Schneider Sepam 1000+ S40
Schneider Sepam 1000+ S40
(2) Sn =
(1) tripping as of 1.2 Is.
.In.Unp.
Description The Is setting is the vertical asymptote of the curve, and T is the operation time delay
The phase overcurrent function comprises 2 groups of for 10 Is.
four units, called Group A and Group B respectively. The tripping time for I/Is values of less than 1.2 depends on the type of curve chosen.
The mode of switching from one group to the other may
be determined by parameter setting: Name of curve Type
by remote control (TC3, TC4) Standard inverse time (SIT) 1.2
by logic input I13 (I13 = 0 group A, I13 = 1 group B) Very inverse time (VIT or LTI) 1.2
or by forcing the use of the group.
Extremely inverse time (EIT) 1.2
Operation Ultra inverse time (UIT) 1.2
The phase overcurrent protection function is three-pole. RI curve 1
It picks up if one, two or three of the phase currents reach IEC standard inverse time SIT / A 1
the operation set point. IEC very inverse time VIT or LTI / B 1
The alarm connected to the operation of the protection IEC extremely inverse time EIT / C 1
function indicates the faulty phase or phases.
IEEE moderately inverse (IEC / D) 1
It is time-delayed. The time delay may be definite time
(DT) or IDMT according to the curves opposite. IEEE very inverse (IEC / E) 1
IEEE extremely inverse (IEC / F) 1
Confirmation
The phase overcurrent protection function includes a IAC inverse 1
paramerizable confirmation component. IAC very inverse 1
The output is confirmed as follows: IAC extremely inverse 1
by phase-to-phase undervoltage protection unit 1 The curve equations are given in the chapter entitled "IDMT protection functions".
by negative sequence overvoltage protection
no confirmation. The function takes into account current variations during the time delay interval.
Definite time protection For currents with a very large amplitude, the protection function has a definite time
Is is the operation set point expressed in Amps, and T characteristic:
is the protection operation time delay. if I > 20 Is, tripping time is the time that corresponds to 20 Is
if I > 40 In, tripping time is the time that corresponds to 40 In.
(In: current transformer rated current defined when the general settings are made).
t Block diagram
MT10911
I1
I2 t 0
I > Is time-delayed
I3 output
T Confirmation
(optionnal)
Is I
Definite time protection principle.
MT10541
type 1,2
T
T tripping
value of internal
time delay
1 1.2 10 20 I/Is counter
IDMT protection principle.
T1 T1
T1
MT10527
I > Is pick-up signal
T tripping
value of internal
time delay
counter
T1
Characteristics
Tripping curve
Setting Definite time,
IDMT: chosen according to list on page 4
Confirmation
Setting by undervoltage (unit 1)
by negative sequence overvoltage
none, by confirmation
$ $
Is set point
$ $
Setting Definite time 0.1 In Is 24 In expressed in Amps
IDMT 0.1 In Is 2.4 In expressed in Amps
Resolution 1 A or 1 digit
Accuracy (1) ±5%
Drop out/pick-up ratio 93.5% ±5 % (with min. reset variance of
0.015 In)
$ $
Time delay T (operation time at 10 Is)
$ $
Setting Definite time inst., 50 ms T 300 s
IDMT 100 ms T 12.5 s or TMS (2)
Resolution 10 ms or 1 digit
Accuracy (1) Definite time ±2% or from -10 ms to +25 ms
IDMT Class 5 or from -10 ms to +25 ms
Timer hold delay T1
Definite time
(timer hold) 0; 0.05 to 300 s
IDMT (3) 0.5 to 20 s
Characteristic times
Operation time pick-up < 35 ms at 2 Is (typically 25 ms)
inst. < 50 ms at 2 Is (confirmed instantaneous)
(typically 35 ms)
Overshoot time < 35 ms
Reset time < 50 ms (for T1 = 0)
(1) in reference conditions (IEC 60255-6).
(2) setting ranges in TMS (Time Multiplier Setting) mode
Inverse (SIT) and IEC SIT/A: 0.04 to 4.20
Very inverse (VIT) and IEC VIT/B: 0.07 to 8.33
Very inverse (LTI) and IEC LTI/B: 0.01 to 0.93
Ext inverse (EIT) and IEC EIT/C: 0.13 to 15.47
IEEE moderately inverse: 0.42 to 51.86
IEEE very inverse: 0.73 to 90.57
IEEE extremely inverse: 1.24 to 154.32
IAC inverse: 0.34 to 42.08
IAC very inverse: 0.61 to 75.75
IAC extremely inverse: 1.08 to 134.4
(3) only for standardized tripping curves of the IEC, IEEE and
IAC types.
Operation The Iso setting is the vertical asymptote of the curve, and T is the operation time
The voltage-restrained phase overcurrent protection delay for 10 Iso.
function is used to protect generators. The operation The tripping time for Io/Iso values of less than 1.2 depends on the type of curve
set point is adjusted according to the voltage to take chosen.
into account cases of faults close to the generator
which cause voltage dips and short-circuit current. Name of curve Type
This protection function is three-pole. It picks up if one, Standard inverse time (SIT) 1.2
two or three phase currents reach the voltage-adjusted
Very inverse time (VIT or LTI) 1.2
operation set point Is*.
Extremely inverse time (EIT) 1.2
The alarm linked to operation indicates the faulty phase
or phases. Ultra inverse time (UIT) 1.2
It is time-delayed, and the time delay may be definite RI curve 1
time (DT) or IDMT according to the curves opposite. IEC standard inverse time SIT / A 1
The set point is adjusted according to the lowest of the IEC very inverse time VIT or LTI / B 1
phase-to-phase voltages measured. IEC extremely inverse time EIT / C 1
The adjusted set point Is* is defined by the following
IEEE moderately inverse (IEC / D) 1
equation:
IEEE very inverse (IEC / E) 1
I*s = ---s- x 4------- – 0, 2
I U IEEE extremely inverse (IEC / F) 1
3 UN IAC inverse 1
IAC very inverse 1
IAC extremely inverse 1
The curve equations are given in the chapter entitled "IDMT protection functions".
MT11030
The function takes into account current variations during the time delay interval.
For currents with a very large amplitude, the protection function has a definite time
characteristic:
if I > 20 Is, tripping time is the time that corresponds to 20 Is
if I > 40 In, tripping time is the time that corresponds to 40 In
(In: current transformer rated current defined when the general settings are made).
t
MT10211
Is*
Is* I
type 1,2
T tripping
value of internal
T time delay
counter
1 1.2 10 20 I/Is*
T1 T1
IDMT protection principle. T1
MT10527
I > Is pick-up signal
T tripping
value of internal
time delay
counter
T1
Characteristics
Tripping curve
Setting Definite time,
IDMT: chosen according to list page 6
$ $
Is set point
$ $
Setting Definite time 0.1 In Is 24 In expressed in Amps
IDMT 0.1 In Is 2.4 In expressed in Amps
Resolution 1 A or 1 digit
Accuracy (1) ±5%
Drop out/pick-up ratio 93.5% ±5 % (with min. reset variance of
0.015 In)
$ $
Time delay T (operation time at 10 Iso)
$ $
Setting Definite time inst. 50 ms T 300
IDMT 100 ms T 12.5 s or TMS (2)
Resolution 10 ms or 1 digit
Accuracy (1) Definite time ±2% or from -10 ms to +25 ms
IDMT class 5 or from -10 ms to +25 ms
Timer hold delay T1
Definite time
(timer hold) 0; 0.05 to 300 s
IDMT (3) 0.5 to 20 s
Characteristic times
Operation time pick-up < 35 ms at 2 Is (typically 25 ms)
inst. < 50 ms at 2 Is (confirmed instantaneous)
(typically 35 ms)
Overshoot time < 35 ms
Reset time < 50 ms (for T1 = 0)
(1) in reference conditions (IEC 60255-6)
(2) setting ranges in TMS (Time Multiplier Setting) mode
Inverse (SIT) and IECIEC SIT/A: 0.04 to 4.20
Very inverse (VIT) and IEC VIT/B: 0.07 to 8.33
Very inverse (LTI) and IEC LTI/B: 0.01 to 0.93
Ext inverse (EIT) and IEC EIT/C: 0.13 to 15.47
IEEE moderately inverse: 0.42 to 51.86
IEEE very inverse: 0.73 to 90.57
IEEE extremely inverse : 1,24 à 154,32
IAC inverse: 0.34 to 42.08
IAC very inverse: 0.61 to 75.75
IAC extremely inverse: 1.08 to 134.4
(3) only for standardized tripping curves of the IEC, IEEE and
IAC types.
