MiCOM C264 & DS Agile GTW

TBUS Configuration
DS Agile Training Level 2
Global Systems Engineering
03/05/2012

GRID

GSE
SAM
Summary

1) MiCOM C264 TBUS Page 3

2) DS Agile GTW TBUS Page 17

3) Taking Control Page 29

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 2
1.1) Reminder (1)

1) Reminder
Limits
up to 4 communication lnks (LBUS+TBUS serial or ethernet)
up to 4 LBUS
up to 2 TBUS
Connections
BIU port 1 => RS232/RS485 Jumpers on BIU board
BIU port 2 => RS232/RS485/RS422

CPU port 3 => RS232 ECU200 => Fiber Optics


CPU port 4 => RS232 ECU201 => RS485/RS422

Ethernet port
Supported Protocols
Serial => T101, DNP3, MODBUS
Ethernet => T104, DNP3, MODBUS GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 3
1.2) Add / Configure a SCADA Protocol (1)

1) TBUS protocol is added at C264 level.

2) C264 SCADA protocol attributes : General tab

Protocol :

Redundancy management :
T101 only
redundant port active when :
- GI received
- Reset Link received
- hot redundancy

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 4
1.2) Add / Configure a SCADA Protocol (2)

3) C264 SCADA protocol attributes : Protocol tab (1)


=> Customer SCADA addressing, data class & structure, ...

T101 attributes :
- link address value coding structure
- ASDU common @ value and coding structure
- data address coding structure
- period for cyclic MV
- time size
- background scan
- type of link (balanced / unbalanced)
- SBO timeout
- ...

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 5
1.2) Add / Configure a SCADA Protocol (3)

DNP3 attributes :
- TCP/IP usage : serial or ethernet
- link address value
- SPS/DPS Class, MV Class, Counter Class
- MV Format MV
- SBO timeout
- ...

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 6
1.2) Add / Configure a SCADA Protocol (4)

T104 attributes :
- ASDU common @ value and coding structure
- data address coding structure
- period for cyclic MV
- time size
- background scan
- multi T104 client addresses
- SBO timeout
- ...

Modbus attributes :
- TCP/IP usage : serial or ethernet
- link address value
- ...

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 7
1.2) Add / Configure a SCADA Protocol (5)

4) Connect C264 SCADA to serial port (for serial protocol)


Relation “has for main comm port”

Note : possibility to add a redundant


communication port

5) Configure C264 serial port

Communication parameters
Note that COM3 and COM4 should have same
transmission speed
For COM3 and COM4 => Tx carrier
management set to Switched

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 8
1.2) Add / Configure a SCADA Protocol (6)

6) Connect C264 SCADA protocol System Info

Redundancy SPS :
Gives port redundancy status

SCADA SPS Com :


Gives connection status between C264 and
SCADA

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 9
1.3) Add / Configure a SCADA Mapping (1)

1) C264 SCADA protocol

SCADA Mapping :
set of SPS, DPS, MPS, MV, SPC, DPC, … sent to SCADA

To add a DP address :
1) select kind of DP Mapping
2) Through Objects Entry Window, add an address

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 10
1.3) Add / Configure a SCADA Mapping (2)

2) Configure DP addresses (example given with T101)


2.1) SPS address
SPS address :
address value, event (Yes with timetag, No), Event
Record, Background Scan, ...

2.2) DPS address


DPS address :
address value, event (Yes with timetag, No), Event
Record, Background Scan, ...

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 11
1.3) Add / Configure a SCADA Mapping (3)

2) Configure DP addresses (example given with T101)


2.3) SPC address
SPC address :
address value, control type (DE/SBO)

2.4) DPC address


DPC address :
address value, control type (DE/SBO)

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 12
1.3) Add / Configure a SCADA Mapping (4)

2) Configure DP addresses (example given with T101)


2.3) MV address
MV address :
address value, event (Yes with timetag, No), event record
Format

Cycle type

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 13
1.3) Add / Configure SCADA Mapping (5)

3) Link DP with the relevant address (example given with T101)


=> Relation “has for SCADA address”
Under datapoint :
DP link with relevant SCADA address

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 14
1.4) Ethernet routing for SCADA

T104, DNP3 over IP, MODBUS over IP frames can be sent through routers
Under Scs / Computer Routing tab

Gateway TCP/IP address :


Router port address

Target TCP/IP address :


SCADA sub-network address

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 15
Summary

1) MiCOM C264 TBUS Page 3

2) DS Agile GTW TBUS Page 17

3) Taking Control Page 29

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 16
2.1) Reminder (1)

1) Reminder
Limits
up to 4 TBUS
redundant link possibility => 8 serial ports

Connections
8 RS232 serial ports
possibility of extra ethernet board for ethernet TBUS

Supported Protocols
Serial => T101, DNP3, MODBUS
Ethernet => T104, OPC (to come IEC61850)

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 17
2.2) Add / Configure a SCADA Protocol (1)

1) TBUS protocol is added at GTW level.

