GC 3000 XT
GC 3000 XT
Product Specification
37896A
Salient Features
easYgen | GC-3400XT
Command up to 248 gensets sorted into 8 groups of
31 gensets each
Cascaded control architecture with
o Peer-to-peer communication
o Load share line redundancy at each level
PC based emulation tool for testing load dependent
start/stop sequence
Direct Connect up to 690 VAC
Applications
Prime Power
Peak shaving
Emergency standby
Import-Export
Group Controller for large fleet of gensets Island parallel
Mains parallel
DESCRIPTION
Redundant CAN-Ethernet
Woodward’s group controller, GC-3400XT is designed to manage virtually any large scale power generation communication between
system you can imagine. It enables you to command up to 248 gensets, with complete genset management, GC-3400XT and easYgen
synchronization, dead bus prioritization, load share, and load dependent start/stop capabilities, in combination
with Woodward’s easYgen-3400XT/3500XT equipped genset controllers. These controllers come with stand- Redundant Ethernet-
ardized software that is simple to configure, yet easily customizable for individual applications. Peer-to-peer
communication between the controls and load share line redundancy at each level ensures single-fail-safe op- Ethernet communication
eration of your power generation control system. among GC-3400XT
The GC-3400XT is based on a scalable multi-master control concept to combine up to 31x easYgen-3000XT Generator Group Breaker
equipped gensets with one group controller in a group. The groups are scaled up to x8, i.e. a total up to 248
gensets can be managed in an application. The data flow within the group is handled by CAN or Ethernet or (GGB) synchronization
CAN & Ethernet bus. The group controller collects and sorts the data of its group and acts like a “Big Genset” and busbar arbitration
control to the other GCs. The data flow among the group controllers is handled by second communication bus
Ethernet B or Ethernet C or Ethernet B & C. Through the decoupling of the overall data flow, the bus bandwidth Mains Circuit Breaker
is kept low and the single genset operation is kept safe, should a group controller become the point of failure.
Furthermore, the group controller may handle a group breaker, to synchronize or prioritize dead busbar closing. (MCB) synchronization
Additionally, the group controller supports the synchronization and soft loading/unloading of a tie- or mains and soft loading /
breaker. Comprehensive diagnostics, monitoring and system update function are implemented to help fast com-
missioning of the system. unloading
Woodward’s easYgen-3400XT/3500XT K51 is an exceptionally versatile genset control with complete engine- Load dependent start /
generator control and protection, genset breaker synchronization, dead bus arbitration and isochronous/droop stop (LDSS) for the entire
load share capabilities. The easYgen-3500XT is available in two packages, P1 and P2, both are compatible to
work with GC-3400XT. Both the packages are available without a display in a rugged metal housing suitable for fleet
back panel installations. A sophisticated touch screen remote panel (RP-3000XT) complements them as an op-
erator control panel. Comprehensive
diagnostics, monitoring
FEATURES and system update
function
Full connectivity of up to 248 gensets sorted into 8 groups of 31 gensets each. One GC-3400XT per group
Redundant or single load share communication over CAN/Ethernet between easYgen and group controller LDSS Emulation tool
Redundant or single load share communication over Ethernet among group controllers
Dedicated Ethernet Modbus TCP communication line to external Modbus master (PLC, SCADA etc.) Emulate generator
Active and reactive load sharing and load dependent start/stop (LDSS) management of the whole fleet sequencing on a PC
LDSS algorithm is emulated with a PC software and the final settings are transferred directly to the GC
Supports synchronization and soft loading/unloading of a tie- or mains breaker Transfer the final settings
Phase angle compensation (Vector group adjustment) in case transformers are used in the application directly to the GC-3400XT
Comprehensive monitoring of all interfaces, loss of redundancy and breaker feedback plausibility check
“System Update” function for troubleshooting and fast commissioning UL 61010, UL 6200, CSA,
Time / Date synchronization over Simple Network Time Protocol (SNTP) and CE compliance
Woodward ToolKit™ software for flexible setup from a single connection to the network. The ToolKit can be
accessed either via USB, or via Ethernet, or via CAN ports.
