FIELD DEVICES – ***POSITIONERS***

Product Specifications
04.2019 PSS EVE0103 A-(en)

SRI983 Electro-Pneumatic Positioner


– Explosion Proof / Intrinsically Safe

The SRI983 Positioner is for operation of pneumatic valve actuators from control systems and electrical
controllers with electric control signals. It is used to reduce the adverse effects of valve friction, for higher thrust
and shorter positioning time.

FEATURES
• Independent adjustment of stroke range and zero • Mounting according to IEC 534, part 6 (NAMUR)
• Adjustable amplification and damping • Rotation adapter for angles up to 120 °
• Split range up to 3-fold possible • Mounting onto any linear or rotary actuator
• One version for 4-20 mA input • Explosion protection:
• Supply pressure up to 6 bar (90 psig) II 2 G Ex d and II 1 G Ex ia according to ATEX, or
explosion proof, intrinsic safety acc. to FM and
• Low vibration effect in all directions CSA, and CU TR
• EMC in accordance with the international standards
and laws (CE)

Equipment should be installed, operated, serviced, and maintained


only by qualified personnel.
No responsibility is assumed by Schneider Electric for any
consequences arising from the use of this material.
PSS EVE0103 A-(en)
Page 2 TECHNICAL DATA SRI983

TECHNICAL DATA Response characteristic1)


Input Amplification ........................... adjustable
Signal ..................................... 4-20 mA Sensitivity................................ < 0.1% F.S.
Input resistance .................... < 260 Ohm Non-linearity (terminal
Stroke range ......................... 8 to 100 mm (0.3 to 4 in) based adjustment) ................. < 1.0% F.S.
Angular range linear ............. 30 °to 120 ° Hysteresis ............................... < 0.5% F.S.
Equal percentage .................. 90 °; from 70 °linear Supply air dependency ......... < 0.3% / 0.1 bar (1.5 psi)
Temperature effect ................ < 0.5% / 10 K
Output
Output to actuator ................. 0 to 100% supply air pressure Air consumption
Supply air pressure air consumption
Supply
single acting
Supply air pressure ............... 1.4 to 6 bar (20 to 90 psig) 1.4 bar (20 psig)................... 200 ln/h ( 7.1 scfh)
Air supply ............................... according to ISO 8573-1 3.0 bar (45 psig)................... 350 ln/h (12.4 scfh)
- Solid particle size and density class 2 6.0 bar (90 psig)................... 600 ln/h (21.2 scfh)
- Oil rate class 3 double acting
- Pressure dew point 10 K under ambient temperature 1.4 bar (20 psig)................... 300 ln/h (10.6 scfh)
The use of filter regulator for air supply of positioner is 3.0 bar (45 psig)................... 500 ln/h (17.7 scfh)
strongly recommended. It reduces the air pressure to 6.0 bar (90 psig)................... 950 ln/h (33.5 scfh)
actuator’s maximum pressure and keeps it constant.
Air output
Ambient conditions Load effect 2)........................... –3 % for delivery flow
Ambient temperature ........... –40 °C (–40 °F) to ... 2 350 ln/h (83 scfh)
(see page 3) +3 % for exhausted flow
Relative humidity ................... up to 100 % 1 900 ln/h (67 scfh)
Operating conditions Capacity at max. deviation
as per IEC 654-1 ................... The device can be operated supply air pressure air output capacity
at a class Dx location 1.4 bar (20 psig)................... 2 700 ln/h ( 95 scfh)
Transport and storage 2.0 bar (30 psig)................... 3 500 ln/h (124 scfh)
temperature ........................... –40 to 80 °C(–40 to 176 °F) 4.0 bar (60 psig)................... 5 500 ln/h (194 scfh)
Protection class 6.0 bar (90 psig)................... 7 500 ln/h (265 scfh)
pneumatic part....................... IP 54, optional IP65
Materials
electrical part
ATEX .................................... IP 65 Base plate, manifold, I/P-housing,
FM+CSA ............................. NEMA 4X rotation adapter...................... Aluminum (Alloy No. 230)
finished with DD-varnish
Electromagnetic compatibility EMC Color gray or blue
Operating conditions ............. industrial environment Cover ...................................... impact resistant polyester
Immunity according to Color blue
- NAMUR recommendation . NE21 fulfilled All moving parts of
- EN61 326 ............................ fulfilled feedback system.................... 1.4305 / 1.4571
- EN 61 000-6-2 .................... fulfilled Mounting bracket ................... 1.4301
Emission according to
Weight
- EN 55 011,
Group 1, Class A................... fulfilled Single acting
- EN 61 000-6-2..................... fulfilled without gauges..................... approx. 1.5 kg (3.3 lbs)
with gauges .......................... approx. 1.7 kg (3.7 lbs)
CE marking Double acting ......................... approx. 1.7 kg (3.7 lbs)
Electromagnetic attachment kit
Compatibility .......................... 2004/108/EC for diaphragm actuators ...... approx. 0.3 kg (0.6 lbs)
Low-voltage regulation ......... not applicable for rotary actuators .............. approx. 0.5 kg (1.1 lbs)