Usual Protocol :
Serial T101, DNP3, MODBUS
Ethernet T104

2) SCADA protocol attributes : General tab

Protocol

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 18
2.2) Add / Configure a SCADA Protocol (2)

3) SCADA protocol attributes : Protocol tab (1)


=> Customer SCADA addressing, data class & structure, ...
T101 attributes :
- link address value coding structure
- ASDU common @ value and coding structure
- data address coding structure
- period for cyclic MV
- time size
- background scan
- type of link (balanced / unbalanced)
- ...

DNP3 attributes :
- link address value
- SPS/DPS Class, MV Class, Counter Class
- MV Format MV
- ...
Note : Interlock Protocol Yes if Take Control used
GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 19
2.2) Add / Configure a SCADA Protocol (3)

3) SCADA protocol attributes : Protocol tab (2)


=> Customer SCADA addressing, data class & structure, ...
T104 attributes :
- ethernet board IP @
- ASDU common @ value and coding structure
- data address coding structure
- period for cyclic MV
- time size
- background scan
- ...

Modbus attributes :
- link address value
- ...

Note : Interlock Protocol Yes if Take Control used


GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 20
2.2) Add / Configure a SCADA Protocol (4)

4) Connect SCADA to serial port (for serial protocol)


Relation “has for main comm port”

Note : possibility to add a redundant


communication port
5) Configure GTW serial port

Communication parameters :
protocol type (Usual Protocol / GI74)
baud rate
plug number = com. port number

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 21
2.2) Add / Configure a SCADA Protocol (5)

6) Connect C264 SCADA protocol System Info

Redundancy SPS :
Gives port redundancy status

SCADA SPS Com :


Gives connection status between GTW and
SCADA

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 22
2.3) Add / Configure a SCADA Mapping (1)

1) SCADA protocol
SCADA Mapping :
set of SPS, DPS, MPS, MV, SPC, DPC, … sent to SCADA

To add a DP address :
1) select kind of DP Mapping
2) Through Objects Entry Window, add an address

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 23
2.3) Add / Configure a SCADA Mapping (2)

2) Configure DP addresses (example given with T101)


2.1) SPS address
SPS address :
address value, event (Yes with timetag, Yes without
timetag, No), Event Record, Background Scan, ...

2.2) DPS address

DPS address :
address value, event (Yes with timetag, Yes without
timetag, No), Event Record, Background Scan, ...

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 24
2.3) Add / Configure a SCADA Mapping (3)

2) Configure DP addresses (example given with T101)


2.3) SPC address
SPC address :
address value, control type (DE/SBO), SBO timeout

2.4) DPC address


DPC address :
address value, control type (DE/SBO), SBO timeout

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 25
2.3) Add / Configure a SCADA Mapping (4)

2) Configure DP addresses (example given with T101)


2.3) MV address

MV address :
address value, event (Yes with timetag, Yes without
timetag, No), event record
Format

Cycle type

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 26
2.3) Add / Configure SCADA Mapping (5)

3) Link DP with the relevant address (example given with T101)


=> Relation “has for SCADA address”
Under datapoint :
DP link with relevant SCADA address

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 27
Summary

1) MiCOM C264 TBUS Page 3

2) DS Agile GTW TBUS Page 17

3) Taking Control Page 29

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 28
3.1) Definition

1) Taking Control / Taking Status

Definition
when several SCADA => only 1 can control the SS at one time
which one ? The one with Taking Status active

How to take control


SCADA sends a Taking Control Order and Taking Status is
transferred from previous one to new one

On DS Agile GTW HMI :


Top Left

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 29
3.2) Add / Configure a Taking Control

1) Taking Control SPC and Taking Status SPS are added at Substation level.

2 Typed Taking Control SPC :


- feedback with relevant Taking Status SPS
- SCADA @ on their own SCADA Protocol

2 Typed Taking Status SPS :


- relation “is taken control of” with relevant protocol
- SCADA @ on all SCADA Protocols

Note : These information are computed by the MiCOM C264 default server of substation
data. Up to 4 taking controls

GSE
L2-12-C264 & GTW TBUS Configuration - Rev G - P 30
www.alstom.com