Aquaciat LD - Ild
Aquaciat LD - Ild
11 - 2020
AQUACIAT LD/ILD
Instruction manual
CONTENTS
1 - INTRODUCTION....................................................................................................................................................................... 4
1.1 - Safety considerations related to protection devices............................................................................................................. 4
1.2 - Refrigerant safety considerations......................................................................................................................................... 5
1.3 - Installation safety considerations......................................................................................................................................... 6
1.4 - Maintenance safety considerations...................................................................................................................................... 7
1.5 - Safety considerations during system interventions.............................................................................................................. 7
2 - RECEIPT OF GOODS.............................................................................................................................................................. 9
2.1 - Check equipment received................................................................................................................................................... 9
3 - HANDLING AND POSITIONING............................................................................................................................................ 10
3.1 - Handling............................................................................................................................................................................. 10
3.2 - Positioning.......................................................................................................................................................................... 10
4 - DIMENSIONS, CLEARANCES................................................................................................................................................11
4.1 - LD/ILD150 to LD/ILD300.....................................................................................................................................................11
4.2 - LD360 to LD600 and ILD302 to ILD600............................................................................................................................. 13
4.3 - Installing several units ....................................................................................................................................................... 15
5 - PHYSICAL AND ELECTRICAL PROPERTIES OF AQUACIAT LD/ILD UNITS.................................................................... 16
5.1 - Physical properties of AQUACIAT LD units ....................................................................................................................... 16
5.2 - Physical properties of AQUACIAT ILD units ...................................................................................................................... 18
5.3 - Electrical data notes for the Units ..................................................................................................................................... 20
5.4 - Short circuit current withstand capability............................................................................................................................ 20
5.5 - Electrical data notes for the hydronic module.................................................................................................................... 21
5.6 - Electrical data notes for the compressors.......................................................................................................................... 22
5.7 - Distribution of compressors per circuit............................................................................................................................... 23
5.8 - Comments on electrical data notes.................................................................................................................................... 23
6 - ELECTRICAL CONNECTION................................................................................................................................................ 24
6.1 - Power supply...................................................................................................................................................................... 24
6.2 - Voltage phase imbalance (%)............................................................................................................................................ 24
6.3 - Recommended cable sections........................................................................................................................................... 24
6.4 - Power cable access routing............................................................................................................................................... 25
6.5 - Field-installed control wiring............................................................................................................................................... 25
6.6 - Electric power reserve for the user.................................................................................................................................... 25
7 - APPLICATION DATA.............................................................................................................................................................. 26
7.1 - AQUACIAT LD operating limits........................................................................................................................................... 26
7.2 - AQUACIAT ILD operating limits.......................................................................................................................................... 26
7.3 - Minimum heat transfer fluid flow rate (units without factory-fitted hydronic module).......................................................... 27
7.4 - Maximum heat transfer fluid flow rate (without factory-fitted hydronic module)................................................................. 27
7.5 - Water exchanger min. water volume and flow rate............................................................................................................ 28
7.6 - Maximum system water volume......................................................................................................................................... 28
7.7 - Pressure drop curves for the water exchanger and its water inlet/outlet piping (for units without pump).......................... 29
8 - WATER CONNECTIONS........................................................................................................................................................ 30
8.1 - Operating precautions and recommendations................................................................................................................... 30
8.2 - Water connections.............................................................................................................................................................. 31
8.3 - Cavitation protection (with hydronic option)....................................................................................................................... 34
8.4 - Flow rate detection............................................................................................................................................................. 34
8.5 - Frost protection.................................................................................................................................................................. 35
8.6 - Extra electrical heaters field-installed or integrated into the buffer tank (depending on the option chosen)...................... 36
9 - NOMINAL SYSTEM WATER FLOW CONTROL.................................................................................................................... 37
9.1 - Units without hydronic module........................................................................................................................................... 37
9.2 - Units with hydronic module and fixed-speed pump (only for negative cold applications).................................................. 38
9.3 - Units with hydronic module and variable speed pump – Pressure differential control....................................................... 39
9.4 - Units with hydronic module and variable speed pump – Temperature differential control................................................. 40
9.5 - Pump flow rate/pressure curves......................................................................................................................................... 41
9.6 - Available static pressure for the installation....................................................................................................................... 42
10 - SYSTEM START-UP............................................................................................................................................................. 44
10.1 - Checks before system start-up........................................................................................................................................ 44
10.2 - Commissioning................................................................................................................................................................. 44
10.3 - Essential points to check.................................................................................................................................................. 45
AQUACIAT LD/ILD EN -2
CONTENTS
The illustrations in this document are for illustrative purposes only and not part of any offer for sale or contract. The manufacturer reserves the right to change the design
at any time without notice.
The units are intended to cool or heat water for building air Classification and control:
conditioning or heating, or for industrial processes.
In accordance with the Pressure Equipment Directive and
They are designed to provide a very high level of safety and national usage monitoring regulations in the European Union,
reliability, making installation, start-up, operation and maintenance the protective devices fitted to these machines are classified as
easier and safer. follows:
They will provide safe and reliable service if used within their
application ranges. Device for limitation
Safety
of damage in the event of
device(1)
They are designed to offer a service life of 15 years, assuming an external fire(2)
a utilisation factor of 75%, which corresponds to approximately Refrigerant side
100,000 operating hours. High pressure switch X
Prior to the initial start-up of the units, everyone involved in the External relief valve(3) X
works should be thoroughly familiar with these instructions and Rupture disk X
with the characteristics of the installation site, and ensure these
Fusible plug X
are respected.
Heat transfer fluid side
The procedures in this manual are arranged in the sequence
External relief valve (4) (4)
required for installation, start-up, operation and maintenance of
the units. Ensure that you follow them and that you take the (1) Classified for protection in normal service situations.
(2) Classified for protection in abnormal service situations. These accessories
required safety precautions, including those listed in this guide,
are sized for fires with a thermal flow of 10 kW/m². No combustible matter
which include wearing personal protective equipment (gloves, should be placed within 6.5 m of the unit.
safety glasses, safety shoes) and having the appropriate tools, (3) The instantaneous over-pressure limitation of 10% of the operating pressure
skills and qualifications (electrical, air conditioning, local does not apply to this abnormal service situation.
The set pressure can be higher than the operating pressure. In this case,
legislation).
either the design temperature or the high pressure switch ensures that the
To find out if these products comply with European directives operating pressure is not exceeded in normal service situations.
(machine safety, low-voltage, electromagnetic compatibility, (4) The classification of these relief valves must be made by the personnel
responsible for completing the hydraulic installation.
pressurised equipment, etc.) check the declarations of conformity
for these products. Do not remove valves / fusible plugs, even if the fire risk is under
control for a particular installation. There is no guarantee that
1.1 - Safety considerations related to the accessories have been re-installed if the system is changed
protection devices or for transport with a gas charge.
When the unit is subjected to fire, a safety device prevents rupture
Do not obstruct any protective devices. due to over-pressure by releasing the refrigerant. The fluid can
This applies to any fusible plugs, rupture disks and valves fitted then break down into toxic residues when in contact with flames:
on the refrigerant or heat-transfer fluid circuits. Check whether • Stay away from the unit;
the original protection plugs are still present at the valve outlets. • Ensure the personnel in charge of extinguishing the fire are
These plugs are generally made of plastic and should not be used. duly warned and issued with recommendations;
If they are still present, please remove them. Fit devices at the • Fire extinguishers appropriate to the system and the
valve or discharge piping outlets to prevent the penetration of refrigerant type must be easily accessible.
foreign bodies (dust, building debris, etc.) and atmospheric agents All factory-fitted relief valves are lead-sealed to prevent any
(water can form rust or ice). These devices, as well as the calibration change.
discharge piping, must not impair operation and not lead to The external relief valves must always be vented to outside if
a pressure drop that is higher than 10% of the set pressure. the units are installed in a closed space. Refer to the installation
regulations, for example those of European standard EN 378
and EN 13136. These pipes must be installed in a way that
ensures that people and property are not exposed to vented
refrigerant. As the fluids can be diffused in the air, ensure that
refrigerant is discharged away from building air intakes, relief
valves must be checked periodically. The valves must be checked
periodically.
If the relief valves are factory fitted on a changeover valve, this
is equipped with a relief valve on each of the two outlets. Only
one of the two relief valves is in operation, the other one is
isolated. Never leave the changeover valve in the intermediate
position, i.e. with both circuits open (move the lever fully forwards
or backwards depending on the output to be isolated). If a valve
is removed for checking or replacement, make sure there is still
a valve active on each of the changeover valves installed on the
unit.
Provide a drain in the discharge pipework, close to each relief
valve, to avoid an accumulation of condensate or rain water.
AQUACIAT LD/ILD EN -4
1 - INTRODUCTION
It is recommended to install an indicating device to check whether Detect and repair the leak, check the type of refrigerant in the
any refrigerant has leaked from the relief valve. machine and then recharge the machine/circuit with the total
The presence of oil at the outlet orifice is a useful indicator that charge, as indicated on the unit nameplate. Do not top up the
refrigerant has leaked. Keep this orifice clean to ensure that any refrigerant charge. Only charge the liquid refrigerant given on
leaks are obvious. The calibration of a valve that has leaked is the nameplate at the liquid line.
generally lower than its original calibration. The new calibration Charging any refrigerant other than the original type will impair
may affect the operating range. To avoid nuisance tripping or machine operation and can even cause irreparable damage to
leaks, replace or re-calibrate the valve. the compressors. The compressors operating with this refrigerant
type are lubricated with a synthetic polyolester oil.
Protective device checks:
Do not unweld the refrigerant pipework or any refrigerant circuit
If no national regulations exist, check the protective devices on component or cut these with a torch until all refrigerant (liquid
site in accordance with standard and vapour) as well as the oil have been removed from the unit.
EN 378: once a year for the high pressure switches, every five Traces of vapour should be displaced with dry nitrogen.
years for external relief valves. Refrigerant in contact with an open flame produces toxic gases.