Released
SPECIFICATIONS
Power supply ..........................................................12/24 VDC (8 to 40 VDC) Discrete inputs .............................................................................. isolated
Intrinsic consumption ............................................................... max. 22 W Input range ............................................................ 12/24 VDC (8 to 40 VDC)
Ambient temperature (operation) .................... -40 to 70 °C / -40 to 158 °F Input resistance.............................................................approx. 20 kOhms
Ambient temperature (storage) ...................... -30 to 80 °C / -22 to 176 °F Relay outputs .................................................................................... isolated
Ambient humidity..................................................... 95%, non-condensing Contact material ................................................................................. AgCdO
Voltage (software configurable) ..................................................... ( /) Load (GP) ....................................................................... 2.00 AAC@250 VAC
100 VAC Rated (Vrated) ............................................ 69/120 VAC 2.00 ADC@24 VDC / 0.36 ADC@125 VDC / 0.18 ADC@250 VDC
Max. value (Vmax) ............................................ 86/150 VAC Analog inputs (isolated) .........................................................freely scalable
and 400 /600 VAC Rated (Vrated)* .......................................... 400/690 VAC Type 1 .............................................. 0 to 1 V / 0 to 2000 Ohms / 0 to 20 mA
Max. value (Vmax) .......................................... 520/897 VAC Resolution ........................................................................................... 16 Bit
Rated surge volt. (Vsurge) ....................................................6.0 kV Maximum permissible voltage against genset Ground ........................... 9 V
Accuracy ..................................................................................... Class 0.5 Maximum permissible voltage between genset Ground & PE ........... 100 V
Measurable alternator windings . 3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w Housing Back panel mounting ............. Powder Coated Sheet metal housing
Setting range ................... primary ................................. 50 to 650,000 VAC Dimensions WxHxD P1:................................... 250 × 228 × 50 mm
Linear measuring range ............................................................ 1.25×Vrated Connection ..................................................... screw/plug terminals 2.5 mm²
Measuring frequency ............................................ 50/60 Hz (30 to 85 Hz) Protection system ................................................................................. IP 20
High Impedance Input; Resistance per path ................................. 2.5 M Weight .................................................................................. approx. 1,750 g
Max. power consumption per path .............................................. < 0.15 W Disturbance test (CE) ............ tested according to applicable IEC standards
Listings ...................................................................CE, UL, cUL, EAC, CSA
___________________________
3 phase 3 wire constellations are limited to 600 VAC system
A*
APPLICATION
Released
DIMENSIONS
Metal housing for cabinet mounting
TERMINAL DIAGRAM
RELATED PRODUCTS
Genset Controller easYgen-3500XT-P1- K51 & easYgen-3500XT-P2- K51 (Product Specification # 37583)
ToolKit (Product Specification # 03366)
LDSS Emulation Tool (Product Specification #37897)
Released
Europe
Tel. Stuttgart: +49 711 78954 510
Tel. Kempen: +49 2152 145 331
[email protected]
Russia
Tel.: +7 812 319 3007
[email protected]
China
Tel.: +86 512 8818 5515
[email protected]
India
Tel.: +91 124 4399 500
LDSS EMULATION TOOL OVERVIEW
[email protected]
LDSS Emulation Tool allows emulating a number of easYgen-3000XT, GC-3000XT, loads and
ASEAN & Oceania mains connections and their load dependent start/stop behavior. The tool allows access by Mod-
Tel.: +49 711 78954 510 bus/TCP master to r/w the parameter set. The final settings file can be directly transferred to the
[email protected] GC-3400XT or can be used offline by ToolKit.
www.woodward.com
Subject to alterations, errors excepted.
© Woodward
PART NUMBERS
Description Order Code
GC-3400XT-P1 8440-2228
easYgen-3500XT-P1-K51 8440-2230
easYgen-3500XT-P2-K51 8440-2238
37896 - 2019/02/Stuttgart