MiCOM C264 & DS Agile GTW
TBUS Configuration
DS Agile Training Level 2
Global Systems Engineering
03/05/2012
GRID
GSE
SAM
Summary
1) MiCOM C264 TBUS Page 3
2) DS Agile GTW TBUS Page 17
3) Taking Control Page 29
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 2
1.1) Reminder (1)
1) Reminder
Limits
up to 4 communication lnks (LBUS+TBUS serial or ethernet)
up to 4 LBUS
up to 2 TBUS
Connections
BIU port 1 => RS232/RS485 Jumpers on BIU board
BIU port 2 => RS232/RS485/RS422
CPU port 3 => RS232 ECU200 => Fiber Optics
CPU port 4 => RS232 ECU201 => RS485/RS422
Ethernet port
Supported Protocols
Serial => T101, DNP3, MODBUS
Ethernet => T104, DNP3, MODBUS GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 3
1.2) Add / Configure a SCADA Protocol (1)
1) TBUS protocol is added at C264 level.
2) C264 SCADA protocol attributes : General tab
Protocol :
Redundancy management :
T101 only
redundant port active when :
- GI received
- Reset Link received
- hot redundancy
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 4
1.2) Add / Configure a SCADA Protocol (2)
3) C264 SCADA protocol attributes : Protocol tab (1)
=> Customer SCADA addressing, data class & structure, ...
T101 attributes :
- link address value coding structure
- ASDU common @ value and coding structure
- data address coding structure
- period for cyclic MV
- time size
- background scan
- type of link (balanced / unbalanced)
- SBO timeout
- ...
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 5
1.2) Add / Configure a SCADA Protocol (3)
DNP3 attributes :
- TCP/IP usage : serial or ethernet
- link address value
- SPS/DPS Class, MV Class, Counter Class
- MV Format MV
- SBO timeout
- ...
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 6
1.2) Add / Configure a SCADA Protocol (4)
T104 attributes :
- ASDU common @ value and coding structure
- data address coding structure
- period for cyclic MV
- time size
- background scan
- multi T104 client addresses
- SBO timeout
- ...
Modbus attributes :
- TCP/IP usage : serial or ethernet
- link address value
- ...
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 7
1.2) Add / Configure a SCADA Protocol (5)
4) Connect C264 SCADA to serial port (for serial protocol)
Relation “has for main comm port”
Note : possibility to add a redundant
communication port
5) Configure C264 serial port
Communication parameters
Note that COM3 and COM4 should have same
transmission speed
For COM3 and COM4 => Tx carrier
management set to Switched
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 8
1.2) Add / Configure a SCADA Protocol (6)
6) Connect C264 SCADA protocol System Info
Redundancy SPS :
Gives port redundancy status
SCADA SPS Com :
Gives connection status between C264 and
SCADA
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 9
1.3) Add / Configure a SCADA Mapping (1)
1) C264 SCADA protocol
SCADA Mapping :
set of SPS, DPS, MPS, MV, SPC, DPC, … sent to SCADA
To add a DP address :
1) select kind of DP Mapping
2) Through Objects Entry Window, add an address
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 10
1.3) Add / Configure a SCADA Mapping (2)
2) Configure DP addresses (example given with T101)
2.1) SPS address
SPS address :
address value, event (Yes with timetag, No), Event
Record, Background Scan, ...
2.2) DPS address
DPS address :
address value, event (Yes with timetag, No), Event
Record, Background Scan, ...
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 11
1.3) Add / Configure a SCADA Mapping (3)
2) Configure DP addresses (example given with T101)
2.3) SPC address
SPC address :
address value, control type (DE/SBO)
2.4) DPC address
DPC address :
address value, control type (DE/SBO)
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 12
1.3) Add / Configure a SCADA Mapping (4)
2) Configure DP addresses (example given with T101)
2.3) MV address
MV address :
address value, event (Yes with timetag, No), event record
Format
Cycle type
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 13
1.3) Add / Configure SCADA Mapping (5)
3) Link DP with the relevant address (example given with T101)
=> Relation “has for SCADA address”
Under datapoint :
DP link with relevant SCADA address
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 14
1.4) Ethernet routing for SCADA
T104, DNP3 over IP, MODBUS over IP frames can be sent through routers
Under Scs / Computer Routing tab
Gateway TCP/IP address :
Router port address
Target TCP/IP address :
SCADA sub-network address
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 15
Summary
1) MiCOM C264 TBUS Page 3
2) DS Agile GTW TBUS Page 17
3) Taking Control Page 29
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 16
2.1) Reminder (1)
1) Reminder
Limits
up to 4 TBUS
redundant link possibility => 8 serial ports
Connections
8 RS232 serial ports
possibility of extra ethernet board for ethernet TBUS
Supported Protocols
Serial => T101, DNP3, MODBUS
Ethernet => T104, OPC (to come IEC61850)
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 17
2.2) Add / Configure a SCADA Protocol (1)
1) TBUS protocol is added at GTW level.