The company or organisation that conducts a pressure switch Do not siphon refrigerant.
test must establish and implement detailed procedures for: Any accidental release of refrigerant, whether this is caused by
• Safety measures, a small leak or significant discharges following the rupture of
• Measuring equipment, a pipe or an unexpected release from a relief valve, may cause
• Values and tolerances for cut-off and discharge devices, any personnel exposed to experience heart palpitations,
• Test stages, faintness, frostbite and burns. Always take any such event
• Recommissioning of the equipment. seriously.
The principle for performing a test without disassembly of the Installers, owners and especially service engineers for these
pressure switch is given here, however the manufacturer units must:
recommends contacting Ciat Service for this type of test: • Create a procedure to ensure medical attention is sought
• Verify and record the setpoints of pressure switches and before treating any symptoms;
external relief devices (valves and possible rupture disks), • Provide first aid equipment, flush the eyes and skin
• Be ready to switch off the main disconnect switch of the immediately if splashed with refrigerant, and seek medical
power supply if the pressure switch does not trigger (avoid attention.
over-pressure or excess gas if there are valves on the high
We recommend to apply standard EN 378-3 Annex 3.
pressure side on the recovery air exchangers, for example),
• Connect a calibrated pressure differential gauge with Ensure there is sufficient ventilation if the unit is installed in an
integral damping (oil bath with pointer if mechanical); enclosed area. In gas form, refrigerant is heavier than air and,
instantaneous reading gauges may give inaccurate readings if allowed to accumulate in a confined area, it can reduce the
because of the control's scanning delay, quantity of oxygen in the air, causing respiratory issues.
• Carry out the HP quicktest built into the control (refer to the The refrigerant used in units in this range is R410A, a high-
Service Guide). pressure fluid (the operating pressure of the unit is greater than
40 bar).
If the test results in the replacement of the pressure
switch, it is necessary to recover the refrigerant Special equipment must be used when working on the refrigerant
charge; these pressure switches are not installed circuit (pressure gauge, charge transfer equipment, etc.).
on Schrader type automatic valves. Do not clean the unit with hot water or steam. This may cause
If the machine operates in a corrosive environment, inspect the the refrigerant pressure to rise.
protection devices more frequently. NOTE: If a liquid line valve is present, never leave refrigerant in
Do not attempt to repair or recondition a valve if there has been liquid form between this closed valve and the expansion valve
any corrosion or build-up of foreign material (rust, dirt, scale, as the change in temperature may cause the liquid to expand,
etc.) on the valve body or mechanism. In this case, it must be rupturing this section of the circuit. This valve is situated on the
replaced. liquid line before the filter drier.
Do not install relief valves in series or backwards. Never apply an open flame or pressurised steam to a refrigerant
container. Dangerous overpressure can result. If it is necessary
to heat the refrigerant, only use hot water.
1.2 - Refrigerant safety considerations
The standard NF E29-795 describes the regulations permitting
Use safety goggles and safety gloves. conditioning and recovery of halogenated hydrocarbons under
All precautions concerning handling of refrigerant must be optimum quality conditions for the products and optimum safety
observed in accordance with local regulations. conditions for people, property and the environment. If any
If a leak occurs or if the refrigerant becomes contaminated damage is caused to the equipment, the refrigerant must be
(e.g by a motor short circuit or BPHE freeze-up), and before any changed in accordance with this standard, or an analysis of the
intervention, remove the complete charge using a recovery unit fluid must be performed by a specialist laboratory.
and store the refrigerant in mobile containers. The compressors Any refrigerant transfer and recovery operations must be carried
cannot transfer the whole refrigerant charge and can be damaged out using a transfer unit.
if used to pump-down. The refrigerant charge should not be
transferred to the high-pressure side.
Service valves are positioned on the liquid, suction and discharge ► For all equipment subject to regular sealing tests,
lines and are available on all units for connection to the transfer the operator must keep a log used to record the
unit. following: the quantities and types of fluids
The units must never be modified to add refrigerant and oil contained in the system (added and recovered),
charging, removal and purging devices. These units have the the quantity of fluid recycled, regenerated or
required openings. Refer to the certified dimensional drawings. destroyed, the date and results of the sealing
It is dangerous and illegal to re-use disposable (non-returnable) tests, the details of the technician and of the
cylinders or attempt to refill them. When the cylinders are empty, company performing the work, etc.
evacuate the remaining gas pressure, fill out the relevant ► Contact your local dealer or installer if you have
paperwork and hand them over to an approved recovery agency. any questions.
Do not incinerate. Information on operating inspections given in EN 378 standard
Operating checks: can be used when similar criteria do not exist in the national
regulation.
IMPORTANT: This product contains fluorinated greenhouse
Check regularly for leaks and, if detected, have these repaired
gas covered by the Kyoto protocol.
immediately.
Type of fluid: refer to the nameplate
Global Warming Potential (GWP): refer to the table below 1.3 - Installation safety considerations
► All interventions on this product's refrigerating After the unit has been received, and before it is started up, it
circuit must be performed in accordance with must be inspected for damage. Check that the refrigerant circuits
applicable legislation. Within the European are intact, especially that no components or pipes have shifted
Union, this legislation notably includes regulation or been damaged (e.g. following a shock). If in doubt, carry out
No. 517/2014, known as F-Gas. a leak tightness check.
► Ensure that refrigerant is never released to the
atmosphere when the equipment is installed, Pressure equipment and components
maintained or sent for disposal. These products include pressure equipment or components
► It is prohibited to deliberately release refrigerant manufactured by the unit manufacturer or by other manufacturers.
into the atmosphere. We recommend that you contact your professional body to find
► If a refrigerant leak is detected, ensure that the out which regulations affect you as the operator or owner of
leak is repaired quickly. pressure equipment or components (declaration, re-qualification,
re-testing). The characteristics of this equipment/these
► Only certified, qualified personnel are permitted
components are given on the nameplate or in the required
to install, service and perform sealing tests on
documentation, supplied with the products.
the refrigerant, decommission the equipment
and recover the refrigerant. These units comply with the European Pressure Equipment
Directive.
► The operator must ensure that any refrigerant
recovered is recycled, regenerated or destroyed. The units are intended to be stored and operated in an
environment where the ambient temperature does not drop below
► The operator is bound by the obligation to
the minimum allowable temperature indicated on the nameplate.
perform sealing tests, or have these performed,
at regular intervals. Do not introduce significant static or dynamic pressure with
regard to the operating pressures used during operation or for
► Regulations within the European Union have set
tests in the refrigerant circuit or in the heat exchange circuits.
the following intervals:
NOTE: Monitoring during operation, re-qualification, re-testing,
System WITHOUT leakage exemption from re-testing:
No test 12 months 6 months 3 months • Follow the regulations on monitoring pressurised equipment.
detection
• The user or operator is usually required to create and
System WITH leakage maintain a monitoring and maintenance log.
No test 24 months 12 months 6 months
detection
• In the absence of any regulations, or in addition to the
Refrigerant charge per
< 5 tons 5<≤50charge 50 ≤ charge Charge regulations, follow the guidance in EN 378.
circuit (equivalent CO2) tons < 500 tons > 500 tonnes* • Follow the local professional recommendations, whenever
3.5 ≤ they exist.
R134a Charge charge 34.9 ≤ charge charge
(PRP 1430) < 3.5 kg < 349.7 kg > 349.7 kg • Regularly monitor the surface of the components to detect
Refrigerant charge per
AQUACIAT LD/ILD EN -6
1 - INTRODUCTION
Repair: Even if the unit has been shut down, the power
Any repair or modification, including replacement of removable circuit remains energized, unless the unit or circuit
parts: disconnect switch is open. Refer to the wiring
• Must comply with local regulations and must be performed diagram for further details. Follow the appropriate
by qualified operators in accordance with qualified safety guidelines. When working in a fan area,
processes, including changing a wiring harness conductor, specifically if the grilles have to be removed, isolate
• Must be approved by the original manufacturer. Repairs the power supply to the fans to prevent their
and modifications which involve a permanent assembly operation.
(welding, soldering, expansion of tubes, etc.) must be Units equipped with the variable speed fan option, variable speed
performed by qualified operators following operating pump options and the power factor option are equipped with
procedures, capacitor batteries which take 5 minutes to fully discharge once
• All modifications and repairs must be listed in the monitoring the power has been switched off.
and maintenance register,
After disconnecting the power supply to the electrics box, wait
• Never attempt to repair or modify a plate heat exchanger.
5 minutes before accessing the electrics box or variable drives.
Recycling: Before any intervention, verify that there is no voltage present
The pressure equipment can be recycled in whole or in part. at any accessible conducting parts of the power circuit.
After use they may contain refrigerant vapours and oil residue. Regularly check that the vibration levels remain acceptable and
Some parts are painted. close to those at the initial machine start-up.
Before opening a refrigerant circuit, purge and read the pressure
1.4 - Maintenance safety considerations indicators.
The manufacturer recommends the following template for the If the refrigerant circuit remains open after an intervention (such
maintenance log (the table below is only given as a guide and as a component replacement, etc.):
does not engage the manufacturer's liability). - Seal the openings if the duration is less than a day
- Beyond this time, charge the circuit with a dry, inert gas
Intervention Name of the (nitrogen).
Applicable national Verification
Nature commissioning
Date regulations Organisation The objective is to prevent penetration of atmospheric humidity
(1) engineer
and the resulting corrosion of the unprotected internal steel walls.
AQUACIAT LD/ILD EN -8
2 - RECEIPT OF GOODS
1330 HT
1061 HT 2050 HT
Legend: NOTES :
All dimensions are in mm.
A Non-certified drawings.
Control box
Refer to the certified dimensional drawings supplied
Water inlet with the unit or available on request, when designing
Water outlet an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity
B Required clearances for air flow
refer to the certified dimensional drawings.
C Recommended clearances for maintenance
B In multiple-chiller installations (maximum four units),
Air outlet, do not obstruct
the side clearance between the units should be
Power cable entry increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.
NOTE: For units with other options, refer to the certified dimensional drawings.
1114 HT 2130 HT
1000
1000
1000
1000
Legend: NOTES :
All dimensions are in mm.
A Non-certified drawings.
Control box
Refer to the certified dimensional drawings supplied
Water inlet with the unit or available on request, when designing
Water outlet an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity
B Required clearances for air flow
refer to the certified dimensional drawings.