Data measured according to VDI/VDE 2177


1) Data based on following parameters:
stroke 30 mm (1.28 in), range spring FES 628/1, feedback lever
effective length 117.5 mm (4.63 in), max. amplification,
supply air pressure 3 bar (45 psig)
2) Measured at air supply 1.4 bar (20 psig) and 50 % of signal range
PSS EVE0103 A-(en)
SRI983 CONNECTION Page 3

Connection Mounting
Pneumatic .............................. Female threads Type of mounting................... for attaching to
Q 1/4-18 NPT diaphragm actuators
acc. to DIN 45 141 acc. IEC 534-6 (NAMUR)
Electric ....................for attaching to
Line entry rotary actuators
Explosion protection Mounting orientation.............. any
acc. to ATEX Ex d........... Female threadM20 x 1.5
acc. to FM and CSA ....... Female threadQ1/2-14NPT Gauges
Note the section “Safety requirements” Indicating range
Terminals ............................ Screw terminals Internal I/P-output .................. 0 to 1.6 bar (0 to 23 psig)
Output ..................................... 0 to 10 bar (0 to 150 psig)
Error limit ................................ class 1.6

SAFETY REQUIREMENTS
Safety .................................... safety class III In the case of operation of the positioner in explosion
as per DIN EN 61010-1 / DIN IEC 61010-1 / VDE 0411 part 1 hazardous areas with an ambient temperature of more than
overvoltage category ............ 1 60 °C, it must be ensured that the connecting cable and
cable entry meet the increased thermal demands (max.
internal fuses ......................... none
ambient temperature plus 10 K).
external fuses ........................ Limitation of power supplies
Electrical connection with cable and wiring entry glands in
for fire protection has to be
accordance with special certification to explosion proof
observed due to EN 61010-1
classification EN 50 018, using suitable cable and wiring or
9.3. ff.
with conduit in accordance with special certification to
Electrical Classification 1) 2) explosion proof classification EN 50 018. A spark barrier
Type of protection “flameproof”, ATEX sealing compound must be applied directly at the point of
Type of protection ................. II 2 G Ex d IIB+H2 T6 entry.
Certificate of conformity ........ FM 14 ATEX 0022 X See Certificate of Conformity EX EVE0103 A
Ta = –40°C to +75°C
Type of protection “Intrinsically Safe”, ATEX Explosion protection according to FM
Type of protection ................. II 1 G Ex ia IICT4 IS / I, II, III / 1 / ABCDEFG / T4
Certificate of conformity ........ FM 14 ATEX 0022 X I / 0 / A Ex ia IIC/ T4
Ta = –55°C to +85°C NI / I / 2 / ABCD / T4
S / II, III / 2 / EFG T4
Type of protection “dust”, ATEX I / 2 / IIC / T4
Type of protection ................. II 2 D Ex tD A21 IP65 T85°C XP / I / 1 / BCD/ T6
Certificate of conformity ........ FM 14 ATEX 0022 X DIP / II, III / 1 / EFG / T6
Ta = –40°C to +75°C I / 1 / A Ex d IIB+H2 / T6
Type of protection “non incendive”, ATEX 21 / A Ex tD / T85°C
Type of protection ................. II 3 G Ex nA nL IIC T6 Type 4X, IP65
Certificate of conformity ........ FM 14 ATEX 0023 X
Ta = –55°C to +85°C Explosion protection according to CSA
Type of protection ................. II 3 G Ex nL IICT4 IS / I, II, III / 1 / ABCDEFG / T4
Certificate of conformity ........ FM 14 ATEX 0023 X I / 0 / Ex ia IIC/ T4
Ta = –55°C to +85°C NI / I / 2 / ABCD / T4
II, III / 2 / EFG / T4
XP / I / 1 / BCD/ T6
DIP / II, III / 1 / EFG / T6
I / 1 / Ex d IIB+H2 / T6
Type 4X, IP65

