ABB industrial drives
User’s guide
ACS880-01 +N5350 cooling tower drives
Any trademarks used in this manual are the property of their respective owners.
Important:
Be sure to check www.baldor.com for the latest software, firmware and drivers for your drive product. Also, you can
download the latest version of this manual in Adobe Acrobat PDF format.
NOTE: Correct counter EMF data is critcal for motor operation success. Please use the template below to record EMF
voltage from the nameplate and the serial number of your motor in case you need to reference this in the future.
Counter EMF:
Motor Serial Number:
Table of Contents
Chapter 1
Introduction
1.1 Getting Assistance from ABB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 Safety Notices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2.1 Safety in Installation and Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2.2 General Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.2.3 Safe Start-Up and Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Chapter 2
Product Familiarization
2.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2 Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2.1 Applicable Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2.2 CE Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2.3 UL Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.3 Usage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.4 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.4.1 Layout (IP21, UL Type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.4.2 Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.5 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.5.1 Main Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.5.2 Overview of Power and Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.5.3 External Control Connection Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.6 Type Designation Label. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2.7 Type Designation Key. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Chapter 3
Ratings
3.1 Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2 Losses, Cooling Data and Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Chapter 4
Terminal Specifications
4.1 Power Wire Gauge Range Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.2 Power Tightening Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.3 Control Wire Gauge and Tightening Torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Chapter 5
Power Wiring
5.1 Grounding the Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2 Incoming Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.3 Input Impedance and Surge Suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.4 Wire Sizing and Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5.5 Motor Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5.2.1 Protecting the Motor Insulation and Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5.2.2 Requirements Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
3AXD50000011888 i
Chapter 6
Control Wiring
6.1 Motor Thermostat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.2 Digital Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.2.1 External Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.2.2 Other Digital Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.3 Analog Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.3.1 Analog Input 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.4 ACS880+N5350 Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6.5 ACS880+N5350 Analog Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Chapter 7
Applying Power
7.1 Select the Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2 Ensure the Cooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.3 Protect the Drive and Input Power Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.4 Check the Insulation of the Input and Motor Cables and the Motor . . . . . . . . . . . . . . . . . . . . 7-1
7.5 Connect the Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.6 Connect the Control Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.7 Default I/O Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.8 UL Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Chapter 8
Keypad and Programming
8.1 Installation and Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1.1 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1.2 First Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.2 Control Panel Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.2.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.2.2 Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
8.2.2.1 Left Softkey. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
8.2.2.2 Right Softkey. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.2.2.3 Arrow Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.2.2.4 Help. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.2.2.5 Start and Stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.2.2.6 Loc/Rem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.2.2.7 Key Shortcuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.2.3 Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8.2.4 USB Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8.2.5 RJ-45 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8.2.6 Type Code Label. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8.2.7 Battery Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8.3 Local Control vs. External Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
8.3.1 Local Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
8.3.2 External Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
ii 3AXD50000011888
8.4 Basic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
8.4.1 User Interface Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
8.4.2 Control Panel Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
8.4.2.1 Navigation Memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
8.4.3 Home View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
8.4.3.1 Navigating in Home View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
8.4.4 Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
8.4.5 Common User Tasks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
8.4.5.1 Basic Operation of the Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
8.4.5.2 Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
8.4.5.3 System Information and Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
8.4.5.4 Faults and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
8.4.5.5 Basic Settings and Assistants. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
Chapter 9
Operating Modes
9.1 2Wire Operating Mode (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.2 3Wire Operating Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9.3 Process Operating Control Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
9.4 Fieldbus Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
Chapter 10
Additional Setup
10.1 Trickle Current Heating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
10.1.1 Parameter Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
10.1.2 CTDD Assistant Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
10.2 Critical Speed Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
10.3 De-Ice Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
10.3.1 De-Ice Parameter Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
10.3.2 CTDD Assistant Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
10.4 Advanced Drive Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
10.4.1 Access Levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
10.4.2 Access Level Flow Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
10.4.3 Access Level Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
Chapter 11
Example Connection Diagrams
11.1 ACS880+N5350 2Wire Operating Mode Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
11.1.1 Manual Motor Disconnect Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
11.2 ACS880+N5350 3Wire Operating Mode Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
11.2.1 Manual Motor Disconnect Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
11.3 Motor Contactor or Shorting Contactor Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
11.3.1 Manual Motor Disconnect Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
11.3.2 Shorting Contactor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
3AXD50000011888 iii
Chapter 12
Startup Assistant & Parameters
12.1 Start-Up Assistant Guide for ACS880+N5350. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.1.1 First Time Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.1.2 Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-9
12.2 Level 1 Parameters (Advanced Prog, Level 1 Blocks) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-16
Chapter 13
Troubleshooting
13.1 Warnings and Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.1.1 Pure Events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.1.2 Editable Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.2 Warning/Fault History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.2.1 Event Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.2.2 Auxiliary Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.2.3 Parameters that Contain Warning/Fault Information. . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.3 Warning Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
13.4 Fault Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-10
Appendix A
Technical Specifications
A.1 ACS880+N5350 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
A.2 Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
A.2.1 Ambient Temperature Derating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
A.2.2 Altitude Derating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
A.2.3 Low Noise Control Derating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Appendix B
Dimensions
B.1 Dimensions, Weights and Free Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Appendix C
CE Guidelines
C.1 Applicable Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
C.2 CE Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
C.2.1 Compliance with the European Low Voltage Directive. . . . . . . . . . . . . . . . . . . . . . . C-1
C.2.2 Compliance with the European EMC Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
C.2.3 Compliance with the European RoHS Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
C.2.4 Compliance with the European Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . C-1
C.3 Compliance with the EN 61800-3:2004. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
C.3.1 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
C.3.2 Category C2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
C.3.3 Category C3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
C.3.4 Category C4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
C.4 UL Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
C.4.1 UL Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
C.4.2 CSA Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-6
C.4.3 “C-tick”Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-6
C.5 GOST R Certificate of Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-6
C.6 Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-6
iv 3AXD50000011888
Appendix D
Mechanical Installation
D.1 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
D.2 Examining the Installation Site. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
D.3 Necessary Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
D.4 Moving the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
D.5 Unpacking and Examining the Delivery (Frames R1 to R5). . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
D.5.1 Frame R5 Cable Entry Box (IP21, UL Type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-3
D.6 Unpacking and Examining the Delivery (Frames R6 to R9) . . . . . . . . . . . . . . . . . . . . . . . . . . . D-4
D.6.1 Frame R6 Cable Entry Box (IP21, UL Type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-5
D.6.2 Frame R7 Cable Entry Box (IP21, UL Type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-6
D.6.3 Frame R8 Cable Entry Box (IP21, UL Type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-7
D.6.4 Frame R9 Cable Entry Box (IP21, UL Type 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-8
D.7 Installing the Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-9
D.7.1 Frames R1 to R4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-9
D.7.2 Frames R4 to R7 (UL Type 12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-10
D.7.3 Frames R5 to R9 without Vibration Dampers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-10
D.8 Cabinet Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-12
3AXD50000011888 v
vi 3AXD50000011888
Chapter 1
Introduction
This manual provides information needed for planning the installation, start-up, operating and servicing the ACS880+N5350
Cooling Tower Drive. The +N5350 control is designed specifically for Baldor Interior Permanent Magnet Cooling Tower Motor
Control. Control is intended for operating cooling tower fans through a 10:1 variable speed range as well as providing torque
control to minimize mechanical stress on the system.
The information in this users guide supports Cooling Tower Drive Firmware V2.01 and ACS880 Drive Firmware V2.3.
This manual is a quick start guide and contains information on:
- Safety Instructions
- Installation and Wiring of the ACS880+N5350
- Programming the drive
- Reference to related manuals
The reader is expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic
symbols.
The information supplied in this guide is intended to provide abbreviated information commonly needed to install and
commission the ACS880+N5350 for Cooling Tower Applications. For complete details please reference the full Hardware
and Software Manuals on the enclosed CD and available on www.abb.com.
1.1 Getting Assistance from ABB
For technical assistance, contact your local ABB representative. Contact phone numbers are located on the inside back
cover of this guide. Before calling, review the troubleshooting section later in this guide. You will be asked for the drive
model number or catalog number that is located on the nameplate along with the drive serial number.
1.2 Safety Notices
This chapter contains the safety instructions which you must follow when installing, operating and servicing the drive. If
ignored, physical injury or death may follow, or damage may occur to the drive, motor or driven equipment. Read the safety
instructions before you work on the unit.
USE of WARNINGS:
Warnings caution you about conditions which can result in serious injury or death and/or damage to the equipment and
advise on how to avoid the danger. The following warning symbols are used in this manual:
Electricity warning warns of hazards from electricity which can cause physical injury and/or
damage to the equipment.
General warning warns about conditions, other than those caused by electricity, which can result
in physical injury and/or damage to the equipment.
Electrostatic sensitive devices warning warns of electrostatic discharge which can damage the
equipment.
1.2.1 Safety in Installation and Maintenance
Electrical Safety -These warnings are intended for all who work on the drive, motor cable or motor.
WARNING: Ignoring the following instructions can cause physical injury or death, or damage to the equipment:
• Only qualified electricians are allowed to install and maintain the drive.
• Never work on the drive, motor cable or motor when main power is applied. After disconnecting the input power, always
wait for 5 minutes to let the intermediate circuit capacitors discharge before you start working on the drive, motor or motor
cable.
Always ensure by measuring with a multimeter (impedance at least 1Mohm) that:
• voltage between drive input phases L1, L2 and L3 and the frame is close to 0V.
• voltage between terminals UDC+ and UDC- and the frame is close to 0V.
• Do not work on the control cables when power is applied to the drive or to the external control circuits. Externally supplied
control circuits may cause dangerous voltages inside the drive even when the main power on the drive is switched off.
3AXD50000011888 Introduction 1-1
• Do not make any insulation or voltage withstand tests on the drive.
• Do not connect the drive to a voltage higher than what is marked on the type designation label. Higher voltage can
activate the brake chopper and lead to brake resistor overload, or activate the overvoltage controller what can lead to
motor rushing to maximum speed.
Note:
• The motor cable terminals on the drive are at a dangerously high voltage when the input power is on, regardless of
whether the motor is running or not.
• The DC terminals (UDC+, UDC-) carry a dangerous DC voltage (over 500V) when internally connected to the intermediate
DC circuit.
• Depending on the external wiring, dangerous voltages (115V, 220V or 230V) may be present on the terminals of relay
outputs (XRO1, XRO2 and XRO3).
• The Safe torque off function does not remove the voltage from the main and auxiliary circuits. The function is ineffective
against deliberate sabotage or misuse.
Grounding - These instructions are intended for all who are responsible for the grounding of the drive.
WARNING: Ignoring the following instructions can cause physical injury or death, or damage to the
equipment:
• Ground the drive, motor and adjoining equipment to ensure personnel safety in all circumstances, and to reduce
electromagnetic emission and interference.
• Make sure that grounding conductors are adequately sized as required by safety regulations.
• In a multiple-drive installation, connect each drive separately to protective earth (PE).
• Where EMC emissions must be minimized, make a 360° high frequency grounding of cable entries in order to suppress
electromagnetic disturbances. In addition, connect the cable shields to protective earth (PE) in order to meet safety
regulations.
• Do not install a drive with EMC filter option +E200 or +E202 on an ungrounded power system or a high-resistance-
grounded (over 30ohms) power system.
Note:
• Power cable shields are suitable for equipment grounding conductors only when adequately sized to meet safety
regulations.
• Standard EN 61800-5-1 (section 4.3.5.5.2.) requires that as the normal touch current of the drive is higher than 3.5mA AC
or 10mA DC, you must use a fixed protective earth connection and
• a cross-section of the protective earthing conductor of at least 10 mm2 Cu or 16 mm2 Al,
or
• automatic disconnection of the supply in case of discontinuity of the protective earthing conductor,
or
• a second protective earthing conductor of the same cross-sectional area as the original protective earthing conductor.
Permanent Magnet Motor Drives - These are additional warnings concerning permanent magnet motor drives.
WARNING: Ignoring the following instructions can cause physical injury or death, or damage to the equipment:
• Do not work on the drive when the permanent magnet motor is rotating. Also, when the supply power is switched off and
the inverter is stopped, a rotating permanent magnet motor feeds power to the intermediate circuit of the drive and the
supply connections become live.
1-2 Introduction 3AXD50000011888
Before installation and maintenance work on the drive:
• Stop the motor.
• Ensure that there is no voltage on the drive power terminals according to step 1 or 2, or if possible, according to the both
steps.
1. Disconnect the motor from the drive with a safety switch or by other means. Check by measuring that there is no
voltage present on the drive input or output terminals (L1, L2, L3, U/T1, V/T2, W/T3, UDC+, UDC-).
2. Stray wind currents can rotate the motor and generate electric potentials. Ensure that the motor is not rotating or is
disconnected from the drive during work. Shorting and isolation contactors can be used to short the motor leads and
isolate the drive from the motor.
1.2.2 General Safety
These instructions are intended for all who install and service the drive.
WARNING: Ignoring the following instructions can cause physical injury or death, or damage to the equipment:
• Handle the unit carefully.
• Frame sizes R6 to R9: Lift the drive using the lifting eyes of the unit. Do not tilt the drive. The drive is heavy and its center
of gravity is high. An overturning unit can cause physical injury.
Figure 1-1
• Beware of hot surfaces. Some parts, such as heatsinks of power semiconductors, remain hot for a while after
disconnection of the electrical supply.
• Ensure that debris from borings and grindings does not enter the drive when installing. Electrically conductive debris
inside the unit may cause damage or malfunction.
• Ensure sufficient cooling.
• Do not attach the drive by riveting or welding.
Printed Circuit Boards
WARNING: Ignoring the following instructions can cause damage to the printed circuit boards.
• Wear a grounding wrist band when handling the boards. Do not touch the boards unnecessarily. The printed circuit boards
contain components sensitive to electrostatic discharge.
3AXD50000011888 Introduction 1-3
1.2.3 Safe Start-Up and Operation
General Safety -These warnings are intended for all who plan the operation of the drive or operate the drive.
WARNING: Ignoring the following instructions can cause physical injury or death, or damage to the equipment:
• Before you connect voltage to the drive, make sure that the drive covers are on. Keep the covers on during the operation.
• Before adjusting the drive and putting it into service, make sure that the motor and all driven equipment are suitable for
operation throughout the speed range provided by the drive. The drive can be adjusted to operate the motor at speeds
above and below the speed provided by connecting the motor directly to the power line.
• Do not activate any automatic fault reset functions of the drive control program if dangerous situations can occur. When
activated, these functions will reset the drive and resume operation after a fault.
• The maximum number of drive power-ups is five in ten minutes. Too frequent power-ups can damage the charging circuit
of the DC capacitors.
• Make sure that any safety circuits (for example, emergency stop and Safe torque off) are validated in start-up. See chapter
Start-up for reference of the validation instructions.
Note:
• If an external source for start command is selected and it is ON, the drive will start immediately after an input voltage
break or fault reset unless the drive is configured for 3-wire (a pulse) start/stop.
• When the control location is not set to local, the stop key on the control panel will not stop the drive.
Permanent Magnet Motor Drives
WARNING: Do not run the motor over the rated speed. Motor overspeed leads to overvoltage which may damage or
explode the capacitors in the intermediate circuit of the drive.
1-4 Introduction 3AXD50000011888
Chapter 2
Product Familiarization
2.1 Overview
The ACS880+N5350 is designed to provide variable speed control for a cooling tower fan. This is accomplished much like
traditional variable frequency drives, but with unique capabilities specific to the type motor used and the type of application
for which the control is being employed.
The +N5350 control is designed specifically for Baldor Interior Permanent Magnet Cooling Tower Motor Control. Control
is intended for operating cooling tower fans through a 10:1 variable speed range as well as providing torque control to
minimize mechanical stress on the system. The motor drive systems are designed for direct drive applications and eliminate
the need for right angle gearboxes. The ACS880 is available for Cooling Tower applications in frame sizes R1 through R9.
Frame size specific information can be found in the ratings section.
2.2 Standards
ACS880+N5350 drives have been designed and tested to comply with the following standards.
2.2.1 Applicable Standards
The compliance with the European Low Voltage Directive is verified according to standard EN61800-5-1.
Table 2-1
Safety of machinery. Electrical equipment of machines.
Part 1: General requirements. Provisions for compliance: The final
assembler of the machine is responsible for installing
EN 60204-1:2006 + A1 2009
- emergency-stop device
- supply disconnecting device.
IEC/EN 60529:1991 + A1 2000 Degrees of protection provided by enclosures (IP code)
Insulation coordination for equipment within low-voltage systems.
IEC 60664-1:2007
Part 1: Principles, requirements and tests.
Adjustable speed electrical power drive systems.
EN 61800-3:2004
Part 3: EMC requirements and specific test methods
Adjustable speed electrical power drive systems.
EN 61800-5-1:2007
Part 5-1: Safety requirements – electrical, thermal and energy
Adjustable speed electrical power drive systems.
EN 61800-5-2:2007
Part 5-2: Safety requirements – Functional
UL 508C:2002 UL Standard for Safety, Power Conversion Equipment, third edition
NEMA 250:2008 Enclosures for Electrical Equipment (1000 Volts Maximum)
CSA C22.2 No. 14-10 Industrial control equipment
Low-voltage switchgear and control gear assemblies.
GOST R 51321-1:2007 Part 1 - Requirements for type-tested and partially type-tested assemblies
- General technical requirements and methods of tests
2.2.2 CE Marking
A CE mark is attached to the drive to verify that the drive follows the provisions of the European Low Voltage, EMC and
RoHS Directives. The CE marking also verifies that the drive, in regard to its safety functions (such as Safe torque off),
conforms with the Machinery Directive as a safety component.
2.2.3 UL Marking
cULus Listed UL Type 1 (IP21) drives:
• frames R1 to R3 of voltage range 208…240V
• frames R1 to R9 of voltage ranges 380…415V and 380…500V
• frames R5 to R9 of voltage range 525…600V
cULus Listed UL Type 12 (IP55) drives:
• frames R1 to R3 of voltage range 208…240V
• frames R1 to R5 of voltage ranges 380…415V and 380…500V
• frames R5 of voltage range 525…600V
The listing is pending for the other types. The approval is valid with rated voltages.
(See also Appendix C for recommendations for CE compliance and UL marking.)
3AXD50000011888 Product Familiarization 2-1
2.3 Usage
The ACS880+N5350 can only be used with Baldor RPM AC Interior Permanent Magnet Cooling Tower Motors. If the motor
you need to control is of any other type, contact your local Baldor District Office for support.
2.4 Enclosure
The ACS880+N5350 is provided in an enclosure that meets UL Type 1, IP21 ratings. This provides protection against
incidental contact with live electrical circuits and from falling dirt. The drive must be mounted in a clean, dry environment
and in a vertical position with at least a 2” clearance on the top, bottom, and both sides. Conductive particles or corrosive
gases must not be present in the atmosphere where the drive is mounted. It is not for use outdoors and should be protected
from direct sunlight. See Appendix A for complete environmental information.
2.4.1 Layout (IP21, UL Type 1)
The components of the standard IP21 drive are shown below (view of frame R5).
Figure 2-1
2-2 Product Familiarization 3AXD50000011888
2.4.2 Control Panel
The control panel can be removed by pulling it forward from the top edge and reinstalled in reverse order. For the use of the
control panel, see the firmware manual or ACS-AP assistant control panels user’s manual (3AUA0000085685 [English]).
Figure 2-2
2.5 Connections
The connections of the ACS880+N5350 are segmented into the two groups classified as Power Connections and Control
Connections. Conduit mounting holes are provided on the enclosure for each group of connections. See Appendix B for
conduit hole sizes so that proper planning can be accomplished for routing conduits to the control.
Access to all connections can be gained by the removal of the front cover.
WARNING: Do not remove the control cover for at least five (5) minutes after AC power is disconnected to
allow capacitors to discharge. Dangerous voltages are present inside the equipment. Electrical
shock can cause serious or fatal injury.
The power connections are grouped separately from the control connections and may be separated by a protective plate
depending on the size of the control. The installer must maintain separation between power connections and control
connections so that electrical noise does not interfere with proper operation. This dictates separate conduits for each group
of wires. See subsequent sections on power and control wiring for details of the required connections.
3AXD50000011888 Product Familiarization 2-3
2.5.1 Main Circuit
The main circuit of the drive is shown below.
Figure 2-3
Table 2-2
1 Rectifier. Converts alternating current and voltage to direct current and voltage.
2 DC link. DC circuit between rectifier and inverter.
3 Inverter. Converts direct current and voltage to alternating current and voltage.
4 Brake chopper. Conducts the surplus energy from the intermediate DC circuit of the drive to the brake
resistor when necessary. The chopper operates when the DC link voltage exceeds a certain maximum limit.
The voltage rise is typically caused by deceleration (braking) of a high inertia motor. User obtains and installs
the brake resistor when needed.
2-4 Product Familiarization 3AXD50000011888
2.5.2 Overview of Power and Control Connections
The diagram shows the power connections and control interfaces of the drive.
Figure 2-4
Table 2-3
1 Option modules can be inserted into slots 1, 2 and 3 as follows:
2 Modules Into slots
3 Analog and digital I/O extension modules except FDIO 1, 2, 3
Feedback interface modules 1, 2, 3
Fieldbus communication modules and FDIO 1, 2, 3
Safety functions modules 2
See section Type designation key
4 Memory unit
5 Connector for safety functions modules (alternative to Slot 2)
6 Default I/O connection diagram and Control unit (ZCU-12) connection data
7 See Control panel
8 du/dt, common mode or sine filter (optional)
3AXD50000011888 Product Familiarization 2-5
2.5.3 External Control Connection Terminals
The layout of external control connection terminals of the drive is shown below.
Figure 2-5
2-6 Product Familiarization 3AXD50000011888
2.6 Type Designation Label
The type designation label includes an IEC and NEMA rating, appropriate markings, a type designation and a serial number,
which allow identification of each unit. The type designation label is located on the front cover. An example label is shown
below.
Figure 2-6
Table 2-4
No. Description
1 Type designation
2 Frame size
3 Ratings in the supply voltage range
4 Valid markings
Serial number. The first digit of the serial number refers to the manufacturing plant. The next four digits
5 refer to the unit’s manufacturing year and week, respectively. The remaining digits complete the serial
number so that there are no two units with the same number.
3AXD50000011888 Product Familiarization 2-7
2.7 Type Designation Key
The type designation contains information on the specifications and configuration of the drive. The first digits from left
express the basic configuration, eg, ACS880-01-12A6-3 The optional selections are given thereafter, separated by
plus signs, eg, +L519. The main selections are described below. Not all selections are available for all types. For more
information, refer to ACS880-01 Ordering Information (3AXD10000014923), available on request.
Table 2-5
Code Description
Basic codes
ACS880 Product series
01 When no options are selected: Wall mounted drive, IP21 (UL Type 1), ACS-AP-I assistant
control panel, no EMC filter, DC choke, ACS880 primary control program, Safe torque
off function, cable entry box, brake chopper in frames R1 to R4, coated boards, printed
multilingual quick guides and CD containing all manuals.
Size
xxxx Refer to the rating tables
Voltage range
2 208…240V
3 380…415V
5 380…500V
7 525…690V
Option codes (plus codes)
Degree of protection
B056 IP55 (UL Type 12)
Construction
C131 Vibration dampers
Resistor braking
D150 Brake chopper for frame R5 and up.
Filters
E200 EMC filter for second environment TN (grounded) system, category C3.
E201 EMC filter for second environment IT (ungrounded) system, category C3. Available for
380…500V frames R6 to R9.
E202 EMC filter for first environment TN (grounded) system, category C2.
Cable entry box
H358 UK cable entry box
Fieldbus adapters
K451 FDNA-01 DeviceNet™ adapter module
K454 FPBA-01 PROFIBUS DP adapter module
K457 FCAN-01 CANopen adapter module
K458 FSCA-01 RS-485 adapter module
K462 FCNA-01 ControlNet™ adapter module
K469 FECA-01 EtherCAT adapter module
K470 FEPL-01 Ethernet POWERLINK adapter module
K473 FENA-11 high performance Ethernet/IP™, Modbus/TCP and PROFINET adapter module
K475 FENA-21 Two-Port Ethernet Adapter (EtherNet/IP™, Modbus/TCP)
2-8 Product Familiarization 3AXD50000011888
Table 2-5 Continued
Code Description
I/O extensions and feedback interfaces
L500 FIO-11 analog I/O extension module
L501 FIO-01 digital I/O extension module
L502 FEN-31 HTL incremental encoder interface module
L503 FDCO-01 optical DDCS communication adapter module
L508 FDCO-02 optical DDCS communication adapter module
L515 FEA-03 I/O extension adapter
L516 FEN-21 resolver interface module
L517 FEN-01 TTL incremental encoder interface module
L518 FEN-11 absolute encoder interface module
L525 FAIO-01 analog I/O extension module
L526 FDIO-01 digital I/O extension module
Specialties
P904 Extended warranty
ATEX-certified function
Q971 ATEX-certified Safe motor disconnection function using the Safe torque off function
Safety functions modules
Q973 FSO-11 safety functions module
Full set of printed manuals in selected language.
Note: The delivered manual set may include manuals in English if the translation is not available.
R700 English
R701 German
R702 Italian
R703 Dutch
R704 Danish
R705 Swedish
R706 Finnish
R707 French
R708 Spanish
R709 Portuguese
R711 Russian
R712 Chinese
R713 Polish
R714 Turkish
3AXD50000011888 Product Familiarization 2-9
2-10 Product Familiarization 3AXD50000011888
Chapter 3
Ratings
3.1 Ratings
The ACS880+N5350 product line includes models to support each motor designed for cooling tower direct drive
applications. The following table provides the electrical ratings of each of the standard available models. If your need is for a
rating not listed below, contact your local ABB representative for support. (Symbols are described below the table.)
Table 3-1 Drive Ratings, Model Numbers and Frame Sizes with 50 and 60 Hz Supply
Input Max Output Ratings
Rating Current Light-Overload Use
Catalog Number Frame
ACS880-01- Size
I1N Imax ILD PLD
A A A kW hp
UN = 208…240V
24A3-2+N5350 R2 24.3 28.6 23.1 5.5 7.5
031A-2+N5350 R3 31 41 29.3 7.5 10
046A-2+N5350 R4 46 64 44 11 15
061A-2+N5350 R4 61 76 58 15 20
075A-2+N5350 R5 75 104 71 18.5 25
087A-2+N5350 R5 87 122 83 22 30
115A-2+N5350 R6 115 148 109 30 40
145A-2+N5350 R6 145 178 138 37 50
170A-2+N5350 R7 170 247 162 45 60
206A-2+N5350 R7 206 287 196 55 75
274A-2+N5350 R8 274 362 260 75 100
UN = 380…415V
12A6-3+N5350 R1 12.6 16 12 5.5 7.5
017A-3+N5350 R2 17 21 16 7.5 10
025A-3+N5350 R2 25 29 24 11 15
032A-3+N5350 R3 32 42 30 15 20
038A-3+N5350 R3 38 54 36 18.5 25
045A-3+N5350 R4 45 64 43 22 30
061A-3+N5350 R4 61 76 58 30 40
072A-3+N5350 R5 72 104 68 37 50
087A-3+N5350 R5 87 122 83 45 60
105A-3+N5350 R6 105 148 100 55 75
145A-3+N5350 R6 145 178 138 75 100
169A-3+N5350 R7 169 247 161 90 125
206A-3+N5350 R7 206 287 196 110 150
246A-3+N5350 R8 246 350 234 132 200
293A-3+N5350 R8 293 418 278 160 225
363A-3+N5350 R9 363 498 345 200 275
430A-3+N5350 R9 430 545 400 200 350
3AXD50000011888 Ratings 3-1
Table 3-1 Drive Ratings, Model Numbers and Frame Sizes with 50 and 60 Hz Supply Cont.
Input Max Output Ratings
Rating Current Light-Overload Use
Catalog Number Frame
ACS880-01- Size
I1N Imax ILD PLD
A A A kW hp
UN = 440…480V
11A0-5+N5350 R1 11 16 11 5.5 7.5
014A-5+N5350 R2 14 21 14 7.5 10
021A-5+N5350 R2 21 29 21 11 15
027A-5+N5350 R3 27 42 27 15 20
034A-5+N5350 R3 34 54 34 18.5 25
040A-5+N5350 R4 40 64 40 22 30
052A-5+N5350 R4 52 76 52 30 40
065A-5+N5350 R5 65 104 65 37 50
077A-5+N5350 R5 77 122 77 45 60
096A-5+N5350 R6 96 148 96 55 75
124A-5+N5350 R6 124 178 124 75 100
156A-5+N5350 R7 156 247 156 90 125
180A-5+N5350 R7 180 287 180 110 150
240A-5+N5350 R8 240 350 240 132 200
260A-5+N5350 R8 260 418 260 132 200
302A-5+N5350 R9 302 498 302 200 250
361A-5+N5350 R9 361 542 361 200 300
414A-5+N5350 R9 414 542 414 250 350
UN = 660…690V
07A3-7+N5350 R5 7.3 12.2 6.9 5.5 7.5
09A8-7+N5350 R5 9.8 18 9.3 7.5 10
14A2-7+N5350 R5 14.2 22 13.5 11 15
018A-7+N5350 R5 18 30 17 15 20
022A-7+N5350 R5 22 44 21 18.5 25
026A-7+N5350 R5 26 54 25 22 30
035A-7+N5350 R5 35 64 33 30 40
042A-7+N5350 R5 42 74 40 37 50
049A-7+N5350 R5 49 76 47 45 60
061A-7+N5350 R6 61 104 58 55 75
084A-7+N5350 R6 84 124 80 75 100
098A-7+N5350 R7 98 168 93 90 125
119A-7+N5350 R7 119 198 113 110 150
142A-7+N5350 R8 142 250 135 132 200
174A-7+N5350 R8 174 274 165 160 225
210A-7+N5350 R9 210 384 200 200 275
271A-7+N5350 R9 271 411 257 250 350
3-2 Ratings 3AXD50000011888
Table 3-2 Definitions
UN Supply voltage range
I1N Nominal rms input current
IN Nominal output current (available continuously with no over-loading)
PN Typical motor power in no-overload use
ILD Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
PLD Typical motor power in light-overload use
Imax Maximum output current. Available for 10 seconds at start. then as long as allowed by drive temperature.
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes.
IHd * Continuous rms output current allowing 30% overload for 1 minute every 5 minutes.
** Continuous rms output current allowing 25% overload for 1 minute every 5 minutes.
PHd Typical motor power in heavy-duty use
Notes:
1. The ratings apply at an ambient temperature of 40°C (104°F).
2. To achieve the rated motor power given in the table, the rated current of the drive must be higher than or equal to the
rated motor current.
The DriveSize dimensioning tool available from ABB is recommended for selecting the drive, motor and gear combination.
3AXD50000011888 Ratings 3-3
3.2 Losses, Cooling Data and Noise
Table 3-3
Catalog Number Frame Air Flow Heat Dissipation Noise
ACS880-01- Size m /h3
ft /min
3
(Watts) dB(A)
UN = 208…240V
24A3-2+N5350 R2 88 52 337 51
031A-2+N5350 R3 134 79 457 57
046A-2+N5350 R4 134 79 500 62
061A-2+N5350 R4 280 165 630 62
075A-2+N5350 R5 280 165 680 62
087A-2+N5350 R5 280 165 730 62
115A-2+N5350 R6 435 256 840 67
145A-2+N5350 R6 435 256 940 67
170A-2+N5350 R7 450 265 1260 67
206A-2+N5350 R7 450 265 1500 67
274A-2+N5350 R8 550 324 2100 65
UN = 380…415V
12A6-3+N5350 R1 44 26 172 46
017A-3+N5350 R2 88 52 232 51
025A-3+N5350 R2 88 52 337 52
032A-3+N5350 R3 134 79 457 57
038A-3+N5350 R3 134 79 562 57
045A-3+N5350 R4 134 79 667 62
061A-3+N5350 R4 280 165 907 62
072A-3+N5350 R5 280 165 1117 62
087A-3+N5350 R5 280 165 1120 62
105A-3+N5350 R6 435 256 1295 67
145A-3+N5350 R6 435 256 1440 67
169A-3+N5350 R7 450 265 1940 67
206A-3+N5350 R7 450 265 2310 67
246A-3+N5350 R8 550 324 3300 65
293A-3+N5350 R8 550 324 3900 65
363A-3+N5350 R9 1150 677 4800 68
430A-3+N5350 R9 1150 677 6000 68
3-4 Ratings 3AXD50000011888
Table 3-3 Continued
Catalog Number Frame Air Flow Heat Dissipation Noise
ACS880-01- Size m /h
3
ft /min
3
(Watts) dB(A)
UN = 440…480V
11A0-5+N5350 R1 44 26 172 46
014A-5+N5350 R2 88 52 232 51
021A-5+N5350 R2 88 52 337 51
027A-5+N5350 R3 134 79 457 57
034A-5+N5350 R3 134 79 562 57
040A-5+N5350 R4 134 79 667 62
052A-5+N5350 R4 280 165 907 62
065A-5+N5350 R5 280 165 1117 62
077A-5+N5350 R5 280 165 1120 62
096A-5+N5350 R6 435 256 1295 67
124A-5+N5350 R6 435 256 1440 67
156A-5+N5350 R7 450 265 1940 67
180A-5+N5350 R7 450 265 2310 67
240A-5+N5350 R8 550 324 3300 65
260A-5+N5350 R8 550 324 3900 65
302A-5+N5350 R9 1150 677 4200 68
361A-5+N5350 R9 1150 677 4800 68
414A-5+N5350 R9 1150 677 6000 68
UN = 660…690V
07A3-7+N5350 R5 280 165 217 62
09A8-7+N5350 R5 280 165 284 62
14A2-7+N5350 R5 280 165 399 62
018A-7+N5350 R5 280 165 490 62
022A-7+N5350 R5 280 165 578 62
026A-7+N5350 R5 280 165 660 62
035A-7+N5350 R5 280 165 864 62
042A-7+N5350 R5 280 165 998 62
049A-7+N5350 R5 280 165 1120 62
061A-7+N5350 R6 435 256 1295 67
084A-7+N5350 R6 435 256 1440 67
098A-7+N5350 R7 450 265 1940 67
119A-7+N5350 R7 450 265 2310 67
142A-7+N5350 R8 550 324 3300 65
174A-7+N5350 R8 550 324 3900 65
210A-7+N5350 R9 1150 677 4200 68
271A-7+N5350 R9 1150 677 4800 68
3AXD50000011888 Ratings 3-5
3-6 Ratings 3AXD50000011888
Chapter 4
Terminal Specifications
Terminal specifications provided in this section should be followed during the installation of the ACS880+N5350 control. The
following tables provide the wire gauge ranges and terminal tightening torques for each group of terminals within the control.
4.1 Power Wire Gauge Range Specifications
Use copper conductors only.
Table 4-1 Power Wire Gauge Specification
Metric 1) US 2)
Catalog Number Cu Cable AI Cable Cu Cable AI Cable
Frame Size
ACS880-01- Type Typical Type Typical Type Typical Type Typical
mm2 mm2 AWG/kcmil AWG/kcmil
208…240V
04A6-2+N5350 R1 3 x 1.5 - 14 -
06A6-2+N5350 R1 3 x 1.5 - 14 -
07A5-2+N5350 R1 3 x 1.5 - 14 -
10A6-2+N5350 R1 3 x 1.5 - 14 -
16A8-2+N5350 R2 3x6 - 10 -
24A3-2+N5350 R2 3x6 - 10 -
031A-2+N5350 R3 3 x 10 - 8 -
046A-2+N5350 R4 3 x 16 3 x 35 6 -
061A-2+N5350 R4 3 x 25 3 x 35 4 -
075A-2+N5350 R5 3 x 35 3 x 50 3 -
087A-2+N5350 R5 3 x 35 3 x 70 3 -
115A-2+N5350 R6 3 x 50 3 x 70 1 -
145A-2+N5350 R6 3 x 95 3 x 120 2/0 -
170A-2+N5350 R7 3 x 120 3 x 150 3/0 -
206A-2+N5350 R7 3 x 150 3 x 240 250 MCM -
274A-2+N5350 R8 - - - -
380…415V
02A4-3+N5350 R1 3 x 1.5 - 14 -
03A3-3+N5350 R1 3 x 1.5 - 14 -
04A0-3+N5350 R1 3 x 1.5 - 14 -
05A6-3+N5350 R1 3 x 1.5 - 14 -
07A2-3+N5350 R1 3 x 1.5 - 14 -
09A4-3+N5350 R1 3 x 1.5 - 14 -
12A6-3+N5350 R1 3 x 1.5 - 14 -
017A-3+N5350 R2 3x6 - 10 -
025A-3+N5350 R2 3x6 - 10 -
032A-3+N5350 R3 3 x 10 - 8 -
038A-3+N5350 R3 3 x 10 - 8 -
045A-3+N5350 R4 3 x 16 3 x 35 6 -
061A-3+N5350 R4 3 x 25 3 x 35 4 -
072A-3+N5350 R5 3 x 35 3 x 50 3 -
087A-3+N5350 R5 3 x 35 3 x 70 3 -
105A-3+N5350 R6 3 x 50 3 x 70 1 -
145A-3+N5350 R6 3 x 95 3 x 120 2/0 -
169A-3+N5350 R7 3 x 120 3 x 150 3/0 -
206A-3+N5350 R7 3 x 150 3 x 240 250 MCM -
246A-3+N5350 R8 2 x (3x70) 3) 2 x (3x95) 300 MCM -
293A-3+N5350 R8 3) 2 x (3x120) 2 x 3/0 -
2 x (3x95)
363A-3+N5350 R9 2 x (3x120) 2 x (3x185) 2 x 4/0 -
430A-3+N5350 R9 2 x (3x150) 2 x (3x240) 2 x 250 MCM -
3AXD50000011888 Terminal Specifications 4-1
Table 4-1 Power Wire Gauge Specification (Cont.)
Metric 1) US 2)
Catalog Number Cu Cable AI Cable Cu Cable AI Cable
Frame Size
ACS880-01- Type Typical Type Typical Type Typical Type Typical
mm2 mm2 AWG/kcmil AWG/kcmil
440…480V
02A1-5+N5350 R1 3 x 1.5 - 14 -
03A0-5+N5350 R1 3 x 1.5 - 14 -
03A4-5+N5350 R1 3 x 1.5 - 14 -
04A8-5+N5350 R1 3 x 1.5 - 14 -
05A2-5+N5350 R1 3 x 1.5 - 14 -
07A6-5+N5350 R1 3 x 1.5 - 14 -
11A0-5+N5350 R1 3 x 1.5 - 14 -
014A-5+N5350 R2 3x6 - 10 -
021A-5+N5350 R2 3x6 - 10 -
027A-5+N5350 R3 3 x 10 - 8 -
034A-5+N5350 R3 3x6 - 8 -
040A-5+N5350 R4 3 x 16 3 x 25 6 -
052A-5+N5350 R4 3 x 25 3 x 25 4 -
065A-5+N5350 R5 3 x 35 3 x 35 3 -
077A-5+N5350 R5 3 x 35 3 x 50 3 -
096A-5+N5350 R6 3 x 50 3 x 70 1 -
124A-5+N5350 R6 3 x 95 3 x 95 2/0 -
156A-5+N5350 R7 3 x 120 3 x 150 3/0 -
180A-5+N5350 R7 3 x 150 3 x 185 250 MCM -
240A-5+N5350 R8 2 x (3x70) 3) 2 x (3x95) 300 MCM -
260A-5+N5350 R8 3) 2 x (3x95) 2 x 3/0 -
2 x (3x70)
302A-5+N5350 R9 2 x (3x95) 2 x (3x120) 2 x 3/0 -
361A-5+N5350 R9 2 x (3x120) 2 x (3x185) 2 x 250 MCM -
414A-5+N5350 R9 2 x (3x150) 2 x (3x240) 2 x 250 MCM -
660…690V
07A3-7+N5350 R5 3 x 1.5 - 14 12
09A8-7+N5350 R5 3 x 1.5 - 14 12
14A2-7+N5350 R5 3 x 2.5 - 14 12
018A-7+N5350 R5 3x4 - 12 10
022A-7+N5350 R5 3x6 - 10 8
026A-7+N5350 R5 3 x 10 3 x 25 8 6
035A-7+N5350 R5 3 x 10 3 x 25 8 6
042A-7+N5350 R5 3 x 16 3 x 25 6 4
049A-7+N5350 R5 3 x 16 3 x 25 6 4
061A-7+N5350 R6 3 x 25 3 x 35 4 3
084A-7+N5350 R6 3 x 35 3 x 50 3 2
098A-7+N5350 R7 3 x 50 3 x 70 2 1/0
119A-7+N5350 R7 3 x 70 3 x 95 1/0 3/0
142A-7+N5350 R8 3 x 95 3) 3 x 120 2/0 4/0
174A-7+N5350 R8 3) 2 x (3x70) 4/0 300 MCM
3 x 120
210A-7+N5350 R9 3 x 185 2 x (3x95) 300 MCM 2 x 3/0
271A-7+N5350 R9 3 x 240 2 x (3x120) 400 MCM 2 x 4/0
4-2 Terminal Specifications 3AXD50000011888
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top of the
other, ambient temperature 30°C, PVC insulation, surface temperature 70°C (EN60204-1 and IEC60364-5-52/2001). For
other conditions, size the cables according to local safety regulations, appropriate input voltage and the load current of
the drive. Refer to Hardware Manual 3AUA0000078093 for accepted cable sizes of the drive.
