P.O. Box 14148, Dammam 31424 , K.S.A.
(: (+9663) 846 2047 / 846 2079
6: (+9663) 846 5254
PRE-COMMISSIONING CHECK SHEET FOR FIRE ALARM SYSTEM
Date:
CLIENT Al Khafji Joint Operation KGOC / AGOC
Water Treatment Facilities
SITE REFERENCE
ROOM REFERNCE Loop No.
FIRE CONTROL PANEL TYPE Addressable Five Loop Panel - NFS2-3030
MAKE Notifier
SL.No Visual Checks Ref.Doc Additional Remarks YES NO N/A QTY
KA-057541
Ensure All Components installed are as per AFC drawings and
1
approved material specifications KA-057505
KA-057504 ( Sheet 1 to 4)
2 Fire Alarm Control Panel and its internal Components installed D-000-1241-016
3 Cabling and Loop Terminations done for FACP KA-057505
4 Battery Installed in the FACP KA-057505
5 Power Supply Units installed and terminated KA-057505
Very Intelligent Early Warning Laser Smoke Detector
6
installed on Cabinets and terminations done D-000-1241-016
7 Isolator Base installed for Loop1 D-000-1241-016
8 Loop Isolator Module installed and terminated. D-000-1241-016
9 Photo Electric Smoke Detector installed and terminated D-000-1241-016
10 Ionization Smoke Detector installed and terminated. D-000-1241-016
11 Alarm Motor Bell installed and terminated D-000-1241-016
12 Horn Strobe installed and terminated D-000-1241-016
13 Abort Station Installed and terminated D-000-1241-032
14 Manual Release Station installed and terminated D-000-1241-016
15 Addressable Monitoring Module installed D-000-1241-016
and terminated
16 Addressable Control Module installed D-000-1241-016
and terminated
17 Remote Releasing Module installed and terminated D-000-1241-032
18 Main to Reserve Transfer Switch installed and terminated D-000-1241-032
19 Key Maintenance Switch installed and terminated D-000-1241-032
20 Supervisory Pressure Switch termination done D-000-1241-032
21 Discharge Pressure Switch termination done D-000-1241-032
22 Termination inside Electric Control Head done D-000-1241-032
23 Intelligent Non-Relay Duct Smoke Detector D-000-1241-016
installation and termination done
24 Cabling and termination done between PSU , Control Module ,
Remote Release Module , Maintenance Switch e.t.c
Note : Electrical Control Head / Solenoid Valve to be connected at the time of handing over only to Pilot N2 Cylinders
Performed By: Witnessed By: Approved By:
Fire Freeze JGC AL Khafji