1) With appropriate order only


2) National requirements have to be observed
PSS EVE0103 A-(en)
Page 4 MODEL CODES SRI983

MODEL CODES SRI983 160419

Electro-pneumatic Positioner SRI983


Version
Single Acting ................................................................................................... -B
Double Acting ................................................................................................. -C
Input
Signal Range 4-20 mA............................................................................................... -I
Mode of Action
Increasing Input Increases Output ....................................................................................... D
Increasing Input Decreases Output ..................................................................................... R
Gauges
Without Gauges ............................................................................................................................. L
Two Built-In Gauges (bar/psi).....(a) ............................................................................................... M
Electrical Certification
II 2G Ex d IIB+H2 T6 - II 2D Ex tD A21 IP65 T85°C .............................................................................. EDZ
II 1G Ex ia IIC T4 - II 2D Ex tD A21 IP65 T85°C .................................................................................... E1Z
II 3G Ex nA nL IIC T6 - II 3G Ex nL IIC T4 ............................................................................................. E3Z
FM Approved For
IS / I, II, III / 1 / ABCDEFG / T4; I / 0 / AEx ia IIC/ T4; NI / I / 2 / ABCD / T4;
S / II, III / 2 / EFG T4; XP / I / 1 / BCD/ T6; DIP / II, III / 1 / EFG / T6;
I / 1 / AEx d IIB+H2 / T6; II,III / 1 / AEx tD / 21 / T85°C; Type 4X, IP65 ................................................. FDZ
CSA Approved For
IS / I, II, III / 1 / ABCDEFG / T4; I / 0 / Ex ia IIC / T4; NI / I / 2 / ABCD / T4;
S / II, III / 2 / EFG T4; XP / I / 1 / BCD/ T6; DIP / II, III / 1 / EFG / T6;
I /1 / Ex d IIB+H2 / T6; Type 4X, IP65 .................................................................................................... CDZ
EAC Approved For Explosion Proof and Intrinsically Safe..................................................................... EAC
Pneumatic Connection
Rear Facing NPT 1/4, Prepared For Linear Actuators ....................................................................................... N
Down Facing NPT 1/4, Prepared For Rotary Actuators ..................................................................................... Q
Options
Certificate EN 10204-2.1 - Certificate of compliance with the order............................................................................. -1
New Generation SRI983.......(b) .................................................................................................................................. -N
Protection Class IP65, made with non return valve exhaust ............................................................................. -FA
Tag No. Labeling
Stamped With Weather Resistant Color ...................................................................................................................... -G
Stainless Steel Label Fixed With Wire ......................................................................................................................... -L