2) The cable sizing is based on NEC Table 310-16 for copper wires, 75°C (167°F) wire insulation at 40°C (104°F) ambient
temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly buried). For other
conditions, size the cables according to local safety regulations, appropriate input voltage and the load current of the
drive. Refer to Hardware Manual 3AUA0000078093 for accepted cable sizes of the drive.
3) The biggest cable size accepted by the connection terminals of frame R8 is 2 × (3×150). Biggest possible cable size is
3x240 or 400 MCM if the terminal type is changed and the cable entry box is not used.
3AXD50000011888 Terminal Specifications 4-3
4.2 Power Tightening Torque Specifications
Table 4-2 Power Tightening Torque Specifications
Tightening Torque
Ground
Catalog Number Frame L1, L2, L3, T1/U, T2/V, T3/W R-, R+/UDC+, UDC
ACS880-01- Size
T (Wire Screw) T (Terminal Nut) T (Wire Screw) T (Terminal Nut) T
Ibf-ft M... N-M Ibf-ft M... N-M Ibf-ft M... N-M Ibf-ft M... N-M Ibf-ft N-M
208…240V
24A3-2+N5350 R2 0.4 0.6 0.4 0.6 1.3 1.8
031A-2+N5350 R3 1.3 1.7 1.3 1.7 1.3 1.8
046A-2+N5350 R4 2.4 3.3 2.4 3.3 2.1 2.9
061A-2+N5350 R4 2.4 3.3 2.4 3.3 2.1 2.9
075A-2+N5350 R5 11.0 15 11.0 15 2.1 2.9
087A-2+N5350 R5 11.0 15 11.0 15 2.1 2.9
115A-2+N5350 R6 22.1 M10 30 M8 24 14.8 M8 20 M8 20 7.2 9.8
145A-2+N5350 R6 22.1 M10 30 M8 24 14.8 M8 20 M8 20 7.2 9.8
29.5 40
170A-2+N5350 R7 M10 M8 24 14.8 M10 30 M10 30 7.2 9.8
(22.1*) (30*)
29.5 40
206A-2+N5350 R7 M10 M8 24 14.8 M10 30 M10 30 7.2 9.8
(22.1*) (30*)
274A-2+N5350 R8 29.5 M10 40 17.7 M10 24 29.5 M10 40 17.7 M8 24 7.2 9.8
380…415V
12A6-3+N5350 R1 0.4 0.6 0.4 0.6 1.3 1.8
017A-3+N5350 R2 0.4 0.6 0.4 0.6 1.3 1.8
025A-3+N5350 R2 0.4 0.6 0.4 0.6 1.3 1.8
032A-3+N5350 R3 1.3 1.7 1.3 1.7 1.3 1.8
038A-3+N5350 R3 1.3 1.7 1.3 1.7 1.3 1.8
045A-3+N5350 R4 2.4 3.3 2.4 3.3 2.1 2.9
061A-3+N5350 R4 2.4 3.3 2.4 3.3 2.1 2.9
072A-3+N5350 R5 11.0 15 11.0 15 2.1 2.9
087A-3+N5350 R5 11.0 15 11.0 15 2.1 2.9
105A-3+N5350 R6 22.1 M10 30 M8 24 14.8 M8 20 M8 20 7.2 9.8
145A-3+N5350 R6 22.1 M10 30 M8 24 14.8 M8 20 M8 20 7.2 9.8
29.5 40
169A-3+N5350 R7 M10 M8 24 14.8 M10 30 M10 30 7.2 9.8
(22.1*) (30*)
29.5 40
206A-3+N5350 R7 M10 M8 24 14.8 M10 30 M10 30 7.2 9.8
(22.1*) (30*)
246A-3+N5350 R8 29.5 M10 40 17.7 M10 24 29.5 M10 40 17.7 M8 24 7.2 9.8
293A-3+N5350 R8 29.5 M10 40 17.7 M10 24 29.5 M10 40 17.7 M8 24 7.2 9.8
363A-3+N5350 R9 51.6 M12 70 17.7 M10 24 51.6 M12 70 17.7 M8 24 7.2 9.8
430A-3+N5350 R9 51.6 M12 70 17.7 M10 24 51.6 M12 70 17.7 M8 24 7.2 9.8
4-4 Terminal Specifications 3AXD50000011888
Table 4-2 Power Tightening Torque Specifications (Cont.)
Tightening Torque
Ground
Catalog Number Frame L1, L2, L3, T1/U, T2/V, T3/W R-, R+/UDC+, UDC
ACS880-01- Size
T (Wire Screw) T (Terminal Nut) T (Wire Screw) T (Terminal Nut) T
Ibf-ft M... N-M Ibf-ft M... N-M Ibf-ft M... N-M Ibf-ft M... N-M Ibf-ft N-M
440…480V
11A0-5+N5350 R1 0.4 0.6 0.4 0.6 1.3 1.8
014A-5+N5350 R2 0.4 0.6 0.4 0.6 1.3 1.8
021A-5+N5350 R2 0.4 0.6 0.4 0.6 1.3 1.8
027A-5+N5350 R3 1.3 1.7 1.3 1.7 1.3 1.8
034A-5+N5350 R3 1.3 1.7 1.3 1.7 1.3 1.8
040A-5+N5350 R4 2.4 3.3 2.4 3.3 2.1 2.9
052A-5+N5350 R4 2.4 3.3 2.4 3.3 2.1 2.9
065A-5+N5350 R5 11.0 15 11.0 15 2.1 2.9
077A-5+N5350 R5 11.0 15 11.0 15 2.1 2.9
096A-5+N5350 R6 22.1 M10 30 M8 24 14.8 M8 20 M8 20 7.2 9.8
124A-5+N5350 R6 22.1 M10 30 M8 24 14.8 M8 20 M8 20 7.2 9.8
29.5 40
156A-5+N5350 R7 M10 M8 24 14.8 M10 30 M10 30 7.2 9.8
(22.1*) (30*)
29.5 40
180A-5+N5350 R7 M10 M8 24 14.8 M10 30 M10 30 7.2 9.8
(22.1*) (30*)
240A-5+N5350 R8 29.5 M10 40 17.7 M10 24 29.5 M10 40 17.7 M8 24 7.2 9.8
302A-5+N5350 R9 51.6 M12 70 17.7 M10 24 51.6 M12 70 17.7 M8 24 7.2 9.8
361A-5+N5350 R9 51.6 M12 70 17.7 M10 24 51.6 M12 70 17.7 M8 24 7.2 9.8
414A-5+N5350 R9 51.6 M12 70 17.7 M10 24 51.6 M12 70 17.7 M8 24 7.2 9.8
660…690V
07A3-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
09A8-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
14A2-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
018A-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
022A-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
026A-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
035A-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
042A-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
049A-7+N5350 R5 11.0 15 11.0 15 2.1 2.9
061A-7+N5350 R6 22.1 M10 30 M8 24 14.8 M8 20 M8 20 7.2 9.8
084A-7+N5350 R6 22.1 M10 30 M8 24 14.8 M8 20 M8 20 7.2 9.8
29.5 40
098A-7+N5350 R7 M10 M8 24 14.8 M10 30 M10 30 7.2 9.8
(22.1*) (30*)
29.5 40
119A-7+N5350 R7 M10 M8 24 14.8 M10 30 M10 30 7.2 9.8
(22.1*) (30*)
142A-7+N5350 R8 29.5 M10 40 17.7 M10 24 29.5 M10 40 17.7 M8 24 7.2 9.8
174A-7+N5350 R8 29.5 M10 40 17.7 M10 24 29.5 M10 40 17.7 M8 24 7.2 9.8
210A-7+N5350 R9 51.6 M12 70 17.7 M10 24 51.6 M12 70 17.7 M8 24 7.2 9.8
271A-7+N5350 R9 51.6 M12 70 17.7 M10 24 51.6 M12 70 17.7 M8 24 7.2 9.8
* For 660…690V volt drives.
3AXD50000011888 Terminal Specifications 4-5
Figure 4-1 Cable Conduit Installation R1, R2 and R3
R-
R+
UDC-
T1/U
T2/V
T3/W
L1
L2
L3
6 AWG
Figure 4-2 Cable Conduit Installation R4, R5
4-6 Terminal Specifications 3AXD50000011888
Figure 4-3 Cable Conduit Installation R6, R7, R8, R9
3AXD50000011888 Terminal Specifications 4-7
4.3 Control Wire Gauge and Tightening Torque
Figure 4-4 Control Wire Gauge Specification and Tightening Torque
0.5 N·m
Wire sizes: 0.5 … 2.5mm2 (24…12AWG)
Tightening torques: 0.5 N·m (5lbf·in) for both
stranded and solid wiring.
1.5 N·m
1.5 N·m
4-8 Terminal Specifications 3AXD50000011888
Chapter 5
Power Wiring
This section outlines the basics of the power wiring for the ACS880+N5350. Sample wiring diagrams are shown later in this
guide.
5.1 Grounding the Control
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before
you ensure that all grounding instructions have been followed. Electrical shock can cause serious
or fatal injury.
To ensure a safe and trouble-free installation, the ACS880+N5350 must be properly grounded. Symmetrical voltage on
all three phases relative to ground is optimum and thus it is recommended that the control be supplied from a 4-wire wye
connected source. The center tap of the supply transformer secondary should be solidly grounded per local code. A ground
wire must be pulled in the same conduit with the L1, L2, and L3 connections from the source ensuring that the ground wire
is terminated on the ACS880+N5350 power terminal block.
5.2 Incoming Power
The ACS880+N5350 is designed for the incoming power ratings listed below. If your installation does not meet these ratings,
contact your local ABB representative for support.
Table 5-1 Incoming Power
Description Rating
ACS880-01-xxxx-2 units: 208 … 240VAC 3-phase +10%…-15%
ACS880-01-xxxx-3 units: 380 … 415VAC 3-phase +10%…-15%
Voltage (U1) ACS880-01-xxxx-5 units: 380 … 500VAC 3-phase +10%…-15%
ACS880-01-xxxx-7 units: 525 … 690VAC 3-phase +10%…-15%
Network type TN (grounded) and IT (ungrounded) systems.
Rated conditional short-circuit current (IEC 61439-1) 65 kA when protected by fuses given in the fuse tables
US and Canada: The drive is suitable for use on a circuit capable
Short-circuit current protection (UL508C,CSA C22.2
of delivering not more than 100 kA symmetrical amperes (rms) at
No. 14-05)
600V maximum when protected by fuses given in the fuse table
Frequency 47 to 63 Hz, maximum rate of change 17%/s
Imbalance Max. ± 3% of nominal phase to phase input voltage
Fundamental power factor (cosphi1) 0.98 (at nominal load)
As stated in the grounding section, the three incoming power wires must be pulled together in a single conduit with the
grounding conductor. These connections are to be made to L1, L2, and L3.
CAUTION: Do not connect AC power to the drive output terminals T1/U, T2, V and T3/W. These terminals are
for supplying power to the motor. Connecting AC power to these terminals may result in damage
to the control.
3AXD50000011888 Power Wiring 5-1
Figure 5-1 Incoming Power Diagram
Incoming power must meet specifications shown in
table 5-1. Power supplied to the ACS880+N5350
Input disconnect and branch circuit protection
must be symmetrical relative to ground. Power Optional customer supplied input reactor shown .
provided by customer to meet local codes. See
factor correction capacitors must not be switched See Chapter 5 of the ACS880-01 Hardware Manual
table 5.2 for recommended ratings. 3AUA0000078093 for details on installation planning.
on/off of the supply while the ACS880+N5350 is
connected to the line to prevent drive damage.
Input Disconnect
Input Reactor
Fuses ACS880+N5350
L1
Input
L2
Power
L3
See tables in Chapter 4
for wire gauge range and
for tightening torques of
incoming terminals.
ACS880+N5350 must be solidly grounded per
Incoming power should be pulled together in a
local code. A continuous ground connection
metallic conduit or be in a sheathed cable. Four
must be made between the ACS880+N5350
conductors must be used (3 for incoming power
and the facility ground. This ground wire should
and 1 for ground). Conduit or sheath must be
be sized per local code and is typically the same
grounded and continuity of ground maintained.
gauge as the power leads. It must be pulled in
same conduit as incoming power leads.
5.3 Protecting the Drive and Input Power Cable in Short-Circuits
Protect the drive and input cable with fuses as follows:
Figure 5-2
~ M
~ 3~
Size the fuses at the distribution board according to Table 5-2. The fuses will protect the input cable in short-circuit
situations, restrict drive damage and prevent damage to adjoining equipment in case of a short-circuit inside the drive.
Note: Circuit breakers must not be used without fuses. For more information, contact ABB.
5-2 Power Wiring 3AXD50000011888
5.4 Wire Sizing and Fuses
It is the responsibility of the installer to ensure that the ACS880+N5350 is installed in accordance with local electrical codes.
This includes, but is not limited to a proper disconnect, branch circuit protection, and wire size.
The following tables can be used as a guide to select wire gauge and input fuses. Recommendations are based upon the
maximum continuous current of the control. This table assumes 75°C wire.
Table 5-2 Wire Sizing
Control Rating
Wire Gauge
Catalog Number Frame kW HP Input Amps (AWG)
ACS880-01-24A3-2+N5350 R2 5.5 7.5 24.3 10
ACS880-01-031A-2+N5350 R3 7.5 10 31 8
ACS880-01-046A-2+N5350 R4 11 15 46 6
ACS880-01-061A-2+N5350 R4 15 20 61 4
ACS880-01-075A-2+N5350 R5 18.5 25 75 3
ACS880-01-087A-2+N5350 R5 22 30 87 3
ACS880-01-115A-2+N5350 R6 30 40 115 1
ACS880-01-145A-2+N5350 R6 37 50 145 2/0
ACS880-01-170A-2+N5350 R7 45 60 170 3/0
ACS880-01-206A-2+N5350 R7 55 75 206 250 MCM
ACS880-01-274A-2+N5350 R8 75 100 274 -
ACS880-01-12A6-3+N5350 R1 5.5 7.5 12.6 14
ACS880-01-017A-3+N5350 R2 7.5 10 17 10
ACS880-01-025A-3+N5350 R2 11 15 25 10
ACS880-01-032A-3+N5350 R3 15 20 32 8
ACS880-01-038A-3+N5350 R3 18.5 25 38 8
ACS880-01-045A-3+N5350 R4 22 30 45 6
ACS880-01-061A-3+N5350 R4 30 40 61 4
ACS880-01-072A-3+N5350 R5 37 50 72 3
ACS880-01-087A-3+N5350 R5 45 60 87 3
ACS880-01-105A-3+N5350 R6 55 75 105 1
ACS880-01-145A-3+N5350 R6 75 100 145 2/0
ACS880-01-169A-3+N5350 R7 90 125 169 3/0
ACS880-01-206A-3+N5350 R7 110 150 206 250 MCM
ACS880-01-246A-3+N5350 R8 132 200 246 300 MCM
ACS880-01-293A-3+N5350 R8 160 225 293 2 x 3/0
ACS880-01-363A-3+N5350 R9 200 275 363 2 x 4/0
ACS880-01-430A-3+N5350 R9 200 350 430 2 x 250 MCM
3AXD50000011888 Power Wiring 5-3
Table 5-2 Wire Sizing Continued
Control Rating Wire Gauge
Catalog Number Frame HP kW Input Amps (AWG)
ACS880-01-11A0-5+N5350 R1 5.5 7.5 11 14
ACS880-01-014A-5+N5350 R2 7.5 10 14 10
ACS880-01-021A-5+N5350 R2 11 15 21 10
ACS880-01-027A-5+N5350 R3 15 20 27 8
ACS880-01-034A-5+N5350 R3 18.5 25 34 8
ACS880-01-040A-5+N5350 R4 22 30 40 6
ACS880-01-052A-5+N5350 R4 30 40 52 4
ACS880-01-065A-5+N5350 R5 37 50 65 3
ACS880-01-077A-5+N5350 R5 45 60 77 3
ACS880-01-096A-5+N5350 R6 55 75 96 1
ACS880-01-124A-5+N5350 R6 75 100 124 2/0
ACS880-01-156A-5+N5350 R7 90 125 156 3/0
ACS880-01-180A-5+N5350 R7 110 150 180 250 MCM
ACS880-01-240A-5+N5350 R8 132 200 240 300 MCM
ACS880-01-260A-5+N5350 R8 132 200 260 2 x 3/0
ACS880-01-302A-5+N5350 R9 200 250 302 2 x 3/0
ACS880-01-361A-5+N5350 R9 200 300 361 2 x 250 MCM
ACS880-01-414A-5+N5350 R9 250 350 414 2 x 250 MCM
ACS880-01-07A3-7+N5350 R5 5.5 7.5 7.3 14
ACS880-01-09A8-7+N5350 R5 7.5 10 9.8 14
ACS880-01-14A2-7+N5350 R5 11 15 14.2 14
ACS880-01-018A-7+N5350 R5 15 20 18 12
ACS880-01-022A-7+N5350 R5 18.5 25 22 10
ACS880-01-026A-7+N5350 R5 22 30 26 8
ACS880-01-035A-7+N5350 R5 30 40 35 8
ACS880-01-042A-7+N5350 R5 37 50 42 6
ACS880-01-049A-7+N5350 R5 45 60 49 6
ACS880-01-061A-7+N5350 R6 55 75 61 4
ACS880-01-084A-7+N5350 R6 75 100 84 3
ACS880-01-098A-7+N5350 R7 90 125 98 2
ACS880-01-119A-7+N5350 R7 110 150 119 1/0
ACS880-01-142A-7+N5350 R8 132 200 142 2/0
ACS880-01-174A-7+N5350 R8 160 225 174 4/0
ACS880-01-210A-7+N5350 R9 200 275 210 300 MCM
ACS880-01-271A-7+N5350 R9 250 350 271 400 MCM
5-4 Power Wiring 3AXD50000011888
The table below assumes 150% rated fast acting fuses.
Table 5-3 Fuses
Input Fuse (one fuse per phase)
Catalog Number Frame Current
Amps A V Manufacturer Type UL Class
ACS880-01-24A3-2+N5350 R2 24.3 40 600 Bussmann JJS-40 T
ACS880-01-031A-2+N5350 R3 31 50 600 Bussmann JJS-50 T
ACS880-01-046A-2+N5350 R4 46 80 600 Bussmann JJS-80 T
ACS880-01-061A-2+N5350 R4 61 100 600 Bussmann JJS-100 T
ACS880-01-075A-2+N5350 R5 75 125 600 Bussmann JJS-125 T
ACS880-01-087A-2+N5350 R5 87 125 600 Bussmann JJS-125 T
ACS880-01-115A-2+N5350 R6 115 150 600 Bussmann JJS-150 T
ACS880-01-145A-2+N5350 R6 145 200 600 Bussmann JJS-200 T
ACS880-01-170A-2+N5350 R7 170 250 600 Bussmann JJS-250 T
ACS880-01-206A-2+N5350 R7 206 300 600 Bussmann JJS-300 T
ACS880-01-274A-2+N5350 R8 274 400 600 Bussmann JJS-400 T
ACS880-01-11A0-5+N5350 R1 11 20 600 Bussmann JJS-20 T
ACS880-01-014A-5+N5350 R2 14 25 600 Bussmann JJS-25 T
ACS880-01-021A-5+N5350 R2 21 35 600 Bussmann JJS-35 T
ACS880-01-027A-5+N5350 R3 27 40 600 Bussmann JJS-40 T
ACS880-01-034A-5+N5350 R3 34 50 600 Bussmann JJS-50 T
ACS880-01-040A-5+N5350 R4 40 60 600 Bussmann JJS-60 T
ACS880-01-052A-5+N5350 R4 52 80 600 Bussmann JJS-80 T
ACS880-01-065A-5+N5350 R5 65 90 600 Bussmann JJS-90 T
ACS880-01-077A-5+N5350 R5 77 110 600 Bussmann JJS-110 T
ACS880-01-096A-5+N5350 R6 96 150 600 Bussmann JJS-150 T
ACS880-01-124A-5+N5350 R6 124 200 600 Bussmann JJS-200 T
ACS880-01-156A-5+N5350 R7 156 225 600 Bussmann JJS-225 T
ACS880-01-180A-5+N5350 R7 180 300 600 Bussmann JJS-300 T
ACS880-01-240A-5+N5350 R8 240 350 600 Bussmann JJS-350 T
ACS880-01-260A-5+N5350 R8 260 400 600 Bussmann JJS-400 T
ACS880-01-302A-5+N5350 R9 302 400 600 Bussmann JJS-400 T
ACS880-01-361A-5+N5350 R9 361 500 600 Bussmann JJS-500 T
ACS880-01-414A-5+N5350 R9 414 600 600 Bussmann JJS-600 T
Note: For -3 and -7 drives, consult 3AUA0000078093 Hardware Manual for fuse information.
3AXD50000011888 Power Wiring 5-5
5.5 Motor Connections
The wiring between the drive and the motor must consist of 3 wires plus a ground routed in the same conduit. The ground
wire must be continuous and terminated in the motor connection box as well as on the drive ground terminal. The output
power wiring is terminated in the drive on terminals T1, T2, and T3 (see Figure 5-3 Motor Connections).
Note that a direct connection between the drive and motor without any other device is an acceptable means of controlling
the motor, but local safety regulations may require the use of a motor isolation switch or contactor to provide a way to
ensure that power is removed from the motor prior to servicing the tower.
The following warnings illustrate the things to consider when using a permanent magnet motor over an induction
motor. Please review these warnings carefully before operating the permanent magnet cooling tower motor.
WARNING: Motor circuit may have high voltage present whenever AC power is applied, even when motor is
not rotating. Electrical shock can cause serious or fatal injury.
WARNING: RPM AC permanent magnet motors can induce voltage and current in the motor leads by rotating
the motor shaft. Electrical shock can cause serious or fatal injury. Therefore, do not couple the
load to the motor shaft until all motor connections have been made. During any maintenance
inspections, be sure the motor shaft will not rotate.
WARNING: If an output motor isolation contactor is installed, the control must be disabled for at least
200mSec before the contactor is opened. If the contactor is opened while the control is supplying
voltage and current to the motor, the control may be damaged. Before the control is enabled, the
contactor must be closed for at least 200mSec.
WARNING: If an output motor isolation disconnect switch is installed, the control must be disabled for at
least 200mSec before the switch is opened. If the switch is opened while the control is supplying
voltage and current to the motor, the control may be damaged. Before the control is enabled, the
switch must be closed for at least 200mSec.
5-6 Power Wiring 3AXD50000011888
Example connection diagrams are shown later in this guide.
The wire leads that connect the motor to the control are critical in terms of sizing, shielding and the cable characteristics.
Figure 5-3 Motor Connections
Motor power connections should be pulled together in a metallic
Optional customer supplied output reactor shown. conduit or be in a sheathed cable. Four conducts must be used (3
See Chapter 5 of the ACS880-01 Hardware Manual for motor power and one ground). Ground must be terminated in
3AUA0000078093 for details on installation planning. the motor conduit box and in the drive. Conduit or sheath must be
grounded and continuity of ground maintained.
Output Reactor
ACS880+N5350 Cooling Tower Motor
T1/U
P2
T2/V M
P1
T3/W
See tables in Chapter 4 for wire gauge
range and tightening torques of
terminals.
XD24
Motor Thermostat Input
DIIL 1
+24 VD 2
DICOM 3
Motor thermostat leads must be pulled in a separate
+24 VD 4 conduit from the motor power leads so electrical noise is
DIOGND 5 not introduced into signal wiring.
Ground Select J6
Customer Supplied
Vibration Sensor Input Power
Power Source
XDI N.C. Dry
Contact Out
DI6 Vibration Switch (External Trip) 6
Customer Supplied
Vibration Switch
Vibration switch leads must be pulled in a separate
conduit from the motor power leads so electrical
noise is not introduced into signal wiring.
3AXD50000011888 Power Wiring 5-7
5.5.1 Protecting the Motor Insulation and Bearings
The drive employs modern IGBT inverter technology. Regardless of frequency, the drive output comprises pulses of
approximately the drive DC bus voltage with a very short rise time. The pulse voltage can almost double at the motor
terminals, depending on the attenuation and reflection properties of the motor cable and the terminals. This can cause
additional stress on the motor and motor cable insulation. Modern variable speed drives with their fast rising voltage pulses
and high switching frequencies can generate current pulses that flow through the motor bearings. This can gradually erode
the bearing races and rolling elements. Optional du/dt filters protect motor insulation system and reduce bearing currents.
Optional common mode filters mainly reduce bearing currents. Insulated N-end (non-drive end) bearings protect the motor
bearings. Cooling tower motors are also available with optional grounding brushes and insulated bearings, which also
reduce bearing currents.
5-8 Power Wiring 3AXD50000011888
Chapter 6
Control Wiring
This section outlines the basics of the control wiring for the ACS880+N5350. Sample wiring diagrams are shown later in this
guide.
6.1 Motor Thermostat
RPM AC permanent magnet cooling tower motors are provided with thermostats in the stator windings that operate should
the motor overheat. The thermostats are dry contacts designed to provide a closed (short) circuit when the motor is at a safe
temperature and an open circuit should the motor overheat. Dedicated connections are provided for a series connection
of these leads within the ACS880+N5350. All ACS880+N5350 drives must be used with motor overtemperature sensing
by correctly connecting the RPM AC cooling tower motor thermostats to the XD24-1 and XD24-2 terminals. The terminal
designations for the motor thermostat connections are XD24-1 and XD24-2 within the ACS880+N5350. The thermostat
wiring between the motor and the control must be run in a conduit separate from the motor power leads to avoid noise
related problems with the system.
6.2 Digital Inputs
The ACS880+N5350 is supplied with 9 digital inputs for controlling the cooling tower fan. The connections for these
digital inputs are made on terminals XD24, XD10 and XDI. XDIO-1 & 2 terminals are dedicated to trickle current and de-ice
enable inputs and cannot be changed. XDI-6 is shipped as an External Trip input as discussed in the next section and it is
recommended that this not be changed. The definitions of inputs on XDI-1 through XDI-5 are determined by the selected
operating mode of the drive. Operating mode selection is used to easily select a pre-configured setup of the drive thus
minimizing the programming required to commission the control. The available operating modes are described later in this
guide.
The digital inputs are shipped as “active high” (NPN) inputs. This means that an input signal is true when it is connected
to XD24-4 (Internal 24VDC Source). Conversely, the digital inputs can be set up to be “active high” inputs. In this case, an
input signal is true or when it is connected to the +24VDC power of a customer provided power source that is being used to
control the digital inputs.
Switch J6 on the control board are used to set up the digital inputs. If the inputs are to be controlled as “active high”
signals utilizing the internal supply of the ACS880+N5350, then no changes to the jumpers will be required. To set up the
digital inputs for other methods of control, reference Figure 6-2 for the jumper settings and the connections required to the
customer supplied inputs and power source.
3AXD50000011888 Control Wiring 6-1
Figure 6-1 Ground Isolation Diagram
Ground isolation diagram
XPOW
+24VDC
GND 2
XAI
+VREF 1
-VREF 2
AGND 3
AI1+ 4
AI1- 5 Common mode voltage between
AI2+ 6 channels +30 V
AI2- 7
XAO
AO1 1
AGND 2
AO2 3
AGND 4
XD2D
B 1
A 2
BGND 3
XRO1, XRO2, XRO3
NC 1
COM 2
NO 3
NC 1
COM 2
NO 3
NC 1
COM 2
NO 3
XD24
DIIL 1
+24VDC
DICOM 3
+24VDC
DIOGND 5 Switch J6 settings:
XDIO
DIO1 1 All digital inputs and
DIO2 2 outputs share a
XDI J6 common ground.
DI1 1
Ground of digital
DI2 2
DI3 3 inputs DI1…DI5 and
DI4 4 DIIL (DICOM) is
DI5 5 separated from the DIO
DI6 6 signal ground (DIOGND)
XSTO (insulation voltage 50V).
OUT1 1
Inputs are “active low”
SGND 2
IN1 3
when 24VDC connected
IN2 4 to DICOM.
Ground
6-2 Control Wiring 3AXD50000011888
Table 6-1 Jumpers and Switches
Jumper/
Description Positions
Switch
Current (I)
Determines whether analog input AI1 is used as a current or
J1 (AI1)
voltage input.
Voltage (U) (Default)
Current (I) (Default)
Determines whether analog input AI2 is used as a current of
J2 (AI2)
voltage input.
Voltage (U)
Drive-to-drive link termination. Must be set to terminated Bus is terminated.
J3
position when the drive is the last unit on the link. Bus is not terminated.
Common digital input ground selection switch. Determines DICOM and DIOGND connected
whether DICOM is separated from DIOGND (i.e.,common (Default),
J6
reference for digital inputs floats). See Ground isolation diagram
in Appendix A. DICOM and DIOGND separated.
Notes:
1. Current [0(4)…20mA, Rin > 100ohm] or voltage [ 0(2)…10V, Rin > 200kohm] input selected with jumper J1. Change of
setting requires reboot of control unit.
2. Current [0(4)…20mA, Rin > 100ohm] or voltage [ 0(2)…10V, Rin > 200kohm] input selected with jumper J2. Change of
setting requires reboot of control unit.
3. Total load capacity of these outputs is 4.8W (200mA / 24V) minus the power taken by DIO1 and DIO2.
4. 0 = open, 1 = closed
DI3 Ramp times according to
0 Parameters 23.12 and 23.13
1 Parameters 23.14 and 23.15
Further information on the usage of the connectors and jumpers is given in the sections below.
6.2.1 Vibration Switch / External Trip
An input is provided within the ACS880+N5350 that forces the drive to fault should the circuit connected to this input open.
The intent for this input is to interrupt the operation of the drive should a customer supplied circuit open. A typical use for
this input is the connection of a vibration sensor. The input is for a dry contact type device. Power is not supplied to the
external device from the ACS880+N5350 and power from the device must not be supplied to the drive terminals. If the
external device requires power (e.g. 120VAC) then the installer must make provisions for this power from an alternate source.
Make the connections for the dry contacts of this external device between terminals XDI6 and XD24-4 when using the
factory default active low configuration. The wiring for this device must be run in a conduit separate from the motor leads to
avoid noise related problems with the system.
6.2.2 Other Digital Inputs
Remaining digital inputs that may be required for operating the ACS880+N5350 are specific to the selected operating mode
and are outlined later in this guide.
3AXD50000011888 Control Wiring 6-3
6.3 Analog Inputs
An analog input is provided standard in the ACS880+N5350 for controlling the speed of the cooling tower fan if desired.
6.3.1 Analog Input 1
Analog Input 1 is capable of accepting a single-ended voltage signal on terminal XAI4 with respect to the analog common
on terminal XAI3. Should the customer desire to control the speed of the fan with a potentiometer, a +10V reference signal is
provided on terminal XAI1 is provided. It is recommended that a potentiometer with a resistance value > 200kΩ be used.
See Table 6-2 for jumper settings. See parameter 12.15 (AI1 Unit Selection Command) to select Analog Input 1 as the speed
reference and parameters 12.17 through 12.20 to customize the scaling and filtering for this input.
Note: This signal can be ±10VDC or 0 to 20mA. The mode (voltage or current) is selected by jumper J1. For detailed
information on hardware settings and software see manual.
Figure 6-2 depicts a potentiometer connection to Analog Input 1.
XAI Reference voltage and
Figure 6-2analog inputs
1 +VREF 10 VDC , RL 1...10 kohm
2 -VREF -10 VDC , RL 1...10 kohm
3 AGND Ground
4 AI1+ Speed reference
5 AI1- 0(2)...10 V, Rin > 200 kohm
6 AI2+ By default not in use
7 AI2- 0(4)...20mA, Rin > 200 kohm
Table 6-2 Analog Input 1 Technical Data
Reference voltage for analog inputs +VREF Connector pitch 5mm, wire size 2.5mm2
and -VREF (XAI:1) 10V ±1% and –10V ±1%, Rload 1…10kohm
Connector pitch 5mm, wire size 2.5mm2
Current input: –20…20mA, Rin: 100ohm
Voltage input: –10…10V, Rin: > 200kohm
Analog inputs AI1 (XAI:4…XAI:7)
Current/voltage input mode selection by Differential inputs, common mode range ±30V
jumpers. Sampling interval per channel: 0.25ms
Hardware filtering: 0.25ms, adjustable digital filtering up to 8ms
Resolution: 11 bit + sign bit
Inaccuracy: 2% of full scale range
Note: XAI6-7 is available as a second analog input for PID or Custom mode. This signal can be ±10VDC or 0 to 20mA. The
mode (voltage or current) is selected by jumper J2. For detailed information on hardware settings and software see
manual.
6-4 Control Wiring 3AXD50000011888
6.4 ACS880+N5350 Relay Outputs
The ACS880+N5350 has the ability of reporting multiple internal states to the user by the use of relay outputs. For example,
a relay can be set up to illuminate an external indicator light should the drive fault.
Three Form-C relay outputs are provided in the ACS880+N5350.
The functions of the relay outputs are selected by parameters 10.24 RO1 Source, 10.27 RO2 Source and 10.30 RO3 Source.
For details on setting the Relay Output function see the ACS880 software manual.
Figure 6-3 depicts connections to the digital outputs for the various ways they can be used.
XR01, XR02, XR03 Relay
Figureoutputs
6-3 Relay Outputs
1 NC Ready
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Running
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Faulted (-1)
2 COM 250 VAC / 30 VDC
3 NO 2A
Table 6-3 Relay Output Technical Data
Connector pitch 5mm, wire size 2.5mm2
Relay outputs RO1…RO3 (XRO1…XRO3) 250VAC / 30VDC, 2A
Protected by varistors
Connector pitch 5mm, wire size 2.5mm2
+24V output (XD24:2 and XD24:4) Total load capacity of these outputs is 4.8W (200mA / 24V)
minus the power taken by DIO1 and DIO2.
3AXD50000011888 Control Wiring 6-5
6.5 ACS880+N5350 Analog Outputs
Two analog outputs are provided in the ACS880+N5350 that can be used by the customer to indicate the value of various
signals within the drive. An example of usage of these signals is to use them to indicate motor speed and torque on remote
meters or to a building control computer system.
Table 6-4 Analog Output Technical Data
Connector pitch 5mm, wire size 2.5mm2
0…20mA, Rload < 500ohm
Analog outputs AO1 and AO2 (XAO) Frequency range: 0…300Hz
Resolution: 11 bit + sign bit
Inaccuracy: 2% of full scale range
Figure 6-4 Analog Outputs
XAO Analog outputs
1 A01 Motor speed rpm
2 AGND 0...20 mA, RL > 500 ohm
3 A02 Motor torque
4 AGND 0...20 mA, RL > 500 ohm
Current is proportional to torque on the Baldor Interior Permanent Magnet Cooling Tower Motor.
6-6 Control Wiring 3AXD50000011888
Chapter 7
Applying Power Quick Install Guide
This guide instructs briefly how to install the drive. For more detailed instructions, engineering guide lines, technical data and
complete safety instructions, see the hardware manual.
Follow the safety listed instructions in Chapter 1.
WARNING: Ignoring the following instructions can cause physical injury or death, or damage to the
equipment.
WARNING: The floor material below the drive must be non-flammable.
7.1 Select the Power Cables
Select the power cables according to local regulations to carry the nominal current given on the type designation label of
your drive.
7.2 Ensure Proper Cooling
See Table 3-3 for the losses and the cooling air flow through the drive. The allowed operating temperature range of the drive
without derating is -5°F to +104°F.
7.3 Protect the Drive and Input Power Cable
See Table 5-2. Check that the operating time of the fuse is below 0.5 seconds.
7.4 Check the Insulation of the Input and Motor Cables and the Motor
Check the insulation of the input cable according to local regulations before connecting it to the drive. Check the insulation
of the motor cable and motor when the cable is disconnected from the drive. Measure the insulation resistance between
each phase conductor and the Protective Earth conductor using a measuring voltage of 1000VDC. The insulation resistance
of an ABB motor must exceed 100 Mohm (reference value at 25°C or 77°F). For the insulation resistance of other motors,
consult the manufacturer’s instructions. Note: Moisture inside the motor casing will reduce the insulation resistance. If
moisture is suspected, dry the motor and repeat the measurement.
Figure 7-1
U1
M
V1
3~
ohm W1
PE
3AXD50000011888 Applying Power Quick Install Guide 7-1
7.5 Connect the Power Cables
See Figures 5-1 and 5-3.
1. Undo the two mounting screws at the sides of the front cover.
2. Remove the cover by sliding it forward.
3. Attach the residual voltage warning sticker in the local language to the control panel mounting platform.
4. Remove the rubber grommets from the lead-through plate for the cables to be connected.
5. Fasten the cable conduits to the cable lead-through plate holes. Strip the cable ends. Slide the cables through the
connectors.
6. Connect the grounding conductors to the grounding terminals.
7. Connect the phase conductors of the input and motor cables. Tighten the screws.
8. Units with option +D150: Connect the brake resistor cable conductors to the R+ and R- terminals.
9. Install the control cable grounding shelf in the cable entry box.
10. Connect the motor cable at the motor end.
7.6 Connect the Control Cables
See Figure 4-4.
1. Fasten the cable conduits to the cable lead-through plate holes. Slide the cables through the connectors.
2. Strip the cable ends and cut to suitable length (note the extra length of the grounding conductors).
3. Ground the outer shields of all control cables 360 degrees at a grounding clamp in the cable entry box.
4. Ground the pair-cable shields to the grounding clamp. Leave the other end of the shields unconnected or ground them
indirectly via a high-frequency capacitor with a few nanofarads, eg, 3.3nF / 630V.
5. Connect the conductors to the appropriate terminals of the control board.
6. Wire the optional modules if included in the delivery.
7. Reinstall the front cover.
7-2 Applying Power Quick Install Guide 3AXD50000011888
7.7 Default I/O Connections
The default I/O connections of the 2-wire mode of the ACS880+N5350 primary control program are shown below.
Figure 7-2
XP0W External power input
1 +24VI Wire sizes: 0.5 … 2.5mm2
24 VDC , 2 A
2 GND (24…12AWG)
XAI Reference voltage and analog inputs Tightening torques: 0.5 N·m (5lbf·in)
1 +VREF 10 VDC , RL 1...10 kohm for both stranded and solid wiring.
2 -VREF -10 VDC , RL 1...10 kohm
3 AGND Ground
4 AI1+ Speed reference
5 AI1- 0(2)...10 V, Rin > 200 kohm
6 AI2+ By default not in use
7 AI2- 0(4)...20 mA, Rin > 200 kohm
XAO Analog outputs
1 A01 Motor speed rpm
2 AGND 0...20 mA, RL > 500 ohm
3 A02 Motor torque %
4 AGND 0...20 mA, RL > 500 ohm
XD2D Drive-to-drive link
1 B Total load capacity of these
outputs is 4.8W (200mA / 24V)
2 A Drive-to-drive link minus the power taken by DIO1
3 BGND and DIO2.
XR01, XR02, XR03 Relay outputs
1 NC Ready
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Running
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Faulted (-1)
2 COM 250 VAC / 30 VDC
3 NO 2A
XD24 Digital interlock
to
1 DIIL Digital Interlock, Thermostat, Ramp Stop Must be Closed for the drive to
2 +24VD +24 VDC 200 mA Start.