C Recommended clearances for maintenance
B In multiple-chiller installations (maximum four units),
Air outlet, do not obstruct
the side clearance between the units should be
Power cable entry increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.
NOTE: For units with other options, refer to the certified dimensional drawings.
Legend: NOTES :
All dimensions are in mm.
A Non-certified drawings.
Control box
Refer to the certified dimensional drawings supplied
Water inlet with the unit or available on request, when designing
Water outlet an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity
B Required clearances for air flow
refer to the certified dimensional drawings.
C Recommended clearances for maintenance
B In multiple-chiller installations (maximum four units),
Air outlet, do not obstruct
the side clearance between the units should be
Power cable entry increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.
NOTE: For units with other options, refer to the certified dimensional drawings.
2130 HT
2311 HT
1000
1000
1000
1000
Legend: NOTES :
All dimensions are in mm.
A Non-certified drawings.
Control box
Refer to the certified dimensional drawings supplied
Water inlet with the unit or available on request, when designing
Water outlet an installation. For the location of fixing points, weight
distribution and coordinates of the centre of gravity
B Required clearances for air flow
refer to the certified dimensional drawings.
C Recommended clearances for maintenance
B In multiple-chiller installations (maximum four units),
Air outlet, do not obstruct
the side clearance between the units should be
Power cable entry increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.
NOTE: For units with other options, refer to the certified dimensional drawings.
AQUACIAT LD 150 180 200 240 260 300 360 390 450 520 600
Sound levels
Standard unit
Sound power(1) dB(A) 80 81 81 81 87 87 84 84 84 90 90
Sound pressure at 10 m(2) dB(A) 49 49 49 49 55 55 52 52 52 58 58
Unit + Xtra Low Noise option
Sound power(1) dB(A) 79 80 80 80 80 80 83 83 83 83 83
Sound pressure at 10 m(2) dB(A) 48 48 48 48 48 48 51 51 51 51 51
Dimensions
Length mm 1090 1090 1090 1090 1090 1090 2270 2270 2270 2270 2270
Width mm 2109 2109 2109 2109 2109 2109 2123 2123 2123 2123 2123
Height mm 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330
Height with Buffer Tank Module mm 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930
Operating weight with Micro-Channel coils(3)
Standard unit kg 422 430 436 449 445 463 753 762 771 829 854
Unit + High pressure single pump option kg 463 472 478 491 487 505 820 829 842 903 928
Unit + High pressure dual-pump option kg 489 498 504 517 513 531 865 874 891 940 965
Unit + High pressure single pump option kg 859 868 874 887 883 901 1253 1262 1275 1336 1361
+ Buffer tank module
Unit + High pressure dual pump option
+ Water buffer tank module kg 885 894 900 913 909 927 1298 1307 1324 1373 1398
Compressors Hermetic Scroll 48.3 rps
Circuit A Qty 2 2 2 2 2 2 3 3 3 2 2
Circuit B Qty - - - - - - - - - 2 2
Number of power stages Qty 2 2 2 2 2 2 3 3 3 4 4
Refrigerant with Micro-Channel coils (3) R410A GWP=2088 following ARI4
kg 4,7 5,3 5,9 6,7 6,2 7,3 10,7 10,8 11,4 6,5 7,4
Circuit A
tCO2e 9,8 11,1 12,3 14,0 12,9 15,2 22,3 22,6 23,8 13,6 15,5
kg - - - - - - - - - 6,5 7,4
Circuit B
tCO2e - - - - - - - - - 13,6 15,5
Oil charge POE SZ160 (EMKARATE RL 32-3MAF).
Circuit A l 5,8 7,2 7,2 7,2 7 7 10,8 10,5 10,5 7 7
Circuit B l - - - - - - - - - 7 7
Control Connect Touch Control
Minimum capacity % 50 50 50 50 50 50 33 33 33 25 25
(1) in dB ref=10-12 W, weighting (A). Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). Measured
in accordance with ISO 9614-1.
(2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For
information, calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit nameplate.
AQUACIAT LD 150 180 200 240 260 300 360 390 450 520 600
AQUACIAT ILD 150 180 200 240 260 300 302 360 390 450 520 600
Sound levels
Standard unit
Sound power(1) dB(A) 80 81 81 86 87 87 84 84 84 84 90 90
Sound pressure at 10 m(2) dB(A) 49 49 49 55 55 55 52 52 52 52 58 58
Unit + Xtra Low Noise option
Sound power(1) dB(A) 79 80 80 80 80 80 83 83 83 83 83 83
Sound pressure at 10 m(2) dB(A) 48 48 48 48 48 48 51 51 51 51 51 51
Dimensions
Length mm 1090 1090 1090 1090 1090 1090 2270 2270 2270 2270 2270 2270
Width mm 2109 2109 2109 2109 2109 2109 2123 2123 2123 2123 2123 2123
Height mm 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440 1440
Height with Buffer Tank Module mm 2040 2040 2040 2040 2040 2040 2040 2040 2040 2040 2040 2040
Operating weight(3)
Standard unit kg 497 506 543 549 559 564 777 896 905 979 1053 1057
Unit + High pressure single pump option kg 539 548 585 591 601 606 844 963 972 1050 1127 1131
Unit + High pressure dual-pump option kg 565 574 611 617 627 632 889 1008 1017 1098 1164 1168
Unit + High pressure single pump option kg 935 943 981 986 996 1001 1276 1395 1404 1482 1560 1563
+ Buffer tank module
Unit + High pressure dual pump option kg 961 969 1006 1012 1022 1027 1321 1440 1449 1531 1597 1600
+ Water buffer tank module
Unit + high pressure single pump option + Water kg 1018 1026 1064 1069 1079 1084
buffer tank module with extra heaters (16 kW)
Unit + high pressure dual pump option + Water kg 1044 1052 1089 1095 1105 1110
buffer tank module with extra heaters (16 kW)
Unit + high pressure single pump option + Water buffer kg 1022 1030 1068 1073 1083 1088
tank module with extra heaters (31 kW and 45 kW)
Unit + high pressure dual pump option + Water buffer kg 1048 1056 1093 1099 1109 1114
tank module with extra heaters (31 kW and 45 kW)
Compressors Hermetic Scroll 48.3 rps
Circuit A Qty 2 2 2 2 2 2 2 3 3 3 2 2
Circuit B Qty - - - - - - - - - - 2 2
Number of power stages Qty 2 2 2 2 2 2 2 3 3 3 4 4
Refrigerant (3) R410A GWP=2088 following ARI4
kg 12,5 13,5 16,5 17,5 18 16,5 21,5 27,5 28,5 33 19 18,5
Circuit A
tCO2e 26,1 28,2 34,5 36,5 37,6 34,5 44,9 57,4 59,5 68,9 39,7 38,6
kg - - - - - - - - - - 19 18,5
Circuit B
tCO2e - - - - - - - - - - 39,7 38,6
Oil charge POE SZ160 (EMKARATE RL 32-3MAF)
Circuit A l 5,8 7,2 7,2 7,2 7,0 7,0 7,2 7,0 7,0 7,0 7,0 7,0
Circuit B l - - - - - - - - - - 7,0 7,0
Control Connect Touch Control
Minimum capacity % 50 50 50 50 50 50 50 33 33 33 25 25
(1) In dB ref=10-12 W, 'A' weighted. Declared dual-number noise emission value in accordance with ISO 4871 (with an uncertainty of +/-3dB(A). Measured in accordance
with ISO 9614-1 and certified by EUROVENT
(2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission value in accordance with ISO 4871 (with an uncertainty of +/-3dB(A). Value calculated from
the sound power level Lw(A).
(3) Weights given as a guide. Refer to the unit nameplate.
AQUACIAT ILD 150 180 200 240 260 300 302 360 390 450 520 600
LD / ILD - Standard unit (without hydronic module) 150 180 200 240 260 300 302 360 390 450 520 600
Power circuit
Nominal voltage V-ph-Hz 400 - 3 -50
Voltage range V 360 - 440
Control circuit supply 24 V via internal transformer
Nominal unit operating current(3)
Circuit A&B A 25,6 29 33 36 42,4 52,8 53,4 55,4 61,7 77,3 84,8 105,6
Max. operating input power (2)
Circuit A&B kW 19,5 22,3 24,5 27,9 31,2 35,8 35,6 42,3 45,6 52,5 62,4 71,6
Cosine Phi unit at maximum power (2) 0,83 0,81 0,81 0,83 0,81 0,78 0,78 0,83 0,81 0,79 0,81 0,78
Unit max. operating current (Un-10%)(5)
Circuit A&B A 38 49,2 51,4 58,4 74,8 79,6 80,2 89 110,3 117,5 149,6 159,2
Maximum unit current draw (Un)(4)
Circuit A&B - Standard unit A 34,8 44,8 46,8 52,8 67 73 73,6 80,6 98,6 107,6 134 146
Maximum start-up current, standard unit (Un) (1)
Circuit A&B A 113,8 134,8 142,8 145,8 176 213 213,6 173,6 207,6 247,6 243 286
Maximum start-up current, unit with soft starter (Un) (1)
Circuit A&B A 74,7 86,5 93,8 96,2 114,4 139,8 139,8 130,4 155,4 181,4 186,4 215,4
(1) Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + fan current(s) + locked rotor current of the largest compressor).
(2) Input power, at the unit’s continuous operating limits (indicated on the unit nameplate).