(a) Only available with Version -B


(b) ALWAYS (mandatory)
PSS EVE0103 A-(en)
SRI983 MODEL CODES Page 5

MODEL CODES Accessories


Attachment Kit EBZG
For diaphragm actuators with casting yoke acc. NAMUR. (incl. standard Couple Lever) (for SRP981, SRI983, ...)............. -GN
For diaphragm actuators with pillar yoke acc. NAMUR. (incl. standard Couple lever) (for SRP981, SRI983, ...) ................. -FN
For rotary actuators, without flange, 3 drill holes 6.5 mm (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ....... -PN
For rotary actuators, without flange, 4 threads M6 (e.g. for Petras actuators) (for SRP981, SRI983, SRI986, ...)................ -NN
For rotary actuators, with flange (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ............................................ -JN
For rotary actuators acc. to VDI/VDE 3845, with shaft (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ........... -ZN
For Masoneilan type Camflex II (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ............................................. -RN
For Masoneilan type Sigma F (for SRI986, SRP981, SRI983) ............................................................................................. -SN
For Honeywell Air-O-Motor Type 05 (for SRI986, SRP981, SRI983) ................................................................................... -SA
For Masoneilan type 37/38, Fisher Elliott type 656, 667 (for SRP981, SRI983,SGE985,SMI983,SMP981) ......................... -TN
For Guide type P (for SRP981, SRI983) .............................................................................................................................. -UN
For Masoneilan type 87/88 (for SRP981, SRI983, SMP981, SMI983, SGE985) .................................................................. -EN
For Masoneilan VariPak (for SRP981, SRI983, SGE985, SMI983, SMP981) ......................................................................-MN
For IAL actuators (for SRP981, SRI983, SGE985, SMI983, SMP981) ................................................................................. -VN
Brackets VDI/VDE 3845 (A = 130mm/5.12 in; B = 50mm/1.97 in) (for SRP981, SRI983, SRI986,SGE985,...) .................... -C3
Brackets VDI/VDE 3845 (A = 80mm/3.15 in; B = 30mm/1.18 in) (for SRP981, SRI983, SRI986, SGE985,...) ..................... -C2
Brackets VDI/VDE 3845 (A = 80mm/3.15 in; B = 20mm/0.79 in) (for SRP981, SRI983, SRI986, SGE985, ...) .................... -C1

Couple Lever / Cam EBZG


Standard (a = 72 mm) (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ........................................................... -AN
Extended (a = 91 mm) (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ........................................................... -BN
Inverse equal percentage cam for rotary actuators (for SRP981, SRI983, SRI986) ............................................................. -CN

Spring Set FESG


Range-Springs (4 pc.) (for SRP981, SRI983,SRI986) ......................................................................................................... -FN
PSS EVE0103 A-(en)
Page 6 ATTACHMENT KITS SRI983

ATTACHMENT KIT FOR DIAPHRAGM ACTUATORS

A tta c h m e n t to c a s tin g y o k e A tta c h m e n t to p illa r y o k e


a c c o r d in g to IE C 5 3 4 - 6 ( N A M U R ) a c c o r d in g to IE C 5 3 4 - 6 ( N A M U R )
C o d e E B Z G -G N C o d e E B Z G -F N
2 0 1 7 2 0 ... 3 5
2 0 1 7
.7 9 ... 1 .3 8
M 8

1 .6 9
4 3
2 1

2 .1 3
2 .1 3

5 4
5 4

2 .8 0
2 .8 0

7 1
7 1

9 9
6 .8 5
1 7 4
4 9 ,5
1 .9 5

F e e d b a c k le v e r
C o d e E B Z G -A N , -F N , -G N
C o d e E B Z G - B N ( e x te n d e d v e r s io n )
2 ,5
.1 0
7 .1 7
1 8 2

6 8 3 7 2 1 4
.2 4 3 .2 7 2 .8 3 .5 5
7 ,9 + 0 ,2
.3 1 + .0 1

.7 8
2 0

1 0
.3 9
9 1 4 9 1 1 5
3 .5 8

M o u n tin g b r a c k e t
a c c o r d in g to IE C 5 3 4 - 6 ( N A M U R )
fo r C o d e E B Z G -G N , F N
9 6
3 .7 8 8 m m
in
9 4 .3 1
.3 5 4 3 .1 6
1 .6 9

2 0
C o r r ie r b o lt
3 0
1 .6 9
4 3

fo r a tta c h m e n t to v a lv e s te m
.3 5
9

.3 5
9

7 ,8 -0 ,0 5
.3 1 -.0 0 2
4 .5 7
1 1 6

M 6

1 6
2 .0 5
5 2
2 .8 0
7 1

1 0
6 5 .3 9
2 .5 6
.4 3
1 1
6 ,5
.2 6

.8 3
2 1

7 2
2 .8 3
.3 1
8

8 0
3 .1 5
PSS EVE0103 A-(en)
SRI983 ATTACHMENT KITS Page 7

ATTACHMENT KIT FOR ROTARY ACTUATORS

W ith s h a ft
( a c c o r d in g to V D I/V D E 3 8 4 5 ) H o u s in g d im e n s io n s
C o d e E B Z G -Z N A tta c h m e n t k it w ith s h a ft C o d e E B Z G - Z N
r e s p . w ith o u t fla n g e C o d e E B Z G - N N