3 DICOM Digital input ground
4 +24VD +24 VDC 200 mA
5 DIOGND Digital input/output ground
XDIO Digital input/outputs
1 DI01 Trickle current enable
2 DI02 De-Ice mode enable
XDI Digital inputs
1 DI1 Stop (0) / Start (1)
2 DI2 By default, not in use
3 DI3 Acc/Dec time set 1 (0) / set 2 (1)
4 DI4 Constant speed 2 (1 = On)
5 DI5 Reset Fault
6 DI6 External Event, Vibration Switch / External Trip Must be Closed for the drive to
XSTO Safe torque off circuits must be closed for the drive Start.
to start. See Hardware manual of drive.
X12 Safety options connection
X13 Control panel connection
X205 Memory unit connection
3AXD50000011888 Applying Power Quick Install Guide 7-3
7.8 UL Checklist
• The drive is to be used in a heated, indoor controlled environment. The drive must be installed in clean air according to
enclosure classification. Cooling air must be clean, free from corrosive materials and electrically conductive dust. See the
hardware manual.
• The maximum ambient air temperature is 40°C (104°F) at rated current. The current is derated for 40°C to 55°C (104°F to
131°F).
• The drive is suitable for use in a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 500V
maximum. The ampere rating is based on tests done according to UL 508C.
• The cables located within the motor circuit must be rated for at least 75°C (167°F) in UL-compliant installations.
• The input cable must be protected with fuses. Circuit breakers must not be used without fuses in the USA. Suitable IEC
(class aR) fuses and UL (class T) fuses are listed in the hardware manual. For suitable circuit breakers, contact your local
ABB representative.
• For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical
Code (NEC) and any applicable local codes. To fulfill this requirement, use the UL classified fuses.
• For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code
and any applicable provincial codes. To fulfill this requirement, use the UL classified fuses.
• The drive provides overload protection in accordance with the National Electrical Code (NEC).
7-4 Applying Power Quick Install Guide 3AXD50000011888
Chapter 8
Keypad and Programming
The ACS880+N5350 is supplied with a display combined with a keypad so that the status of the control can be monitored
and parameters can be programmed. Additionally, the keypad can be used to control the cooling tower fan locally. This
keypad can be left on the front cover of the drive, but is not required to operate the drive in the remote mode where control
is accomplished using the drive terminal strip or via a network communications card.
8.1 Installation and Start-Up
This section describes how to install and start up the Assistant control panel for the first time.
8.1.1 Installation
You can attach the control panel directly to the drive or use a separate mounting kit (for example, for cabinet door mounting).
To attach the control panel,
1. place its bottom end into the bottom of the slot in the drive (A),
2. pivot the control panel and push the upper part (B) until you hear a click.
To detach the control panel,
1. release the control panel by pressing the clip (B),
2. pull the upper end of the control panel out of the slot in the drive.
Figure 8-1
3AXD50000011888 Keypad and Programming 8-1
8.1.2 First Start-Up
The following instructions explain how to start up the control panel for the first time.
1. Make sure that all drive-specific safety precautions have been taken into account.
2. Install the control panel as instructed in Installation.
3. Power up the drive.
The control panel start-up begins automatically. Wait until the control panel enters the language selection view.
Note: The language selection view only appears during the first start-up of the control panel, but it is possible to change the
language later in the Settings menu (see parameter 96.01) or with the set-up assistant.
Figure 8-2
English
Deutsch
Italiano
Espaňol
Portugues
Nederlands
Français
OK
4. Use or to select a language.
5. Press (OK) to confirm your selection.
Wait until the control panel completes uploading the language file. Its progress is indicated by a progress bar.
Figure 8-3
ACS880
Cooling Tower Drive
ACS880
There is a Basic set-up assistant in the drive that the control panel prompts to begin the Cooling Tower Assistant. Details on
the assistant are contained in Chapter 12 of this manual.
Figure 8-4
Remote CTDD 0.0 rpm
Cooling Tower Direct ...
Use arrow keys and soft keys to
Navigate the assistant
Exit 00:00 Continue
Completing the assistant or Exiting returns you to the Home view. Once you are in the Home view, the control panel is ready
for use.
Figure 8-5
Local CTDD 0.0 rpm
Motor speed used rpm
0.00
Motor current A
0.00
Options 00:00 Menu
To return to the assistant screen, select Menu Assistants CTDD Setup.
Press Select to launch the assistant.
8-2 Keypad and Programming 3AXD50000011888
8.2 Control Panel Overview
This section describes the display, keys and main parts of the Assistant control panel.
Figure 8-6 Display, Keys and Parts
Table 8-1
1 Display 8 Start (see Start and Stop)
2 Left softkey 9 Local/Remote (see Loc/Rem)
3 Right softkey 10 USB connector
4 Status LED 11 Clip
5 Help 12 RJ-45 connector
6 Arrow keys 13 Type code label
7 Stop (see Start and Stop) 14 Battery cover
8.2.1 Display
In most views, the following elements are shown on the display:
Figure 8-7
Local CTDD 0.0 rpm
0.0
Output voltage
V
Motor current
A 0.00
0.0
Motor torque%
%
Options 00:00 Menu
3AXD50000011888 Keypad and Programming 8-3
1. Control location: Indicates how the drive is controlled:
• Local: The drive is in local control, ie, controlled from the control panel.
• Remote: The drive is in remote control, ie, controlled through I/O or fieldbus.
• (Remote): The drive is in remote control (as above), but some commands (such as start, stop, direction change or
reference) are configured to be controlled by the control panel.
2. Status icon: Indicates the status of the drive and the motor. The direction of the arrow indicates forward (clockwise) or
reverse (counter-clockwise) rotation.
Table 8-2
Status Icon Animation Drive Status
- Stopped
- Stopped, start inhibited
Blinking Stopped, start command given but start inhibited
Blinking Faulted
Blinking Running, at reference, but the reference value is 0
Rotating Running, not at reference
Rotating Running, at reference
Note: For non-rotating driven equipment, the numbers 1 and 0 are used to indicate that the drive is running or stopped,
respectively.
3. Drive name: If a name has been given, it is displayed in the top pane. By default, it is blank. You can change the name in
the Settings menu.
4. Reference value: Speed, frequency, etc. is shown with its unit.
5. Content area: The actual content of the view is displayed in this area. The content varies from view to view. The example
view above is the main view of the control panel which is called the Home view.
6. Softkey selections: Displays the functions of the softkeys ( and ) in a given context.
7. Clock: The clock displays the current time. The time can be changed through the Settings menu.
You can adjust the display contrast and backlight functionality in the Settings menu.
8.2.2 Keys
The keys of the control panel are described below.
Figure 8-8
8.2.2.1 Left Softkey
The left softkey ( ) is usually used for exiting and canceling. Its function in a given situation is shown by the softkey
selection in the bottom left corner of the display.
Holding down exits each view in turn until you are back in the Home view. This function does not work in special
screens.
8-4 Keypad and Programming 3AXD50000011888
8.2.2.2 Right Softkey
The right softkey ( ) is usually used for selecting, accepting and confirming. The function of the right softkey in a given
situation is shown by the softkey selection in the bottom right corner of the display.
8.2.2.3 Arrow Keys
The up and down arrow keys ( and ) are used to highlight selections in menus and selection lists, to scroll up and down
on text pages, and to adjust values when, for example, setting the time, entering a passcode or changing a parameter value.
The left and right arrow keys ( and ) are used to move the cursor left and right in parameter editing and to move
forward and backward in assistants. In menus, and function the same way as and , respectively.
8.2.2.4 Help
The help key ( ? ) opens a help page. The help page is context-sensitive, in other words, the content of the page is relevant
to the menu or view in question.
8.2.2.5 Start and Stop
In local control, the start key ( ) and the stop key ( ) start and stop the drive, respectively.
8.2.2.6 Loc/Rem
The location key ( Loc/Rem ) is used for switching the control between the control panel (Local) and remote connections
(Remote). When switching from Remote to Local while the drive is running, the drive keeps running at the same speed.
When switching from Local to Remote, the status of the remote location is adopted. See the drive-specific firmware manual
for more details.
8.2.2.7 Key Shortcuts
The table below lists key shortcuts and combinations. Simultaneous key presses are indicated by the plus sign ( + ).
Table 8-3
Shortcut Available in Effect
+ Save a screenshot. Up to fifteen images may be stored in the control panel
Any view memory. For instructions on how to transfer the images into a PC, see
+ section the ACS-AP-X assistant control panel manual.
+
Any view Adjust backlight brightness.
+
+
Any view Adjust display contrast.
+
or Home view Adjust reference.
+ Parameter edit
Revert an editable parameter to its default value.
views
+ Any view Show/hide parameter index and parameter group numbers.
Any view Return to Home view by pressing down the key until Home view is shown.
(keep down)
3AXD50000011888 Keypad and Programming 8-5
8.2.3 Status LED
The control panel has a status LED that indicates if there are any faults or warnings present. The table below shows the
meaning of the LED indications.
Table 8-4 LED Indications
Green, Continuous The drive is functioning normally.
Data is transferred between the PC tool and drive through the USB connection
Green, Flickering
of the control panel.
Green, Blinking There is an active warning in the drive.
Red, Continuous There is an active fault in the drive.
For further information on fault and warning indications, see Chapter 13, Troubleshooting.
8.2.4 USB Connector
The USB connector is used for connecting the control panel to a PC. When connected, the control panel acts as an USB
adapter for data transfer between the PC tool and the drive. It is also possible to transfer data between the PC and the
control panel through the USB connection.
8.2.5 RJ-45 Connector
The RJ-45 connector is used to electrically connect the control panel to the drive. Mechanical connection is achieved with
the clip on the top.
8.2.6 Type Code Label
The type code label contains revision information. The revision letter and the software version of the control panel are
highlighted in the image below.
Figure 8-9
8.2.7 Battery Cover
Underneath the cover there is a compartment for the battery that powers the real-time clock of the control panel.
8-6 Keypad and Programming 3AXD50000011888
8.3 Local Control vs. Remote Control
The ACS880+N5350 is designed so that it can be run via keypad control (Local) or via the terminal strip or network
communications (Remote). The Local/Remote Control can be changed by using the Local/Remote key on the keypad.
Figure 8-10 ACS880
External control
I/O
PLC
Local control
Fieldbus adapter (Fxxx)
Control panel or Drive composer
PC tool (optional)
M
3~
MOTOR
8.3.1 Local Control
The control commands are given from the control panel keypad or from a PC equipped with Drive composer when the drive
is set to local control. Speed control is available for local control.
Local control is mainly used during commissioning and maintenance. The control panel always overrides the external control
signal sources when used in local control. Thermal and Vibration signals are still active.
By default the drive will fault if there is a control panel or PC tool communication break. See software manual if desired
function is to be changed in parameter 49.05 (communication loss action).
8.3.2 Remote Control
When the drive is in remote control, control commands are given through:
• the I/O terminals (digital and analog inputs), or optional I/O extension modules
or
• an optional fieldbus adapter module
The source for the Start/Stop and Speed Reference commands is selected using control operating modes. See Chapter 9
for available operating mode configurations.
3AXD50000011888 Keypad and Programming 8-7
8.4 Basic Operation
This section describes the basic operations and components of the user interface, lists common user tasks and gives short
instructions on how to complete them.
8.4.1 User Interface Overview
The user interface has the following main components:
• The Home view through which you can monitor signals.
• The main Menu through which you can access most functions of the control panel. The Menu functions are described in
detail in chapter Functions in the main Menu.
• The Options menu through which you can set a reference, change the motor direction, select the drive, edit Home view
pages, and see the fault and warning status.
• The Help view which provides advice in many situations.
• Faults and warnings view which appear when the drive or the control panel experiences an error.
8.4.2 Control Panel Navigation
Use the arrow keys and softkeys for navigation. Follow the choices on the screen.
Figure 8-11
Home view
Options Menu
Reference Parameters
Direction change Assistants
Select drive Energy efficiency
Edit Home view Event log
Fault status History graphs
Backups
System info
Settings
8.4.2.1 Navigation Memory
The Assistant control panel has a navigation memory that allows you to backtrack your steps through the user interface with
the arrow keys and . The path you have last accessed remains in the memory for 10 minutes.
• The left arrow key ( ) moves you backwards in the menu structure. If you press repeatedly, you return back to the
Home view.
• The right arrow key ( ) moves you forward in the menu structure. If you press repeatedly, you move forward along
the path in the menu structure you had previously accessed.
8-8 Keypad and Programming 3AXD50000011888
8.4.3 Home View
The main view of the control panel is called the Home view. In the Home view, you can monitor the status of the drive, such
as its speed, torque or power. The Home view has nine pages, each of which can display a set of signals.
In the example below, three Home view pages are used, showing different display formats.
Figure 8-12
Local ACS880 CTDD 0.0 Rpm Local ACS880 CTDD 0.0 Rpm Local ACS880 CTDD 0.0 Rpm
0.0
Motor speed DC Voltage 618.31V
Motor speed
Rpm 0.0 Rpm 0 800
Motor current
A 0.0 Drive temperature
-40
14.5%
160
Motor current
A 0.0 Motor volts
V 0.0
Output Power
-32768.0
0.0 kW
32768.0
Options 00:00 Menu Options 00:00 Menu Options 00:00 Menu
The Home view opens automatically when you power up the drive. The Home view is also displayed from the Options menu
or the main Menu if no key is pressed for 10 minutes.
Tip: You can return to the Home view from any view except special screens by holding down the left softkey .
8.4.3.1 Navigating in the Home View
• Use and to move between the different pages of the Home view. The page numbers are shown while you scroll
between pages.
• Use or to adjust the reference (visible in the top right corner).
• Press (Menu) to open the main Menu.
• Press (Options) to open the Options menu.
8.4.4 Help
You can open a context-sensitive help page in all menus and views by pressing ? . The help page provides information on
the use of the current view or menu, or on possible problems associated with it.
On the help page, you can:
•Press ? again or (Exit) to exit.
8.4.5 Common User Tasks
This following tables list common user tasks and describes how to complete them.
8.4.5.1 Basic Operation of the Drive
Table 8-5
Task Actions
Start and stop the drive. In local control, press to start the drive and to stop
the drive.
In local control, go to Options > Reference. Set the reference
Set the reference (for example, speed) in the Home view.
with the arrow keys.
Switch between local and remote control. Press Loc/Rem
.
Change the direction of motor rotation. In local control, go to the Home view, press (Options) to
open the Options menu and select Direction change.
3AXD50000011888 Keypad and Programming 8-9
8.4.5.2 Parameters
Table 8-6
Task Actions
Choose parameters displayed on the Favorites list. Go to Menu > Parameters > Favorites > Edit.
View/edit parameters. Go to Menu > Parameters to view parameters.
Add parameters to the Home view. See assistant panel manual.
Show/hide parameter index and group numbers. Press + .
Restore parameter default value. In the editing mode, press + .
To save the default value, press (Save).
View parameters that differ from Application defaults. Go to Menu > Parameters > Modified.
8.4.5.3 System Information and Help
Table 8-7
Task Actions
How to get help. Press ? to open the context-sensitive help.
View control panel version. Go to Menu > System into > Control panel.
View drive information. Go to Menu > System into > Drive.
8.4.5.4 Faults and Warnings
See Fault tracing in Chapter 13 for detailed information on faults and warnings.
Table 8-8
Task Actions
Faults are automatically displayed. If you hide a fault by
pressing (Hide), it automatically reappears after 60
Hide/view an active fault.
seconds of no key presses. You can also view the fault through
Options > Fault status.
Open help page on a fault. Press ? to view the help page.
Reset an active fault. Press (Reset) to reset an active fault.
View tripping faults. Go to Menu > Event log > Primary faults.
Warnings are automatically displayed. If you hide a warning by
Hide/view and active warning. pressing (Hide), it automatically reappears if the warning is
still active after 60 seconds of no key presses.
Open help page on a warning. Press (How to fix) or ? to view the help page.
Warnings disappear automatically once the condition that has
Reset an active warning.
triggered it goes away.
View past warnings and faults. Go to Menu > Event log > Other events.
8.4.5.5 Basic Settings and Assistants
Table 8-9
Task Actions
Adjust backlight brightness. Press + or
Adjust display contrast. Press + or
Change language. Go to Menu > Settings > Language.
Change time and date, and related settings. Go to Menu > Settings > Date & time.
Launch an assistant. Go to Menu > Assistants and select an assistant to launch.
8-10 Keypad and Programming 3AXD50000011888
Chapter 9
Operating Modes
The ACS880+N5350 can be placed in any one of 5 different operating modes. These modes are used to quickly set up the
drive to operate from the drive terminal strip or from a network communications card. Many inputs are still programmable.
NOTE: Stop drive and place drive in “Local” before changing mode. Cycle power or reboot drive after changing mode.
CAUTION: Drive may start unexpectedly on changing mode.
9.1 2Wire Operating Mode (Default)
Figure 9-1 ACS880+N5350 2Wire Operating Mode Connection Diagram (76.03 = 1)
XP0W External power input
1 +24VI
24 VDC , 2 A
2 GND
XAI Reference voltage and analog inputs
1 +VREF 10 VDC , RL 1...10 kohm
2 -VREF -10 VDC , RL 1...10 kohm
3 AGND Ground
4 AI1+ Speed reference
5 AI1- 0(2)...10 V, Rin > 200 kohm
6 AI2+ By default not in use
7 AI2- 0(4)...20 mA, Rin > 200 kohm
XAO Analog outputs
1 A01 Motor speed rpm
2 AGND 0...20 mA, RL > 500 ohm
3 A02 Motor torque %
4 AGND 0...20 mA, RL > 500 ohm
XD2D Drive-to-drive link
1 B
2 A Drive-to-drive link
3 BGND
XR01, XR02, XR03 Relay outputs
1 NC Ready
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Running
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Faulted (-1)
2 COM 250 VAC / 30 VDC
3 NO 2A
XD24 Digital interlock
to
1 DIIL Digital Interlock, Thermostat, Ramp Stop
2 +24VD +24 VDC 200 mA
3 DICOM Digital input ground
4 +24VD +24 VDC 200 mA
5 DIOGND Digital input/output ground
XDIO Digital input/outputs
1 DI01 Trickle current enable
2 DI02 De-Ice mode enable
XDI Digital inputs
1 DI1 Stop (0) / Start (1)
2 DI2 By default, not in use
3 DI3 Acc/Dec time set 1 (0) / set 2 (1)
4 DI4 Constant speed 2 (1 = On)
5 DI5 Reset Fault
6 DI6 External Event, Vibration Switch
XSTO Safe torque off circuits must be closed for the drive
to start. See Hardware manual of drive.
X12 Safety options connection
X13 Control panel connection
X205 Memory unit connection
3AXD50000011888 Operating Modes 9-1
9.2 3Wire Operating Mode
Figure 9-2 ACS880+N5350 3Wire Operating Mode Connection Diagram (76.03 = 2)
XP0W External power input
1 +24VI
24 VDC , 2 A
2 GND
XAI Reference voltage and analog inputs
1 +VREF 10 VDC , RL 1...10 kohm
2 -VREF -10 VDC, RL 1...10 kohm
3 AGND Ground
4 AI1+ Speed reference
5 AI1- 0(2)...10 V, Rin > 200 kohm
6 AI2+ By default not in use
7 AI2- 0(4)...20 mA, Rin > 200 kohm
XAO Analog outputs
1 A01 Motor speed rpm
2 AGND 0...20 mA, RL > 500 ohm
3 A02 Motor torque %
4 AGND 0...20 mA, RL > 500 ohm
XD2D Drive-to-drive link
1 B
2 A Drive-to-drive link
3 BGND
XR01, XR02, XR03 Relay outputs
1 NC Ready
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Running
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Faulted (-1)
2 COM 250 VAC / 30 VDC
3 NO 2A
XD24 Digital interlock
to
1 DIIL Digital Interlock, Thermostat, Ramp Stop
2 +24VD +24 VDC 200 mA
3 DICOM Digital input ground
4 +24VD +24 VDC 200 mA
5 DIOGND Digital input/output ground
XDIO Digital input/outputs
1 DI01 Trickle current enable
2 DI02 De-Ice mode enable
XDI Digital inputs
1 DI1 Start
2 DI2 Stop
3 DI3 ACC/DEC Time Set 1 (0) / Set 2 (1)
4 DI4 Constant speed 2 (1 = On)
5 DI5 Reset Fault
6 DI6 External Event, Vibration Switch
XSTO Safe torque off circuits must be closed for the drive
to start. See Hardware manual of drive.
X12 Safety options connection
X13 Control panel connection
X205 Memory unit connection
9-2 Operating Modes 3AXD50000011888
9.3 Process Control (PID) Operating Mode
The process control mode provides an auxiliary closed loop general purpose PID set point control. The process control loop
may be configured in various ways.
For details on setting parameters and adjusting PID configuration see the ACS880 software manual. Default I/O
configurations are shown in the figure below.
Figure 9-3 Process Control Operating Mode Connection Diagram (76.03 = 3)
XP0W External power input
1 +24VI
24 VDC , 2 A
2 GND
XAI Reference voltage and analog inputs
1 +VREF 10 VDC , RL 1...10 kohm
2 -VREF -10 VDC , RL 1...10 kohm
3 AGND Ground
4 AI1+ Process or Speed reference
5 AI1- 0(2)...10 V, Rin > 200 kohm
P 6 AI2+ Process feedback
I 7 AI2- 0(4)...20 mA, Rin > 200 kohm
XAO Analog outputs
1 A01 Motor speed rpm
2 AGND 0...20 mA, RL > 500 ohm
3 A02 Motor torque %
4 AGND 0...20 mA, RL > 500 ohm
XD2D Drive-to-drive link
1 B
2 A Drive-to-drive link
3 BGND
XR01, XR02, XR03 Relay outputs
1 NC Ready
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Running
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Faulted (-1)
2 COM 250 VAC / 30 VDC
3 NO 2A
XD24 Digital interlock
to
1 DIIL Digital Interlock, Thermostat, Ramp Stop
2 +24VD +24 VDC 200 mA
3 DICOM Digital input ground
4 +24VD +24 VDC 200 mA
5 DIOGND Digital input/output ground
XDIO Digital input/outputs
1 DI01 Trickle current enable
2 DI02 De-Ice mode enable
XDI Digital inputs
1 DI1 Stop (0)/ Start (1) – Speed or Process Control
2 DI2 Speed control (0) / Process Control (1)
3 DI3 ACC/DEC Time Set 1(0)/Set 2(1)
4 DI4 Constant Speed 2 (1=ON)
5 DI5 Fault Reset
6 DI6 External Event, Vibration Switch
XSTO Safe torque off circuits must be closed for the drive
to start. See Hardware manual of drive.
X12 Safety options connection
X13 Control panel connection
X205 Memory unit connection
3AXD50000011888 Operating Modes 9-3
9.4 Fieldbus Operating Mode
The drive can be connected to an external control system through an optional fieldbus adapter mounted onto the control
unit of the drive. When Fieldbus Operating Mode is selected, the drive Starts and Stops using the Main Command Word,
(6.01) bit 2, if DI2 is on for Remote FBA. DI2(1) also selects FBA Ref1 a the speed reference. The drive actually has two
independent interfaces for fieldbus connection called “fieldbus adapter A” (FBA A) and “fieldbus adapter B” (FBA B).
Fieldbus adapters are available for various communication systems and Industrial Protocols, for example:
Fieldbus Adapters
FDNA-01 DeviceNet™ Adapter K451
FPBA-01 PROFIBUS DP Adapter K454
FCAN-01 CanOpen Adapter K457
FSCA-01 Modbus Adapter, comes with a price when Built-in Modbus K458
FCNA-01 ControlNet™ Adapter K462
FECA-01 EtherCAT Adapter K469
FEPL-02 Ethernet Powerlink Adapter K470
FENA-11 Ethernet Adapter (EtherNet/IP™, Modbus/TCP, PROFINET IO) K473
FENA-21 Two-Port Ethernet Adapter (EtherNet/IP™, Modbus/TCP) K475
Reference software manual for configuration Network parameter settings. See Figure 9-4 on next page.
9-4 Operating Modes 3AXD50000011888
Figure 9-4 Fieldbus Operating Mode Connection Diagram (76.03 = 4)
XP0W External power input
1 +24VI
24 VDC, 2 A
2 GND
XAI Reference voltage and analog inputs
1 +VREF 10 VDC, RL 1...10 kohm
2 -VREF -10 VDC, RL 1...10 kohm
3 AGND Ground
4 AI1+ Speed reference Local Reference
5 AI1- 0(2)...10V, Rin > 200 kohm
6 AI2+ By default not in use
7 AI2- 0(4)...20 mA, Rin > 200 kohm
XAO Analog outputs
1 A01 Motor speed rpm
2 AGND 0...20 mA, RL > 500 ohm
3 A02 Motor torque %
4 AGND 0...20 mA, RL > 500 ohm
XD2D Drive-to-drive link
1 B
2 A Drive-to-drive link
3 BGND
XR01, XR02, XR03 Relay outputs
1 NC Ready
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Running
2 COM 250 VAC / 30 VDC
3 NO 2A
1 NC Faulted
2 COM 250 VAC / 30 VDC
3 NO 2A
XD24 Digital interlock
to
1 DIIL Digital Interlock, Thermostat, Ramp Xtop
2 +24VD +24 VDC 200 mA
3 DICOM Digital input ground
4 +24VD +24 VDC 200 mA
5 DIOGND Digital input/output ground
XDIO Digital input/outputs
1 DI01 Trickle current enable
2 DI02 De-Ice mode enable
XDI Digital inputs
1 DI1 Local Stop (0) / Start (1)
2 DI2 Local/Remote Local(0)/FBA(1)+(bit2)*
3 DI3 Run enable
4 DI4 Constant Speed 2 (1 = On)
5 DI5 Reset Fault
6 DI6 External Event, Vibration Switch
Safe torque off circuits must be closed for the drive
XSTO
to start. See Hardware manual of drive.
X12 Safety options connection
X13 Control panel connection
X205 Memory unit connection
*Remote reference is FBA REF1
Note: De-Ice will not function in Local operation.
3AXD50000011888 Operating Modes 9-5
9-6 Operating Modes 3AXD50000011888
Chapter 10
Additional Setup
Once the motor has been identified to the drive and the operating mode chosen, the drive is ready to operate. Additional
setup may be desired to enable Trickle Current Heating when not running, for set up of skip frequencies during operation,
and/or enabling De-Ice control function.
10.1 Trickle Current Heating
Trickle Current Heating is a feature of the ACS880+N5350 that can be used by the customer to maintain a small amount
of power going to the motor from the drive while the fan is not being used. This feature will not cause fan rotation and aids
in eliminating moisture in the motor. This eliminates the need for motor space heaters which are normally specified when a
motor is placed in a humid environment.
Trickle Current Heating is disabled as a factory default since it depends on motor related information. Once enabled, Trickle
Current will start flowing in the motor windings after the fan has been stopped. Should the motor be restarted at any time
(before or after the timer has expired) Trickle Currrent will immediately stop and the motor will start normally. In other words,
the Run Command has priority over Trickle. See parameter 74.01 (Trickle Current Enable) for information on enabling Trickle
Current.
The below chart has traditionally been used to size space heaters for various frame motors and is equally applicable to
deciding how much trickle current to the motor.
Table 10-1
Motor Frame Size Wattage
FL250 75
FL280 100
FL320 125
FL360 150
FL400 175
FL440 225
FL5800 400
In addition to the wattage from the above table, the motor stator resistance value is needed. The stator resistance is taken
from parameter 98.09 Rs user SI after ID run is complete.
Utilize the below calculation to check the trickle current value:
Trickle Current = Wattage from Table 10-1
3 x Stator R
The wattage from the above table can then be programmed into parameter 74.02 (Trickle Power). This will enable Trickle
Current to flow in the motor after it has been stopped for time set in parameter 74.03 (Trickle Delay Time). Note that the
customer is limited to a current value that is no more than 100% of the motor rated current so that there is no danger in
overheating the motor.
Should the motor be restarted at any time (before or after the timer has expired) Trickle Current will immediately stop and the
motor will start normally.
Trickle Current will not work while the motor is in Local.
3AXD50000011888 Additional Setup 10-1
10.1.1 Parameter Settings
Trickle Current Enable (74.01) Default: 0 (Disable)
Range: 0 - 4
0 (Disable) Disable Trickle Current
1 (Enable) Enable Trickle Current whenever motor is not running
2 (DIO1) Enable Trickle Current when DIO2 is True
3 (FBA) Enable Trickle Current over Fieldbus Adapter Module
4 (EFB) Enable Trickle Current over Embedded Fieldbus
Software Enable (1) or Disable (0) Trickle Current parameter setting.
A hardware enable on DIO1 is also required to activate Trickle Current.
Trickle Power (74.02) Default: 100W
Range: 0 to 500W
The level of Trickle Current is determined by frame size of the motor and input to
the drive power level, no decimal required.
Trickle Current Delay (74.03) Default: 1 Min
Range: 0 - 10 Min
The time delay before Trickle Current starts. This delay ensures the motor has
ramped down and stopped prior to Trickle Current beginning.
10.1.2 CTDD Assistant Access
In addition to programming changes in group 74, Trickle Current is an option under the CTDD startup assistant:
Figure 10-1 Trickle Current
Local CTDD 50.0 rpm
Trickle Current
Set parameters for Trickle Current.
Enable Disabled
Trickle Power 100W
Trickle Time Delay 1 min
Back 00:00 Next
10.2 Critical Speed Function
When applying a variable speed control to a cooling tower fan, mechanical resonances may occur at various points of
operation. The ACS880+N5350 provides for up to three frequency avoidance bands that are used to prohibit continuous
operation at the points of mechanical resonance.
While in LOCAL control, the keypad can be used to start and stop the drive and to locally adjust the speed.
Use the “UP” arrow key to slowly increase the speed of the motor. Should the cooling tower fan start to resonate, record the
RPM. Continue this process until you have tested the motor at all points between minimum speed and maximum speed.
The parameters that are used to provide for the critical speeds are located in the Speed Reference Selection Block
(parameter numbers 22.51 through 22.57). Program a band around each point of resonance using parameter settings critical
speed low and high.
For a more detailed description of these parameters see Chapter 12.
10-2 Additional Setup 3AXD50000011888
10.3 De-Ice Function
This is a cooling tower function to run at low speed in the opposite (reverse) direction than standard. This function is for
prevention of ice build up in colder climates.
Set De-Ice Speed (75.02) to a value under 30% base motor speed.
Set the De-Ice Run Time (75.03) to the time desired for operation in this function.
Select a De-Ice Enabling Mechanism and set 75.01 accordingly.
When De-Ice is enabled with XDIO2 terminal Closed, the drive will enter De-Ice mode for the Run Time set in 75.03. If the
drive has a valid Run Command applied at the same time as a De-Ice Command, the drive will run in De-Ice mode (Reverse)
for the specified time and then enter Run.
NOTE: De-Ice in Keypad Operation or Custom Mode
The Keypad operates the CTDD drive in local control. To initiate De-Ice while using the Keypad, the drive must first
be placed in remote control. If the drive is running in Custom mode, the drive must be stopped before De-Ice will run.
10.3.1 De-Ice Parameter Settings
De-Ice Enable (75.01) Default: 0 (Disable)
Range: 0 - 3
0 (Disable) Disable De-Ice mode
1 (DIO2) Enable De-Ice mode using DIO2
2 (FBA) Enable De-Ice mode using Fieldbus Adapter Module
3 (EFB) Enable De-Ice mode using Embedded Fieldbus
Disable (0) disables the De-Ice function. If set to DIO2 (1), the Digital Input DIO2
will be used to enable the De-Ice function. If set to FBA (2), the De-Ice function is
commanded via the Control Word of the Fieldbus Adapter Module. If set to EFB
(3), the De-Ice function is commanded via the Control Word of the Embedded
Fieldbus.
De-Ice Speed (75.02) Default: 30%
Range: 0 to 100%
De-Ice speed can be reprogrammed from 0% to 100% speed.
De-Ice Run Time (75.03) Default: 1 Min.
Range: 1 - 1500 Mins.
Value of time to run in De-Ice function when Software Enable is active, and a
hardware input is present. Drive will run at De-Ice function speed for the set run
time and then shut down.
10.3.2 CTDD Assistant Access
In addition to programming changes in group 75, De-Ice function setup is an option under the CTDD startup assistant:
Figure 10-2 De-Ice Function
Local CTDD 50.0 rpm
De-Ice
Set parameters for De-ice.
Enable Disabled
De-Ice Speed 30%
Run Time 1 min
Minimum torque 1 -30.0 %
Back 00:00 Next
3AXD50000011888 Additional Setup 10-3
10.4 Advanced Drive Settings
See ACS880 Software Manual, 3AUA0000085967, for information on advanced drive functions such as PID and Fieldbus
control.
10.4.1 Access Levels
Access levels are based on CTDD USER, Fieldbus or Expert Commissioner. Selection for access level is contained in the
96.02 passcode parameter; accessible in the programming window (but not the startup assistant, passcode changes are for
expert users only). Changing modes will automatically set access level.
There is no default setting for 96.02. Setting access level to 13 (Fieldbus) opens all Fieldbus applicable parameters. Expert
Commissioner enables all parameters in the drive by setting 96.02 = 12.
Expert Commissioner is set in PID and Custom modes.
Fieldbus operating mode opens up all parameters in groups 50 to 56 and monitoring parameters 3.05, 3.06, 6.01 and 6.11.
CTDD User Default Access Level
Pass Code (96.02) Default: -
Set to values below for access level
14 CTDD User
13 Fieldbus
12 Expert Commissioner
Parameter 96.03 shows the current access level setting, note ABB default will show active with the addition of the set level
shown below. Value is offset by one from the password entered.
Access Level (96.03) Default: Read Only
Range: -
11 Expert Commissioner
12 Fieldbus
13 CTDD User
10-4 Additional Setup 3AXD50000011888
10.4.2 Access Level Flow Diagram
Figure 10-3 Access Level Flow Diagram
Remote CTDD 50.0 rpm Remote CTDD 50.0 rpm
Complete list Changing other parameters...
46 Monitoring/scaling settings
74 Trickle Current
75 De-ice
95 HW configuration
96 System
Back 00:00 Select 00:00
Remote CTDD 50.0 rpm Remote CTDD 50.0 rpm
96 System 96 System CTDD User
96.01 Language English 96.01 Language English
96.02 Pass code 96.02 Pass code
96.03 Access levels ac… 0010 000 0… 96.03 Access levels ac… 0010 000 0…
96.04 Macro select Done 96.04 Macro select Done
96.05 Macro active CTDD 96.05 Macro active CTDD
Back 00:00 Edit Back 00:00 Edit
Remote CTDD 0.0 rpm Remote CTDD 50.0 rpm
99.07 Pass code 96.03 Access levels active
10 0 . = Inactive
0000014 11 0 Commissioning
12 0 CTDD Fieldbus
= Inactive
= Inactive
13 1 CTDD User = Active
14 0 Parameter lock = Inactive
Cancel 00:00 Enter Back 00:00 Edit
10.4.3 Access Level Indication
The display will indicate the access level with a key symbol and access level:
Figure 10-4
CTDD User
If no symbol is present, the ABB default access level is active.
3AXD50000011888 Additional Setup 10-5
10-6 Additional Setup 3AXD50000011888
Chapter 11
Example Connection Diagrams
The installation of the ACS880+N5350 is ultimately the responsibility of the user to ensure that it is installed in a manner
that will provide a safe and trouble-free system that meets local safety and electrical codes. The information provided in
this section is not intended to specifically dictate how the ACS880+N5350 is to be wired or even to imply that all safety
factors have been considered since these may vary from one installation to another. These diagrams are provided so that the
installer may visualize several possible ways the drive can be connected based upon the 2Wire Operating Mode as well as
the 3Wire Operating Mode.
The devices external to the ACS880+N5350 and the RPM AC Cooling Tower Motor depicted in the following diagrams are
considered user supplied unless they are ordered as a packaged drive from ABB or as separate line items. Contact your
local ABB representative for support regarding the additional equipment or a packaged drive.
3AXD50000011888 Example Connection Diagrams 11-1
11.1 ACS880+N5350 2Wire Operating Mode Example
The 2Wire Operating Mode is provided for those customers that wish to control their cooling tower fan using what is
traditionally called “2-Wire Control”. This method of control utilizes a single “Off – On” selector switch to stop / run the fan.
On power loss to the drive, the drive will restart automatically when power is restored.
11.1.1 Manual Motor Disconnect Switch
This diagram depicts an example of using the 2Wire Operating Mode along with a manual disconnect switch between the
drive and the motor. The disconnect switch used in this diagram is a 3 position switch. The intent here is to provide one
position that is used when the fan is actually being run by the ACS880+N5350. There is a neutral position where the motor
leads are open circuit, and also a position which shorts the motor leads together. The position that shorts the leads together
is used to prohibit hazardous voltages from being present on the motor leads when it is disconnected from the drive should
the fan rotate. This could occur since the motor includes permanent magnets in its rotor thus giving it the characteristics
of being a generator when not connected to a drive. Another benefit of this position is that it will cause the motor to resist
windmilling. Note that it is required to provide an auxiliary contact on the disconnect switch that is open any time the motor
is not connected to the drive. This contact needs to be of the “Late Make / Early Break” style such that the contacts on the
auxiliary open before the power contacts open. Additionally, when the disconnect switch is closed, the power contacts of
the disconnect switch must close prior to the closure of the auxiliary contact.
Figure 11-1 ACS880+N5350 2Wire Manual Motor Disconnect Switch
Input Disconnect
SW1 Line Output Disconnect
Fuses Reactor SW2
L1 ACS880+N5350+P934 T1/U Cooling Tower Motor
Input
L2 T2/V
Power
M
L3 T3/W
XAI
1 +10V DC Analog Ref. Power
Fan 2 - VREF
Speed 3 Analog Common
Setting 4 AI1+ Speed Reference
5 AI1-
6 AI2+
7 AI2-
J1 AI1 Current/Voltage Jumper
J2 AI2 Current Voltage Jumper XD24 Motor Thermostat Input
DIIL 1
XAO
AO1
1 +24 VD 2
AGND
2 DICOM 3
AO2
3 +24 VD 4
Trickle Current AGND
4 DIOGND 5
Ground Select J6
De-Ice XDIO
1 DIO1 Trickle Current Enable
2 DIO2 De-Ice Enable Customer Supplied
Vibration Sensor Input Power
Run Power Source
SW2 (Aux) XDI
1 DI1 Start / Stop
Late Make / Early Break 2 DI2 By default, not in use N.C. Dry
(closed when SW2 is in Contact Out
Reset 3 DI3 Accel / Decel 1 or 2 Select
the ACS880 position only)
4 DI4 Constant Speed 2
5 DI5 Fault Reset Customer Supplied
6 DI6 Vibration Switch (External Trip) Vibration Switch
XR01, XR02, XR03
RO 1 NC 1
Note: Power wiring to be in separate conduits from signal
COM 2
wiring such as thermostat and vibration switch.
RO 1 NO 3
RO 2 NC 1
COM 2
RO 2 NO 3
Example Jumper Settings
RO 3 NC 1
J1 AI1 Voltage
COM 2
RO 3 NO 3 J2 AI1 Current
Bus is terminated
J3 Bus not terminated
DICOM and DIOGND
connected (default)
J6 DICOM and DIOGND
separated
11-2 Example Connection Diagrams 3AXD50000011888
11.2 ACS880+N5350 3Wire Operating Mode Example
The 3Wire Operating Mode is provided for those customers that wish to control their cooling tower fan using what is
traditionally called “3-Wire Control”. This method of control utilizes a momentary normally open “Start” pushbutton to
run the fan and a momentary normally closed “Stop” pushbutton to stop the fan. On power loss to the drive, the “start”
pushbutton will restart the drive when power is restored.
11.2.1 Manual Motor Disconnect Switch
This diagram depicts an example of using the CTD 3Wire Operating Mode along with a manual disconnect switch between
the drive and the motor. The disconnect switch used in this diagram is a 3 position switch. The intent here is to provide one
position that is used when the fan is actually being run by the ACS880+N5350. There is a neutral position where the motor
leads are open circuit, and also a position which shorts the motor leads together. The position that shorts the leads together
is used to prohibit hazardous voltages from being present on the motor leads when it is disconnected from the drive should
the fan rotate. This could occur since the motor includes permanent magnets in its rotor thus giving it the characteristics
of being a generator when not connected to a drive. Another benefit of this position is that it will cause the motor to resist
windmilling. Note that it is required to provide an auxiliary contact on the disconnect switch that is open any time the motor
is not connected to the drive. This contact needs to be of the “Late Make / Early Break” style such that the contacts on the
auxiliary open before the power contacts open. Additionally, when the disconnect switch is closed, the power contacts of
the disconnect switch must close prior to the closure of the auxiliary contact.
