Smart D fferent al Level Controller
BAB100-DL Manual
BAB100-DL MANUAL DOC REV1.1
1.0 GENERAL SPECIFICATION
Selectable Input : 2x4-20 mA or 1x0-10 VDC and 1x4-20 mA
Selectable Output 1 : 4-20 mA, 0-10 VDC
Output 2 : 4 SPDT relays, 2A
Commun cat on : RS485 Modbus RTU
Analog Input Resolut on : 10 B t
D splay : 4.3" 480x272 p xel res st ve touchscreen
Hum d ty : %10...85 non-condensate
Power Supply : 24 VDC, ±10%
Power Consumpt on :3W
D mens on : 144x144 mm (front), 134x134 (rear), depth 100 mm
Protect on : IP65 (front)
1.1. Mount ng Hole D mens ons
138 mm
138 mm
BAB100-DL MANUAL DOC REV1.1
1.2. Term nal W r ng
SUPPLY
1: +24 VDC
2: -24 VDC 29:
RTD-1
3: GND 30:
31:
RS485-OUT
RS485-IN
4: GND 45: GND
5: A 32: 46: A
RTD-2
6: B 47: B
33:
RELAY
7: DC+
34:
35: C 1-2
OUTPUT
DIGITAL
36: R1-NO 8: DC-
37: R1-NC 9: DO
38: R2-NO 10: Batch
39: R2-NC
40: C 3-4 19: AO 0-10V/4-20mA+
41: R3-NO 20: AO 0-10V/4-20mA-
42: R3-NC 21: AI1 4-20mA+
DIGITAL
43: R4-NO INPUT 22: AI1 4-20mA-
44: R4-NC 11: Com1 23: AI2 4-20mA+
12: Input1
24: AI2 4-20mA-
13: Input2
14: - 25: AI 0-10V+
15: - 26: AI 0-10V-
16: Com2
17: Input3 27: -
18: Input4 28: -
Made in Turkey
GOOD
Back s de of dev ce
Connector
WRONG
Back s de of dev ce
BAB100-DL MANUAL DOC REV1.1
Connector
1.2.1. Analog Inputs
SUPPLY
1: +24 VDC
2: -24 VDC 29:
RTD-1
3: GND 30:
31:
V+ s gnal to 0-10 VDC Input + term nal,
RS485-OUT
RS485-IN
4: GND 45: GND
5: A 32: 46: A
V- s gnal to 0-10 VDC Input - term nal.
RTD-2
6: B 47: B
33:
RELAY
34:
35: C 1-2 7: DC+
OUTPUT
DIGITAL
36: R1-NO 8: DC-
37: R1-NC 9: DO
38: R2-NO 10: Batch
39: R2-NC
40: C 3-4 19: AO 0-10V/4-20mA+
41: R3-NO 20: AO 0-10V/4-20mA-
42: R3-NC 21: AI1 4-20mA+
DIGITAL
43: R4-NO INPUT 22: AI1 4-20mA-
44: R4-NC 11: Com1 23: AI2 4-20mA+
12: Input1
24: AI2 4-20mA-
13: Input2
14: - 25: AI 0-10V+
15: - 26: AI 0-10V-
16: Com2
17: Input3 27: -
18: Input4 28: -
Made in Turkey
1.2.2. Analog Outputs
SUPPLY
1: +24 VDC
2: -24 VDC 29:
RTD-1
3: GND 30:
31:
RS485-OUT
RS485-IN
4: GND 45: GND
5: A 32: 46: A
RTD-2
6: B 47: B
33:
RELAY
34:
35: C 1-2 7: DC+
OUTPUT
DIGITAL
36: R1-NO 8: DC-
37: R1-NC 9: DO
38: R2-NO 10: Batch
39: R2-NC
40: C 3-4 19: AO 0-10V/4-20mA+
41: R3-NO 20: AO 0-10V/4-20mA-
42: R3-NC 21: AI1 4-20mA+
DIGITAL
