Pneum.
Controllers, Indicators, Recorders PC451 - PM451
PC451 Pneumatic Controller CP 600/400 compact P
PM451 Manual Control Unit CP 600/400/200
• Flat scale indication
• Bellows measuring systems
• All important information and controls located at the
front. No controls have a double function
• Modular construction
• Mounting in individual housing or shelf
• Pre-installation and connection can be carried out
• Pneumatic circuity carried within diecast backplates
• Controller is plug-in-type, with self-seating connec-
tions to Manual Control Unit
• Test switch
• Optional additional features among other things:
• Bumpless transfer M → A and A → M
• Limitation of controller output CP 600/400 Controllers and Manual Control Units for
the automatic control of process plants. CP 200 Ma-
• Inductive or microswitch alarms
nual Control Units with terminal plate and separately
• Alarm lamps (LED) mounted Controllers simplify installation in consoles,
• Built-in I-p Converter due to the reduced insertion depth of 193 mm.
• Pi switch
• Ratio controller
• Manual Control Stations
• Manual Control Units 193 mm long, Controller se- For complete specification, refer to Product Specification
parated Sheet PSS EIC2312 A-(en)
Complete instrument Controller section
Frontal dimensions. . . . . . . . 72 x 144 mm Control system . . . . . . . . . . . cross-bellows
Length . . . . . . . . . . . . . . . . . 605 mm or 465 mm, 193 mm Control actions . . . . . . . . . . . P, PD, PI, PID
for Manual Control Unit Operating point of
Front finish. . . . . . . . . . . . . . bezel grey RAL 7037 P or PD Controller . . . . . . . . pneumatically adjustable
facia grey RAL 7035 internally or remotely
Measured value x, Proportional band Xp . . . . . . 5 ... 400 % and higher
set point w, output y . . . . . . 0.2 ... 1 bar, 3 ... 15 psi, Gain K p . . . . . . . . . . . . . . . . 20 ... 0.25 and lower
20 to 100 kPa Reset time Tn . . . . . . . . . . . . 0.03 ... 50 mins.
Supply air. . . . . . . . . . . . . . . 1.4 ± 0.1 bar / 20 ± 1.4 psi Derivative time T v . . . . . . . . . 0.03 ... 20 mins.
Inherent air consumption . . . . ≤ 500 l / hr
Inherent air consumption . . . ≤ 300 l / hr
Manual Control Module Controller section
13
Extra module Terminal plate and multibore band
(only for CP 600 possible)
02/2000 CA EIC2312 A-(en)
13-1
Pneum. Controllers, Indicators, Recorders PC451 - PM451
Model Codes
Pneumatic Manual Control Unit Compact P PM451
Version
compact 200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -2
compact 400/600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -4
Manual Control Unit for
Local set control (auto- selector,master) . . . . . . . . . . . . . . . . . . . . . . A
Local set control for auto- selector,slave . . . . . . . . . . . . . . . . . . . . . . B
Slave control with remote/local switch (auto- selector) . . . . . . . . . . . . . . . C
Slave control without remote/local switch (auto- selector) . . . . . . . . . . . . . D
Manual Loader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
Manual Loader with process indicator YH display large size . . . . . . . . . . . . F
Manual Loader with process indicator YH display small size . . . . . . . . . . . . G
Double Manual Loader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H
Double Manual Loader with process indicator . . . . . . . . . . . . . . . . . . . J
Setpoint Station with remote/local switch and x-indicator . . . . . . . . . . . . . K
Transfer Station with indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . L
Transfer and Manual Loader . . . . . . . . . . . . . . . . . . . . . . . . . . . M
Circuit
Auto-Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
Normal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N
Signal Range
0.2 -1.0 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 - 15 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
20 - 100 kPa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Indicating Range for output signal
without (a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
0 - 1.2 bar (b) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
0 - 18 psi (b) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
0 - 120 kPa (b) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Indicating Range (Scale)
0 - 10 linear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
0 - 10 square . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
0 - 100% linear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
0 - 100% square . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
to be specified (acc.standard list) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
acc. customer specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
Additional Module
without . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
I-P transmitter for x (c) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
I-P transmitter for Wext. (c) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
Inductiv alarm from -x- (microswitch) (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
Inductiv alarm from -xw- (microswitch) (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
Options
Tracking unit (bumpless switching) auto - manual / Wint.- Wext. (e) . . . . . . . . . . . . . . . . . . . . . . . . . . . . -BT
nur für Version 2 Electr.connection: flat pins (g) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -EF