Description The Iso setting is the vertical asymptote of the curve, and T is the operation time
The earth fault protection function comprises 2 groups delay for 10 Iso.
of four units, called Group A and Group B respectively. The tripping time for Io/Iso values of less than 1.2 depends on the type of curve
The mode of switching from one group to the other may chosen.
be determined by parameter setting:
by remote control (TC3, TC4) Name of curve Type
by logic input I13 (I13 = 0 group A, I13 = 1 group B) Standard inverse time (SIT) 1.2
or by forcing the use of the group. Very inverse time (VIT or LTI) 1.2
Operation Extremely inverse time (EIT) 1.2
The earth fault protection function is single-pole. Ultra inverse time (UIT) 1.2
It picks up if the earth fault current reaches the RI curve 1
operation set point. IEC standard inverse time SIT / A 1
It is time-delayed. The time delay may be definite time IEC very inverse time VIT or LTI / B 1
(DT) or IDMT according to the curves opposite. IEC extremely inverse time EIT / C 1
The protection function includes harmonic 2 restraint
IEEE moderately inverse (IEC / D) 1
which provides greater stability when transformers are
energized. IEEE very inverse (IEC / E) 1
The restraint disables tripping, regardless of the IEEE extremely inverse (IEC / F) 1
fundamental current. IAC inverse 1
The restraint may be inhibited by parameter setting. IAC very inverse 1
Definite time protection IAC extremely inverse 1
Iso is the operation set point expressed in Amps, and T The curve equations are given in the chapter entitled "IDMT protection functions".
is the protection operation time delay.
The function takes into account current variations during the time delay interval.
For currents with a very large amplitude, the protection function has a definite time
characteristic:
t if I > 20 Iso, tripping time is the time that corresponds to 20 Iso
if I > 20 Ino, tripping time is the time that corresponds to 20 Ino (operation based
MT10212
on Io input)
if Io > 40 Ino (1), tripping time is the time that corresponds to 40 Ino (operation
based on sum of phase currents).
T Block diagram
I1
I2 "pick-up" signal and
MT10213
I3 to logic discrimination
Iso Io
t 0
Definite time protection principle. Io > Iso time-delayed
output
CSH core bal. CT
IDMT protection CT + CSH30
IDMT protection operates in accordance with the H2
core bal. + ACE990
IEC (60255-3), BS 142 and IEEE (C-37112) standards.
type 1 The choice between Io (measured) and IoΣ (calculated by the sum of the phase
t currents) may be set for each unit, by default units 1 and 2 set to Io and units 2 and
type 1,2 4 to IoΣ.
By mixing the 2 possibilities on the different units, it is possible to have:
different dynamic set points
MT10665
different applications, e.g. zero sequence and tank earth leakage protection.
Timer hold delay
The function includes an adjustable timer hold delay T1:
T definite time (timer hold) for all the tripping curves
Io > Iso time-delayed output
MT10547
1 1.2 10 20 Io/Iso
IDMT protection principle.
Io > Iso pick-up signal
T tripping
value of internal
time delay
counter
T1 T1
T1
MT10532
Io > Iso pick-up signal
T tripping
value of internal
time delay
counter
T1
Characteristics
Tripping curve
Setting Definite time,
IDMT: chosen according to list page 8
$ $
Iso set point
$ $
Definite time setting 0.1 Ino Iso 15 Ino (1) expressed in Amps
Sum of CTs 0.1 Ino Iso 15 Ino
With CSH sensor
2 A rating 0.2 A to 30 A
5 A rating 0.5 A to 75 A
$ $
20 A rating 2 A to 300 A
CT + CSH30 0.1 Ino Iso 15 Ino (min. 0.1 A)
Core balance CT
$ $
with ACE990 0.1 Ino < Iso < 15 Ino
$ $
IDMT time setting 0.1 Ino Iso Ino (1) expressed in Amps
Sum of CTs 0.1 Ino Iso Ino
With CSH sensor
2 A rating 0.2 A to 2 A
5 A rating 0.5 A to 75 A
$ $
20 A rating 2 A to 20 A
CT + CSH30 0.1 Ino Iso Ino (min. 0.1 A)
Core balance CT
with ACE990 0.1 Ino < Iso < Ino
Resolution 0.1 A or 1 digit
Accuracy (2) ±5%
Drop out/pick-up ratio 93.5% ±5% for Iso > 0.1 Ino
Harmonic 2 restraint
Fixed threshold 17%
(1) Ino = In if the sum of the three phase currents is used for the
$ $
Time delay T (operation time at 10 Iso)
measurement.
$ $
Setting Definite time inst. 50 ms T 300 s
Ino = sensor rating if the measurement is taken by a CSH core
balance CT. IDMT 100 ms T 12.5 s or TMS (3)
Ino = In of the CT at In/10 according to parameter setting if the Resolution 10 ms or 1 digit
measurement is taken by a 1 A or 5 A current transformer. Accuracy (2) Definite time ±2% or from -10 ms to +25 ms
(2) in reference conditions (IEC 60255-6)
IDMT class 5 or from -10 ms to +25 ms
(3) setting ranges in TMS (Time Multiplier Setting) mode
Inverse (SIT) and IECIEC SIT/A: 0.04 to 4.20 Timer hold delay T1
Very inverse (VIT) and IEC VIT/B: 0.07 to 8.33 Definite time
Very inverse (LTI) and IEC LTI/B: 0.01 to 0.93 (timer hold) 0; 0.05 to 300 s
Ext inverse (EIT) and IEC EIT/C: 0.13 to 15.47
IDMT (4) 0.5 to 20 s
IEEE moderately inverse: 0.42 to 51.86
IEEE very inverse: 0.73 to 90.57 Characteristic times
IEEE extremely inverse: 1.24 to 154.32 Operation time pick-up < 35 ms at 2 Iso (typically 25 ms)
IAC inverse: 0.34 to 42.08 inst. < 50 ms at 2 Iso (confirmed instantaneous)
IAC very inverse: 0.61 to 75.75
(typically 35 ms)
IAC extremely inverse: 1.08 to 134.4
(4) only for standardized tripping curves of the IEC, IEEE and Overshoot time < 35 ms
IAC types. Reset time < 40 ms (for T1 = 0)
Operation
This function is designed to detect the failure of breakers that do not open when a
tripping order is sent.
Automatic activation of this protection function requires the use of the program logic
circuit breaker control function. A specific input may also be used to activate the
protection from the equation editor. That option is useful for adding special cases of
activation (e.g. tripping by an external protection unit).
The time-delayed output of the protection unit should be assigned to a logic output
via the control matrix.
The starting and stopping of the time delay T counter are conditioned by the
presence of a current above the set point (I > Is).
Block diagram
MT11173
Example of setting
Below is a case that may be used to determine the time-delay setting of the breaker
failure function:
Overcurrent protection setting: T = inst.
Circuit breaker operating time: 60 ms.
Auxiliary relay operating time to open the upstream breaker or breakers: 10 ms.
MT11174
overshoot time
The breaker failure function time delay is the sum of the following times:
Sepam O1 output relay pick-up time = 10 ms
Circuit breaker opening time = 60 ms
Breaker failure function memory time = 20 ms
To avoid unwanted tripping of the upstream breakers, choose a margin of
approximately 20 ms.
This gives us a time delay T = 110 ms.
Characteristic
Is set point
Setting 0.2 In to 2 In
Accuracy ±5 %
Resolution 0.1 A
Drop out/pick-up ratio (87.5 ±10)%
Time delay
Setting 0,05 s to 300 s
Accuracy ±2 %, or from 0 to 15 ms
Resolution 10 ms or 1 digit
Characteristic time
Overshoot time < 20 ms
Taking into account of circuit breaker position
Setting With / without
MT10223
-⋅T
t = --------------------------
If Sepam is connected to 2 phase current sensors only, ( Ii ⁄ Ib ) 1 ⋅5
the negative sequence current is:
for 0.5 $ Ii/Ib $ 5
1
li = ------- x ( l1 - a l3 )
2 4 ⋅ 64
-⋅T
t = ----------------------------
3 ( Ii ⁄ Ib ) 0⋅96
2π
j ------- for Ii/Ib > 5
with a = e 3 t=T
Both formulas are equivalent when there is no zero
Schneider curve
sequence current (earth fault).
t 0
2 Ii > Is time-delayed
output
t 3
MT10228
“pick-up”
signal
Characteristics
Curve
T Setting Definite, standardized IDMT (a choice of 6), Schneider IDMT
$ $
Is set point
$ $
Setting Definite time 10% Ib Is 500% Ib
Standardized IDMT 10% Ib Is 100% Ib
Is Ii
$ $
(IEC, IEEE)
Definite time protection principle. Schneider IDMT 10% Ib Is 50% Ib
Standardized IDMT protection Resolution 1%
IDMT protection operates in accordance with the Accuracy (1) ±5%
$ $
IEC (60255-3), BS 142 and IEEE (C-37112) standards. Time delay T
$ $
t Setting Definite time 100 ms T 300 s
IDMT 100 ms T 1 s
MT10229
Resolution 10 ms ou 1 digit
Accuracy (1) Definite time ±2% or ±25 ms
IDMT ±5% or ±35 ms
Characteristic times
Operation time pick-up < 55 ms
Overshoot time < 35 ms
T
Reset time < 55 ms
(1) in reference conditions (IEC 60255-6).
1 1.2 10 20 Ii/Is
IDMT protection principle.
The Is setting is the vertical asymptote of the curve and
T is the operation time delay for 10 Is.
For currents with a very large amplitude, the protection
function has a definite time characteristic:
if Ii > 20 Is, tripping time is the time that corresponds
to 20 Is
if Ii > 40 In, tripping time is the time that corresponds
to 40 In.