Figure 11-2 ACS880+N5350 3Wire Manual Motor Disconnect Switch
Input Disconnect
SW1 Line Output Disconnect
Fuses Reactor SW2
L1 ACS880+N5350+P934 T1/U Cooling Tower Motor
Input
L2 T2/V
Power
M
L3 T3/W
XAI
1 +10V DC Analog Ref. Power
Fan 2 - VREF
Speed 3 Analog Common
Setting 4 AI1+ Speed Reference
5 AI1-
6 AI2+
7 AI2-
J1 AI1 Current/Voltage Jumper
J2 AI2 Current Voltage Jumper XD24 Motor Thermostat Input
DIIL 1
XAO
AO1
1 +24 VD 2
AGND
2 DICOM 3
AO2
Trickle Current 3 +24 VD 4
AGND
4 DIOGND 5
Ground Select J6
De-Ice XDIO
1 DIO1 Trickle Current Enable
2 DIO2 De-Ice Enable Customer Supplied
Vibration Sensor Input Power
Start Power Source
XDI
1 DI1 Start
2 DI2 Stop N.C. Dry
Contact Out
Stop 3 DI3 ACC/DEC Time Set 1 (0) / Set 2 (1)
SW2 (Aux)
4 DI4 Constant Speed 2 (1 = On)
Late Make / Early Break 5 DI5 Fault Reset
(closed when SW2 is in
Customer Supplied
the ACS880 position only) Reset 6 DI6 Vibration Switch (External Trip) Vibration Switch
XR01, XR02, XR03
RO 1 NC 1
Note: Power wiring to be in separate conduits from signal
COM 2
wiring such as thermostat and vibration switch.
RO 1 NO 3
RO 2 NC 1
COM 2
RO 2 NO 3
Example Jumper Settings
RO 3 NC 1
J1 AI1 Voltage
COM 2
RO 3 NO 3 J2 AI1 Current
Bus is terminated
J3 Bus not terminated
DICOM and DIOGND
connected (default)
J6 DICOM and DIOGND
separated
3AXD50000011888 Example Connection Diagrams 11-3
11.3 Motor Contactor or Shorting Contactor Examples
The following configurations are intended as examples on providing a manual motor disconnect or a power off fail safe
shorting contactor. These approaches can be used independent of the drive starting mode or reference source and are not
tied directly to the drive controller. Figure 11-3 depicts the preferred usage of a shorting contactor and a motor disconnect
when used with the ACS880+N5350 drive.
11.3.1 Manual Motor Disconnect Switch
The motor disconnect should be located remotely from the drive panel, within site of the direct drive RPM AC motor and
driven load. This is in compliance with National Electric Code Sections 420.102 to 430.109. The switch should only be
shorted after the ACS880+N5350 drive has been powered down or de-activated by opening the enable input.
11.3.2 Shorting Contactor
The intent of the Shorting Contactor is to provide one position (open) that is used when the fan is being run by the
ACS880+N5350. This is the normal power on state. The other power off position (closed) shorts the motor leads together.
For both the options, the position that shorts the leads together is used to prohibit hazardous voltages from being present
on the motor leads when it is disconnected from the drive should the fan rotate. This could occur since the motor includes
permanent magnets in its rotor thus giving it the characteristics of being a generator when not connected to a drive. Another
benefit of this position is that it will cause the motor to resist wind-milling.
Figure 11-3 Motor Contactor Example
Input Power
Input Disconnect
SW1
Line Reactor
Output Contactor Output Disconnect
ACS880+N5350+P934
OC SW2
L1 T1/U Cooling Tower Motor
L2 T2/V P2
M
L3 T3/W P1
T1 Select T1 Control transformer in
accordance with the input voltage
115V rating of the ACS880+N5350
AC
Shorting Contactor
XD24 SC
DIIL 1
OC
+24 VD 2
DICOM 3
+24 VD 4 Customer Supplied
SC
DIOGND 5 Vibration Sensor Input Power
Ground Select J6 Power Source
N.C. Dry
XDI Contact Out
External Trip 6
Customer Supplied
Vibration Switch
11-4 Example Connection Diagrams 3AXD50000011888
Chapter 12
Startup Assistant & Parameters
12.1 Startup Assistants Guide for ACS880+N5350
This chapter describes the basic start-up assistants for motor data and ID run; and setting up the ACS880 drive equipped
with +N5350 cooling tower program. In this guide, the drive is set up using the ACS-AP-I control panel. Complete
documentation of the drive firmware can be found in Firmware manual, 3AUA0000085967.
Never work on the drive, the braking chopper circuit, the motor cable or the motor when power is applied to the drive.
Always ensure by measuring that no voltage is actually present.
Note: Before you start ensure that the drive has been mechanically and electrically installed as described in the appropriate
sections of this manual.
WARNING: All electrical installation and maintenance work on the drive should be carried out by qualified electricians.
12.1.1 Motor Data and ID Run
On initial startup, the drive automaticlly goes into the Motor data setup.
Table 12-1 Initial Start-up / Motor Data and ID Run
Safety
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the safety instructions on the first
pages of the appropriate Hardware manual.
Check the installation. See the installation checklist in the appropriate Hardware manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if there is a risk of damage in case of an incorrect direction of rotation.
Power-Up, Date and Time Settings
Power up the drive.
English
On initial power up the cooling tower drive requests
a language selection for the setup process. Deutsch
Italiano
Espaňol
Portugues
Nederlands
Français
OK
Select language using and and press
(continue) to accept.
ACS880
The drive will load the selected language; this may
take a few minutes.
ABB loading screen will appear after the language
selection completes.
Cooling Tower Drive
ACS880
3AXD50000011888 Startup Assistant & Parameters 12-1
Table 12-1 Initial Start-up / Motor Data and ID Run
On initial startup, the drive goes into the Motor data setup.
and this screen will not be shown. Remote CTDD 0.0 rpm
Note: This screen will not show on first startup. Assistants
On subsequent startups, select “Motor Data and ID Run” Motor Data & ID Run
from the Assistants menu, which is located off of the main CTDD Setup
menu.
Back 00:00 Select
Motor Data and ID Run Assistant will load. Press
(continue) to begin the cooling tower startup Remote CTDD 0.0 rpm
assistant.
Motor Set-up
Use arrow keys and soft keys to
Navigate the assistant
Exit 00:00 Continue
Press (next) to start the set-up assistant.
Remote CTDD 0.0 rpm
Set-up Assistant
Start set-up
Exit and don’t show at power-up
Exit 00:00 Next
12-2 Startup Assistant & Parameters 3AXD50000011888
Table 12-1 Level 1 Parameter Block Definitions Continued
Table 12-1 Initial Start-up / Motor Data and ID Run
In the Date & Time menu, use the to highlight
the value to edit. It is recommended to set the Local CTDD 0.0 rpm
current date & time so that faults & alarms can
provide accurate time stamps. Highlight date and Date & Time
press to edit or (next) to continued. Please enter the current date and time.
Date 01.01.2014
Time 12:34:56
Show date as day.month.year
Show time as 24-hour
Exit 00:00 Next
In the month screen use to select the value
for editing. Use to modify the value. Pressing Local CTDD 0.0 rpm
(save) returns to the date & time menu.
Date
Month day Year
This screen is only visible the first time the Motor
Data assistant is run. 03/20/2014
Thursday
Cancel 00:00 Save
Confirm language selection. Highlight the language
with the and press (continue). Local CTDD 0.0 rpm
Language
Language changes take some time.
Not selected
English
Deutsch
Italiano
Exit 00:00 Next
Unit Selection
Confirm local units. Highlight selection with the
and press (next). Local CTDD 0.0 rpm
Localization
Unit Defaults:
US standard (Imperial)
International (SI)
Exit 00:00 Next
3AXD50000011888 Startup Assistant & Parameters 12-3
Table 12-1 Initial Start-up / Motor Data and ID Run
Highlight the desired unit with the and press
(next). Local CTDD 0.0 rpm
Use to move between the units. Use to
Units
select the value for editing. Change the display units if needed.
Pressing (save) returns to the unit selection Unit Selection
menu. 0000 0000 0001 00011
Tariff currency unit USD
AI1 unit selection V
Back 00:00 Next
Supply Voltage Settings
Press to edit the supply voltage input to the
CTDD drive. Local CTDD 0.0 rpm
Supply voltage
Note: For 460 to 480 V, it is recommended that
supply voltage is set to 440 V to 480 V. Set supply voltage.
Supply voltage 500 V
Back 00:00 Next
Motor Data Settings
Refer to the motor nameplate for the following parameter settings. Whenever possible, enter the values exactly as
shown on the motor nameplate.
Example of a nameplate of a Back-EMF motor: Example of a nameplate of a permanent magnet motor:
WARNING TM
DUTY HP RPM AMPS VOLTS HZ
LR40567
PERMANENT MAGNET MOTOR
WHEN SHAFT IS ROTATED, VOLTAGE WILL BE R CAT SPEC
NO. NO.
GENERATED AT THE MOTOR TERMINALS. C US
SER. NO. FR. INSUL
MEASURED OPEN CIRCUIT VOLTAGE PH.
MAX. SAFE
SPEED AMB. °C MIN. AMB. °C
IS VOLTS AT RPM. DESIGN NO. TYPE ENCL.
000692-000VY
D.E.
000613-006AAP
MOTOR PHASE CURRENT SHOULD NOT S.F. BRG.
O.D.E.
EXCEED AMPS RMS PEAK TO ENCL. MOD. BRG.
MINIMUM AIRFLOW VELOCITY FT. PER MINUTE
AVOID DEMAGNETIZATION.
patent US 7,385,328
PLANT 15
PATENT US 7,880,348 B2
12-4 Startup Assistant & Parameters 3AXD50000011888
Table 12-1 Initial Start-up / Motor Data and ID Run
Highlight the motor value to be edited using
keys. Use to edit the values. Local CTDD 50.0 rpm
Motor data
Use and to change the value of a digit. Use Check the values from the motor’s
and to move the curser left and right.
Press (save) to enter the value. nameplate, and enter them here.
Motor Type PMSM
.
Back EMF voltage 360.0 V
Motor nominal current 1.3 A
Motor nominal speed 500 rpm
Back 00:00 Next
Important! Motor Back EMF voltage (located on Local CTDD 0.0 rpm
the motor nameplate) is critical to the successful
operation of the cooling tower motor. Please record 99.07 Motor Back EMF voltage
this data here for future reference.
000.0 v
Back EMF Voltage:
Motor Serial Number:
Note: Back EMF Voltage is referrred to as
Measured Open Circuit Voltage on the motor 80.0 960.0
nameplate.
Cancel 00:00 Save
Motor ID Run
Autophasing
Local CTDD 50.0 rpm
The drive is now ready to run the motor identification
routine (ID run). During the ID run, the motor is Autophasing
injected with DC current. Autophase stops the rotor Select parameters for autophasing.
prior to the ID run.
Autophasing Current 50%
Note: Autophase time has a default of 15 seconds. Autophasing Time 15 S
It is best to observe the time it takes the fan to stop
moving and use this as an accurate autophase time.
Use the keys to move between selections.
Use to select the value to edit. Back 00:00 Next
3AXD50000011888 Startup Assistant & Parameters 12-5
Table 12-1 Initial Start-up / Motor Data and ID Run
Motor ID Run
Local CTDD 50.0 rpm
The drive is now ready to run the motor identification
routine (ID run). The motor is injected with DC ID run?
current.
None
Standstill ID run
Back 00:00 Next
Use the key to select Standstill ID run and then
press (next).
Local CTDD 50.0 rpm
ID run?
Note: On initial startup, an ID run must be performed None
and Next will not advance to next step. Standstill ID run
Back 00:00 Next
Motor ID Run
Local CTDD 50.0 rpm
No command rotation is given, however with a
permanent magnet motor the shaft could rotate up Press Start for ID run
to half a revolution. When you press Start, the motor is
You must press Local Keypad START to activate ID
injected with DC
Run. Current for about 1 minute, and may
Rotate up to half a
Note: ID Run requires Local control, press Revolution. After the ID run the drive
Loc/Rem if the Keypad does not indicated local
control is active.
stops.
Next is not visible until ID run is performed once. Back 00:00 Next
12-6 Startup Assistant & Parameters 3AXD50000011888
Table 12-1 Initial Start-up / Motor Data and ID Run
The ID run in progress screen will automatically
display showing speed and amps. Local CTDD 50.0 rpm
The screen will also indicate if an ID run has been ID run in progress...
completed before. If not, it will read “none”. If a run
has been completed, it will read “Standstill”. 01.01 Motor speed used 0.00 rpm
01.07 Motor current 0.00 A
99.14 Last ID run performed None
Back 00:00
When ID run is complete, the next screen will be
displayed. Local CTDD 50.0 rpm
ID run in progress...
01.01 Motor speed used 0.00 rpm
01.07 Motor current 0.00 A
99.14 Last ID run performed None
√ ID run done
Exit 00:00
NOTE: If the motor data is incorrect, after pressing ,
the display will indicate check motor parameters. Local CTDD 0.0 rpm
Press (exit) and check that the motor information
is correct. Check the motor param...
The motor parameters are probably
set incorrectly. Check the parameters.
Exit 00:00 Check params
3AXD50000011888 Startup Assistant & Parameters 12-7
Table 12-1 Initial Start-up / Motor Data and ID Run
Direction Test
Local CTDD 50.0 rpm
NOTE: The Autophasing delay occurs everytime the Direction test
motor starts, including direction testing.
Spin the motor to check direction
No, skip the test
Yes, test now
Back 00:00 Next
Use the key to perform a direction test of the
rotation of the motor. Then press (next).
Local CTDD 50.0 rpm
Direction test
Spin the motor to check direction
No, skip the test
Yes, test now
Back 00:00 Next
The following warning message will appear.
Local CTDD 50.0 rpm
Press START to check direction of the motor. Press Start
A screen will appear next asking if the motor is Warning! Until set-up is done, safeties
running in the correct direction. are not activate and motor speed is
limited between 1/3 to 2/3 speed.
Press Start now to start the motor,
then check the direction of rotation.
Back 00:00 Next
Motor set-up is complete.
Local CTDD 50.0 rpm
To exit and save all data, select (Done).
Motor set-up complete
To exit without saving data, select (cancel).
Connect I/O according to the User
Manual.
Cancel 00:00 Done
NOTE: After initial startup sequencing a new power-up will initiate the standard CTDD startup mode (see Table
12-2).
12-8 Startup Assistant & Parameters 3AXD50000011888
12.1.2 Drive Assistant
Selecting drive assistant (CTDD) will display the cooling tower application assistant. After motor data start-up, the
applicaiton is only capable of 2-wire functionality with no options.
Table 12-2 Drive Assistant
Safety
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the safety instructions on the first
pages of the appropriate Hardware manual.
Check the installation. See the installation checklist in the appropriate Hardware manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if there is a risk of damage in case of an incorrect direction of rotation.
Power-Up, Date and Time Settings
Power up the drive.
Main Menu Screen appears.
Select “Assistants” from the main menu.
Select assistant to run. Selecting the CTDD Setup
will display the cooling tower application assistant. Remote CTDD 0.0 rpm
Assistants
Motor Data & ID Run
CTDD Setup
Back 00:00 Select
In the assistant view, press (continue) to enter
the Startup Assistant. Local CTDD 0.0 rpm
Note: To leave the assistant, press (exit) and go Drive Set-up
back to the Home screen.
Use arrow keys and soft keys to
navigate the assistant.
Exit 00:00 Continue
3AXD50000011888 Startup Assistant & Parameters 12-9
Table 12-2 Drive Assistant
Press (next) to start the set-up assistant.
Remote CTDD 0.0 rpm
“Restore ....” will reload all default parameters
except for motor data. Set-up Assistant
Start set-up
Restore default CTDD parameters.
Exit 00:00 Next
In the Date & Time menu, use the to highlight
the value to edit. It is recommended to set the Local CTDD 0.0 rpm
current date & time so that faults & alarms can
provide accurate time stamps. Highlight date and Date & Time
press to edit or (next) to continued. Please enter the current date and time.
Date 01.01.2014
Time 12:34:56
Show date as day.month.year
Show time as 24-hour
Exit 00:00 Next
In the month screen use to select the value
for editing. Use to modify the value. Pressing Local CTDD 0.0 rpm
(save) returns to the date & time menu.
Date
(See Motor Data)
Month day Year
03/20/2014
Thursday
Cancel 00:00 Save
Highlight the language with the and press
Local CTDD 0.0 rpm
(continued).
Language
Language changes take some time.
Not selected
English
Deutsch
Italiano
Exit 00:00 Next
NOTE: After editing all desired date & time values, press (next) to continue.
12-10 Startup Assistant & Parameters 3AXD50000011888
Table 12-2 Drive Assistant
Drive Limit Settings
The CTDD will automatically set limits according to
motor data entered. For most CTDD applications, Local CTDD 50.0 rpm
the default values are acceptable. However, values
are adjustable within Limits: Limits
Minimum Speed ≥ 10% Motor Speed CT Minimum Speed 50.00 rpm
Maximum Speed ≤ Motor Speed Maximum speed 500.00 rpm
Constant Speed 2 set to 0.00 (adjustable) Minimum torque -30.0 %
Minimum Torque 1 set to -30% (adjustable) Maximum torque 110.0 %
Maximum Torque 1 set to 110% (adjustable)
Acceleration time 1
Back 00:00 Next
Use the to highlight the ramp rate to be
adjusted. Press to enter the edit screen once Local CTDD 50.0 rpm
highlighted or (next) if the default value is
acceptable. Limits
Maximum torque 110.0 %
Acceleration time 1 100.000 s
Deceleration time 1 100.000 s
Acceleration time 2 100.000 s
Deceleration time 2 100.000 s
Back 00:00 Next
Naming the Drive
Local CTDD 50.0 rpm
The default drive name is CTDD. Use to edit the
drive name or (next) to continue. Naming the drive
The name will show at the top of the
panel screen, making it easier to see
which motor this drive controls.
Drive name CTDD
Back 00:00 Next
Selecting Operating Mode
Select Operating Mode
Local CTDD 50.0 rpm
Operating modes are sets of default wire and
parameters suitable for most CTDD applications. Select Operating Mode
The active operating mode is displayed, (2-wire) Select mode below.
default. If this is correct, press (next). To edit Operating Mode 2-Wire
the operating mode press .
Caution: Ensure drive is stopped and in Local before
changing mode. Drive could unexpectedly start
when changing mode.
Back 00:00 Next
3AXD50000011888 Startup Assistant & Parameters 12-11
Table 12-2 Drive Assistant
Highlight the operating mode suitable to the
application and press save. Local CTDD 50.0 rpm
Press (save) to select. 76.03 Operating Mode
If mode was changed, cycle power to drive after [0]Custom
setup is complete. [1] 2-Wire
[7] 3-Wire
[8] PID
[9] Fieldbus
[10] Keypad
Cancel 00:00 Save
Additional Settings & Parameter Backup
Trickle Current Function
Local CTDD 50.0 rpm
Primary purpose is to prevent fan rotation during
standby condition and to prevent condensation
Trickle Current
Set parameters for Trickle Current.
in the motor. Use the to enable the function in
software. Highlight enable or fieldbus and press Enable Disabled
(save). Use to highlight trickle power and Trickle Power 100W
to set the level. Refer to Chapter 10 or parameter Trickle Time Delay 1 min
group 74 for proper setup of this function. When
finished, press (next) to continue.
Back 00:00 Next
Trickle Selection
Local ACS880 0.0 rpm
Select the I/O or Communication Link that will
Enable the Trickle Current Function.
74.01 Trickle Selection
[0] DISABLE
If you select “ENABLE”, the Trickle Current Function [1] ENABLE
will be Enabled whenever the Drive is not running. [2] DI01
[3] FBA
[4] EFB
Cancel 00:00 Save
De-Ice
Local CTDD 50.0 rpm
This is a Cooling Tower mode to run the tower in
reverse at a slow speed to prevent ice build up. Use De-Ice
the to highlight the setting and to access Set parameters for De-ice.
level values. Enable Disabled
De-Ice Speed 30%
Refer to Chapter 10 or parameter group
75 for proper setup. When finished, press
Run Time 1 min
(next) to continue. Minimum torque 1 -30.0 %
Back 00:00 Next
12-12 Startup Assistant & Parameters 3AXD50000011888
Table 12-2 Drive Assistant
De-Ice Selection
Local ACS880 0.0 rpm
Select the I/O or Communication Link that will
Enable De-Ice mode.
75.01 De-Ice Selection
[0] DISABLE
[1] DI01
[2] FBA
[3] EFB
Cancel 00:00 Save
Backup
Local CTDD 50.0 rpm
Copies all settings into a backup file stored in the
control panel. Press to highlight Backup and Make backup?
to begin the Backup. Copies all settings into a backup file
stored in the control panel. To restore
a backup, go to Menu > Backups.
Not now
Backup
Back 00:00 Next
Backup Status
Local CTDD 0.0 rpm
A status screen indicates progress.
Backing up data from drive
Press (back) to backout and exit to home menu.
Remote ACS880 600.0 rpm
Set-up complete
I/O should be connected as follows:
Start/Stop: Digital Input DI 1
Speed reference: Analog Input AI 1 90-10 V)
Back 00:00 Done
Control Signal Settings
Check the positions of jumpers J1 and J2 on the control unit of the drive. These jumpers determine whether
analog inputs AI1 and AI2 are current or voltage.
3AXD50000011888 Startup Assistant & Parameters 12-13
Table 12-2 Drive Assistant
Check/adjust the following parameters.
12.15 AI1 unit selection
Set this to either mA or V corresponding to the setting of jumper J1.
12.17 AI1 min
12.18 AI1 max
12.19 AI1 scaled at AI1 min
12.20 AI1 scaled at AI1 max
The default input for speed reference is analog input AI1. (This is controlled by the parameters in group 22.)
Parameters 12.17 and 12.18 set the low and high limits of the analog input signal. Scaling parameters 12.19
and 12.20 define the internal signal levels that correspond to these limits as follows:
The corresponding parameters for analog input AI2 are 12.27 - 12.30. Analog input 2 is only available in
“Custom” mode as a speed reference.
13.12 AO1 source
13.17 AO1 source min
13.18 AO1 source max
13.19 AO1 out at AI1 src min
13.20 AO1 out at AI1 src max
Parameter 13.12 selects the source for analog output AO1 (by default, motor speed in rpm).
Parameters 13.17 and 13.18 set low and high source signal values that correspond to the actual analog output
values defined by parameters 13.19 and 13.20.
12-14 Startup Assistant & Parameters 3AXD50000011888
Table 12-2 Drive Assistant
46.10 Speed scaling
23.11 Ramp set selection
23.12 Acceleration time 1
23.13 Deceleration time 1
23.14 Acceleration time 2
23.15 Deceleration time 2
You can define two different sets of acceleration/deceleration ramps. The source that switches between the
two sets is selected by parameter 23.11.
Each acceleration/deceleration time set in parameters 23.12 - 23.15 refers to the time it takes for the drive to
accelerate or decelerate between 0 and scaling speed (parameter 46.10).
30.11 Minimum speed
30.12 Maximum speed
30.17 Maximum current
30.19 Minimum torque
30.20 Maximum torque
Check, and set if necessary, the limits for motor speed, current and torque.
Start the drive with a positive (forward) speed reference:
• From control panel (Local control): In the Home view,press (Options), select Reference, adjust the
reference using the , , , and keys, press Save, and press the Start button.
• From I/O: In Remote control, adjust analog input AI1 (reference), switch digital input DI1 to 1 (start). DI2 for
reverse is only available in “Custom” mode.
The ACS880+N5350 utilizes various parameters to determine its operation. Many of these parameters will not need adjusting
for most applications, but are provided to allow for a user to customize the operation of the control if desired.
Table 12-3 Terms and Abbreviations
Term Definition
Actual Signal Type of parameter that is the result of a measurement or calculation by the drive, or
contains status information. Most actual signals are read-only, but some (especially
counter-type actual signals) can be reset.
Def (In the following table, shown on the same row as the parameter name)
The default value of a parameter when used in the CTDD macro.
FbEq16 (In the following table, shown on the same row as the parameter range, or for each
selection)
A dash (-) indicates that the parameter is not accessible in 16-bit format.
Other The value is taken from another parameter.
Choosing “Other” displays a parameter list in which the user can specify the source
parameter.
Other [bit] The value is taken from a specific bit in another parameter.
Choosing “Other” displays a parameter list in which the user can specify the source
parameter and bit.
Parameter Either a user-adjustable operating instruction for the drive, or an actual signal.
p.u. Per unit
3AXD50000011888 Startup Assistant & Parameters 12-15
12.2 Level 1 Parameters (Advanced Prog, Level 1 Blocks)
Table 12-4 Level 1 Parameter Block Definitions
Parameter (Number)
Block Title Descriptions
Selection (Value)
ACTUAL VALUES Basic signals for monitoring the drive. All parameters in this group are read-only unless otherwise noted.
MOTOR SPEED USED (01.01) Default: Read Only
Range: -30000.00 to +30000.00 RPM
Measured or estimated motor speed depending on which type of
feedback is used (see parameter 90.41 Motor feedback selection). A
filter time constant for this signal can be defined by parameter 46.11
Filter time motor speed.
MOTOR SPEED ESTIMATED Default: Read Only
(01.02) Range: -30000.00 to +30000.00 RPM
Estimated motor speed in rpm. A filter time constant for this signal can
be defined by parameter 46.11 Filter time motor speed.
MOTOR SPEED % (01.03) Default: 10 = 1%
Range: -1000.00 to +1000.00%
Measured or estimated motor speed. Shows the value of 01.01 Motor
speed used in percent of the synchronous speed of the motor.
OUTPUT FREQUENCY (01.06) Default: Read Only
Range: -500.00 to +500.00 Hz
Estimated drive output frequency in Hz. A filter time constant for this
signal can be defined by parameter 46.12 Filter time output frequency.
MOTOR CURRENT (01.07) Default: Read Only
Range: 0.00 to 30000.00 A
Measured (absolute) motor current in A.
MOTOR CURRENT % OF Default: Read Only
MOTOR NOM (01.08) Range: 0.0 to 1000.0 %
Measured motor current in %.
MOTOR TORQUE % (01.10) Default: Read Only
Range: -1600.0 to +1600.0 %
Motor torque in percent of the nominal motor torque. See also
parameter 01.30 Nominal torque scale.
A filter time constant for this signal can be defined by parameter 46.13
Filter time motor torque.
DC VOLTAGE (01.11) Default: Read Only
Range: 0.00 - 2000.00 V
Measured DC link voltage.
OUTPUT VOLTAGE (01.13) Default: Read Only
Range: 0 - 2000 V
Calculated motor voltage in VAC
Fieldbus Equivalent: 10 = 1 V
OUTPUT POWER (01.14) Default: Read Only
Range: -32768 to +32767 kW or HP
Drive output power. The unit is selected by parameter 96.16 Unit
selection. A filter time constant for this signal can be defined by
parameter 46.14 Filter time power out.
OUTPUT POWER % OF Default: Read Only
MOTOR NOM (01.15) Range: -300.00 to +300.00%
Shows the value of 01.14 Output power in percent of the nominal
power of the motor.
12-16 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
ACTUAL VALUES MOTOR SHAFT POWER Default: Read Only
(Continued) (01.17) Range: -32768 to +32767 kW or HP
Estimated mechanical power at motor shaft. The unit is selected by
parameter 96.16 Unit selection. A filter time constant for this signal can
be defined by parameter 46.14 Filter time power out.
INVERTER GWh COUNTER Default: Read Only
(01.18) Range: 0 - 65535 GWh
Energy in GWh - Amount of energy that has passed through the drive
(in either direction) in full gigawatt-hours. The minimum value is zero.
INVERTER MWh COUNTER Default: Read Only
(01.19) Range: 0 - 999 MWh
Energy in MWh - Amount of energy that has passed through the drive
(in either direction) in full megawatt-hours. Whenever the counter rolls
over, 01.18 Inverter GWh counter is incremented. The minimum value
is zero.
INVERTER kWh COUNTER Default: Read Only
(01.20) Range: 0 - 999 kWh
Energy in kWh - Amount of energy that has passed through the drive
(in either direction) in full kilowatt-hours. Whenever the counter rolls
over, 01.19 Inverter MWh counter is incremented.The minimum value
is zero.
Fieldbus Equivalent: 10 = 1kWh
U-PHASE CURRENT (01.21) Default: Read Only
Range: -30000.00 to +30000.00 A
Measured U-phase current.
V-PHASE CURRENT (01.22) Default: Read Only
Range: -30000.00 to +30000.00 A
Measured V-phase current.
W-PHASE CURRENT (01.23) Default: Read Only
Range: -30000.00 to +30000.00 A
Measured W-phase current.
FLUX ACTUAL % (01.24) Default: Read Only
Range: -0 to +200%
Used flux reference in percent of nominal flux of motor.
SPEED CHANGE RATE (01.29) Default: Read Only
Range: -15000 to +15000 RPM
Rate of actual speed change. Positive values indicate acceleration,
negative values indicate deceleration.
See also parameters 31.32 Emergency ramp supervision, 31.33
Emergency ramp supervision delay, 31.37 Ramp stop supervision and
31.38 Ramp stop supervision delay.
NOMINAL TORQUE SCALE Default: Read Only
(01.30) Range: 0.0000 - lb-ft
Nominal Torque - Torque that corresponds to 100% of nominal motor
torque.
The unit is selected by parameter 96.16 Unit selection.
Note: This value is copied from parameter 99.12 Motor nominal torque
if entered. Otherwise the value is calculated from other motor
data.
AMBIENT TEMPERATURE Default: Read Only
(01.31) Range: -32768 to +327670C or 0F
Measured temperature of incoming cooling air. The unit is selected by
parameter 96.16 Unit selection.
3AXD50000011888 Startup Assistant & Parameters 12-17
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
ACTUAL VALUES INVERTER GWh Default: Read Only
(Continued) REGENERATING (01.32) Range: 0 to 32767 GWh
Motoring energy in GWh. Amount of energy that has passed through
the drive (towards the supply) in full gigawatt-hours. The minimum
value is zero.
INVERTER MWh Default: Read Only
REGENERATING (01.33) Range: 0 to 999 MWh
Motoring energy in MWh. Amount of energy that has passed through
the drive (towards the supply) in full megawatt-hours. Whenever the
counter rolls over, 01.32 Inverter GWh regenerating is incremented.
The minimum value is zero.
INVERTER kWh Default: Read Only
REGENERATING (01.34) Range: 0 to 999 kWh
Motoring energy in kWh. Amount of energy that has passed through
the drive (towards the supply) in full kilowatt-hours. Whenever the
counter rolls over, 01.33 Inverter MWh regenerating is incremented.
The minimum value is zero.
MOT - REGEN ENERGY GWh Default: Read Only
(01.35) Range: -32768 to +32767 GWh
Motoring energy in GWh. Amount of net energy (motoring energy
- regenerating energy) that has passed through the drive in full
gigawatthours.
MOT - REGEN ENERGY MWh Default: Read Only
(01.36) Range: -999 to +999 MWh
Motoring energy in MWh. Amount of net energy (motoring energy
- regenerating energy) that has passed through the drive in full
megawatthours. Whenever the counter rolls over, 01.35 Mot - regen
energy GWh is incremented or decremented.
MOT - REGEN ENERGY kWh Default: Read Only
(01.37) Range: -999 to +999 kWh
Motoring energy in kWh. Amount of energy (motoring energy -
regenerating energy) that has passed through the drive in full kilowatt-
hours. Whenever the counter rolls over, 01.36 Mot - regen energy MWh
is incremented or decremented.
ABS MOTOR SPEED USED Default: Read Only
(01.61) Range: 0.00 to 30000.00 RPM
Measured or estimated motor speed. Absolute value of 01.01 Motor
speed used.
ABS MOTOR SPEED % (01.62) Default: Read Only
Range: 0.00 to 1000.00%
Measured or estimated motor speed. Absolute value of 01.03 Motor
speed %.
ABS OUTPUT FREQUENCY Default: Read Only
(01.63) Range: 0.00 to 500.00 Hz
Estimated output frequency. Absolute value of 01.06 Output frequency.
ABS MOTOR TORQUE (01.64) Default: Read Only
Range: 0.0 to 1600.0%
Motor torque. Absolute value of 01.10 Motor torque.
ABS OUTPUT POWER (01.65) Default: Read Only
Range: 0.00 to 32767.00 kW or HP
Output power. Absolute value of 01.14 Output power.
12-18 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
ACTUAL VALUES ABS OUTPUT POWER % Default: Read Only
(Continued) MOTOR NOM (01.66) Range: 0.00 to 300.00%
Output power. Absolute value of 01.15 Output power % of motor nom.
ABS MOTOR SHAFT POWER Default: Read Only
(01.68) Range: 0.00 to 32767.00 kW or HP
Motor shaft power. Absolute value of 01.17 Motor shaft power.
INPUT Values of references received from various sources. All parameters in this group are read-only unless
REFERENCES otherwise noted. These parameters are for Fieldbus only.
FB A REFERENCE 1 (03.05) Default: Read Only
“Fieldbus” mode reference Range: -100000.00 to +100000.00
Reference 1 received through fieldbus adapter A.
FB A REFERENCE 2 (03.06) Default: Read Only
Range: -100000.00 to +100000.00
Reference 2 received through fieldbus adapter A.
FB B REFERENCE 1 (03.07) Default: Read Only
Range: -100000.00 to +100000.00
Reference 1 received through fieldbus adapter B.
FB B REFERENCE 2 (03.08) Default: Read Only
Range: -100000.00 to +100000.00
Reference 2 received through fieldbus adapter B.
EFB REFERENCE 1 (03.09) Default: Read Only
Range: -30000.00 to +30000.00
Reference 1 received through the embedded fieldbus interface. Scaled
reference 1 received through the embedded fieldbus interface. The
scaling is defined by 58.26 EFB ref1 type.
EFB REFERENCE 2 (03.10) Default: Read Only
Range: -30000.00 to +30000.00
Reference 2 received through the embedded fieldbus interface. Scaled
reference 2 received through the embedded fieldbus interface. The
scaling is defined by 58.27 EFB ref2 type.
WARNINGS AND Information on warnings and faults that occurred last. All parameters in this group are read-only unless
FAULTS otherwise noted.
TRIPPING FAULT (04.01) Default: Read Only
Range: 0000h - FFFFh
Code of the 1st active fault (the fault that caused the current trip).
ACTIVE FAULT 2 (04.02) Default: Read Only
Range: 0000h - FFFFh
Code of the 2nd active fault.
ACTIVE FAULT 3 (04.03) Default: Read Only
Range: 0000h - FFFFh
Code of the 3rd active fault.
ACTIVE FAULT 4 (04.04) Default: Read Only
Range: 0000h - FFFFh
Code of the 4th active fault.
ACTIVE FAULT 5 (04.05) Default: Read Only
Range: 0000h - FFFFh
Code of the 5th active fault.
3AXD50000011888 Startup Assistant & Parameters 12-19
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
WARNINGS ACTIVE WARNING 1 (04.06) Default: Read Only
AND FAULTS Range: 0000h - FFFFh
(Continued)
Code of the 1st active warning.
ACTIVE WARNING 2 (04.07) Default: Read Only
Range: 0000h - FFFFh
Code of the 2nd active warning.
ACTIVE WARNING 3 (04.08) Default: Read Only
Range: 0000h - FFFFh
Code of the 3rd active warning.
ACTIVE WARNING 4 (04.09) Default: Read Only
Range: 0000h - FFFFh
Code of the 4th active warning.
ACTIVE WARNING 5 (04.10) Default: Read Only
Range: 0000h - FFFFh
Code of the 5th active warning.
LATEST FAULT (04.11) Read Only
Range: 0000h - FFFFh
Code of the 1st stored (non-active) fault.
2ND LATEST FAULT (04.12) Default: Read Only
Range: 0000h - FFFFh
Code of the 2nd stored (non-active) fault.
3RD LATEST FAULT (04.13) Default: Read Only
Range: 0000h - FFFFh
Code of the 3rd stored (non-active) fault.
4TH LATEST FAULT (04.14) Default: Read Only
Range: 0000h - FFFFh
Code of the 4th stored (non-active) fault.
5TH LATEST FAULT (04.15) Default: Read Only
Range: 0000h - FFFFh
Code of the 5th stored (non-active) fault.
LATEST WARNING (04.16) Default: Read Only
Range: 0000h - FFFFh
Code of the 1st stored (non-active) warning.
2ND LATEST WARNING Default: Read Only
(04.17) Range: 0000h - FFFFh
Code of the 2nd stored (non-active) warning.
3RD LATEST WARNING Default: Read Only
(04.18) Range: 0000h - FFFFh
Code of the 3rd stored (non-active) warning.
4TH LATEST WARNING Default: Read Only
(04.19) Range: 0000h - FFFFh
Code of the 4th stored (non-active) warning.
5TH LATEST WARNING (04.20) Default: Read Only
Range: 0000h - FFFFh
Code of the 5th stored (non-active) warning.
12-20 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
WARNINGS EVENT WORD 1 (04.40) Default: Read Only
AND FAULTS Range: 0000h - FFFFh
(Continued)
User-defined event word. This word collects the status of the events
(warnings, faults or pure events) selected by parameters 04.41 to
04.72.
For each event, an auxiliary code can optionally be specified for
filtering. This parameter is read-only.
Bit Name Description
1 = Event selected by parameters 04.41 (and 04.42) is
0 User bit 0
active
1 = Event selected by parameters 04.43 (and 04.44) is
1 User bit 1
active
--- --- ---
1 = Event selected by parameters 04.71 (and 04.72) is
15 User bit 15
active
EVENT WORD 1 BIT 0 CODE Default: 0000h
(04.41) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 0 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 0 AUX Default: 0000 0000h
CODE (04.42) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 1 CODE Default: 0000h
(04.43) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 1 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 1 AUX Default: 0000 0000h
CODE (04.44) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 2 CODE Default: 0000h
(04.45) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 2 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 2 AUX Default: 0000 0000h
CODE (04.46) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
3AXD50000011888 Startup Assistant & Parameters 12-21
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
WARNINGS EVENT WORD 1 BIT 3 CODE Default: 0000h
AND FAULTS (04.47) Range: 0000h - FFFFh
(Continued)
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 3 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 3 AUX Default: 0000 0000h
CODE (04.48) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 4 CODE Default: 0000h
(04.49) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 4 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 4 AUX Default: 0000 0000h
CODE (04.50) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 5 CODE Default: 0000h
(04.51) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 5 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 5 AUX Default: 0000 0000h
CODE (04.52) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 6 CODE Default: 0000h
(04.53) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 6 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 6 AUX Default: 0000 0000h
CODE (04.54) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
12-22 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
WARNINGS EVENT WORD 1 BIT 7 CODE Default: 0000h
AND FAULTS (04.55) Range: 0000h - FFFFh
(Continued)
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 7 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 7 AUX Default: 0000 0000h
CODE (04.56) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 8 CODE Default: 0000h
(04.57) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 8 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 8 AUX Default: 0000 0000h
CODE (04.58) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 9 CODE Default: 0000h
(04.59) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 9 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 9 AUX Default: 0000 0000h
CODE (04.60) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 10 CODE Default: 0000h
(04.61) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 10 of 04.40 Event
word 1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 10 AUX Default: 0000 0000h
CODE (04.62) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
3AXD50000011888 Startup Assistant & Parameters 12-23
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
WARNINGS EVENT WORD 1 BIT 11 CODE Default: 0000h
AND FAULTS (04.63) Range: 0000h - FFFFh
(Continued)
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 11 of 04.40 Event
word 1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 11 AUX Default: 0000 0000h
CODE (04.64) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 12 CODE Default: 0000h
(04.65) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 12 of 04.40 Event
word 1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 12 AUX Default: 0000 0000h
CODE (04.66) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 13 CODE Default: 0000h
(04.67) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 13 of 04.40 Event
word 1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 13 AUX Default: 0000 0000h
CODE (04.68) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 14 CODE Default: 0000h
(04.69) Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 14 of 04.40 Event
word 1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 14 AUX Default: 0000 0000h
CODE (04.70) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
12-24 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
WARNINGS EVENT WORD 1 BIT 15 CODE Default: 0000h
AND FAULTS (04.71) Range: 0000h - FFFFh
(Continued)
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 15 of 04.40 Event
word 1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 15 AUX Default: 0000 0000h
CODE (04.72) Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
DIAGNOSTICS Various run-time-type counters and measurements related to drive maintenance. All parameters in this
group are read-only unless otherwise noted.
