0% found this document useful (0 votes)
30 views76 pages

Aquaciat LD - Ild

Ledaqua

Uploaded by

Geeja Edger
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views76 pages

Aquaciat LD - Ild

Ledaqua

Uploaded by

Geeja Edger
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 76

10147

11 - 2020

AQUACIAT LD/ILD

Instruction manual
CONTENTS

1 - INTRODUCTION....................................................................................................................................................................... 4
1.1 - Safety considerations related to protection devices............................................................................................................. 4
1.2 - Refrigerant safety considerations......................................................................................................................................... 5
1.3 - Installation safety considerations......................................................................................................................................... 6
1.4 - Maintenance safety considerations...................................................................................................................................... 7
1.5 - Safety considerations during system interventions.............................................................................................................. 7
2 - RECEIPT OF GOODS.............................................................................................................................................................. 9
2.1 - Check equipment received................................................................................................................................................... 9
3 - HANDLING AND POSITIONING............................................................................................................................................ 10
3.1 - Handling............................................................................................................................................................................. 10
3.2 - Positioning.......................................................................................................................................................................... 10
4 - DIMENSIONS, CLEARANCES................................................................................................................................................11
4.1 - LD/ILD150 to LD/ILD300.....................................................................................................................................................11
4.2 - LD360 to LD600 and ILD302 to ILD600............................................................................................................................. 13
4.3 - Installing several units ....................................................................................................................................................... 15
5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS.................................................................... 16
5.1 - Physical properties of AQUACIAT LD units ....................................................................................................................... 16
5.2 - Physical properties of AQUACIAT ILD units ...................................................................................................................... 18
5.3 - Electrical data notes for the Units ..................................................................................................................................... 20
5.4 - Short circuit current withstand capability............................................................................................................................ 20
5.5 - Electrical data notes for the hydronic module.................................................................................................................... 21
5.6 - Electrical data notes for the compressors.......................................................................................................................... 22
5.7 - Distribution of compressors per circuit............................................................................................................................... 23
5.8 - Comments on electrical data notes.................................................................................................................................... 23
6 - ELECTRICAL CONNECTION................................................................................................................................................ 24
6.1 - Power supply...................................................................................................................................................................... 24
6.2 - Voltage phase imbalance (%)............................................................................................................................................ 24
6.3 - Recommended cable sections........................................................................................................................................... 24
6.4 - Power cable access routing............................................................................................................................................... 25
6.5 - Field-installed control wiring............................................................................................................................................... 25
6.6 - Electric power reserve for the user.................................................................................................................................... 25
7 - APPLICATION DATA.............................................................................................................................................................. 26
7.1 - AQUACIAT LD operating limits........................................................................................................................................... 26
7.2 - AQUACIAT ILD operating limits.......................................................................................................................................... 26
7.3 - Minimum heat transfer fluid flow rate (units without factory-fitted hydronic module).......................................................... 27
7.4 - Maximum heat transfer fluid flow rate (without factory-fitted hydronic module)................................................................. 27
7.5 - Water exchanger min. water volume and flow rate............................................................................................................ 28
7.6 - Maximum system water volume......................................................................................................................................... 28
7.7 - Pressure drop curves for the water exchanger and its water inlet/outlet piping (for units without pump).......................... 29
8 - WATER CONNECTIONS........................................................................................................................................................ 30
8.1 - Operating precautions and recommendations................................................................................................................... 30
8.2 - Water connections.............................................................................................................................................................. 31
8.3 - Cavitation protection (with hydronic option)....................................................................................................................... 34
8.4 - Flow rate detection............................................................................................................................................................. 34
8.5 - Frost protection.................................................................................................................................................................. 35
8.6 - Extra electrical heaters field-installed or integrated into the buffer tank (depending on the option chosen)...................... 36
9 - NOMINAL SYSTEM WATER FLOW CONTROL.................................................................................................................... 37
9.1 - Units without hydronic module........................................................................................................................................... 37
9.2 - Units with hydronic module and fixed-speed pump (only for negative cold applications).................................................. 38
9.3 - Units with hydronic module and variable speed pump – Pressure differential control....................................................... 39
9.4 - Units with hydronic module and variable speed pump – Temperature differential control................................................. 40
9.5 - Pump flow rate/pressure curves......................................................................................................................................... 41
9.6 - Available static pressure for the installation....................................................................................................................... 42
10 - SYSTEM START-UP............................................................................................................................................................. 44
10.1 - Checks before system start-up........................................................................................................................................ 44
10.2 - Commissioning................................................................................................................................................................. 44
10.3 - Essential points to check.................................................................................................................................................. 45

Translation of the original document

AQUACIAT LD/ILD EN -2
CONTENTS

11 - MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS................................................................. 46


11.1 - Compressors.................................................................................................................................................................... 46
11.2 - Lubricant........................................................................................................................................................................... 46
11.3 - Air heat exchanger............................................................................................................................................................ 46
11.4 - Fans.................................................................................................................................................................................. 46
11.5 - Electronic expansion valve (EXV).................................................................................................................................... 47
11.6 - Moisture indicator............................................................................................................................................................. 47
11.7 - Dryer filter......................................................................................................................................................................... 48
11.8 - Water type heat exchanger.............................................................................................................................................. 48
11.9 - Refrigerant........................................................................................................................................................................ 48
11.10 - HP safety pressostat...................................................................................................................................................... 48
11.11 - Tank................................................................................................................................................................................ 48
11.12 - 4-way valve..................................................................................................................................................................... 48
11.13 - Electrical box.................................................................................................................................................................. 48
11.14 - Variable speed ventilation .............................................................................................................................................. 48
11.15 - Electrical box.................................................................................................................................................................. 48
11.16 - Connect Touch control ................................................................................................................................................... 48
12 - OPTIONS.............................................................................................................................................................................. 49
12.1 - Tables of options.............................................................................................................................................................. 49
12.2 - Description....................................................................................................................................................................... 51
13 - STANDARD MAINTENANCE............................................................................................................................................... 66
13.1 - Level 1 maintenance........................................................................................................................................................ 66
13.2 - Level 2 maintenance........................................................................................................................................................ 66
13.3 - Level 3 maintenance........................................................................................................................................................ 67
13.4 - Tightening of the electrical connections........................................................................................................................... 67
13.5 - Tightening torques for the main fastenings...................................................................................................................... 67
13.6 - Air heat exchanger........................................................................................................................................................... 68
13.7 - Water type heat exchanger.............................................................................................................................................. 68
13.8 - Frequency inverter........................................................................................................................................................... 68
13.9 - Refrigerant volume........................................................................................................................................................... 68
13.10 - Refrigerant properties.................................................................................................................................................... 69
14 - FINAL SHUTDOWN.............................................................................................................................................................. 70
14.1 - Shutting down.................................................................................................................................................................. 70
14.2 - Recommendations for disassembly................................................................................................................................. 70
14.3 - Fluids to be recovered for treatment................................................................................................................................ 70
14.4 - Materials to be recovered for recycling............................................................................................................................ 70
14.5 - Waste electrical and electronic equipment (WEEE)......................................................................................................... 70
15 - UNIT START-UP CHECKLIST FOR INSTALLERS PRIOR TO CONTACTING THE MANUFACTURER........................... 71

The illustrations in this document are for illustrative purposes only and not part of any offer for sale or contract. The manufacturer reserves the right to change the design
at any time without notice.

EN-3 AQUACIAT LD/ILD


1 - INTRODUCTION

The units are intended to cool or heat water for building air Classification and control:
conditioning or heating, or for industrial processes.
In accordance with the Pressure Equipment Directive and
They are designed to provide a very high level of safety and national usage monitoring regulations in the European Union,
reliability, making installation, start-up, operation and maintenance the protective devices fitted to these machines are classified as
easier and safer. follows:
They will provide safe and reliable service if used within their
application ranges. Device for limitation
Safety
of damage in the event of
device(1)
They are designed to offer a service life of 15 years, assuming an external fire(2)
a utilisation factor of 75%, which corresponds to approximately Refrigerant side
100,000 operating hours. High pressure switch X
Prior to the initial start-up of the units, everyone involved in the External relief valve(3) X
works should be thoroughly familiar with these instructions and Rupture disk X
with the characteristics of the installation site, and ensure these
Fusible plug X
are respected.
Heat transfer fluid side
The procedures in this manual are arranged in the sequence
External relief valve (4) (4)
required for installation, start-up, operation and maintenance of
the units. Ensure that you follow them and that you take the (1) Classified for protection in normal service situations.
(2) Classified for protection in abnormal service situations. These accessories
required safety precautions, including those listed in this guide,
are sized for fires with a thermal flow of 10 kW/m². No combustible matter
which include wearing personal protective equipment (gloves, should be placed within 6.5 m of the unit.
safety glasses, safety shoes) and having the appropriate tools, (3) The instantaneous over-pressure limitation of 10% of the operating pressure
skills and qualifications (electrical, air conditioning, local does not apply to this abnormal service situation.
The set pressure can be higher than the operating pressure. In this case,
legislation).
either the design temperature or the high pressure switch ensures that the
To find out if these products comply with European directives operating pressure is not exceeded in normal service situations.
(machine safety, low-voltage, electromagnetic compatibility, (4) The classification of these relief valves must be made by the personnel
responsible for completing the hydraulic installation.
pressurised equipment, etc.) check the declarations of conformity
for these products. Do not remove valves / fusible plugs, even if the fire risk is under
control for a particular installation. There is no guarantee that
1.1 - Safety considerations related to the accessories have been re-installed if the system is changed
protection devices or for transport with a gas charge.
When the unit is subjected to fire, a safety device prevents rupture
Do not obstruct any protective devices. due to over-pressure by releasing the refrigerant. The fluid can
This applies to any fusible plugs, rupture disks and valves fitted then break down into toxic residues when in contact with flames:
on the refrigerant or heat-transfer fluid circuits. Check whether • Stay away from the unit;
the original protection plugs are still present at the valve outlets. • Ensure the personnel in charge of extinguishing the fire are
These plugs are generally made of plastic and should not be used. duly warned and issued with recommendations;
If they are still present, please remove them. Fit devices at the • Fire extinguishers appropriate to the system and the
valve or discharge piping outlets to prevent the penetration of refrigerant type must be easily accessible.
foreign bodies (dust, building debris, etc.) and atmospheric agents All factory-fitted relief valves are lead-sealed to prevent any
(water can form rust or ice). These devices, as well as the calibration change.
discharge piping, must not impair operation and not lead to The external relief valves must always be vented to outside if
a pressure drop that is higher than 10% of the set pressure. the units are installed in a closed space. Refer to the installation
regulations, for example those of European standard EN 378
and EN 13136. These pipes must be installed in a way that
ensures that people and property are not exposed to vented
refrigerant. As the fluids can be diffused in the air, ensure that
refrigerant is discharged away from building air intakes, relief
valves must be checked periodically. The valves must be checked
periodically.
If the relief valves are factory fitted on a changeover valve, this
is equipped with a relief valve on each of the two outlets. Only
one of the two relief valves is in operation, the other one is
isolated. Never leave the changeover valve in the intermediate
position, i.e. with both circuits open (move the lever fully forwards
or backwards depending on the output to be isolated). If a valve
is removed for checking or replacement, make sure there is still
a valve active on each of the changeover valves installed on the
unit.
Provide a drain in the discharge pipework, close to each relief
valve, to avoid an accumulation of condensate or rain water.

AQUACIAT LD/ILD EN -4
1 - INTRODUCTION

It is recommended to install an indicating device to check whether Detect and repair the leak, check the type of refrigerant in the
any refrigerant has leaked from the relief valve. machine and then recharge the machine/circuit with the total
The presence of oil at the outlet orifice is a useful indicator that charge, as indicated on the unit nameplate. Do not top up the
refrigerant has leaked. Keep this orifice clean to ensure that any refrigerant charge. Only charge the liquid refrigerant given on
leaks are obvious. The calibration of a valve that has leaked is the nameplate at the liquid line.
generally lower than its original calibration. The new calibration Charging any refrigerant other than the original type will impair
may affect the operating range. To avoid nuisance tripping or machine operation and can even cause irreparable damage to
leaks, replace or re-calibrate the valve. the compressors. The compressors operating with this refrigerant
type are lubricated with a synthetic polyolester oil.
Protective device checks:
Do not unweld the refrigerant pipework or any refrigerant circuit
If no national regulations exist, check the protective devices on component or cut these with a torch until all refrigerant (liquid
site in accordance with standard and vapour) as well as the oil have been removed from the unit.
EN 378: once a year for the high pressure switches, every five Traces of vapour should be displaced with dry nitrogen.
years for external relief valves. Refrigerant in contact with an open flame produces toxic gases.
The company or organisation that conducts a pressure switch Do not siphon refrigerant.
test must establish and implement detailed procedures for: Any accidental release of refrigerant, whether this is caused by
• Safety measures, a small leak or significant discharges following the rupture of
• Measuring equipment, a pipe or an unexpected release from a relief valve, may cause
• Values and tolerances for cut-off and discharge devices, any personnel exposed to experience heart palpitations,
• Test stages, faintness, frostbite and burns. Always take any such event
• Recommissioning of the equipment. seriously.
The principle for performing a test without disassembly of the Installers, owners and especially service engineers for these
pressure switch is given here, however the manufacturer units must:
recommends contacting Ciat Service for this type of test: • Create a procedure to ensure medical attention is sought
• Verify and record the setpoints of pressure switches and before treating any symptoms;
external relief devices (valves and possible rupture disks), • Provide first aid equipment, flush the eyes and skin
• Be ready to switch off the main disconnect switch of the immediately if splashed with refrigerant, and seek medical
power supply if the pressure switch does not trigger (avoid attention.
over-pressure or excess gas if there are valves on the high
We recommend to apply standard EN 378-3 Annex 3.
pressure side on the recovery air exchangers, for example),
• Connect a calibrated pressure differential gauge with Ensure there is sufficient ventilation if the unit is installed in an
integral damping (oil bath with pointer if mechanical); enclosed area. In gas form, refrigerant is heavier than air and,
instantaneous reading gauges may give inaccurate readings if allowed to accumulate in a confined area, it can reduce the
because of the control's scanning delay, quantity of oxygen in the air, causing respiratory issues.
• Carry out the HP quicktest built into the control (refer to the The refrigerant used in units in this range is R410A, a high-
Service Guide). pressure fluid (the operating pressure of the unit is greater than
40 bar).
If the test results in the replacement of the pressure
switch, it is necessary to recover the refrigerant Special equipment must be used when working on the refrigerant
charge; these pressure switches are not installed circuit (pressure gauge, charge transfer equipment, etc.).
on Schrader type automatic valves. Do not clean the unit with hot water or steam. This may cause
If the machine operates in a corrosive environment, inspect the the refrigerant pressure to rise.
protection devices more frequently. NOTE: If a liquid line valve is present, never leave refrigerant in
Do not attempt to repair or recondition a valve if there has been liquid form between this closed valve and the expansion valve
any corrosion or build-up of foreign material (rust, dirt, scale, as the change in temperature may cause the liquid to expand,
etc.) on the valve body or mechanism. In this case, it must be rupturing this section of the circuit. This valve is situated on the
replaced. liquid line before the filter drier.

Do not install relief valves in series or backwards. Never apply an open flame or pressurised steam to a refrigerant
container. Dangerous overpressure can result. If it is necessary
to heat the refrigerant, only use hot water.
1.2 - Refrigerant safety considerations
The standard NF E29-795 describes the regulations permitting
Use safety goggles and safety gloves. conditioning and recovery of halogenated hydrocarbons under
All precautions concerning handling of refrigerant must be optimum quality conditions for the products and optimum safety
observed in accordance with local regulations. conditions for people, property and the environment. If any
If a leak occurs or if the refrigerant becomes contaminated damage is caused to the equipment, the refrigerant must be
(e.g by a motor short circuit or BPHE freeze-up), and before any changed in accordance with this standard, or an analysis of the
intervention, remove the complete charge using a recovery unit fluid must be performed by a specialist laboratory.
and store the refrigerant in mobile containers. The compressors Any refrigerant transfer and recovery operations must be carried
cannot transfer the whole refrigerant charge and can be damaged out using a transfer unit.
if used to pump-down. The refrigerant charge should not be
transferred to the high-pressure side.

EN-5 AQUACIAT LD/ILD


1 - INTRODUCTION

Service valves are positioned on the liquid, suction and discharge ► For all equipment subject to regular sealing tests,
lines and are available on all units for connection to the transfer the operator must keep a log used to record the
unit. following: the quantities and types of fluids
The units must never be modified to add refrigerant and oil contained in the system (added and recovered),
charging, removal and purging devices. These units have the the quantity of fluid recycled, regenerated or
required openings. Refer to the certified dimensional drawings. destroyed, the date and results of the sealing
It is dangerous and illegal to re-use disposable (non-returnable) tests, the details of the technician and of the
cylinders or attempt to refill them. When the cylinders are empty, company performing the work, etc.
evacuate the remaining gas pressure, fill out the relevant ► Contact your local dealer or installer if you have
paperwork and hand them over to an approved recovery agency. any questions.
Do not incinerate. Information on operating inspections given in EN 378 standard
Operating checks: can be used when similar criteria do not exist in the national
regulation.
IMPORTANT: This product contains fluorinated greenhouse
Check regularly for leaks and, if detected, have these repaired
gas covered by the Kyoto protocol.
immediately.
Type of fluid: refer to the nameplate
Global Warming Potential (GWP): refer to the table below 1.3 - Installation safety considerations
► All interventions on this product's refrigerating After the unit has been received, and before it is started up, it
circuit must be performed in accordance with must be inspected for damage. Check that the refrigerant circuits
applicable legislation. Within the European are intact, especially that no components or pipes have shifted
Union, this legislation notably includes regulation or been damaged (e.g. following a shock). If in doubt, carry out
No. 517/2014, known as F-Gas. a leak tightness check.
► Ensure that refrigerant is never released to the
atmosphere when the equipment is installed, Pressure equipment and components
maintained or sent for disposal. These products include pressure equipment or components
► It is prohibited to deliberately release refrigerant manufactured by the unit manufacturer or by other manufacturers.
into the atmosphere. We recommend that you contact your professional body to find
► If a refrigerant leak is detected, ensure that the out which regulations affect you as the operator or owner of
leak is repaired quickly. pressure equipment or components (declaration, re-qualification,
re-testing). The characteristics of this equipment/these
► Only certified, qualified personnel are permitted
components are given on the nameplate or in the required
to install, service and perform sealing tests on
documentation, supplied with the products.
the refrigerant, decommission the equipment
and recover the refrigerant. These units comply with the European Pressure Equipment
Directive.
► The operator must ensure that any refrigerant
recovered is recycled, regenerated or destroyed. The units are intended to be stored and operated in an
environment where the ambient temperature does not drop below
► The operator is bound by the obligation to
the minimum allowable temperature indicated on the nameplate.
perform sealing tests, or have these performed,
at regular intervals. Do not introduce significant static or dynamic pressure with
regard to the operating pressures used during operation or for
► Regulations within the European Union have set
tests in the refrigerant circuit or in the heat exchange circuits.
the following intervals:
NOTE: Monitoring during operation, re-qualification, re-testing,
System WITHOUT leakage exemption from re-testing:
No test 12 months 6 months 3 months • Follow the regulations on monitoring pressurised equipment.
detection
• The user or operator is usually required to create and
System WITH leakage maintain a monitoring and maintenance log.
No test 24 months 12 months 6 months
detection
• In the absence of any regulations, or in addition to the
Refrigerant charge per
< 5 tons 5<≤50charge 50 ≤ charge Charge regulations, follow the guidance in EN 378.
circuit (equivalent CO2) tons < 500 tons > 500 tonnes* • Follow the local professional recommendations, whenever
3.5 ≤ they exist.
R134a Charge charge 34.9 ≤ charge charge
(PRP 1430) < 3.5 kg < 349.7 kg > 349.7 kg • Regularly monitor the surface of the components to detect
Refrigerant charge per

< 34.9 kg cavernous corrosion. To do this check an uninsulated part


2.8 ≤ of the pressure vessel or at a joint in the insulation.
circuit (kg)

R407C Charge charge 28.2 ≤ charge charge


(PRP 1774) < 2.8 kg < 281.9 kg > 281.9 kg Regularly check for the presence of any impurities
< 28.2 kg
(e.g. sand, grit) in the heat transfer fluids. These impurities
2.4 ≤ can cause wear and/or pitting corrosion.
R410A Charge charge 23.9 ≤ charge charge
(PRP 2088) < 2.4 kg < 239.5 kg > 239.5 kg Filter the heat transfer fluid and perform internal visits and
< 23.9 kg
inspections as described in EN 378 Reports from the periodical
HFOs: R1234ze No requirement checks by the user or the operator must be added to the
* From 01/01/2017, units must be equipped with a leak detection system. monitoring and maintenance register.

AQUACIAT LD/ILD EN -6
1 - INTRODUCTION

Repair: Even if the unit has been shut down, the power
Any repair or modification, including replacement of removable circuit remains energized, unless the unit or circuit
parts: disconnect switch is open. Refer to the wiring
• Must comply with local regulations and must be performed diagram for further details. Follow the appropriate
by qualified operators in accordance with qualified safety guidelines. When working in a fan area,
processes, including changing a wiring harness conductor, specifically if the grilles have to be removed, isolate
• Must be approved by the original manufacturer. Repairs the power supply to the fans to prevent their
and modifications which involve a permanent assembly operation.
(welding, soldering, expansion of tubes, etc.) must be Units equipped with the variable speed fan option, variable speed
performed by qualified operators following operating pump options and the power factor option are equipped with
procedures, capacitor batteries which take 5 minutes to fully discharge once
• All modifications and repairs must be listed in the monitoring the power has been switched off.
and maintenance register,
After disconnecting the power supply to the electrics box, wait
• Never attempt to repair or modify a plate heat exchanger.
5 minutes before accessing the electrics box or variable drives.
Recycling: Before any intervention, verify that there is no voltage present
The pressure equipment can be recycled in whole or in part. at any accessible conducting parts of the power circuit.
After use they may contain refrigerant vapours and oil residue. Regularly check that the vibration levels remain acceptable and
Some parts are painted. close to those at the initial machine start-up.
Before opening a refrigerant circuit, purge and read the pressure
1.4 - Maintenance safety considerations indicators.
The manufacturer recommends the following template for the If the refrigerant circuit remains open after an intervention (such
maintenance log (the table below is only given as a guide and as a component replacement, etc.):
does not engage the manufacturer's liability). - Seal the openings if the duration is less than a day
- Beyond this time, charge the circuit with a dry, inert gas
Intervention Name of the (nitrogen).
Applicable national Verification
Nature commissioning
Date regulations Organisation The objective is to prevent penetration of atmospheric humidity
(1) engineer
and the resulting corrosion of the unprotected internal steel walls.