50
20
max. curve (T=1s)
10
0.5
0.2
0,1
0.02
0.01
0.005
0.002
0.001 I/Ib
li (% lb) cont’d 80 85 90 95 100 110 120 130 140 150 160 170 180 190 200 210
K cont’d 5.74 5.42 5.13 4.87 4.64 4.24 3.90 3.61 3.37 3.15 2.96 2.80 2.65 2.52 2.40 2.29
li (% lb) cont’d 22. 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370
K cont’d 2.14 2.10 2.01 1.94 1.86 1.80 1.74 1.68 1.627 1.577 1.53 1.485 1.444 1.404 1.367 1.332
li (% lb) cont’d 380 390 400 410 420 430 440 450 460 470 480 490 ≥ 500
K cont’d 1.298 1.267 1.236 1.18 1.167 1.154 1.13 1.105 1.082 1.06 1.04 1.02 1
Description
The directional phase overcurrent function includes 2
MT11128
groups of 2 units called respectively Group A and
Group B.
The mode for switching from one group to the other may
be determined by parameter setting:
by remote control (TC3, TC4)
by logic input I13 (I13 = 0 group A, I13 = 1 group B)
or by forcing the use of the group.
Voltage memory
Should all the voltages disappear during a 3-phase fault
near the busbar, the voltage level may be insufficient for
the fault direction to be detected (< 1.5% Unp). The
protection function therefore uses a voltage memory to
reliably determine the direction. The fault direction is
saved as long as the voltage level is too low and the
current is above the Is set point.
Block diagram
MT11177
MT11178
MT11179
MT11180
MT11181
Tripping logic The Is setting is the vertical asymptote of the curve, and T is the operation time delay
In certain cases, it is wise to choose a tripping logic of for 10 Is.
the two out of three phases type. Such cases may occur The tripping time for I/Is values of less than 1.2 depends on the type of curve chosen.
when two parallel transformers (Dy) are being
protected. For a 2-phase fault on a transformer primary Name of curve Type
winding, there is a 2-1-1 ratio current distribution at the Standard inverse time (SIT) 1.2
secondary end. The highest current is in the expected
Very inverse time (VIT or LTI) 1.2
zone (operation zone for the faulty incomer, no
Extremely inverse time (EIT) 1.2
operation zone for the fault-free incomer).
One of the lowest currents is at the limit of the zone. Ultra inverse time (UIT) 1.2
According to the line parameters, it may even be in the RI curve 1
wrong zone. IEC standard inverse time SIT / A 1
There is therefore a risk of tripping both incomers. IEC very inverse time VIT or LTI / B 1
Time delay IEC extremely inverse time EIT / C 1
IEEE moderately inverse (IEC / D) 1
Definite time protection
IEEE very inverse (IEC / E) 1
Is is the operation set point expressed in Amps, and T
is the protection operation time delay. IEEE extremely inverse (IEC / F) 1
IAC inverse 1
t IAC very inverse 1
IAC extremely inverse 1
MT10911
The curve equations are given in the chapter entitled "IDMT protection functions".
The function takes into account current variations during the time delay interval.
For currents with a very large amplitude, the protection function has a definite time
T
characteristic:
if I > 20 Is, tripping time is the time that corresponds to 20 Is
if I > 40 In, tripping time is the time that corresponds to 40 In.
Is I (In: current transformer rated current defined when the general settings are made).
Definite time protection principle.
MT10541
type 1,2
T
T tripping
value of internal
time delay
1 1.2 10 20 I/Is counter
IDMT protection principle.
T1 T1
T1
MT10527
I > Is pick-up signal
T tripping
value of internal
time delay
counter
T1
Characteristics
Characteristic angle θ
Setting 30°, 45°, 60°
Accuracy ±2°
Tripping direction
Setting Busbar / line
Tripping logic
Setting One out of three / two out of three
Tripping curve
Setting Definite time
IDMT: chosen according to list page 16
$ $
Is set point
$ $
Setting Definite time 0.1 In Is 24 In expressed in Amps
IDMT 0.1 In Is 2.4 In expressed in Amps
Resolution 1 A or 1 digit
Accuracy (1) ±5 %
Drop out/pick-up ratio 93.5% ±5 % (with min. reset variance of
0.015 In)
$ $
Time delay T (operation time at 10 Is)
$ $
Setting Definite time inst., 50 ms T 300 s
IDMT 100 ms T 12.5 s or TMS (2)
Resolution 10 ms or 1 digit
Accuracy(1) Definite time ±2% or from -10 ms to +25 ms
IDMT Class 5 or from -10 ms to +25 ms
Timer hold delay T1
Definite time
(timer hold) 0 ; 0.05 to 300 s
IDMT (3) 0.5 to 20 s
Characteristic times
Operation time pick-up < 75 ms to 2 Is (typically 65 ms)
inst < 90 ms to 2 Is (confirmed instantaneous)
(typically 75 ms)
(1) in reference conditions (IEC 60255-6). Overshoot time < 40 ms
(2) setting ranges in TMS (Time Multiplier Setting) mode Reset time < 50 ms (for T1 = 0)
Inverse (SIT) and IEC SIT/A: 0.04 to 4.20
Very inverse (VIT) and IEC VIT/B: 0.07 to 8.33
Very inverse (LTI) and IEC LTI/B: 0.01 to 0.93
Ext inverse (EIT) and IEC EIT/C: 0.13 to 15.47
IEEE moderately inverse: 0.42 to 51.86
IEEE very inverse: 0.73 to 90.57
IEEE extremely inverse: 1.24 to 154.32
IAC inverse: 0.34 to 42.08
IAC very inverse: 0.61 to 75.75
IAC extremely inverse: 1.08 to 134.4
(3) only for standardized tripping curves of the IEC, IEEE and
IAC types.
Description
characteristic angle :
θo ≠ 0˚
MT10563
Iso set point This function comprises 2 groups of settings, with 2 units for each group.
The mode of switching groups of settings may be determined by parameter setting:
by input I13 (I13 = 0 group A, I13 = 1 group B)
θo by remote control (TC3, TC4)
operation with a single group (group A or group B).
To adapt to all cases of applications and all earthing systems, the protection function
operates according to two different types of characteristics, i.e. a choice of:
Vo type 1: the protection function uses Io vector projection
type 2: the protection function uses Io vector magnitude.
Type 1 operation
The function determines the projection of the residual current Io on the characteristic
tripping zone
line, the position of which is set by the setting of characteristic angle θo in relation to
the residual voltage. The projection value is compared to the Iso set point.
The projection method is suitable for radial feeders in resistive, isolated or
compensated neutral systems.
Tripping characteristic of protection function 67N type 1
(θo ≠ 0°). With compensated neutral systems, it is characterized by its capacity to detect very
brief, repetitive faults (recurrent faults). In the case of Petersen coils with no
additional resistance, fault detection in steady state operating conditions is not
characteristic angle : possible due to the absence of active zero sequence current. The protection function
MT10561
θo = 0˚ uses the transient current at the beginning of the fault to ensure tripping.
The θo = 0° setting is suitable for compensated neutral systems. When this setting is
sector selected, the parameter setting of the sector is used to reduce the protection tripping
Vo zone to ensure its stability on fault-free feeders.
The protection function operates with the residual current measured at the relay Io
input (operation with sum of three currents impossible). The protection function is
inhibited for residual voltages below the Vso set point. The time delay is definite time.
Iso set point
When a memory is added, recurrent faults can be detected; the memory is controlled
by a time delay or by the residual voltage value.
tripping zone
The tripping direction can be set at the busbar end or line end.
MT10534
T
Iso Io
Definite time protection principle.
Memory
The detection of recurrent faults is controlled by the time delay Tomem which extends
the transient pick-up information, thereby enabling the operation of the definite time
delay even with faults that are rapidly extinguished (≈ 2 ms) and restrike periodically.
Even when a Petersen coil with no additional resistance is used, tripping is ensured
by fault detection during the transient fault appearance, with detection extended
throughout the duration of the fault based on the Vo " Vomem criterion, within the
limit of Tomem. With this type of application, Tomem must be greater than T (definite
time delay).
Standard setting
The settings below are given for usual applications in the different earthing systems.
The shaded boxes represent default settings.
Isolated neutral Impedant neutral Compensated
neutral
Iso set point To be set according to To be set according to To be set according to
network coordination network coordination network coordination
study study study
Characteristic angle θo 90° 0° 0°
Time delay T To be set according to To be set according to To be set according to
network coordination network coordination network coordination
study study study
Direction Line Line Line
Vso setpoint 2% of Uns 2% of Uns 2% of Uns
Sector N/A 86° 86°
Memory time Tomem 0 0 200 ms
Memory voltage 0 0 0
Vomem
Characteristics type 1
Characteristic angle θo
Setting -45°, 0°, 15°, 30°, 45°, 60°, 90°
Accuracy ±5°
Tripping direction
Setting Busbar / line
$ $
Iso set point
Setting (1) 0.1 Ino Iso 15 Ino (1) expressed in Amps
$ $
With CSH sensor
$ $
2 A rating 0.2 A Iso 30 A
$ $
5 A rating 0.5 A Iso 75 A
$ $
20 A rating 2A Iso 300 A
$ $
TC + CSH30 (1) 0.1 Ino Iso 15 Ino (min. 0.1 A)
Core balance CT with 0.1 Ino Iso 15 Ino
ACE990
Resolution 0.1 A or 1 digit
$
Accuracy ±5%
Drop out/pick-up ratio 93.5% 5%
Vso set point
Setting 2% Unp to 80% Unp
Resolution 1%
Accuracy ±5 %
Sector
Setting 86°; 83°; 76°
Accuracy ±2°
$ $
Time delay T
Setting inst., 0.05 ms T 300 s
$
Resolution 10 ms or 1 digit
Accuracy 2 % or -10 ms to +25 ms
$ $
Memory time Tomem
Setting 0; 50 ms Tomem 300 s
Resolution 10 ms ou 1 digit
Memory voltage
$ $
Vomem
Setting 0; 2 % Unp Vomem 80% Unp
Resolution 1%
Characteristic times
Operation time pick-up < 35 ms
Overshoot time < 35 ms
Reset time < 35 ms (at Tomem = 0)
(1) Ino = sensor rating if the measurement is taken by a CSH120 or CSH200 core balance CT.