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(4) Unit maximum current at 400 V, in non-continuous operation (indicated on the unit name plate)
(5) Unit maximum current at 360 V, in non-continuous operation
Unit low-pressure single and dual pumps (Fixed speed single pumps, hydronic module option)
ILD
No.(2) Description(3) Units
150 180 200 240 260 300 302 360 390 450 520 600
Nominal efficiency at full load and nominal
1 % 81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 83,4 83,4 84,8 84,8
voltage
Nominal efficiency at 75% of full load and
1 % 80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 81,2 81,2 82,2 82,2
nominal voltage
Nominal efficiency at 50% of full load and
1 % 77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 78,3 78,3 79 79
nominal voltage
2 Efficiency level - IE3
This information varies depending on the manufacturer and model at the time of incorporation. Please refer
3 Year of manufacture - to the motor nameplates.
Manufacturer's name and trademark,
4 commercial registration number and - Same as above
manufacturer's head office
5 Product's model number - Same as above
6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 2
Nominal shaft power output at full load and
7-1 kW 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,8 1,3 1,3 1,7 1,7
nominal voltage (400 V)
7-2 Maximum input power (400 V)(4) kW 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,6 1,6 2,4 2,4
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)(5) A 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,9 2,9 4,2 4,2
rps - rpm 2850 2850 2850 2850 2850 2850 2850 2850 2890 2890 2870 2870
10 Nominal speed
47 47 47 47 47 47 47 47 48 48 48 48
11 Product disassembly, recycling or disposal at - Disassembly using standard tools. Disposal and recycling using an appropriate company.
end of life
Operating conditions for which the motor is
specifically designed
I- Altitudes above sea level m < 1000(6)
12 II - Ambient air temperature °C < 55
Please refer to the operating conditions given in this manual or
III - Maximum operating temperature °C in the specific conditions given in the selection programs.
IV - Potentially explosive atmospheres - Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric
motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the electrical data table to the pump
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
Unit high pressure single and dual-pumps (Fixed speed single pumps, hydronic module option)
LD / ILD
No.(2) Description(3) Units
150 180 200 240 260 300 302 360 390 450 520 600
Nominal efficiency at full load and nominal
1 % 84,8 84,8 84,8 84,8 84,8 84,8 84,8 84,8 84,8 85,9 85,9 85,9
voltage
Nominal efficiency at 75% of full load and
1 % 82,2 82,2 82,2 82,2 82,2 82,2 82,2 82,2 82,2 84 84 84
nominal voltage
Nominal efficiency at 50% of full load and
1 % 79 79 79 79 79 79 79 79 79 82,1 82,1 82,1
nominal voltage
2 Efficiency level - IE3
This information varies depending on the manufacturer and model at the time of incorporation.
3 Year of manufacture - Please refer to the motor nameplates.
Manufacturer's name and trademark,
4 commercial registration number and - Same as above
manufacturer's head office
5 Product's model number - Same as above
6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 2
Nominal shaft power output at full load and
7-1 kW 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 2,2 2,2 2,2
nominal voltage (400 V)
7-2 Maximum input power (400 V)(4) kW 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,9 2,9 2,9
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)(5) A 4,2 4,2 4,2 4,2 4,2 4,2 4,2 4,2 4,2 5 5 5
rps - rpm 2870 2870 2870 2870 2870 2870 2870 2870 2870 2855 2855 2855
10 Nominal speed
48 48 48 48 48 48 48 48 48 48 48 48
11 Product disassembly, recycling or disposal at - Disassembly using standard tools. Disposal and recycling using an appropriate company.
end of life
Operating conditions for which the motor is
specifically designed
I- Altitudes above sea level m < 1000(6)
12 II - Ambient air temperature °C < 55
Please refer to the operating conditions given in this manual or
III - Maximum operating temperature °C in the specific conditions given in the selection programs.
IV - Potentially explosive atmospheres - Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric
motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the electrical data table to the pump
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
LD / ILD
Compressor Circuit
150 180 200 240 260 300 302 360 390 450 520 600
A 2 - - - - - - - - - - -
ZP90
B - - - - - - - - - - - -
A - 2 - - - - - - - - - -
ZP103
B - - - - - - - - - - - -
A - - 2 - - - - - - - - -
ZP120
B - - - - - - - - - - - -
A - - - 2 - - - 3 - - - -
ZP137
B - - - - - - - - - - - -
A - - - - 2 - - - 3 - 2 -
ZP154
B - - - - - - - - - - 2 -
A - - - - - 2 2 - - 3 - 2
ZP182
B - - - - - - - - - - - 2
I Nom: Nominal current (A) under Eurovent conditions (see definition of conditions under unit nominal current)
I Max: Maximum operating current (A), 360 V
(1) Locked rotor current (A), at nominal voltage
(2) Locked rotor current (A) with electronic starter, at nominal voltage
Example:
On a 400 V - 3 ph - 50 Hz power supply, the individual phase
voltages were measured with the following values: AB= 406V;
BC= 399V; AC= 394V
Average voltage =(406+399+394)/3=1199/3 =399.7 i.e. 400 V
Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6
Motor
Table of minimum and maximum cable sections (per phase) for connection to the units
The protection against direct contact at the electrical connection point is compatible with the addition of terminals extension.
The installer must determine whether these are necessary based on the cable sizing calculation.
Minimum and maximum cable sections (per phase) for connection to the extra heater ILD units
6.4 - Power cable access routing See the control manual and the certified electric wiring diagram
supplied with the unit for the field control wiring of the following
The power cables can be routed into the electrical box for the
devices:
units:
• Device automatic operation control
- via the underside of the unit,
• Setpoint 1/Setpoint 2 switching
- via the side of the unit,
• Heating / cooling selection
- on the bottom of the corner post.
• Demand limits
A removable aluminium plate on the base of the electrical cabinet • Operating fault display
provides access for the power cables. • Locking switch (safety chain)
It is important to check that the power cable bend radius is • Customer pump switch control (on/off)
compatible with the connection space available inside the • Setpoint adjustable by 4-20 mA signal
electrical cabinet. • Second power limitation level
• Desuperheater activation control
Refer to the certified dimensional drawing for the unit.
• Unit shut down general fault reporting
• Free cooling drycooler management
6.5 - Field-installed control wiring
IMPORTANT: Connecting the interface circuits on-site creates 6.6 - Electric power reserve for the user
certain safety risks; any modification to the electrical box must
ensure the equipment remains compliant with local regulations. Control circuit power reserve:
In particular, precautions must be taken to prevent accidental After all possible options have been connected, the
electrical contact between the circuits supplied by different CT transformer ensures the availability of 1 A of power for the
sources: control cabling on-site on 24 V, 50 Hz.
• The choice of routing and/or insulation characteristics of
the conductors ensures double electrical insulation.
• The conductors should be fixed together inside the electrical
box to prevent contact between the end of the conductor
and a live part in case of accidental disconnection.
Very Low
Temperature
Winter operation
option
or XtraFan
option
Very Low
Temperature
option
Winter operation or Evaporator water outlet temperature, °C
XtraFan option Full load Minimum load
Winter operation option Very Low Temperature option
Low Temperature option
Evaporator water outlet temperature, °C
Full load Minimum load
Winter operation option Very Low Temperature option
Low Temperature option
NOTE: Ducted machines (Xtra Fan option) This operating range applies up to a static pressure of 130 Pa without a suction duct
for sizes 070-080 and 140-160, and up to 240 Pa for all other sizes.
Operating range for standard unit, heating mode 7.3 - Minimum heat transfer fluid flow rate
(units without factory-fitted hydronic module)
AQUACIAT ILD / Heating mode Minimum Maximum
The minimum heat transfer fluid flow rate is given in the
Water heat exchanger paragraph "water exchanger min. water volume and flow rate".
Water inlet temperature (at start-up) °C 8 45 If the system flow rate is less than the unit's minimum flow rate,
Water outlet temperature (in operation) °C 25 55 the exchanger flow can be recirculated, as shown in the diagram
Inlet/outlet temperature difference K 3 10
Air-cooled exchanger (3) For a minimum heat-transfer fluid flow rate
Air inlet temperature °C -15 40
Hydronic module(4) 1
Air inlet temperature
Without pump °C -20 -
With Single or Dual pump option (LP or HP) °C 0 -
With Single or Dual pump (LP or HP) + Frost °C -20 -
protection option
With Buffer Tank option °C 0 2
If the system flow rate is less than the minimum flow rate, there
may be a high risk of fouling.
If using an external variable speed pump, make sure that the
Outlet water temperature, °C
AQUACIAT LD 150 180 200 240 260 300 360 390 450 520 600
Minimum system water volume, air conditioning application (litres) 121 140 164 182 207 243 181 205 240 204 240
Minimum system water volume, industrial process application (litres) 304 351 410 454 518 608 452 513 601 510 601
0.9 / 0.9 / 1.2 / 1.3 / 1.5 / 1.7 / 2.3 /
Min. / max. water exchanger flow rate without hydronic module(1) (l/s) 0.9 / 3 3.4 4.2 0.9 / 5 1/5 5.5 6.8 7.7 8.5 2 / 10.6 11.2
Low pressure(3) 2,9 3,2 3,7 4,1 4,1 4,4 5,1 6,3 6,5 7,9 8,2
Maximum water exchanger flow rate, Dual pump (l/s) (2)
High pressure (3) 3,4 3,8 4,4 5 5 5,2 6,2 6,5 8 8,7 8,9
(1) Maximum flow rate for a pressure drop of 100 kPa in the water exchanger
(2) Maximum flow rate corresponding to an operating pressure of 50 kPa (unit with high pressure pump).
(3) Maximum flow rate with single pump 2 to 4% higher, depending on the size.
NOTE: For the Buffer Tank Module option, the tank volume must be taken into account: 250 litres
AQUACIAT ILD 150 180 200 240 260 300 302 360 390 450 520 600
Minimum system water volume, air conditioning application (litres) 202 234 274 303 346 405 405 301 342 400 340 401
Minimum system water volume, industrial process application (litres) 304 351 410 454 518 608 608 452 513 601 510 601
Min. / max. water exchanger flow rate without hydronic module(1) (l/s) 0.9 / 3 0.9/3.4 0.9/4.2 0.9/5 1/5 1.2/5.5 1.2/6.8 1.3/6.8 1.5/7.7 1.7/8.5 2/10.6 2.3/11.2
Low pressure(3) 2,9 3,2 3,7 4,1 4,1 4,4 5,1 5,1 6,3 6,5 7,9 8,2
Maximum water exchanger flow rate, Dual pump (l/s)(2)
High pressure (3) 3,4 3,8 4,4 5 5 5,2 6,2 6,2 6,5 8 8,7 8,9
(1) Maximum flow rate for a pressure drop of 100 kPa in the water exchanger
(2) Maximum flow rate for an available pressure of 20 kPa (unit with low-pressure pumps) or 50 kPa (high pressure).
(3) Maximum flow rate with single pump 2 to 4% higher, depending on the size.