Usual Protocol :
Serial T101, DNP3, MODBUS
Ethernet T104
2) SCADA protocol attributes : General tab
Protocol
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 18
2.2) Add / Configure a SCADA Protocol (2)
3) SCADA protocol attributes : Protocol tab (1)
=> Customer SCADA addressing, data class & structure, ...
T101 attributes :
- link address value coding structure
- ASDU common @ value and coding structure
- data address coding structure
- period for cyclic MV
- time size
- background scan
- type of link (balanced / unbalanced)
- ...
DNP3 attributes :
- link address value
- SPS/DPS Class, MV Class, Counter Class
- MV Format MV
- ...
Note : Interlock Protocol Yes if Take Control used
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 19
2.2) Add / Configure a SCADA Protocol (3)
3) SCADA protocol attributes : Protocol tab (2)
=> Customer SCADA addressing, data class & structure, ...
T104 attributes :
- ethernet board IP @
- ASDU common @ value and coding structure
- data address coding structure
- period for cyclic MV
- time size
- background scan
- ...
Modbus attributes :
- link address value
- ...
Note : Interlock Protocol Yes if Take Control used
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 20
2.2) Add / Configure a SCADA Protocol (4)
4) Connect SCADA to serial port (for serial protocol)
Relation “has for main comm port”
Note : possibility to add a redundant
communication port
5) Configure GTW serial port
Communication parameters :
protocol type (Usual Protocol / GI74)
baud rate
plug number = com. port number
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 21
2.2) Add / Configure a SCADA Protocol (5)
6) Connect C264 SCADA protocol System Info
Redundancy SPS :
Gives port redundancy status
SCADA SPS Com :
Gives connection status between GTW and
SCADA
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 22
2.3) Add / Configure a SCADA Mapping (1)
1) SCADA protocol
SCADA Mapping :
set of SPS, DPS, MPS, MV, SPC, DPC, … sent to SCADA
To add a DP address :
1) select kind of DP Mapping
2) Through Objects Entry Window, add an address
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 23
2.3) Add / Configure a SCADA Mapping (2)
2) Configure DP addresses (example given with T101)
2.1) SPS address
SPS address :
address value, event (Yes with timetag, Yes without
timetag, No), Event Record, Background Scan, ...
2.2) DPS address
DPS address :
address value, event (Yes with timetag, Yes without
timetag, No), Event Record, Background Scan, ...
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 24
2.3) Add / Configure a SCADA Mapping (3)
2) Configure DP addresses (example given with T101)
2.3) SPC address
SPC address :
address value, control type (DE/SBO), SBO timeout
2.4) DPC address
DPC address :
address value, control type (DE/SBO), SBO timeout
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 25
2.3) Add / Configure a SCADA Mapping (4)
2) Configure DP addresses (example given with T101)
2.3) MV address
MV address :
address value, event (Yes with timetag, Yes without
timetag, No), event record
Format
Cycle type
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 26
2.3) Add / Configure SCADA Mapping (5)
3) Link DP with the relevant address (example given with T101)
=> Relation “has for SCADA address”
Under datapoint :
DP link with relevant SCADA address
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 27
Summary
1) MiCOM C264 TBUS Page 3
2) DS Agile GTW TBUS Page 17
3) Taking Control Page 29
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 28
3.1) Definition
1) Taking Control / Taking Status
Definition
when several SCADA => only 1 can control the SS at one time
which one ? The one with Taking Status active
How to take control
SCADA sends a Taking Control Order and Taking Status is
transferred from previous one to new one
On DS Agile GTW HMI :
Top Left
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 29
3.2) Add / Configure a Taking Control
1) Taking Control SPC and Taking Status SPS are added at Substation level.
2 Typed Taking Control SPC :
- feedback with relevant Taking Status SPS
- SCADA @ on their own SCADA Protocol
2 Typed Taking Status SPS :
- relation “is taken control of” with relevant protocol
- SCADA @ on all SCADA Protocols
Note : These information are computed by the MiCOM C264 default server of substation
data. Up to 4 taking controls
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 30
www.alstom.com
GRID
GSE