1.5 - Safety considerations during system


interventions
To prevent any damage or accidents, trained personnel must
(1) Maintenance service the various parts of this machine and must resolve any
Any technician carrying out work on the electrical or refrigerating malfunctions or leaks immediately.
section must be authorised, with the relevant qualifications and Comply with the regulations and recommendations given in the
certifications, including for brazing operations and for operation safety standards for refrigerant systems and machines, such as:
of the shut-off valve. He/she must have been specifically trained EN 378, ISO 5149, etc.
on this equipment and system.
Risk of explosion:
The manual valves must only be manipulated when the machine
is off. Do not forget to refit protective caps to prevent leaks. Never use air or gases containing oxygen during leak tests,
to purge pipework or to pressurise a unit. Pressurised air mixtures
Technicians working on the units must be equipped as follows:
or gases containing oxygen can be the cause of an explosion.
Operations Oxygen reacts violently with oil and grease.
Personal protection Maintenance, Only use dry nitrogen for leak tests, possibly with an appropriate
equipment (PPE)(1) Welding or
Handling service tracer gas.
strong brazing(2)
operations
A failure to observe the above recommendations can have
Protective gloves, serious or even fatal consequences and damage the
eye protection, X X X installations.
safety shoes,
protective clothing. Never exceed the specified maximum operating pressures. Verify
Ear protection. X X the maximum permissible high and low test pressures by
Filtering respirator. X checking the instructions in this manual or the pressures given
on the unit nameplate.
(1) We recommend following the instructions in EN 378-3.
(2) Performed in the presence of A1 refrigerant according to EN 378-1. The necessary protection equipment must be available, and
Never work on a unit that is still energised. appropriate fire extinguishers for the system and the refrigerant
type used must be within easy reach.
Never work on any of the electrical components until the general
power supply to the unit has been isolated and locked out.

EN-7 AQUACIAT LD/ILD


1 - INTRODUCTION

Do not attempt to remove refrigerant circuit components or fittings


while the machine is under pressure or while it is running. Make
sure the circuit pressure is zero and that the unit has been
stopped and powered off before removing components or
opening a circuit. When the refrigerant circuit is opened to repair,
see the recommendations in chapter “Maintenance safety
considerations”.
No part of the unit must be used as a walkway, rack or support.
Periodically check and repair or, if necessary, replace any
component or piping that shows signs of damage.
The lines can break under the weight and release refrigerant,
causing personal injury.
Do not climb on a machine. Use a platform to work at height.
Use mechanical lifting equipment (crane, hoist, winch, etc.)
to lift or move heavy components.
For lighter components, use lifting equipment if there is any risk
of slipping or losing your balance.
Use only original replacement parts for any repair or component
replacement. Consult the list of replacement parts that
corresponds to the original equipment.
Do not drain the heat exchange fluid circuit without informing the
site technical / service department or other competent body first.
Close the shut-off valves on the water inlet and outlet and drain
the unit's hydraulic circuit before working on the components
installed on the circuit (screen filter, pump, water flow sensor,
etc.).
Periodically inspect all valves, fittings and pipes on the refrigerant
and hydraulic circuits to ensure that they do not show any signs
of corrosion or leaks.

AQUACIAT LD/ILD EN -8
2 - RECEIPT OF GOODS

2.1 - Check equipment received


Check that the unit and the accessories have not been damaged during transport and that no parts are missing. If the unit and the
accessories have been damaged or the shipment is incomplete, send a claim to the shipping company.
Compare the name plate data with the order.
The name plate is attached in two places to the unit:
• On the outside of one of the unit frames,
• On the inside of the electrical panel door.
The unit name plate must include the following information:
• Model number - size,
• CE marking,
• Serial number,
• Year of manufacture and pressure and leak tightness test date,
• Fluid used for transport,
• Refrigerant used,
• Refrigerant charge per circuit,
• PS: Min./max. allowable pressure (high and low pressure side),
• TS: Min./max. allowable temperature (high and low pressure side),
• Pressure switch cut-out pressure,
• Unit leak test pressure,
• Voltage, frequency, number of phases,
• Maximum current,
• Maximum power input,
• Unit net weight,

EN-9 AQUACIAT LD/ILD


3 - HANDLING AND POSITIONING

3.1 - Handling 3.2 - Positioning


It is strongly recommended that a specialised lifting company is The machine must be installed in a place that is not accessible
employed to unload the machine. to the public, or protected against access by non-authorised
Do not remove the skid or the packaging until the unit is in its persons.
final position. If the unit is to be raised, ensure the machine's surroundings
These units can be safely moved by trained personnel with a fork permit easy access for maintenance operations.
lift truck with the correct capacity for the dimensions and weight For the centre of gravity coordinates, the position of the unit
of the unit, as long as the forks are positioned in the location and mounting holes, and the weight distribution points, refer to the
direction shown on the unit. certified dimensional drawings. Ensure the free space shown in
More particularly, units equipped with the optional water buffer the dimensional drawings is respected to facilitate maintenance
tank module can be handled by forklift in compliance with the and connection.
instructions below: The typical applications of these units are cooling and heating,
• Pick up the load as close as possible to the mast (at the which do not require earthquake resistance. Earthquake
heel of the fork) resistance has not been verified.
• The forks of the forklift must pass all the way under the load Before positioning the unit, check that:
• The load must be lowered down a slope in reverse, with • The permitted loading at the site is adequate or that
the mast tilted backwards. appropriate strengthening measures have been taken.
• The load must be raised up a slope in forward gear, with • The unit is installed level on an even surface (maximum
the mast tilted backwards tolerance is 5 mm along both axes).
In both cases, drive at low speed, applying the brakes gradually. • If the support structure is sensitive to vibration and/or noise
transmission it is advisable to insert anti-vibration mounts
(elastomer mounts or metal springs) between the unit and
the structure. Selection of these devices is based on the
system characteristics and the comfort level required and
should be made by technical specialists.
• There is adequate space above and around the unit for air
to circulate and for access to the components (see
dimensional drawings).
• The number of support points is adequate and that they are
in the right places.
MAX
. 10
• If the optional anti-vibration mounts are present, their
% number and position must comply with the indications given
on the certified dimensional drawing.
• The location is not subject to flooding.
• For outdoor applications, avoid installing the unit in a
location where snow is likely to accumulate (in areas subject
to long periods of sub-zero temperatures, the unit should
be raised).
• Baffles may be necessary to deflect strong winds. They
must not restrict air flow into the unit.
Before lifting the unit, check that all casing panels
and grilles are securely fixed in place. Lift and set
down the unit with great care. Tilting and jarring
can damage the unit.

Never apply pressure or leverage to any of the unit's


. 10% panels or uprights; only the base of the unit frame
MAX
is designed to withstand such stresses. No force
or effort must be applied to pressurised parts,
Unit with protection grilles option especially via pipes connected to the water type
The units can also be lifted with slings, using only the designated heat exchanger (with or without the hydraulic
lifting points marked on the unit (labels on the chassis and label module if the unit is equipped with this).
with the unit handling instructions, attached to the unit). All welding operations (connection to the hydraulic network) must
be performed by qualified welders. The Victaulic® connection or
Use slings with the correct capacity, and follow the lifting instructions
the counter-flange must be removed before welding as a matter
on the certified dimensional drawings supplied for the unit.
of course.
Only attach slings to the clearly marked points on
the unit provided for this purpose.
It is advisable to protect coils against crushing while a unit is
being moved. Use struts or a lifting beam to spread the slings
above the unit. Do not tilt a unit more than 15°.
Safety can only be guaranteed if these instructions are carefully
followed. Otherwise there is a risk of equipment deterioration or
injury to personnel.

AQUACIAT LD/ILD EN -10


4 - DIMENSIONS, CLEARANCES

4.1 - LD/ILD150 to LD/ILD300

Without buffer tank module

1330 HT
1061 HT 2050 HT

Legend: NOTES :
All dimensions are in mm.
A Non-certified drawings.
Control box
Refer to the certified dimensional drawings supplied
Water inlet with the unit or available on request, when designing
Water outlet an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity
B Required clearances for air flow
refer to the certified dimensional drawings.
C Recommended clearances for maintenance
B In multiple-chiller installations (maximum four units),
Air outlet, do not obstruct
the side clearance between the units should be
Power cable entry increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.

NOTE: For units with other options, refer to the certified dimensional drawings.

EN-11 AQUACIAT LD/ILD


4 - DIMENSIONS, CLEARANCES

With buffer tank module

1114 HT 2130 HT

1972 with Xtra Fan option


1930 HT
1061 2050

1000
1000

1000
1000

Legend: NOTES :
All dimensions are in mm.
A Non-certified drawings.
Control box
Refer to the certified dimensional drawings supplied
Water inlet with the unit or available on request, when designing
Water outlet an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity
B Required clearances for air flow
refer to the certified dimensional drawings.
C Recommended clearances for maintenance
B In multiple-chiller installations (maximum four units),
Air outlet, do not obstruct
the side clearance between the units should be
Power cable entry increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.

NOTE: For units with other options, refer to the certified dimensional drawings.

AQUACIAT LD/ILD EN -12


4 - DIMENSIONS, CLEARANCES

4.2 - LD360 to LD600 and ILD302 to ILD600

Without buffer tank module

Legend: NOTES :
All dimensions are in mm.
A Non-certified drawings.
Control box
Refer to the certified dimensional drawings supplied
Water inlet with the unit or available on request, when designing
Water outlet an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity
B Required clearances for air flow
refer to the certified dimensional drawings.
C Recommended clearances for maintenance
B In multiple-chiller installations (maximum four units),
Air outlet, do not obstruct
the side clearance between the units should be
Power cable entry increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.

NOTE: For units with other options, refer to the certified dimensional drawings.

EN-13 AQUACIAT LD/ILD


4 - DIMENSIONS, CLEARANCES

With buffer tank module

2130 HT
2311 HT

1972 with Xtra Fan option


1930 HT
2050
2258

1000

1000
1000

1000

Legend: NOTES :
All dimensions are in mm.
A Non-certified drawings.
Control box
Refer to the certified dimensional drawings supplied
Water inlet with the unit or available on request, when designing
Water outlet an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity
B Required clearances for air flow
refer to the certified dimensional drawings.
C Recommended clearances for maintenance
B In multiple-chiller installations (maximum four units),
Air outlet, do not obstruct
the side clearance between the units should be
Power cable entry increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.

NOTE: For units with other options, refer to the certified dimensional drawings.

AQUACIAT LD/ILD EN -14


4 - DIMENSIONS, CLEARANCES

4.3 - Installing several units


NOTE: if the height of the walls is more than 2 metres, consult the factory

Solid surface Solid surface

EN-15 AQUACIAT LD/ILD


5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS
5.1 - Physical properties of AQUACIAT LD units

AQUACIAT LD 150 180 200 240 260 300 360 390 450 520 600

Sound levels
Standard unit
Sound power(1) dB(A) 80 81 81 81 87 87 84 84 84 90 90
Sound pressure at 10 m(2) dB(A) 49 49 49 49 55 55 52 52 52 58 58
Unit + Xtra Low Noise option
Sound power(1) dB(A) 79 80 80 80 80 80 83 83 83 83 83
Sound pressure at 10 m(2) dB(A) 48 48 48 48 48 48 51 51 51 51 51
Dimensions
Length mm 1090 1090 1090 1090 1090 1090 2270 2270 2270 2270 2270
Width mm 2109 2109 2109 2109 2109 2109 2123 2123 2123 2123 2123
Height mm 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330
Height with Buffer Tank Module mm 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930
Operating weight with Micro-Channel coils(3)
Standard unit kg 422 430 436 449 445 463 753 762 771 829 854
Unit + High pressure single pump option kg 463 472 478 491 487 505 820 829 842 903 928
Unit + High pressure dual-pump option kg 489 498 504 517 513 531 865 874 891 940 965
Unit + High pressure single pump option kg 859 868 874 887 883 901 1253 1262 1275 1336 1361
+ Buffer tank module
Unit + High pressure dual pump option
+ Water buffer tank module kg 885 894 900 913 909 927 1298 1307 1324 1373 1398
Compressors Hermetic Scroll 48.3 rps
Circuit A Qty 2 2 2 2 2 2 3 3 3 2 2
Circuit B Qty - - - - - - - - - 2 2
Number of power stages Qty 2 2 2 2 2 2 3 3 3 4 4
Refrigerant with Micro-Channel coils (3) R410A GWP=2088 following ARI4
kg 4,7 5,3 5,9 6,7 6,2 7,3 10,7 10,8 11,4 6,5 7,4
Circuit A
tCO2e 9,8 11,1 12,3 14,0 12,9 15,2 22,3 22,6 23,8 13,6 15,5
kg - - - - - - - - - 6,5 7,4
Circuit B
tCO2e - - - - - - - - - 13,6 15,5
Oil charge POE SZ160 (EMKARATE RL 32-3MAF).
Circuit A l 5,8 7,2 7,2 7,2 7 7 10,8 10,5 10,5 7 7
Circuit B l - - - - - - - - - 7 7
Control Connect Touch Control
Minimum capacity % 50 50 50 50 50 50 33 33 33 25 25
(1) in dB ref=10-12 W, weighting (A). Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). Measured
in accordance with ISO 9614-1.
(2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For
information, calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit nameplate.

AQUACIAT LD/ILD EN -16


5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS

AQUACIAT LD 150 180 200 240 260 300 360 390 450 520 600

Air heat exchanger Micro-Channel coil


Fans - Standard unit
Quantity 1 1 1 1 1 1 2 2 2 2 2
Maximum total air flow l/s 4111 4111 4111 4167 5500 5583 8056 8056 8222 11000 11167
Maximum rotation speed rps 12 12 12 12 16 16 12 12 12 16 16
Water heat exchanger Direct expansion, plate heat exchanger
Water volume l 2,6 3 3,3 4 4,8 5,6 8,7 9,9 11,3 12,4 14,7
Max. water-side operating pressure without hydronic kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
module
Hydronic module (option)
Single or dual-pump (as selected) Pump, Victaulic screen filter, relief valve, purge valves (water and air), pressure sensors
Expansion tank volume (optional) l 18 18 18 18 18 18 35 35 35 35 35
Expansion vessel pressure(4) l 1 1 1 1 1 1 1,5 1,5 1,5 1,5 1,5
Max. water-side operating pressure with hydronic module kPa 400 400 400 400 400 400 400 400 400 400 400
Water buffer tank module (option)
Single or dual-pump (as selected) Pump, Victaulic screen filter, relief valve, purge valves (water and air), pressure sensors
Water volume l 250 250 250 250 250 250 250 250 250 250 250
Expansion tank volume (optional) l 18 18 18 18 18 18 35 35 35 35 35
Expansion vessel pressure(4) bar 1 1 1 1 1 1 1,5 1,5 1,5 1,5 1,5
Max. water-side operating pressure with hydronic module kPa 400 400 400 400 400 400 400 400 400 400 400
Water connections with or without hydronic module Victaulic®
Connections in 2 2 2 2 2 2 2 2 2 2 2
Outside diameter mm 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3
Casing paint Colour code RAL 7035/RAL 7024
(4) Upon delivery, the standard preinflation of the vessels is not necessarily at the optimum value for the installation. In order to enable free variation of the water
volume, adjust the inflation pressure to a pressure close to that corresponding to the static head of the installation. Charge the installation with water (purging the
air), to a pressure 10 to 20 kPa higher than that of the vessel.

EN-17 AQUACIAT LD/ILD


5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS

5.2 - Physical properties of AQUACIAT ILD units

AQUACIAT ILD 150 180 200 240 260 300 302 360 390 450 520 600

Sound levels
Standard unit
Sound power(1) dB(A) 80 81 81 86 87 87 84 84 84 84 90 90
Sound pressure at 10 m(2) dB(A) 49 49 49 55 55 55 52 52 52 52 58 58
Unit + Xtra Low Noise option
Sound power(1) dB(A) 79 80 80 80 80 80 83 83 83 83 83 83
Sound pressure at 10 m(2) dB(A) 48 48 48 48 48 48 51 51 51 51 51 51
Dimensions
Length mm 1090 1090 1090 1090 1090 1090 2270 2270 2270 2270 2270 2270
Width mm 2109 2109 2109 2109 2109 2109 2123 2123 2123 2123 2123 2123
Height mm 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440
Height with Buffer Tank Module mm 2040 2040 2040 2040 2040 2040 2040 2040 2040 2040 2040 2040
Operating weight(3)
Standard unit kg 497 506 543 549 559 564 777 896 905 979 1053 1057
Unit + High pressure single pump option kg 539 548 585 591 601 606 844 963 972 1050 1127 1131
Unit + High pressure dual-pump option kg 565 574 611 617 627 632 889 1008 1017 1098 1164 1168
Unit + High pressure single pump option kg 935 943 981 986 996 1001 1276 1395 1404 1482 1560 1563
+ Buffer tank module
Unit + High pressure dual pump option kg 961 969 1006 1012 1022 1027 1321 1440 1449 1531 1597 1600
+ Water buffer tank module
Unit + high pressure single pump option + Water kg 1018 1026 1064 1069 1079 1084
buffer tank module with extra heaters (16 kW)
Unit + high pressure dual pump option + Water kg 1044 1052 1089 1095 1105 1110
buffer tank module with extra heaters (16 kW)
Unit + high pressure single pump option + Water buffer kg 1022 1030 1068 1073 1083 1088
tank module with extra heaters (31 kW and 45 kW)
Unit + high pressure dual pump option + Water buffer kg 1048 1056 1093 1099 1109 1114
tank module with extra heaters (31 kW and 45 kW)
Compressors Hermetic Scroll 48.3 rps
Circuit A Qty 2 2 2 2 2 2 2 3 3 3 2 2
Circuit B Qty - - - - - - - - - - 2 2
Number of power stages Qty 2 2 2 2 2 2 2 3 3 3 4 4
Refrigerant (3) R410A GWP=2088 following ARI4
kg 12,5 13,5 16,5 17,5 18 16,5 21,5 27,5 28,5 33 19 18,5
Circuit A
tCO2e 26,1 28,2 34,5 36,5 37,6 34,5 44,9 57,4 59,5 68,9 39,7 38,6
kg - - - - - - - - - - 19 18,5
Circuit B
tCO2e - - - - - - - - - - 39,7 38,6
Oil charge POE SZ160 (EMKARATE RL 32-3MAF)
Circuit A l 5,8 7,2 7,2 7,2 7,0 7,0 7,2 7,0 7,0 7,0 7,0 7,0
Circuit B l - - - - - - - - - - 7,0 7,0
Control Connect Touch Control
Minimum capacity % 50 50 50 50 50 50 50 33 33 33 25 25
(1) In dB ref=10-12 W, 'A' weighted. Declared dual-number noise emission value in accordance with ISO 4871 (with an uncertainty of +/-3dB(A). Measured in accordance
with ISO 9614-1 and certified by EUROVENT
(2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission value in accordance with ISO 4871 (with an uncertainty of +/-3dB(A). Value calculated from
the sound power level Lw(A).
(3) Weights given as a guide. Refer to the unit nameplate.

AQUACIAT LD/ILD EN -18


5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS

AQUACIAT ILD 150 180 200 240 260 300 302 360 390 450 520 600

Air heat exchanger Grooved copper tube and aluminium fins


Fans
Quantity 1 1 1 1 1 1 2 2 2 2 2 2
Maximum total air flow l/s 3694 3694 3889 5278 5278 5278 7778 7389 7389 7778 10556 10556
Maximum rotation speed rps 12 12 12 16 16 16 12 12 12 12 16 16
Water heat exchanger Direct expansion, plate heat exchanger
Water volume l 2,6 3 4 4,8 4,8 5,6 8,7 8,7 9,9 11,3 12,4 14,7
Max. operating pressure, water side kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydronic module (option)
Single or dual-pump (as selected) Pump, Victaulic screen filter, relief valve, purge valves (water and air), pressure sensors
Expansion tank volume (optional) l 18 18 18 18 18 18 35 35 35 35 35 35
Expansion vessel pressure(4) l 1 1 1 1 1 1 1,5 1,5 1,5 1,5 1,5 1,5
Max. water-side operating pressure with hydronic module kPa 400 400 400 400 400 400 400 400 400 400 400 400
Water buffer tank module (option)
Single or dual-pump (as selected) Pump, Victaulic screen filter, relief valve, purge valves (water and air), pressure sensors
Water volume l 250 250 250 250 250 250 250 250 250 250 250 250
Expansion tank volume (optional) l 18 18 18 18 18 18 35 35 35 35 35 35
Expansion vessel pressure (4) bar 1 1 1 1 1 1 1,5 1,5 1,5 1,5 1,5 1,5
Max. water-side operating pressure with hydronic module kPa 400 400 400 400 400 400 400 400 400 400 400 400
Water buffer tank module with extra heaters (option)
Pump, Victaulic screen filter, relief valve, purge valves (water and air), pressure sensors,
Single or dual-pump (as selected) vent at the top of the tank
2x 2x 2x 2x 2x 2x
16 kW extra heaters in the tank kW 8kW 8kW 8kW 8kW 8kW 8kW
2x 2x 2x 2x 2x 2x
8kW + 8kW + 8kW + 8kW + 8kW + 8kW +
31 kW extra heaters in the tank kW 1x 1x 1x 1x 1x 1x
15kW 15kW 15kW 15kW 15kW 15kW
3x 3x 3x 3x 3x 3x
45 kW extra heaters in the tank kW 15kW 15kW 15kW 15kW 15kW 15kW

Water connections with or without hydronic module Victaulic®


Connections in 2 2 2 2 2 2 2 2 2 2 2 2
Outside diameter mm 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3
Casing paint Colour code RAL 7035 and RAL 7024
(4) "Upon delivery, the standard preinflation of the vessels is not necessarily at the optimum value for the installation. In order to enable free variation of the water
volume, adjust the inflation pressure to a pressure close to that corresponding to the static head of the installation. Charge the installation with water (purging the
air), to a pressure 10 to 20 kPa higher than that of the vessel.

