E tp E tc

GEP1

GEP2

GEP3

GL31
<2Ω <10Ω <2Ω <2Ω <2Ω
Drawing title:
EP1

EP2

EP3

EP4

EP5

EP6

EP7

EP8

EP9

L31

B
EB has been omitted.
11kV 400V Substation
Single Line Diagram (1)
Scale Drawn Checked Approved Size
N/S A1
N/S Date: 08 Feb 2020 Date: Date:
A3
Drawing Number Rev
TC-NYSH-SD-E-SL-001 B
52F3 52FG1

1F Electrical Room DB-5 DB-4


29 35 THIS DRAWING IS THE COPYRIGHT OF
(Temp Alarm) (Temp Alarm) TAISEI CORPORATION AND MUST NOT
3φ4WTR 3φ4WTR BE COPIED OR USED WITHOUT
TAISEI CORPORATION PERMISSION.
500kVA 750kVA
R11000V/415V/240V R11000V/415V/240V
Manual Tap Changer Manual Tap Changer
Dry Type Dry Type
NOTES:
Common Alarm
EFx3 Over Demand
CTT CTT
30 Breaker Trip
Leakage 36
Common Alarm MCB4P
(5A)
ZCT Over Demand 50/20AT ZCT
EFx3 x9set
Breaker Trip Multi
Leakage CTx2 V,A,W,Wh
To ET Panel SPDx4 To ET Panel Meter
(5A) MCCB3P1250/1000AT 1500A/5A
① ③
Multi V,A,W,Wh
CTx2 Meter
750A/5A
B
RFI 212 Question No.95
Transformer No.31 and MSB No. 32 have been omitted.
and Load shall be transferred to MSB No. 38.

SPD SPD SPD SPD SPD SPD SPD SPD SPD

131.8

37.37

35.70

26.47

20.78

20.12

32.55

10.98

37.28

12.08

12.08

12.08

12.08
kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA
633.477
KW

KW

KW

KW

KW

KW

KW

KW

KW

KW

KW
37.1

37.1

51.2

63.0

63.0

10.2

741.48
7.4

6.0

6.0

1.4

1.9

9.6

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

100

100

100

5.2

1.5

1.5

1.5
50

50

75

75

75
AT

AT

AT

AT

AT

400AF 300 AT

225AF 125 AT

225AF 125 AT

225AF 175 AT

225AF 200 AT

225AF 200 AT

225AF 150 AT

225AF 150 AT

AT

100AF 100 AT

100AF 100 AT

100AF 100 AT

225AF 125 AT

AT

AT

AT

AT

AT

AT

AT

AT

AT

1HGP1 400AF 250 AT

1HGP2 225AF 125 AT

1HGP3 225AF 125 AT

1HGP4 400AF 250 AT

1HGP5 400AF 250 AT

1HGP6 225AF 175 AT

1HGP7 225AF 175 AT

1HGP8 225AF 175 AT

50 AF 50 AT

50 AF 50 AT

225AF 150 AT

50 AF 30 AT

100AF 75 AT

100AF 75 AT

100AF 75 AT

100AF 75 AT

50 AF 20 AT

EGL10 50 AF 20 AT

EGL11 50 AF 20 AT
50 AF 30

50 AF 30

50 AF 30

50 AF 20

50 AF 20

50 AF 50

50 AF 30

50 AF 30

50 AF 30

50 AF 30

50 AF 30

50 AF 30

50 AF 30

50 AF 30
50 AF 30

TOTAL

TOTAL
1P10

1P11

EGL1

EGL2

EGL3

EGL4

EGL5

EGL6

EGL7

EGL8

EGL9
1P1

1P2

1P3

1P4

1P5

1P6

1P7

1P8

1P9

L11

L12

L13

L14

L15

L16

L17

L18

L19

L20

L21

L22

L23

L24

L25

L26
52FG2 52FG3

DB-4 DB-5 B
37 RFI 212 Question No.94 39
(Temp Alarm) (Temp Alarm) Change Transformer Capacity
from 300kVA to 750kVA
3φ4WTR 3φ4WTR
750kVA 750kVA
R11000V/415V/240V R11000V/415V/240V
Manual Tap Changer Manual Tap Changer
Dry Type Dry Type

EFx3 EFx3

CTT CTT To
(5A) 38 (5A) 40 RF Electrical Earth Terminal Board
ZCT Multi V,A,W,Wh ZCT Multi V,A,W,Wh Room
Meter Meter MCB4P From 1F Tr 1F Tr 1F Tr 1F Tr 1F Tr RF Tr RF Tr
MCCB3P1250/1000AT
CTx2 CTx2 50/20AT
x9set Energy Center HV
NO. DESCRIPTION OF REVISION REV DATE
To ET Panel To ET Panel N/P N/P N/P N/P N/P N/P N/P
④ 1500A/5A 1500A/5A LV SPD
Common Alarm ⑤ Common Alarm
SPDx4
1F Transformer Room ① ② ③ ④ ⑤ ⑥ ⑦ 1 For Approval A 11.Dec.2019
Over Demand Over Demand

100sq

100sq
Breaker Trip Breaker Trip AVR Line has been changed from Panel No.40 to No.36
Leakage Leakage due to mistake.
2 B 08.Feb.2020
Change Transformer Capacity of No. 25 and 39.
Omit HV Feeder Panel of No. 11, 13 and 19.