NOTE: For the Buffer Tank Module option, the tank volume must be taken into account: 250 litres
7.7 - Pressure drop curves for the water exchanger and its water inlet/outlet piping (for
units without pump)
Data applicable for pure water at 20°C.
Option
Option Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
Legend
Components of the unit and hydronic module System components
1 Screen filter (particle size of 1.2 mm) 16 Pocket
O 2 Expansion tank (option) 17 Air purge
3 Relief valve O 18 Flexible connection (Option)
4 Circulating pump (single or dual) 19 Shut-off valve
5 Air purge 20 800 µm screen filter (option – mandatory in the case of a unit without hydronic
6 Water drain tap module / Included on version with hydronic module)
7 Pressure sensor 21 Pressure gauge
Note: Provides pressure information for the pump inlet (see Control manual) 22 Water flow control valve
8 Temperature probe Note: not required if hydronic module with variable speed pump
Note: Provides temperature information for the water exchanger outlet (see 23 Charging valve
Control manual) 24 Bypass valve for frost protection (if shut-off valves are closed (item 19) during
9 Temperature probe
winter)
Note: Provides temperature information for the water exchanger inlet (see
Control manual) 25 Buffer tank (if required)
10 Pressure sensor 26 Extra heaters in the tank (option): the option includes a vent on the tank +
Note: Provides pressure information for the water exchanger outlet (see Control WTOT temperature sensor at the tank outlet
manual) - - - - - Hydronic module (unit with hydronic module option)
11 Check valve (if dual-pump) NOTE:
12 Plate heat exchanger - The system must be protected against frost.
O 13 Heater or heat trace cable for frost protection (Option)
- The unit's hydronic module and the water type heat exchanger may be protected
14 Water type heat exchanger flow rate sensor (factory-fitted option) against freezing using electric heaters and heat trace
O 15 Buffer Tank Module (Option)
cables (13)
- The pressure sensors are assembled on connections without Schrader.
Depressurise and drain the system before any work.
Figure 2: Internal hydronic equipment with dual pump option and buffer tank
Legend
B Steel sleeve F Victaulic clamp
C 800 µm screen filter G Hose
D Brass connector Water outlet
E Shut-off valve Water inlet
Figure 3: Internal hydraulic equipment with dual pump option, buffer tank and extra heaters
The plate exchangers, the pipes, the buffer tank pump(s) and Unité
Unit Réseau
Water eau
system
ouvert
open
the hydronic module pumps can be damaged by frost. fermé
closed
The components of the unit (heat exchanger, pipes, hydronic
module, buffer tank module) will be protected by following the
recommendations below. Protection of the remainder of the
system is the responsibility of the installer. IMPORTANT:
The plate heat exchanger and all the components of the water Depending on the atmospheric conditions in your region, you
circuit can be protected against freezing by draining the entire need to:
machine completely, checking that there are no retention points. • Add an appropriate antifreeze solution (maximum of 45%)
If this is not possible, the plate heat exchanger and all the to protect the system down to a temperature of 10 K below
components of the water circuit can be protected against the lowest temperature likely to occur locally.
freezing: • For extended shut-downs, drain and add an anti-freeze
• Down to -20°C by heaters and heat trace cables (fitted as solution to the heat exchanger (use the drain valve located
an option on the exchanger and internal pipe system) at the water inlet).
supplied automatically (for units without the hydronic • To prevent corrosion due to differential aeration, if the
module) system is to be empty for more than 1 month, the heat-
• Down to -10°C for cooling only machines (without buffer transfer fluid circuit should be protected with a blanket of
tank module option) and 0°C for reversible machines, neutral gas (0.5 bar maximum). If the heat-transfer fluid
Cooling only with buffer tank via a heater on the heat does not meet the recommendations, a nitrogen blanket
exchanger supplied automatically and pump cycling (for must be applied immediately.
units with hydronic module). • At the start of the next season, refill the unit with water and
• Down to -20°C by heaters and heat trace cables (fitted as add an inhibitor.
an option on the exchanger, buffer tank module (option) • If additional equipment is added to the system, the installer
and internal pipe system) supplied automatically and pump must comply with the basic recommendations, especially
circulation (for units with the hydronic module) the minimum and maximum flow rates which must be
between the values shown in the operating limits table
Never power off the heaters for the water exchanger and the (application data).
water circuit or pump, as they will no longer be providing frost • If frost protection is dependent on electric heaters, never
protection. deenergize the unit when frost protection is required. To
To ensure they continue to receive power, the main switch for ensure protection, the main unit disconnect switch and the
the unit or the customer's circuit and the auxiliary circuit breaker auxiliary heater protection circuit breaker must be closed
for the heaters must be left closed (see the wiring diagram for (see wiring diagram to locate these components). If it is not
the location of these components). to be used in freezing conditions, or during a prolonged
To protect units with a hydronic module from freezing, water must period without power (whether or not this is scheduled), the
be circulated in the water circuit by the pump, which is activated water exchanger and external pipes must be drained
at regular intervals. If the system is isolated by a valve, it is immediately
imperative to install a bypass as indicated below. • In case of prolonged non-usage, the hydraulic circuits must
be protected by circulating a passivating solution. (Consult
a specialist).
• The exchanger temperature sensors are an essential frost
protection element: if piping trace heaters are used, ensure
the external heaters do not affect the measurements
provided by these sensors.
• If auxiliary equipment is installed in the system, the installer
must ensure that the resultant flow rates are still within the
minimum and maximum values indicated in the operating
limits table (application data).
8.6 - Extra electrical heaters field-installed or integrated into the buffer tank (depending on
the option chosen)
To compensate for the reduction in the heat pump's output at low ambient temperatures, which changes significantly as shown in
the graph below, it is possible to install on the water outlet auxiliary electrical heaters of sufficient power to offset the heat pump
capacity drop.
These heaters can be controlled via the dedicated option.
Up to four outputs are available to control the contactors (not supplied on the plate for the option to be field installed) on the heaters,
thereby enabling gradual compensation of the reduction in the heat pump output.
These outputs are configurable to allow for two, three or four stages as required (depending on the option chosen). The last stage
is only activated in case of shut-down due to a fault on the heat pump (emergency).
It is possible to choose an extra heater option to be field installed or an option which directly integrates the heaters in the buffer
tank. In the case of this second option, three extra heater outputs are available: 16 kW / 31 kW / 45 kW.
The graph below shows an example of operation with additional heaters, where the power of the four heaters equals the capacity
of the heat pump at an outdoor air temperature of 7 °C.
Example: Unit with specified nominal flow rate of 3.7 l/s 9.2 - Units with hydronic module and
fixed-speed pump (only for negative cold
applications)
See the paragraph on "Units without hydronic module"
Hydraulic circuit cleaning procedure
Pressure drop , kPa
9.3 - Units with hydronic module and variable Procedure for controlling the pressure differential setpoint
speed pump – Pressure differential control Once the circuit is cleaned, place the water circuit in the
The system flow rate has not been set to a nominal value. configuration for which the unit selection was performed
(generally, this will be all valves open and all cooling coils active)
The flow rate will be adjusted, by varying the pump speed,
to maintain a system pressure differential value defined by the Read the value of the flow on the user interface and compare it
user. with the theoretical value of the range:
• If the flow rate read is greater than the preset value, reduce
This is checked by the pressure sensor at the water exchanger
the pressure differential setpoint on the user interface to
outlet (item 10 on the main water circuit diagram).
reduce the flow rate value;
The system calculates the measured pressure difference, • If the value read is lower than the preset value, increase
compares it with the setpoint value set by the user and then the pressure differential setpoint on the user interface to
modulates the pump speed module, resulting in: increase the flow rate value
• an increase in the flow rate if the measurement is below
Repeat until the unit's nominal flow rate at the required operation
the setpoint,
point is achieved.
• a decrease in the flow rate if the measurement exceeds the
setpoint. Stop the forced operation of the pump and proceed to the
configuration of the unit for the required control mode. Modify
This modulation is limited only by the maximum and minimum
the control parameters:
flow rates for the unit and by the maximum and minimum
• Set water flow control to ‘pressure differential’
allowable pump speeds.
• Set the value of the required pressure differential.
The maintained pressure difference value may, in certain cases,
The unit's default factory configuration is the maximum speed
differ from the setpoint value:
(frequency: 50 Hz).
• if the setpoint value is too high (obtained for a flow rate
higher than the maximum value or a frequency greater than NOTE:
the maximum value), the system will stop once it reaches If during adjustment, the low or high frequency limits are reached
the maximum flow rate or maximum frequency, which will before reaching the specified flow rate, keep the pressure
result in a pressure difference below the setpoint, differential value at its lower or higher limit as the control
• if the setpoint value is too low (obtained for a flow rate lower parameter value.
than the minimum value or a frequency less than the If the user knows in advance the pressure differential value at
minimum value), the system will stop once it reaches the the unit outlet to be maintained, this value can be entered directly
minimum flow rate or minimum frequency, which will result as data to be declared. You should not, however, omit the water
in a pressure difference greater than the setpoint. circuit cleaning sequence
Contact the manufacturer's service department to implement the
procedures described below.
Hydraulic circuit cleaning procedure
Before proceeding, it is advisable to remove any possible
contamination from the water circuit.
• Start-up the system pump by using the forced start
command.
• Control the frequency to the maximum value to generate
a higher flow.
• If there is a ‘‘Maximum flow exceeded’’ alarm, reduce the
frequency until an acceptable value is reached.
• Read the value of the flow on the user interface.
• Let the pump run for 2 hours continuously to clean up the
system's hydraulic circuit (presence of contaminating
solids).
• Perform another reading of the flow and compare this value
with the initial value. A reducing value of the flow indicates
that the filters on the system need to be removed and
cleaned. In this case, close the shut-off valves on the water
inlet and outlet (item 19) and remove the filters (items 20
and 1) after draining the hydronic part of the unit (items 6).
• Remove the air from the circuit (items 5 and 17).
• Repeat until all fouling is removed from the filter
9.4 - Units with hydronic module and variable speed pump – Temperature differential control
The system flow rate has not been set to a nominal value.
The flow rate will be adjusted, by varying the pump speed, to maintain a heat exchanger temperature differential value defined by
the user.
This is checked by the temperature sensors at the water exchanger inlet and outlet (items 8 and 9 on the main water circuit diagram).