EN-19 AQUACIAT LD/ILD


5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS

5.3 - Electrical data notes for the Units

LD / ILD - Standard unit (without hydronic module) 150 180 200 240 260 300 302 360 390 450 520 600

Power circuit
Nominal voltage V-ph-Hz 400 - 3 -50
Voltage range V 360 - 440
Control circuit supply 24 V via internal transformer
Nominal unit operating current(3)
Circuit A&B A 25,6 29 33 36 42,4 52,8 53,4 55,4 61,7 77,3 84,8 105,6
Max. operating input power (2)
Circuit A&B kW 19,5 22,3 24,5 27,9 31,2 35,8 35,6 42,3 45,6 52,5 62,4 71,6
Cosine Phi unit at maximum power (2) 0,83 0,81 0,81 0,83 0,81 0,78 0,78 0,83 0,81 0,79 0,81 0,78
Unit max. operating current (Un-10%)(5)
Circuit A&B A 38 49,2 51,4 58,4 74,8 79,6 80,2 89 110,3 117,5 149,6 159,2
Maximum unit current draw (Un)(4)
Circuit A&B - Standard unit A 34,8 44,8 46,8 52,8 67 73 73,6 80,6 98,6 107,6 134 146
Maximum start-up current, standard unit (Un) (1)
Circuit A&B A 113,8 134,8 142,8 145,8 176 213 213,6 173,6 207,6 247,6 243 286
Maximum start-up current, unit with soft starter (Un) (1)
Circuit A&B A 74,7 86,5 93,8 96,2 114,4 139,8 139,8 130,4 155,4 181,4 186,4 215,4
(1) Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + fan current(s) + locked rotor current of the largest compressor).
(2) Input power, at the unit’s continuous operating limits (indicated on the unit nameplate).
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(4) Unit maximum current at 400 V, in non-continuous operation (indicated on the unit name plate)
(5) Unit maximum current at 360 V, in non-continuous operation

5.4 - Short circuit current withstand capability

Short circuit current withstand capability (TN system(1))


AQUACIAT LD / ILD 150 180 200 240 260 300 302 360 390 450 520 600
Value without upstream protection
Short time assigned current (1s) - Icw kA eff 3,36 3,36 3,36 3,36 3,36 3,36 3,36 5,62 5,62 5,62 5,62 5,62
Allowable peak assigned current - Ipk kA pk 20 20 20 20 20 15 15 20 20 15 20 15
Value with upstream protection
Conditional short circuit assigned current Icc kA eff 40 40 40 40 40 40 40 40 40 40 30 30
Associated Schneider circuit breaker - Compact type range(2) NS100H NS100H NS100H NS100H NS100H NS100H NS100H NS100H NS160H NS160H NS250H NS250H
(1) Type of system earthing
(2) If another current limiting protection device is used, its time-current trip and I²t thermal stress characteristics must be at least equivalent to those of the recommended
Schneider circuit breaker.
The short-circuit stability current values above are in accordance with the TN system.

AQUACIAT LD/ILD EN -20


5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS

5.5 - Electrical data notes for the hydronic module


The pumps that are factory-installed in these units comply with the European Ecodesign directive ErP. The additional electrical
data required(1) is as follows:

Unit low-pressure single and dual pumps (Fixed speed single pumps, hydronic module option)

ILD
No.(2) Description(3) Units
150 180 200 240 260 300 302 360 390 450 520 600
Nominal efficiency at full load and nominal
1 % 81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 83,4 83,4 84,8 84,8
voltage
Nominal efficiency at 75% of full load and
1 % 80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 81,2 81,2 82,2 82,2
nominal voltage
Nominal efficiency at 50% of full load and
1 % 77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 78,3 78,3 79 79
nominal voltage
2 Efficiency level - IE3
This information varies depending on the manufacturer and model at the time of incorporation. Please refer
3 Year of manufacture - to the motor nameplates.
Manufacturer's name and trademark,
4 commercial registration number and - Same as above
manufacturer's head office
5 Product's model number - Same as above
6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 2
Nominal shaft power output at full load and
7-1 kW 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,8 1,3 1,3 1,7 1,7
nominal voltage (400 V)
7-2 Maximum input power (400 V)(4) kW 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,6 1,6 2,4 2,4
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)(5) A 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,9 2,9 4,2 4,2
rps - rpm 2850 2850 2850 2850 2850 2850 2850 2850 2890 2890 2870 2870
10 Nominal speed
47 47 47 47 47 47 47 47 48 48 48 48
11 Product disassembly, recycling or disposal at - Disassembly using standard tools. Disposal and recycling using an appropriate company.
end of life
Operating conditions for which the motor is
specifically designed
I- Altitudes above sea level m < 1000(6)
12 II - Ambient air temperature °C < 55
Please refer to the operating conditions given in this manual or
III - Maximum operating temperature °C in the specific conditions given in the selection programs.
IV - Potentially explosive atmospheres - Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric
motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the electrical data table to the pump
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.

EN-21 AQUACIAT LD/ILD


5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS

Unit high pressure single and dual-pumps (Fixed speed single pumps, hydronic module option)

LD / ILD
No.(2) Description(3) Units
150 180 200 240 260 300 302 360 390 450 520 600
Nominal efficiency at full load and nominal
1 % 84,8 84,8 84,8 84,8 84,8 84,8 84,8 84,8 84,8 85,9 85,9 85,9
voltage
Nominal efficiency at 75% of full load and
1 % 82,2 82,2 82,2 82,2 82,2 82,2 82,2 82,2 82,2 84 84 84
nominal voltage
Nominal efficiency at 50% of full load and
1 % 79 79 79 79 79 79 79 79 79 82,1 82,1 82,1
nominal voltage
2 Efficiency level - IE3
This information varies depending on the manufacturer and model at the time of incorporation.
3 Year of manufacture - Please refer to the motor nameplates.
Manufacturer's name and trademark,
4 commercial registration number and - Same as above
manufacturer's head office
5 Product's model number - Same as above
6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 2
Nominal shaft power output at full load and
7-1 kW 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 2,2 2,2 2,2
nominal voltage (400 V)
7-2 Maximum input power (400 V)(4) kW 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,9 2,9 2,9
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)(5) A 4,2 4,2 4,2 4,2 4,2 4,2 4,2 4,2 4,2 5 5 5
rps - rpm 2870 2870 2870 2870 2870 2870 2870 2870 2870 2855 2855 2855
10 Nominal speed
48 48 48 48 48 48 48 48 48 48 48 48
11 Product disassembly, recycling or disposal at - Disassembly using standard tools. Disposal and recycling using an appropriate company.
end of life
Operating conditions for which the motor is
specifically designed
I- Altitudes above sea level m < 1000(6)
12 II - Ambient air temperature °C < 55
Please refer to the operating conditions given in this manual or
III - Maximum operating temperature °C in the specific conditions given in the selection programs.
IV - Potentially explosive atmospheres - Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric
motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the electrical data table to the pump
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.

5.6 - Electrical data notes for the compressors

I Max I Max LRA(1) LRA(2) Cos


Compressor I Nom
(Un) (Un-10%) A A Phi Max
ZP90 11,4 16 17,6 95 57 0,82
ZP103 13,1 21 23,1 111 67 0,84
ZP120 15,1 22 24,3 118 71 0,84
ZP137 16,6 25 27,8 118 71 0,86
ZP154 18,7 31 34,9 140 84 0,85
ZP182 23,9 34 37,3 174 104 0,84
I Nom: Nominal current (A) under Eurovent conditions (see definition of conditions under unit nominal current)
I Max: Maximum operating current (A), 360 V
(1) Locked rotor current (A), at nominal voltage
(2) Locked rotor current (A) with electronic starter, at nominal voltage

AQUACIAT LD/ILD EN -22


5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS

5.7 - Distribution of compressors per circuit

LD / ILD
Compressor Circuit
150 180 200 240 260 300 302 360 390 450 520 600
A 2 - - - - - - - - - - -
ZP90
B - - - - - - - - - - - -
A - 2 - - - - - - - - - -
ZP103
B - - - - - - - - - - - -
A - - 2 - - - - - - - - -
ZP120
B - - - - - - - - - - - -
A - - - 2 - - - 3 - - - -
ZP137
B - - - - - - - - - - - -
A - - - - 2 - - - 3 - 2 -
ZP154
B - - - - - - - - - - 2 -
A - - - - - 2 2 - - 3 - 2
ZP182
B - - - - - - - - - - - 2
I Nom: Nominal current (A) under Eurovent conditions (see definition of conditions under unit nominal current)
I Max: Maximum operating current (A), 360 V
(1) Locked rotor current (A), at nominal voltage
(2) Locked rotor current (A) with electronic starter, at nominal voltage

5.8 - Comments on electrical data notes

Electrical data notes and operating conditions - Notes:


• LD/ILD 150-600 units have a single connection point to the electrical mains, - presence of solids: classification 4S2 (presence of insignificant dust),
situated immediately upstream of the power supply connections. - presence of corrosive and pollutant substances, classification 4C2
• The electrical box contains as standard: (negligible),
- motor start-up and protection equipment for each compressor, the fans and 2. Power supply frequency variations: ± 2 Hz.
the pump. 3. The neutral wire (N) must not be connected directly to the unit (if necessary
- Main disconnect switch, use transformers.)
- A main disconnect switch is fitted as standard in the electrics box 4. Overcurrent protection of the power supply conductors is not provided with
• On-site connections: the unit.
All connections to the system and the electrical installations must be in accordance 5. The factory-fitted switch is of a type suitable for power interruption in
with all applicable codes. compliance with EN 60947-3 (equivalent to IEC 60947-3)
• CIAT LD / ILD units are designed to ensure compliance with these guidelines. 6. The units are designed to be connected more easily to TN systems
European standard EN 60204-1 (Safety of machinery - electrical equipment of (IEC 60364). In the case of IT systems, provide a local earth. Consult the
machines - part one: general requirements - equivalent to IEC 60204-1) is taken competent local organisations to perform the electrical installation. Units
into account in the design of the machine's electrical equipment*. supplied with a speed drive (28 and 116J/K/V/W options) are not compatible
• The QF circuit breaker is delivered with an auxiliary contactor which enables with the TIC system.
a safety loop to be installed, in order to provide status feedback on the heater 7. Leakage currents: if leakage current monitoring protection is required to
and the power supply to the electronic boards, and thereby prevent the evaporator guarantee the safety of the installation, its trip value must be set taking into
from freezing when the heaters and boards are off. consideration the presence of leakage currents induced by the presence
NOTE: of frequency inverters on the machine. In particular, a value of at least
• Generally, the recommendations of the International Electrotechnical 150 mA is recommended for the differential protection device setting.
Commission (IEC 60364) are accepted as meeting the requirements of the
installation guidelines. WARNING: if particular aspects of an installation require different properties
Compliance with standard EN 60204-1 is a good way of meeting the requirements to those listed above (or which are not listed), please contact your
(˜1.5.1) of the Machinery Directive. manufacturer.
• Appendix B of standard EN 60204-1 specifies the electrical data notes under
* The absence of a main power disconnect switch on the standard machines is
which the machines operate.
an exception to take into account during on-site installation.
• The operating conditions of the LD / ILD units are specified below: ** The required protection level for this class is IP43BW (according to reference
1. Environment** document IEC 60529). Since all LD / ILD units are IP44CW, they fulfil this
- The classification of the environment is specified in standard EN 60721 protection condition:
- equivalent to IEC 60721): - The closed electrics box is IP44CW
- outdoor installation**, - The open electrics box (for interface access) is IPxxB
- ambient temperature range: -20 °C for the minimum temperature,
up to +48 °C, classification 4K4H,
- altitude less than or equal to 2000 m (see notes for tables in paragraph
entitled - Electrical data notes for the hydronic module-).

EN-23 AQUACIAT LD/ILD


6 - ELECTRICAL CONNECTION
Please refer to the certified dimensional drawings, supplied with 6.3 - Recommended cable sections
the unit.
Wire sizing is the responsibility of the installer, and depends on
the characteristics and regulations applicable to each installation
6.1 - Power supply site. The following is only to be used as a guideline, and does
The power supply must meet the specification on the unit's not engage the manufacturer's liability.
nameplate. After wire sizing has been completed, using the certified
The supply voltage must be within the range specified in the dimensional drawing, the installer must verify the appropriate
electrical data table. means of connection and define any modifications necessary
on site.
For connections refer to the wiring diagrams and certified
dimensional drawings. The connections provided as standard for the customer-supplied
power supply cables are designed for the number and type of
WARNING: Operation of the unit with an incorrect supply
wires listed in the table below.
voltage or excessive phase imbalance constitutes misuse
which will invalidate the manufacturer's warranty. If the The calculations of favourable and unfavourable cases are
phase imbalance exceeds 2% for voltage, or 10% for current, performed by using the maximum current possible for each unit
contact your local electricity supplier at once and ensure fitted with a hydronic module (see the tables of electrical data
that the unit is not switched on until corrective measures for the unit and the hydronic module).
have been taken. The study includes the standardised installation cases according
After the unit has been installed, the power supply must only be to IEC 60364: cables with PVC (70°C) or XLPE (90°C) insulation
disconnected for quick maintenance operations (one day with copper core; routing in accordance with table 52C of the
maximum). For longer maintenance operations or when the unit standard.
is taken out of service (for example, during winter when the unit The maximum length mentioned is calculated to limit the voltage
does not need to generate cooling) the power supply of the unit drop to 5 %.
must be maintained permanently.
IMPORTANT: Before connecting the main power cables
(L1 - L2 - L3), always check 3 phases are in the correct order
6.2 - Voltage phase imbalance (%) (clockwise) before proceeding to the connection on the main
100 x max. deviation from average voltage disconnect switch.
Average voltage

Example:
On a 400 V - 3 ph - 50 Hz power supply, the individual phase
voltages were measured with the following values: AB= 406V;
BC= 399V; AC= 394V
Average voltage =(406+399+394)/3=1199/3 =399.7 i.e. 400 V
Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6
Motor

Table of minimum and maximum cable sections (per phase) for connection to the units

Calculation of unfavourable case:


Calculation of favourable case:
- Conductors in ducts or multi-conductor cables in closed
Max. connectable section(1) - Suspended overhead line (standardised routing no. 17)
conduits (standardised routing no. 61)
- Cable with XLPE insulation
AQUACIAT - Cable with PVC insulation
LD / ILD Connection cage Section(2)
Max length for
Cable type(3) Section(2)
Max length for
Cable type(3)
a voltage drop < 5% a voltage drop < 5%
mm² mm² mm²
m - m -
(per phase) (per phase) (per phase)
150 1 x 95 1 x 16 165 XLPE Copper 1 x 25 300 PVC Copper
180 1 x 95 1 x 16 165 XLPE Copper 1 x 25 300 PVC Copper
200 1 x 95 1 x 16 165 XLPE Copper 1 x 25 300 PVC Copper
240 1 x 95 1 x 25 210 XLPE Copper 1 x 35 305 PVC Copper
260 1 x 95 1 x 35 220 XLPE Copper 1 x 50 350 PVC Copper
300 1 x 95 1 x 35 220 XLPE Copper 1 x 70 380 PVC Copper
302 1 x 95 1 x 35 220 XLPE Copper 1 x 70 380 PVC Copper
360 1 x 95 1 x 35 220 XLPE Copper 1 x 70 380 PVC Copper
390 1 x 95 1 x 70 280 XLPE Copper 1 x 95 410 PVC Copper
450 1 x 95 1 x 70 280 XLPE Copper 1 x 95 410 PVC Copper
520 1 x 185 1 x 95 305 XLPE Copper 1 x 185 465 PVC Copper
600 1 x 185 1 x 120 320 XLPE Copper 1 x 185 465 PVC Copper
NOTE:
(1) Connection capacities actually available for each machine. These are defined according to the connection terminal size, the electrical box access opening dimensions
and the available space inside the electrical box.
(2) Selection simulation result considering the hypotheses indicated.
(3) If the maximum calculated section is for an XLPE cable type, this means that a selection based on a PVC cable type can exceed the connection capacity actually
available. Special attention must be given to selection.
The protection against direct contact at the electrical connection point is compatible with the addition of terminals extension. The installer must determine whether
these are necessary based on the cable sizing calculation.

AQUACIAT LD/ILD EN -24


6 - ELECTRICAL CONNECTION

The protection against direct contact at the electrical connection point is compatible with the addition of terminals extension.
The installer must determine whether these are necessary based on the cable sizing calculation.

Minimum and maximum cable sections (per phase) for connection to the extra heater ILD units

Calculation of unfavourable case:


Calculation of favourable case:
- Conductors in ducts or multi-conductor cables in closed
Max. connectable section(1) - Suspended overhead line (standardised routing no. 17) conduits (standardised routing no. 61)
- Cable with XLPE insulation - Cable with PVC insulation
AQUACIAT
Max length for Max length for
ILD Connection cage Section(2) a voltage drop Cable type(3) Section(2) a voltage drop Cable type(3)
< 5% < 5%
mm² mm² mm²
m - m -
(per phase) (per phase) (per phase)
150 1 x 95 1 x 35 178 XLPE Copper 1 x 70 343 PVC Copper
180 1 x 95 1 x 35 163 XLPE Copper 1 x 70 316 PVC Copper
200 1 x 95 1 x 35 161 XLPE Copper 1 x 70 311 PVC Copper
240 1 x 95 1 x 35 153 XLPE Copper 1 x 95 393 PVC Copper
260 1 x 95 1 x 50 198 XLPE Copper 1 x 95 360 PVC Copper
300 1 x 95 1 x 50 190 XLPE Copper 1 x 95 346 PVC Copper
(1) Connection capacities actually available for each machine. These are defined according to the connection terminal size, the electrical box access opening dimensions
and the available space inside the electrical box.
(2) Selection simulation result considering the hypotheses indicated.
(3) If the maximum calculated section is for an XLPE cable type, this means that a selection based on a PVC cable type can exceed the connection capacity actually
available. Special attention must be given to selection.
The protection against direct contact at the electrical connection point is compatible with the addition of terminals extension. The installer must determine whether
these are necessary based on the cable sizing calculation.

6.4 - Power cable access routing See the control manual and the certified electric wiring diagram
supplied with the unit for the field control wiring of the following
The power cables can be routed into the electrical box for the
devices:
units:
• Device automatic operation control
- via the underside of the unit,
• Setpoint 1/Setpoint 2 switching
- via the side of the unit,
• Heating / cooling selection
- on the bottom of the corner post.
• Demand limits
A removable aluminium plate on the base of the electrical cabinet • Operating fault display
provides access for the power cables. • Locking switch (safety chain)
It is important to check that the power cable bend radius is • Customer pump switch control (on/off)
compatible with the connection space available inside the • Setpoint adjustable by 4-20 mA signal
electrical cabinet. • Second power limitation level
• Desuperheater activation control
Refer to the certified dimensional drawing for the unit.
• Unit shut down general fault reporting
• Free cooling drycooler management
6.5 - Field-installed control wiring
IMPORTANT: Connecting the interface circuits on-site creates 6.6 - Electric power reserve for the user
certain safety risks; any modification to the electrical box must
ensure the equipment remains compliant with local regulations. Control circuit power reserve:
In particular, precautions must be taken to prevent accidental After all possible options have been connected, the
electrical contact between the circuits supplied by different CT transformer ensures the availability of 1 A of power for the
sources: control cabling on-site on 24 V, 50 Hz.
• The choice of routing and/or insulation characteristics of
the conductors ensures double electrical insulation.
• The conductors should be fixed together inside the electrical
box to prevent contact between the end of the conductor
and a live part in case of accidental disconnection.

EN-25 AQUACIAT LD/ILD


7 - APPLICATION DATA

7.1 - AQUACIAT LD operating limits 7.2 - AQUACIAT ILD operating limits

AQUACIAT LD Minimum Maximum AQUACIAT ILD / Cooling mode Minimum Maximum


Water type heat exchanger Water heat exchanger
Water inlet temperature (at start-up) °C 7.5 (1) 30 Water inlet temperature (at start-up) °C 7.5 (1) 30
Water outlet temperature (in operation) °C 5 (2) 20 Water outlet temperature (in operation) °C 5 (2) 20
Water outlet temperature (in operation) / Low Inlet/outlet temperature difference °C 3 (2) 10
°C 0 (2) 20
Temperature option Standard air-cooled exchanger
Water outlet temperature (in operation) / Very Low °C Air inlet temperature °C 0 48
-15 (2) 20
Temperature option
Air inlet temperature at partial load °C 0 48
Inlet / outlet temperature difference K 3 10
Air-cooled exchanger, Winter operation or Xtra Fan
Standard air-cooled exchanger
option(3)
Air inlet temperature at full load °C 0 46
Air inlet temperature at full load °C -20 46
Air inlet temperature at partial load °C 0 48
Air inlet temperature at partial load °C -20 48
Air-cooled exchanger, Winter operation or Xtra Fan
Hydronic module(4)
option(3)
Air inlet temperature
Air inlet temperature at full load °C -20 46
Without pump °C -20 -
Air inlet temperature at partial load °C -20 48
With Single or Dual pump option (LP or HP) °C 0 -
Hydronic module(4)
With Single or Dual pump (LP or HP) + Frost
Air inlet temperature °C -20 -
protection option
Without pump °C -20 - With Buffer Tank option °C 0
With Single or Dual-pump option (HP) °C -10 - With Buffer Tank + Frost protection option °C -20 -
With Single or Dual-pump (HP) + Frost protection °C -20 - Note: Do not exceed the maximum operating temperature.
option
(1) For a water inlet temperature at start-up of less than 7.5°C, contact the
With Buffer Tank option °C 0 manufacturer.
With Buffer Tank + Frost protection option °C -20 - (2) Use of antifreeze is obligatory if the water outlet temperature is below 5°C.
(3) Ducted machines (Xtra Fan option) This operating range applies up to a static
Note: Do not exceed the maximum operating temperature. pressure of 130 Pa for sizes 240-300 and 520-600, and up to 240 Pa for all
(1) For a water inlet temperature at start-up of less than 7.5°C, contact the other sizes.
manufacturer. (4) Defines the antifreeze protection temperature of the hydronic components for
(2) Use of antifreeze is obligatory if the water outlet temperature is below 5°C. use without glycol
(3) Ducted machines (Xtra Fan option) This operating range applies up to a static In case of storing and transporting AQUACIAT LD units, the min. and max.
pressure of 130 Pa for sizes 260-300 and 520-600, and up to 240 Pa for all temperature limits are -20°C and +48°C. It is recommended to take into
other sizes. consideration these temperatures in case of container transport.
(4) Defines the antifreeze protection temperature of the hydronic components for
use without glycol
In case of storing and transporting AQUACIAT LD units, the min. and max.
temperature limits are -20°C and +48°C. It is recommended to take into
consideration these temperatures in case of container transport.
Ambient air temperature, °C

Low Temperature option


Ambient air temperature, °C

Low Temperature option

Very Low
Temperature
Winter operation
option
or XtraFan
option
Very Low
Temperature
option
Winter operation or Evaporator water outlet temperature, °C
XtraFan option Full load Minimum load
Winter operation option Very Low Temperature option
Low Temperature option
Evaporator water outlet temperature, °C
Full load Minimum load
Winter operation option Very Low Temperature option
Low Temperature option

NOTE: Ducted machines (Xtra Fan option) This operating range applies up to a static pressure of 130 Pa without a suction duct
for sizes 070-080 and 140-160, and up to 240 Pa for all other sizes.