ON-TIME COUNTER (05.01) Default: Read Only
Range: 0 - 65535 d
On-time counter - The counter runs when the drive is powered.
RUN-TIME COUNTER (05.02) Default: Read Only
Range: 0 - 65535 d
Motor run-time counter - The counter runs when the inverter
modulates.
FAN ON-TIME COUNTER Default: Read Only
(05.04) Range: 0 - 65535 d
Cooling fan run-time counter - Running time of the drive cooling fan.
Can be reset from the control panel by keeping Reset depressed for
over 3 sec.
INVERTER TEMPERATURE Default: Read Only
(05.11) Range: -40.0 to +160.0 %
Drive temperature in percent - Estimated drive temperature in percent
of fault limit. The fault limit varies according to the type of the drive.
0.0% = 0°C (32°F); 100.0% = Fault limit
DIAGNOSTIC WORD 3 (05.22) Default: Read Only
Range: 0000h - FFFFh
Diagnostic word 3.
Bit Name Value
0 - 10 Reserved
11 Fan command 1 = Drive fan is rotating above idle speed.
12 - 15 Reserved
MAIN FAN SERVICE Default: Read Only
COUNTER (05.41) Range: 0 to 150%
Main cooling fan age. Displays the age of the main cooling fan as a
percentage of its estimated lifetime. The estimate is based on the duty,
operating conditions and other operating parameters of the fan. When
the counter reaches 100%, a warning (A8C0 Fan service counter) is
generated.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
3AXD50000011888 Startup Assistant & Parameters 12-25
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
DIAGNOSTICS AUX. FAN SERVICE COUNTER Default: Read Only
(Continued) (05.42) Range: 0 to 150%
Auxiliary cooling fan age. Displays the age of the auxiliary cooling fan
as a percentage of its estimated lifetime. The estimate is based on
the duty, operating conditions and other operating parameters of the
fan. When the counter reaches 100%, a warning (A8C0 Fan service
counter) is generated.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
CONTROL AND All parameters in this group are read-only unless otherwise noted.
STATUS WORDS These parameters are for Fieldbus only. Main Control Word only used in “Custom” mode.
MAIN CONTROL WORD Default: Read Only
(06.01) Range: 0000h - FFFFh
Bit CTD Command Word
0 Trickle Enable
1 De-Ice Enable
2 CTD Run
When Fieldbus is selected in parameter 74.1, Trickle Current is enabled
by setting parameter 9.1, “bit 0” High.
When Fieldbus is selected in parameter 75.1, De-Ice is enabled by
setting parameter 9.1, “bit 1” High.
When Fieldbus mode is selected in parameter 76.3 and DI2 is on, the
drive will run by setting parameter 9.1, “bit 2” High.
To get this CTD Command Word to work, FBA A data out 1, parameter
53.1 must point to parameter 9.1. Other fieldbus settings are made
based on the type of fieldbus used.
APPLICATION CONTROL Default: Read Only
WORD (06.02) Range: 0000h - FFFFh
Application program control word. The drive control word received
from the application program (if any).
This parameter is read-only.
FBA A TRANSPARENT Default: Read Only
CONTROL WORD (06.03) Range: 00000000h - FFFFFFFFh
Control word received through fieldbus adapter A. Displays the
unaltered control word received from the PLC through fieldbus
adapter A when a transparent communication profile is selected eg.
by parameter group 51 FBA A settings. See section Control word and
Status word.
This parameter is read-only.
FBA B TRANSPARENT Default: Read Only
CONTROL WORD (06.04) Range: 00000000h - FFFFFFFFh
Control word received through fieldbus adapter B. Displays the
unaltered control word received from the PLC through fieldbus
adapter B when a transparent communication profile is selected eg.
by parameter group 54 FBA B settings. See section Control word and
Status word.
This parameter is read-only.
EFB TRANSPARENT Default: Read Only
CONTROL WORD (06.05) Range: 00000000h - FFFFFFFFh
Control word received through the embedded fieldbus interface.
Displays the unaltered control word received from the PLC through
the embedded fieldbus interface when a transparent communication
profile is selected in parameter 58.25 Control profile. See section The
Transparent profile.
This parameter is read-only.
12-26 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND MAIN STATUS WORD (06.11) Default: Read Only
STATUS WORDS Range: 0000h - FFFFh
(Continued)
Main status word of the drive. This parameter is read-only.
Bit Name Value Description
Ready to 1 Ready to switch ON
0
switch ON 0 Not ready to switch ON
1 Ready to operate
1 Ready run
0 OFF1 active
1 Operation enabled
2 Ready ref
0 Operation inhibited
1 Fault
3 Tripped
0 No fault
1 OFF2 inactive
4 OFF2 inactive
0 OFF2 active
1 OFF3 inactive
5 OFF3 inactive
0 OFF3 active
Switch-on 1 Switch-on inhibited
6
inhibited 0 --
1 Warning active
7 Warning
0 No warning active
Operating - Actual value equals reference = is within
1
tolerance limits (see parameters 46.21 - 46.23)
8 At setpoint
Actual value differs from reference = is outside tolerance
0
limits
1 Drive control location: Remote (EXT1 or EXT2)
9 Remote
0 Drive control location: Local
Trickle Current 0 Trickle Current OFF
10
Active 1 Trickle Current ON
De-Ice Mode 0 De-Ice Mode OFF
11
Active 1 De-Ice Mode ON
0 CTD Drive Not Running
12 CTD Run
1 CTD Drive Running
0 CTD Autophase OFF
13 CTD HOLD
1 CTD Autophase ON
14 User bit 3 - See parameter 06.33 MSW bit 14 sel
15 Reserved
3AXD50000011888 Startup Assistant & Parameters 12-27
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND DRIVE STATUS WORD 1 Default: Read Only
STATUS WORDS (06.16) Range: 0000h - FFFFh
(Continued)
Drive status word 1. This parameter is read-only.
Bit Name Description
1 = Both run enable (see par. 20.12) and start enable (20.19)
0 Enabled signals are present
Note: This bit is not affected by the presence of a fault
1 = Start inhibited - See parameters 06.18 and 06.25 for the
1 Inhibited
source of the inhibiting signal
2 DC charged 1 = DC circuit has been charged
Ready to
3 1 = Drive is ready to receive a start command
start
Following
4 1 = Drive is ready to follow given reference
reference
5 Started 1 = Drive has been started
6 Modulating 1 = Drive is modulating (output stage is being controlled)
7 Limiting 1 = Any operating limit (speed, torque, etc.) is active
8 Local control 1 = Drive is in local control
9 Network ctrl 1 = Drive is in network control
10 Ext1 active 1 = Control location Ext1 active
11 Ext2 active 1 = Control location Ext2 active
12 Reserved
13 Start request 1 = Start requested
14-15 Reserved
DRIVE STATUS WORD 2 Default: Read Only
(06.17) Range: 0000h - FFFFh
Drive status word 2. This parameter is read-only.
Bit Name Description
Identification run
0 1 = Motor identification (ID) run has been performed
done
1 Magnetized 1 = The motor has been magnetized
2 Torque control 1 = Torque control mode active
3 Speed control 1 = Speed control mode active
4 Power control 1 = Power control mode active
Safe reference 1 = A “safe” reference is being applied by functions such as
5
active parameters 49.05 and 50.02
Last speed 1 = A “last speed” reference is being applied by functions such as
6
active parameters 49.05 and 50.02
7 Loss of reference 1 = Reference signal lost
Emergency stop
8 1 = Emergency stop failed (see parameters 31.32 and 31.33)
failed
9 Jogging active 1 = Jogging enable signal is on
1 = Actual speed, frequency or torque equals or exceeds limit
10 Above limit (defined by parameters 46.31 - 46.33) - Valid in both directions of
rotation
Emergency stop 1 = An emergency stop command signal is active, or the drive is
11
active stopping after receiving an emergency stop command
12 Reduced run 1 = Reduced run active (see section Reduced run function)
13 Reserved
14 Stop failed 1 = Stopping failed (see parameters 31.37 and 31.38)
15 Reserved
12-28 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND START INHIBIT STATUS Default: Read Only
STATUS WORDS WORD (06.18) Range: 0000h - FFFFh
(Continued)
Start inhibit status word. This word specifies the source of the
inhibiting signal that is preventing the drive from starting. The
conditions marked with an asterisk (*) only require that the start
command is cycled. In all other instances, the inhibiting condition must
be removed first.
See also parameter 06.25 Drive inhibit status word 2, and 06.16 Drive
status word 1, bit 1. This parameter is read-only.
Bit Name Description
1 = DC voltage is missing or drive has not been parametrized
0 Not ready run
correctly - Check the parameters in groups 95 and 99
1 Ctrl location changed * 1 = Control location has changed
2 SSW inhibit 1 = Control program is keeping itself in inhibited state
3 Fault reset * 1 = A fault has been reset
4 Lost start enable 1 = Start enable signal missing
5 Lost run enable 1 = Run enable signal missing
6 FSO inhibit 1 = Operation prevented by FSO-xx safety functions module
7 STO 1 = Safe torque off active
Current calibration
8 * 1 = Current calibration routine has finished
ended
9 ID run ended * 1 = Motor identification run has finished
10 Auto phase ended * 1 = Autophasing routine has finished
11 Em Off1 1 = Emergency stop signal (mode Off1)
12 Em Off2 1 = Emergency stop signal (mode Off2)
13 Em Off3 1 = Emergency stop signal (mode Off3)
14 Auto reset inhibit 1 = The autoreset function is inhibiting operation
15 Jogging active 1 = The jogging enable signal is inhibiting operation
SPEED CONTROL STATUS Default: Read Only
WORD (06.19) Range: 0000h - FFFFh
Speed control status word. This parameter is read-only.
Bit Name Description
1 = Drive is running at zero speed, ie. the absolute value of par.
90.01 Motor speed for control has remained below 21.06 Zero
speed limit for longer than 21.07 Zero speed delay.
Notes:
0 Zero speed • This bit is not updated when mechanical brake control is
enabled by par. 44.06 and the drive is modulating.
• During a ramp stop when the drive is running forward, the
delay count runs whenever [90.01] < [21.06]. From the reverse
direction, the delay count runs whenever 90.01 > -[21.06].
1 = Drive is running in forward direction above zero speed limit,
1 Forward
ie. [90.01] > +[21.06]
1 = Drive is running in reverse direction above zero speed limit,
2 Reverse
ie. [90.01] < -[21.06]
3 Out of window 1 = Speed error window control active (see par. 24.41)
1 = Estimated speed feedback used in motor control, ie.
Internal speed estimated speed is selected by par. 90.41 or 90.46, or selected
4
feedback encoder has faulted (par. 90.45)
0 = Encoder 1 or 2 used for speed feedback
1 = Encoder 1 used for speed feedback in motor control
Encoder 1
5 0 = Encoder 1 faulted or not selected as source of speed
feedback
feedback (see par. 90.41 and 90.46)
1 = Encoder 2 used for speed feedback in motor control
Encoder 2
6 0 = Encoder 2 faulted or not selected as source of speed
feedback
feedback (see par. 90.41 and 90.46)
Any constant 1 = A constant speed or frequency has been selected; see par.
7
speed request 06.20
Follower speed 1 = Minimum limit of speed correction (in a speed-controlled
8
corr min lim follower) has been reached (see par. 23.39 - 23.41)
Follower speed 1 = Maximum limit of speed correction (in a speed-controlled
9
corr max lim follower) has been reached (see par. 23.39 - 23.41)
10-15 Reserved
3AXD50000011888 Startup Assistant & Parameters 12-29
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND CONSTANT SPEED STATUS Default: Read Only
STATUS WORDS WORD (06.20) Range: 0000h - FFFFh
(Continued)
Constant speed/frequency status word. Indicates which constant
speed or frequency is active (if any). See also parameter 06.19 Speed
control status word, bit 7, and section Constant speeds/frequencies.
This parameter is read-only.
Bit Name Description
0 Constant speed 1 1 = Constant speed or frequency 1 selected
1 Constant speed 2 1 = Constant speed or frequency 2 selected
2 Constant speed 3 1 = Constant speed or frequency 3 selected
3 Constant speed 4 1 = Constant speed or frequency 4 selected
4 Constant speed 5 1 = Constant speed or frequency 5 selected
5 Constant speed 6 1 = Constant speed or frequency 6 selected
6 Constant speed 7 1 = Constant speed or frequency 7 selected
7-15 Reserved
DRIVE STATUS WORD 3 Default: Read Only
(06.21) Range: 0000h - FFFFh
Drive status word 3. This parameter is read-only.
Bit Name Description
0 DC hold active 1 = DC hold is active (see par. 21.08)
Post-magnetizing
1 1 = Post-magnetizing is active (see par. 21.08)
active
Motor pre-heating
2 1 = Motor pre-heating is active (see par. 21.14)
active
3 PM smooth start active Reserved
4-15 Reserved
CONSTANT SPEED STATUS Default: Read Only
WORD (06.25) Range: 0000h - FFFFh
Drive inhibit status word 2. This word specifies the source of the
inhibiting signal that is preventing the drive from starting.
See also parameter 06.18 Start inhibit status word, and 06.16 Drive
status word 1, bit 1.
This parameter is read-only.
Bit Name Description
0 Follower drive 1 = A follower is preventing the master from starting
1 = The application program is preventing the drive
1 Application
from starting
1 = A control unit auxiliary power failure is preventing
2 Aux. power failure
the drive from starting
1 = The encoder feedback configuration is preventing
3 Encoder feedback
the drive from starting
1 = A reference source parametrization conflict is
Ref source
4 preventing the drive from starting. See warning A6DA
parametrization
Reference source parametrization
5-15 Reserved
MSW BIT 14 SEL (06.33) Default: False (0)
Range: 0, 1, Other
False 0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is transmitted as bit 14 of 06.11
Main status word.
12-30 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND LSU STATUS WORD (06.36) Default: Read Only
STATUS WORDS Range: 0000h - FFFFh
(Continued)
(Only visible with a BCU control unit) Shows the status of the supply
unit. See also section Control of a supply unit (LSU), and parameter
group 60 DDCS communication. This parameter is read-only.
Bit Name Description
0 Ready on 1 = Ready to switch on
1 Ready run 1 = Ready to operate, DC link charged
2 Ready ref 1 = Operation enabled
3 Tripped 1 = A fault is active
4-6 Reserved
7 Warning 1 = A warning is active
8 Modulating 1 = The supply unit is modulating
1 = Remote control (EXT1 or EXT2)
9 Remote
0 = Local control
10 Net ok 1 = Supply network voltage OK
11-12 Reserved
Charging or
13 1 = Bit 1 or bit 14 active
ready run
1 = Charging contactor closed
14 Charging
0 = Charging contactor open
15 Reserved
INTERNAL STATE MACHINE Default: Read Only
LSU CW (06.39) Range: 0000h - FFFFh
(Only visible with a BCU control unit) Shows the control word sent
to the supply unit from the INULSU (inverter unit/supply unit) state
machine. This parameter is read-only.
Bit Name Description
1 = Start charging
0 ON/OFF
0 = Open main contactor (switch power off)
1 OFF 2 0 = Emergency stop (Off2)
2 OFF 3 0 = Emergency stop (Off3)
1 = Start modulating
3 START
0 = Stop modulating
4-6 Reserved
0 -> 1 = Reset an active fault - A fresh start command
7 RESET
is required after reset
8-11 Reserved
12 USER BIT 0 See parameter 06.40 LSU CW user bit 0 selection
13 USER BIT 1 See parameter 06.41 LSU CW user bit 1 selection
14 USER BIT 2 See parameter 06.42 LSU CW user bit 2 selection
15 USER BIT 3 See parameter 06.43 LSU CW user bit 3 selection
LSU CW USER BIT 0 Default: MCW user bit 0 (2)
SELECTION (06.40) Range: 0 - 5, Other
False (0) 0
True (1) 1
MCW user bit 0 (2) Bit 12 of 06.01 Main control word
MCW user bit 1 (3) Bit 13 of 06.01 Main control word
MCW user bit 2 (4) Bit 14 of 06.01 Main control word
MCW user bit 3 (5) Bit 15 of 06.01 Main control word
Other [bit] Source selection (see Terms and abbreviations)
(Only visible with a BCU control unit)
Selects a binary source whose status is transmitted as bit 12 of 06.39
Internal state machine LSU CW to the supply unit.
3AXD50000011888 Startup Assistant & Parameters 12-31
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND LSU CW USER BIT 1 Default: MCW user bit 1 (3)
STATUS WORDS SELECTION (06.41) Range: 0 - 5, Other
(Continued)
False (0) 0
True (1) 1
MCW user bit 0 (2) Bit 12 of 06.01 Main control word
MCW user bit 1 (3) Bit 13 of 06.01 Main control word
MCW user bit 2 (4) Bit 14 of 06.01 Main control word
MCW user bit 3 (5) Bit 15 of 06.01 Main control word
Other [bit] Source selection (see Terms and abbreviations)
(Only visible with a BCU control unit) Selects a binary source whose
status is transmitted as bit 13 of 06.39 Internal state machine LSU CW
to the supply unit.
LSU CW USER BIT 2 Default: MCW user bit 2 (4)
SELECTION (06.42) Range: 0 - 5, Other
False (0) 0
True (1) 1
MCW user bit 0 (2) Bit 12 of 06.01 Main control word
MCW user bit 1 (3) Bit 13 of 06.01 Main control word
MCW user bit 2 (4) Bit 14 of 06.01 Main control word
MCW user bit 3 (5) Bit 15 of 06.01 Main control word
Other [bit] Source selection (see Terms and abbreviations)
(Only visible with a BCU control unit) Selects a binary source whose
status is transmitted as bit 14 of 06.39 Internal state machine LSU CW
to the supply unit.
LSU CW USER BIT 3 Default: MCW user bit 3 (5)
SELECTION (06.43) Range: 0 - 5, Other
False (0) 0
True (1) 1
MCW user bit 0 (2) Bit 12 of 06.01 Main control word
MCW user bit 1 (3) Bit 13 of 06.01 Main control word
MCW user bit 2 (4) Bit 14 of 06.01 Main control word
MCW user bit 3 (5) Bit 15 of 06.01 Main control word
Other [bit] Source selection (see Terms and abbreviations)
(Only visible with a BCU control unit) Selects a binary source whose
status is transmitted as bit 15 of 06.39 Internal state machine LSU CW
to the supply unit.
FOLLOWER CW USER BIT 0 Default: MCW user bit 0 (2)
SELECTION (06.45) Range: 0 - 5, Other
False (0) 0
True (1) 1
MCW user bit 0 (2) Bit 12 of 06.01 Main control word
MCW user bit 1 (3) Bit 13 of 06.01 Main control word
MCW user bit 2 (4) Bit 14 of 06.01 Main control word
MCW user bit 3 (5) Bit 15 of 06.01 Main control word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is transmitted as bit 12 of the
Follower control word to follower drives. (Bits 0-11 of the Follower
control word are taken from 06.01 Main control word.)
See also section Master/follower functionality.
12-32 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND FOLLOWER CW USER BIT 1 Default: MCW user bit 1 (3)
STATUS WORDS SELECTION (06.46) Range: 0 - 5, Other
(Continued)
False (0) 0
True (1) 1
MCW user bit 0 (2) Bit 12 of 06.01 Main control word
MCW user bit 1 (3) Bit 13 of 06.01 Main control word
MCW user bit 2 (4) Bit 14 of 06.01 Main control word
MCW user bit 3 (5) Bit 15 of 06.01 Main control word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is transmitted as bit 13 of the
Follower control word to follower drives. (Bits 0-11 of the Follower
control word are taken from 06.01 Main control word.)
FOLLOWER CW USER BIT 2 Default: MCW user bit 2 (4)
SELECTION (06.47) Range: 0 - 5, Other
False (0) 0
True (1) 1
MCW user bit 0 (2) Bit 12 of 06.01 Main control word
MCW user bit 1 (3) Bit 13 of 06.01 Main control word
MCW user bit 2 (4) Bit 14 of 06.01 Main control word
MCW user bit 3 (5) Bit 15 of 06.01 Main control word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is transmitted as bit 14 of the
Follower control word to follower drives. (Bits 0-11 of the Follower
control word are taken from 06.01 Main control word.)
FOLLOWER CW USER BIT 3 Default: MCW user bit 3 (5)
SELECTION (06.48) Range: 0 - 5, Other
False (0) 0
True (1) 1
MCW user bit 0 (2) Bit 12 of 06.01 Main control word
MCW user bit 1 (3) Bit 13 of 06.01 Main control word
MCW user bit 2 (4) Bit 14 of 06.01 Main control word
MCW user bit 3 (5) Bit 15 of 06.01 Main control word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is transmitted as bit 15 of the
Follower control word to follower drives. (Bits 0-11 of the Follower
control word are taken from 06.01 Main control word.)
USER STATUS WORD 1 (06.50) Default: Read Only
Range: 0000h - FFFFh
User-defined status word. This word shows the status of the binary
sources selected by parameters 06.60 - 06.75.
This parameter is read-only.
Bit Name Description
0 User status bit 0 Status of source selected by parameter 06.60
1 User status bit 1 Status of source selected by parameter 06.61
-- -- --
15 User status bit 15 Status of source selected by parameter 06.75
3AXD50000011888 Startup Assistant & Parameters 12-33
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND USER STATUS WORD 1 BIT 0 Default: False (0)
STATUS WORDS SEL (06.60) Range: 0, 1, Other
(Continued)
False 0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 0 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 1 Default: Out of Window (2)
SEL (06.61) Range: 0 - 2, Other
False 0
True 1
Out of Window 2 - Bit 3 of 06.19 Speed control status word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 1 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 2 Default: Emergency stop failed (2)
SEL (06.62) Range: 0 - 2, Other
False 0
True 1
Emergency stop failed 2 - Bit 8 of 06.17 Drive status word 2
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 2 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 3 Default: Magnetized (2)
SEL (06.63) Range: 0 - 2, Other
False 0
True 1
Magnetized 2 - Bit 1 of 06.17 Drive status word 2
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 3 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 4 Default: Run disable (2)
SEL (06.64) Range: 0 - 2, Other
False 0
True 1
Run disable 2 - Bit 5 of 06.18 Start inhibit status word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 4 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 5 Default: False (0)
SEL (06.65) Range: 0, 1, Other
False 0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 5 of 06.50 User
status word 1.
12-34 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND USER STATUS WORD 1 BIT 6 Default: False (0)
STATUS WORDS SEL (06.66) Range: 0, 1, Other
(Continued)
False 0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 6 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 7 Default: Identification run done (2)
SEL (06.67) Range: 0 - 2, Other
False 0
True 1
Identification run done 2 - Bit 0 of 06.17 Drive status word 2
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 7 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 8 Default: Start inhibition (2)
SEL (06.68) Range: 0 - 2, Other
False 0
True 1
Start inhibition 2 - Bit 7 of 06.18 Start inhibit status word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 8 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 9 Default: Limiting (2)
SEL (06.69) Range: 0 - 2, Other
False 0
True 1
Limiting 2 - Bit 7 of 06.16 Drive status word 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 9 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 10 Default: Torque control (2)
SEL (06.70) Range: 0 - 2, Other
False 0
True 1
Torque control 2 - Bit 2 of 06.17 Drive status word 2
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 10 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 11 Default: Zero speed (2)
SEL (06.71) Range: 0 - 2, Other
False 0
True 1
Zero speed 2 - Bit 0 of 06.19 Speed control status word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 11 of 06.50 User
status word 1.
3AXD50000011888 Startup Assistant & Parameters 12-35
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CONTROL AND USER STATUS WORD 1 BIT 12 Default: Internal speed feedback (2)
STATUS WORDS SEL (06.72) Range: 0 - 2, Other
(Continued)
False 0
True 1
Internal speed feedback 2 - Bit 4 of 06.19 Speed control status word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 12 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 13 Default: False (0)
SEL (06.73) Range: 0, 1, Other
False 0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 13 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 14 Default: False (0)
SEL (06.74) Range: 0, 1, Other
False 0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 14 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 15 Default: False (0)
SEL (06.75) Range: 0, 1, Other
False 0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 15 of 06.50 User
status word 1.
USER CONTROL WORD 1 Default: Read Only
(06.100) Range: 0000h - FFFFh
User-defined control word 1. This parameter is read-only.
Bit Name Description
0 User control word 1 bit 0 User defined bit
1 User control word 1 bit 1 User defined bit
-- -- --
15 User control word 1 bit 15 User defined bit
USER CONTROL WORD 2 Default: Read Only
(06.101) Range: 0000h - FFFFh
User-defined control word 2. This parameter is read-only.
Bit Name Description
0 User control word 2 bit 0 User defined bit
1 User control word 2 bit 1 User defined bit
-- -- --
15 User control word 2 bit 15 User defined bit
12-36 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SYSTEM INFO Drive hardware and firmware information. All parameters in this group are read-only.
DRIVE RATING ID (07.03) Default: Read Only
Range: 0 - 999
Type of the drive/inverter unit.
FIRMWARE NAME (07.04) Default: Read Only
Range: -
Firmware identification.
FIRMWARE VERSION (07.05) Default: Read Only
Range: -
Version number of the firmware.
LOADING PACKAGE NAME Default: Read Only
(07.06) Range: -
Name of the firmware loading package.
LOADING PACKAGE VERSION Read Only
(07.07) Range: -
Version number of the firmware loading package.
BOOTLOADER VERSION Default: Read Only
(07.08) Range: -
Version number of the firmware bootloader.
CPU USAGE (07.11) Default: Read Only
Range: 0 - 100%
Microprocessor load in percent.
PU LOGIC VERSION NUMBER Default: Read Only
(07.13) Range: -
Version number of the power unit logic.
APPLICATION ENVIRONMENT Default: Read Only
STATUS 1 (07.21) Range: 0000h - FFFFh
Shows which tasks of the application program are running.
Bit Name Description
0 Pre task 1 = Pre-task running
1 Appl task1 1 = Task 1 running
2 Appl task2 1 = Task 2 running
3 Appl task3 1 = Task 3 running
4-14 Reserved
15 Task monitoring 1 = Task monitoring enabled
APPLICATION ENVIRONMENT Default: Read Only
STATUS 2 (07.22) Range: 0000h - FFFFh
Shows the status of the openings in the application program.
Bit Name Description
0 Opening1 Status of opening 1 in the application program
1 Opening2 Status of opening 2 in the application program
-- -- --
15 Opening16 Status of opening 16 in the application program
APPLICATION NAME (07.23) Default: Read Only
Range: -
First five ASCII letters of the name given to the application program in
the programming tool. The full name is visible under System info on
the control panel or the Drive composer PC tool.
_N/A_ = None
3AXD50000011888 Startup Assistant & Parameters 12-37
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SYSTEM INFO APPLICATION VERSION Default: Read Only
(Continued) (07.24) Range: -
Application program version number given to the application program
in the programming tool. Also visible under System info on the control
panel or the Drive composer PC tool.
CUSTOMIZATION PACKAGE Default: Read Only
NAME (07.25) Range: -
First five ASCII letters of the name given to the customization package.
The full name is visible under System info on the control panel or the
Drive composer PC tool.
_N/A_ = None
CUSTOMIZATION PACKAGE Default: Read Only
VERSION (07.26) Range: -
Customization package version number. Also visible under System info
on the control panel or the Drive composer PC tool.
ADAPTIVE PROGRAM Default: Read Only
STATUS (07.30) Range: 0000h - FFFFh
Shows the status of the adaptive program. See section Adaptive
programming.
Bit Name Description
0 Initialized 1 = Adaptive program initialized
1 Editing 1 = Adaptive program is being edited
2 Edit done 1 = Editing of adaptive program finished
3 Running 1 = Adaptive program running
4-13 Reserved
1 = State change in progress in adaptive
14 State changing
programming engine
15 Faulted 1 = Error in adaptive program
STANDARD DI, RO Configuration of digital inputs and relay outputs.
DI STATUS (10.01) Default: Read Only
Range: 0000h - FFFFh
Displays the electrical status of digital inputs DIIL and DI6 - DI1. The
activation/deactivation delays of the inputs (if any are specified) are
ignored. A filtering time can be defined by parameter 10.51 DI filter
time.
Bits 0 - 5 reflect the status of DI1 - DI6; bit 15 reflects the status of the
DIIL input. Example: 1000000000010011b = DIIL, DI5, DI2 and DI1 are
on, DI3, DI4 and DI6 are off.
This parameter is read-only.
DI DELAYED STATUS (10.02) Default: Read Only
Range: 0000h - FFFFh
Displays the status of digital inputs DIIL and DI6 - DI1. This word is
updated only after activation/deactivation delays (if any are specified).
Bits 0 - 5 reflect the delayed status of DI1 - DI6; bit 15 reflects the
delayed status of the DIIL input.
This parameter is read-only.
12-38 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD DI, RO DI FORCE SELECTION (10.03) Default: 0000h
(Continued) Range: 0000h - FFFFh
The electrical statuses of the digital inputs can be overridden for eg.
testing purposes. A bit in parameter 10.04 DI force data is provided for
each digital input, and its value is applied whenever the corresponding
bit in this parameter is 1.
Bit Value
0 1 = Force DI1 to value of bit 0 of parameter 10.04 DI force data
1 1 = Force DI2 to value of bit 1 of parameter 10.04 DI force data
2 1 = Force DI3 to value of bit 2 of parameter 10.04 DI force data
3 1 = Force DI4 to value of bit 3 of parameter 10.04 DI force data
4 1 = Force DI5 to value of bit 4 of parameter 10.04 DI force data
5 1 = Force DI6 to value of bit 5 of parameter 10.04 DI force data
6-14 Reserved
15 1 = Force DIIL to value of bit 15 of parameter 10.04 DI force data
DI FORCE DATA (10.04) Default: 0000h
Range: 0000h - FFFFh
Contains the values that the digital inputs are forced to when selected
by 10.03 DI force selection.
Bit 0 is the forced value for DI1; bit 15 is the forced value for the DIIL
input.
DI ON DELAY (10.05) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input DI1.
1
*DI status
1
**Delayed DI status
0
Time
tOn tOff tOn tOff
tOn = 10.05 DI1 ON delay
tOff = 10.06 DI1 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
DI OFF DELAY (10.06) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input DI1. See parameter
10.05 DI1 ON delay.
DI2 ON DELAY (10.07) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input DI2.
1
*DI status
1
**Delayed DI status
0
Time
tOn tOff tOn tOff
tOn = 10.07 DI2 ON delay
tOff = 10.08 DI2 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
3AXD50000011888 Startup Assistant & Parameters 12-39
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD DI, RO DI2 OFF DELAY (10.08) Default: 0.0 s
(Continued) Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input DI2. See parameter
10.07 DI2 ON delay.
DI3 ON DELAY (10.09) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input DI3.
1
*DI status
1
**Delayed DI status
0
Time
tOn tOff tOn tOff
tOn = 10.09 DI3 ON delay
tOff = 10.10 DI3 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
DI3 OFF DELAY (10.10) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input DI3. See parameter
10.09 DI3 ON delay.
DI4 ON DELAY (10.11) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input DI4.
1
*DI status
1
**Delayed DI status
0
Time
tOn tOff tOn tOff
tOn = 10.11 DI4 ON delay
tOff = 10.12 DI4 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
DI4 OFF DELAY (10.12) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input DI4. See parameter
10.11 DI4 ON delay.
12-40 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD DI, RO DI5 ON DELAY (10.13) Default: 0.0 s
(Continued) Range: 0.0 to 3000.0 s
Defines the activation delay for digital input DI5.
1
*DI status
1
**Delayed DI status
0
Time
tOn tOff tOn tOff
tOn = 10.13 DI5 ON delay
tOff = 10.14 DI5 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
DI5 OFF DELAY (10.14) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input DI5. See parameter
10.13 DI5 ON delay.
DI6 ON DELAY (10.15) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input DI6.
1
*DI status
1
**Delayed DI status
0
Time
tOn tOff tOn tOff
tOn = 10.15 DI6 ON delay
tOff = 10.16 DI6 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
DI6 OFF DELAY (10.16) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input DI6. See parameter
10.15 DI6 ON delay.
RO STATUS (10.21) Default: Read Only
Range: 0000h - FFFFh
Status of relay outputs RO8 - RO1. Example: 00000001b = RO1 is
energized, RO2 - RO8 are de-energized.
3AXD50000011888 Startup Assistant & Parameters 12-41
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD DI, RO RO1 SOURCE (10.24) Default: Ready run (2)
(Continued) Range: 0 - 44, Other
Not energized (0) Output is not energized
Energized (1) Output is energized
Ready run (2) Bit 1 of 06.11 Main status word
Enabled (4) Bit 0 of 06.16 Drive status word 1
Started (5) Bit 5 of 06.16 Drive status word 1
Magnetized (6) Bit 1 of 06.17 Drive status word 2
Running (7) Bit 6 of 06.16 Drive status word 1
Ready ref (8) Bit 2 of 06.11 Main status word
At setpoint (9) Bit 8 of 06.11 Main status word
Reverse (10) Bit 2 of 06.19 Speed control status word
Zero speed (11) Bit 0 of 06.19 Speed control status word
Above limit (12) Bit 10 of 06.17 Drive status word 2
Warning (13) Bit 7 of 06.11 Main status word
Fault (14) Bit 3 of 06.11 Main status word
Fault (-1) (15) Inverted bit 3 of 06.11 Main status word
Open brake command (22) Bit 0 of 44.01 Brake control status
Ext2 active (23) Bit 11 of 06.16 Drive status word 1
Remote control (24) Bit 9 of 06.11 Main status word
Supervision 1 (33) Bit 0 of 32.01 Supervision status
Supervision 2 (34) Bit 1 of 32.01 Supervision status
Supervision 3 (35) Bit 2 of 32.01 Supervision status
RO/DIO control word bit 0 (40) Bit 0 of 10.99 RO/DIO control word
RO/DIO control word bit 1 (41) Bit 1 of 10.99 RO/DIO control word
RO/DIO control word bit 2 (42) Bit 2 of 10.99 RO/DIO control word
RO/DIO control word bit 8 (43) Bit 8 of 10.99 RO/DIO control word
RO/DIO control word bit 9 (44) Bit 9 of 10.99 RO/DIO control word
Other [bit] Source selection (see Terms and abbreviations)
Selects a drive signal to be connected to relay output RO1.
RO1 ON DELAY (10.25) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for relay output RO1.
1
Status of selected
source
0
1
RO status
0
Time
tOn tOff tOn tOff
tOn = 10.25 RO1 ON delay
tOff = 10.26 RO1 OFF delay
12-42 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD DI, RO RO1 OFF DELAY (10.26) Default: 0.0 s
(Continued) Range: 0.0 to 3000.0 s
Defines the deactivation delay for relay output RO1. See parameter
10.25 RO1 ON delay.
RO2 SOURCE (10.27) Default: Running (7) (95.20 b3)
Range: 0 - 44, Other
Selects a drive signal to be connected to relay output RO2. For the
available selections, see parameter 10.24 RO1 source.
RO2 ON DELAY (10.28) Default: 0.0 s (95.20 b3)
Range: 0.0 to 3000.0 s
Defines the activation delay for relay output RO2.
1
Status of selected
source
0
1
RO status
0
Time
tOn tOff tOn tOff
tOn = 10.28 RO2 ON delay
tOff = 10.29 RO2 OFF delay
RO2 OFF DELAY (10.29) Default: 0.0 s (95.20 b3)
Range: 0.0 to 3000.0 s
Defines the deactivation delay for relay output RO2. See parameter
10.28 RO2 ON delay.
RO3 SOURCE (10.30) Default: Fault (-1) (15)
Range: 0 - 44, Other
Selects a drive signal to be connected to relay output RO3. For the
available selections, see parameter 10.24 RO1 source.
RO3 ON DELAY (10.31) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for relay output RO3.
1
Status of selected
source
0
1
RO status
0
Time
tOn tOff tOn tOff
tOn = 10.31 RO3 ON delay
tOff = 10.32 RO3 OFF delay
RO3 OFF DELAY (10.32) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for relay output RO3. See parameter
10.31 RO3 ON delay.
DI FILTER TIME (10.51) Default: 10.0 ms
Range: 0.3 - 100.0 ms
Defines a filtering time for parameter 10.01 DI status.
3AXD50000011888 Startup Assistant & Parameters 12-43
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD DI, RO RO/DIO CONTROL WORD Default: 0000h
(Continued) (10.99) Range: 0000h - FFFFh
Storage parameter for controlling the relay outputs and digital input/
outputs eg. through the embedded fieldbus interface.
To control the relay outputs (RO) and the digital input/outputs (DIO)
of the drive, send a control word with the bit assignments shown
below as Modbus I/O data. Set the target selection parameter of that
particular data (58.101 - 58.124) to RO/DIO control word. In the source
selection parameter of the desired output, select the appropriate bit of
this word.
Bit Name Description
0 RO1
Source bits for relay outputs RO1 - RO3 (see
1 RO2
parameters 10.24, 10.27 and 10.30).
2 RO3
3-7 Reserved
8 DIO1 Source bits for digital input/outputs DIO1 - DIO3 (see
9 DIO2 parameters 11.06 and 11.10).
10-15 Reserved
STANDARD DIO, Configuration of digital input/outputs and frequency inputs/outputs.
FI, FO
DIO STATUS (11.01) Default: Read Only
Range: 0000b - 0011b
Displays the status of digital input/outputs DIO2 and DIO1. The
activation/deactivation delays (if any are specified) are ignored. A
filtering time (for input mode) can be defined by parameter 10.51 DI
filter time. Example: 0010 = DIO2 is on, DIO1 is off.
This parameter is read-only.
DIO DELAYED STATUS (11.02) Default: Read Only
Range: 0000b - 0011b
Displays the delayed status of digital input/outputs DIO2 and DIO1.
This word is updated only after activation/deactivation delays (if any
are specified). Example: 0010 = DIO2 is on, DIO1 is off.
This parameter is read-only.
DIO1 FUNCTION (11.05) Default: Output (0)
Range: 0 - 2
Output (0) DIO1 is used as a digital output
Input (1) DIO1 is used as a digital input
Frequency (2) DIO1 is used as a frequency input
Selects whether DIO1 is used as a digital output or input, or a
frequency input.
12-44 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD DIO, DIO1 OUTPUT SOURCE Default: Ready run (2)
FI, FO (11.06) Range: 0 - 44, Other
(Continued)
Not energized (0) Output is off
Energized (1) Output is on
Ready run (2) Bit 1 of 06.11 Main status word
Enabled (4) Bit 0 of 06.16 Drive status word 1
Started (5) Bit 5 of 06.16 Drive status word 1
Magnetized (6) Bit 1 of 06.17 Drive status word 2
Running (7) Bit 6 of 06.16 Drive status word 1
Ready ref (8) Bit 2 of 06.11 Main status word
At setpoint (9) Bit 8 of 06.11 Main status word
Reverse (10) Bit 2 of 06.19 Speed control status word
Zero speed (11) Bit 0 of 06.19 Speed control status word
Above limit (12) Bit 10 of 06.17 Drive status word 2
Warning (13) Bit 7 of 06.11 Main status word
Fault (14) Bit 3 of 06.11 Main status word
Fault (-1) (15) Inverted bit 3 of 06.11 Main status word
Open brake command (22) Bit 0 of 44.01 Brake control status
Ext2 active (23) Bit 11 of 06.16 Drive status word 1
Remote control (24) Bit 9 of 06.11 Main status word
Supervision 1 (33) Bit 0 of 32.01 Supervision status
Supervision 2 (34) Bit 1 of 32.01 Supervision status
Supervision 3 (35) Bit 2 of 32.01 Supervision status
RO/DIO control word bit 0 (40) Bit 0 of 10.99 RO/DIO control word
RO/DIO control word bit 1 (41) Bit 1 of 10.99 RO/DIO control word
RO/DIO control word bit 2 (42) Bit 2 of 10.99 RO/DIO control word
RO/DIO control word bit 8 (43) Bit 8 of 10.99 RO/DIO control word
RO/DIO control word bit 9 (44) Bit 9 of 10.99 RO/DIO control word
Other [bit] Source selection (see Terms and abbreviations)
Selects a drive signal to be connected to digital input/output DIO1
when parameter 11.05 DIO1 function is set to Output.