Ino = In of the CT if the measurement is taken by a 1 A or 5 A current transformer + CSH30.
Ino = In of the CT /10 if the measurement is taken by a 1 A or 5 A current transformer + CSH30
with the sensitivity x 10 option.
Type 2 operation
The protection function operates like an earth fault protection function with an added
direction criterion.
It is suitable for closed ring distribution networks with directly earthed neutral. It has
θo all the characteristics of an earth fault protection function (50N/51N) and can
therefore be easily coordinated with that function.
The residual current is the current measured at the Sepam Io input or calculated
tripping zone using the sum of the phase currents, according to the parameter setting.
Vo The time delay may be definite time (DT) or IDMT according to the curves below.
The protection function includes a timer hold delay T1 for the detection of restriking
faults.
The tripping direction may be set at the busbar end or line end.
Iso set point
Definite time protection
Iso is the operation set point expressed in Amps, and T is the protection operation
time delay.
t
MT10534
Iso Io
IDMT protection
The IDMT protection function operates in accordance with the IEC (60255-3),
BS 142 and IEEE (C-37112) standards.
type 1
MT10544
t
type 1.2
1 1.2 10 20 Io/Iso
The Is setting is the vertical asymptote of the curve, and T is the operation time delay
for 10 Iso.
The tripping time for Io/Iso values of less than 1.2 depends on the type of curve
chosen.
Block diagram
MT11163
T tripping
value of internal
time delay
counter
T1 T1
T1
T tripping
value of internal
time delay
counter
T1
Characteristics type 2
Characteristic angle θo
Setting -45°, 0°, 15°, 30°, 45°, 60°, 90°
Accuracy ±5°
Tripping direction
Setting Busbar / line
$ $
Iso setting
$ $
Definite time setting 0.1 Ino Iso 15 Ino (1) expressed in Amps
Sum of CTs 0.1 Ino Iso 15 Ino
With CSH sensor
2 A rating 0.2 A to 30 A
5 A rating 0.5 A to 75 A
$ $
20 A rating 2 A to 300 A
CT + CSH30 0.1 Ino Iso 15 Ino (min. 0.1 A)
Core balance CT with 0.1 Ino < Iso < 15 Ino
$ $
ACE990
$ $
Definite time setting 0.1 Ino Iso Ino(1) expessed in Amps
Sum of CTs 0.1 Ino Iso Ino
With CSH sensor
2 A rating 0.2 A to 2 A
5 A rating 0.5 A to 5 A
$ $
20 A rating 2 A to A
$ $
CT + CSH30 0.1 Ino Iso 1 Ino (min. 0.1 A)
Core balance CT with 0.1 Ino Iso Ino
ACE990
Resolution 0.1 A or 1 digit
Accuracy (2) ±5 %
Drop out/pick up ratio 93.5 % ±5 %
Vso set point
Setting 2 % Un to 80 % Un
Resolution 1%
Accuracy ±5 %
Sector
(1) Ino = In if the sum of the three phase currents is used for the Setting 86°; 83°; 76°
measurement. Accuracy ±2°
Ino = sensor rating if the measurement is taken by a CSH120
$ $
or CSH200 core balance CT. Time delay T (operation time at 10 Iso)
$ $
Ino = In of the CT if the measurement is taken by a 1 A or 5 A Setting definite time inst., 50 ms T 300 s
current transformer + CSH30. IDMT 100 ms T 12.5 s or TMS (3)
Ino = In of the CT /10 if the measurement is taken by a 1 A or
5 A current transformer + CSH30 with the sensitivity x 10 Resolution 10 ms or 1 digit
option. Accuracy (2) definite time 2% or -10 ms to +25 ms
(2) in reference conditions (IEC 60255-6)
IDMT Class 5 or from -10 to +25 ms
(3) setting ranges in TMS (Time Multiplier Setting) mode
$ $
Inverse (SIT) et IEC SIT/A: 0.04 to 4.20 Timer hold delay T1
Very inverse (VIT) and IEC VIT/B:0.07 to 8.33
$ $
Definite time (timer hold) 0; 0.50 ms T1 300 s
Very inverse (LTI) and IEC LTI/B:0.01 to 0.93
Ext inverse (EIT) and IEC EIT/C: 0.13 to 15.47 IDMT (4) 0.5 s T1 20 s
IEEE moderately inverse:0.42 to 51.86 Characteristic times
IEEE very inverse: 0.73 to 90.57 Operation time pick up < 35 ms at 2 Iso (typically 25 ms)
IEEE extremely inverse: 1.24 to 154.32
IAC inverse: 0.34 to 42.08 inst. < 50 ms at 2 Iso (confirmed
IAC very inverse: 0.61 to 75.75 instantaneous) (typically 35 ms)
IAC extremely inverse:1.08 to 134.4 Overshoot time < 35 ms
(4) only for standardized tripping curves of the IEC, IEEE and Reset time < 40 ms (for T1 = 0)
IAC types.
Operation
MT11165
The power sign is determined according to the general feeder or incomer parameter,
iaccording to the convention:
Operating zone. for the feeder circuit:
# power exported by the busbar is positive
# power supplied to the busbar is negative.
MT11183
Block diagram
MT11166
Characteristics
Tripping direction
Setting overpower/reverse power
Ps set point
Setting 1 % Sn(1) to 120 % Sn (1)
Resolution 0.1 kW
Accuracy (2) ±0.3 % Sn for Ps between 1 % Sn and 5 % Sn
±5 % for Ps between 5 % Sn and 40 % Sn
±3 % for Ps between 40 % Sn and 120 % Sn
Drop out/pick up ratio (93.5 ±5) %
Min. return variance 0.004 Sn
Time delay T
Setting 100 ms to 300 s
Resolution 10 ms or 1 digit
Accuracy (2) ±2 %, or from - 10 ms to +25 ms
Characteristic times
Operation time < 80 ms
Overshoot time < 90 ms
Reset time < 80 ms
(1) Sn = .Unp.In
(2) in reference conditions (IEC 60255-6).
Operation
MT11167
reverse
MT11183
power
Block diagram
MT11168
Characteristics
Tripping direction
Setting overpower/reverse power
Qs set point
Setting 5 % Sn(1) to 120 % Sn (1)
Resolution 0.1 var
Accuracy (2) ±5 % for Qs between 5 % Sn and 40 % Sn
±3 % for Qs between 40 % Sn and 120 % Sn
Drop out/pick up ratio (93.5 ±5) %
Time delay T
Setting 100 ms to 300 s
Resolution 10 ms or 1 digit
Accuracy (2) ±2 %, or from -10 ms to ±25 ms
Characteristic times
Operation time < 80 ms
Overshoot time < 90 ms
Reset time < 80 ms
(1) Sn = .Unp.In
Description For self-ventilated rotating machines, cooling is more effective when the machine is
This function is used to protect equipment (motors, running than when it is stopped. Running and stopping of the equipment are
transformers, generators, lines, capacitors) against calculated from the value of the current:
overloads, based on measurement of the current running if I > 0.1 Ib
consumed. stopped if I < 0.1 Ib.
Two time constants may be set:
Operation curve
T1: heat rise time constant: concerns equipment that is running
The protection gives a trip order when the heat rise E,
T2: cooling time constant: concerns equipment that is stopped.
calculated according to the measurement of an
equivalent current Ieq, is greater than the set point Es. Accounting for harmonics
The greatest permissible continuous current is The current measured by the thermal protection is an RMS 3-phase current which
I = Ib Es takes into account harmonics up to number 17.
The protection tripping time is set by the time Accounting for ambient temperature
constant T. Most machines are designed to operate at a maximum ambient temperature of 40°.
the calculated heat rise depends on the current The thermal overload function takes into account the ambient temperature
consumed and the previous heat rise state (Sepam 1000+ equipped with the temperature sensor option (1)) to increase the
the cold curve defines the protection tripping time calculated heat rise value when the temperature measured exceeds 40°.
based on zero heat rise Tmax – 40°
the hot curve defines the protection tripping time Increase factor: fa = -----------------------------------------------------
Tmax – Tambient
based on 100 % nominal heat rise.
in which T max is the machine’s maximum temperature.