AQUACIAT LD/ILD EN -26


7 - APPLICATION DATA

Operating range for standard unit, heating mode 7.3 - Minimum heat transfer fluid flow rate
(units without factory-fitted hydronic module)
AQUACIAT ILD / Heating mode Minimum Maximum
The minimum heat transfer fluid flow rate is given in the
Water heat exchanger paragraph "water exchanger min. water volume and flow rate".
Water inlet temperature (at start-up) °C 8 45 If the system flow rate is less than the unit's minimum flow rate,
Water outlet temperature (in operation) °C 25 55 the exchanger flow can be recirculated, as shown in the diagram
Inlet/outlet temperature difference K 3 10
Air-cooled exchanger (3) For a minimum heat-transfer fluid flow rate
Air inlet temperature °C -15 40
Hydronic module(4) 1
Air inlet temperature
Without pump °C -20 -
With Single or Dual pump option (LP or HP) °C 0 -
With Single or Dual pump (LP or HP) + Frost °C -20 -
protection option
With Buffer Tank option °C 0 2

With Buffer Tank + Frost protection option °C -20 -


Note: Do not exceed the maximum operating temperature.
(3) Ducted machines (Xtra Fan option) This operating range applies up to a static
pressure of 130 Pa for sizes 240 to 300 and 520 to 600, and up to 240 Pa for
all other sizes.
(4) Defines the frost protection temperature of the hydraulic components for use
without glycol.

B Water type heat exchanger


C Recirculation

If the system flow rate is less than the minimum flow rate, there
may be a high risk of fouling.
If using an external variable speed pump, make sure that the
Outlet water temperature, °C

minimum set flow rate is above the minimum acceptable flow


rate. A dedicated connector can be used to check the pump
variator (0-10 V signal). Refer to the Connect Touch control
manual.

7.4 - Maximum heat transfer fluid flow rate


(without factory-fitted hydronic module)
The maximum heat transfer fluid flow rate is given in the
paragraph "water exchanger min. water volume and flow rate".
If the system flow rate exceeds the unit's maximum value, it can
be bypassed as shown in the diagram.

Ambient air temperature, °C For a maximum heat-transfer fluid flow rate


Full load Minimum load

B Water type heat exchanger


C Recirculation

It is limited by the allowable pressure drop for the water exchanger.


Furthermore, it must ensure a minimum ΔT in the water exchanger
of 2.8 K, which corresponds to a flow rate of 0.09 l/s per kW.

EN-27 AQUACIAT LD/ILD


7 - APPLICATION DATA

7.5 - Water exchanger min. water volume and flow rate


The Connect Touch control is equipped with anticipation logic making it highly flexible in adjusting operation to parameter drift,
particularly on hydraulic systems with low water volumes. By adjusting compressor running times, it prevents short cycle protection
cycles from starting and, in most cases, eliminates the need for a buffer tank.
Note: The minimum heat transfer fluid volumes are calculated for EUROVENT rated conditions:
• heat transfer fluid temperature in the water exchanger = 12°C / 7°C
• inlet air temperature in the air exchanger = 35°C
This value applies to most air conditioning applications (assembly with fan coil units)
For reversible machines (ILD), these minimum volumes take into account the defrosting cycles in order to prevent temperature
degradation of the water loop.
Note:
For installations operating on low water volumes (assembly with air handling unit) or for industrial processes, the buffer tank is
essential.

AQUACIAT LD 150 180 200 240 260 300 360 390 450 520 600

Minimum system water volume, air conditioning application (litres) 121 140 164 182 207 243 181 205 240 204 240
Minimum system water volume, industrial process application (litres) 304 351 410 454 518 608 452 513 601 510 601
0.9 / 0.9 / 1.2 / 1.3 / 1.5 / 1.7 / 2.3 /
Min. / max. water exchanger flow rate without hydronic module(1) (l/s) 0.9 / 3 3.4 4.2 0.9 / 5 1/5 5.5 6.8 7.7 8.5 2 / 10.6 11.2
Low pressure(3) 2,9 3,2 3,7 4,1 4,1 4,4 5,1 6,3 6,5 7,9 8,2
Maximum water exchanger flow rate, Dual pump (l/s) (2)
High pressure (3) 3,4 3,8 4,4 5 5 5,2 6,2 6,5 8 8,7 8,9
(1) Maximum flow rate for a pressure drop of 100 kPa in the water exchanger
(2) Maximum flow rate corresponding to an operating pressure of 50 kPa (unit with high pressure pump).
(3) Maximum flow rate with single pump 2 to 4% higher, depending on the size.

NOTE: For the Buffer Tank Module option, the tank volume must be taken into account: 250 litres

AQUACIAT ILD 150 180 200 240 260 300 302 360 390 450 520 600

Minimum system water volume, air conditioning application (litres) 202 234 274 303 346 405 405 301 342 400 340 401
Minimum system water volume, industrial process application (litres) 304 351 410 454 518 608 608 452 513 601 510 601
Min. / max. water exchanger flow rate without hydronic module(1) (l/s) 0.9 / 3 0.9/3.4 0.9/4.2 0.9/5 1/5 1.2/5.5 1.2/6.8 1.3/6.8 1.5/7.7 1.7/8.5 2/10.6 2.3/11.2
Low pressure(3) 2,9 3,2 3,7 4,1 4,1 4,4 5,1 5,1 6,3 6,5 7,9 8,2
Maximum water exchanger flow rate, Dual pump (l/s)(2)
High pressure (3) 3,4 3,8 4,4 5 5 5,2 6,2 6,2 6,5 8 8,7 8,9
(1) Maximum flow rate for a pressure drop of 100 kPa in the water exchanger
(2) Maximum flow rate for an available pressure of 20 kPa (unit with low-pressure pumps) or 50 kPa (high pressure).
(3) Maximum flow rate with single pump 2 to 4% higher, depending on the size.

NOTE: For the Buffer Tank Module option, the tank volume must be taken into account: 250 litres

7.6 - Maximum system water volume


Units supplied with a hydronic module may include an expansion vessel which limits the volume in the water loop.
The table below gives the maximum loop volume compatible with the expansion vessel (for pure water or ethylene glycol depending
on the system's various concentrations and static pressures). If this volume is less than the volume of the installed loop, then it is
necessary to add an additional expansion vessel within the system.

LD / ILD without Buffer Tank option 150-300 302-600

Static pressure bar 1 2 3 1 2 3


Pure water l 597 398 199 1741 1161 580
10% EG l 471 314 157 1373 915 458
20% EG l 389 259 130 1135 757 378
30% EG l 348 232 116 1014 676 338
40% EG l 289 193 96 843 562 281
EG: Ethylene glycol

LD / ILD with Buffer Tank option 150-300 302-600

Static pressure bar 1 2 3 1 2 3


Pure water l 896 597 299 1680 1120 560
10% EG l 706 471 235 1260 840 420
20% EG l 584 389 195 930 620 310
30% EG l 522 348 174 750 500 250
40% EG l 434 289 145 630 420 210
EG: Ethylene glycol
NOTE: Take into account the buffer tank volume (250 litres)

AQUACIAT LD/ILD EN -28


7 - APPLICATION DATA

7.7 - Pressure drop curves for the water exchanger and its water inlet/outlet piping (for
units without pump)
Data applicable for pure water at 20°C.

LD/ILD sizes 150-300


Pressure drop , kPa

Water flow rate, l/s

B LD/ILD 150 E LD/ILD 240


C LD/ILD 180 F LD/ILD 260
D LD/ILD 200 G LD/ILD 300

LD/ILD sizes 302-600


Pressure drop , kPa

Water flow rate, l/s

B ILD 302 E LD/ILD 450


C LD/ILD 360 F LD/ILD 520
D LD/ILD 390 G LD/ILD 600

EN-29 AQUACIAT LD/ILD


8 - WATER CONNECTIONS
When connecting units to the water distribution pipe work, refer 8.1 - Operating precautions and
to the certified dimensional drawings supplied with the unit for recommendations
the dimensions and position of the exchanger water inlet and
Before the system start-up verify that the water circuits are
outlet connections.
connected to the appropriate heat exchangers.
The piping must not transmit any axial or radial force to the
The water circuit must have as few bends and horizontal sections
exchangers, or any vibrations.
at different levels as possible,
The water supply must be analysed and the circuit created must
include the required water treatment elements: filters, additives, Main points to be checked for the connection:
intermediate exchangers, bleed devices, vents, shut-off valves, • Observe the water inlet and outlet connections shown on
etc., according to the results, to prevent corrosion (for example, the unit.
damage to the tube protective surface if there is contamination • Install manual or automatic air purge valves at all high points
in the fluid), fouling and deterioration of the pump lining in the circuit.
Before any start-up, make sure the heat-transfer fluid is compatible • Maintain the pressure of the circuit(s) with a pressure-
with the water circuit materials and coating. Where additives or reducing valve and install a relief valve and an expansion
fluids other than those recommended by the manufacturer are vessel. Units supplied with a hydronic module include
used, ensure that these are not considered gases, and that they a valve. The expansion vessel is supplied as an option.
are class 2, as defined in directive 2014/68/EU. • Install thermometers in both the water inlet and outlet pipes.
• Install drain connections at all low points to allow the whole
Manufacturer's recommendations concerning heat transfer circuit to be drained.
fluids: • Install shut-off valves close to the water inlet and outlet
• No NH4+ ammonium ions in the water - these are very connections.
harmful to copper. This is one of the most important factors • Use flexible connections to reduce the transmission of
for the operating life of copper piping. A content of several vibrations.
tenths of mg/l will badly corrode the copper over time. • Insulate the cold water pipework, after testing for leaks, to
• Cl- Chloride ions are also harmful to copper with a risk of prevent heat transmission and condensation.
perforating corrosion. Keep at a level below 125 mg/l. • Cover the insulation with a vapour barrier. If the water pipes
• SO4- sulphate ions can cause perforating corrosion if their outside the unit pass through an area where the ambient
content is above 30 mg/l. temperature is likely to fall below 0°C, it must be protected
• No fluoride ions (<0.1 mg/l). against frost (antifreeze solution or electric heaters)
• No Fe2+ and Fe3+ ions if non-negligible levels of dissolved • If there are particles in the fluid which are liable to foul the
oxygen are present. Dissolved iron < 5 mg/l with dissolved exchanger, a screen filter must be installed upstream of the
oxygen < 5 mg/l. pump.
• Dissolved silica: Silica is an acid element of water and can NOTE: A screen filter must be installed for units supplied without
also lead to corrosion risks. Content < 1 mg/l. a hydronic module. This must be installed on the unit's water
• Water hardness: >0.5 mmol/l. Values between 1.0 and inlet pipe, close to the unit heat exchanger. It must be located
2.5 mmol/l are recommended. This will facilitate scale somewhere easily accessible to enable disassembly and
deposit that can limit corrosion of copper. Values that are cleaning.
too high can cause piping blockage over time. A total
If the filter is missing, the plate heat exchanger can quickly
alkalimetric titre (TAC) below 100 mg/l is desirable. Similarly,
become fouled during the first start-up, as it will trap any debris
regularly check the scaling of the extra heaters in the buffer
in the system, and correct unit operation will be affected (reduced
tank (if the option has been selected), as deposits of scale
water flow rate due to the increased pressure drop).
may limit the functions of the heaters or prevent them from
operating. Units with hydronic module are equipped with this type of filter.
• Dissolved oxygen: Avoid any sudden change in water • Do not introduce any excessive static or dynamic pressure
oxygenation conditions. It is as detrimental to deoxygenate into the heat exchange circuit (with regard to the design
the water by mixing it with inert gas as it is to over-oxygenate operating pressures).
it by mixing it with pure oxygen. The disturbance of • Products used for thermal insulation of recipients during
oxygenation conditions encourages destabilisation of hydraulic connection must be chemically neutral to the
copper hydroxides and enlargement of particles. surfaces on which they are applied. All original materials
• Electric conductivity 10-600 µS/cm. supplied by the manufacturer comply with this requirement.
• pH: Ideal case pH neutral at 20-25°C (7.5 < pH < 9).
Filling, topping up or emptying of the water circuit
must be carried out by qualified personnel using
the air bleed devices and tools and equipment
suitable for the products.
The heat transfer fluid should be filled and drained
using devices fitted to the water circuit by the
installer. The unit's exchangers must never be used
to top up the heat transfer fluid charge.

If an extra heater module is present in the water tank,


check that the tank is completely filled and that it is
well-vented (presence of a vent at the top of the tank).
If one of the extra heaters is not immersed in the
water, there is a risk it may be damaged (electrical
hazard).

AQUACIAT LD/ILD EN -30


8 - WATER CONNECTIONS

8.2 - Water connections


The hydronic module options are compatible only with closed loops.
The use of the hydronic module on open systems is prohibited.

Typical hydraulic circuit diagram without hydronic module

Option
Option Option

Option
Option

Typical hydraulic circuit diagram with hydronic module

Option
Option

Option
Option
Option

Option

Option

Option

Legend
Components of the unit and hydronic module System components
1 Screen filter (particle size of 1.2 mm) 16 Pocket
O 2 Expansion tank (option) 17 Air purge
3 Relief valve O 18 Flexible connection (Option)
4 Circulating pump (single or dual) 19 Shut-off valve
5 Air purge 20 800 µm screen filter (option – mandatory in the case of a unit without hydronic
6 Water drain tap module / Included on version with hydronic module)
7 Pressure sensor 21 Pressure gauge
Note: Provides pressure information for the pump inlet (see Control manual) 22 Water flow control valve
8 Temperature probe Note: not required if hydronic module with variable speed pump
Note: Provides temperature information for the water exchanger outlet (see 23 Charging valve
Control manual) 24 Bypass valve for frost protection (if shut-off valves are closed (item 19) during
9 Temperature probe
winter)
Note: Provides temperature information for the water exchanger inlet (see
Control manual) 25 Buffer tank (if required)
10 Pressure sensor 26 Extra heaters in the tank (option): the option includes a vent on the tank +
Note: Provides pressure information for the water exchanger outlet (see Control WTOT temperature sensor at the tank outlet
manual) - - - - - Hydronic module (unit with hydronic module option)
11 Check valve (if dual-pump) NOTE:
12 Plate heat exchanger - The system must be protected against frost.
O 13 Heater or heat trace cable for frost protection (Option)
- The unit's hydronic module and the water type heat exchanger may be protected
14 Water type heat exchanger flow rate sensor (factory-fitted option) against freezing using electric heaters and heat trace
O 15 Buffer Tank Module (Option)
cables (13)
- The pressure sensors are assembled on connections without Schrader.
Depressurise and drain the system before any work.

EN-31 AQUACIAT LD/ILD


8 - WATER CONNECTIONS

Figure 1: Internal hydronic equipment with dual pump option

LD/ILD sizes 150-300

LD/ILD sizes 302-600

AQUACIAT LD/ILD EN -32


8 - WATER CONNECTIONS

Figure 2: Internal hydronic equipment with dual pump option and buffer tank

LD/ILD sizes 150-300

LD/ILD sizes 302-600

LD/ILD sizes 150-300 LD/ILD sizes 302-600

Legend
B Steel sleeve F Victaulic clamp
C 800 µm screen filter G Hose
D Brass connector Water outlet
E Shut-off valve Water inlet

EN-33 AQUACIAT LD/ILD


8 - WATER CONNECTIONS

Figure 3: Internal hydraulic equipment with dual pump option, buffer tank and extra heaters

8.3 - Cavitation protection (with hydronic 8.4 - Flow rate detection


option)
Standard machine
To ensure the durability of pumps fitted on the integrated hydronic
modules, the control algorithm of units in the range includes All units are equipped as standard with a factory-set flow switch.
protection against cavitation. It cannot be adjusted on site.
It is therefore necessary to ensure a minimum pressure of 60 kPa The heat-transfer fluid pump must be servo-controlled by the
(0.6 bar) at the pump inlet both when shut down and during assembly if the unit is not equipped with the hydronic module
operation. option. Dedicated terminals are provided for installing the heat-
transfer fluid pump servo control (auxiliary operation switch of
A pressure below 60 kPa will prevent unit start-up, or will cause
the pump to be wired on site).
an alarm and shut-down.
To obtain an adequate pressure, it is recommended: Machine with hydronic module (option)
• To pressurise the hydraulic circuit between 100 kPa (1 bar) The “flow rate detection” functionality is handled by the option
and 400 kPa (4 bar) maximum at the pump inlet; via the pressure sensors.
• To clean the hydraulic circuit during water filling or after any
modifications are made;
• To regularly clean the screen filter.

AQUACIAT LD/ILD EN -34


8 - WATER CONNECTIONS

8.5 - Frost protection Winter position


fermé
closed
Damage caused by frost is not covered by the
warranty.

The plate exchangers, the pipes, the buffer tank pump(s) and Unité
Unit Réseau
Water eau
system
ouvert
open
the hydronic module pumps can be damaged by frost. fermé
closed
The components of the unit (heat exchanger, pipes, hydronic
module, buffer tank module) will be protected by following the
recommendations below. Protection of the remainder of the
system is the responsibility of the installer. IMPORTANT:
The plate heat exchanger and all the components of the water Depending on the atmospheric conditions in your region, you
circuit can be protected against freezing by draining the entire need to:
machine completely, checking that there are no retention points. • Add an appropriate antifreeze solution (maximum of 45%)
If this is not possible, the plate heat exchanger and all the to protect the system down to a temperature of 10 K below
components of the water circuit can be protected against the lowest temperature likely to occur locally.
freezing: • For extended shut-downs, drain and add an anti-freeze
• Down to -20°C by heaters and heat trace cables (fitted as solution to the heat exchanger (use the drain valve located
an option on the exchanger and internal pipe system) at the water inlet).
supplied automatically (for units without the hydronic • To prevent corrosion due to differential aeration, if the
module) system is to be empty for more than 1 month, the heat-
• Down to -10°C for cooling only machines (without buffer transfer fluid circuit should be protected with a blanket of
tank module option) and 0°C for reversible machines, neutral gas (0.5 bar maximum). If the heat-transfer fluid
Cooling only with buffer tank via a heater on the heat does not meet the recommendations, a nitrogen blanket
exchanger supplied automatically and pump cycling (for must be applied immediately.
units with hydronic module). • At the start of the next season, refill the unit with water and
• Down to -20°C by heaters and heat trace cables (fitted as add an inhibitor.
an option on the exchanger, buffer tank module (option) • If additional equipment is added to the system, the installer
and internal pipe system) supplied automatically and pump must comply with the basic recommendations, especially
circulation (for units with the hydronic module) the minimum and maximum flow rates which must be
between the values shown in the operating limits table
Never power off the heaters for the water exchanger and the (application data).
water circuit or pump, as they will no longer be providing frost • If frost protection is dependent on electric heaters, never
protection. deenergize the unit when frost protection is required. To
To ensure they continue to receive power, the main switch for ensure protection, the main unit disconnect switch and the
the unit or the customer's circuit and the auxiliary circuit breaker auxiliary heater protection circuit breaker must be closed
for the heaters must be left closed (see the wiring diagram for (see wiring diagram to locate these components). If it is not
the location of these components). to be used in freezing conditions, or during a prolonged
To protect units with a hydronic module from freezing, water must period without power (whether or not this is scheduled), the
be circulated in the water circuit by the pump, which is activated water exchanger and external pipes must be drained
at regular intervals. If the system is isolated by a valve, it is immediately
imperative to install a bypass as indicated below. • In case of prolonged non-usage, the hydraulic circuits must
be protected by circulating a passivating solution. (Consult
a specialist).
• The exchanger temperature sensors are an essential frost
protection element: if piping trace heaters are used, ensure
the external heaters do not affect the measurements
provided by these sensors.
• If auxiliary equipment is installed in the system, the installer
must ensure that the resultant flow rates are still within the
minimum and maximum values indicated in the operating
limits table (application data).

EN-35 AQUACIAT LD/ILD


8 - WATER CONNECTIONS

8.6 - Extra electrical heaters field-installed or integrated into the buffer tank (depending on
the option chosen)
To compensate for the reduction in the heat pump's output at low ambient temperatures, which changes significantly as shown in
the graph below, it is possible to install on the water outlet auxiliary electrical heaters of sufficient power to offset the heat pump
capacity drop.
These heaters can be controlled via the dedicated option.
Up to four outputs are available to control the contactors (not supplied on the plate for the option to be field installed) on the heaters,
thereby enabling gradual compensation of the reduction in the heat pump output.
These outputs are configurable to allow for two, three or four stages as required (depending on the option chosen). The last stage
is only activated in case of shut-down due to a fault on the heat pump (emergency).
It is possible to choose an extra heater option to be field installed or an option which directly integrates the heaters in the buffer
tank. In the case of this second option, three extra heater outputs are available: 16 kW / 31 kW / 45 kW.
The graph below shows an example of operation with additional heaters, where the power of the four heaters equals the capacity
of the heat pump at an outdoor air temperature of 7 °C.