DIO1 ON DELAY (11.07) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input/output DIO1 (when used
as a digital output or digital input).
1
*DIO status
1
**Delayed DIO status
0
Time
tOn tOff tOn tOff
tOn = 11.07 DIO1 ON delay
tOff = 11.08 DIO1 OFF delay
*Electrical status of digital input. Indicated by 11.01 DIO status.
**Indicated by 11.02 DIO delayed status.
3AXD50000011888 Startup Assistant & Parameters 12-45
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD DIO, DIO1 OFF DELAY (11.08) Default: 0.0 s
FI, FO Range: 0.0 to 3000.0 s
(Continued)
Defines the deactivation delay for digital input/output DIO1 (when used
as a digital output or digital input). See parameter 11.07 DIO1 ON
delay.
DIO2 FUNCTION (11.09) Default: Output (0)
Range: 0 - 2
Output (0) DIO2 is used as a digital output
Input (1) DIO2 is used as a digital input
Frequency (2) DIO2 is used as a frequency input
Selects whether DIO2 is used as a digital output or input, or a
frequency output.
DIO2 OUTPUT SOURCE Default: Running (7)
(11.10) Range: 0 - 44, Other
Selects a drive signal to be connected to digital input/output DIO2
when parameter 11.09 DIO2 function is set to Output.
For the available selections, see parameter 11.06 DIO1 output source.
DIO2 ON DELAY (11.11) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input/output DIO2 (when used
as a digital output or digital input).
1
*DIO status
1
**Delayed DIO status
0
Time
tOn tOff tOn tOff
tOn = 11.11 DIO2 ON delay
tOff = 11.12 DIO2 OFF delay
*Electrical status of digital input. Indicated by 11.01 DIO status.
**Indicated by 11.02 DIO delayed status.
DIO2 OFF DELAY (11.12) Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input/output DIO2 (when used
as a digital output or digital input). See parameter 11.11 DIO2 ON
delay.
DIO FILTER TIME (11.81) Default: 10.0 ms
Range: 0.3 - 100.0 ms
Defines a filtering time for parameter 11.01 DIO status. The filtering
time will only affect the DIOs that are in input mode.
12-46 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD AI Configuration of standard analog inputs.
AI TUNE (12.01) Default: No action (0)
Range: 0 - 4
No action (0) AI tune is not activated.
Current analog input AI1 signal value is set as minimum value of AI1
AI1 min tune (1) into parameter 12.17 AI1 min. The value reverts back to No action
automatically.
Current analog input AI1 signal value is set as maximum value of AI1
AI1 max tune (2) into parameter 12.18 AI1 max. The value reverts back to No action
automatically.
Current analog input AI2 signal value is set as minimum value of AI2
AI2 min tune (3) into parameter 12.27 AI2 min. The value reverts back to No action
automatically.
Current analog input AI2 signal value is set as maximum value of AI2
AI2 max tune (4) into parameter 12.28 AI2 max. The value reverts back to No action
automatically.
Triggers the analog input tuning function.
Connect the signal to the input and select the appropriate tuning
function.
AI SUPERVISION FUNCTION Default: No action (0)
(12.03) Range: 0 - 4
No action (0) No action taken.
Fault (1) Drive trips on 80A0 AI supervision.
Warning (2) Drive generates an A8A0 AI supervision warning.
Drive generates a warning (A8A0 AI supervision) and freezes the speed
(or frequency) to the level the drive was operating at. The speed/
frequency is determined on the basis of actual speed using 850 ms low-
Last speed (3)
pass filtering.
WARNING! Make sure that it is safe to continue operation in case of a
communication break.
Drive generates a warning (A8A0 AI supervision) and sets the speed
to the speed defined by parameter 22.41 Speed ref safe (or 28.41
Speed ref safe (4) Frequency ref safe when frequency reference is being used).
WARNING! Make sure that it is safe to continue operation in case of a
communication break.
Selects how the drive reacts when an analog input signal moves out of
the minimum and/or maximum limits specified for the input.
The supervision applies a margin of 0.5 V or 1.0 mA to the limits. For
example, if the maximum limit for the input is 7.000 V, the maximum
limit supervision activates at 7.500 V.
The inputs and the limits to be observed are selected by parameter
12.04 AI supervision selection.
Note: Analog input signal supervision is only active when
• the analog input is set as the source (using the AI1 scaled or AI2
scaled selection) in parameter 22.11, 22.12, 22.15, 22.17, 23.42,
26.11, 26.12, 26.16, 26.25, 28.11, 28.12, 30.21, 30.22, 40.16, 40.17,
40.50, 41.16, 41.17, 41.50 or 44.09, and
• is being used as the active source.
AI SUPERVISION SELECTION Default: 0000b
(12.04) Range: 0000b - 1111b
Specifies the analog input limits to be supervised. See parameter
12.03 AI supervision function.
Bit Name Description
0 AI1 < MIN 1 = Minimum limit supervision of AI1 active
1 AI1 > MAX 1 = Maximum limit supervision of AI1 active
2 AI2 < MIN 1 = Minimum limit supervision of AI2 active
3 AI2 > MAX 1 = Maximum limit supervision of AI2 active
4-15 Reserved
3AXD50000011888 Startup Assistant & Parameters 12-47
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD AI AI1 ACTUAL VALUE (12.11) Default: Read Only
(Continued) Range: -22.000 to +22.000mA or V
Displays the value of analog input AI1 in mA or V (depending on
whether the input is set to current or voltage by a hardware setting).
This parameter is read-only.
AI1 SCALED VALUE (12.12) Default: Read Only
Range: -32768.000 to +32767.000
Displays the value of analog input AI1 after scaling. See parameters
12.19 AI1 scaled at AI1 min and 12.20 AI1 scaled at AI1 max.
This parameter is read-only.
AI1 UNIT SELECTION (12.15) Default: V
Range: V or mA
V Volts
mA Milliamperes
Selects the unit for readings and settings related to analog input AI1.
Note: This setting must match the corresponding hardware setting on
the drive control unit (see the hardware manual of the drive).
Control board reboot (either by cycling the power or through
parameter 96.08 Control board boot) is required to validate any
changes in the hardware settings.
AI1 FILTER TIME (12.16) Default: 0.100 s
Range: 0.000 - 30.000 s
Defines the filter time constant for analog input AI1.
%
Unfiltered signal
100
63 Filtered signal
t
T
-t/T
O = I × (1 - e )
I = filter input (step)
O = filter output
t = time
T = filter time constant
Note: The signal is also filtered due to the signal interface hardware
(approximately 0.25 ms time constant). This cannot be changed
by any parameter.
AI1 MIN (12.17) Default: 0.000mA or V
Range: -22.000 to +22.000mA or V
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal from
plant is wound to its minimum setting.
See also parameter 12.01 AI tune.
AI1 MAX (12.18) Default: 20.000mA or 10.000V
Range: -22.000 to +22.000mA or V
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal from
plant is wound to its maximum setting.
See also parameter 12.01 AI tune.
12-48 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD AI AI1 SCALED AT AI1 MIN Default: 0.000
(Continued) (12.19) Range: -32768.000 to +32767.000
Defines the real internal value that corresponds to the minimum analog
input AI1 value defined by parameter 12.17 AI1 min. (Changing the
polarity settings of 12.19 and 12.20 can effectively invert the analog
input.) AI scaled (12.12 )
12.20
AI in (12.11 )
12.17
12.18
12.19
AI1 SCALED AT AI1 MAX Default: 1500.000; 1800.000 (95.20 b0)
(12.20) Range: -32768.000 to +32767.000
Defines the real internal value that corresponds to the maximum
analog input AI1 value defined by parameter 12.18 AI1 max. See the
drawing at parameter 12.19 AI1 scaled at AI1 min.
AI2 ACTUAL VALUE (12.21) Default: Read Only
Range: -22.000 to +22.000mA or V
Displays the value of analog input AI2 in mA or V (depending on
whether the input is set to current or voltage by a hardware setting).
This parameter is read-only.
AI2 SCALED VALUE (12.22) Default: Read Only
Range: -32768.000 to +32767.000
Displays the value of analog input AI2 after scaling. See parameters
12.29 AI2 scaled at AI2 min and 12.30 AI2 scaled at AI2 max.
This parameter is read-only.
AI2 UNIT SELECTION (12.25) Default: mA
Range: V or mA
V Volts
mA Milliamperes
Selects the unit for readings and settings related to analog input AI2.
Note: This setting must match the corresponding hardware setting on
the drive control unit (see the hardware manual of the drive).
Control board reboot (either by cycling the power or through
parameter 96.08 Control board boot) is required to validate any
changes in the hardware settings.
AI2 FILTER TIME (12.26) Default: 0.100 s
Range: 0.000 - 30.000 s
Defines the filter time constant for analog input AI2. See parameter
12.16 AI1 filter time.
AI2 MIN (12.27) Default: 0.000mA or V
Range: -22.000 to +22.000mA or V
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal from
plant is wound to its minimum setting.
See also parameter 12.01 AI tune.
3AXD50000011888 Startup Assistant & Parameters 12-49
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD AI AI2 MAX (12.28) Default: 20.000mA or 10.000V
(Continued) Range: -22.000 to +22.000mA or V
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal from
plant is wound to its maximum setting.
See also parameter 12.01 AI tune.
AI2 SCALED AT AI2 MIN Default: 0.000
(12.29) Range: -32768.000 to +32767.000
Defines the real value that corresponds to the minimum analog input
AI2 value defined by parameter 12.27 AI2 min. (Changing the polarity
settings of 12.29 and 12.30 can effectively invert the analog input.)
AI scaled (12.22 )
12.30
AI in (12.21)
12.27
12.28
12.29
AI2 SCALED AT AI2 MAX Default: 100.000
(12.30) Range: -32768.000 to +32767.000
Defines the real value that corresponds to the maximum analog input
AI2 value defined by parameter 12.28 AI2 max.
See the drawing at parameter 12.29 AI2 scaled at AI2 min.
12-50 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD AO Configuration of standard analog outputs.
AO1 ACTUAL VALUE (13.11) Default: Read Only
Range: 0.000 to +22.000mA
Displays the value of AO1 in mA. This parameter is read-only.
AO1 SOURCE (13.12) Default: 1 (Motor Speed Used)
Range: 0 - 23, 37, 38, Other
0 Zero
1 Motor speed used
3 Output frequency
4 Motor current
6 Motor torque
7 DC voltage
8 Power inu out
10 Speed ref ramp in
11 Speed ref ramp out
12 Speed ref used
13 Torq ref used
14 Freq ref used
16 Process PID out
17 Process PID fbk
18 Process PID act
19 Process PID dev
20 Force PT100 excitation
21 Force KTY84 excitation
22 Force PTC excitation
23 Force Pt1000 excitation
37 AO1 data storage
38 AO2 data storage
- Other
Selects a signal to be connected to analog output AO1. Alternatively,
sets the output to excitation mode to feed a constant current to a
temperature sensor.
AO1 FILTER TIME (13.16) Default: 0.100 s
Range: 0.000 - 30.000 s
Defines the filtering time constant for analog output AO1.
%
Unfiltered signal
100
63 Filtered signal
t
T
-t/T
O = I × (1 - e )
I = filter input (step)
O = filter output
t = time
T = filter time constant
3AXD50000011888 Startup Assistant & Parameters 12-51
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD AO AO1 SOURCE MIN (13.17) Default: 0.0
(Continued) Range: -32768.0 to +32767.0
Defines the real minimum value of the signal (selected by parameter
13.12 AO1 source) that corresponds to the minimum required AO1
output value (defined by parameter 13.19 AO1 out at AO1 src min).
I AO1 (mA)
13.20
13.19
13.17 13.18 Signal (real)
selected by
13.12
Programming 13.17 as the maximum value and 13.18 as the minimum
value inverts the output.
I AO1 (mA)
13.20
13.19
13.18 13.17 Signal real
selected by
13.12
AO1 SOURCE MAX (13.18) Default: 1500.0; 1800.0 (95.20 b0)
Range: -32768.0 to +32767.0
Defines the real maximum value of the signal (selected by parameter
13.12 AO1 source) that corresponds to the maximum required AO1
output value (defined by parameter 13.20 AO1 out at AO1 src max).
See parameter 13.17 AO1 source min.
AO1 OUT AT AO1 SRC MIN Default: 0.000mA
(13.19) Range: 0.000 - 22.000mA
Defines the minimum output value for analog output AO1. See also
drawing at parameter 13.17 AO1 source min.
AO1 OUT AT AO1 SRC MAX Default: 20.000mA
(13.20) Range: 0.000 - 22.000mA
Defines the maximum output value for analog output AO1. See also
drawing at parameter 13.17 AO1 source min.
AO2 ACTUAL TIME (13.21) Default: Read Only
Range: 0.000 - 22.000mA
Displays the value of AO2 in mA.
This parameter is read-only.
AO2 SOURCE (13.22) Default: 4 (Motor Current)
Range: 0 - 23, 37-38, Other
Selects a signal to be connected to analog output AO2. Alternatively,
sets the output to excitation mode to feed a constant current to a
temperature sensor.
For the selections, see parameter 13.12 AO1 source.
12-52 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD AO AO2 FILTER TIME (13.26) Default: 0.100 s
(Continued) Range: 0.000 - 30.000 s
Defines the filtering time constant for analog output AO2. See
parameter 13.16 AO1 filter time.
AO2 SOURCE MIN (13.27) Default: 0.0
Range: -32768.0 to +32767.0
Defines the real minimum value of the signal (selected by parameter
13.22 AO2 source) that corresponds to the minimum required AO2
output value (defined by parameter 13.29 AO2 out at AO2 src min).
IAO2 (mA)
13.30
13.29
13.27 13.28 Signal (real)
selected by
13.22
Programming 13.27 as the maximum value and 13.28 as the minimum
value inverts the output.
IAO2 (mA)
13.30
13.29
13.28 13.27 Signal (real)
selected by
13.22
AO2 SOURCE MAX (13.28) Default: 100.0
Range: -32768.0 to +32767.0
Defines the real maximum value of the signal (selected by parameter
13.22 AO2 source) that corresponds to the maximum required AO2
output value (defined by parameter 13.30 AO2 out at AO2 src max).
See parameter 13.27 AO2 source min.
AO2 OUT AT AO2 SRC MIN Default: 0.000mA
(13.29) Range: 0.000 - 22.000mA
Defines the minimum output value for analog output AO2. See also
drawing at parameter 13.27 AO2 source min.
AO2 OUT AT AO2 SRC MAX Default: 20.000mA
(13.30) Range: 0.000 - 22.000mA
Defines the maximum output value for analog output AO2. See also
drawing at parameter 13.27 AO2 source min.
3AXD50000011888 Startup Assistant & Parameters 12-53
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
STANDARD AO AO1 DATA STORAGE (13.91) Default: 0.00
(Continued) Range: -327.68 to +327.67
Storage parameter for controlling analog output AO1 eg. through
fieldbus.
In 13.12 AO1 source, select AO1 data storage. Then set this parameter
as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target selection
parameter of that particular data (58.101 - 58.124) to AO1 data
storage.
AO2 DATA STORAGE (13.92) Default: 0.00
Range: -327.68 to +327.67
Storage parameter for controlling analog output AO2 eg. through
fieldbus.
In 13.22 AO2 source, select AO2 data storage. Then set this parameter
as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target selection
parameter of that particular data (58.101 - 58.124) to AO2 data
storage.
OPERATION Selection of local and external control location sources and operating modes.
MODE See also section Operating modes of the drive.
ACTUAL OPERATION MODE Default: Read Only
(19.01) Range: 1 - 6, 10, 11, 20
Zero (1) None
Speed (2) Speed control (in DTC motor control mode)
Torque (3) Torque control (in DTC motor control mode)
The torque selector is comparing the output of the speed controller
Min (4) (25.01 Torque reference speed control) and torque reference (26.74
Torque ref ramp out) and the smaller of the two is used
The torque selector is comparing the output of the speed controller
Max (5) (25.01 Torque reference speed control) and torque reference (26.74
Torque ref ramp out) and the greater of the two is used
Add (6) The speed controller output is added to the torque reference
Scalar (Hz) (10) Frequency control in scalar motor control mode
Scalar (rpm) (11) Speed control in scalar motor control mode
Forced magnetizing (20) Motor is in magnetizing mode
Displays the operating mode currently used. See parameters 19.11 -
19.14. This parameter is read-only.
EXT1/EXT2 SELECTION Default: EXT1 (0)
(19.11) Range: 0 - 8, 11, 12, 32, Other
EXT1 (0) EXT1 (permanently selected)
EXT2 (1) EXT2 (permanently selected)
FBA A MCW bit 11 (2) Control word bit 11 received through fieldbus interface A
DI1 (3) Digital input DI1 (10.02 DI delayed status, bit 0)
DI2 (4) Digital input DI2 (10.02 DI delayed status, bit 1)
DI3 (5) Digital input DI3 (10.02 DI delayed status, bit 2)
DI4 (6) Digital input DI4 (10.02 DI delayed status, bit 3)
DI5 (7) Digital input DI5 (10.02 DI delayed status, bit 4)
DI6 (8) Digital input DI6 (10.02 DI delayed status, bit 5)
DIO1 (11) Digital input/output DIO1 (11.02 DIO delayed status, bit 0)
DIO2 (12) Digital input/output DIO2 (11.02 DIO delayed status, bit 1)
EFB MCW bit 11 (32) Control word bit 11 received through the embedded fieldbus interface
Other [bit] Source selection (see Terms and abbreviations
Selects the source for external control location EXT1/EXT2 selection.
0 = EXT1
1 = EXT2
12-54 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
START/ STOP Start and stop modes; emergency stop mode and signal source selection; DC magnetization settings;
MODE autophasing mode selection.
START MODE (21.01) Default: 2 (Automatic)
Range: 0 - 3
The drive pre-magnetizes the motor before start. The premagnetizing
time is determined automatically, being typically 200 ms to 2 s
0 (Fast)
depending on motor size. This mode should be selected if a high
break-away torque is required.
The drive pre-magnetizes the motor before start. The premagnetizing
time is defined by parameter 21.02 Magnetization time. This mode
should be selected if constant pre-magnetizing time is required (e.g. if
the motor start must be synchronized with the release of a mechanical
brake).
This setting also guarantees the highest possible break-away torque
1 (Constant Time) when the pre-magnetizing time is set long enough.
WARNING! The drive will start after the set magnetizing time has
passed even if motor magnetization is not
completed. In applications where a full break-away
torque is essential, ensure that the constant
magnetizing time is long enough to allow generation
of full magnetization and torque.
Automatic start guarantees optimal motor start in most cases. It
includes the flying start function (starting into a rotating motor) and
the automatic restart function (a stopped motor can be restarted
2 (Automatic)
immediately without waiting the motor flux to die away). The drive
motor control program identifies the flux as well as the mechanical
state of the motor and starts the motor instantly under all conditions.
This method is intended for asynchronous motors only, and is
3 (Flying Start) optimized for applications where the drive must be started into a
rotating motor at high frequencies (above 150 Hz).
Selects the motor start function for the DTC motor control mode, ie.
when 99.04 Motor control mode is set to DTC.
Notes:
• The start function for the scalar motor control mode is selected by
parameter 21.19 Scalar start mode.
• Starting into a rotating motor is not possible when DC magnetizing is
selected (Fast or Constant time).
• With permanent magnet motors and synchronous reluctance motors,
Automatic start mode must be used.
• This parameter cannot be changed while the drive is running.
AUTO RESTART TIME (21.18) Default: 5.0s
Range: 0.0 - 5.0s
0.0s Automatic restarting disabled
0.1 - 5.0s Maximum power failure duration
The motor can be automatically started after a short supply power failure
using the automatic restart function. See section Automatic restart.
When this parameter is set to 0.0 seconds, automatic restarting is
disabled. Otherwise, the parameter defines the maximum duration of the
power failure after which restarting is attempted. Note that this time also
includes the DC precharging delay.
WARNING! Before you activate the function, make sure that no
dangerous situations can occur. The function restarts
the drive automatically and continues operation after
a supply break.
3AXD50000011888 Startup Assistant & Parameters 12-55
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SPEED Speed reference selection; motor potentiometer settings. See the control chain diagrams.
REFERENCE
SELECTION SPEED REF UNLIMITED Default: Read Only
Only available in (22.01) Range: -30000.00 to +30000.00 RPM
“Custom” mode Displays the output of the speed reference selection block.
See the control chain diagram. This parameter is read-only.
SPEED REF2 SOURCE (22.12) Default: 0 (Zero)
Range: 0 - 13, 15, 16, 18, 19
0 (Zero) None
1 (AI1 scaled) 12.12 AI1 scaled value
2 (AI2 scaled) 12.22 AI2 scaled value
4 (FB A ref1) 03.05 FB A reference 1
5 (FB A ref2) 03.06 FB A reference 2
8 (EFB ref1) 03.09 EFB reference 1
9 (EFB ref2) 03.10 EFB reference 2
10 (DDCS ctrl ref1) 03.11 DDCS controller ref 1
11 (DDCS ctrl ref2) 03.12 DDCS controller ref 2
12 (D2D or M/F reference 1) 03.13 M/F or D2D ref1
13 (D2D or M/F reference 2) 03.14 M/F or D2D ref2
15 (Motor potentiometer) 22.80 Motor potentiometer ref act (output of the motor potentiometer)
16 (PID) 40.01 Process PID output actual (output of the process PID controller)
Control panel reference, with initial value from last-used panel
18 (Control panel (ref saved)) reference. See section Using the control panel as an external control
source.
Control panel reference, with initial value from previous source or actual
19 (Control panel (ref copied))
value. See section Using the control panel as an external control source
Other Source selection
Selects speed reference source 2. Two signal sources can be defined
by this parameter and 22.12 Speed ref2 source. A digital source
selected by 22.14 Speed ref1/2 selection can be used to switch
between the two sources, or a mathematical function (22.13 Speed
ref1 function) applied to the two signals to create the reference.
22.11
22.13
0
AI Ref1
FB 22.81
… … ADD 22.14
Other SUB 0
MUL 22.83
MIN 1
22.12
MAX
0
AI
22.82
FB
… …
Other
12-56 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SPEED CONSTANT SPEED Default: 0000b
REFERENCE FUNCTION (22.21) Range: 0000b - 0011b
SELECTION
(Continued) Determines how constant speeds are selected, and whether the
rotation direction signal is considered or not when applying a constant
speed.
Bit Name Information
1 = Packed: 7 constant speeds are selectable using the
three sources defined by parameters 22.22, 22.23 and
22.24.
Constant
0 speed 0 = Separate: Constant speeds 1, 2 and 3 are separately
mode activated by the sources defined by parameters 22.22,
22.23 and 22.24 respectively.
In case of conflict, the constant speed with the smaller
number takes priority.
1 = Start dir: To determine running direction for a
constant speed, the sign of the constant speed setting
(parameters 22.26 - 22.32) is multiplied by the direction
signal (forward: +1, reverse: -1). This effectively allows
the drive to have 14 (7 forward, 7 reverse) constant
Direction speeds if all values in 22.26 - 22.32 are positive.
1 WARNING: If the direction signal is reverse and the
enable
active constant speed is negative, the drive
will run in the forward direction.
0 = Accord Par: The running direction for the constant
speed is determined by the sign of the constant speed
setting (parameters 22.26 - 22.32).
2-15 Reserved
CONSTANT SPEED SEL2 Default: 6 (DI5)
(22.22) Range: 0 - 11
0 (Not Selected) Always off
1 (Selected) Always on
2 (DI1) Digital input DI1 (10.02 DI delayed status, bit 0)
3 (DI2) Digital input DI2 (10.02 DI delayed status, bit 1)
4 (DI3) Digital input DI3 (10.02 DI delayed status, bit 2)
5 (DI4) Digital input DI4 (10.02 DI delayed status, bit 3)
6 DI5) Digital input DI5 (10.02 DI delayed status, bit 4)
7 (DI6) Digital input DI6 (10.02 DI delayed status, bit 5)
10 (DIO1) Digital input/output DIO1 (11.02 DIO delayed status, bit 0)
11 (DIO2) Digital input/output DIO2 (11.02 DIO delayed status, bit 1)
Other [bit] Source selection
When bit 0 of parameter 22.21 Constant speed function is 0
(Separate), selects a source that activates constant speed 1. When
bit 0 of parameter 22.21 Constant speed function is 1 (Packed), this
parameter and parameters 22.23 Constant speed sel2 and 22.24
Constant speed sel3 select three sources whose states activate
constant speeds as follows:
Source defined Source defined Source defined Constant speed
by par. 22.22 by par. 22.23 by par. 22.24 active
0 0 0 None
1 0 0 Constant speed 1
0 1 0 Constant speed 2
1 1 0 Constant speed 3
0 0 1 Constant speed 4
1 0 1 Constant speed 5
0 1 1 Constant speed 6
1 1 1 Constant speed 7
3AXD50000011888 Startup Assistant & Parameters 12-57
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SPEED CONSTANT SPEED SEL2 Default: 0 (Not Selected)
REFERENCE (22.23) Range: 0 - 11
SELECTION
(Continued) When bit 0 of parameter 22.21 Constant speed function is 0
(Separate), selects a source that activates constant speed 2. When
bit 0 of parameter 22.21 Constant speed function is 1 (Packed), this
parameter and parameters 22.22 Constant speed sel1 and 22.24
Constant speed sel3 select three sources that are used to activate
constant speeds. See table at parameter 22.22 Constant speed sel1.
For the selections, see parameter 22.22 Constant speed sel1.
CONSTANT SPEED SEL3 Default: 0 (Not Selected)
(22.24) Range: 0 - 11
When bit 0 of parameter 22.21 Constant speed function is 0
(Separate), selects a source that activates constant speed 3. When
bit 0 of parameter 22.21 Constant speed function is 1 (Packed), this
parameter and parameters 22.22 Constant speed sel1 and 22.23
Constant speed sel2 select three sources that are used to activate
constant speeds. See table at parameter 22.22 Constant speed sel1.
For the selections, see parameter 22.22 Constant speed sel1.
CONSTANT SPEED 2 (22.27) Default: 0.00 RPM
Range: -30000.00 to +30000.00 RPM
Defines constant speed 2 (the speed the motor will turn when constant
speed 2 is selected).
CONSTANT SPEED 3 (22.28) Default: 0.00 RPM
Range: -30000.00 to +30000.00 RPM
Defines constant speed 3 (the speed the motor will turn when constant
speed 3 is selected).
CRITICAL SPEED FUNCTION Default: 0000b
(22.51) Range: 0000b - 0011b
Enables/disables the critical speeds function. Also determines whether
the specified ranges are effective in both rotating directions or not.
See also section Critical speeds/frequencies.
Bit Name Information
1 = Enable: Critical speeds enabled
0 Enable
0 = Disable: Critical speeds disabled
1 = Signed: The signs of parameters 22.52 - 22.57 are
taken into account.
Sign
1 0 = Absolute: Parameters 22.52 - 22.57 are handled as
Mode
absolute values.
Each range is effective in both directions of rotation.
2-15 Reserved
CRITICAL SPEED 1 LOW Default: 0.00 RPM
(22.52) Range: -30000.00 to +30000.00 RPM
Defines the low limit for critical speed range 1.
Note: This value must be less than or equal to the value of 22.53
Critical speed 1 high.
CRITICAL SPEED 1 HIGH Default: 0.00 RPM
(22.53) Range: -30000.00 to +30000.00 RPM
Defines the high limit for critical speed range 1.
Note: This value must be greater than or equal to the value of 22.52
Critical speed 1 low.
CRITICAL SPEED 2 LOW Default: 0.00 RPM
(22.54) Range: -30000.00 to +30000.00 RPM
Defines the low limit for critical speed range 2.
Note: This value must be less than or equal to the value of 22.55
Critical speed 2 high.
12-58 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SPEED CRITICAL SPEED 2 HIGH Default: 0.00 RPM
REFERENCE (22.55) Range: -30000.00 to +30000.00 RPM
SELECTION
(Continued) Defines the high limit for critical speed range 2.
Note: This value must be greater than or equal to the value of 22.54
Critical speed 2 low.
CRITICAL SPEED 3 LOW Default: 0.00 RPM
(22.56) Range: -30000.00 to +30000.00 RPM
Defines the low limit for critical speed range 3.
Note: This value must be less than or equal to the value of 22.57
Critical speed 3 high.
CRITICAL SPEED 3 HIGH Default: 0.00 RPM
(22.57) Range: -30000.00 to +30000.00 RPM
Defines the high limit for critical speed range 3.
Note: This value must be greater than or equal to the value of 22.56
Critical speed 3 low.
SPEED REFERENCE ACT 1 Default: Read Only
(22.81) Range: -30000.00 to +30000.00 RPM
Displays the value of speed reference source 1 (selected by parameter
22.11 Speed ref1 source). See the control chain diagram on page 546.
This parameter is read-only.
SPEED REFERENCE ACT 2 Default: Read Only
(22.82) Range: -30000.00 to +30000.00 RPM
Displays the value of speed reference source 2 (selected by parameter
22.12 Speed ref2 source). See the control chain diagram on page 546.
This parameter is read-only.
SPEED REFERENCE ACT 3 Default: Read Only
(22.83) Range: -30000.00 to +30000.00 RPM
Displays the value of speed reference after the mathematical function
applied by parameter 22.13 Speed ref1 function and reference
1/2 selection (22.14 Speed ref1/2 selection). See the control chain
diagram.
This parameter is read-only.
SPEED REFERENCE ACT 4 Default: Read Only
(22.84) Range: -30000.00 to +30000.00 RPM
Displays the value of speed reference after application of 1st speed
additive (22.15 Speed additive 1 source). See the control chain
diagram.
This parameter is read-only.
SPEED REFERENCE ACT 5 Default: Read Only
(22.85) Range: -30000.00 to +30000.00 RPM
Displays the value of speed reference after the application of the
speed share scaling factor (22.16 Speed share). See the control chain
diagram.
This parameter is read-only.
SPEED REFERENCE ACT 6 Default: Read Only
(22.86) Range: -30000.00 to +30000.00 RPM
Displays the value of speed reference after application of 2nd speed
additive (22.17 Speed additive 2 source). See the control chain
diagram.
This parameter is read-only.
3AXD50000011888 Startup Assistant & Parameters 12-59
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SPEED SPEED REFERENCE ACT 7 Default: Read Only
REFERENCE (22.87) Range: -30000.00 to +30000.00 RPM
SELECTION
(Continued) Displays the value of speed reference before application of critical
speeds. See the control chain diagram. The value is received from
22.86 Speed reference act 6 unless overridden by
• any constant speed
• a jogging reference
• network control reference
• control panel reference
• safe speed reference.
This parameter is read-only.
SPEED Speed reference ramp settings (programming of the acceleration and deceleration rates for the drive).
REFERENCE See the control chain diagram.
RAMP
SPEED REF RAMP INPUT Default: Read Only
(23.01) Range: -30000.00 to +30000.00 RPM
Displays the used speed reference (in rpm) before it enters the ramping
and shaping functions. See the control chain diagram.
This parameter is read-only.
SPEED REF RAMP OUTPUT Default: Read Only
(23.02) Range: -30000.00 to +30000.00 RPM
Displays the ramped and shaped speed reference in rpm. See the
control chain diagram.
This parameter is read-only.
RAMP SET SELECTION (23.11) Default: 5 (DI4)
Range: 0 - 7, 10, 11, 18
0 (Acc/Dec time 1) 0
1 (Acc/Dec time 2) 1
2 (DI1) Digital input DI1 (10.02 DI delayed status, bit 0)
3 (DI2) Digital input DI2 (10.02 DI delayed status, bit 1)
4 (DI3) Digital input DI3 (10.02 DI delayed status, bit 2)
5 (DI4) Digital input DI4 (10.02 DI delayed status, bit 3)
6 (DI5) Digital input DI5 (10.02 DI delayed status, bit 4)
7 (DI6) Digital input DI6 (10.02 DI delayed status, bit 5)
10 (DIO1) Digital input/output DIO1 (11.02 DIO delayed status, bit 0)
11 (DIO2) Digital input/output DIO2 (11.02 DIO delayed status, bit 1)
Bit 11 (selection of external control location) of the control word
18 (FBA A)
received from fieldbus interface A.
Other Source selection
Selects the source that switches between the two sets of acceleration/
deceleration ramp times defined by parameters 23.12 - 23.15.
0 = Acceleration time 1 and deceleration time 1 are active
1 = Acceleration time 2 and deceleration time 2 are active
ACCELERATION TIME 1 Default: s = Motor Nom Spd/10
(23.12) Range: 5.000 - 1800.000 s
Defines acceleration time 1 as the time required for the speed to
change from zero to the speed defined by parameter 46.01 Speed
scaling (this value is set automatically to 99.09 motor nominal speed).
If the speed reference increases faster than the set acceleration rate,
the motor speed will follow the acceleration rate.
If the speed reference increases slower than the set acceleration rate,
the motor speed will follow the reference.
If the acceleration time is set too short, the drive will automatically
prolong the acceleration in order not to exceed the drive torque limits.
12-60 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SPEED DECELERATION TIME 1 Default: 60s
REFERENCE (23.13) Range: 0.000 - 1800.000 s
RAMP
(Continued) Defines deceleration time 1 as the time required for the speed to
change from the speed defined by parameter 46.01 Speed scaling (set
automatically to the value entered in 99.09 motor nominal speed) to
zero.
If the speed reference decreases slower than the set deceleration rate,
the motor speed will follow the reference.
If the reference changes faster than the set deceleration rate, the
motor speed will follow the deceleration rate.
If the deceleration rate is set too short, the drive will automatically
prolong the deceleration in order not to exceed drive torque limits (or
not to exceed a safe DC link voltage). If there is any doubt about the
deceleration time being too short, ensure that DC overvoltage control
is on (parameter 30.30 Overvoltage control).
Note: If a short deceleration time is needed for a high inertia
application, the drive should be equipped with braking
equipment such as a brake chopper and brake resistor.
ACCELERATION TIME 2 Default: s = Motor Nom Spd/10
(23.14) Range: 0.000 - 1800.000s
Defines acceleration time 2. See parameter 23.12 Acceleration time 1.
DECELERATION TIME 2 Default: 60s
(23.15) Range: 0.000 - 1800.000s
Defines deceleration time 2. See parameter 23.13 Deceleration time 1.
SPEED Speed error calculation; speed error window control configuration; speed error step.
REFERENCE See the control chain diagrams.
CONDITIONING
USED SPEED REFERENCE Default: Read Only
(24.01) Range: -30000.00 to +30000.00 RPM
Displays the ramped and corrected speed reference (before speed
error calculation). See the control chain diagram.
This parameter is read-only.
USED SPEED FEEDBACK Default: Read Only
(24.02) Range: -30000.00 to +30000.00 RPM
Displays the speed feedback used for speed error calculation. See the
control chain diagram.
This parameter is read-only.
3AXD50000011888 Startup Assistant & Parameters 12-61
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SPEED CONTROL Speed controller settings. See the control chain diagrams.
TORQUE REFERENCE SPEED Default: Read Only
CONTROL (25.01) Range: -1600.0 to +1600.0%
Displays the speed controller output that is transferred to the torque
controller. See the control chain diagram.
This parameter is read-only.
SPEED PROPORTIONAL GAIN Default: 0.85
(25.02) Range: 0.00 - 250.00
Defines the proportional gain (Kp) of the speed controller. Too high a
gain may cause speed oscillation. The figure below shows the speed
controller output after anerror step when the error remains constant.
%
Gain = Kp = 1
TI = Integration time = 0
TD= Derivation time = 0
Error value
Controller output
Controller e = Error value
output = Kp × e
Time
If gain is set to 1, a 10% change in error value (reference - actual value)
causes the speed controller output to change by 10%, ie. the output
value is input × gain.
SPEED INTEGRATION TIME Default: 0.50s
(25.03) Range: 0.00 to 1000.00s
Defines the integration time of the speed controller. The integration
time defines the rate at which the controller output changes when the
error value is constant and the proportional gain of the speed controller
is 1. The shorter the integration time, the faster the continuous error
value is corrected. This time constant must be set to the same order
of magnitude as the time constant (time to respond) of the actual
mechanical system being controlled, otherwise instability will result.
Setting the integration time to zero disables the I-part of the controller.
This is useful to do when tuning the proportional gain; adjust the
proportional gain first, then return the integration time.Anti-windup
(the integrator just integrates up to 100%) stops the integrator if the
controller output is limited.The figure below shows the speed controller
output after an error step when the error remains constant.
Controller output
Gain = Kp = 1
TI = Integration time > 0
TD= Derivation time = 0
Kp × e
Kp × e e = Error value
Time
TI
12-62 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SPEED CONTROL SPEED DERIVATION TIME Default: 0.000s
(Continued) (25.04) Range: 0.000 to 1000.00s
Defines the derivation time of the speed controller. Derivative action
boosts the controller output if the error value changes. The longer the
derivation time, the more the speed controller output is boosted during
the change. If the derivation time is set to zero, the controller works as
a PI controller, otherwise as a PID controller. The derivation makes the
control more responsive for disturbances. For simple applications
(especially those without a pulse encoder), derivative time is not
normally required and should be left at zero. The speed error derivative
must be filtered with a low pass filter to eliminate disturbances. The
figure below shows the speed controller output after an error step
when the error remains constant.
SPEED ADAPT MIN LIMIT Default: 0 RPM
(25.18) Range: 0 - 30000 RPM
Minimum actual speed for speed controller adaptation.Speed
controller gain and integration time can be adapted according to actual
speed (90.01 Motor speed for control).
This is done by multiplying the gain (25.02 Speed proportional gain)
and integration time (25.03 Speed integration time) by coefficients at
certain speeds. The coefficients are defined individually for both gain
and integration time.
When actual speed is below or equal to 25.18 Speed adapt min limit,
the gain and integration time are multiplied by 25.21 Kp adapt coef at
min speed and 25.22 Ti adapt coef at min speed respectively.When
actual speed is equal to or above 25.19 Speed adapt max limit, no
adaptation takes place (the coefficient is 1).
When actual speed is between 25.18 Speed adapt min limit and 25.19
Speed adapt max limit, the coefficients for the gain and integration
time are calculated linearly on the basis of the breakpoints.
Coefficient for Kp or TI Kp = Proportional gain
TI = Integration time
1.000
25.21 Kp adapt coef at min speed or
25.22 Ti adapt coef at min speed
Actual speed
(90.01) (rpm)
0 25.18 Speed 25.19 Speed
adapt min limit adapt max limit
SPEED ADAPT MAX LIMIT Default: 0 RPM
(25.19) Range: 0 - 30000 RPM
Maximum actual speed for speed controller adaptation.
See parameter 25.18 Speed adapt min limit.
KP ADAPT COEF AT MIN Default: 1.000
SPEED (25.21) Range: 0.000 to 10.000
Proportional gain coefficient at minimum actual speed.
See parameter 25.18 Speed adapt min limit.
TI ADAPT COEF AT MIN Default: 1.000
SPEED (25.22) Range: 0.000 to 10.000
Integration time coefficient at minimum actual speed.
See parameter 25.18 Speed adapt min limit.
3AXD50000011888 Startup Assistant & Parameters 12-63
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
LIMITS Drive operation limits.
LIMIIT WORD 1 (30.01) Default: Read Only
Range: 0000h - FFFFh
Displays limit word 1. This parameter is read-only.
Bit Name Information
1 = Drive torque is being limited by the motor
control (undervoltage control, current control,
0 Torq lim
load angle control or pull-out control), or by the
torque limits defined by parameters.
1 = Speed controller output is being limited by
1 Spd ctl tlim min
25.11 Speed control min torque
1 = Speed controller output is being limited by
2 Spd ctl tlim max
25.12 Speed control max torque
1 = Torque reference ramp input is being limited
by 26.09 Maximum torque ref, source of 30.25
3 Torq ref max
Maximum torque sel, 30.26 Power motoring limit
or 30.27 Power generating limit.
1 = Torque reference ramp input is being limited
by 26.08 Minimum torque ref, source of 30.18
4 Torq ref min
Minimum torque sel, 30.26 Power motoring limit
or 30.27 Power generating limit.