101 Cold curve T ambient is the measured temperature.
2
leq
---------
MT10858
MT10420
1
Learning of the cooling time constant T2
0,63 The cooling time constant T2 may be learnt according to the temperatures measured
0,36 in the equipment by temperature sensors connected to the MET148-2 module.
T2 is calculated every time that the equipment runs for a sufficient time, followed by
0 0 a shutdown (I < 0.1Ib) and temperature stabilization.
T1 t T2 t For motors and generators, T2 is calculated according to the temperatures measured
Heat rise time constant. Cooling time constant. on the stator by RTDs 1, 2 and 3.
For transformers, T2 is calculated according to the temperatures measured on the
primary winding by RTDs 1, 3 and 5.
For better accuracy, it is advisable to measure the ambient temperature with RTD 8.
If in the RTD assignment table, «other applications» is selected, T2 is not calculated.
Once the calculation has been made, the calculated value may be used to replace
the T2 (2) parameter in two ways according to the configuration:
automatically, in which case each new calculated value updates the T2 constant
used
or manually by entering the value in the T2 parameter.
(1) MET148-2 module, RTD 8 predefined for ambient temperature measurement.
(2) it is advisable to use the calculated T2 if the equipment has carried out at least three starting
cycles followed by cooling.
Start inhibit Switching from one group of thermal settings to the other is done without losing the
The thermal overload protection can inhibit the closing heat rise value. It is controlled:
of the motor’s control device until the heat rise drops either via a logic input, assigned to the "switching of thermal settings" function
back down below a value that allows restarting. or when the phase current reaches an adjustable Is set point (to be used to
This value takes into account the heat rise produced by process the switching of thermal settings of a motor with locked rotor).
the motor when starting. User information
The inhibition function is grouped together with the The following information is available for the user:
starts per hour protection and the indication START heat rise
INHIBIT informs the user. learnt cooling time constant T2
time before restart enabled (in case of inhibition of starting)
Saving of heat rise time before tripping (with constant current).
The current heat rise is saved in the event of an auxiliary See chapter "Machine operation assistance functions".
power failure.
Characteristics
Inhibition of tripping
Set point Rate 1 Rate 2
Tripping of the thermal overload protection may be
Setting Es1 alarm set point 50% to 300% 50% to 300%
inhibited by the logic input "Inhibit thermal overload"
Es2 tripping set point 50% to 300% 50% to 300%
when required by the process.
Eso initial heat rise 0 to 100% 0 to 100%
Resolution 1% 1%
Use of two operating rates Time constants
The thermal overload protection function may be used Setting T1 running (heat rise) 1 mn to 600 mn 1 mn to 600 mn
to protect equipment with two operating rates, for
T2 stopped (cooling) 5 mn to 600 mn 5 mn to 600 mn
example:
Resolution 1 mn 1 mn
transformers with two ventilation modes, with or
Accounting for negative sequence component
without forced ventilation (ONAN / ONAF)
Setting K 0 - 2,25 - 4,5 - 9
two-speed motors.
Maximum equipment temperature (insulation class)
The protection function comprises two groups of
settings, and each group is suitable for equipment Setting Tmax 60° to 200°
protection in one of the two operating rates. Resolution 1°
The equipment’s basis current, used to calculate heat Tripping time
rise, also depends on the operating rate: Accuracy(1) 2%
with rate 1, the basis current Ib, defined as a general Change of operating rate
Sepam parameter, is used to calculate the heat rise in By current threshold Is Setting 0,25 to 8 Ib
the equipment By logic input "Switching of thermal settings"
with rate 2, the basis current Ib-rate 2, a specific Basis current for thermal operating rate 2
thermal overload protection setting, is used to calculate Setting 0,2 to 2,6 In
the heat rise in the equipment. Use of learnt cooling time constant (T2)
Setting Yes / no
(1) in reference conditions (IEC 60255-6).
Block diagram
MT10859
Example 1 For an overload of 2*Ib, the value t/T1 = 0.0339 (2) is obtained.
The following data are available: In order for Sepam to trip at the point 1 (t = 70 s), T1 is equal to 2065 sec ≈ 34 min.
time constants for on operation T1 and off operation With a setting of T1 = 34 min, the tripping time is obtained based on a cold state (point
T2: 2). In this case, it is equal to t/T1 = 0.3216 ⇒ t ⇒ 665 sec, i.e. ≈ 11 min, which is
# T1 = 25 min compatible with the thermal resistance of the motor when cold.
# T2 = 70 min The negative sequence factor is calculated using the equation defined on page 34.
maximum curve in steady state: Imax/Ib = 1.05. The parameters of the second thermal overload relay do not need to be set.
They are not taken into account by default.
Setting of tripping set point Es2
Es2 = (Imax/Ib)2 = 110% Example 3
Please note: if the motor absorbs a current of 1.05 Ib in The following data are available:
steady state, the heat rise calculated by the thermal motor thermal resistance in the form of hot and cold curves (see solid line curves
overload protection will reach 110%. in Figure 1),
Setting of alarm set point Es1 cooling time constant T2
Es1 = 90% (I/Ib = 0.95). maximum steady state current: Imax/Ib = 1.1.
Knegative: 4.5 (usual value) The thermal overload parameters are determined in the same way as in the previous
The other thermal overload parameters do not need to example.
be set. They are not taken into account by default. Setting of tripping set point Es2
Es2 = (Imax/Ib)2 = 120%
Example 2
The following data are available: Setting of alarm set point Es1
motor thermal resistance in the form of hot and cold Es1 = 90% (I/Ib = 0.95).
curves (see solid line curves in Figure 1) The time constant T1 is calculated so that the thermal overload protection trips after
cooling time constant T2 100 s (point 1).
maximum steady state current: Imax/Ib = 1.05. With t/T1 = 0.069 (I/Ib = 2 and Es2 = 120%):
⇒ T1 = 100s / 0.069 = 1449 sec ≈ 24 min.
Setting of tripping set point Es2
The tripping time starting from the cold state is equal to:
Es2 = (Imax/Ib)2 = 110%
t/T1 = 0.3567 ⇒ t = 24 min*0.3567 = 513 s (point 2’).
Setting of alarm set point Es1: This tripping time is too long since the limit for this overload current is 400 s (point 2).
Es1 = 90% (I/Ib = 0.95). If the time constant T1 is lowered, the thermal overload protection will trip earlier,
The manufacturer’s hot/cold curves (1) may be used to below point 2.
determine the heating time constant T1. There risk that motor starting when hot will not be possible also exists in this case
The method consists of placing the Sepam hot/cold (see Figure 2 in which a lower Sepam hot curve would intersect the starting curve
curves below those of the motor. with U = 0.9 Un).
The Es0 parameter is a setting that is used to solve these differences by lowering
the Sepam cold curve without moving the hot curve.
In this example, the thermal overload protection should trip after 400 s starting from
the cold state.
The following equation is used to obtain the Es0 value:
t ne cess ary
2 ---------------------- 2
l T
Eso = -------------------- – e 1
processed . l-------------------
processed – Es2
-
lb lb
Figure 1: motor thermal resistance and thermal with:
overload tripping curves t necessary : tripping time necessary starting from a cold state.
I processed : equipment current.
MT10860
motor cold curve (1) When the machine manufacturer provides both a time constant T1 and the machine hot/cold
Sepam cold curve curves, the use of the curves is recommended since they are more accurate.
(2) The charts containing the numerical values of the Sepam hot curve may be used, or else
the equation of the curve which is given on page 10.
time before tripping/s
1.05 2 I/Ib
In numerical values, the following is obtained: Use of the additional setting group
400 sec When a motor rotor is locked or is turning very slowly, its thermal behavior is different
---------------------------
4 – 1.2 = 0.3035 ≈ 31%
Eso = 4 – e 24x60sec . from that with the rated load. In such conditions, the motor is damaged by
overheating of the rotor or stator. For high power motors, rotor overheating is most
By setting Es0 = 31%, point 2’ is moved downward to often a limiting factor.
obtain a shorter tripping time that is compatible with the The thermal overload parameters chosen for operation with a low overload are no
motor’s thermal resistance when cold (see Figure 3). longer valid.
Please note: A setting Es0 = 100% therefore means In order to protect the motor in this case, “excessive starting time” protection may be
that the hot and cold curves are the same. used.
Nevertheless, motor manufacturers provide the thermal resistance curves when the
Figure 2: hot/cold curves not compatible with the rotor is locked, for different voltages at the time of starting.
motor’s thermal resistance
Figure 4: Locked rotor thermal resistance
Sepam cold curve motor running locked rotor
MT10861
MT10863
513 2’
motor cold curve
time before tripping/s
400 2
motor hot curve
times / s
1
100 1 Sepam hot curve
3
2
starting at Un
starting at 0.9*Un
1.05 2 I/Ib 4 5 6
1.1 2 Is I/Ib
Figure 3: hot/cold curves compatible with the ➀: thermal resistance, motor running
motor’s thermal resistance via the setting of an ➁: thermal resistance, motor stopped
initial heat rise Eso ➂: Sepam tripping curve
➃: starting at 65% Un
➄: starting at 80% Un
➅: starting at 100% Un
MT10862
adjusted Sepam
cold curve In order to take these curves into account, the second thermal overload relay may be
motor cold curve used.
time before tripping/s
The time constant in this case is, in theory, the shortest one: however, it should not
400 be determined in the same way as that of the first relay.