4 3 9 5
1 .6 9 3 .7 4
1 4 1 ,5
5 .5 7

5 0 M 6
M 6 x 1 4 (2 x )
D IN 9 1 2 1 .9 7

D e ta il Z
1 4
1 .1 8
3 0

2 .5 2
.5 5

6 4
.4 7
1 2

3 .9 0
9 9
1 .1 0 + .0 2
2 8 + 0 ,5
4 ,5
.1 8

1 6 H 8
.6 3
4
.3 1
8

.1 6
6
.5 3 1 6 7
6 .5 7
1 3 ,5
.5 3

W ith o u t fla n g e
C o d e E B Z G -N N , -P N
H o u s in g d im e n s io n s
A tta c h m e n t k it w ith o u t fla n g e
C o d e E B Z G -P N
1 4 1 ,5
5 .5 7

4 3 9 5
1 .6 9 3 .7 4
4 5 0 ,2
1 .7 7 .0 1
1 .1 8

6 ,5 1 4 - 6
3 0

/
.2 6 .5 5 - .2 4
D e ta il Y 1 1
.4 3

2 .5 2
6 4
.4 7
1 ,2
.0 5

1 2

3 .9 0
9 9
2 2
.8 7
.0 1

A d a p tio n o f th e a c tu a to r d r iv e s h a ft e n d
0 ,2

a n d c o r r e c t a x ia l lo c a tio n b y c lie n t !
.5 9
1 5

1 4 ... 1 5 ,5 1 6 7
M 6
1 6 .5 5 ... .6 1 6 .5 7
.4 7
1 2

.6 3

W ith fla n g e
C o d e E B Z G -J N
1 8 1 ,5
7 .1 5

.4 7
1 2
.3 9
1 0
.0 1
0 ,2
2 .7 6

.0 1
0 ,2
7 0

2 .9 5
7 5
.2 0
5

2 .3 6
6 0

m m 6
.2 4 5 0
.1 2

4 7
3

in
1 .9 7
1 .8 5
5 4
5
6,
.3 9
1 0

2 .1 3
.2

6 3
2 .4 8
8 6
3 .3 9 R o ta tio n a n g le m a x 1 2 0 ° ; to r q u e r e q u ir e m e n t 1 4 N m
PSS EVE0103 A-(en)
Page 8 SRI983

DIMENSIONS, CONNECTIONS

1 1 1 1 0 5

8 ,8 5 8 (9 3 **)
4 .3 7
m m 4 .1 3
6 2 ,5
.3 5 2 .2 8 (3 .6 6 * * ) in 2 .4 6

4 7 ,5
1 .8 7
2 .8 3
7 2
3 .9 4
1 0 0

7 .1 7
1 8 2

.6 7
1 7
.6 7
1 7

4
2 .9 3
7 4 ,5

1 0 6 ,5
1 3 8 4 .1 9
5 .4 3

5 1 6 7 8 9

1 1
.4 3

Front view * Code M, N 1 Electrical connection, line entry


Code L 1 0 1 1 2 Screw terminals (+/–) for signal input
3 Earth connection
4 Rear facing pneumatic connections
(when using linear actuators)
5 Angled pneumatic connections
(when using rotary actuators)
6 Output II
(only on double-acting valve positioners)
7 Supply air
8 Output I
2 9 Feedback lever
10 Gauge for internal I/P-output (w)
11 Gauge for output (y)

1 * Dimensions of model with built-in gauges


** I/P converter cover removed

Schneider Electric Systems USA, Inc. Global Customer Support Copyright 2010-2019 Schneider Electric
38 Neponset Avenue Inside U.S.: 1-866-746-6477 Systems USA, Inc. All rights reserved.
Foxboro, MA 02035 Outside U.S.:1-508-549-2424
United States of America https://pasupport.schneider-electric.com **Schneider Electric is a trademark** of
http://www.schneider-electric.com Schneider Electric Systems USA, Inc., its
subsidiaries, and affiliates. All other trademarks
are the property of their respective owners.

DOKT 535 783 028


FD-PSS-PO-003-EN 0419

You might also like