Example of additional electric heaters


Pump power (%)

Outdoor air temperature, °C


Legend
B Stage 1
C Stage 2
D Stage 3
E Stage 4 (safety)
A Variation of the pump output with air temperature
B Building heat load
C Equilibrium point between the heat pump output and the building heat load
Operating range for which the heat pump output is less than the building thermal load
Operating range for which the heat pump output is greater than the building thermal load

AQUACIAT LD/ILD EN -36


9 - NOMINAL SYSTEM WATER FLOW CONTROL
Refer to the diagram in the "Hydraulic connections" section Hydraulic circuit cleaning procedure
for all reference points mentioned in this chapter. • Open all control valves completely (item 22).
The water circulation pumps of unit range have been designed • Start up the system pump.
to allow the hydronic modules to operate at each possible • Read the pressure drop of the plate heat exchanger, using
conditions, i.e. with chilled water temperature differences at full the pressure differential gauge to find the difference
load from 3 to 10 K. between the unit inlet and outlet (item 21).
• Let the pump run for 2 hours consecutively to clean up the
This temperature difference required between the water inlet
hydraulic circuit of the system (presence of contaminating
and outlet determines the nominal flow of the system. Use the
solids).
specification provided while selecting the unit to determine the
• Perform another reading.
operating conditions of the system.
• Compare this value to the initial value.
In particular, collect the data to be used for setting the installation • A reducing value of the flow indicates that the filters on the
flow rate: system need to be removed and cleaned. In this case, close
• For a unit without hydronic module: nominal pressure drop the shut-off valves on the water inlet and outlet (item 19)
at the unit terminals (plate heat exchanger + internal water and remove the filters (items 20 and 1) after draining the
pipe). This is measured with pressure differential gauges hydronic part of the unit (items 6).
that must be installed at the unit's inlet and outlet (item 21). • Remove the air from the circuit (items 5 and 17).
• Units with fixed speed pumps: nominal flow rate. The Repeat until all fouling is removed from the filter.
pressure of the fluid is measured by sensors installed at
the inlet of the pump and outlet of the unit (items 7 and 10). Water flow control procedure
The system calculates the flow rate associated with this Once the circuit is cleaned, read the pressures on the pressure
differential pressure. The flow rate can be read directly on gauges (water inlet and outlet pressure) to determine the
the user interface (refer to the control manual for the range). pressure drop within the unit (plate heat exchanger + internal
• Units with variable speed pumps – control on pressure pipework).
difference: pressure difference at the hydronic module
Compare the value obtained with the design value predicted by
terminals; the buffer tank module option is not taken into
the selection software.
account.
• Units with variable speed pumps - control on temperature If the pressure drop reading is above the preset value,
difference: nominal temperature delta at the exchanger. this indicates that the flow rate at the terminals of the unit
(and therefore within the installation) is too high. In this case,
If this information is not available when the system is started up,
close the control valve and read the new difference in pressure.
contact the engineering and design department responsible for
the system to obtain it. Repeat as necessary, closing the control valve until the specific
pressure drop corresponding to the unit's nominal flow rate at
These data can be obtained either from the performance tables
the required operation point is achieved
included in the technical documentation (for cases where the
water exchanger temperature delta is 5 K) or from the "Electronic NOTE:
Catalogue" selection program for all other applicable temperature If the network has an excessive pressure drop in relation to the
delta in the range of 3 to 10 K. available static pressure delivered by the system's pump, the
nominal water flow cannot be obtained (lower resulting flow) and
9.1 - Units without hydronic module the difference in temperature between the water inlet and outlet
of the water heat exchanger will be increased.
General
To reduce the system's hydronic network pressure drop:
The nominal flow rate of the system will be set using a manual • Reduce the pressure drops of individual components
valve that should be installed on the water outlet pipe (item 22 (bends, level changes, options, etc.) as much as possible;
on the water circuit schematic diagram). • Use the correct pipe diameter
Due to the pressure drop it generates on the hydraulic network, • Do not extend the piping system.
this flow control valve is used to set the network pressure/flow
rate curve to the pump pressure/flow rate curve, to obtain the
nominal flow rate at the desired operation point.
This is checked by reading the pressure drop on the unit (plate
heat exchanger + internal piping).
As the exact total system pressure drop is not known at start-up,
it is necessary to adjust the water flow with the control valve to
obtain the system's specific flow rate.

EN-37 AQUACIAT LD/ILD


9 - NOMINAL SYSTEM WATER FLOW CONTROL

Example: Unit with specified nominal flow rate of 3.7 l/s 9.2 - Units with hydronic module and
fixed-speed pump (only for negative cold
applications)
See the paragraph on "Units without hydronic module"
Hydraulic circuit cleaning procedure
Pressure drop , kPa

• Open all control valves completely (item 22).


• Start up the unit's pump.
• Read the value of the flow on the user interface.
• Let the pump run for 2 hours consecutively to clean up the
hydraulic circuit of the system (presence of contaminating
solids).
• Perform another reading.
• Compare this value to the initial value.
• A reducing value of the flow rate indicates that the filters on
the system need to be removed and cleaned. In this case,
close the shut-off valves on the water inlet and outlet
Water flow rate, l/s
(item 19) and remove the filters (items 20 and 1) after
draining the hydronic part of the unit (items 6).
Legend: • Remove the air from the circuit (items 5 and 17).
1 ‘‘Pressure drop across unit terminals / Flow rate’’ curve
• Repeat until all fouling is removed from the filter
2 With the valve open, the pressure drop reading (111 kPa) gives point A on the
curve
Water flow control procedure
A Operating point reached with the valve open
3 With the valve open, the flow rate reached is 4.8 l/s: this is too high, the valve Once the circuit is cleaned, read the flow value on the user
needs to be re-closed
interface and compare it to the theoretical selection value.
4 With the valve partially re-closed, the pressure drop reading (65 kPa) gives
point B on the curve If the flow rate read is greater than the specified value, this
B Operating point reached with the valve partially closed indicates that the overall pressure drop in the system is too low
5 With the valve partially re-closed, the flow rate reached is 3.7 l/s: this is the
target flow rate, so the valve is suitably positioned
compared to the available static pressure generated by the pump.
In this case, close the control valve (item 22) and read the new
flow rate value.
Repeat as necessary, closing the control valve (item 22) until
the system's specific pressure drop corresponding to the unit's
design flow rate is achieved.
NOTE:
If the network has an excessive pressure drop in relation to the
available static pressure delivered by the unit pump, the nominal
water flow rate cannot be obtained (lower resulting flow rate)
and the difference in temperature between the water inlet and
outlet of the water type heat exchanger will be increased
To reduce the system's hydraulic network pressure drop:
• Reduce the pressure drops of individual components
(bends, level changes, options, etc.) as much as possible;
• Use the correct pipe diameter;
• Do not extend the hydronic systems

AQUACIAT LD/ILD EN -38


9 - NOMINAL SYSTEM WATER FLOW CONTROL

9.3 - Units with hydronic module and variable Procedure for controlling the pressure differential setpoint
speed pump – Pressure differential control Once the circuit is cleaned, place the water circuit in the
The system flow rate has not been set to a nominal value. configuration for which the unit selection was performed
(generally, this will be all valves open and all cooling coils active)
The flow rate will be adjusted, by varying the pump speed,
to maintain a system pressure differential value defined by the Read the value of the flow on the user interface and compare it
user. with the theoretical value of the range:
• If the flow rate read is greater than the preset value, reduce
This is checked by the pressure sensor at the water exchanger
the pressure differential setpoint on the user interface to
outlet (item 10 on the main water circuit diagram).
reduce the flow rate value;
The system calculates the measured pressure difference, • If the value read is lower than the preset value, increase
compares it with the setpoint value set by the user and then the pressure differential setpoint on the user interface to
modulates the pump speed module, resulting in: increase the flow rate value
• an increase in the flow rate if the measurement is below
Repeat until the unit's nominal flow rate at the required operation
the setpoint,
point is achieved.
• a decrease in the flow rate if the measurement exceeds the
setpoint. Stop the forced operation of the pump and proceed to the
configuration of the unit for the required control mode. Modify
This modulation is limited only by the maximum and minimum
the control parameters:
flow rates for the unit and by the maximum and minimum
• Set water flow control to ‘pressure differential’
allowable pump speeds.
• Set the value of the required pressure differential.
The maintained pressure difference value may, in certain cases,
The unit's default factory configuration is the maximum speed
differ from the setpoint value:
(frequency: 50 Hz).
• if the setpoint value is too high (obtained for a flow rate
higher than the maximum value or a frequency greater than NOTE:
the maximum value), the system will stop once it reaches If during adjustment, the low or high frequency limits are reached
the maximum flow rate or maximum frequency, which will before reaching the specified flow rate, keep the pressure
result in a pressure difference below the setpoint, differential value at its lower or higher limit as the control
• if the setpoint value is too low (obtained for a flow rate lower parameter value.
than the minimum value or a frequency less than the If the user knows in advance the pressure differential value at
minimum value), the system will stop once it reaches the the unit outlet to be maintained, this value can be entered directly
minimum flow rate or minimum frequency, which will result as data to be declared. You should not, however, omit the water
in a pressure difference greater than the setpoint. circuit cleaning sequence
Contact the manufacturer's service department to implement the
procedures described below.
Hydraulic circuit cleaning procedure
Before proceeding, it is advisable to remove any possible
contamination from the water circuit.
• Start-up the system pump by using the forced start
command.
• Control the frequency to the maximum value to generate
a higher flow.
• If there is a ‘‘Maximum flow exceeded’’ alarm, reduce the
frequency until an acceptable value is reached.
• Read the value of the flow on the user interface.
• Let the pump run for 2 hours continuously to clean up the
system's hydraulic circuit (presence of contaminating
solids).
• Perform another reading of the flow and compare this value
with the initial value. A reducing value of the flow indicates
that the filters on the system need to be removed and
cleaned. In this case, close the shut-off valves on the water
inlet and outlet (item 19) and remove the filters (items 20
and 1) after draining the hydronic part of the unit (items 6).
• Remove the air from the circuit (items 5 and 17).
• Repeat until all fouling is removed from the filter

EN-39 AQUACIAT LD/ILD


9 - NOMINAL SYSTEM WATER FLOW CONTROL

9.4 - Units with hydronic module and variable speed pump – Temperature differential control
The system flow rate has not been set to a nominal value.
The flow rate will be adjusted, by varying the pump speed, to maintain a heat exchanger temperature differential value defined by
the user.
This is checked by the temperature sensors at the water exchanger inlet and outlet (items 8 and 9 on the main water circuit diagram).
The system reads the measured temperature values, calculates the corresponding Delta T, compares it with the setpoint value set
by the user and then modulates the pump speed.
• This results in an increase in the flow rate if the Delta T° exceeds the setpoint.
• This results in a decrease in the flow rate if the Delta T° is less than the setpoint.
This modulation is limited only by the maximum and minimum flow rates for the unit and by the maximum and minimum allowable
pump speeds.
The resulting Delta T° may, in certain cases, differ from the setpoint value:
• if the setpoint value is too high (obtained for a flow rate lower than the minimum value or a frequency less than the minimum
value), the system will stop once it reaches the minimum flow rate or minimum frequency, which will result in a temperature
delta below the setpoint,
• if the setpoint value is too low (obtained for a flow rate higher than the maximum value or a frequency greater than the maximum
value), the system will stop once it reaches the maximum flow rate or maximum frequency, which will result in a Delta T°
above the setpoint.
Contact the manufacturer's service department to implement the procedures described below.
Hydraulic circuit cleaning procedure
Refer to the water circuit cleaning procedure.
Procedure for adjusting the Delta T° setpoint
Once the circuit is cleaned, stop the forced start of the pump and proceed to the configuration of the unit for the required control
mode.
Modify the control parameters:
• Set water flow control to ‘temperature differential’
• Set the value of the required differential temperature.
The unit's default configuration is at the fixed speed (50 Hz)

AQUACIAT LD/ILD EN -40


9 - NOMINAL SYSTEM WATER FLOW CONTROL

9.5 - Pump flow rate/pressure curves


Units with hydronic module (fixed speed pump or variable speed pump at 50 Hz)
Data applicable for:
Pure water at 20 °C.
Refer to the "Water type heat exchanger water flow" section for the maximum water flow values.
If ethylene glycol is used, the maximum flow rate is reduced.

Low pressure pumps


Pressure head, kPa

Water flow rate, l/s

B LD/ILD 150 to 360


C LD/ILD 390 and 450
D LD/ILD 520 and 600

High pressure pumps


Pressure head, kPa

Water flow rate, l/s

B LD/ILD 150 to 390


C LD/ILD 450 to 600

EN-41 AQUACIAT LD/ILD


9 - NOMINAL SYSTEM WATER FLOW CONTROL

9.6 - Available static pressure for the installation


Units with hydronic module (fixed speed pump or variable speed pump at 50 Hz)
Data applicable for:
• Pure water at 20 °C.
• Refer to the "Water type heat exchanger water flow" section for the maximum water flow values.
• If ethylene glycol is used, the maximum flow rate is reduced.
WARNING: With the filter and/or buffer tank module option, the curves below do not take the pressure drops for these
components into account. If necessary, refer to the water filter and/or buffer tank characteristic curves to correct the data
below.

Low pressure pumps


140 220

200
120
180

Pressure head, kPa


Pressure head, kPa

160
100
140

80 120

100
60
80

60
40
40
1 2 3 4 5 1 2 3 4 5
20 20
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 0 1 2 3 4 5 6 7 8 9 10

Water flow rate, l/s Water flow rate, l/s


B ILD 150 E ILD 240 & 260 B ILD 302 & 360 E ILD 520
C ILD 180 F ILD 300 C ILD 390 F ILD 600
D ILD 200 D ILD 450

High pressure pumps


230 230

210 210
Pressure head, kPa
Pressure head, kPa

190 190

170 170

150 150

130 130

110 110

90 90

70 70

B C D E F G B C DE F
50 50
0 1 2 3 4 5 6 0 1 2 3 4 5 6 7 8 9 10

Water flow rate, l/s Water flow rate, l/s


B LD 150 E LD 240 B LD 360 E LD 520
C LD 180 F LD 260 C LD 390 F LD 600
D LD 200 G LD 300 D LD 450

230 230

210 210
Pressure head, kPa
Pressure head, kPa

190 190

170 170

150 150

130 130

110 110

90 90

70 70
B C D E F B C D E F
50 50
0 1 2 3 4 5 6 0 1 2 3 4 5 6 7 8 9 10

Water flow rate, l/s Water flow rate, l/s


B ILD 150 E ILD 240 & 260 B ILD 302 & 360 E ILD 520
C ILD 180 F ILD 300 C ILD 390 F ILD 600
D ILD 200 D ILD 450

AQUACIAT LD/ILD EN -42


9 - NOMINAL SYSTEM WATER FLOW CONTROL

800 µm water filter pressure drop curves

ΔP [kPa]

Qv [m3/h]
LD/ILD 150-300 LD/ILD 302-600

Buffer tank pressure drop curves


ΔP [kPa]

Qv [m3/h]
LD/ILD 150-602

EN-43 AQUACIAT LD/ILD


10 - SYSTEM START-UP

10.1 - Checks before system start-up 10.2 - Commissioning


Before starting up the thermodynamic system, the complete Always ensure you have read and fully understood the operating
system, including the thermodynamic system, must be verified instructions for the units before starting up the unit, and ensure
against the installation drawings, dimensional drawings, system the following precautions have been taken:
piping and instrumentation diagrams and the wiring diagrams. • Check the heat-transfer fluid circulation pumps, the air
All measures must be taken to ensure that the pressure and handling equipment, and any other equipment connected
temperature limits, which are specifically those listed on the to the exchangers.
nameplates, are not exceeded during operation, maintenance • Refer to these instructions.
and recirculation. • Refer to the electrical diagram delivered with the unit.
• Ensure that there is no refrigerant leak.
Heat exchange fluid temperatures above the maximum
• Check that all clamps securing the pipes are correctly
recommended can lead to an increase in the refrigerant pressure
tightened.
and can cause a loss of refrigerant due to the relief valve
• Check the power supply at the main connection point and
discharge.
the order of phases.
National regulations must be followed during these checks. If • Open the suction shut-off valves on each circuit for the
the national regulation does not specify any details, refer to corresponding units.
standard EN 378 as follows: • For units without the factory-fitted hydronic module option,
External visual checks of the installation: the installer is responsible for heat protection and the
• Ensure that the unit is charged with refrigerant. Verify on connections relating to the system pump.
the unit nameplate that the ‘fluid transported’ is that • Check the operation of the compressor oil crankcase
recommended for operation, and is not nitrogen. heaters 6 hours before starting up the system.
• Compare the complete system with the cooling system and IMPORTANT: Commissioning and start-up must be
power circuit diagrams. supervised by a qualified engineer.
• Check that all documents provided by the manufacturer • The system must have a heat load and water flowing in the
(dimensional drawings, pipe and instrument diagram (PID), exchangers when it is started up and tested.
declarations, etc.) to comply with the regulations are • All setpoint adjustments and control tests must be carried
present. If any documentation is missing, order out before the unit is started up.
a replacement. • Refer to the Service guide.
• Verify that the environmental safety and protection devices
Proceed with the unit commissioning.
and arrangements provided by the manufacturer to comply
Make sure all safety devices are operational, and especially that
with the regulations are present and correct.
the high pressure switches are activated and that any alarms
• Check that all declarations of conformity for the pressure
have been cleared.
vessels, identification plates, and documentation required
to comply with local regulations are present. NOTE: If the manufacturer's recommendations (system, water
• Verify that access and safety routes are unobstructed. and power connections) are not observed, no claims made under
• Comply with the instructions and directives to prevent the the warranty will be accepted.
deliberate release of refrigerant fluids.
• Verify the installation of connections.
• Verify the supports and fixing elements (materials, routing
and connection).
• Verify the quality of welds and other joints.
• Check the protection against mechanical damage.
• Check the protection against heat.
• Check the protection of moving parts.
• Verify the accessibility for maintenance or repair and to
check the piping.
• Verify the status of the valves.
• Verify the quality of the thermal insulation.
• Check the condition of 400 V cable insulation.
IMPORTANT: If the compressors are equipped with mounts,
check whether these mounts have clamping mechanisms.
If they do, the clamping mechanisms must be removed
before system start-up. Clamping mechanisms are identified
by red collars and signalled by a label affixed to the
compressor sub-assembly.

AQUACIAT LD/ILD EN -44


10 - SYSTEM START-UP

10.3 - Essential points to check

Compressors
Ensure that each compressor is rotating in the correct direction,
checking that the discharge temperature rises quickly, the HP
increases and the LP drops. If it is rotating in the wrong direction,
the electric power supply is incorrectly wired (reversed phases).
To ensure rotation in the correct direction, swap the two power
supply phases.
- Check the compressor discharge temperature with a contact
sensor
- Check the input current; it should be normal
- Check all safety devices to make sure they operate correctly
Hydraulics
The exact total drop in system pressure will not be known at
commissioning. It will therefore be necessary to adjust the flow
of water with the control valve until the desired nominal rate is
obtained.
By causing the pressure in the water system to drop, this control
valve aligns the system pressure/flow curve with that of the pump
so that the nominal flow rate corresponding to the desired
operating point is obtained. The pressure drop in the water
exchanger (read using the pressure gauge placed on the
exchanger inlet and outlet) is the reference to be used to check
and adjust the nominal flow rate of the system.
Follow the procedure described below:
- Open the control valve completely
- Let the pump run for two hours to flush out any solid particles
in the circuit
- Read the pressure drop in the water exchanger when the
pump is turned on and then two hours afterwards
- If the pressure drop has decreased, this means that the screen
filter is clogged. It must be removed and cleaned
- Repeat until the filter is completely clean
- If the system pressure drops are above the available static
pressure delivered by the pump, the resulting water flow rate
will be low and the difference in temperature between the
exchanger inlet and outlet will be too high. This is why pressure
drops must be minimised. Check that this difference is within
the values on the curve (refer to section "Water type heat
exchanger min. water volume and flow rate")
- If the extra heater option is present in the water tank, check
that the tank is completely filled so that all the heaters are
immersed, check that the immersion heaters are operating
correctly, and that the safety thermostats are triggered
(present on each immersion heater).
Refrigerant charge
Each unit is shipped with an exact charge of refrigerant.

EN-45 AQUACIAT LD/ILD


11 - MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS
11.1 - Compressors See the Service Guide for the oil removal and refill procedures.
The units use hermetically sealed scroll compressors. WARNING: too much oil in the circuit can cause the unit to
malfunction.
Each compressor is equipped with a crankcase oil heater,
as standard. There is no heater fault detection. NOTE: only use oils which have been approved for the
compressors. Never use oils which have been exposed to air.
Each compressor sub-assembly has:
• Anti-vibration mountings between the unit chassis and the WARNING: polyolester oils are completely incompatible with
chassis of the compressor sub-assembly, mineral oils. Only use the oils specified by the manufacturer.
• A safety pressure switch on the discharge line of each
circuit, 11.3 - Air heat exchanger
• Pressure and temperature sensors at the common suction
The coils on the units are composed of:
line and a pressure sensor at the common discharge line.
- Aluminium fins fixed onto copper pipes with grooves inside
(RTPF) for reversible machines
11.2 - Lubricant - Micro-Channel coils made entirely from aluminium for Cooling
The compressors installed on the units have an oil charge, only machines.
ensuring good lubrication under all operating conditions. The oil
level check can be done:
• On the system: the oil levels must be greater than or equal
to half of the sight glass.
• A few minutes after the sub-function has come to a complete
stop: the oil levels must be visible in the sight glasses.
If this is not the case, there might be a leak or an oil trap in the
circuit. If there is an oil leak, find and repair it, then refill with
refrigerant and oil.

11.4 - Fans
Each fan motor is equipped with a high-performance impeller made from a recyclable composite material. The motors are
three-phase, with permanently lubricated bearings and class F insulation (rated IP55).
For more detailed information, refer to the requirements in the table below according to Regulation No. 327/2011 implementing
Directive 2009/125/EC with regard to eco-design requirements for motor-driven fans with an electric input power of between 125 W
and 500 kW.

Standard LD(1) or with Xtra low LD with Winter Operation option


Product/ Option Standard LD(2)
noise option down to -20°C or Xtra Fan

Fan overall efficiency % 36,6 38,0 39,8


Measurement category Static Static Static
Efficiency category A A A
Target energy efficiency N(2015) 40 N(2015) 40 N(2015) 40
Efficiency level at the optimum 43,3 42,3 43,7
energy efficiency point
Frequency inverter NO NO YES
Year of manufacture See label on the unit See label on the unit See label on the unit
Fan manufacturer Simonin Simonin Simonin
Motor manufacturer Regal Beloit Regal Beloit Regal Beloit
Fan reference 00PSG000000100A 00PSG000000100A 00PSG000000100A
Motor reference 00PPG000464500A 00PPG000464600A 00PPG000464700A
Motor nominal power kW 0,88 2,09 2,41
Flow rate m3/s 3,59 4,07 5,11
Pressure Pa 90 195 248
Rotation speed rpm 710 966 1137
Specific ratio 1,002 1,002 1,002
Relevant information to facilitate end-of-life disassembly, See service manual See service manual See service manual
recycling and disposal
Relevant information to minimise impact on the See service manual See service manual See service manual
environment
(1) For sizes LD150 to 240 and LD 360 to 450 only
(2) For sizes LD 260 to 300 and 520 to 600 only

AQUACIAT LD/ILD EN -46


11 - MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS

Regulation 2019/1781 repealing regulation 640/2009, governs the requirements relating to ecodesign applicable to electric motors
and to speed regulators in accordance with the directive 2009/125/EC. Our fan motor assemblies are excluded from this:

Standard LD(1) or with Xtra low LD with Winter Operation option


Product/ Option Standard LD(2)
noise option down to -20°C or Xtra Fan
Motor type Dual-speed asynchronous Dual-speed asynchronous Asynchronous
Number of poles 8 6 6
Rated input frequency Hz 50 50 50
Nominal voltage V 400 400 400
Number of phases 3 3 3
Fan included in the scope of application of regulation NO NO NO
2019/1781
Product leaflet for exemption Article 2.2.a) Article 2.2.a) Article 2.2.a)
Ambient air temperature for which the motor is °C 68,5 68,5 68,5
specifically designed
(1) For sizes LD150 to 240 and LD 360 to 450 only
(2) For sizes LD 260 to 300 and 520 to 600 only

Standard ILD(1) or with ILD with Winter Operation option


Product/ Option Standard ILD(2)
Xtra low noise option down to -20°C

Fan overall efficiency % 36,6 38 39,8


Measurement category A A A
Efficiency category static static static
Target efficiency level ERP2015 40 40 40
Efficiency level at optimum efficiency point 43,3 42,3 43,7
Frequency inverter NO NO YES
Year of manufacture See label on the unit See label on the unit See label on the unit
Fan manufacturer Simonin Simonin Simonin
Motor manufacturer Regal Beloit Regal Beloit Regal Beloit
Fan reference 00PSG000000100A 00PSG000000100A 00PSG000000100A
Motor reference 00PPG000464500A 00PPG000464600A 00PPG000464700A
Motor nominal power kW 0,88 2,09 2,41
Flow rate m3/s 3,59 4,07 5,11
Pressure Pa 90 195 248
Rotation speed rpm 710 966 1137
Specific ratio 1,002 1,002 1,002
Relevant information to facilitate end-of-life disassembly, See service manual See service manual See service manual
recycling and disposal
Relevant information to minimise impact on the environment See service manual See service manual See service manual

(1) For sizes ILD150 to 200 and LD 302 to 450 only


(2) For sizes ILD 240 to 300 and LD 520 to 600 only

Standard ILD(1) or with ILD with Winter Operation option


Product/ Option Standard ILD(2)
Xtra low noise option down to -20°C
Motor type Dual-speed asynchronous Dual-speed asynchronous Asynchronous
Number of poles 8 6 6
Rated input frequency Hz 50 50 60
Nominal voltage V 400 400 400
Number of phases 3 3 3
Motor included in the application domain NO NO NO
of regulation 2019/1781
Sales leaflet for exemption Article 2.2.a) Article 2.2.a) Article 2.2.a)
Ambient air temperature for which °C 68.5 68.5 68.5
the motor is specifically designed
(1) For sizes ILD150 to 200 and LD 302 to 450 only
(2) For sizes ILD 240 to 300 and LD 520 to 600 only

11.5 - Electronic expansion valve (EXV)


The EXV is equipped with an electronically controlled stepper motor.