SPD

14sq

35sq

35sq

35sq

35sq

35sq

35sq

35sq

6sq

6sq
19.03

30.61

21.39

26.31

33.43
kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA
220.36
75.0

75.0

15.0

15.0

15.0

15.0

15.0

15.0

60.0

48.0

48.0

48.0

48.0

17.1
KW

KW

KW

KW

KW

KW

KW

10.0
KW

4.29

16.3
150

7.5

7.5

7.5

7.5

7.5

7.5

387

2.3

2.3

7.4

5.2

6.7

3.0

5.0

5.0

5.0
E(LA) E(TrN) E(TrN) E(TrN) E(TrN) E(TrN) E(TrN) E(TrN) E tp E tc
225 AF 175 AT

225 AF 175 AT

AT

AT

AT

AT

AT

AT

AT

AT

AT

AT

AT

AT

225 AF 225 AT

225 AF 175 AT

225 AF 175 AT

225 AF 175 AT

225 AF 175 AT

50 AF 50 AT

50 AF 20 AT

50 AF 20 AT

50 AF 30 AT

50 AF 30 AT

50 AF 30 AT

50 AF 20 AT

50 AF 30 AT

100AF 75 AT

225AF 125 AT

50 AF 30 AT

100AF 75 AT

100AF 75 AT

100AF 75 AT

225AF 125 AT

50 AF 30 AT

50 AF 30 AT

50 AF 30 AT
<10Ω <2Ω <2Ω <2Ω <2Ω <2Ω <2Ω <2Ω
50 AF 30

50 AF 30

50 AF 30

2HGP10 50 AF 30

2HGP11 50 AF 30

100 AF 75

100 AF 75

100 AF 75

100 AF 75

100 AF 75

100 AF 75
50 AF 30

B
AVR EB has been omitted.
2HGP4

2HGP5

TOTAL

2HGP6

2HGP7

2HGP8

2HGP9

EGL21

EGL22

EGL23

EGL24

EGL25

EGL26

EGL27

EGL28

EGL29

EGL30

EGL31

TOTAL

TOTAL
1GP1

1GP2

1GP3

1GP4

1GP5

1GP6

1GP7

1GP8

GL10
GL1

GL2

GL3

GL4

GL5

GL6

GL7

GL8

GL9
AVR
750kVA
C
Project:
Please let us know whether fault alarm to BMS
is necessary or not
New Yangon Specialist Hospital
C
The Corner of Min Ye' Kyaw Swar Road And
RFI 198 Question 61
Pyay Road,Yangon Division
Main Feeder for ANGIO 1~3 have been omitted.

52F4 52FG4
Consultant:
GF Electrical Room RF Electrical Room
DB-6 DB-6
41 43
(Temp Alarm) (Temp Alarm) YAMASHITA SEKKEI INC.
3φ4WTR 3φ4WTR ARCHITECTS, ENGINEERS & CONSULTANTS
500kVA 300kVA
R11000V/415V/240V R11000V/415V/240V
Manual Tap Changer Manual Tap Changer
Dry Type Dry Type

CTT
Common Alarm
CTT
Common Alarm
Contractor:
ZCT EFx3
Over Demand 42 ZCT EFx3
Over Demand 44
Breaker Trip Breaker Trip
Leakage Leakage
To 1F ET Panel (5A) To 1F ET Panel (5A)
⑥ ⑦
CTx2
Multi V,A,W,Wh Multi V,A,W,Wh The Tokyo Enterprise Building,
Meter Meter
750A/5A 400A/5A No.32 , Pyay Road, 6 1/2 miles,
MCCB4P800/700ATx4 Hlaing Township ,Yangon ,Myanmar
Tel: (95)1 654838 , 514862 , 527103

Sub Contractor:
Battery Yurtec Corporation
UPS Myanmar Office
Bank
170.5

108.7

46.17
kVA

17.07
kVA

46.17
kVA

17.07
kVA

46.17
kVA

17.07
kVA

46.17
kVA

17.07
kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA

kVA
kVA

kVA
578.737
KW

14.8
KW

14.8
KW

14.8
KW

KW

2.20

KW

KW

KW

KW

KW

KW

7.45

7.58

7.45

7.58

7.45

7.58

7.45

7.58
3.7

5.0

5.0

5.0

5.0

5.0

0.1

88.92
AVR
MCCB2P 1250/1000AT UPS
400 AF 400 AT

50 AF 50 AT

50 AF 50 AT

50 AF 50 AT

400 AF 250 AT

225 AF 175 AT

100 AF 75 AT

225 AF 175 AT

100 AF 75 AT

225 AF 175 AT

100 AF 75 AT

225 AF 175 AT

100 AF 75 AT

50 AF 20 AT

50 AF 20 AT

50 AF 50 AT

50 AF 50 AT

50 AF 50 AT

50 AF 50 AT

50 AF 50 AT

50 AF 30 AT

50 AF 30 AT

50 AF 30 AT

50 AF 30 AT

50 AF 30 AT

50 AF 30 AT

50 AF 30 AT

50 AF 30 AT

50 AF 20 AT
400kVA
AVR Drawing title:
750kVA

C 11kV 400V Substation


TOTAL

TOTAL
2GP1

2GP2

2GP3

2GP4

2GP5

2GP6

GL21

GL22

GL23

GL24

GL25

GL26

GL27

GL28

GL29
Please let us know whether fault alarm to BMS is necessary or not
2P1

2P2

2P3

2P4

2P5

L21

L22

L23

L24

L25

L26

L27

L28

L29

Single Line Diagram (2)


Scale Drawn Checked Approved Size
N/S A1
N/S Date:08 Feb 2020 Date: Date:
A3
Drawing Number Rev
TC-NYSH-SD-E-SL-002 B