BDCBB/BDFB with

Smartpack2 Touch
The Eltek BDCBB/BDFB can be equipped as a single bus bay or
offer up to six load busses – depending upon the desired
configuration. The bay is designed to provide 800 amps per feed
at –48V, and has a maximum total current capacity of 4800
amps.

Minipack 1.6kW System with DC distribution


with loadbreakers and controller

BDCBB/BDFB
–48 VDC Power Distribution Bay
Doc 2102146, Issue 4

BENEFITS PRODUCT DESCRIPTION KEY FEATURES


CONFIGURATION • The distribution bay is equipped with • ADVANCED-FUNCTION SMARTPACK2
TOUCH CONTROLLER
The BDFB can be configured with up to six the industry-leading Smartpack2
• CABLE MANAGEMENT PACKAGE
load busses and utilizes TPS/TLS fuses to Touch controller, which displays
• OPTIONAL ALARM BATTERY SUPPLY
125 amps and or plug-in breakers up to system load voltage and current on
(ABS) CIRCUIT
250 amps. each bus. In addition to standard
• FUSE AND/OR CIRCUIT BREAKER
alarms, the controller’s extensive DISTRIBUTION:
CAPACITY programing capabilities allow for • UPGRADEABLE IN THE FIELD
At 800A per feed at -48V, it offers a total custom alarm threshold values, alarm • 15” DEEP, 7’ TALL WITH OPTIONAL 2’
current capacity of 4800A. grouping and more through both EXTENSIONS
remote and local access. • 26” AND 34”-WIDE BAY OPTIONS
ABS CIRCUIT • EITHER TWO, FOUR, OR SIX 800 AMP
• The bay can be ordered either with or A/B INPUT FEEDS, EACH EQUIPPED
Optional Alarm Battery Supply (ABS), without an internal ground bus WITH 1000 AMP SHUNTS
which allows for continued alarm and assembly. Optional external ground • TWO 750 KCMIL TERMINATIONS PER
controller access in the event of power bars are also available. It is designed FEED
loss. for top- or bottom-feed cabling. • OPTIONAL INCREASE TO FOUR 750
KCMIL TERMINATIONS PER FEED
ACCESS AND CONTROL • Each bay includes a standard cable • AUDIBLE ALARM WITH USER-
The Smartpack2 Touch controller offers management package. CONFIGURABLE ON/OFF FEATURE
remote and local access to system data, • REMOVABLE SIDE PANELS
• Optional rear-facing DC load cabling
programmable settings, and alarming and • NEBS LEVEL 3; CSA/VDE 60950-1, 2ND
available. EDITION
monitoring features.

Eltek— 2925 E Plano Pkwy, Plano, TX 75034, USA Phone: 469-330-9100 Eltek © 2019 – www.eltek.com 1(2)
BDCBB/BDFB
Doc 2102146 – rev 4

DISTRIBUTION BAY
ENVIRONMENTAL
Operating Temperature −5°C to 30°C
Storage Temperature −40°C to 70°C
Safety Compliance EN/UL 60950-1, 2nd Edition
NEBS Compliance Level 3
EMC GR-1089; Environmental GR- 63
Earthquake Rating Zone 4
GENERAL
Dimensions (D x H x W) 15” x 84” x 26” / 34” (two width options)
Maximum Weight (approx.) 375 lbs. (26” bay) / 415 lbs. (34” bay), fully loaded
CAPACITY
Total Capacity Six Panels, 144 positions (72 per A/B load)
Distribution Breakers or fuses
CABLING
Maximum Input Cable Size Two 750 kcmil per feed (option of four terminations per feed)
Input Lug Specs Two-hole 3/8” on 1” centers
One-pole breakers: Two-hole 1/4” on 5/8” centers (one-pole breakers)
Output Lug Specs
Two- and three-pole breaker adapters: Two-hole 3/8” on 1” centers

SMARTPACK 2 TOUCH CONTROLLER

Load History and Statistics Energy Logging


• Average and peak values of all monitors
Both total and individual energy consumption are logged
SD Card Slot Monitoring
• Stores event log, data log and energy log Individual load panels have both voltage and current monitored
• Backup configuration and setup Load alarm monitoring
• Upload firmware to control system Load descriptions are configurable

Multiple Communication Ports Additional Features


• Ethernet port (10/100BASE-T) for permanent LAN connection Large, full-color screen
(side port; auto-MDI/MDIX – detects the type of cable connected User-friendly touchpad navigation
and configures the port accordingly) Status messages clearly displayed
• Additional front Ethernet port for addressing controller SNMP Traps
• Front USB host port (2.0) for addressing controller Supports Eltek CAN nodes, including alarm, battery, and load monitors
• Side USB (2.0) host port
• Com port (RS-232 and RX-485, Modbus)
• 3-pin terminal block (for CAN communication with third-party
equipment)

Doc 2102146 – rev 4 Specifications are subject to change without notice