43: R4-NO INPUT 22: AI1 4-20mA-
44: R4-NC 11: Com1 23: AI2 4-20mA+
12: Input1
24: AI2 4-20mA-
13: Input2
14: - 25: AI 0-10V+
15: - 26: AI 0-10V-
16: Com2
17: Input3 27: -
18: Input4 28: -
Made in Turkey
BAB100-DL MANUAL DOC REV1.1
1.2.6. RS485 MODBUS-RTU Commun cat on
SUPPLY
1: +24 VDC
2: -24 VDC 29:
RTD-1
3: GND 30:
31:
RS485-OUT
RS485-IN
4: GND 45: GND
5: A 32: 46: A
RTD-2
6: B 47: B
33:
RELAY
34:
35: C 1-2 7: DC+
OUTPUT
DIGITAL
36: R1-NO 8: DC-
37: R1-NC 9: DO
38: R2-NO 10: Batch
39: R2-NC
40: C 3-4 19: AO 0-10V/4-20mA+
41: R3-NO 20: AO 0-10V/4-20mA-
42: R3-NC 21: AI1 4-20mA+
DIGITAL
43: R4-NO INPUT 22: AI1 4-20mA-
44: R4-NC 11: Com1 23: AI2 4-20mA+
12: Input1
24: AI2 4-20mA-
13: Input2
14: - 25: AI 0-10V+
15: - 26: AI 0-10V-
16: Com2
17: Input3 27: -
18: Input4 28: -
Made in Turkey
2.0 MENU and CONFIGURATION of PARAMETERS
2.1. Ma n Screen (P1)
P1
BAB100-DL R1 R2 R3 R4
Ver .1.1 %68
6.848 m
4.543 m
E-005 L1&L2 MENU
E-006
F rst Row : L1 Level Value
Second Row : L2 Level Value
Bar Graph : Level Rate (Full Scale accord ng to L1 or L2 Analog Output)
Batch : Relay Status
MENU : Touch MENU for enter
BAB100-DL MANUAL DOC REV1.1
2.2. Password
-Password- Password s 1234 as standard. Push “ENT” when you enter
1234 on screen.
7 8 9 < ESC Y ou can change the password on “SETTINGS”
4 5 6
1 2 3 - ENT Please consult factory f you forgot password.
0 .
2.3. Menu Screen (Page 2)
MENU P2
There are s x pages under Menu Page. You can select
Un ts the pages accord ng to your requ rements.
All Parameters
Process Config Please touch BACK f you go back to ma n screen.
Sett ngs
Contact Us
BACK
2.3.2. All Parameters (Page 4)
ALL PARAMETERS P4 You can see all measurable un ts n one screen thanks to
L1: ---- ALL PARAMETERS
L2: ---- L1 : L1 Level Value
L1-L2: ---- L2 : L2 Level Value
L2-L1: ---- L1-L2 : L1-L2 Level Value (L1 m nus L2)
4_20 mA1: ---- L2-L1 : L2-L1 Level Value (L2 m nus L1)
4_20 mA2: ---- 4_20 mA1 : Analog Input value as mA
Ang.Out.: 0% MAIN 4_20 mA2 : Analog Input value as mA
Ang.Out : Analog output value w ll shown as percentage
BACK
Please touch BACK f you go back to P2 or MAIN for go
back to P1
2.3.4 Process Config (Page 6)
PROCESS CONFIG P6 Dmp.Tm : Refresh t me of ma n screen.
L1-(4_20mA1) L2-(4_20mA1) DmpTm.
