CFP Standard 4 Zone Conventional Fire Alarm Panel

Part No. CFP704-4

Overview
Certified to EN54 parts 2, 4 and 13, C-TEC's CFP 4 zone conventional fire alarm panel offers an array of user and installer-friendly features at a
very competitive price. Supplied in an attractive flush or surface mountable plastic enclosure, it includes two detector zones, four conventional
sounder circuits, class change and alert inputs, on-board fire and fault relays and combined keypad/keyswitch entry. A wide range of engineering
functions are also provided including selectable zone delays, coincidence and non-latching zone facilities. Comprehensive test and fault finding
facilities are also provided. Optional repeaters and relay expansion boards also available.

More Information

Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) and EN54 part 13 certified by Kiwa
Telefication.
Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
Manufactured by C-TEC in the UK.
Four detector zone circuits.
Four conventional sounder circuits.
Integral 1.5A EN54-4/A2 compliant switch mode PSU.
Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
Two on-board relays (Fire and Fault).
Two open-collector outputs (Remote and Reset).
'Class change' and alert inputs.
Installer-friendly design.
Attractive flush or surface mountable plastic lid and enclosure - no bezel required.
Low 25mA quiescent current.
Multiple indicators.
System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP
relay boards and optional EN54-13 compliant sounder circuit boards.
Space for two x 12V 3.3Ah VRLA batteries.
Fully compatible with C-TEC's ActiV fire detectors, sounders and visual alarm devices.

Technical Specifications

Approvals/certifications Certifed to EN54 Parts 2 & 4 by the LPCB., Certified to EN54-13 by Kiwa Telefication.
Mains supply 230V 50/60Hz.
Mains rated current 350mA maximum.
Internal power supply 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total output current limited to 1.5A @ 230Vac (ImaxA eq 146mA).
Quiescent current 25mA (mains failed, internal sounder active, PSU & gen fault LED lit)
Max battery size and type 2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
No. of detector zone circuits 4 (Max. length per circuit is 500m).
Call point resistor value 470 to 680Ω.
Max. devices per detector zone 25 detectors (or 32 detectors/manual call points combined).
No. of conventional sounder circuits 4 (Max. length per circuit is 500m).
EOL resistor value 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Alarm voltage 27V max, 20V min (final battery voltage)
Max. sounder output current 4 x 200mA (800mA total).
Two: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch
Auxiliary relays
voltage 30Vdc.
Two: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition
Open collector outputs
provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltag
Other outputs 24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).
Two: (1) ‘Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max.
Auxiliary inputs
input voltage 27V (non-latching)
Program coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones for non-
Engineer (AL3) functions
latching operation; Program sounders to resound (or not resound) when a new zone enters al
Yes – for optional network driver cards (one required per repeater system), relay output cards and
Expansion connections
EN54-13 sounder circuit interface boards.
380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D mm. No bezel
Product dimensions (mm)
required).
Construction & finish Plastic lid and base; RAL7035 textured
IP Rating IP30.
Weight 1.75kg (without batteries)
Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%.