H - A - switch with electr. feedback signal (f). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -MA
Ext.-int.-switch with electr. feedback signal (e) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -EI
Tag.No. Labeling with inscription . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -LL
nur für Version 2 Electr.connection: screw terminals (g) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -ES
Footnotes
(a) Not available with Manual unit Code A.B,C,D,G,J
(b) Not available with Manual unit Code E,F,H,K,L,M
(c) Not available with Manual unit Code E,F,H,J,L
(d) Not available with Version Code2
(e) Only available with Manual unit Code C&K
(f) Not available with Manual unit Code B,F,G,H,J,K,M
(g) Only together with Option MA or EI
Housings /Shelves see EIC9001
Terminal block see EIC9001
Tube fittings see EOO9001
CA EIC2312 A-(en) 02/2000
13-2
Pneum. Controllers, Indicators, Recorders PC451 - PM451
Model Codes
Pneumatic Controller Compact P PC451
Version
compact 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . -4
compact 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . -6
Manual Control Unit Module
Local set control (auto- selector,master) . . . . . . . . . . . . . . . . . . A
Local set control for auto- selector,slave . . . . . . . . . . . . . . . . . . B
Slave control with remote/local switch (auto- selector) . . . . . . . . . . . C
Slave control without remote/local switch (auto- selector) . . . . . . . . . . D
Circuit
Auto-Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
Normal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N
Signal Range
0.2 -1.0 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 - 15 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
20 - 100 kPa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Indicating Range for output signal
0 - 1.2 bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
0 - 18 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
0 - 120 kPa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Indicating Range (Scale) for X and W
0 - 10 linear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
0 - 10 square . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
0 - 100% linear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
0 - 100% square . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
to be specified (acc.standard list) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
acc. customer specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F
Controller Module (standard equipment)
P Operating point internally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
P Operating point externally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
PD Operating point internally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
PD Operating point externally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
PI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Additional Module
without . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
I-P transmitter for x (a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B
I-P transmitter for Wext. (a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C
Inductive alarm from -x- (microswitch) (a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D
Inductive alarm from -xw- (microswitch) (a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
Options
Optionals for manual control unit, Tracking unit (bumpless switching) auto - manual / Wint.- Wext. (f) . . . . . . . . . . . -BT
Optionals for manual control unit, H - A - switch with electr. feedback signal . . . . . . . . . . . . . . . . . . . . . . . . -MA
Optionals for manual control unit, Ext.-int.-switch with electr. feedback signal (b) . . . . . . . . . . . . . . . . . . . . . . -EI
Optionals for manual control unit, Tag.No. Labeling with inscription . . . . . . . . . . . . . . . . . . . . . . . . . . . . -LL
Optionals for controller, High limitation (YA+R) (c) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -12
Optionals for controller, Low limitation (YA+R) (c) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -13
Optionals for controller, Tracking relay (bumpless H - A) (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -17
Optionals for controller, PI-switch, PF internal (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -21
Optionals for controller, PI-switch, PF external (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -24
Optionals for controller, High limitation (R) (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -27
Optionals for controller, Low limitation (R) (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -28
Optionals for controller, P - PI - change-over (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -32
Optionals for controller, External reset (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -35
Optionals for controller, Auto - selector (d) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -39
Optionals for controller, Plug for test sleeve (e) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -43
Footnotes
(c) Limitation of R not available by:Control mode P,PD,Option Code -32,-35,-39,
(a) Not available with version Code 4
(e) Only available with Control mode P / PD
(d) Only available with Control mode PI / PID
(f) Only available with Manual unit Code A,C
(b) Only with Manual unit Code C 13
Housings /Shelves see EIC9001
Terminal block see EIC9001
Tube fittings see EOO9001
02/2000 CA EIC2312 A-(en)
13-3