1 = Torque reference is being limited by the rush
5 Tlim max speed control because of maximum speed limit (30.12
Maximum speed)
1 = Torque reference is being limited by the rush
6 Tlim min speed control because of minimum speed limit (30.11
Minimum speed)
Max speed ref 1 = Speed reference is being limited by 30.12
7
lim Maximum speed
1 = Speed reference is being limited by 30.11
8 Min speed ref lim
Minimum speed
1 = Frequency reference is being limited by
9 Max freq ref lim
30.14 Maximum frequency
1 = Frequency reference is being limited by
10 Min freq ref lim
30.13 Minimum frequency
11 Reserved
1 = Requested output frequency cannot be
reached because of switching frequency
12 Sw freq ref lim
limitation (because of eg. output filtering or
ATEXrelated protections)
13 - 15 Reserved
12-64 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
LIMITS TORQUE LIMIT STATUS Default: Read Only
(Continued) (30.02) Range: 0000h - FFFFh
Displays the torque controller limitation status word.
This parameter is read-only.
Bit Name Information
0 Undervoltage *1 = Intermediate DC circuit undervoltage
1 Overvoltage *1 = Intermediate DC circuit overvoltage
*1 = Torque is being limited by 30.26 Power
2 Minimum torque motoring limit, 30.27 Power generating limit or
the source of 30.18 Minimum torque sel.
*1 = Torque is being limited by 30.26 Power
3 Maximum torque motoring limit, 30.27 Power generating limit or
the source of 30.25 Maximum torque sel.
1 = An inverter current limit (identified by bits
4 Internal current
8 - 11) is active
(With permanent magnet motors and
synchronous reluctance motors only)
5 Load angle
1 = Load angle limit is active, ie. the motor
cannot produce any more torque
(With asynchronous motors only)
6 Motor pullout 1 = Motor pull-out limit is active, ie. the motor
cannot produce any more torque
7 Reserved
1 = Input current is being limited by the main
8 Thermal
circuit thermal limit
9 Max current *1 = Maximum output current (IMAX) is being
limited
*1 = Output current is being limited by 30.17
10 User current
Maximum current
*1 = Output current is being limited by a calculated
11 Thermal IGBT
thermal current value
IGBT *1 = Output current is being limited because of
12
overtemperature estimated IGBT temperature
*1 = Output current is being limited because of
13 IGBT overload
IGBT junction to case temperature
14 - 15 Reserved
*Only one out of bits 0 - 3, and one out of bits 9 - 13 can be on simultaneously.
The bit typically indicates the limit that is exceeded first.
MAXIMUM SPEED (30.12) Default: Motor Nominal Speed
Range: 0.00 to Motor Nominal Speed
Defines the maximum allowed speed. Value is adjustable from 99.09
motor nominal speed or lower.
MAXIMUM START CURRENT Default: 0 (Disable)
ENABLE (30.15) Range: 0, 1
0 (Disable) Start current limit disabled
1 (Enable) Start current limit enabled
A temporary motor current limit specifically for starting can be defined
by this parameter and 30.16 Maximum start current.
When this parameter is set to Enable, the drive observes the start
current limit defined by 30.16 Maximum start current.
The limit is in force for 2 seconds after initial magnetization (of an
asynchronous induction motor) or autophasing (of a permanent
magnet motor), but not more often than once in every 7 seconds.
Otherwise, the limit defined by 30.17 Maximum current is in force.
Note: The availability of a start current higher than the general limit
depends on drive hardware.
3AXD50000011888 Startup Assistant & Parameters 12-65
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
LIMITS MAXIMUM CURRENT (30.17) Default: 0.00 A
(Continued) Range: -30000.00 to +30000.00 RPM
Defines the maximum allowed motor current.
MAXIMUM TORQUE (30.31) Default: 1 (Enable)
Range: 0, 1
0 (Disable) Undervoltage control disabled
1 (Enable) Undervoltage control enabled
Enables the undervoltage control of the intermediate DC link. If the DC
voltage drops due to input power cut off, the undervoltage controller
will automatically decrease the motor torque in order to keep the
voltage above the lower limit. By decreasing the motor torque, the
inertia of the load will cause regeneration back to the drive, keeping
the DC link charged and preventing an undervoltage trip until the
motor coasts to a stop. This will act as a power-loss ride-through
functionality in systems with high inertia, such as a centrifuge or a fan.
FAULT Configuration of external events; selection of behavior of the drive upon fault situations.
FUNCTIONS
EXTERNAL EVENT 1 SOURCE Default: Inactive (1)
(31.01) Range: 0 - 8, 11, 12, Other
0 Active False
1 Inactive True
2 (DIIL) DIIL input (10.02 DI delayed status, bit 15)
3 (DI1) Digital input DI1 (10.02 DI delayed status, bit 0)
4 (DI2) Digital input DI2 (10.02 DI delayed status, bit 1)
5 (DI3) Digital input DI3 (10.02 DI delayed status, bit 2)
6 (DI4) Digital input DI4 (10.02 DI delayed status, bit 3)
7 (DI5) Digital input DI5 (10.02 DI delayed status, bit 4)
8 (DI6) Digital input DI6 (10.02 DI delayed status, bit 5)
11 (DIO1) Digital input/output DIO1 (11.02 DIO delayed status, bit 0)
12 (DIO2) Digital input/output DIO2 (11.02 DIO delayed status, bit 1)
Other [bit] Source selection (see Terms and abbreviations)
Defines the source of external event 1.
See also parameter 31.02 External event 1 type.
0 = Trigger event
1 = Normal operation
EXTERNAL EVENT 1 TYPE Default: 0 (Fault)
(31.02) Range: 0, 1, 3
0 (Fault) The external event generates a fault.
1 (Warning) The external event generates a warning.
If the drive is modulating, the external event generates a fault.
3 (Warning/Fault)
Otherwise, the event generates a warning.
Selects the type of external event 1.
12-66 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
FAULT FAULT RESET SELECTION Default: 4 (DI3)
FUNCTIONS (31.11) Range: 0 - 7, 10, 11, 30, 32, Other
(Continued)
Not selected 0
Selected 1
2 (DI1) Digital input DI1 (10.02 DI delayed status, bit 0)
3 (DI2) Digital input DI2 (10.02 DI delayed status, bit 1)
4 (DI3) Digital input DI3 (10.02 DI delayed status, bit 2)
5 (DI4) Digital input DI4 (10.02 DI delayed status, bit 3)
6 (DI5) Digital input DI5 (10.02 DI delayed status, bit 4)
7 (DI6) Digital input DI6 (10.02 DI delayed status, bit 5)
10 (DIO1) Digital input/output DIO1 (11.02 DIO delayed status, bit 0)
11 (DIO2) Digital input/output DIO2 (11.02 DIO delayed status, bit 1)
30 (FBA A MCW bit 7) Control word bit 7 received through fieldbus interface A
32 (EFB MCW bit 7) Control word bit 7 received through the embedded fieldbus interface
Other [bit] Source selection (see Terms and abbreviations)
Selects the source of an external fault reset signal. The signal resets
the drive after a fault trip if the cause of the fault no longer exists.
0 –> 1 = Reset
Note: A fault reset from the fieldbus interface is always observed
regardless of this parameter.
USER SELECTABLE FAULT Default: 0000h
(31.13) Range: 0000h to FFFFh
Defines the fault that can be automatically reset using parameter 31.12
Autoreset selection, bit 10. The faults are listed in chapter Fault tracing.
NUMBER OF TRIALS (31.14) Default: 0
Range: 0 - 5
Defines the maximum number of automatic resets that the drive is
allowed to attempt within the time specified by 31.15 Total trials time.
If the fault persists, subsequent reset attempts will be made at intervals
defined by 31.16 Delay time.
The faults to be automatically reset are defined by 31.12 Autoreset
selection.
TOTAL TRIALS TIME (31.15) Default: 30.0 s
Range: 1.0 - 600.0 s
Defines a time window for automatic fault resets. The maximum number
of attempts made during any period of this length is defined by 31.14
Number of trials.
Note: If the fault condition remains and cannot be reset, each reset
attempt will generate an event and start a new time window. In
practice, if the specified number of resets (31.14) at specified
intervals (31.16) take longer than the value of 31.15, the drive
will continue to attempt resetting the fault until the cause is
eventually removed.
DELAY TIME (31.16) Default: 0.0 s
Range: 0.0 - 120.0 s
Defines the time that the drive will wait after a fault (or a previous reset
attempt) before attempting an automatic reset. See parameter 31.12
Autoreset selection.
SUPPLY PHASE LOSS (31.21) Default: 1 (Fault)
Range: 0, 1
0 (No action) No action taken.
1 (Fault) The drive trips on fault 3130 Input phase loss.
Selects how the drive reacts when a supply phase loss is detected.
3AXD50000011888 Startup Assistant & Parameters 12-67
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
BRAKE CHOPPER Settings for the internal brake chopper.
BRAKING RESISTOR Default: Read Only
TEMPERATURE (43.01) Range: 0.0 - 120.0%
Displays the estimated temperature of the brake resistor, or how close
the brake resistor is to being too hot.The value is given in percent where
100% is the temperature the resistor would reach if the maximum
continuous braking power (43.09 Brake resistor Pmax cont) is applied to
the resistor for 100% rated time. The thermal time constant (43.08 Brake
resistor thermal tc) defines the rated time to achieve 63% temperature.
100% would be reached when 100% time has elapsed.
BRAKE CHOPPER ENABLE Default: 0 (Disabled)
(43.06) Range: 0 - 2
0 (Disabled)
Brake chopper control disabled.
1 (Enabled with thermal model)Brake chopper enabled with resistor overload protection.
Brake chopper control enabled without resistor overload protection.
2 (Enabled without thermal This setting can be used, for example, if the resistor is equipped with
model) a thermal circuit breaker that is wired to stop the drive if the resistor
overheats.
Enables brake chopper control.
Note: Before enabling brake chopper control, ensure that
• a brake resistor is connected
• overvoltage control is switched off (parameter 30.30 Overvoltage
control)
• the supply voltage range (parameter 95.01 Supply voltage) has been
selected correctly.
BRAKE CHOPPER RUNTIME Default: 1 (On)
ENABLE (43.07) Range: 0, 1
0 (Off) 0
1 (On) 1
(Other [bit]) Source selection
Selects the source for quick brake chopper on/off control.
0 = Brake chopper IGBT pulses are cut off
1 = Normal brake chopper IGBT modulation.
This parameter can be used to program the chopper control to
function only when the supply is missing from a drive with a
regenerative supply unit.
BRAKE RESISTOR THERMAL Default: 0s
TC (43.08) Range: 0 to 10000s
Defines the thermal time constant of the brake resistor for overload
protection.
BRAKE RESISTOR PMAX CONT Default: 0.00 kW
(43.09) Range: 0.00 to 10000.00 kW
Defines the maximum continuous braking power of the resistor (in
kW) which will raise the resistor temperature to the maximum allowed
value. The value is used in the overload protection.
BRAKE RESISTANCE (43.10) Default: 0.0 ohm
Range: 0.0 to 1000.0 ohm
Defines the resistance value of the brake resistor. The value is used for
brake chopper protection.
BRAKE RESISTOR FAULT Default: 105%
LIMIT (43.11) Range: 0 to 150%
Selects the fault limit for the brake resistor temperature protection
function. When the limit is exceeded, the drive trips on fault 7183 BR
excess temperature.The value is given in percent of the temperature
the resistor reaches when loaded with the power defined by parameter
43.09 Brake resistor Pmax cont.
12-68 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
BRAKE CHOPPER BRAKE RESISTOR WARNING Default: 95%
(Continued) LIMIT (43.12) Range: 0 to 150%
Selects the warning limit for the brake resistor temperature protection
function. When the limit is exceeded, the drive generates a A793
BR excess temperature warning.The value is given in percent of the
temperature the resistor reaches when loaded with the power defined
by parameter 43.09 Brake resistor Pmax cont.
ENERGY Settings for the energy saving calculators. See also section Energy saving calculators.
EFFICIENCY
SAVED GW HOURS (45.01) Default: Read Only
Range: 0 - 65535 GWh
Energy saved in GWh compared to direct-on-line motor connection.
This parameter is incremented when 45.02 Saved MW hours rolls over.
See parameter 45.21 Energy calculations reset.
SAVED MW HOURS (45.02) Default: Read Only
Range: 0 - 999 MWh
Energy saved in MWh compared to direct-on-line motor connection.
This parameter is incremented when 45.03 Saved kW hours rolls over.
When this parameter rolls over, parameter 45.01 Saved GW hours is
incremented.
SAVED kW HOURS (45.03) Default: Read Only
Range: 0.0 - 999.9 kWh
Energy saved in kWh compared to direct-on-line motor connection.
If the internal brake chopper of the drive is enabled, all energy fed by
the motor to the drive is assumed to be converted into heat, but the
calculation still records savings made by controlling the speed. If the
chopper is disabled, then
regenerated energy from the motor is also recorded here. When
this parameter rolls over, parameter 45.02 Saved MW hours is
incremented.
Fieldbus Equivalent: 10 = 1 kWh
SAVED MONEY X1000 (45.05) Default: Read Only
Range: 0 - 294967295 thousands
Monetary savings in thousands compared to direct-on-line motor
connection. This parameter is incremented when 45.06 Saved money
rolls over. The currency is defined by parameter 45.17 Tariff currency
unit.
SAVED MONEY (45.06) Default: Read Only
Range: 0.00 - 999.99 units
Monetary savings compared to direct-on-line motor connection.
This value is a calculated by multiplying the saved energy in kWh
by the currently active energy tariff (45.14 Tariff selection). When
this parameter rolls over, parameter 45.05 Saved money x1000
is incremented. The currency is defined by parameter 45.17 Tariff
currency unit.
CO2 REDUCTION IN Default: Read Only
KILOTONS (45.08) Range: 0 - 65535 metric kilotons
Reduction in CO2 emissions in metric kilotons compared to direct-
on-line motor connection. This value is incremented when parameter
45.09 CO2 reduction in tons rolls over.
CO2 REDUCTION IN TONS Default: Read Only
(45.09) Range: 0.0 - 999.9 metric tons
Reduction in CO2 emissions in metric tons compared to direct-on-line
motor connection. This value is calculated by multiplying the saved
energy in MWh by the value of parameter 45.18 CO2 conversion factor
(by default, 0.5 metric tons/MWh).
When this parameter rolls over, parameter 45.08 CO2 reduction in
kilotons is incremented.
3AXD50000011888 Startup Assistant & Parameters 12-69
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
ENERGY ENERGY OPTIMIZER (45.11) Default: 0 (Disable)
EFFICIENCY Range: 0, 1
(Continued)
0 (Disable) Energy optimization disabled
1 (Enable) Energy optimization enabled
Enables/disables the energy optimization function. The function
optimizes the motor flux so that total energy consumption and motor
noise level are reduced when the drive operates below the nominal
load. The total efficiency (motor and drive) can be improved by
1 - 20% depending on load torque and speed.
Note: With a permanent magnet motor or a synchronous reluctance
motor, energy optimization is always enabled regardless of this
parameter.
ENERGY TARIFF 1 (45.12) Default: 1.000 units
Range: 0.000 - 4294967.295 units
Defines energy tariff 1 (price of energy per kWh). Depending on the
setting of parameter 45.14 Tariff selection, either this value or 45.13
Energy tariff 2 is used for reference when monetary savings are
calculated.
The currency is defined by parameter 45.17 Tariff currency unit.
Note: Tariffs are read only at the instant of selection, and are not
applied retroactively.
ENERGY TARIFF 2 (45.13) Default: 2.000 units
Range: 0.000 - 4294967.295 units
Defines energy tariff 2 (price of energy per kWh).
See parameter 45.12 Energy tariff 1.
TARIFF SELECTION (45.14) Default: 0 (Energy tariff 1)
Range: 0 - 7, 10, 11, Other
Energy tariff 1 0
Energy tariff 2 1
2 (DI1) Digital input DI1 (10.02 DI delayed status, bit 0)
3 (DI2) Digital input DI2 (10.02 DI delayed status, bit 1)
4 (DI3) Digital input DI3 (10.02 DI delayed status, bit 2)
5 (DI4) Digital input DI4 (10.02 DI delayed status, bit 3)
6 (DI5) Digital input DI5 (10.02 DI delayed status, bit 4)
7 (DI6) Digital input DI6 (10.02 DI delayed status, bit 5)
10 (DIO1) Digital input/output DIO1 (11.02 DIO delayed status, bit 0)
11 (DIO2) Digital input/output DIO2 (11.02 DIO delayed status, bit 1)
Other [bit] Source selection (see Terms and abbreviations)
Selects (or defines a source that selects) which pre-defined energy
tariff is used.
0 = 45.12 Energy tariff 1
1 = 45.13 Energy tariff 2
TARIFF CURRENCY UNIT Default: 101 (EUR)
(45.17) Range: 100, 101, 102
100 (Local currency) Local currency
101 (EUR) Euro
102 (USD) US dollar
Specifies the currency used for the savings calculations.
12-70 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
ENERGY CO2 CONVERSION FACTOR Default: 0.500 tn/MWh
EFFICIENCY (45.18) Range: 0.000 - 65.535 tn/MWh
(Continued)
Defines a factor for conversion of saved energy into CO2 emissions
(kg/kWh or tn/MWh).
COMPARISON POWER (45.19) Default: 0.0 kW
Range: 0.0 - 100000.0 kW
Actual power that the motor absorbs when connected direct-on-line
and operating the application. The value is used for reference when
energy savings are calculated.
Note: The accuracy of the energy savings calculation is directly
dependent on the accuracy of this value. If nothing is entered
here, then the nominal motor power is used by the calculation,
but that may inflate the energy savings reported as many motors
do not absorb nameplate power.
ENERGY CALCULATIONS Default: 0 (Done)
RESET (45.21) Range: 0, 1
0 (Done) Reset not requested (normal operation), or reset complete.
Reset the savings counter parameters. The value reverts automatically
1 (Reset)
to Done.
Resets the savings counter parameters 45.01 - 45.09.
MONITORING/ Speed supervision settings; actual signal filtering; general scaling settings.
SCALING
SETTINGS SPEED SCALING (46.01) Default: Max Speed (P 30.12)
Range: 0.10 to 30000.00 RPM
Defines the maximum speed value used to define the acceleration
ramp rate and the initial speed value used to define the deceleration
ramp rate (see parameter group 23 Speed reference ramp). The speed
acceleration and deceleration ramp times are therefore related to this
value (not to parameter 30.12 Maximum speed).
Also defines the 16-bit scaling of speed-related parameters. The value
of this parameter corresponds to 20000 in fieldbus, master/follower
etc. communication.
TORQUE SCALING (46.03) Default: 100.0%
Range: 0.1 to 1000.0%
Defines the 16-bit scaling of torque parameters. The value of this
parameter (in percent of nominal motor torque) corresponds to 10000
in fieldbus, master/follower etc. communication.
See also parameter 46.42 Torque decimals.
FILTER TIME MOTOR SPEED Default: 10 ms
(46.11) Range: 2 - 20000 ms
Defines a filter time for signals 01.01 Motor speed used, 01.02 Motor
speed estimated, 01.04 Encoder 1 speed filtered and 01.05 Encoder 2
speed filtered.
FILTER TIME OUTPUT Default: 500 ms
FREQUENCY (46.12) Range: 2 - 20000 ms
Defines a filter time for signal 01.06 Output frequency.
FILTER TIME MOTOR Default: 10 ms
TORQUE (46.13) Range: 2 - 20000 ms
Defines a filter time for signal 01.10 Motor torque %.
3AXD50000011888 Startup Assistant & Parameters 12-71
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
DATA STORAGE Data storage parameters that can be written to and read from using other parameters’ source and target
settings.
Note that there are different storage parameters for different data types. Integer-type storage parameters
cannot be used as the source of other parameters. See also section Data storage parameters.
DATA STORAGE 1 REAL32 Default: 0.000
(47.01) Range: See par. 47.31
Data storage parameter 1.
Parameters 47.01 - 47.08 are real 32-bit numbers that can be used as
source values of other parameters.
Storage parameters 47.01 - 47.08 can be used as the target of
received 16-bit data (parameter group 62 D2D and DDCS receive data)
or the source of transmitted 16-bit data (parameter group 61 D2D and
DDCS transmit data). The scaling and range are defined by parameters
47.31 - 47.38.
DATA STORAGE 2 REAL32 Default: 0.000
(47.02) Range: See par. 47.32
Data storage parameter 2.
See also parameter 47.01 Data storage 1 real32.
DATA STORAGE 3 REAL32 Default: 0.000
(47.03) Range: See par. 47.33
Data storage parameter 3.
See also parameter 47.01 Data storage 1 real32.
DATA STORAGE 1 REAL32 Default: 0 (Unscaled)
TYPE (47.31) Range: 0 - 5
0 (Unscaled) Data storage only. Range: -2147483.264 to +2147473.264
1 (Transparent) Scaling: 1 = 1. Range: -32768 to +32767
2 (General) Scaling: 1 = 100. Range: -327.68 to +327.67
The scaling is defined by parameter 46.03 Torque scaling.
3 (Torque)
Range: -1600.0 to +1600.0
The scaling is defined by parameter 46.01 Speed scaling.
4 (Speed)
Range: -30000.00 to +30000.00
The scaling is defined by parameter 46.02 Frequency scaling.
5 (Frequency)
Range: -500.00 to +500.00
Defines the scaling of parameter 47.01 Data storage 1 real32 to
and from 16-bit integer format. This scaling is used when the data
storage parameter is the target of received 16-bit data (defined in
parameter group 62 D2D and DDCS receive data), or when the data
storage parameter is the source of transmitted 16-bit data (defined in
parameter group 61 D2D and DDCS transmit data).
The setting also defines the visible range of the storage parameter.
DATA STORAGE 2 REAL32 Default: 0 (Unscaled)
TYPE (47.32) Range: 0 - 5
Defines the 16-bit scaling of parameter 47.02 Data storage 2 real32.
See parameter 47.31 Data storage 1 real32 type.
DATA STORAGE 3 REAL32 Default: 0 (Unscaled)
TYPE (47.33) Range: 0 - 5
Defines the 16-bit scaling of parameter 47.03 Data storage 3 real32.
See parameter 47.31 Data storage 1 real32 type.
12-72 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
FIELDBUS Parameters 50 - 56 are for FIELDBUS ONLY and are adapter module-specific. For more
ADAPTER information, see the documentation of the fieldbus adapter module. Note that not all of these
parameters are necessarily in use.
EMBEDDED Configuration of the embedded fieldbus (EFB) interface. See also chapter Fieldbus control through the
FIELDBUS embedded fieldbus interface (EFB).
PROTOCOL ENABLE (58.01) Default: 0 (None)
Range: 0, 1
0 (None) None (communication disabled)
1 (Modbus RTU) Embedded fieldbus interface is enabled and uses the Modbus RTU
protocol
Enables/disables the embedded fieldbus interface and selects the
protocol to use.
Note: When the embedded fieldbus interface is enabled, the drive-to-
drive link functionality is automatically disabled.
PROTOCOL ID (58.02) Default: Read Only
Range: -
Displays the protocol ID and revision.
This parameter is read-only.
NODE ADDRESS (58.03) Default: 1
Range: 0 - 255
Defines the node address of the drive on the fieldbus link.
Values 1 - 247 are allowable. Two devices with the same address are
not allowed on-line.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
BAUD ADDRESS (58.04) Default: 3 (19.2 kbps)
Range: 2 - 7
2 (9.6 kbps) 9.6 kbit/s
3 (19.2 kbps) 19.2 kbit/s
4 (38.4 kbps) 38.4 kbit/s
5 (57.6 kbps) 57.6 kbit/s
6 (76.8 kbps) 76.8 kbit/s
7 (115.2 kbps) 115.2 kbit/s
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
PARITY (58.05) Default: 2 (8 EVEN 1)
Range: 0 - 3
0 (8 NONE 1) Eight data bits, no parity bit, one stop bit
1 (8 NONE 2) Eight data bits, no parity bit, two stop bits
2 (8 EVEN 1) Eight data bits, even parity bit, one stop bit
3 (8 ODD 1) Eight data bits, odd parity bit, one stop bit
Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
3AXD50000011888 Startup Assistant & Parameters 12-73
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED COMMUNICATION CONTROL Default: 0 (Enabled)
FIELDBUS (58.06) Range: 0 - 2
(Continued)
0 (Enabled) Normal operation
1 (Refresh settings) Validates any changed EFB configuration settings. Reverts
automatically to Enabled.
2 (Silent mode) Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the Refresh settings
selection of this parameter.
Validates any changes in the EFB settings, or activates silent mode.
COMMUNICATION Default: Read Only
DIAGNOSTICS (58.07) Range: 0000h - FFFFh
Displays the status of the EFB communication.
This parameter is read-only.
Bit Name Information
0 Init failed 1 = EFB initialization failed
1 Addr config err 1 = Node address not allowed by protocol
1 = Drive not allowed to transmit
2 Silent mode
0 = Drive allowed to transmit
3 Autobauding Reserved
4 Wiring error 1 = Errors detected (A/B wires possibly swapped)
1 = Error detected: check parameters 58.04 and
5 Parity error
58.05
1 = Error detected: check parameters 58.05 and
6 Baud rate error
58.04
7 No bus activity 1 = 0 bytes received during last 5 seconds
1 = 0 packets (addressed to any device) detected
8 No packets
during last 5 seconds
Noise or addressing 1 = Errors detected (interference, or another
9
error device with the same address on line)
1 = 0 packets addressed to the drive received
10 Comm loss
within timeout (58.16)
1 = No control word or references received within
11 CW/Ref loss
timeout (58.16)
12 Not active Reserved
13 Protocol 1 Reserved
14 Protocol 2 Reserved
15 Internal error Reserved
RECEIVED PACKETS (58.08) Default: -
Range: 0 - 4294967295
Displays a count of valid packets addressed to the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
TRANSMITTED PACKETS Default: -
(58.09) Range: 0 - 4294967295
Displays a count of valid packets transmitted by the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
12-74 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED ALL PACKETS (58.10) Default: -
FIELDBUS Range: 0 - 4294967295
(Continued)
Displays a count of valid packets addressed to any device on the bus.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
UART ERRORS (58.11) Default: -
Range: 0 - 4294967295
Displays a count of character errors received by the drive.
An increasing count indicates a configuration problem on the bus.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
CRC ERRORS (58.12) Default: -
Range: 0 - 4294967295
Displays a count of packets with a CRC error received by the drive. An
increasing count indicates interference on the bus.
Can be reset from the control panel by keeping Reset depressed for
over 3 seconds.
COMMUNICATION LOSS Default: 1 (Fault))
ACTION (58.14) Range: 0 - 5
0 (No) No action taken (monitoring disabled).
Drive trips on 6681 EFB comm loss. This only occurs if control is
1 (Fault) expected from the EFB (EFB selected as source of start/stop in the
currently active location).
Drive generates an A7CE EFB comm loss warning and freezes the
speed to the level the drive was operating at. This only occurs if
control is expected from the EFB.
2 (Last speed) The speed is determined on the basis of actual speed using 850 ms
low-pass filtering.
WARNING! Make sure that it is safe to continue operation in case of a
communication break.
Drive generates an A7CE EFB comm loss warning and sets the speed
to the speed defined by parameter 22.41 Speed ref safe (or 28.41
Frequency ref safe when frequency reference is being used). This only
3 (Speed ref safe)
occurs if control is expected from the EFB.
WARNING! Make sure that it is safe to continue operation in case of a
communication break.
Drive trips on 6681 EFB comm loss. This occurs even though no
4 (Fault always)
control is expected from the EFB.
Drive generates an A7CE EFB comm loss warning. This occurs even
though no control is expected from the EFB.
5 (Warning)
WARNING! Make sure that it is safe to continue operation in case of a
communication break.
Selects how the drive reacts to an EFB communication break.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
See also parameters 58.15 Communication loss mode and 58.16
Communication loss time.
3AXD50000011888 Startup Assistant & Parameters 12-75
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED COMMUNICATION LOSS Default: 2 (Cw / Ref1 / Ref2)
FIELDBUS MODE (58.15) Range: 1, 2
(Continued)
1 (Any message) Any message addressed to the drive resets the timeout.
A write of the control word or a reference from the fieldbus resets the
2 (Cw / Ref1 / Ref2)
timeout.
Defines which message types reset the timeout counter for detecting
an EFB communication loss.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
See also parameters 58.14 Communication loss action and 58.16
Communication loss time.
COMMUNICATION LOSS Default: 3.0 s
TIME (58.16) Range: 0.0 - 6000.0 s
Sets a timeout for EFB communication. If a communication break
lasts longer than the timeout, the action specified by parameter 58.14
Communication loss action is taken.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
See also parameter 58.15 Communication loss mode.
TRANSMIT DELAY (58.17) Default: 0 ms
Range: 0 - 65535 ms
Defines a minimum response delay in addition to any fixed delay
imposed by the protocol.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
EFB CONTROL WORD (58.18) Default: Read Only
Range: 0000h - FFFFh
Displays the raw (unmodified) control word sent by the Modbus
controller to the drive. For debugging purposes.
This parameter is read-only.
EFB STATUS WORD (58.19) Default: Read Only
Range: 0000h - FFFFh
Displays the raw (unmodified) status word sent by the drive to the
Modbus controller. For debugging purposes.
This parameter is read-only.
CONTROL PROFILE (58.25) Default: 0 (ABB Drives)
Range: 0, 2
ABB Drives profile (with a 16-bit control word) with registers in the
0 (ABB Drives)
classic format for backward compatibility.
Transparent profile (16-bit or 32-bit control word) with registers in the
2 (Transparent)
classic format.
Defines the control profile used by the protocol.
12-76 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED EFB REF1 TYPE (58.26) Default: 0 (Auto)
FIELDBUS Range: 0 - 5
(Continued)
Type and scaling are chosen automatically according to which
reference chain (see settings Torque, Speed, Frequency) the incoming
0 (Auto)
reference is connected to. If the reference is not connected to any
chain, no scaling is applied (as with setting Transparent).
1 (Transparent) No scaling is applied.
Generic reference with a scaling of 100 = 1 (ie. integer and two
2 (General)
decimals).
3 (Torque) The scaling is defined by parameter 46.03 Torque scaling.
4 (Speed) The scaling is defined by parameter 46.01 Speed scaling.
5 (Frequency) The scaling is defined by parameter 46.02 Frequency scaling.
Selects the type and scaling of reference 1 received through the
embedded fieldbus interface.
The scaled reference is displayed by 03.09 EFB reference 1.
EFB REF2 TYPE (58.27) Default: 3 (Torque)
Range: 0 - 5
Selects the type and scaling of reference 2 received through the
embedded fieldbus interface.
The scaled reference is displayed by 03.10 EFB reference 2.
For the selections, see parameter 58.26 EFB ref1 type.
EFB ACT1 TYPE (58.28) Default: 0 (Auto)
Range: 0 - 6
Type/source and scaling follow the type of reference 1 selected by
0 (Auto) parameter 58.26 EFB ref1 type. See the individual settings below for
the sources and scalings.
The value selected by parameter 58.31 EFB act1 transparent source is
1 (Transparent) sent as actual value 1. No scaling is applied (the 16-bit scaling is 1 = 1
unit).
The value selected by parameter 58.31 EFB act1 transparent source is
2 (General) sent as actual value 1 with a 16-bit scaling of 100 = 1 unit (ie. integer
and two decimals).
01.10 Motor torque is sent as actual value 1. The scaling is defined by
3 (Torque)
parameter 46.03 Torque scaling.
01.01 Motor speed used is sent as actual value 1. The scaling is
4 (Speed)
defined by parameter 46.01 Speed scaling.
01.06 Output frequency is sent as actual value 1. The scaling is
5 (Frequency)
defined by parameter 46.02 Frequency scaling.
Motor position is sent as actual value 1. See parameter 90.06 Motor
6 (Position)
position scaled.
Selects the type/source and scaling of actual value 1 transmitted to the
fieldbus network through the embedded fieldbus interface.
3AXD50000011888 Startup Assistant & Parameters 12-77
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED EFB ACT2 TYPE (58.29) Default: 3 (Torque)
FIELDBUS Range: 0 - 6
(Continued)
Type/source and scaling follow the type of reference 2 selected by
0 (Auto) parameter 58.27 EFB ref2 type. See the individual settings below for
the sources and scalings.
The value selected by parameter 58.32 EFB act2 transparent source is
1 (Transparent) sent as actual value 2. No scaling is applied (the 16-bit scaling is 1 = 1
unit).
The value selected by parameter 58.32 EFB act2 transparent source is
2 (General) sent as actual value 2 with a 16-bit scaling of 100 = 1 unit (ie. integer
and two decimals).
01.10 Motor torque is sent as actual value 2. The scaling is defined by
3 (Torque)
parameter 46.03 Torque scaling.
01.01 Motor speed used is sent as actual value 2. The scaling is
4 (Speed)
defined by parameter 46.01 Speed scaling.
01.06 Output frequency is sent as actual value 2. The scaling is
5 (Frequency)
defined by parameter 46.02 Frequency scaling.
Motor position is sent as actual value 2. See parameter 90.06 Motor
6 (Position)
position scaled.
Selects the type/source and scaling of actual value 2 transmitted to the
fieldbus network through the embedded fieldbus interface.
EFB STATUS WORD Default: 0 (Not selected)
TRANSPARENT SOURCE Range: 0
(58.30)
0 (Not selected) None
Other (-) Source selection (see Terms and abbreviations
Selects the source of the status word when 58.25 Control profile is set
to Transparent.
EFB STATUS ACT1 Default: 0 (Not selected)
TRANSPARENT SOURCE Range: 0
(58.31)
0 (Not selected) None
Other (-) Source selection (see Terms and abbreviations
Selects the source of actual value 1 when 58.28 EFB act1 type is set to
Transparent or General.
EFB STATUS ACT2 Default: 0 (Not selected)
TRANSPARENT SOURCE Range: 0
(58.32)
0 (Not selected) None
Other (-) Source selection (see Terms and abbreviations
Selects the source of actual value 1 when 58.29 EFB act2 type is set to
Transparent or General.
12-78 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED ADDRESSING MODE (58.33) Default: 0 (Mode 0)
FIELDBUS Range: 0 - 2
(Continued)
16-bit values (groups 1 - 99, indexes 1 - 99):
Register address = 400000 + 100 × parameter group + parameter
index. For example, parameter 22.80 would be mapped to register
400000 + 2200 + 80 = 402280.
0 (Mode 0)
32-bit values (groups 1 - 99, indexes 1 - 99):
Register address = 420000 + 200 × parameter group + 2 × parameter
index. For example, parameter 22.80 would be mapped to register
420000 + 4400 + 160 = 424560.
16-bit values (groups 1 - 255, indexes 1 - 255):
Register address = 400000 + 256 × parameter group + parameter
1 ( Mode 1)
index. For example, parameter 22.80 would be mapped to register
400000 + 5632 + 80 = 405712.
32-bit values (groups 1 - 127, indexes 1 - 255):
Register address = 400000 + 512 × parameter group + 2 × parameter
2 ( Mode 2)
index. For example, parameter 22.80 would be mapped to register
400000 + 11264 + 160 = 411424.
Defines the mapping between parameters and holding registers in the
400101 - 465535 Modbus register range.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
WORD ORDER (58.34) Default: 1 (LO-HI)
Range: 0, 1
The first register contains the high order word, the second contains the
0 (HI-LO)
low order word.
The first register contains the low order word, the second contains the
1 (LO-HI)
high order word.
Selects in which order 16-bit registers of 32-bit parameters are
transferred.
For each register, the first byte contains the high order byte and the
second byte contains the low order byte.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
EFB COMM SUPERVISION Default: 0000b
FORCE (58.36) Range: 0000b - 0111b
Activates fieldbus communication monitoring separately for each
control location (see section Local control vs. external control).
The parameter is primarily intended for monitoring the communication
with EFB when it is connected to the application program and not
selected as a control source by drive parameters.
Bit Name Information
1 = Communication monitoring active when Ext 1 is
0 Ext 1
being used
1 = Communication monitoring active when Ext 2 is
1 Ext 2
being used
1 = Communication monitoring active when local
2 Local
control is being used
3-15 Reserved
3AXD50000011888 Startup Assistant & Parameters 12-79
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED DATA I/O 1 (58.101) Default: 1 (CW 16bit)
FIELDBUS Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
(Continued)
0 (None) None
1 (CW 16bit) Control Word (16 bits)
2 (Ref1 16bit) Reference REF1 (16 bits)
3 (Ref2 16bit) Reference REF2 (16 bits)
4 (SW 16bit) Status Word (16 bits)
5 (Act1 16bit) Actual value ACT1 (16 bits)
6 (Act2 16bit) Actual value ACT2 (16 bits)
11 (CW 32bit) Control Word (32 bits)
12 (Ref1 32bit) Reference REF1 (32 bits)
13 (Ref2 32bit) Reference REF2 (32 bits)
14 (SW 32bit) Status Word (32 bits)
15 (Act1 32bit) Actual value ACT1 (32 bits)
16 (Act2 32bit) Actual value ACT2 (32 bits)
Control Word 2 (16 bits)
21 (CW2 16bit) When a 32-bit control word is used, this setting means the most-
significant 16 bits
Status Word 2 (16 bits).
24 (SW2 16bit) When a 32-bit control word is used, this setting means the most-
significant 16 bits
31 (RO/DIO control word) Parameter 10.99 RO/DIO control word
32 (AO1 data storage) Parameter 13.91 AO1 data storage
33 (AO2 data storage) Parameter 13.92 AO2 data storage
40 (Feedback data storage) Parameter 40.91 Feedback data storage
41 (Setpoint data storage) Parameter 40.92 Setpoint data storage
Other (-) Source selection (see Terms and abbreviations)
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400001.
The master defines the type of the data (input or output). The value is
transmitted in a Modbus frame consisting of two 16-bit words. If the
value is 16-bit, it is transmitted in the LSW (least significant word). If
the value is 32-bit, the subsequent parameter is also reserved for it
and must be set to None.
DATA I/O 2 (58.102) Default: 2 (Ref1 16bit)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400002.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 3 (58.103) Default: 3 (Ref2 16bit)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400003.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 4 (58.104) Default: 4 (SW 16bit)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400004.
For the selections, see parameter 58.101 Data I/O 1.
12-80 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED DATA I/O 5 (58.105) Default: 5 (Act1 16bit)
FIELDBUS Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
(Continued)
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400005.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 6 (58.106) Default: 6 (Act2 16bit)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400006.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 7 (58.107) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400007.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 8 (58.108) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400008.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 9 (58.109) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400009.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 10 (58.110) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400010.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 11 (58.111) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400011.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 12 (58.112) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400012.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 13 (58.113) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400013.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 14 (58.114) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400014.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 15 (58.115) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400015.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 16 (58.116) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400016.
For the selections, see parameter 58.101 Data I/O 1.
3AXD50000011888 Startup Assistant & Parameters 12-81
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
EMBEDDED DATA I/O 17 (58.117) Default: 0 (None)
FIELDBUS Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
(Continued)
Parameter selector for Modbus register address 400017.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 18 (58.118) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400018.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 19 (58.119) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400019.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 20 (58.120) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400020.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 21 (58.121) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400021.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 22 (58.122) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400022.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 23 (58.123) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400023.
For the selections, see parameter 58.101 Data I/O 1.
DATA I/O 24 (58.124) Default: 0 (None)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Parameter selector for Modbus register address 400024.
For the selections, see parameter 58.101 Data I/O 1.
TRICKLE Trickle currrent prevents rotation of fan during standby condition (anti wind mill feature). This can be
CURRENT caused by exterior wind conditions or by adjacent tower airflow that can act on the fan blades. Trickle
current will produce a low level dc voltage across the windings of the direct drive motor. The dc voltage
when applied to a permanent magnet motor will inhibit rotation of the fan blades. As a secondary benefit
the voltage will produce enough heating in the motor windings to inhibit condensation in the motor
caused by humidity. Operation will be while the tower is in a power on but standby mode.
TRICKLE CURRENT ENABLE Default: 0 (Disable)
(74.01) Range: 0 - 4
0 (Disable) Trickle Current is not used.
Trickle Current is active at all times after the Trickle Delay Time (74.03)
1 (Enable)
has completed.
2 (DIO1) Trickle Current is Enabled via DIO1.