IN.MAX : Level value L1 and L2 equ valent to 20 mA nput
IN.MAX 2.50m 8.00m 1sec
IN.MIN : Level value L1 and L2 equ valent to 4 mA nput
IN.MIN 0.00m 0.00m
OFFSET : To sh ft the measured level by a constant value
OFFSET 0.00m 0.00m
Dsly : Selectable level opt ons on d splay
Po nt ***.*** Po nt ***.***
Po nt : Dec mal po nt select on
OUT T. 0_10v OUTSEL L1
Out T. : Analog output select on. 4-20 mA or 0-10VDC
O.MAX 2.50m MAIN O.MAX : Level value equ valent to 20 mA or 10V output
O.MIN 0.00m
BACK
O.MIN : Level value equ valent to 4 mA or 0V output
Un t : Selectable length, volume un ts
OUTSEL : Selectable level output (L1 or L2)
BAB100-DL MANUAL DOC REV1.1
You can change below parameters by cl ck ;
R1 S2.50m R:2.80m H L1
R1 : relay s act ve
R2 S:0.00m R:0.00m AL L1
R3 S:0.00m R:0.00m H L2 R1 : relay s deact ve
R4 S:0.00m R:0.00m H L2 S : 2.50m : Relay start po nt
Low Normally Open Relay
:
MAIN High : Normally Close Relay
BACK
R : 02.80m : Relay reset po nt
Please touch BACK f you go back to P2 or MAIN for go back to P1
2.3.5 Sett ngs (Page 7)
SETTINGS P7
Th s parameter for change the passwords and Modbus
Password Sett ngs
sett ngs.
Menu Pass. 1234
Tot.Res Pass. 0.00ton
Please take a note f you change the passwords.
Modbus RTU sett ngs
Please consult factory f you forgot passwords.
Mb Address: 4 MAIN
Baud Rate: 9600bps
BACK
Par ty/Stopb t: 8,E,1
2.3.6 Contact Us (Page 8)
CONTACT P8
Please call us or send e-ma l for all techn cal quest ons.
BASS INSTRUMENTS
Address: Fusun Sok. No:59
TR-34776
Telephone: 0216 660 01 63
0216 660 01 64
Fax: 0216 660 01 65 MAIN
E-ma l:
[email protected] BACK
web: www.bass.com.tr
3.0 ERROR MESSAGES
Error Codes Mean ng Solut on
E-001 not for th s dev ce
E-003 4-20 mA_1 analog nput error Please make sure w r ng. See 1.2.2
E-004 4-20 mA_2 analog nput error
Amb ent temperature s h gher than
E-005 OT Dev ce h gh temperature work ng temperature. Please move the
dev ce su table place.
Analog output error
E-006 Short c rcu t error Make sure analog output w r ng well.
BAB100-DL MANUAL DOC REV1.1
H gh empedance warn ng
Make sure the val d common mode
E-007 Analog output commonmode error
voltage s not exceeded
4.0 MODBUS DETAILS
4.1 Holding Registers
Var able Name M n – Max Data Type Address
Level Un t 16 b t 0 13 Uns gned Long 0x0000
FLASHWRITE 16 b t 0 1 Uns gned Long 0x0001
Level Un ts :
"mm","cm","m"," nch","ft","lt","m3","kg","ton","gal","deg C","deg F"
4.2 Input Registers
Var able Name Descr pt on Data Type Address
LEVEL1_L 32 b t Float 0x0000
LEVEL1_H 0x0001
LEVEL2_L 32 b t Float 0x0002
LEVEL2_H 0x0003
LEVEL1-LEVEL2_L 32 b t Float 0x0004
LEVEL1-LEVEL2_H 0x0005
LEVEL2-LEVEL1_L 32 b t Float 0x0006
LEVEL2-LEVEL1_H 0x0007
ALARM_L 32 b t Uns gned Long 0x0008
ALARM_H 0x0009
4.3 Alarm Register
B t Number Descr pt on
0 Reserved
1 Reserved
2 4-20mA_1 Analog input error E-003
3 4-20mA_2 Analog input error E-004
4 OT Device high temperature ( OT) E-005
Analog output error
5 Short circuit error E-006
High empedance warning
6 Analog output commonmode error (CM) E-007
7 Reserved
8 Reserved
9 Reserved
10 Reserved
BAB100-DL MANUAL DOC REV1.1