11.6 - Moisture indicator


Located on the EXV, permits monitoring of the unit charge and indicates moisture in the circuit.
The presence of bubbles in the sight glass indicates an insufficient charge or non-condensables in the system. The presence of
moisture changes the colour of the indicator paper in the sight glass

EN-47 AQUACIAT LD/ILD


11 - MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS

11.7 - Dryer filter 11.12 - 4-way valve


This single-piece brazed component is situated on the liquid line. Used to reverse the cycle for operating in cooling and heating
The role of the filter drier is to keep the circuit clean and moisture- modes, as well as during defrost cycles.
free. The moisture indicator shows when the filter drier needs to
be changed. A temperature difference between the box inlet and 11.13 - Electrical box
outlet indicates fouling of the component.
The electrical box for the units in the range is equipped with
In the case of reversible machines, the dehydrator is "bi-flow",
electric heaters to prevent the formation of condensation when
i.e. it filters and dehydrates in both operating modes. Its pressure
running at low outdoor temperatures. These heaters are fitted
drop is much bigger in heating mode.
on top of the box, on the outside, and are covered with a layer
of thermal insulation. They are activated according to the ambient
11.8 - Water type heat exchanger temperature.
The water exchanger is a "brazed plate" type, with 1 or
2 refrigerating circuits 11.14 - Variable speed ventilation
The water connections of the heat exchanger are Victaulic The variable-speed drives on the fans are used to optimise the
connections. efficiency of the unit depending on the condition of use (air
The water heat exchanger is thermally insulated with 19 mm of temperature, circuit capacity) and hence improve the seasonal
foam rubber. It is equipped as standard with an electric heater efficiency (SEER and SCOP).
providing frost protection All the variable-speed fans are actuated by the machine
Thermal insulation of chiller / piping must be chemically neutral controller, and each variable-speed fan is equipped with its own
to the surfaces on which they are applied. All original materials variable speed drive. The speed is controlled by the refrigerating
supplied by the manufacturer comply with this requirement. circuit.
NOTE - Monitoring in operation This rotation speed at full load or partial load for each circuit is
• Follow local regulations on the monitoring of pressure controlled by an algorithm that continuously optimises the
equipment condensing temperature to obtain the best unit energy efficiency
• The user or operator is usually required to create and (EER and COP) whatever the operating conditions.
maintain a monitoring and maintenance log.
• In the absence of any regulations, or in addition to the 11.15 - Electrical box
regulations, follow the guidance in the EN 378 standard.
The electrical box for reversible units in the range is equipped
• Follow the local professional recommendations,
with electric heaters to prevent the formation of condensation
whenever they exist.
when operating at low outdoor temperatures. These heaters are
• Regularly check for the presence of any impurities (e.g.
fitted on top of the box, on the outside, and are covered with
sand, grit) in the heat transfer fluids. These impurities
a layer of thermal insulation. They are activated according to the
can cause wear and/or pitting corrosion.
ambient temperature.
• The reports of the periodical checks by the user or the
operator must be included in the monitoring and Fan motor electrical protection
maintenance register.
Each fan is individually protected by a magnetothermal circuit
breaker. Refer to the wiring diagram to identify the associated
11.9 - Refrigerant outlets.
Units running with R410A
11.16 - Connect Touch control
11.10 - HP safety pressostat The interface of the Connect Touch Control has the following
The units are equipped with high pressure safety switches with properties:
automatic reset on the HP side. These pressure switches are • It is a 4-inch 1/3 colour interface.
located at the discharge of each circuit. • It is intuitive and user-friendly. Clear and concise information
is presented in the local language (8 available).
11.11 - Tank • The complete menu can be adapted to the various users
(end customer, maintenance personnel, manufacturer),
The reversible units in the range are equipped with mechanically • Unit use and configuration are secure. Password protection
welded tanks which can store the excess load when the unit is prevents non-authorized access to advanced settings.
operating in heating mode. • No password is required to access the most important
operating parameters.

AQUACIAT LD/ILD EN -48


12 - OPTIONS

12.1 - Tables of options

Options Description Advantages LD ILD

Corrosion protection, Fins made of pre-treated aluminium (polyurethane Improved corrosion resistance, recommended for
NO •
traditional coils and epoxy) moderate marine and urban environments
Medium-temperature brine Low temperature chilled water production down to Covers specific applications such as ice storage
• •
solution 0 °C with ethylene glycol and propylene glycol. and industrial processes
Low temperature chilled water production down to
Low-temperature brine Covers specific applications such as ice storage
-15°C with ethylene glycol and -12°C with • •
solution and industrial processes
propylene glycol.
Unit equipped with specifics variable-speed fans :
XtraFans (See specific chapter for maximum Ducted fan discharge, optimised temperature
XtraFan available static pressure according to size), each control, based on the operating conditions and • •
fan equipped with a connection flange & sleeves system characteristics
allowing the connection to the ducting system.
Xtra Low Noise Acoustic compressor enclosure and low-speed fans Noise emission reduction at reduced fan speed • •
Protection grilles Metallic protection grilles Coil protection against possible impact • •
Soft starter Electronic starter on each compressor Reduced start-up current • •
EC fans for winter operation EC fan control via integrated Electronic
Stable unit operation when the air temperature is
cooling mode down to Commutated motors. One EC fan on each • NO
between 0°C and -20°C
-20°C refrigerant circuit
All year round cooling Stable unit operation when the air temperature is
Fanspeed control via frequency converter NO •
operation down to -20°C between 0°C and -20°C
Hydronic module frost Hydraulic module frost protection at low outside
Electric heater on the hydraulic module • •
protection temperatures down to -20°C
Electric heater on the water exchanger hydraulic Water exchanger and hydraulic module frost
Exchanger & hydraulic frost ALL with water ALL with water
module and optional expansion tank & water buffer protection between 0°C and -20°C outside air
protection buffer tank buffer tank
tank temperature
Production of free high-temperature hot-water
Unit equipped with one desuperheater on each
Partial heat recovery simultaneously with chilled water production (or hot • •
refrigerant circuit.
water for Heat pump)
Unit equipped with supplementary water outlet
temperature sensor kit (to be field installed) Optimised operation of two units connected in
Master/slave operation • •
allowing master/slave operation of two units parallel operation with operating time equalisation
connected in parallel
Single high-pressure water pump, water filter,
All sizes,
electronic water flow control, pressure transducers.
HP single-pump hydraulic low-temperature
For more details, refer to the dedicated chapter Easy and fast installation (plug & play) •
module brine solution
(expansion tank not included. Option with built-in
application only
safety hydraulic components available.)
Dual high-pressure water pump, water filter,
All sizes,
electronic water flow control, pressure transducers.
HP dual-pump hydraulic low-temperature
For more details, refer to the dedicated chapter Easy and fast installation (plug & play) •
module brine solution
(expansion tank not included Option with built-in
application only
safety hydraulic components available)
Single low-pressure water pump, water filter,
electronic water flow control, pressure transducers.
LP single-pump hydraulic
For more details, refer to the dedicated chapter Easy and fast installation (plug & play) NO •
module
(expansion tank not included Option with built-in
safety hydraulic components available)
Dual low-pressure water pump, water filter,
electronic water flow control, pressure transducers.
LP dual-pump hydraulic
For more details, refer to the dedicated chapter Easy and fast installation (plug & play) NO •
module
(expansion tank not included Option with built-in
safety hydraulic components available)
Single high-pressure water pump with variable
speed drive (VSD), water filter, electronic water
Easy and fast installation (plug & play), significant
flow control, pressure transducers. Multiple
HP evap. variable-speed pumping energy cost savings (more than
possibilities of water flow control. For more details, • •
single-pump two-thirds), tighter water flow control, improved
refer to the dedicated chapter (expansion tank not
system reliability
included Option with built-in safety hydraulic
components available)
Dual high-pressure water pump with variable speed
drive (VSD), pressure transducers. Multiple Easy and fast installation (plug & play), significant
HP VSD dual-pump possibilities of water flow control. For more details, pumping energy cost savings (more than
• •
hydraulic mod. refer to the dedicated chapter (expansion tank not two-thirds), tighter water flow control, improved
included Option with built-in safety hydraulic system reliability
components available)
Bi-directional communication board complying with Connects the unit by communication bus to
Lon gateway • •
Lon Talk protocol a building management system

EN-49 AQUACIAT LD/ILD


12 - OPTIONS

Options Description Advantages LD ILD

Easy and high-speed connection by Ethernet line to


Bi-directional high-speed communication using
Bacnet over IP a building management system. Allows access to • •
BACnet protocol over Ethernet network (IP)
multiple unit parameters
Extended remote control capabilities to a boiler on/
Control board factory-installed on the unit to control
External boiler management off command. NO •
a boiler
Permits easy control of a basic heating system
Control board factory-installed on the unit with Extended remote control capabilities to up to
Electric heaters
additional inputs/outputs in order to manage up to 4 electrics heaters. Permits easy control of a basic NO •
management
4 externals heating stage (electrical heaters…) heating system
Compliance with Russian
EAC certification Compliance with Russian regulations • •
regulations
Coating by conversion process which modifies the
surface of the aluminium producing a coating that is Protect2 Improved corrosion resistance of the
MCHE anti-corrosion
integral to the coil. Complete immersion in a bath to MCHE coils by 2, recommended for use in • NO
protection Protect2
ensure 100% coverage. No heat transfer variation, moderately corrosive environments
tested 4000 hours salt spray per ASTM B117
Extremely durable and flexible epoxy polymer
coating applied on micro channel coils by electro
Protect4 Improved corrosion resistance of the
MCHE anti-corrosion coating process, final UV protective topcoat.
MCHE coils by 4, recommended for use in • NO
protection Protect4 Minimal heat transfer variation, tested 6000 hours
corrosive environments
constant neutral salt spray per ASTM B117,
superior impact resistance per ASTM D2794
Evaporator screw
Evaporator inlet/outlet screw connection sleeves Allows unit connection to a screw connector • •
connection sleeves (kit)
Allows unit installation in domestic residential All sizes with All sizes with
Reinforced ECM filtration Fan variable frequency drive compliance to
environment by reducing electromagnetic variable speed variable speed
for fan VFD IEC 61800-3 C1 class
interferences fans fans
Allows unit installation in domestic residential All sizes with All sizes with
Reinforced ECM filtration Pump variable frequency drive compliance to
environment by reducing electromagnetic variable speed variable speed
for pump VFD IEC 61800-3 C1 class
interferences pump pump
Easy and fast installation (plug & play), &
6 bar expansion tank integrated in the hydraulic ALL units with ALL units with
Expansion tank Protection of closed water systems from excessive
module (requires hydraulic module option) pump option pump option
pressure
Real-time expert technical support to improve
M2M supervision Monitoring solution which allows customers to track
equipment availability and reports at customer hand • •
(accessory) and monitor their equipment remotely in real time
to monitor and optimize operating equipment.
Avoid short cycle on compressors and ensure
Water buffer tank module Integrate water buffer tank • •
a stable water in the loop
Elastomer anti-vibration mounts to be place under
Isolate unit from the building, avoid transmission of
the unit
Anti-vibration mounts (kit) vibration and associate noise to the building. Must • •
(Material classified B2 fire class according to
be associate with flexible connection on water side
DIN 4102 ).
Exchangers flexible sleeves Easy installation. Limit transmission of vibrations on
Flexible connections on the exchanger water side • •
connection (kit) the water network
ALL units without ALL units without
Exchangers water filter (kit) Water filter Eliminate dust in the water network
pump option pump option
Set point adjustment by Easy energy management, allow to adjust set point
Connections to allow a 4-20 mA signal input • •
4-20 mA signal by a 4-20 mA external signal
Easy system management, Extended control
Free Cooling dry cooler Control & connections to a Free Cooling Drycooler
capabilities to a drycooler used in Free Cooling • NO
management Opera or Vextra fitted with option FC control box
mode
All sizes,
low-temperature
Evap. single pump power/ Unit equipped with an electrical power and control Quick and easy installation: the control of fixed
brine solution •
control circuit circuit for one pump evaporator side speed pumps is embedded in the unit control
application and HP
pump only
All sizes,
low-temperature
Evap. dual pumps power/ Unit equipped with an electrical power and control Quick and easy installation: the control of fixed
brine solution •
control circuit circuit for two pumps evaporator side speed pumps is embedded in the unit control
application and HP
pump only
Variable speed single pump Unit equipped with an electrical power and control Quick and easy installation: the control of variable
• NO
power/control circuit circuit for variable speed single pump speed pumps is embedded in the unit control
Variable speed dual pump Unit equipped with an electrical power and control Quick and easy installation: the control of variable
• NO
power/control circuit circuit for variable speed dual pump speed pumps is embedded in the unit control
Desuperheater flexible Flexible connections on the desuperheater water Easy installation. Limit transmission of vibrations on
• •
sleeve connection (kit) side the water network
The tank avoids short cycles on the compressors
Water buffer tank module Integrates a water buffer tank module with a and ensures the water in the loop is stable. NO 150-300
with extra heater 16/31/45 kW extra heater The extra heater provides additional or backup
heating in heating mode.

AQUACIAT LD/ILD EN -50


12 - OPTIONS

Accessories Description Advantages LD ILD

Real-time expert technical support to improve


Monitoring solution enabling customers to remotely
M2M 1 supervision unit - equipment availability and reports at customer
track and monitor equipment in real time, France • •
France hand to monitor and optimize operating
only equipment.
Monitoring solution enabling customers to remotely Real-time expert technical support to improve
M2M 3 supervision units - track and monitor several items of equipment in equipment availability and reports at customer • •
France real time, France only hand to monitor and optimize operating
equipment.
Real-time expert technical support to improve
Monitoring solution enabling customers to
M2M 1 supervision unit - remotely track and monitor equipment in real time, equipment availability and reports at customer • •
International hand to monitor and optimize operating
outside of France equipment.
Real-time expert technical support to improve
Monitoring solution enabling customers to
M2M 3 supervision units - equipment availability and reports at customer
remotely track and monitor several items of • •
International hand to monitor and optimize operating
equipment in real time, outside of France equipment.

12.2 - Description 12.2.2 - Hydronic module with variable speed


The composition of the hydronic module with variable speed is
12.2.1 - Hydronic module without variable speed similar to that of the hydronic module without variable speed.
The hydronic module is composed of the system's main hydronic In this case, the pump is controlled by a frequency inverter that
components: factory-fitted water pump, screen filter and relief allows the pump's nominal flow to be adjusted based on the
valve. chosen control mode (constant pressure or temperature
differential or fixed speed) and the installation's operating
This pump provides the fixed, nominal flow rate for the system.
conditions.
Several types of water pump are available to suit all applications:
• Single or dual low pressure pump (AQUACIAT ILD only) The use of the hydronic module on open systems
• Single or dual high pressure pumps. is prohibited.
The nominal flow of the system should be adjusted using
a manual control valve provided by the client.
12.2.3 - Partial heat recovery by desuperheaters
The relief valve placed on the water inlet pipes at the pump inlet
limits the pressure to 400 kPa (4 bar). This option enables free hot water to be produced through heat
recovery by desuperheating the compressor outlet gas. The
A screen filter that can be easily removed placed at the pump
option is available across the entire range.
inlet and an external filter protects both the pump and the plate
heat exchanger against solid particles greater than 800 µm in size. A water-cooled heat exchanger is installed as standard with air-
cooled exchangers on the compressor discharge line on each
Additional options can be ordered if necessary:
circuit.
• Protection of the hydronic module in outdoor temperatures
of down to -20°C. The control is configured for the Partial heat recovery option in
• Expansion vessel. the factory (see the section on Control configuration with the
desuperheater option).
The use of the hydronic module on open systems The installer must protect the water-cooled exchanger against
is prohibited. the risk of frost.

EN-51 AQUACIAT LD/ILD


12 - OPTIONS

12.2.3.1 Physical properties of units with partial heat recovery using desuperheaters

LD partial heat recovery mode 150 180 200 240 260 300 360 390 450 520 600

Standard unit kg 436 445 454 470 468490 785 796 827 867 899
Unit + High pressure single pump option kg 478 486 496 512 510532 852 863 898 941 973
Unit + High pressure dual-pump option kg 504 512 522 537 536558 897 908 947 978 1010
Unit + high pressure single pump + Water buffer tank module option kg 874 882 892 908 906928 1285 1296 1331 1374 1406
Unit + high pressure dual-pump + Water buffer tank module option kg 900 908 918 933 932954 1330 1341 1380 1411 1443
Refrigerant with MCHE coils R410A
Circuit A kg 4,7 5,3 5,9 6,7 6,2 7,3 10,7 10,8 11,4 6,5 7,4
Circuit B kg - - - - - - - - - 6,5 7,4
Air heat exchanger "Micro Channel Heat Exchanger" (Micro-Channel) coils made entirely from aluminium
Desuperheater on circuits A and B Plate heat exchanger
Water volume l 0,549 0,549 0,549 0,549 0,732 0,732 0,976 0,976 0,976 0,732 0,732
Water volume l - - - - - - - - - 0,732 0,732
Max. water-side operating pressure without hydronic module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Water connections Cylindrical male gas thread
Connections in 1 1 1 1 1 1 1 1 1 1 1
Outside diameter mm 42 42 42 42 42 42 42 42 42 42 42
(1) Weights given as a guide.

ILD partial heat recovery mode 150 180 200 240 260 300 302 360 390 450 520 600

Standard unit kg 506 515 552 558 569


574 787 907 916 990 1068 1072
Unit + High pressure single pump option kg 548 557 594 600 611
616 854 974 983 1061 1142 1146
Unit + High pressure dual-pump option kg 574 583 620 626 637
642 899 1019 1028 1109 1179 1183
Unit + high pressure single pump + Water buffer tank module option kg 944 952 990 995 1006
1011 1286 1406 1415 1493 1575 1578
Unit + high pressure dual-pump + Water buffer tank module option kg 970 978 1015 1021 1032
1037 1331 1451 1460 1542 1612 1615
Refrigerant with copper tube coils / aluminium fins(1) R410A
Circuit A kg 12,5 13,5 16,5 17,5 18 16,5 21,5 27,5 28,5 33 19 18,5
Circuit B kg - - - - - - - - - - 19 18,5
Air heat exchanger Grooved copper tube and aluminium fins
Desuperheater on circuits A and B Plate heat exchanger
Water volume l 0,549 0,549 0,549 0,732 0,732 0,732 0,732 0,976 0,976 0,976 0,732 0,732
Water volume l - - - - - - - - - - 0,732 0,732
Max. water-side operating pressure without hydronic module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Water connections Cylindrical male gas thread
Connections in 1 1 1 1 1 1 1 1 1 1 1 1
Outside diameter mm 42 42 42 42 42 42 42 42 42 42 42 42
(1) Weights given as a guide.

AQUACIAT LD/ILD EN -52


12 - OPTIONS

Position of the desuperheater inlets and outlets

LD/ILD150 to LD/ILD300
Without Buffer Tank module

B
C

B Unit water inlet and outlet


C Water inlet and outlet, unit with option desuperheater

With Buffer Tank module

1972 with Xtra Fan option


1930 HT

B C

All dimensions are in mm.

NOTES :
A Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an
installation. For the location of fixing points, weight distribution and coordinates of the centre of gravity refer to the
certified dimensional drawings.
B The unit must be installed level (less than 2 mm per metre deviation in both axes).

EN-53 AQUACIAT LD/ILD


12 - OPTIONS

Position of the desuperheater inlets and outlets

LD360 à LD600 et ILD302 à ILD600


Without Buffer Tank module

B Unit water inlet and outlet


C Water inlet and outlet, unit with option desuperheater

With Buffer Tank module

1972 with Xtra Fan option


1930 HT

All dimensions are in mm.

NOTES :
A Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an
installation. For the location of fixing points, weight distribution and coordinates of the centre of gravity refer to the
certified dimensional drawings.
B The unit must be installed level (less than 2 mm per metre deviation in both axes).

AQUACIAT LD/ILD EN -54


12 - OPTIONS

12.2.3.2 Installation and operation of the heat recovery with partial heat recovery option
The units with the desuperheater option are supplied with one plate heat exchanger per refrigerant circuit.
When installing the unit, the heat recovery plate heat exchangers must be insulated and protected against frost if required.
Refer to the main diagram below for the main components or functions associated with a unit with desuperheater option in a standard
system.