2
motor hot curve
The thermal overload protection switches between the first and second relay if the
equivalent current Ieq exceeds the Is value (set point current).
100
1 Sepam hot curve
I/Ib 1.85 1.90 1.95 2.00 2.20 2.40 2.60 2.80 3.00 3.20 3.40 3.60 3.80 4.00 4.20 4.40 4.60
Es (%)
105 0.0209 0.0193 0.0180 0.0168 0.0131 0.0106 0.0087 0.0073 0.0063 0.0054 0.0047 0.0042 0.0037 0.0033 0.0030 0.0027 0.0025
110 0.0422 0.0391 0.0363 0.0339 0.0264 0.0212 0.0175 0.0147 0.0126 0.0109 0.0095 0.0084 0.0075 0.0067 0.0060 0.0055 0.0050
115 0.0639 0.0592 0.0550 0.0513 0.0398 0.0320 0.0264 0.0222 0.0189 0.0164 0.0143 0.0126 0.0112 0.0101 0.0091 0.0082 0.0075
120 0.0862 0.0797 0.0740 0.0690 0.0535 0.0429 0.0353 0.0297 0.0253 0.0219 0.0191 0.0169 0.0150 0.0134 0.0121 0.0110 0.0100
125 0.1089 0.1007 0.0934 0.0870 0.0673 0.0540 0.0444 0.0372 0.0317 0.0274 0.0240 0.0211 0.0188 0.0168 0.0151 0.0137 0.0125
130 0.1322 0.1221 0.1132 0.1054 0.0813 0.0651 0.0535 0.0449 0.0382 0.0330 0.0288 0.0254 0.0226 0.0202 0.0182 0.0165 0.0150
135 0.1560 0.1440 0.1334 0.1241 0.0956 0.0764 0.0627 0.0525 0.0447 0.0386 0.0337 0.0297 0.0264 0.0236 0.0213 0.0192 0.0175
140 0.1805 0.1664 0.1540 0.1431 0.1100 0.0878 0.0720 0.0603 0.0513 0.0443 0.0386 0.0340 0.0302 0.0270 0.0243 0.0220 0.0200
145 0.2055 0.1892 0.1750 0.1625 0.1246 0.0993 0.0813 0.0681 0.0579 0.0499 0.0435 0.0384 0.0341 0.0305 0.0274 0.0248 0.0226
150 0.2312 0.2127 0.1965 0.1823 0.1395 0.1110 0.0908 0.0759 0.0645 0.0556 0.0485 0.0427 0.0379 0.0339 0.0305 0.0276 0.0251
155 0.2575 0.2366 0.2185 0.2025 0.1546 0.1228 0.1004 0.0838 0.0712 0.0614 0.0535 0.0471 0.0418 0.0374 0.0336 0.0304 0.0277
160 0.2846 0.2612 0.2409 0.2231 0.1699 0.1347 0.1100 0.0918 0.0780 0.0671 0.0585 0.0515 0.0457 0.0408 0.0367 0.0332 0.0302
165 0.3124 0.2864 0.2639 0.2442 0.1855 0.1468 0.1197 0.0999 0.0847 0.0729 0.0635 0.0559 0.0496 0.0443 0.0398 0.0360 0.0328
170 0.3410 0.3122 0.2874 0.2657 0.2012 0.1591 0.1296 0.1080 0.0916 0.0788 0.0686 0.0603 0.0535 0.0478 0.0430 0.0389 0.0353
175 0.3705 0.3388 0.3115 0.2877 0.2173 0.1715 0.1395 0.1161 0.0984 0.0847 0.0737 0.0648 0.0574 0.0513 0.0461 0.0417 0.0379
180 0.4008 0.3660 0.3361 0.3102 0.2336 0.1840 0.1495 0.1244 0.1054 0.0906 0.0788 0.0692 0.0614 0.0548 0.0493 0.0446 0.0405
185 0.4321 0.3940 0.3614 0.3331 0.2502 0.1967 0.1597 0.1327 0.1123 0.0965 0.0839 0.0737 0.0653 0.0583 0.0524 0.0474 0.0431
190 0.4644 0.4229 0.3873 0.3567 0.2671 0.2096 0.1699 0.1411 0.1193 0.1025 0.0891 0.0782 0.0693 0.0619 0.0556 0.0503 0.0457
195 0.4978 0.4525 0.4140 0.3808 0.2842 0.2226 0.1802 0.1495 0.1264 0.1085 0.0943 0.0828 0.0733 0.0654 0.0588 0.0531 0.0483
200 0.5324 0.4831 0.4413 0.4055 0.3017 0.2358 0.1907 0.1581 0.1335 0.1145 0.0995 0.0873 0.0773 0.0690 0.0620 0.0560 0.0509
MT10429
& time-delayed
set point output”
it is inactive when the current is less than 10% of Ib
it is insensitive to current drops (breaking) due to “pick-up”
circuit breaker tripping signal
it includes a definite time delay T. I>
0.1 Ib
$ $
T time delay
T Setting 50 ms T 300 s
Accuracy (1) ± 2% or ± 25 ms
Resolution 10 ms or 1 digit
0 0,1 Ib Is I Characteristic times
Operation time < 60 ms
Overshoot time < 35 ms
Reset time < 40 ms
Operating principle (1) in reference conditions (IEC 60255-6).
1.06 Is
Is
MT10865
0.1 Ib
“pick up”
signal
time-delayed
output
Case of current sag.
1.06 Is
Is
MT10866
0.1 Ib
“pick up”
signal = 0 <15 ms
time-delayed
output = 0
Case of circuit breaker tripping.
I Operation
MT10430
I
Motor re-acceleration
MT10431
When the motor re-accelerates, it consumes a current in the vicinity of the starting
current (> Is) without the current first passing through a value less than 10% of Ib.
Is
The ST time delay, which corresponds to the normal starting time, may be
reinitialized by the logic input "motor re-acceleration" which:
reinitialize the excessive starting time protection,
0.1Ib set the locked rotor protection LT time delay to a low value.
ST
Starting is detected when the current consumed is 10% greater than the Ib curent.
excessive
starting time An output is set when starting is in progress, to be used in the equation editor.
locked
rotor
Case of excessive starting time.
Block diagram
I
MT10432
MT11169
Is
0.1Ib
excessive ST LT
starting time
locked
rotor
Case of locked rotor.
Characteristics
$ $
Is set point
Setting 50 % Ib Is 500 % Ib
Resolution 1%
Accuracy (1) ±5 %
Drop out/pick up ratio 93.5 % ±5 %
$ $
Time delay ST, LT and LTS
$ $
Setting ST 500 ms T 300 s
$ $
LT 50 ms T 300 s
LTS 50 ms T 300 s
Resolution 10 ms or 1 digit
Accuracy (1) ±2 % or ±25 ms
(1) in reference conditions (IEC 60255-6).
Operation
This function is three-phase.
It picks up when the number of starts reaches the following limits:
maximum number of starts (Nt) allowed per period of time (P)
maximum allowed number of consecutive hot starts (Nh)
maximum allowed number of consecutive cold starts (Nc).
Starting is detected when the current consumed becomes greater than 10% of the Ib
current.
The number of consecutive starts is the number starts counted during the last P/Nt
minutes, Nt being the number of starts allowed per period.
The motor hot state corresponds to the overshooting of the fixed set point (50% heat
rise) of the thermal overload function.
When the motor re-accelerates, it undergoes a stress similar to that of starting
without the current first passing through a value less than 10% of Ib, in which case
the number of starts is not incremented.
It is possible however to increment the number of starts when a re-acceleration
occurs by a logic data input (logic input "motor re-acceleration").
The "stop/start" time delay T may be used to inhibit starting after a stop until the delay
has elapsed.
Use of circuit breaker closed data
In synchronous motor applications, it is advisable to connect the "circuit breaker
closed" data to a logic input in order to enable more precise detection of starts. If the
"circuit breaker closed" data is not connected to a logic input, the detection of a start
is not conditioned by the position of the circuit breaker.
User information
The following information is available for the user:
the waiting time before a start is allowed
the number of starts still allowed.
See chapter "Machine operation assistance functions".
Block diagram
MT11170
Characteristics
Period of time (P)
Setting 1 to 6 hour
Resolution 1
Nt total number of starts
Setting 1 to 60
Resolution 1
Nh and Nc number of consecutive starts
Setting(1) 1 to Nt
Resolution 1
T time delay stop/start $ $
Setting 0 mn T 90 mn
$
Resolution 1 mn or 1 digit
(1) With Nh Nc.
Operation
Positive sequence undervoltage
The protection picks up when the positive sequence component Vd of a three-phase
voltage system drops below the Vsd set point with
2
Vd = ( 1 ⁄ 3 ) [ V1 + aV2 + a V3 ]
2
Vd = ( 1 ⁄ 3 ) [ U21 – a U32 ]
2π
j -------
U 3
with V = ------- and a = e
3
Block diagram
MT10872
Characteristics
Vsd set point
Setting 15 % Unp to 60 % Unp
Accuracy (1) ±2 %
Pick-up/drop-out ratio 103 % ±2.5 %
Resolution 1%
Time delay
Setting 50 ms to 300 s
Accuracy (1) ±2 %, or ±25 ms
Resolution 10 ms or 1 digit
Characteristic times
Operating time pick up < 55 ms
Overshoot time < 35 ms
Reset time < 35 ms
(1) in reference conditions (IEC 60255-6).