The system reads the measured temperature values, calculates the corresponding Delta T, compares it with the setpoint value set
by the user and then modulates the pump speed.
• This results in an increase in the flow rate if the Delta T° exceeds the setpoint.
• This results in a decrease in the flow rate if the Delta T° is less than the setpoint.
This modulation is limited only by the maximum and minimum flow rates for the unit and by the maximum and minimum allowable
pump speeds.
The resulting Delta T° may, in certain cases, differ from the setpoint value:
• if the setpoint value is too high (obtained for a flow rate lower than the minimum value or a frequency less than the minimum
value), the system will stop once it reaches the minimum flow rate or minimum frequency, which will result in a temperature
delta below the setpoint,
• if the setpoint value is too low (obtained for a flow rate higher than the maximum value or a frequency greater than the maximum
value), the system will stop once it reaches the maximum flow rate or maximum frequency, which will result in a Delta T°
above the setpoint.
Contact the manufacturer's service department to implement the procedures described below.
Hydraulic circuit cleaning procedure
Refer to the water circuit cleaning procedure.
Procedure for adjusting the Delta T° setpoint
Once the circuit is cleaned, stop the forced start of the pump and proceed to the configuration of the unit for the required control
mode.
Modify the control parameters:
• Set water flow control to ‘temperature differential’
• Set the value of the required differential temperature.
The unit's default configuration is at the fixed speed (50 Hz)
200
120
180
160
100
140
80 120
100
60
80
60
40
40
1 2 3 4 5 1 2 3 4 5
20 20
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 0 1 2 3 4 5 6 7 8 9 10
210 210
Pressure head, kPa
Pressure head, kPa
190 190
170 170
150 150
130 130
110 110
90 90
70 70
B C D E F G B C DE F
50 50
0 1 2 3 4 5 6 0 1 2 3 4 5 6 7 8 9 10
230 230
210 210
Pressure head, kPa
Pressure head, kPa
190 190
170 170
150 150
130 130
110 110
90 90
70 70
B C D E F B C D E F
50 50
0 1 2 3 4 5 6 0 1 2 3 4 5 6 7 8 9 10
ΔP [kPa]
Qv [m3/h]
LD/ILD 150-300 LD/ILD 302-600
Qv [m3/h]
LD/ILD 150-602
Compressors
Ensure that each compressor is rotating in the correct direction,
checking that the discharge temperature rises quickly, the HP
increases and the LP drops. If it is rotating in the wrong direction,
the electric power supply is incorrectly wired (reversed phases).
To ensure rotation in the correct direction, swap the two power
supply phases.
- Check the compressor discharge temperature with a contact
sensor
- Check the input current; it should be normal
- Check all safety devices to make sure they operate correctly
Hydraulics
The exact total drop in system pressure will not be known at
commissioning. It will therefore be necessary to adjust the flow
of water with the control valve until the desired nominal rate is
obtained.
By causing the pressure in the water system to drop, this control
valve aligns the system pressure/flow curve with that of the pump
so that the nominal flow rate corresponding to the desired
operating point is obtained. The pressure drop in the water
exchanger (read using the pressure gauge placed on the
exchanger inlet and outlet) is the reference to be used to check
and adjust the nominal flow rate of the system.
Follow the procedure described below:
- Open the control valve completely
- Let the pump run for two hours to flush out any solid particles
in the circuit
- Read the pressure drop in the water exchanger when the
pump is turned on and then two hours afterwards
- If the pressure drop has decreased, this means that the screen
filter is clogged. It must be removed and cleaned
- Repeat until the filter is completely clean
- If the system pressure drops are above the available static
pressure delivered by the pump, the resulting water flow rate
will be low and the difference in temperature between the
exchanger inlet and outlet will be too high. This is why pressure
drops must be minimised. Check that this difference is within
the values on the curve (refer to section "Water type heat
exchanger min. water volume and flow rate")
- If the extra heater option is present in the water tank, check
that the tank is completely filled so that all the heaters are
immersed, check that the immersion heaters are operating
correctly, and that the safety thermostats are triggered
(present on each immersion heater).
Refrigerant charge
Each unit is shipped with an exact charge of refrigerant.
11.4 - Fans
Each fan motor is equipped with a high-performance impeller made from a recyclable composite material. The motors are
three-phase, with permanently lubricated bearings and class F insulation (rated IP55).
For more detailed information, refer to the requirements in the table below according to Regulation No. 327/2011 implementing
Directive 2009/125/EC with regard to eco-design requirements for motor-driven fans with an electric input power of between 125 W
and 500 kW.
Regulation 2019/1781 repealing regulation 640/2009, governs the requirements relating to ecodesign applicable to electric motors
and to speed regulators in accordance with the directive 2009/125/EC. Our fan motor assemblies are excluded from this:
Corrosion protection, Fins made of pre-treated aluminium (polyurethane Improved corrosion resistance, recommended for
NO •
traditional coils and epoxy) moderate marine and urban environments
Medium-temperature brine Low temperature chilled water production down to Covers specific applications such as ice storage
• •
solution 0 °C with ethylene glycol and propylene glycol. and industrial processes
Low temperature chilled water production down to
Low-temperature brine Covers specific applications such as ice storage
-15°C with ethylene glycol and -12°C with • •
solution and industrial processes
propylene glycol.
Unit equipped with specifics variable-speed fans :
XtraFans (See specific chapter for maximum Ducted fan discharge, optimised temperature
XtraFan available static pressure according to size), each control, based on the operating conditions and • •
fan equipped with a connection flange & sleeves system characteristics
allowing the connection to the ducting system.
Xtra Low Noise Acoustic compressor enclosure and low-speed fans Noise emission reduction at reduced fan speed • •
Protection grilles Metallic protection grilles Coil protection against possible impact • •
Soft starter Electronic starter on each compressor Reduced start-up current • •
EC fans for winter operation EC fan control via integrated Electronic
Stable unit operation when the air temperature is
cooling mode down to Commutated motors. One EC fan on each • NO
between 0°C and -20°C
-20°C refrigerant circuit
All year round cooling Stable unit operation when the air temperature is
Fanspeed control via frequency converter NO •
operation down to -20°C between 0°C and -20°C
Hydronic module frost Hydraulic module frost protection at low outside
Electric heater on the hydraulic module • •
protection temperatures down to -20°C
Electric heater on the water exchanger hydraulic Water exchanger and hydraulic module frost
Exchanger & hydraulic frost ALL with water ALL with water
module and optional expansion tank & water buffer protection between 0°C and -20°C outside air
protection buffer tank buffer tank
tank temperature
Production of free high-temperature hot-water
Unit equipped with one desuperheater on each
Partial heat recovery simultaneously with chilled water production (or hot • •
refrigerant circuit.
water for Heat pump)
Unit equipped with supplementary water outlet
temperature sensor kit (to be field installed) Optimised operation of two units connected in
Master/slave operation • •
allowing master/slave operation of two units parallel operation with operating time equalisation
connected in parallel
Single high-pressure water pump, water filter,
All sizes,
electronic water flow control, pressure transducers.
HP single-pump hydraulic low-temperature
For more details, refer to the dedicated chapter Easy and fast installation (plug & play) •
module brine solution
(expansion tank not included. Option with built-in
application only
safety hydraulic components available.)
Dual high-pressure water pump, water filter,
All sizes,
electronic water flow control, pressure transducers.
HP dual-pump hydraulic low-temperature
For more details, refer to the dedicated chapter Easy and fast installation (plug & play) •
module brine solution
(expansion tank not included Option with built-in
application only
safety hydraulic components available)
Single low-pressure water pump, water filter,
electronic water flow control, pressure transducers.
LP single-pump hydraulic
For more details, refer to the dedicated chapter Easy and fast installation (plug & play) NO •
module
(expansion tank not included Option with built-in
safety hydraulic components available)
Dual low-pressure water pump, water filter,
electronic water flow control, pressure transducers.
LP dual-pump hydraulic
For more details, refer to the dedicated chapter Easy and fast installation (plug & play) NO •
module
(expansion tank not included Option with built-in
safety hydraulic components available)
Single high-pressure water pump with variable
speed drive (VSD), water filter, electronic water
Easy and fast installation (plug & play), significant
flow control, pressure transducers. Multiple
HP evap. variable-speed pumping energy cost savings (more than
possibilities of water flow control. For more details, • •
single-pump two-thirds), tighter water flow control, improved
refer to the dedicated chapter (expansion tank not
system reliability
included Option with built-in safety hydraulic
components available)
Dual high-pressure water pump with variable speed
drive (VSD), pressure transducers. Multiple Easy and fast installation (plug & play), significant
HP VSD dual-pump possibilities of water flow control. For more details, pumping energy cost savings (more than
• •
hydraulic mod. refer to the dedicated chapter (expansion tank not two-thirds), tighter water flow control, improved
included Option with built-in safety hydraulic system reliability
components available)
Bi-directional communication board complying with Connects the unit by communication bus to
Lon gateway • •
Lon Talk protocol a building management system
12.2.3.1 Physical properties of units with partial heat recovery using desuperheaters
LD partial heat recovery mode 150 180 200 240 260 300 360 390 450 520 600
Standard unit kg 436 445 454 470 468490 785 796 827 867 899
Unit + High pressure single pump option kg 478 486 496 512 510532 852 863 898 941 973
Unit + High pressure dual-pump option kg 504 512 522 537 536558 897 908 947 978 1010
Unit + high pressure single pump + Water buffer tank module option kg 874 882 892 908 906928 1285 1296 1331 1374 1406
Unit + high pressure dual-pump + Water buffer tank module option kg 900 908 918 933 932954 1330 1341 1380 1411 1443
Refrigerant with MCHE coils R410A
Circuit A kg 4,7 5,3 5,9 6,7 6,2 7,3 10,7 10,8 11,4 6,5 7,4
Circuit B kg - - - - - - - - - 6,5 7,4
Air heat exchanger "Micro Channel Heat Exchanger" (Micro-Channel) coils made entirely from aluminium
Desuperheater on circuits A and B Plate heat exchanger
Water volume l 0,549 0,549 0,549 0,549 0,732 0,732 0,976 0,976 0,976 0,732 0,732
Water volume l - - - - - - - - - 0,732 0,732
Max. water-side operating pressure without hydronic module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Water connections Cylindrical male gas thread
Connections in 1 1 1 1 1 1 1 1 1 1 1
Outside diameter mm 42 42 42 42 42 42 42 42 42 42 42
(1) Weights given as a guide.