AQUACIAT LD/ILD unit with desuperheater option without hydronic module


Boundary between the AQUACIAT LD/ILD unit and the installation
Standard system

Legend:
Components of the AQUACIAT LD/ILD unit System components (installation example)
1- Evaporator 20- Pump (hydraulic circuit of the desuperheater loop)
2- Compressor 21- Shut-off valve
3- Desuperheater 22- Desuperheater water flow rate control and balancing valve
4- Air condenser (coils) 23- Accessory for limitation of damage in the event of a fire (valve)
5- Expansion valve (EXV) 24- Expansion tank
6- Accessory for limitation of damage in the event of a fire (valve) 25- Charge or drain valve
7- Electric heater for protecting the desuperheater from freezing (not provided) 26- Air bleed
8- Insulation for the desuperheater (not supplied) 27- Coil heat exchanger or plate heat exchanger
9- Electrical box for the unit 28- Pressure gauge
10- NA 29- Flow rate sensor
11- Water inlet on the desuperheater 30- Pump (sanitary hot water circuit)
12- Water outlet on the desuperheater 31- Three-way valves + controller
13- Evaporator water inlet 32- Filter to protect the pump and the desuperheaters
14- Evaporator water outlet 33- Municipal water inlet
15- Unit with desuperheater option without hydronic module 34- Domestic hot water outlet
16- System heat load
17- Boundary between the AQUACIAT LD/ILD unit

EN-55 AQUACIAT LD/ILD


12 - OPTIONS

12.2.3.3 Installation ILD 150 - 600/Cooling Mode


The hydraulic supply for each desuperheater is delivered in
ILD 150 - 600
parallel.
Water inlet temperature on desuperheater, °C
The hydraulic connection on the desuperheater water inlet and
45 50 55
outlets must not generate any localised mechanical stress on
the exchangers. if necessary, install the flexible connective Qhr q Δp Qhr q Δp Qhr q Δp
couplings. kW l/s kPa kW l/s kPa kW l/s kPa
Fit water flow rate balancing and control valves at the exchanger 150 10,9 0,26 4,4 9,1 0,22 3,1 7,1 0,18 2,1
outlet. 180 14,4 0,34 7,5 12,2 0,29 5,4 10,0 0,24 3,7
Balancing and control of the flow rates may be performed by 200 17,2 0,41 10,5 14,7 0,35 7,8 12,3 0,29 5,6
reading the pressure drop in the exchangers. 240 17,4 0,44 6,6 15,1 0,36 4,6 12,3 0,29 3,0
The pressure drop on each of these must be identical to the total 260 21,4 0,51 9,3 17,9 0,43 6,7 14,7 0,35 4,8
water flow rate given by the selection programme. 300 26,8 0,64 14,7 22,5 0,54 10,4 18,8 0,45 7,5
To adjust the balancing valves before starting up the system, 302 23,9 0,57 12,1 21,2 0,51 7,8 16,3 0,39 5,8
refer to the pressure drop curves below. 360 28,1 0,67 9,9 23,9 0,57 7,1 19,7 0,47 5,1
It is possible to fine-tune the water flow rate settings for each 390 33,9 0,81 14,0 28,3 0,68 10,1 23,7 0,57 7,2
desuperheater when the unit is running at full load by trying to 450 37,7 0,90 17,5 31,7 0,76 12,4 26,5 0,63 8,9
obtain water outlet temperatures which are strictly identical for 520(1) 42,9 1,03 9,4 35,5 0,85 6,7 29,1 0,70 4,5
each of the circuits. 600(1) 52,3 1,25 14,1 44,2 1,06 10,1 36,9 0,88 7,1
Heating capacity recovered by the desuperheaters Legend:
Qhr Total heating capacity reclaimed at the desuperheater(s), kW
q Total water flow rate on the desuperheater loop, l/s
LD 150 - 600 Δp Water pressure drop per desuperheater, kPa
(1) Sizes 520 and 600 are fitted with 2 desuperheaters, one per circuit.
LD 150 - 600 Application data:
Water type heat exchanger inlet/outlet temperature: 12/7°C
Water inlet temperature on desuperheater, °C
Outside air temperature: 35°C
45 50 55 Water inlet/outlet difference on desuperheater: 10 K
Evaporator fluid: chilled water
Qhr q Δp Qhr q Δp Qhr q Δp
Fouling level coefficient: 0.18 x 10-4 m2.K/W
kW l/s kPa kW l/s kPa kW l/s kPa
150 12,9 0,31 6,1 10,9 0,26 4,4 9,0 0,21 3,1 ILD 150 - 600/Heating Mode
180 16,5 0,40 9,5 14,3 0,34 7,4 12,0 0,29 5,2
200 18,1 0,43 11,7 15,4 0,37 8,5 12,8 0,31 6,1 ILD 150 - 600
240 19,3 0,46 12,9 16,6 0,40 9,8 13,7 0,33 6,9 Water inlet temperature on desuperheater, °C
260 24,3 0,58 11,8 21,0 0,50 9,2 17,5 0,42 6,5 45 50 55
300 28,6 0,68 16,3 24,4 0,58 12,1 20,6 0,49 8,8 Qhr q Δp Qhr q Δp Qhr q Δp
360 30,5 0,73 11,4 25,8 0,62 8,2 21,5 0,51 5,8 kW l/s kPa kW l/s kPa kW l/s kPa
390 36,4 0,87 16,0 31,9 0,76 12,4 27,0 0,64 8,9 150 10,1 0,24 3,8 8,3 0,20 2,7 6,8 0,16 1,8
450 43,1 1,03 22,6 37,4 0,89 17,2 31,6 0,75 12,3 180 11,1 0,27 4,6 9,3 0,22 3,3 7,7 0,18 2,3
520(1) 47,1 1,12 11,3 39,7 0,95 8,3 33,0 0,79 5,9 200 14,0 0,33 7,1 11,8 0,28 5,2 9,9 0,24 3,6
600(1) 54,0 1,29 15,0 45,6 1,09 10,7 38,3 0,92 7,8 240 14,3 0,34 4,4 11,8 0,28 3,0 9,4 0,22 2,0
Legend: 260 17,1 0,41 6,3 14,4 0,34 4,5 11,9 0,28 3,1
Qhr Total heating capacity reclaimed at the desuperheater(s), kW 300 19,1 0,46 7,8 16,0 0,38 5,6 13,2 0,32 3,9
q Total water flow rate on the desuperheater loop, l/s
Δp Water pressure drop per desuperheater, kPa 302 17,5 0,42 6,6 14,6 0,35 4,8 11,7 0,28 3,2
(1) Sizes 520 and 600 are fitted with 2 desuperheaters, one per circuit. 360 21,4 0,51 6,0 17,7 0,42 4,1 14,7 0,35 2,8
Application data: 390 20,6 0,49 5,1 16,5 0,39 3,4 12,7 0,30 2,0
Water type heat exchanger inlet/outlet temperature: 12/7°C
Outside air temperature: 35°C 450 23,0 0,55 6,9 18,5 0,44 4,7 14,5 0,35 3,0
Water inlet/outlet difference on desuperheater: 10 K 520(1) 32,0 0,77 5,5 26,7 0,64 3,8 21,6 0,52 2,6
Evaporator fluid: chilled water
Fouling level coefficient: 0.18 x 10-4 m2.K/W
600(1) 37,5 0,90 7,3 31,2 0,75 5,4 25,4 0,61 3,7
Legend:
Qhr Total heating capacity reclaimed at the desuperheater(s), kW
q Total water flow rate on the desuperheater loop, l/s
Δp Water pressure drop per desuperheater, kPa
(1) Sizes 520 and 600 are fitted with 2 desuperheaters, one per circuit.
Application data:
Water type heat exchanger inlet/outlet temperature: 40/45°C
Outside air temperature: 7°C
Water inlet/outlet difference on desuperheater: 10 K
Evaporator fluid: chilled water
Fouling level coefficient: 0.18 x 10-4 m2.K/W

AQUACIAT LD/ILD EN -56


12 - OPTIONS

12.2.3.4 Operating limits

AQUACIAT LD

Operating mode COOLING


Desuperheater minimum maximum
Water inlet temperature at start-up °C 25(1) 60
Water outlet temperature during operation °C 30 65
Air condenser minimum maximum
Outdoor ambient operating temperature °C -10(2) 46
(1) The water inlet temperature at start-up must not drop below 25°C.
For installations with a lower temperature, a 3-way valve is required.
(2) With Winter Operation option

AQUACIAT ILD

Operating mode COOLING HEATING


Desuperheater Minimum Maximum Minimum Maximum
Water inlet temperature at start-up °C 25(1) 60 25(1) 60
Water outlet temperature during operation °C 30 65 30 65
Air condenser Minimum Maximum Minimum Maximum
Outdoor ambient operating temperature °C -10(2) 46 -10 48
(1) The water inlet temperature at start-up must not drop below 25°C.
For installations with a lower temperature, a 3-way valve is required.
(2) With Winter Operation option

12.2.3.5 Control configuration with the desuperheater option


This configuration enables the user to enter a setpoint relating to the minimum condensation temperature (default value = 40°C)
to increase the heating capacity recovered by the desuperheaters, if required.
In fact, the recovered heating capacity percentage in relation to the total capacity released by the air-cooled exchanger increase
based on the saturated condensation temperature.
Refer to the control manual for adjustment of the minimum saturated condensation temperature setpoint.
Other parameters directly affect the effective capacity recovered from the desuperheater, which are mainly:
- The unit's load rate, which governs whether it runs at full load (100%) or at part load (depending on the number of compressors
the unit has per circuit).
- The water inlet temperature in the desuperheater, depending on the unit's "Heating" or "Cooling" operating modes:
• in "Heating" mode, the water inlet temperature in the water-cooled exchanger
• in "Cooling" mode, the ambient temperature at the air-cooled exchanger air inlet.

EN-57 AQUACIAT LD/ILD


12 - OPTIONS

12.2.4 - Two units running as master/slave Case 1: operation in parallel - control


on water inlet for a hydronic module
The customer must connect both units with a communication
bus using a 0.75 mm² twisted, shielded cable (contact the
manufacturer's Service for installation).
All parameters required for Master/Slave operation must be
configured by the Service configuration menu.
All remote controls of the Master/slave assembly (start/stop,
unloading, etc.) are managed by the unit configured as Master
and must be applied only to the Master unit.
Units supplied with hydronic module
Master-slave operation is possible only when the units are
installed in parallel:
• The master-slave assembly is controlled on the water inlet
without any additional sensors (standard configuration) (see
example 1).
• Control of Master and Slave on the water outlet is possible
by adding two additional sensors in the common supply
pipe work (see example 2).
Case 2: operation in parallel - control
Each unit controls its own water pump.
on water outlet for a hydronic module
Units supplied without hydronic module
In the case of units installed in parallel and if there is only one
common pump installed by the installer, isolating valves must be
installed on each unit. These should be controlled (opened and
closed) using the control for the relevant unit (valves for each
unit can be controlled using the unit water pump control outputs).
Refer to the control manual for the connections.
IMPORTANT:
Both of the units must be equipped with an option to allow
Master-Slave operation
If the variable speed option is equipped on one or two units,
it is strongly recommended not to configure the control
mode on a pressure differential.
It is recommended to configure the temperature differential
mode with the same setpoint.
Legend:
B Master Unit

C Slave unit

Electrical boxes for Master and Slave units

Water inlet

Water outlet
Water pumps for each unit (included as standard in units with hydronic
module)
Additional sensors for the control of the water outlet to be connected
T
on channel 1 of the slave boards of each Master and Slave unit
Communication bus

Connection of two additional sensors

Non-return valve

AQUACIAT LD/ILD EN -58


12 - OPTIONS

12.2.5 - Low temperature / Very low temperature This value will be used to define the following limits:
glycol/water mix options 1. Evaporator antifreeze protection.
This option enables glycol/water mix production down to 0°C 2. Low-pressure protection.
(low temperature glycol/water mix option) / -15°C (very low It is recommended that a low or very low temperature installation
temperature glycol/water mix option) be commissioned by the manufacturer.
The unit is equipped with a suction tube isolation device (for very For information, for the different antifreezes used in our
low temperature glycol/water mix only) and frequency inverters laboratory, the protection values given by our supplier are as
on the ventilation. follows (these values may change depending on the suppliers):
The operating range depends on the suction pressure, which
itself depends on: Freezing point, °C Freezing point, °C
% glycol mass
• the glycol type, ethylene glycol propylene glycol
• its concentration, 10 -3.8 -2.6
• the flow rate, 15 -6.1 -4.3
• the temperature of the glycol solution, 20 -8.8 -6.6
• the condensation pressure (ambient temperature). 25 -11.8 -9.6
Example: for operation with 45% ethylene glycol and brine 30 -15.2 -13
temperature -15°C (with -10°C at the inlet), the maximum 35 -19.1 -16.7
operating ambient temperature will be approximately 33°C.
40 -23.6 -20.7
Operating range 45 -29 -25.3
with ethylene glycol at 45% For example, depending on the table above, if an ethylene glycol
mass concentration measured in the loop is 35%, the value of
55
-19.1°C must be entered in the software.
It is vital to perform a (minimum) annual inspection of the glycol
45
level and adjust the controller's frost protection value to the
measured level.
35 This procedure must be systematic when topping up with water
or antifreeze solution.
Ambient temperature (°C)

25 The curve below gives the minimum frost protection temperature


to be observed depending on the water outlet temperature.
15
Minimum frost protection

5 0
Minimum protection temperature,

-5
-5
-10

-15
-15
°C

-25 -20

-20 -15 -10 -5 0 5 10


-25
Evaporator leaving water temperature (°C)
Low temperature option -30
Very low temperature option -16 -14 -12 -10 -8 -6 -4 -2 0

Evaporator leaving water temperature (°C)


Frost protection
The low-pressure and antifreeze protection of the evaporator NOTE:
depend on the antifreeze level in the water loop. • In the case of frost protection of the unit by low air
temperature, the percentage brine must be evaluated
The evaporator pinch (LWT – SST) and the antifreeze protection
accordingly.
depend on this level.
• The maximum glycol level in the case of units equipped
So it is essential, when first activating the unit, to check the with a hydronic module is 45%.
antifreeze level in the loop (circulate for 30 minutes to ensure • The brine temperature of -15°C is achievable only with 45%
good mixing homogeneity before sampling). ethylene glycol.
Refer to the manufacturer data to define the antifreeze protection, • The maximum recommended temperature differential is
dependent on the measured concentration level. 5K.
The antifreeze protection temperature must be entered in the
unit's software parameters.

EN-59 AQUACIAT LD/ILD


12 - OPTIONS

IMPORTANT: 12.2.6.1 Installation


For glycol concentrations of less than 20 %, it is essential IMPORTANT: In units which are ductable in heating mode,
to use a corrosion inhibitor suited to the application, to dehumidification of ambient air, as well as defrosting the air
eliminate the risk of corrosion due to the aggressiveness exchangers, produces a large volume of condensates which
of the brine. must be dealt with on the unit installation site.
The presence of glycol reduces the life of the pump fittings. Ductable units must be installed on a waterproof base
Changing the packings or pump is recommended: enabling efficient drainage and evacuation of the condensate
• Every 40,000 hours for applications with water, from the heat exchangers.
• Every 15,000 hours for applications with glycol Similarly, in case of low outdoor temperatures when
concentrations of more than 30 %. air-cooled exchangers freeze, the water from defrosting
In order to facilitate maintenance operations, it is must be collected so as to prevent any risk of flooding the
recommended to install isolation valves upstream and rooms where the heat pumps are installed.
downstream of the machine. Each fan is controlled by a variable speed drive. Therefore
each circuit operates independently.
12.2.6 - Units with variable available pressure fans
(XTraFan option) Each refrigerant circuit must have an independent ductwork
system so as to prevent any air recycling between the
Ductable units are intended to be ducted on the fan discharge, air-cooled exchangers of different refrigerant circuits.
and can be installed inside a machine room. On ductable units, each fan is equipped with a factory-fitted
For this type of installation, the hot or cold air emerging from the connection interface frame providing a link between the
air-cooled exchangers is evacuated from the building by the fans ductwork itself and the refrigerating circuit to which the fan
by means of a ductwork system, which causes pressure drops belongs.
in the air circuit. Refer to the dimensional plans of the units for the precise
Installing a ductwork system on the fan discharge generated dimensions of this connection interface.
a pressure drop due to the air flow resistance.
Therefore, more powerful fan motors are installed in this option 12.2.6.2 Air connection on discharge
than on the standard units.
Refer to the dimensional plans of the units for the precise
For each installation, the duct pressure drops differ, depending dimensions of the connection interface.
on the duct length, the duct section and the changes in direction.
A flexible sleeve providing connection to the ductwork is delivered
Ductable units equipped with this option are designed to operate with the unit.
with ducts whose air evacuation generates a maximum pressure
drop of 180 Pa or 240 Pa, depending on the models.
Using a speed variation up to 19 rps enables the system to
overcome the pressure drops in the ducts while maintaining an
optimised air flow in each circuit.
All the fans in the same circuit run at the same time at the same
speed.
In the cooling / heating mode, the full-load or part-load speed is
controlled by a patented algorithm that permanently optimizes
the condensing / evaporating temperature to ensure the best
unit energy efficiency (EER / COP) whatever the operating
conditions and pressure drop of the system ductwork.
If required by a specific installation, the unit's maximum fan speed
can be configured in the Service configuration menu. For this
modification, consult the control manual.
The maximum configured speed applies to both the cooling and
heating modes.
The performances (capacity, efficiency, noise level) depend on
the fan speed. Please refer to the manufacturer's electronic
catalogue to evaluate the estimated impact of the duct system
on the unit's operating conditions.

Unit with protection grilles option

B Fan motor access hatches (allow for a 700 x 700 mm hatch) for each single
or dual duct
C Connection bellows or sleeve

AQUACIAT LD/ILD EN -60


12 - OPTIONS

12.2.6.3 Rules applicable to units within an air ductwork Xtrafan ILD option
system
Cooling mode
Make sure that the suction or blowing ports cannot be
inadvertently obstructed by fitting panels (low return for example,
or when doors or other parts are opened). ILD 150-200/ILD 302-450
Duct pressure Fan rotation Power input Cooling capacity
12.2.6.4 Correction factors for Xtra Fan machine performances drop speed (rps) variation variation
0 12 0,943 1,019
The cooling/heating capacities are provided for an available
50 13,33 0,962 1,012
pressure of 160 Pa.
100 14,66 0,980 1,006
To calculate the performances with other pressure drops,
130 15,46 0,990 1,003
you can use the coefficients in the table below.
160 16,26 1,000 1,000
Xtrafan LD option 200 17,31 1,012 0,998
240 18,36 1,023 0,996
LD 150-240/LD 360-450
ILD 240-300/ILD 520-600
Duct pressure Fan rotation Power input Cooling capacity
drop speed (rps) variation variation Duct pressure Fan rotation Power input Cooling capacity
0 12 0,943 1,019 drop speed (rps) variation variation
50 13,33 0,962 1,012 0 15,83 0,929 1,018
100 14,66 0,98 1,006 50 16,81 0,944 1,016
130 15,46 0,99 1,003 100 17,78 0,964 1,014
160 16,26 1 1 130 18,36 0,978 1,011
200 17,31 1,012 0,998 160 18,36 1,000 1,000
240 18,36 1,023 0,996 180 18,36 1,019 0,991

LD 260-300/LD 520-600 Heating mode


Duct pressure Fan rotation Power input Cooling capacity
drop speed (rps) variation variation ILD 150-200/ILD 302-450
0 12 0,943 1,019
Duct pressure Fan rotation Power input Cooling capacity
50 13,33 0,962 1,012 drop speed (rps) variation variation
100 14,66 0,98 1,006 0 18,36 0,990 1,016
160 16,26 1 1 50 18,36 0,990 1,012
200 17,31 1,012 0,998 100 18,36 0,990 1,009
240 18,36 1,023 0,996 130 18,36 1,000 1,005
160 18,36 1,000 1,000
200 18,36 1,000 0,994
240 18,36 1,010 0,981

ILD 240-300/ILD 520-600


Duct pressure Fan rotation Power input Cooling capacity
drop speed (rps) variation variation
0 18,36 1,000 1,026
50 18,36 1,000 1,02
100 18,36 1,000 1,011
130 18,36 1,000 1,007
160 18,36 1,000 1,000
180 18,36 1,001 0,993

EN-61 AQUACIAT LD/ILD


12 - OPTIONS

12.2.7 - Water filter and flexible connective couplings


This equipment is supplied in the device for units equipped with pump(s), optionally for units without pumps.
Below are the equipment diagrams for the various configurations:

LD/ILD 150 - 300 LD/ILD 302 - 600 water filter


water filter option + screw-in connections option

This optional equipment is delivered in the device

LD/ILD 302 - 600 water filter option LD/ILD 150 - 600 connection hoses option

NOTE: The hoses must have a min. straight length of 205 mm,
LD/ILD 150 - 300 water filter and a min. curve radius of 490 mm
+ screw-in connections option

Legend:

B Steel sleeve

C 800 µm screen filter

D Brass connector

E Shut-off valve

F Victaulic clamp

G Hose

Water inlet

Water outlet

AQUACIAT LD/ILD EN -62


12 - OPTIONS

LD/ILD 150 - 300 water filter LD/ILD 302 - 600 water filter + connection hoses
+ connection hoses option + screw-in connections option

NOTE: The hoses must have a min. straight length of 205 mm, NOTE: The hoses must have a min. straight length of 205 mm,
and a min. curve radius of 490 mm and a min. curve radius of 490 mm

LD/ILD 302 - 600 water filter LD/ILD 150 - 600 water filter
+ connection hoses option + connection hoses option

NOTE: The hoses must have a min. straight length of 205 mm, Legend:
and a min. curve radius of 490 mm
B Steel sleeve
LD/ILD 150 - 300 water filter + connection hoses C 800 µm screen filter
+ screw-in connections option D Brass connector

E Shut-off valve

F Victaulic clamp

G Hose

Water inlet

Water outlet

NOTE: The hoses must have a min. straight length of 205 mm,
and a min. curve radius of 490 mm

EN-63 AQUACIAT LD/ILD


12 - OPTIONS

12.2.8 - Pump protection and control options 12.2.9 - Unit operation with a free cooling drycooler
(optional)
The pump protection and control options give the customer
access to outlets designed for the supply and actuation of pumps
external to the machine. 12.2.9.1 - Operating principle
These outlets provide electrical protection via a thermal-magnetic The units have been designed to optimize the operation of
circuit breaker (fixed and variable speed pumps) and a control systems, using drycoolers as free cooling system (method using
switch actuated by the machine's control system (fixed speed low outdoor air temperature to chill the water of the air
pump only). conditioning system).
The protections and controls are sized based on the factory-fitted This system allows substantial energy and cost savings, which
pumps outlined in the section "Electrical data for the hydraulic is the most effective when the outdoor air temperature is low.
module". The TouchPilot control of the unit includes algorithms to permit
Proposed assembly for external variable speed pumps: constant automatic optimization of:
• drycooler fans operation
Single pump • water flow rate variation in the loop
• lcooling capacity (drycooler and chiller can operate
independently or simultaneously),
CIAT unit • valves positions depending on operating mode.
The control defines the optimal configuration considering water
setpoint value, outdoor air temperature and water loop
temperature (the control will give priority to the drycooler).
Parallel control of the fans and of the variable water flow rate of
the loop permit system operation down to -20 °C outside
temperature without any additional control.
VFD WARNING: the drycooler and chiller must both be equipped
with the Free Cooling Management option.