Operation
This protection is single-phase:
it picks up when the U21 phase-to-phase voltage is less than the Us set point
the protection includes a definite time delay.
Block diagram
T 0
U21 U < Us time-delayed output
MT10875
(or V1)
“pick-up” signal
Characteristics
Us set point
Setting 5 % Unp to 100 % Unp
Accuracy (1) ±5 % or ±0.005 Unp
Resolution 1%
Drop out/pick up ratio 104 % ±3 %
Time delay T
Setting 50 ms to 300 s
Accuracy (1) ±2 %, or ±25 ms
Resolution 10 ms or 1 digit
Characteristic times
Operation time < 40 ms
Overshoot time < 20 ms
Reset time < 30 ms
(1) in reference conditions (IEC 60255-6).
Operation
The protection function is three-phase and operates according to parameter setting
with phase-to-neutral or phase-to-phase voltage:
it picks up if one of the 3 phase-to-neutral or phase-to-phase voltages drops below
the Us/Vs set point
it includes a definite time delay T
with phase-to-neutral operation, it indicates the faulty phase in the alarm
associated with the fault.
Block diagram
U21/V1 T 0
< Us/ Vs
MT10230
U32/V2 T 0
< Us/ Vs 1 time-delayed
output
U13/V3 T 0
< Us/ Vs
1 “pick-up” signal
Characteristics
Us/Vs set point
Setting 5% Unp/Vnp to 100% Unp/Vnp
Accuracy (1) ±2% or ±0.005 Vnp
Resolution 1%
Drop out/pick up ratio 103% ±2.5%
Time delay T
Setting 50 ms to 300 s
Accuracy (1) ±2%, or ±25 ms
Resolution 10 ms or 1 digit
Characteristic times
Operation time pick-up < 35 ms (typically 25 ms)
Overshoot time < 35 ms
Reset time < 40 ms
(1) in reference conditions (IEC 60255-6).
Connection conditions
Type of connection V1V2V3 U21 U21/U32 U21 + Vo U21/U32 +Vo
Phase-to-neutral Yes No No No Yes
operation
Phase-to-phase Yes on U21 only Yes on U21 only Yes
operation
Operation
The protection function is single-phase and operates with phase-to-neutral or phase-
to-phase voltage:
it picks up if one of the voltages concerned is above the Us/Vs set point
it includes a definite time delay T
with phase-to-neutral operation, it indicates the faulty phase in the alarm
associated with the fault.
Block diagram
U21/V1 T 0
> Us/ Vs
MT10553 U32/V2 T 0
> Us/ Vs 1 time-delayed output
U13/V3 T 0
> Us/ Vs
1 “pick-up” signal
Characteristics
Us/Vs set point
Setting 50 % Unp/Vnp to 150% Unp/Vnp(2)
Accuracy (1) ±2 % or ±0.005 Unp
Resolution 1%
Drop out/pick up ratio 97 % ±1 %
Time delay T
Setting 50 ms to 300 s
Accuracy (1) ±2%, or ±25 ms
Resolution 10 ms or 1 digit
Characteristic times
Operation time pick-up < 35 ms (typically 25 ms)
Overshoot time < 35 ms
Reset time < 40 ms
Connnection conditions
Type of connection V1V2V3 U21 U21/U32 U21 + Vo U21/U32 +Vo
Phase-to-neutral Yes No No No Yes
operation
Phase-to-phase Yes on U21 only Yes on U21 only Yes
operation
Operation
The protection function picks up if the residual voltage Vo is above a Vso set point,
with Vo = V1 + V2 + V3 ,
it includes a definite time delay T.
the residual voltage is either calculated from the 3 phase voltages or measured by
an external VT
the protection function operates for connections: V1V2V3, U21/U32 + Vo and
U21 + Vo.
Block diagram
V1
MT10548
V2 Σ
V3
T 0
Vo > Vso time-delayed output
external VT
“pick-up” signal
Characteristics
Vso set point
Setting 2 % Unp to 80 % Unp if Vnso (2) = sum of 3Vs
2 % Unp to 80 % Unp if Vnso(2) = Uns
5 % Unp to 80 % Unp if Vnso(2) = Uns
Accuracy (1) ±2 % or ±0.005 Unp
Resolution 1%
Drop out/pick up ratio 97 % ±1 %
Temporisation T
Setting 50 ms to 300 s
Accuracy (1) ±2 %, or ±25 ms
Resolution 10 ms or 1 digit
Characteristic times
Operation time pick-up < 35 ms
Overshoot time < 35 ms
Reset time < 40 ms
(1) in reference conditions (IEC 60255-6).
(2) Vnso is one of the general settings.
Operation
The protection function picks up if the negative sequence component of the voltages
(Vi) is above the set point (Vsi).
it includes a definite time delay T
the negative sequence voltage Vi is determined from the three phase voltages:
Vi = --- V1 + a V2 + aV3
1 2
3
or
Vi = --- [ U21 – aU32 ]
1
3
2π
j -------
with a = e 3
Block diagram
U21 T 0
Vi >Vsi time-delayed output
MT10554
U32
“pick-up” signal
Characteristics
Vsi set point
"
Setting 1 % Unp to 50 % Unp
Accuracy (1) ±2 % for Vi 10 % Unp
±5 % for Vi < 10 % Unp
"
Resolution 1%
Drop out/pick up ratio (97 ±2.5) % at Vi 10 % Unp
Time delay T
Setting 50 ms to 300 s
Accuracy (1) ±2 %, or ±25 ms
Resolution 10 ms or 1 digit
Characteristic times
Operation time pick-up < 55 ms
Overshoot time < 35 ms
Reset time < 55 ms
(1) in reference conditions (IEC 60255-6).
Operation
The protection function picks up when the positive sequence voltage frequency is
above the Fs set point and the positive sequence voltage is above the Vs set point.
If a single VT is connected (U21), the function picks up when the frequency is above
the Fs set point and the U21 voltage is above the Vs set point.
It includes a definite time delay T.
Block diagram
MT11171
Characteristics
Fs set point
Setting 50 to 53 Hz or 60 to 63 Hz
Accuracy (1) ±0.02 Hz
Resolution 0.1 Hz
Pick up / drop out difference 0.25 Hz ±0.1 Hz
Vs set point
Setting 20% Unp to 50% Unp
Accuracy (1) ±2%
Resolution 1%
Time delay T
Setting 100 ms to 300 s
Accuracy (1) ±2% or ±25 ms
Resolution 10 ms or 1 digit
Characteristic times (1)
Operation time pick-up < 80 ms (typically 80 ms)
Overshoot time < 40 ms
Reset time < 50 ms
(1) in reference conditions (IEC 60255-6).
Operation
The function picks up when the positive sequence voltage frequency is below the Fs
set point and if the negative sequence voltage is above the Vs set point.
If a single VT is connected (U21), the function picks up when the frequency is below
the Fs set point and the U21 voltage is is above the Vs set point.
It includes a definite time delay T.
The protection function includes a restraint which may be configured according to the
rate of change of frequency which inhibits the protection in the event of a continuous
decrease in frequency greater than the inhibition set point.
This setting avoids the tripping of all the feeders when the busbar is resupplied by
remanent motor voltage following the loss of the incomer.
Characteristics
Fs set point
Setting 40 to 50 Hz or 50 to 60 Hz
Accuracy (1) ±0.02 Hz
Resolution 0.1 Hz
Pick-up / drop out difference 0.25 Hz ±0.1 Hz
Vs set point
Setting 20 % Unp to 50 % Unp
Accuracy (1) 2%
Resolution 1%
Restraint on frequency variation
Setting With / without
dFs/dt set point 1 Hz/s to 15 Hz/s
Accuracy (1) 1 Hz/s
Resolution 1 Hz/s
Time delay T
Setting 100 ms to 300 s
Accuracy(1) ±2% or ±25 ms
Resolution 10 ms or 1 digit
Characteristic times(1)
Operation time pick-up < 80 ms
Overshoot time < 40 ms
Reset time < 50 ms
(1) in reference conditions (IEC 60255-6).
Characteristics
Reclosing cycles Setting
Number of cycles 1 to 4
Activation of cycle 1 (1) max I 1 to 4 inst. / delayed / no activation
max Io 1 to 4 inst. / delayed / no activation
directional max I 1 to 2 inst. / delayed / no activation
directional max Io 1 to 2 inst. / delayed / no activation
V_TRIPCB output activation / no activation
(logical equation)
Activation of cycles 2, 3 and 4 (1) max I 1 to 4 inst. / delayed / no activation
max Io 1 to 4 inst. / delayed / no activation
directional max I 1 to 2 inst. / delayed / no activation
directional max Io 1 to 2 inst. / delayed / no activation
V_TRIPCB output activation / no activation
(logical equation)
Time delays
Reclaim time 0.1 to 300 s
Dead time cycle 1 0.1 to 300 s
cycle 2 0.1 to 300 s
cycle 3 0.1 to 300 s
cycle 4 0.1 to 300 s
Safety time until 79 ready 0 to 60 s
Maximum additional dead time 0.1 to 60 s
(Twait_max)
Accuracy ±2% or 25 ms
Resolution 10 ms or 1 digit
(1) If a protection function that does not activate reclosing cycles leads to circuit breaker opening,
the recloser is inhibited.