ILD partial heat recovery mode 150 180 200 240 260 300 302 360 390 450 520 600
LD/ILD150 to LD/ILD300
Without Buffer Tank module
B
C
B C
NOTES :
A Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an
installation. For the location of fixing points, weight distribution and coordinates of the centre of gravity refer to the
certified dimensional drawings.
B The unit must be installed level (less than 2 mm per metre deviation in both axes).
NOTES :
A Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on request, when designing an
installation. For the location of fixing points, weight distribution and coordinates of the centre of gravity refer to the
certified dimensional drawings.
B The unit must be installed level (less than 2 mm per metre deviation in both axes).
12.2.3.2 Installation and operation of the heat recovery with partial heat recovery option
The units with the desuperheater option are supplied with one plate heat exchanger per refrigerant circuit.
When installing the unit, the heat recovery plate heat exchangers must be insulated and protected against frost if required.
Refer to the main diagram below for the main components or functions associated with a unit with desuperheater option in a standard
system.
Legend:
Components of the AQUACIAT LD/ILD unit System components (installation example)
1- Evaporator 20- Pump (hydraulic circuit of the desuperheater loop)
2- Compressor 21- Shut-off valve
3- Desuperheater 22- Desuperheater water flow rate control and balancing valve
4- Air condenser (coils) 23- Accessory for limitation of damage in the event of a fire (valve)
5- Expansion valve (EXV) 24- Expansion tank
6- Accessory for limitation of damage in the event of a fire (valve) 25- Charge or drain valve
7- Electric heater for protecting the desuperheater from freezing (not provided) 26- Air bleed
8- Insulation for the desuperheater (not supplied) 27- Coil heat exchanger or plate heat exchanger
9- Electrical box for the unit 28- Pressure gauge
10- NA 29- Flow rate sensor
11- Water inlet on the desuperheater 30- Pump (sanitary hot water circuit)
12- Water outlet on the desuperheater 31- Three-way valves + controller
13- Evaporator water inlet 32- Filter to protect the pump and the desuperheaters
14- Evaporator water outlet 33- Municipal water inlet
15- Unit with desuperheater option without hydronic module 34- Domestic hot water outlet
16- System heat load
17- Boundary between the AQUACIAT LD/ILD unit
AQUACIAT LD
AQUACIAT ILD
C Slave unit
Water inlet
Water outlet
Water pumps for each unit (included as standard in units with hydronic
module)
Additional sensors for the control of the water outlet to be connected
T
on channel 1 of the slave boards of each Master and Slave unit
Communication bus
Non-return valve
12.2.5 - Low temperature / Very low temperature This value will be used to define the following limits:
glycol/water mix options 1. Evaporator antifreeze protection.
This option enables glycol/water mix production down to 0°C 2. Low-pressure protection.
(low temperature glycol/water mix option) / -15°C (very low It is recommended that a low or very low temperature installation
temperature glycol/water mix option) be commissioned by the manufacturer.
The unit is equipped with a suction tube isolation device (for very For information, for the different antifreezes used in our
low temperature glycol/water mix only) and frequency inverters laboratory, the protection values given by our supplier are as
on the ventilation. follows (these values may change depending on the suppliers):
The operating range depends on the suction pressure, which
itself depends on: Freezing point, °C Freezing point, °C
% glycol mass
• the glycol type, ethylene glycol propylene glycol
• its concentration, 10 -3.8 -2.6
• the flow rate, 15 -6.1 -4.3
• the temperature of the glycol solution, 20 -8.8 -6.6
• the condensation pressure (ambient temperature). 25 -11.8 -9.6
Example: for operation with 45% ethylene glycol and brine 30 -15.2 -13
temperature -15°C (with -10°C at the inlet), the maximum 35 -19.1 -16.7
operating ambient temperature will be approximately 33°C.
40 -23.6 -20.7
Operating range 45 -29 -25.3
with ethylene glycol at 45% For example, depending on the table above, if an ethylene glycol
mass concentration measured in the loop is 35%, the value of
55
-19.1°C must be entered in the software.
It is vital to perform a (minimum) annual inspection of the glycol
45
level and adjust the controller's frost protection value to the
measured level.
35 This procedure must be systematic when topping up with water
or antifreeze solution.
Ambient temperature (°C)
5 0
Minimum protection temperature,
-5
-5
-10
-15
-15
°C
-25 -20
B Fan motor access hatches (allow for a 700 x 700 mm hatch) for each single
or dual duct
C Connection bellows or sleeve
12.2.6.3 Rules applicable to units within an air ductwork Xtrafan ILD option
system
Cooling mode
Make sure that the suction or blowing ports cannot be
inadvertently obstructed by fitting panels (low return for example,
or when doors or other parts are opened). ILD 150-200/ILD 302-450
Duct pressure Fan rotation Power input Cooling capacity
12.2.6.4 Correction factors for Xtra Fan machine performances drop speed (rps) variation variation
0 12 0,943 1,019
The cooling/heating capacities are provided for an available
50 13,33 0,962 1,012
pressure of 160 Pa.
100 14,66 0,980 1,006
To calculate the performances with other pressure drops,
130 15,46 0,990 1,003
you can use the coefficients in the table below.
160 16,26 1,000 1,000
Xtrafan LD option 200 17,31 1,012 0,998
240 18,36 1,023 0,996
LD 150-240/LD 360-450
ILD 240-300/ILD 520-600
Duct pressure Fan rotation Power input Cooling capacity
drop speed (rps) variation variation Duct pressure Fan rotation Power input Cooling capacity
0 12 0,943 1,019 drop speed (rps) variation variation
50 13,33 0,962 1,012 0 15,83 0,929 1,018
100 14,66 0,98 1,006 50 16,81 0,944 1,016
130 15,46 0,99 1,003 100 17,78 0,964 1,014
160 16,26 1 1 130 18,36 0,978 1,011
200 17,31 1,012 0,998 160 18,36 1,000 1,000
240 18,36 1,023 0,996 180 18,36 1,019 0,991
LD/ILD 302 - 600 water filter option LD/ILD 150 - 600 connection hoses option
NOTE: The hoses must have a min. straight length of 205 mm,
LD/ILD 150 - 300 water filter and a min. curve radius of 490 mm
+ screw-in connections option
Legend:
B Steel sleeve
D Brass connector
E Shut-off valve
F Victaulic clamp
G Hose
Water inlet
Water outlet
LD/ILD 150 - 300 water filter LD/ILD 302 - 600 water filter + connection hoses
+ connection hoses option + screw-in connections option
NOTE: The hoses must have a min. straight length of 205 mm, NOTE: The hoses must have a min. straight length of 205 mm,
and a min. curve radius of 490 mm and a min. curve radius of 490 mm
LD/ILD 302 - 600 water filter LD/ILD 150 - 600 water filter
+ connection hoses option + connection hoses option
NOTE: The hoses must have a min. straight length of 205 mm, Legend:
and a min. curve radius of 490 mm
B Steel sleeve
LD/ILD 150 - 300 water filter + connection hoses C 800 µm screen filter
+ screw-in connections option D Brass connector
E Shut-off valve
F Victaulic clamp
G Hose
Water inlet
Water outlet
NOTE: The hoses must have a min. straight length of 205 mm,
and a min. curve radius of 490 mm
12.2.8 - Pump protection and control options 12.2.9 - Unit operation with a free cooling drycooler
(optional)
The pump protection and control options give the customer
access to outlets designed for the supply and actuation of pumps
external to the machine. 12.2.9.1 - Operating principle
These outlets provide electrical protection via a thermal-magnetic The units have been designed to optimize the operation of
circuit breaker (fixed and variable speed pumps) and a control systems, using drycoolers as free cooling system (method using
switch actuated by the machine's control system (fixed speed low outdoor air temperature to chill the water of the air
pump only). conditioning system).
The protections and controls are sized based on the factory-fitted This system allows substantial energy and cost savings, which
pumps outlined in the section "Electrical data for the hydraulic is the most effective when the outdoor air temperature is low.
module". The TouchPilot control of the unit includes algorithms to permit
Proposed assembly for external variable speed pumps: constant automatic optimization of:
• drycooler fans operation
Single pump • water flow rate variation in the loop
• lcooling capacity (drycooler and chiller can operate
independently or simultaneously),
CIAT unit • valves positions depending on operating mode.
The control defines the optimal configuration considering water
setpoint value, outdoor air temperature and water loop
temperature (the control will give priority to the drycooler).
Parallel control of the fans and of the variable water flow rate of
the loop permit system operation down to -20 °C outside
temperature without any additional control.
VFD WARNING: the drycooler and chiller must both be equipped
with the Free Cooling Management option.
Chiller NO
Pump
NC
Communication bus
V2V control
Dual-pump DC free cooling
CIAT unit
Pump
12.2.9.2 - Communication to control the drycooler 12.2.9.3 - Configuration of the fans control
When the option is selected, a specific electronic board is To set the configuration corresponding to the drycooler installed
integrated in the control box of the drycooler. A communication (number of fans, control type – fixed or variable speed), please
LEN bus connected between the drycooler (board AUX1) and refer to the instructions in the TouchPilot control manual.
the chiller is needed for the overall system control. Following these parameters, the TouchPilot control will activate
This cable should be a 3 points Wago type (5 mm spacing or the adequate number of digital outputs to control the fans.
equivalent) and should be shielded. TouchPilot controls the automatic switching of all fans, based on
The board integrated in the control box of the drycooler has operating time and number of start-up, to ensure a long operating
analogue inputs for outside air temperature and drycooler leaving life of fan motors.
water temperature sensors, as well as digital outputs permitting Compatible fans configuration:
the control of the fans. • 1 to 20 fans
The option works as a system split in two parts: • fixed speed or variable speed
• fans in one 1 or 2 lines
The chiller (with free cooling option): Refer to the drycooler electrical diagram to see the fan stages
arrangement.