Chiller NO

Pump
NC
Communication bus

V2V control
Dual-pump DC free cooling

CIAT unit

For an optimal free cooling operation, the chiller has to be


configured:
VFD VFD • on entering water temperature control
• on delta temperature control in case of variable speed pump
option

Pump

Supplied by CIAT Supplied by Customer

AQUACIAT LD/ILD EN -64


12 - OPTIONS

12.2.9.2 - Communication to control the drycooler 12.2.9.3 - Configuration of the fans control
When the option is selected, a specific electronic board is To set the configuration corresponding to the drycooler installed
integrated in the control box of the drycooler. A communication (number of fans, control type – fixed or variable speed), please
LEN bus connected between the drycooler (board AUX1) and refer to the instructions in the TouchPilot control manual.
the chiller is needed for the overall system control. Following these parameters, the TouchPilot control will activate
This cable should be a 3 points Wago type (5 mm spacing or the adequate number of digital outputs to control the fans.
equivalent) and should be shielded. TouchPilot controls the automatic switching of all fans, based on
The board integrated in the control box of the drycooler has operating time and number of start-up, to ensure a long operating
analogue inputs for outside air temperature and drycooler leaving life of fan motors.
water temperature sensors, as well as digital outputs permitting Compatible fans configuration:
the control of the fans. • 1 to 20 fans
The option works as a system split in two parts: • fixed speed or variable speed
• fans in one 1 or 2 lines
The chiller (with free cooling option): Refer to the drycooler electrical diagram to see the fan stages
arrangement.
- Dedicated control algorithms with LEN connector to
communicate and control the drycooler
12.2.9.4 – Water valves
The drycooler (with free cooling option): The free cooling system requires 2 two-way valves (one Normally
- AUX board with the I/O Opened, one Normally Closed) or a three-way valve, not supplied
- OAT sensor to be place in outdoor zone. with the unit or the dry cooler.
- Dry Cooler Leaving Water Temperature (factory mounted)
- Water loop Temperature (to be mounted on the common pipe
before valve)
- Control & 230-V power supply for 2 two ways valve or one
three ways valve
The temperature difference between dry-cooler OAT and water
loop sensor defines if free cooling mode can be activated.

EN-65 AQUACIAT LD/ILD


13 - STANDARD MAINTENANCE

To ensure optimal efficiency and reliability of the equipment and 13.2 - Level 2 maintenance
all its functions, we recommend taking out a maintenance
This level requires specific expertise in electrical, hydraulic and
contract with the local organisation set up by your manufacturer.
mechanical systems. it is possible that this expertise may be
This contract will include regular inspections by the manufacturer’s
available locally; there may be a maintenance service, industrial
Service specialists so that any malfunction is detected and
site or specialist subcontractor in the area.
corrected quickly, ensuring that no serious damage can occur.
The manufacturer's service maintenance contract is the best The frequency of this maintenance may be monthly or annual,
way to ensure the maximum operating life for your equipment depending on the type of check.
and, through the expertise of manufacturer's qualified personnel, In these cases, the following maintenance operations are
provides the ideal way to manage your system energy recommended:
consumption effectively.
Carry out all level 1 operations, then:
The refrigeration equipment must be serviced by professionals;
however, routine checks may be carried out locally by specially- Electrical checks (annual checks):
trained technicians. See the standard EN 378-4. - At least once a year tighten the electrical connections for the
power supply circuits (see tightening torques table),
All refrigerant charging, removal and recovery operations must
- Check and tighten all control connections, if required,
be carried out by a qualified technician and with the correct
- Check the labelling of the system and instruments, re-apply
equipment for the unit. Any inappropriate handling can lead to
the missing labels if required,
uncontrolled fluid or pressure leaks.
- Remove the dust and clean the interior of the electrical boxes.
IMPORTANT: Before performing any work on the machine Be careful not to blow dust or debris into components; use
ensure it is de-energised. If a refrigerant circuit is opened, a brush and vacuum wherever possible,
it must be evacuated, recharged and tested for leaks. Before - Clean the insulators and bus bar supports (dust combined
any operation on a refrigerant circuit, it is necessary to with moisture reduces the insulation gaps and increases
evacuate the refrigerant charge from the device using current leakage between phases and from phase to ground),
a charge transfer unit. - Check the presence, condition and operation of electrical
Simple preventive maintenance will allow you to get the best protective devices,
performance from your HVAC unit: - Check the presence, condition and operation of control
- Optimisation of energy performance, components,
- Reduced electricity consumption, - Check that all heaters are operating correctly,
- Prevention of accidental component failure - Replace the fuses every 3 years or every 15000 hours
- Prevention of major time-consuming and costly work, (ageing),
- Protection of the environment. - Check that no water has penetrated into the electrical box,
There are five maintenance levels for HVAC units, as defined by - On the electrical box and for units equipped with an inverter,
the AFNOR X60-010 standard. regularly check the cleanliness of the filter media to maintain
the correct air flow.
NOTE: Any deviation from or failure to comply with
these maintenance criteria will render the guarantee Mechanical:
conditions for the refrigeration unit null and void, Check that the mounting bolts for the ventilation sub-assemblies,
and will release the manufacturer from its liability. fans, compressors and electrics box are securely tightened
Hydraulics:
13.1 - Level 1 maintenance
- When working on the water circuit, take care not to damage
These simple procedures can be carried out by the user: the adjacent air heat exchanger,
- Visual inspection for traces of oil (indicates a refrigerant leak), - Check the water connections,
- Check for leaks in the hydraulic circuit (monthly), - Check the condition of the expansion tank (presence of
- Clean the air-cooled exchangers (see the dedicated chapter), corrosion or loss of gas pressure) and replace it if required,
- Check that the protective grilles are present and in good - Drain the water circuit (see chapter “Water flow control
condition, and that the doors and covers are properly closed, procedure”),
- Check the unit's alarm report (see the control manual), - Clean the water filter (see chapter “Water flow rate control
- Verify the refrigerant charge in the liquid line sight glass, procedure”),
- Verify the chilled water temperature difference at the heat - Replace the gland packing of the pump after 20000 hours of
exchanger outlet is correct, operation and the bearings after 17500 hours,
- Check for any general signs of deterioration, - Check the operation of the low water flow safety device,
- Check the anti-corrosion coatings. - Check the condition of pipe thermal insulation,
- Check the concentration of the anti-freeze protection solution
(ethylene glycol or propylene glycol),
- Check the water flow using the heat exchanger pressure
difference,
- Check the condition of the heat transfer fluid or the water
quality,
- Check for corrosion of the steel pipe work.
- Check the level of scaling on the extra heaters (if the option
is available)
- Check that the extra heaters are operating correctly and that
the thermostat present on each immersion heater (if the option
is available) is triggered..

AQUACIAT LD/ILD EN -66


13 - STANDARD MAINTENANCE

Refrigerant circuit checks: 13.4 - Tightening of the electrical connections


- Check the unit operating parameters and compare them with
the previous values, Designation in Value
Component / Screw type
- Check the operation of the high pressure switches. Replace the unit (N.m)
them if defective, Customer incoming PE terminal (M8) PE 14,5
- Check the fouling of the filter drier. Replace it if required Screw on incoming terminal
- Keep an up-to-date service booklet specific to the refrigeration Terminal 56.395.0055.0 X100 10
unit in question.
Terminal 56.398.0055.0 14
Ensure all adequate safety measures are taken for Screw on incoming switch ranges
all these operations: use appropriate PPE (personal Switch - MG 28908 QS_ 8
protective equipment), comply with all industry and Switch - MG 28910 8
local regulations, use common sense. Switch - MG 28912 8
Switch - MG 31102 15
Screw terminal, compressor contactor
13.3 - Level 3 maintenance Contactor LC1D12B7 KM* 1,7
Maintenance at this level requires specific skills, qualifications, Contactor LC1D18B7 1,7
tools and expertise. Only the manufacturer, his representative Contactor LC1D25B7 2,5
or authorised agent are permitted to carry out this work. Compressor circuit breaker cage screw terminal
This maintenance work relates to the following: Circuit breaker 25507 QM* 3,6
- Replacement of major components (compressor, water heat Circuit breaker 25508
exchanger), Circuit breaker 25509
- Operations on the refrigerant circuit (handling refrigerant), Control transformer cage screw terminal
- Modification of factory-set parameters (change of application),
Transformer - 40958E TC 0,6
- Movement or disassembly of the refrigeration unit,
Transformer - 40959E
- Any operation due to proven lack of maintenance,
- Any operation covered by the warranty, Transformer - 40888E
- One or two leak detection operations per year performed by Transformer - 40894E
qualified personnel using a certified leak detector. Compressor earth terminal in power box
- To reduce waste, the refrigerant and the oil must be transferred M6 Gnd 5,5
in accordance with applicable regulations, using methods that Earth connection on compressor
limit refrigerant leaks and pressure drops and with materials
M8 Gnd 2,83
that are suitable for the products.
- Any detected leaks must be repaired immediately Circuit breaker cage screw terminal (fan, pump)
- The compressor oil that is recovered during maintenance Circuit breaker GV2ME08 QM_ 1,7
contains refrigerant and must be treated accordingly. Circuit breaker GV2ME10
- Refrigerant under pressure must not be vented to the open Circuit breaker GV2ME14
air. Contactor cage screw terminal (fan, pump)
- If the refrigerating circuit must be opened, cap all openings Contactor LC1K0610B7 KM 0.8 to 1.3
for a period of up to one day. If open for longer, blanket the
Contactor LC1K09004B7
circuit with a dry, inert gas (e.g. nitrogen).
Contactor LC1K0910B7
Contactor LC1K0901B7

13.5 - Tightening torques for the main


fastenings

Tightening Tightening
Screw type Use
torque (Nm) torque (Nm)
CP sleeve compressor bracket 30 30
M8 nut BPHE mounting(1) 15 15
M10 nut Compressor stud 30 30
M16 nut Compressor mounting 30 30
Oil nut Oil equalisation line 75 75
M6 taptite screw Ventilation support 7 7
M8 taptite screw Ventilation motor mounting 13 13
M8 H screw Helix mounting 18 18
Panel screw Metal panels 4,2 4,2
H M6 screw Stauff clamp 10 10
Earth screw Compressor 2,8 2,8

(1) BPHE: Brazed Plate Heat Exchanger

EN-67 AQUACIAT LD/ILD


13 - STANDARD MAINTENANCE

13.6 - Air heat exchanger Never use a fluid with a temperature above 45°C to clean
the air heat exchangers.
We recommend that coils are inspected regularly to check the
degree of cleanliness. This depends on the environment where Correct and frequent cleaning (approximately every three
the unit is installed, in particular urban and industrial sites, and months) will prevent 2/3 of the corrosion problems. Protect
for units installed near trees that shed their leaves. the electrics box during cleaning operations.

Recommendations for maintenance and cleaning of copper


13.7 - Water type heat exchanger
pipe coils and aluminium fins (RTPF):
- Regularly cleaning the coil surface is essential for correct unit Check that:
operation. - The insulation has not been detached or torn during
- Eliminating contamination and removal of harmful residue will operations,
increase the operating life of the coils and the unit. - The heaters and probes are operating and correctly positioned
- Specific recommendation in case of snow: For long term in their support,
storage, regularly check that no snow has accumulated on - The water-side connections are clean and show no sign of
the coil. leakage,
- Clean the coils completely using a low pressure jet and - The periodic inspections required by local regulations have
a biodegradable cleaning agent. been carried out
- It is essential to control the pressure and take care not to
damage the fins. 13.8 - Frequency inverter

Recommendations for maintenance and cleaning of Before any work on the frequency inverter, ensure
micro-channel coils (MCHE): that the circuit is isolated and there is no voltage
- Regularly cleaning the coil surface is essential for correct unit present (reminder: the capacitors take approximately
operation. 5 minutes to discharge once the circuit breaker has
- Eliminating contamination and removal of harmful residue will been opened). Only appropriately qualified
increase the operating life of the coils and the unit. personnel are authorised to work on the frequency
- The maintenance and cleaning procedures below are part of inverter.
the regular maintenance to increase the operating life of coils. In case of any alarm or persistent problem related to the
- Specific recommendation in case of snow: For long term frequency inverter, contact the manufacturer's service.
storage, regularly check that no snow has accumulated on
The frequency inverters fitted on the units do not require
the coil.
a dielectric test, even if being replaced: they are systematically
- Clean the surface of the coil by spraying the coil regularly and
checked before delivery. Moreover, the filtering components
uniformly from bottom to top, orienting the water jet at right
installed in the frequency inverter can falsify the measurement
angles to the surface. Do not exceed a water pressure of
and may even be damaged. If there is a need to test the insulation
6200 kPa (62 bar) or an angle of 45° related to the coil. The
of the unit components (fan motors and pumps, cables, etc.),
nozzle must be at least 300 mm away from the coil surface.
the frequency inverter must be disconnected at the power circuit.
- Clean and scrub the entire connection with a flexible Nylon,
PolyPro® or Tynex® brush and low-pressure tap water.
13.9 - Refrigerant volume
Level 1 cleaning: It is essential to run the unit in cooling mode to find out whether
- Remove all foreign objects or fragments/debris attached to the charge is correct; this is done by checking the actual
the coil surface or wedged between the chassis and the subcooling.
supports. Following a slight leak, it will be possible to feel a drop in the
- Use a low-pressure dry air jet to remove all traces of dust from refrigerant charge from the initial charge, and this will affect the
the coil. subcooling value obtained at the air-cooled exchanger outlet;
it cannot, however, be felt in heating mode.
Level 2 cleaning: IMPORTANT: it is therefore not possible to optimise the
- Carry out the level 1 cleaning operations. charge in heating mode following a leak. The unit must be
- Clean the coil using suitable products. run in cooling mode if the charge needs topping up.
Use appropriate PPE including safety glasses and/or mask,
waterproof clothes and safety gloves. It is recommended to
wear clothing that covers the whole body.
Specific products approved by the manufacturer for cleaning
coils are available from the manufacturer's spare parts
network. The use of any other product is strictly prohibited.
After the cleaning product is applied, rinsing with water is
mandatory.
IMPORTANT: Never use a pressure water spray without
a large diffuser.
Concentrated and/or rotating water jets are strictly
forbidden.

AQUACIAT LD/ILD EN -68


13 - STANDARD MAINTENANCE

13.10 - Refrigerant properties

Properties of R410A

Saturated temperatures (°C) based on the relative pressure (in kPa).


Saturated temp. Pressure gauge Saturated temp. Pressure gauge Saturated temp. Pressure gauge Saturated temp. Pressure gauge
-20 297 4 807 28 1687 52 3088
-19 312 5 835 29 1734 53 3161
-18 328 6 864 30 1781 54 3234
-17 345 7 894 31 1830 55 3310
-16 361 8 924 32 1880 56 3386
-15 379 9 956 33 1930 57 3464
-14 397 10 987 34 1981 58 3543
-13 415 11 1020 35 2034 59 3624
-12 434 12 1053 36 2087 60 3706
-11 453 13 1087 37 2142 61 3789
-10 473 14 1121 38 2197 62 3874
-9 493 15 1156 39 2253 63 3961
-8 514 16 1192 40 2311 64 4049
-7 535 17 1229 41 2369 65 4138
-6 557 18 1267 42 2429 66 4229
-5 579 19 1305 43 2490 67 4322
-4 602 20 1344 44 2551 68 4416
-3 626 21 1384 45 2614 69 4512
-2 650 22 1425 46 2678 70 4610
-1 674 23 1467 47 2744
0 700 24 1509 48 2810
1 726 26 1596 49 2878
2 752 25 1552 50 2947
3 779 27 1641 51 3017

EN-69 AQUACIAT LD/ILD


14 - FINAL SHUTDOWN

14.1 - Shutting down


Separate the units from their energy sources, allow them to cool then drain them completely.

14.2 - Recommendations for disassembly


Use the original lifting equipment.
Sort the components according to their material for recycling or disposal, in accordance with regulations in force.
Check whether any part of the unit can be recycled for another purpose.

14.3 - Fluids to be recovered for treatment


- Refrigerant
- Heat-transfer fluid: depending on the installation, water, glycol/water mix, etc.
- Compressor oil

14.4 - Materials to be recovered for recycling


- Steel
- Copper
- Aluminium
- Plastics
- Polyurethane foam (insulation)

14.5 - Waste electrical and electronic equipment (WEEE)


At the end of its life, this equipment must be disassembled and contaminated fluids removed by professionals and processed via
approved channels for electrical and electronic equipment (WEEE).

AQUACIAT LD/ILD EN -70


15 - UNIT START-UP CHECKLIST FOR INSTALLERS PRIOR TO CONTACTING THE
MANUFACTURER
(USE FOR MACHINE FILE)

Preliminary information
Job name:............................................................................................................................................................................................
Location:..............................................................................................................................................................................................
Installing contractor:............................................................................................................................................................................
Distributor:...........................................................................................................................................................................................
Commissioning performed by:....................................................... Date: ..........................................................................................

Equipment
AQUACIATPOWER LD ST / HE model:............................................... Serial number..........................................................................

Compressors

Circuit A Circuit B
1. Model #........................................................................................ 1. Model #..............................................................................
Serial number............................................................................... Serial number.....................................................................

2. Model #........................................................................................ 2. Model #..............................................................................


Serial number............................................................................... Serial number.....................................................................

3. Model #........................................................................................ 3. Model #..............................................................................


Serial number............................................................................... Serial number.....................................................................

4. Model #........................................................................................ 4. Model #..............................................................................


Serial number............................................................................... Serial number.....................................................................

Air handling equipment


Manufacturer ......................................................................................................................................................................................
Model #............................................................................................. Serial number..........................................................................

Additional air handling units and accessories.....................................................................................................................................


............................................................................................................................................................................................................

Preliminary equipment check


Is there any shipping damage?........................................................ If so, where?............................................................................
............................................................................................................................................................................................................

Will this damage prevent unit start-up?...............................................................................................................................................

Unit is level in its installation


Power supply agrees with the unit nameplate
Power circuit wiring has been sized and installed properly
Unit ground wire has been connected
Electrical circuit protection has been sized and installed properly
All terminals are tight
All cables and thermistors have been inspected for crossed wires
All plug assemblies are tight

Check air handling systems


All air handlers are operating
All chilled water valves are open
All fluid piping is connected properly
All air has been vented from the system
Chilled water pump is operating with the correct rotation. Amperage: Nominal............... .Actual...................

EN-71 AQUACIAT LD/ILD


15 - UNIT START-UP CHECKLIST FOR INSTALLERS PRIOR TO CONTACTING THE
MANUFACTURER
Unit start-up
Chilled water pump contactor has been correctly cabled with the chiller
Oil level is correct
Unit has been leak checked (including fittings)
Locate, repair, and report any refrigerant leaks
............................................................................................................................................................................................................

............................................................................................................................................................................................................

............................................................................................................................................................................................................

Check voltage imbalance: AB................ AC.................. BC...................


Average voltage = ...................................... (see installation instructions)
Maximum deviation = ................................. (see installation instructions)
Voltage imbalance = ................................... (see installation instructions)....

Voltage imbalance is less than 2%

WARNING
Do not start the chiller if the voltage imbalance is greater than 2%. Contact your local power company for assistance.

All incoming power voltage is within the nominal voltage range


The compressor crankcase heaters have been running for 6 hours

Check evaporator water loop


Water loop volume = ................... (litres)
Calculated volume = ................... (litres)
2.5 litres/nominal kW capacity for air conditioning
6.50 litres/nominal kW capacity for air conditioning

Proper loop volume established


Correct loop corrosion inhibitor included ....... litres of.............................
Proper loop frost protection included (if required)....................... ....... litres of...............................
Water pipes have been fitted with trace heating up to the evaporator
Return water piping is equipped with a screen filter with a mesh size of 1.2 mm

Check pressure drop on the evaporator (without hydronic module) or ESP* (with hydronic module)
Evaporator inlet = ....................................... (kPa)
Evaporator outlet = ..................................... (kPa)
Pressure drop (Inlet - Outlet) = ................... (kPa)

*ESP : External Static Pressure

WARNING
Plot the pressure drop on the evaporator flow/pressure drop curve to determine the flow rate in l/s at the nominal operating
conditions for the system.
If necessary use the control valve to adjust the flow rate to the desired value.
For units with hydronic module, the flow rate is indicated by the unit control (Consult the AQUACIAT control manual).

Flow rate from the pressure drop curve, l/s = .................


Nominal flow rate, l/s = ...........................
The flow rate in l/s is higher than the minimum unit flow rate
The flow rate in l/s corresponds to the specification of ............................ (l/s)

AQUACIAT LD/ILD EN -72


15 - UNIT START-UP CHECKLIST FOR INSTALLERS PRIOR TO CONTACTING THE
MANUFACTURER
Carry out the QUICK TEST function (Consult the manufacturer's service):

Check and log on to the user menu configuration


Load sequence selection.....................................................................................................................................................................
Capacity ramp loading selection.........................................................................................................................................................
Start-up delay......................................................................................................................................................................................
Pump control.......................................................................................................................................................................................
Setpoint reset mode............................................................................................................................................................................
Night mode capacity limitation.............................................................................................................................................................

Re-enter the setpoints

To start up the chiller


WARNING
Be sure that all service valve sets are open, and that the pump is on before attempting to start this machine. Once all
checks are complete, start up the unit.
The unit starts and operates properly

Temperatures and pressures


WARNING
Once the machine has been operating for a while and the temperatures and pressures have stabilised, record the following:
Evaporator water inlet.........................................................................................................................................................................
Evaporator water outlet.......................................................................................................................................................................
Ambient temperature ..........................................................................................................................................................................
Circuit A suction pressure....................................................................................................................................................................
Circuit B suction pressure...................................................................................................................................................................
Circuit A discharge pressure................................................................................................................................................................
Circuit B discharge pressure...............................................................................................................................................................
Circuit A suction temperature .............................................................................................................................................................
Circuit B suction temperature..............................................................................................................................................................
Circuit A discharge temperature..........................................................................................................................................................
Circuit B discharge temperature..........................................................................................................................................................
Circuit A liquid line temperature...........................................................................................................................................................
Circuit B liquid line temperature..........................................................................................................................................................

NOTES:
............................................................................................................................................................................................................

............................................................................................................................................................................................................

............................................................................................................................................................................................................

EN-73 AQUACIAT LD/ILD


AQUACIAT LD/ILD EN -74
EN-75 AQUACIAT LD/ILD
Manufacturer: Carrier SCS, Montluel, France. Printed in the European Union.
Manufacturer reserves the right to change any product specifications without notice.

You might also like