Operation
This protection is associated with an RTD of the Pt100 platinum (100 Ω at 0 °C) or
(nickel 100 Ω, nickel 120 Ω) type in accordance with the IEC 60751 and DIN 43760
standards.
it picks up when the monitored temperature is greater than the Ts set point
it has two independent set points:
# alarm set point
# tripping set point
when the protection is activated, it detects whether the RTD is shorted or
disconnected:
# RTD shorting is detected if the measured temperature is less than -35 °C
(measurement displayed “****”)
# RTD disconnection is detected if the measured temperature is greater than
+205 °C (measurement displayed “-****”).
If an RTD fault is detected, the set point output relays are inhibited: the protection
outputs are set to zero.
The "RTD fault" item is also made available in the control matrix and an alarm
message is generated specifying the faulty RTD module.
Block diagram
MT10878
T < +205 ˚C
& T > Ts1 set point 1
Characteristics
Ts1 and Ts2 set points °C °F
Setting 0 °C to 180 °C 32 °F to 356 °F
Accuracy (1) ± 1,5 °C ± 2.7 °F
Resolution 1 °C 1 °F
Pick-up/drop-out difference 3 °C ± 0,5 °
Characteristic times
Tripping time < 5 seconds
(1) see temperature measurement chapter for accuracy derating according to wiring cross-
section
Operation time depends on the type of protection The time delay setting that should be made in order for the operation curve to pass
(phase current, earth fault current, …). through the point k(Ik, tk) is:
Operation is represented by a characteristic curve:
t = f(I) curve for the phase overcurrent function tk
ts
T = Ts10 × ---------
MT10537
t = f(Io) curve for the earth fault function. tsk
The rest of the document is based on t = f(I); the
reasoning may be extended to other variables Io,…
The curve is defined by:
tk k
type (standard inverse, very inverse, extremely
inverse...)
tsk
current setting Is which corresponds to the vertical
asymptote of the curve Ts10
time delay T which corresponds to the operation time
for I = 10 Is.
tA
T
tsA
Ts10
1 IA/Is 10 I/Is
Table of values of K
I/Is SIT VIT, LTI EIT UIT RI IEEE MI IEEE VI IEEE EI IAC I IAC VI IAC EI
and IEC/A and IEC/B and IEC/C (IEC/D) (IEC/E) (IEC/F)
1.0 — — — — 3.062 — — — 62.005 62.272 200.226
1.1 24.700(1) 90.000(1) 471.429(1) — 2.534 22.461 136.228 330.606 19.033 45.678 122.172
1.2 12.901 45.000 225.000 545.905 2.216 11.777 65.390 157.946 9.413 34.628 82.899
1.5 5.788 18.000 79.200 179.548 1.736 5.336 23.479 55.791 3.891 17.539 36.687
2.0 3.376 9.000 33.000 67.691 1.427 3.152 10.199 23.421 2.524 7.932 16.178
2.5 2.548 6.000 18.857 35.490 1.290 2.402 6.133 13.512 2.056 4.676 9.566
3.0 2.121 4.500 12.375 21.608 1.212 2.016 4.270 8.970 1.792 3.249 6.541
3.5 1.858 3.600 8.800 14.382 1.161 1.777 3.242 6.465 1.617 2.509 4.872
4.0 1.676 3.000 6.600 10.169 1.126 1.613 2.610 4.924 1.491 2.076 3.839
4.5 1.543 2.571 5.143 7.513 1.101 1.492 2.191 3.903 1.396 1.800 3.146
5.0 1.441 2.250 4.125 5.742 1.081 1.399 1.898 3.190 1.321 1.610 2.653
5.5 1.359 2.000 3.385 4.507 1.065 1.325 1.686 2.671 1.261 1.473 2.288
6.0 1.292 1.800 2.829 3.616 1.053 1.264 1.526 2.281 1.211 1.370 2.007
6.5 1.236 1.636 2.400 2.954 1.042 1.213 1.402 1.981 1.170 1.289 1.786
7.0 1.188 1.500 2.063 2.450 1.033 1.170 1.305 1.744 1.135 1.224 1.607
7.5 1.146 1.385 1.792 2.060 1.026 1.132 1.228 1.555 1.105 1.171 1.460
8.0 1.110 1.286 1.571 1.751 1.019 1.099 1.164 1.400 1.078 1.126 1.337
8.5 1.078 1.200 1.390 1.504 1.013 1.070 1.112 1.273 1.055 1.087 1.233
9.0 1.049 1.125 1.238 1.303 1.008 1.044 1.068 1.166 1.035 1.054 1.144
9.5 1.023 1.059 1.109 1.137 1.004 1.021 1.031 1.077 1.016 1.026 1.067
10.0 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000
10.5 0.979 0.947 0.906 0.885 0.996 0.981 0.973 0.934 0.985 0.977 0.941
11.0 0.959 0.900 0.825 0.787 0.993 0.963 0.950 0.877 0.972 0.957 0.888
11.5 0.941 0.857 0.754 0.704 0.990 0.947 0.929 0.828 0.960 0.939 0.841
12.0 0.925 0.818 0.692 0.633 0.988 0.932 0.912 0.784 0.949 0.922 0.799
12.5 0.910 0.783 0.638 0.572 0.985 0.918 0.896 0.746 0.938 0.907 0.761
13.0 0.895 0.750 0.589 0.518 0.983 0.905 0.882 0.712 0.929 0.893 0.727
13.5 0.882 0.720 0.546 0.471 0.981 0.893 0.870 0.682 0.920 0.880 0.695
14.0 0.870 0.692 0.508 0.430 0.979 0.882 0.858 0.655 0.912 0.868 0.667
14.5 0.858 0.667 0.473 0.394 0.977 0.871 0.849 0.631 0.905 0.857 0.641
15.0 0.847 0.643 0.442 0.362 0.976 0.861 0.840 0.609 0.898 0.846 0.616
15.5 0.836 0.621 0.414 0.334 0.974 0.852 0.831 0.589 0.891 0.837 0.594
16.0 0.827 0.600 0.388 0.308 0.973 0.843 0.824 0.571 0.885 0.828 0.573
16.5 0.817 0.581 0.365 0.285 0.971 0.834 0.817 0.555 0.879 0.819 0.554
17.0 0.808 0.563 0.344 0.265 0.970 0.826 0.811 0.540 0.874 0.811 0.536
17.5 0.800 0.545 0.324 0.246 0.969 0.819 0.806 0.527 0.869 0.804 0.519
18.0 0.792 0.529 0.307 0.229 0.968 0.812 0.801 0.514 0.864 0.797 0.504
18.5 0.784 0.514 0.290 0.214 0.967 0.805 0.796 0.503 0.860 0.790 0.489
19.0 0.777 0.500 0.275 0.200 0.966 0.798 0.792 0.492 0.855 0.784 0.475
19.5 0.770 0.486 0.261 0.188 0.965 0.792 0.788 0.482 0.851 0.778 0.463
20.0 0.763 0.474 0.248 0.176 0.964 0.786 0.784 0.473 0.848 0.772 0.450
(1) values only suitable for IEC A, B and C curves.
Standard inverse time SIT curve Extremely inverse time EIT curve
Very inverse time VIT or LTI curve Ultra inverse time UIT curve
t (s) t (s)
100.00 1 000.00
MT10539
MT10540
100.00
10.00
curve (T = 1s)
curve (T = 1s)
10.00
1.00 RI
1.00
I/Is
I/Is 0.10
0.10
1 10 100
1 10 100
MT10529
1000.00
100.00
VI
100.00
MI EI
VI
10.00
EI
10.00
1.00
1.00
I/Is
0.10 I/Is 0.10
1 10 100 1 10 100
Curve equations
IEC curve, inverse type Characteristic curves k α β
k - T
t d ( I ) = ---------------------- × --- IEC standard inverse / A 0.14 0.02 2.97
I α
---- β IEC very inverse / B 13.5 1 1.50
- –1
Is IEC long time inverse / B 120 1 13.33
IEC curve, RI type IEC extremely inverse / C 80 2 0.808
I T IEC ultra inverse 315.2 2.5 1
t d ( I ) = ------------------------------------------------------ × -------------------
– 1 3, 1706
0, 339 – 0,236 ----
I
Is
10 I/Is
tr
enables the function to be activated with intermittent faults
IDMT:
makes it possible to emulate an electromagnetic disk protection relay.
TMS = 1
T1 T T- = TMS
t r ( I ) = ----------------------2 × --- with : --
β β
1 – -----
I
Is
T1
T1 = timer hold delay setting (timer hold delay for I reset = 0 and TMS = 1)
T = tripping time delay setting (at 10 Is)
k -
β = basic tripping curve value at 10Is = ------------------
α
0 1 I/Is 10 – 1
The standardized or estimated values of T1 are available in the SFT2841 software
help.