- Dedicated control algorithms with LEN connector to
communicate and control the drycooler
12.2.9.4 – Water valves
The drycooler (with free cooling option): The free cooling system requires 2 two-way valves (one Normally
- AUX board with the I/O Opened, one Normally Closed) or a three-way valve, not supplied
- OAT sensor to be place in outdoor zone. with the unit or the dry cooler.
- Dry Cooler Leaving Water Temperature (factory mounted)
- Water loop Temperature (to be mounted on the common pipe
before valve)
- Control & 230-V power supply for 2 two ways valve or one
three ways valve
The temperature difference between dry-cooler OAT and water
loop sensor defines if free cooling mode can be activated.
To ensure optimal efficiency and reliability of the equipment and 13.2 - Level 2 maintenance
all its functions, we recommend taking out a maintenance
This level requires specific expertise in electrical, hydraulic and
contract with the local organisation set up by your manufacturer.
mechanical systems. it is possible that this expertise may be
This contract will include regular inspections by the manufacturer’s
available locally; there may be a maintenance service, industrial
Service specialists so that any malfunction is detected and
site or specialist subcontractor in the area.
corrected quickly, ensuring that no serious damage can occur.
The manufacturer's service maintenance contract is the best The frequency of this maintenance may be monthly or annual,
way to ensure the maximum operating life for your equipment depending on the type of check.
and, through the expertise of manufacturer's qualified personnel, In these cases, the following maintenance operations are
provides the ideal way to manage your system energy recommended:
consumption effectively.
Carry out all level 1 operations, then:
The refrigeration equipment must be serviced by professionals;
however, routine checks may be carried out locally by specially- Electrical checks (annual checks):
trained technicians. See the standard EN 378-4. - At least once a year tighten the electrical connections for the
power supply circuits (see tightening torques table),
All refrigerant charging, removal and recovery operations must
- Check and tighten all control connections, if required,
be carried out by a qualified technician and with the correct
- Check the labelling of the system and instruments, re-apply
equipment for the unit. Any inappropriate handling can lead to
the missing labels if required,
uncontrolled fluid or pressure leaks.
- Remove the dust and clean the interior of the electrical boxes.
IMPORTANT: Before performing any work on the machine Be careful not to blow dust or debris into components; use
ensure it is de-energised. If a refrigerant circuit is opened, a brush and vacuum wherever possible,
it must be evacuated, recharged and tested for leaks. Before - Clean the insulators and bus bar supports (dust combined
any operation on a refrigerant circuit, it is necessary to with moisture reduces the insulation gaps and increases
evacuate the refrigerant charge from the device using current leakage between phases and from phase to ground),
a charge transfer unit. - Check the presence, condition and operation of electrical
Simple preventive maintenance will allow you to get the best protective devices,
performance from your HVAC unit: - Check the presence, condition and operation of control
- Optimisation of energy performance, components,
- Reduced electricity consumption, - Check that all heaters are operating correctly,
- Prevention of accidental component failure - Replace the fuses every 3 years or every 15000 hours
- Prevention of major time-consuming and costly work, (ageing),
- Protection of the environment. - Check that no water has penetrated into the electrical box,
There are five maintenance levels for HVAC units, as defined by - On the electrical box and for units equipped with an inverter,
the AFNOR X60-010 standard. regularly check the cleanliness of the filter media to maintain
the correct air flow.
NOTE: Any deviation from or failure to comply with
these maintenance criteria will render the guarantee Mechanical:
conditions for the refrigeration unit null and void, Check that the mounting bolts for the ventilation sub-assemblies,
and will release the manufacturer from its liability. fans, compressors and electrics box are securely tightened
Hydraulics:
13.1 - Level 1 maintenance
- When working on the water circuit, take care not to damage
These simple procedures can be carried out by the user: the adjacent air heat exchanger,
- Visual inspection for traces of oil (indicates a refrigerant leak), - Check the water connections,
- Check for leaks in the hydraulic circuit (monthly), - Check the condition of the expansion tank (presence of
- Clean the air-cooled exchangers (see the dedicated chapter), corrosion or loss of gas pressure) and replace it if required,
- Check that the protective grilles are present and in good - Drain the water circuit (see chapter “Water flow control
condition, and that the doors and covers are properly closed, procedure”),
- Check the unit's alarm report (see the control manual), - Clean the water filter (see chapter “Water flow rate control
- Verify the refrigerant charge in the liquid line sight glass, procedure”),
- Verify the chilled water temperature difference at the heat - Replace the gland packing of the pump after 20000 hours of
exchanger outlet is correct, operation and the bearings after 17500 hours,
- Check for any general signs of deterioration, - Check the operation of the low water flow safety device,
- Check the anti-corrosion coatings. - Check the condition of pipe thermal insulation,
- Check the concentration of the anti-freeze protection solution
(ethylene glycol or propylene glycol),
- Check the water flow using the heat exchanger pressure
difference,
- Check the condition of the heat transfer fluid or the water
quality,
- Check for corrosion of the steel pipe work.
- Check the level of scaling on the extra heaters (if the option
is available)
- Check that the extra heaters are operating correctly and that
the thermostat present on each immersion heater (if the option
is available) is triggered..
Tightening Tightening
Screw type Use
torque (Nm) torque (Nm)
CP sleeve compressor bracket 30 30
M8 nut BPHE mounting(1) 15 15
M10 nut Compressor stud 30 30
M16 nut Compressor mounting 30 30
Oil nut Oil equalisation line 75 75
M6 taptite screw Ventilation support 7 7
M8 taptite screw Ventilation motor mounting 13 13
M8 H screw Helix mounting 18 18
Panel screw Metal panels 4,2 4,2
H M6 screw Stauff clamp 10 10
Earth screw Compressor 2,8 2,8
13.6 - Air heat exchanger Never use a fluid with a temperature above 45°C to clean
the air heat exchangers.
We recommend that coils are inspected regularly to check the
degree of cleanliness. This depends on the environment where Correct and frequent cleaning (approximately every three
the unit is installed, in particular urban and industrial sites, and months) will prevent 2/3 of the corrosion problems. Protect
for units installed near trees that shed their leaves. the electrics box during cleaning operations.
Recommendations for maintenance and cleaning of Before any work on the frequency inverter, ensure
micro-channel coils (MCHE): that the circuit is isolated and there is no voltage
- Regularly cleaning the coil surface is essential for correct unit present (reminder: the capacitors take approximately
operation. 5 minutes to discharge once the circuit breaker has
- Eliminating contamination and removal of harmful residue will been opened). Only appropriately qualified
increase the operating life of the coils and the unit. personnel are authorised to work on the frequency
- The maintenance and cleaning procedures below are part of inverter.
the regular maintenance to increase the operating life of coils. In case of any alarm or persistent problem related to the
- Specific recommendation in case of snow: For long term frequency inverter, contact the manufacturer's service.
storage, regularly check that no snow has accumulated on
The frequency inverters fitted on the units do not require
the coil.
a dielectric test, even if being replaced: they are systematically
- Clean the surface of the coil by spraying the coil regularly and
checked before delivery. Moreover, the filtering components
uniformly from bottom to top, orienting the water jet at right
installed in the frequency inverter can falsify the measurement
angles to the surface. Do not exceed a water pressure of
and may even be damaged. If there is a need to test the insulation
6200 kPa (62 bar) or an angle of 45° related to the coil. The
of the unit components (fan motors and pumps, cables, etc.),
nozzle must be at least 300 mm away from the coil surface.
the frequency inverter must be disconnected at the power circuit.
- Clean and scrub the entire connection with a flexible Nylon,
PolyPro® or Tynex® brush and low-pressure tap water.
13.9 - Refrigerant volume
Level 1 cleaning: It is essential to run the unit in cooling mode to find out whether
- Remove all foreign objects or fragments/debris attached to the charge is correct; this is done by checking the actual
the coil surface or wedged between the chassis and the subcooling.
supports. Following a slight leak, it will be possible to feel a drop in the
- Use a low-pressure dry air jet to remove all traces of dust from refrigerant charge from the initial charge, and this will affect the
the coil. subcooling value obtained at the air-cooled exchanger outlet;
it cannot, however, be felt in heating mode.
Level 2 cleaning: IMPORTANT: it is therefore not possible to optimise the
- Carry out the level 1 cleaning operations. charge in heating mode following a leak. The unit must be
- Clean the coil using suitable products. run in cooling mode if the charge needs topping up.
Use appropriate PPE including safety glasses and/or mask,
waterproof clothes and safety gloves. It is recommended to
wear clothing that covers the whole body.
Specific products approved by the manufacturer for cleaning
coils are available from the manufacturer's spare parts
network. The use of any other product is strictly prohibited.
After the cleaning product is applied, rinsing with water is
mandatory.
IMPORTANT: Never use a pressure water spray without
a large diffuser.
Concentrated and/or rotating water jets are strictly
forbidden.
Properties of R410A
Preliminary information
Job name:............................................................................................................................................................................................
Location:..............................................................................................................................................................................................
Installing contractor:............................................................................................................................................................................
Distributor:...........................................................................................................................................................................................
Commissioning performed by:....................................................... Date: ..........................................................................................
Equipment
AQUACIATPOWER LD ST / HE model:............................................... Serial number..........................................................................
Compressors
Circuit A Circuit B
1. Model #........................................................................................ 1. Model #..............................................................................
Serial number............................................................................... Serial number.....................................................................
............................................................................................................................................................................................................
............................................................................................................................................................................................................
WARNING
Do not start the chiller if the voltage imbalance is greater than 2%. Contact your local power company for assistance.
Check pressure drop on the evaporator (without hydronic module) or ESP* (with hydronic module)
Evaporator inlet = ....................................... (kPa)
Evaporator outlet = ..................................... (kPa)
Pressure drop (Inlet - Outlet) = ................... (kPa)
WARNING
Plot the pressure drop on the evaporator flow/pressure drop curve to determine the flow rate in l/s at the nominal operating
conditions for the system.
If necessary use the control valve to adjust the flow rate to the desired value.
For units with hydronic module, the flow rate is indicated by the unit control (Consult the AQUACIAT control manual).
NOTES:
............................................................................................................................................................................................................
............................................................................................................................................................................................................
............................................................................................................................................................................................................