3 (FBA) Trickle Current is Enabled via the FBA Control Word (6.01) - Bit 0.
4 (EFB) Trickle Current is Enabled via the EFB Control Word (6.01) - Bit 0.
Software Enable (1) or Disable (0) Trickle Current parameter setting.
A hardware enable on DIO1, FBA and EFB is also required to activate
Trickle Current.
12-82 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
TRICKLE TRICKLE POWER (74.02) Default: 100W
CURRENT Range: 0 - 500W
(Continued)
The level of trickle current is determined by frame size of the motor and
input to the drive power level, no decimal required. Formula for how
current value is determined:
Motor Frame Size Wattage
FL250 75
FL280 100
FL320 125
FL360 150
FL400 175
FL440 225
FL5800 400
Setting is entered as a power level.
TRICKLE DELAY TIME (74.03) Default: 1 Min
Range: 0 - 10 Min
The time delay before trickle current starts. This delay ensures the
motor has ramped down and stopped prior to trickle current beginning.
DE-ICE FUNCTION This is a cooling tower function to run at a low speed but in the opposite direction than standard.
Primarily this function is to prevent ice buildup in towers for colder climates. De-Ice function consists of a
setting for the speed and a time value.
DE-ICE ENABLE (75.01) Default: 0 (Disable)
Range: 0 - 3
0 (Disable) De-Ice mode is not used.
1 (DIO2) De-Ice mode is Enabled via DIO2.
2 (FBA) De-Ice mode is Enabled via the FBA Control Word (6.01) - Bit 1.
3 (EFB) De-Ice mode is Enabled via the EFB Control Word (6.01) - Bit 1.
Disable (0) De-Ice function. A hardware enable on DIO2, FBA and EFB
is also required to activate De-Ice function.
DE-ICE SPEED (75.02) Default: 30%
Range: 0 - 100%
De-Ice speed can be reprogrammed from 0% to 100% speed.
DE-ICE RUN TIME (75.03) Default: 1 Min
Range: 0 - 1500 Mins
Value of time to run in De-Ice function when Software Enable is active,
and a hardware input is present. Drive will run at De-Ice function speed
for the set run time and then shut down.
Note: Zero range means that the De-Ice Mode will run until disabled.
CTD MOTOR AUTOPHASING CURRENT Default: 50% Current
CONTROL (76.01) Range: 0 to 150% Current
The Autophasing current is the DC current level the drive puts out to
line up the rotor.
AUTOPHASING TIME (76.02) Default: 100 Seconds
Range: 0 to 100 Seconds
The Autophasing time is how long the rotor can take to settle out
before rotation is started. Because of the high inertia of the large fans,
it could take 100 seconds to settle out.
3AXD50000011888 Startup Assistant & Parameters 12-83
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
CTD MOTOR OPERATING MODE (76.03) Default: 1 (2-Wire)
CONTROL Range: 0 - 5
(Continued)
0 Custom
1 2-Wire
2 3-Wire
3 PID control
4 Fieldbus
5 EFB
Operating Mode sets the method to start the drive for normal
operation. Mode 1-5 configures DI1 and DI2 for EXT2 control. Custom
mode allows custom programming of EXT1 control. Trickle and De-Ice
always use EXT2. In modes 1-5, De-Ice has priority and Trickle will
automatically start when drive is in standby.
In Custom mode drive must be stopped before De-Ice will start. Trickle
must be stopped before normal run.
The CTDD application requires a limited set of operating modes. It
is envisioned that the selection for this will be through CTDD Setup
assistant programmed.
CT MINIMUM SPEED (76.04) Default: 0 RPM
Range: 0 to 650 RPM
Sets the minimum forward operating speed of the CTDD motor.
HW SUPPLY VOLTAGE (95.01) Default: -
CONFIGURATION Range: 0 - 6
No voltage range selected. The drive will not start modulating before a
0 (Not Given)
range is selected.
1 (208 - 240V) 208 - 240V
2 (380 - 415V) 380 - 415V (Default for Demo Unit)
3 (440 - 480V) 440 - 480V
4 (500V) 500V (Default for normal drive)
5 (525 - 600V) 525 - 600V
6 (660 - 690V) 660 - 690V
Selects the supply voltage range. This parameter is used by the drive
to determine the nominal voltage of the supply network. The parameter
also affects the current ratings and the DC voltage control functions
(trip and brake chopper activation limits) of the drive.
WARNING: An incorrect setting may cause the motor to rush
uncontrollably, or the brake chopper or resistor to
overload.
Note: The selections shown depend on the hardware of the drive. If
only one voltage range is valid for the drive in question, it is
selected by default.
CONTROL BOARD SUPPLY Default: 0 (Internal 24V)
(95.04) Range: 0 - 2
The drive control unit is powered from the drive power unit it is
0 (Internal 24V)
connected to.
1 (External 24V) The drive control unit is powered from an external power supply.
(Type BCU control units only) The drive control unit is powered from
2 (Redundant external 24V) two redundant external power supplies. The loss of one of the supplies
generates a warning (AFEC External power signal missing).
Specifies how the control unit of the drive is powered.
12-84 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SYSTEM LANGUAGE (96.01) Default: English
Range: -
Not selected None
English English
Deutsch German
Italiano Italian
Español Spanish
Portugues Portuguese
Nederlands Dutch
Français French
Dansk Danish
Suomi Finnish
Svenska Swedish
Russki Russian
Polski Polish
Czech Czech
Türkçe Turkish
Selects the language of the parameter interface and other displayed
information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the Drive
composer PC tool. (Those are specified under View – Settings.)
PASS CODE (96.02) Default: -
Range: 0 to 99999999
14 CTDD User
13 Fieldbus
12 Expert Commissioner
Does not default. Setting access level to 13 (Fieldbus) opens all
Fieldbus applicable parameters (groups 50 to 56 and monitoring
parameters 3.05, 3.06, 6.01 and 6.11). Expert commissioner enables
all parameters in the drive by setting 96.02 = 12.
ACCESS LEVELS STATUS Default: Read Only
(96.03) Range: -
11 Expert Commissioner
12 Fieldbus
13 CTDD User
Shows which access levels have been activated by pass codes
entered into parameter 96.02 Pass code.
Parameter 96.03 shows the current access level setting, note ABB
default will show active with the addition of the set level shown above.
Value is offset by one from the password entered.
3AXD50000011888 Startup Assistant & Parameters 12-85
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SYSTEM MACRO SELECT (96.04) Default: CTDD
(Continued) Range:
CTDD
Done
Selects the application macro. Only CTDD macro is available.
After a selection is made, the parameter reverts automatically to Done.
Note: Selecting 96.04 will cause a reset to factory default (selecting
CTDD).
MACRO ACTIVE (96.05) Default: Read Only
Range: CTDD
CTDD
Defaults to CTDD.
To change the macro, use parameter 96.04 Macro select.
PARAMETER RESTORE Default: 0 (Done)
(96.06) Range: 0, 8, 62
0 (Done) Restoring is completed.
All editable parameter values are restored to default values, except
• motor data and ID run results
• control panel/PC communication settings
• I/O extension module settings
8 (Restore defaults)
• fieldbus adapter settings
• encoder configuration data
• parameter 95.20 HW options word 1 and the differentiated defaults
implemented by it.
All editable parameter values are restored to default values, except
• control panel/PC communication settings
• fieldbus adapter settings
62 (Clear all)
• parameter 95.20 HW options word 1 and the differentiated defaults
implemented by it.
PC tool communication is interrupted during the restoring.
Restores the original settings of the control program (parameter default
values).
Note: This parameter cannot be changed while the drive is running.
PARAMETER SAVE Default: 0 (Done)
MANUALLY (96.07) Range: 0, 1
0 (Done) Save completed.
1 (Save) Save in progress.
Saves the valid parameter values to permanent memory. This
parameter should be used to store values sent from a fieldbus, or
when using an external power supply to the control board as the
supply might have a very short hold-up time when powered off.
Note: A new parameter value is saved automatically when changed
from the PC tool or control panel but not when altered through a
fieldbus adapter connection.
12-86 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
SYSTEM UNIT SELECTION (96.16) Default: 0001 0001
(Continued) Range: 0000h - FFFFh
Selects the unit of parameters indicating power, temperature and
torque. Default setting is HP, °F and lb-ft.
Bit Name Information
0 = kW
0 Power unit
1 = hp default
1 Reserved
0 = C (°C) default
2 Temperature unit
1 = F (°F)
3 Reserved
0 = Nm (N·m)
4 Torque unit
1 = lbft (lb·ft) default
5 - 15 Reserved
MOTOR DATA MOTOR TYPE (99.03) Default: 1 (PMSM)
Range: 0, 1
0 Training Demo
Permanent magnet synchronous motor. Three-phase AC synchronous
1
motor with permanent magnet rotor and sinusoidal Back EMF voltage.
Selects the motor type.
Note: This parameter cannot be changed while the drive is running.
MOTOR CONTROL MODE Default: 0 (DTC)
(99.04) Range: 0, 1
Direct torque control. This mode is suitable for most applications.
Note: Instead of direct torque control, scalar control is also available,
and should be used in the following situations:
• with multimotor applications 1) if the load is not equally shared
between the motors, 2) if the motors are of different sizes, or 3) if the
0 (DTC) motors are going to be changed after the motor identification (ID run)
• if the nominal current of the motor is less than 1/6 of the nominal
output current of the drive
• if the drive is used with no motor connected (for example, for test
purposes).
See also section Operating modes of the drive.
Scalar control. The outstanding motor control accuracy of DTC cannot
be achieved in scalar control.
Refer to the DTC selection above for a list of applications where scalar
control should definitely be used.
Notes:
1 (SCALAR)
• Correct motor operation requires that the magnetizing current of the
motor does not exceed 90% of the nominal current of the inverter.
• Some standard features are disabled in scalar control mode.
See also section Scalar motor control (page 60), and section Operating
modes of the drive.
Selects the motor control mode.
MOTOR NOMINAL CURRENT Default: 0.0 A
(99.06) Range: 0.0 - 6400.0 A
Defines the nominal motor current. Must be equal to the value on the
motor rating plate. If multiple motors are connected to the drive, enter
the total current of the motors.
Note: This parameter cannot be changed while the drive is running.
3AXD50000011888 Startup Assistant & Parameters 12-87
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
MOTOR DATA BACK EMF VOLTAGE (99.07) Default: Back EMF
(Continued) Range: 0.0 - 800.0
Defines the motor Back EMF voltage. This setting must match the
value on the auxiliary rating plate of the motor.
Notes:
• With permanent magnet motors, the nominal voltage is the Back
EMF voltage at nominal speed of the motor.
• The stress on the motor insulation is always dependent on the
drive supply voltage. This also applies to the case where the motor
voltage rating is lower than that of the drive and the supply.
• This parameter cannot be changed while the drive is running.
MOTOR NOMINAL Default: 0.0 Hz
FREQUENCY (99.08) Range: 0.0 - 500.0 Hz
Defines the nominal motor frequency. This setting must match the
value on the rating plate of the motor.
Note: This parameter cannot be changed while the drive is running.
MOTOR NOMINAL SPEED Default: 0 RPM
(99.09) Range: 0 - 650 RPM
Defines the nominal motor speed. The setting must match the value on
the rating plate of the motor.
Note: This parameter cannot be changed while the drive is running.
MOTOR NOMINAL POWER Default: 0.00 kW or hp
(99.10) Range: -10000.00 to +10000.00 kW or -13404.83 to +13404.83 hp
Defines the nominal motor power. The setting must match the value on
the rating plate of the motor. The unit is selected by parameter 96.16
Unit selection.
Note: This parameter cannot be changed while the drive is running.
MOTOR NOMINAL COS Default: 0.00
(99.11) Range: 0.00 - 1.00
Cosphi of the motor. Defines the cosphi of the motor for a more
accurate motor model. The value is not obligatory, but is useful with
an asynchronous motor, especially when performing a standstill
identification run. The setting should match the value on the rating
plate of the motor.
With a permanent magnet or synchronous reluctance motor, this value
is not needed.
Note: This parameter cannot be changed while the drive is running.
MOTOR NOMINAL TORQUE Default: 0.000 N·m or lb·ft
(99.12) Range: 0.000 to N·m or lb·ft
Defines the nominal motor shaft torque. This value can be given
instead of nominal power (99.10) if shown on the rating plate of the
motor.
The unit is selected by parameter 96.16 Unit selection.
Notes:
• This setting is an alternative to the nominal power value (99.10). If
both are entered, 99.12 takes priority.
• This parameter cannot be changed while the drive is running.
12-88 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions Continued
Parameter (Number)
Block Title Descriptions
Selection (Value)
MOTOR DATA ID RUN REQUESTED (99.13) Default: 0 (None)
(Continued) Range: 0 - 7
0 (None) See Firmware Manual.
1 (Normal) See Firmware Manual.
2 (Reduced) See Firmware Manual.
Preferred ID run mode for cooling tower applications -- Standstill
ID run. The motor is injected with DC current. With an AC induction
3 (Standstill)
asynchronous) motor, the motor shaft is not rotated. With a permanent
magnet motor, the shaft can rotate up to half a revolution.
4 (Autophasing) See Firmware Manual.
5 (Current Measurement
See Firmware Manual.
Calibration)
6 (Advanced) See Firmware Manual.
7 (Advanced Standstill) See Firmware Manual.
Selects the type of the motor identification routine (ID run) performed
at the next start of the drive. During the ID run, the drive will identify the
characteristics of the motor for optimum motor control.
If no ID run has been performed yet (or if default parameter values have
been restored using parameter 96.06 Parameter restore), this parameter is
automatically set to Standstill, signifying that an ID run must be performed.
After the ID run, the drive stops and this parameter is automatically set to
None.
Notes:
• For the Advanced ID run, the machinery must always be de-coupled from
the motor.
• With a permanent magnet or synchronous reluctance motor, a Normal,
Reduced or Standstill ID run requires that the motor shaft is NOT locked
and the load torque is less than 10%.
• With scalar control mode (99.04 Motor control mode = Scalar), only the
Current measurement calibration ID run mode is possible.
• Once the ID run is activated, it can be canceled by stopping the drive.
• The ID run must be performed every time any of the motor parameters
(99.04, 99.06 - 99.12) have been changed.
• Ensure that the Safe torque off and emergency stop circuits (if any) are
closed during the ID run.
• Mechanical brake (if present) is not opened by the logic for the ID run.
• This parameter cannot be changed while the drive is running.
LAST ID RUN PERFORMED Default: 0 (None)
(99.14) Range: 0 - 6
Shows the type of ID run that was performed last.
• See parameter 99.13.
MOTOR POLEPAIRS Default: Read Only
CALCULATED (99.15) Range: 0 - 1000
Calculated number of pole pairs in the motor.
MOTOR PHASE ORDER Default: 0 (U V W)
(99.16) Range: 0, 1
0 (U V W) Normal
1 (U W V) Reversed Rotation Direction
Switches the rotation direction of motor. This parameter can be used if
the motor turns in the wrong direction (i.e. because of the wrong phase
order in the motor cable), and correcting the cabling is considered
impractical.
Note: Changing this parameter does not affect speed reference
polarities, so positive speed reference will rotate the motor
forward. The phase order selection ensures that “forward” is the
correct direction.
3AXD50000011888 Startup Assistant & Parameters 12-89
Table 12-4 Level 1 Parameter Block Definitions Continued
NOTES
_____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
____________________________________________________________________________________________________________________________________________________________________________
12-90 Startup Assistant & Parameters 3AXD50000011888
Chapter 13
Troubleshooting
The ACS880+N5350 will annunciate events that are abnormal during operation as a warnings or fault. The codes and names
of active warnings/faults are displayed on the control panel of the drive. Only the codes of warnings/faults are available over
fieldbus.
The chapter lists the warning and fault messages including possible causes and corrective actions. The causes of most
warnings and faults can be identified and corrected using the information in this chapter.
13.1 Warnings and Faults
Warnings do not need to be reset; they stop showing when the cause of the warning ceases. Warnings do not latch and the
drive will continue to operate the motor.
Faults do latch inside the drive and cause the drive to trip, and the motor stops. After the cause of a fault has been removed,
the fault can be reset from a selectable 386 Fault tracing source (see parameter 31.11 Fault reset selection) such as the
control panel, Drive composer PC tool, the digital inputs of the drive, or fieldbus. After the fault is reset, the drive can be
restarted.
13.1.1 Pure Events
In addition to warnings and faults, there are pure events that are only recorded in the event log of the drive. The codes of
these events are included in the Warning messages table.
13.1.2 Editable Messages
For some warnings and faults, the message text can be edited and instructions and contact information added. To edit these
messages, choose Menu - Settings - Edit texts on the control panel.
13.2 Warning/Fault History
13.2.1 Event Log
All indications are stored in the event log with a time stamp and other information. The event log can be accessed from the
main Menu on the control panel. It can also be accessed (and reset) using the Drive composer PC tool. In Drive composer,
some faults are presented with additional data recorded prior to the fault; refer to Drive composer Start-up and maintenance
PC tool User’s manual (3AUA0000094606.
13.2.2 Auxiliary Codes
Some events generate an auxiliary code that often helps in pinpointing the problem. On the control panel, the auxiliary code
is stored as part of the details of the event; in the Drive composer PC tool, the auxiliary code is shown in the event listing.
13.2.3 Parameters that Contain Warning/Fault Information
The drive is able to store a list of the active faults actually causing the drive to trip at the present time. The faults are
displayed in parameter group 04 Warnings and faults. The parameter group also displays a list of faults and warnings that
have previously occurred.
3AXD50000011888 Troubleshooting 13-1
13.3 Warning Messages
NOTE: This list contains events that only appear in the Event Log.
Table 13-1 Warning Messages (Alphabetical by Keypad Text)
Warning Fault # Cause What to do
Current offset and gain
Informative warning. (See parameter 99.13 ID run
Current Calibration A2A1 measurement calibration
requested.)
will occur at next start.
Check motor load.
Check acceleration times in parameter group 23 Speed
reference ramp (speed control), 26 Torque reference chain
(torque control) or 28 Frequency reference chain
(frequency control). Also check parameters 46.01 Speed
scaling, 46.02 Frequency scaling and 46.03 Torque
scaling.
Output current has
Check motor and motor cable (including phasing and
Overcurrent A2B1 exceeded internal fault
delta/star connection).
limit.
Check there are no contactors opening and closing in
motor cable.
Check that the start-up data in parameter group 99
corresponds to the motor rating plate.
Check that there are no power factor correction
capacitors or surge absorbers in motor cable.
Check encoder cable (including phasing).
Check there are no power factor correction capacitors or
surge absorbers in motor cable.
Check for an earth fault in motor or motor cables by
Drive has detected load
measuring the insulation resistances of motor and motor
unbalance typically due to
Earth leakage A2B3 cable.
earth fault in motor or
Try running the motor in scalar control mode if allowed.
motor cable.
(See parameter 99.04 Motor control mode.)
If no earth fault can be detected, contact your local ABB
representative.
Check motor and motor cable for cabling errors.
Short-circuit in motor
Short circuit A2B4 Check there are no power factor correction capacitors or
cable(s) or motor.
surge absorbers in motor cable.
Excessive IGBT junction to
Check motor cable.
case temperature. This
Check ambient conditions.
warning protects the
IGBT overload A2BA Check air flow and fan operation.
IGBT(s) and can be
Check heatsink fins for dust pick-up.
activated by a short
Check motor power against drive power.
circuit in the motor cable.
Intermediate circuit DC
DC link overvoltage A3A1 voltage too high (when the
drive is stopped).
Check the supply voltage setting (parameter 95.01 Supply
Intermediate circuit DC voltage). Note that the wrong setting of the parameter
DC link
A3A2 voltage too low (when the may cause the motor to rush uncontrollably, or may
undervoltage
drive is stopped). overload the brake chopper or resistor.
Check the supply voltage. If the problem persists, contact
The voltage of the your local ABB representative.
intermediate DC circuit
DC not charged A3AA
has not yet risen to
operating level.
Difference in DC voltages
DC voltage between parallel-
A3C1 Contact your local ABB representative.
difference connected inverter
modules.
Calculated motor cable Check the settings of parameters 35.61 and 35.62.
Motor cable
A480 temperature has exceeded Check the dimensioning of the motor cable in regard to
overload
warning limit. required load.
13-2 Troubleshooting 3AXD50000011888
Table 13-1 Warning Messages (Alphabetical by Keypad Text) Continued
Warning Fault # Cause What to do
Check the settings of temperature source parameters
Sensor type mismatch
35.11 and 35.21 against 91.21 and 91.24.
Incorrect
temperature A490 Faulty wiring between an
Check the wiring of the sensor.
sensor setup encoder interface module
The auxiliary code (see the event log) identifies the
and the temperature
interface module. (0 = Module 1, 1 = Module 2).
sensor.
External Check the value of parameter 35.02 Measured
temperature Measured temperature temperature 1.
1 A491 1 has exceeded warning Check the cooling of the motor (or other equipment
limit. whose temperature is being measured).
(Editable message text) Check the value of 35.13 Temperature 1 warning limit.
External Check the value of parameter 35.03 Measured
temperature Measured temperature temperature 2.
2 A492 2 has exceeded warning Check the cooling of the motor (or other equipment
limit. whose temperature is being measured).
(Editable message text) Check the value of 35.23 Temperature 2 warning limit.
Check ambient conditions.
IGBT Estimated drive IGBT Check air flow and fan operation.
A4A1
overtemperature temperature is excessive. Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check ambient temperature. If it exceeds 40°C (104°F),
ensure that load current does not exceed derated load
Drive module temperature capacity of drive. See appropriate Hardware Manual.
Cooling A4A9
is excessive. Check drive module cooling air flow and fan operation.
Check inside of cabinet and heatsink of drive module for
dust pick-up. Clean whenever necessary.
Check ambient conditions.
Power unit module Check air flow and fan operation.
Excess temperature A4B0
temperature is excessive. Check heatsink fins for dust pick-up.
Check motor power against drive power.
High temperature
Excess temperature difference Check the motor cabling.
A4B1
difference between the IGBTs of Check cooling of drive module(s).
different phases.
Check ambient conditions.
Drive IGBT temperature is Check air flow and fan operation.
IGBT temperature A4F6
excessive. Check heatsink fins for dust pick-up.
Check motor power against drive power.
Communication errors
detected between the Check the connections between the drive control unit and
PU communication A580
drive control unit and the the power unit.
power unit.
Safe torque off Safe torque off function is
Check safety circuit connections. For more information,
active, i.e. safety circuit
Programmable warning: A5A0 see appropriate drive hardware manual and description of
31.22 STO indication signal(s) connected to
parameter 31.22 STO indication run/stop.
run/stop connector XSTO is lost.
Problem with internal
Measurement circuit
A5EA temperature measurement Contact your local ABB representative.
temperature
of the drive.
Power unit power supply
PU board powerfail A5EB Contact your local ABB representative.
failure.
Communication errors
PU communication detected between the Check the connections between the drive control unit and
A5EC
internal drive control unit and the the power unit.
power unit.
Measurement circuit
A5ED Measurement circuit fault. Contact your local ABB representative.
ADC
3AXD50000011888 Troubleshooting 13-3
Table 13-1 Warning Messages (Alphabetical by Keypad Text) Continued
Warning Fault # Cause What to do
Measurement circuit
A5EE Measurement circuit fault. Contact your local ABB representative.
DFF
State feedback from
PU state feedback A5EF output phases does not Contact your local ABB representative.
match control signals.
Charging feedback signal Check the feedback signal coming from the charging
Charging feedback A5F0
missing. system.
The motor parameters are Check the settings of the motor configuration parameters
set incorrectly. in group 99.
Motor nominal value A6A4
The drive is not
Check that the drive is sized correctly for the motor.
dimensioned correctly.
Check that all the required parameters in group 99 have
Parameters in group 99 been set.
No motor data A6A5
have not been set. Note: It is normal for this warning to appear during the
start-up and continue until the motor data is entered.
Supply voltage The supply voltage has
A6A6 Set supply voltage in parameter 95.01 Supply voltage.
unselected not been defined.
The drive does not have a
functionality requested Check PLC programming.
FBA A parameter
A6D1 by a PLC, or requested Check settings of parameter groups 50 Fieldbus adapter
conflict
functionality has not been (FBA) and 51 FBA A settings.
activated.
The drive does not have a
functionality requested Check PLC programming.
FBA B parameter
A6D2 by a PLC, or requested Check settings of parameter groups 50 Fieldbus adapter
conflict
functionality has not been (FBA) and 54 FBA B settings.
activated.
Check the event log for an auxiliary code. The code
The current/voltage identifies the analog input whose settings are in conflict.
hardware setting of an Adjust either the hardware setting (on the drive control
AI parametrization A6E5 analog input does unit) or parameter 12.15/12.25.
not correspond to Note: Control board reboot (either by cycling the power or
parameter settings. through parameter 96.08 Control board boot) is required
to validate any changes in the hardware settings.
Motor stall Motor is operating in stall
region because of e.g. Check motor load and drive ratings.
A780
Programmable warning: excessive load or Check fault function parameters.
31.24 Stall function
insufficient motor power.
Motor fan Check external fan (or other equipment controlled) by the
No feedback received
A781 logic.
Programmable warning: from external fan.
35.106 DOL starter event type Check settings of parameters 35.100…35.106.
Error in temperature
measurement when
Check that parameter 35.11 Temperature 1 source /
temperature sensor (KTY
35.21 Temperature 2 source setting corresponds to actual
or PTC) connected to
encoder interface installation.
encoder interface FEN-xx
FEN temperature A782 is used.
Error in temperature
measurement when KTY FEN-01 does not support temperature measurement with
sensor connected to KTY sensor. Use PTC sensor or other encoder interface
encoder interface FEN-01 module.
is used.
Brake resistor broken or Check that a brake resistor has been connected.
Brake resistor A791
not connected. Check the condition of the brake resistor.
13-4 Troubleshooting 3AXD50000011888
Table 13-1 Warning Messages (Alphabetical by Keypad Text) Continued
Warning Fault # Cause What to do
Stop drive. Let resistor cool down.
Brake resistor temperature Check resistor overload protection function settings
has exceeded warning (parameter group 43 Brake chopper).
BR excess
A793 limit defined by parameter Check warning limit setting, parameter 43.12 Brake
temperature
43.12 Brake resistor resistor warning limit.
warning limit. Check that the resistor has been dimensioned correctly.
Check that braking cycle meets allowed limits.
Brake resistor data has Check the resistor data settings (parameters
BR data A794
not been given. 43.08…43.10).
Check the event log for an auxiliary code (format XXYY
ZZZZ). “XX” specifies the number of the encoder interface
Speed feedback
Speed feedback module (01: 91.11/91.12, 02: 91.13/91.14), “YY” specifies
A797 configuration has
configuration the encoder (01: 92 Encoder 1 configuration, 02: 93
changed.
Encoder 2 configuration). “ZZZZ” indicates the problem
(see actions for each code below).
Adapter not found in
0001 Check module location (91.12 or 91.14).
specified slot.
Detected type of interface
Check the module type (91.11 or 91.13) against status
0002 module does not match
(91.02 or 91.03).
parameter setting.
0003 Logic version too old. Contact your local ABB representative.
0004 Software version too old. Contact your local ABB representative.
Encoder type incompatible
Check module type (91.11 or 91.13) against encoder type
0006 with interface module
(92.01 or 93.01).
type.
0007 Adapter not configured. Check module location (91.12 or 91.14).
Speed feedback
Use parameter 91.10 Encoder parameter refresh) to
0008 configuration has
validate any changes in the settings.
changed.
Replace brake chopper if external. Drives with internal
Short circuit in brake
BC short circuit A79B choppers will need to be returned to ABB.
chopper IGBT
Ensure brake resistor is connected and not damaged.
Let chopper cool down.
Check for excessive ambient temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Brake chopper IGBT Check the dimensioning and cooling of the cabinet.
BC IGBT excess
A79C temperature has exceeded Check resistor overload protection function settings
temperature
internal warning limit. (parameters 43.06…43.10).
Check minimum allowed resistor value for the chopper
being used.
Check that braking cycle meets allowed limits.
Check that drive supply AC voltage is not excessive.
Mechanical brake Check mechanical brake connection.
Status of mechanical
closing failed Check mechanical brake settings in parameter group 44
brake acknowledgement
A7A1 Mechanical brake control.
is not as expected during
Programmable warning: Check that acknowledgement signal matches actual
44.17 Brake fault function brake close.
status of brake.
Mechanical brake Check mechanical brake connection.
Status of mechanical
opening failed Check mechanical brake settings in parameter group 44
brake acknowledgement
A7A2 Mechanical brake control.
is not as expected during
Programmable warning: Check that acknowledgement signal matches actual
44.17 Brake fault function brake open.
status of brake.
3AXD50000011888 Troubleshooting 13-5
Table 13-1 Warning Messages (Alphabetical by Keypad Text) Continued
Warning Fault # Cause What to do
Open conditions of
mechanical brake Check mechanical brake settings in parameter group 44
Mechanical brake
cannot be fulfilled (for Mechanical brake control (especially 44.11 Keep brake
opening not allowed
A7A5 example, brake has been closed).
Programmable warning: prevented from opening Check that acknowledgement signal (if used) matches
44.17 Brake fault function
by parameter 44.11 Keep actual status of brake.
brake closed).
Check the event log for an auxiliary code (format 0000
XXYY). “XX” specifies the number of the I/O extension
module (01: parameter group 14 I/O extension module
1, 02: 15 I/O extension module 2, 03: 16 I/O extension
The hardware current/ module 3). “YY” specifies the analog input on the module.
voltage setting of an For example, in case of I/O extension module 1, analog
FIO-11 AI analog input (on an input AI1 (auxiliary code 0000 0101), the hardware
A7AA
parametrization I/O extension module) current/voltage setting on the module is shown by
does not correspond to parameter 14.29. The corresponding parameter setting is
parameter settings. 14.30. Adjust either the hardware setting on the module
or the parameter to solve the mismatch.
Note: Control board reboot (either by cycling the power or
through parameter 96.08 Control board boot) is required
to validate any changes in the hardware settings.
The I/O extension module Check the event log for an auxiliary code. The code
types and locations indicates which I/O extension module is affected.
Extension I/O
A7AB specified by parameters Check the type and location settings of the modules
configuration failure
do not match the detected (parameters 14.01, 14.02, 15.01, 15.02, 16.01 and 16.02).
configuration. Check that the modules are properly installed.
Check the event log for an auxiliary code (format XXYY
Motor speed ZZZZ). “XX” specifies the number of the encoder interface
feedback No motor speed feedback module (01: 91.11/91.12, 02: 91.13/91.14), “YY” specifies
A7B0
Programmable warning:
is received. the encoder (01: 92 Encoder 1 configuration, 02: 93
90.45 Motor feedback fault Encoder 2 configuration). “ZZZZ” indicates the problem
(see actions for each code below).
Motor gear definition
0001 Check motor gear settings (90.43 and 90.44).
invalid or outside limits.
Check encoder settings (92 Encoder 1 configuration or 93
Encoder 2 configuration).
0002 Encoder not configured.
Use parameter 91.10 Encoder parameter refresh) to
validate any changes in the settings.
0003 Encoder stopped working. Check encoder status.
0004 Encoder drift detected. Check for slippage between encoder and motor.
Check status of fieldbus communication. See user
Cyclical communication
FBA A documentation of fieldbus interface.
between drive and
communication Check settings of parameter groups 50 Fieldbus adapter
fieldbus adapter module
A7C1 (FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A
A or between PLC and
Programmable warning: data out.
50.02 FBA A comm loss func fieldbus adapter
Check cable connections.
module A is lost.
Check if communication master is able to communicate.
Cyclical communication Check status of fieldbus communication. See user
FBA B between drive and documentation of fieldbus interface.
communication fieldbus adapter module Check settings of parameter group 50 Fieldbus adapter
A7C2
Programmable warning:
B or between PLC and (FBA).
50.32 FBA B comm loss func fieldbus adapter Check cable connections.
module B is lost. Check if communication master is able to communicate.
DDCS controller Check status of controller. See user documentation of
DDCS (fiber optic)
comm loss controller.
communication between
A7CA Check settings of parameter group 60 DDCS
Programmable warning: drive and external
60.59 DDCS controller communication.
controller is lost.
comm loss function Check cable connections. If necessary, replace cables.
13-6 Troubleshooting 3AXD50000011888
Table 13-1 Warning Messages (Alphabetical by Keypad Text) Continued
Warning Fault # Cause What to do
Check status of other drives on the master/follower link.
MF comm loss
Master/follower Check settings of parameter group 60 DDCS
A7CB
Programmable warning: communication is lost. communication.
60.09 M/F comm loss function
Check cable connections. If necessary, replace cables.
Check the event log for an auxiliary code (format XXYY
ZZZZ). “XX” specifies the number of the encoder interface
module (01: 91.11/91.12, 02: 91.13/91.14), “YY” specifies
Encoder 1 A7E1 Encoder error.
the encoder (01: 92 Encoder 1 configuration, 02: 93
Encoder 2 configuration). “ZZZZ” indicates the problem
(see actions for each code below).
Check the conductor order at both ends of the encoder
cable.
Check the groundings of the encoder cable.
0001 Cable fault
If the encoder was working previously, check the encoder,
encoder cable and encoder interface module for damage.
See also parameter 92.21 Encoder cable fault mode.
0002 No encoder signal Check the condition of the encoder.
0003 Overspeed Contact your local ABB representative.
0004 Overfrequency Contact your local ABB representative.
0005 Resolver ID run failed Contact your local ABB representative.
0006 Resolver overcurrent fault Contact your local ABB representative.
0007 Speed scaling error Contact your local ABB representative.
Panel loss Control panel or PC tool Check PC tool or control panel connection.
selected as active control Check control panel connector.
Programmable warning: A7EE
49.05 Communication loss location for drive has Check mounting platform if being used.
action ceased communicating. Disconnect and reconnect the control panel.
Motor bearing Check the event log for an auxiliary code.
Programmable warnings: Check the source of the warning corresponding to the
33.14 On-time 1
warn message Warning generated by an code:
33.24 On-time 2 A880 ontime timer or a value 0: 33.13 On-time 1 source
warn message counter. 1: 33.23 On-time 2 source
33.55 Value counter 1
warn message 4: 33.53 Value counter 1 source
33.65 Value counter 2
warn message
5: 33.63 Value counter 2 source.
Output relay A881 Warning generated by an
Motor starts A882 edge counter. Check the event log for an auxiliary code.
Programmable warnings: Check the source of the warning corresponding to the
Power ups A883 33.35 Edge counter 1 code:
warn message 2: 33.33 Edge counter 1 source
Main contactor A884 33.45 Edge counter 2 3: 33.43 Edge counter 2 source.
DC charge A885 warn message
On-time 1
(Editable message text) Warning generated by on- Check the source of the warning (parameter 33.13 On-
A886
Programmable warning: time timer 1. time 1 source).
33.14 On-time 1 warn
message
On-time 2
(Editable message text) Warning generated by on- Check the source of the warning (parameter 33.23 On-
A887
Programmable warning: time timer 2. time 2 source).
33.24 On-time 2 warn
message
Edge counter 1
(Editable message text) Warning generated by Check the source of the warning (parameter 33.33 Edge
A888
Programmable warning: edge counter 1. counter 1 source).
33.35 Edge counter 1
warn message
3AXD50000011888 Troubleshooting 13-7
Table 13-1 Warning Messages (Alphabetical by Keypad Text) Continued
Warning Fault # Cause What to do
Edge counter 2
(Editable message text) Warning generated by Check the source of the warning (parameter 33.43 Edge
A889
Programmable warning: edge counter 2. counter 2 source).
33.45 Edge counter 2
warn message
Value counter 1
(Editable message text) Warning generated by Check the source of the warning (parameter 33.53 Value
A88A
Programmable warning: value counter 1. counter 1 source).
33.55 Value counter 1
warn message
Value counter 2
(Editable message text) Warning generated by Check the source of the warning (parameter 33.63 Value
A88B
Programmable warning: value counter 2. counter 2 source).
33.65 Value counter 2
warn message
Device clean A88C Warning generated by an
Check the event log for an auxiliary code.
DC capacitor A88D ontime timer.
Check the source of the warning corresponding to the
Programmable warnings:
code:
Cabinet fan A88E 33.14 On-time 1
0: 33.13 On-time 1 source
warn message
Cooling fan A88F 1: 33.23 On-time 2 source
33.24 On-time 2
10: 05.04 Fan on-time counter.
Additional cooling A890 warn message
AI supervision Check signal level at the analog input.
An analog signal is outside
Check the wiring connected to the input.
Programmable warning: A8A0 the limits specified for the
12.03 AI supervision Check the minimum and maximum limits of the input in
analog input.
function parameter group 12 Standard AI.
Signal supervision
Warning generated by
(Editable message text) Check the source of the warning (parameter 32.07, 32.17
Programmable warning: A8B0 a signal supervision
32.06 Supervision 1 action or 32.28).
32.16 Supervision 2 action
function.
32.26 Supervision 3 action
External warning 1
Check the external device.
(Editable message text)
Programmable warning:
A981 Fault in external device 1. Check setting of parameter 31.01 External event 1
31.01 External event 1 source source.
31.02 External event 1 type
External warning 2
Check the external device.
(Editable message text)
Programmable warning:
A982 Fault in external device 2. Check setting of parameter 31.03 External event 2
31.03 External event 2 source source.
31.04 External event 2 type
External warning 3
Check the external device.
(Editable message text)
Programmable warning:
A983 Fault in external device 3. Check setting of parameter 31.05 External event 3
31.05 External event 3 source source.
31.06 External event 3 type
External warning 4
Check the external device.
(Editable message text)
Programmable warning:
A984 Fault in external device 4. Check setting of parameter 31.07 External event 4
31.07 External event 4 source source.
31.08 External event 4 type
External warning 5
Check the external device.
(Editable message text)
Programmable warning:
A985 Fault in external device 5. Check setting of parameter 31.09 External event 5
31.09 External event 5 source source.
31.10 External event 5 type
Check status of other converter (parameters 06.36 and
FA2FA DDCS com DDCS (fiber optic)
06.39).
loss communication between
Check settings of parameter group 60 DDCS
AF80 converters (for example,
communication. Check the corresponding settings in the
Programmable warning: the inverter unit and the
60.79 INU-LSU com loss ctrl control program of the other converter.
supply unit) is lost.
Check cable connections. If necessary, replace cables.
13-8 Troubleshooting 3AXD50000011888
Table 13-1 Warning Messages (Alphabetical by Keypad Text) Continued
Warning Fault # Cause What to do
If using a control panel or the Drive composer tool,
Line side unit The supply unit has connect to the supply unit to read the warning code.
AF85
warning generated a warning. Refer to the firmware manual of the supply unit for
instructions related to the code.
Process PID sleep The drive is entering sleep Informative warning. See section Sleep function for
AF8C
mode mode. process PID control, and parameters 40.41…40.48.
A fault is about to be Informative warning. See the settings in parameter group
Autoreset AFAA
autoreset. 31 Fault functions.
Drive has received an
Emergency stop Check that it is safe to continue operation. Then return
AFE1 emergency stop (mode
(off2) emergency stop push button to normal position. Restart
selection off2) command.
drive.
Drive has received an If the emergency stop was unintentional, check the
Emergency stop emergency stop (mode source selected by parameter 21.05 Emergency stop
AFE2
(off1 or off3) selection off1 or off3) source.
command.
Enable start signal
missing No enable start signal Check the setting of (and the source selected by)
AFEA
received. parameter 20.19 Enable start command.
(Editable message text)
Check setting of parameter 20.12 Run enable 1 source.
No run enable signal is
Run enable missing AFEB Switch signal on (e.g. in the fieldbus Control Word) or
received.
check wiring of selected source.
95.04 Control board
supply is set to External
External power 24V but no voltage is Check the external 24 V DC power supply to the control
AFEC
signal missing connected to the unit, or change the setting of parameter 95.04.
XPOW connector of the
control unit.
Motor ID run will occur at
Identification run AFF6 Informative warning.
next start.
Autophasing will occur at
Autophasing AFF7 Informative warning.
next start.
STO event Safe torque off function is
Check safety circuit connections. For more information,
active, i.e. safety circuit
B5A0 see appropriate drive hardware manual and description of
Programmable event: signal(s) connected to
31.22 STO indication run/stop parameter 31.22 STO indication run/stop.
connector XSTO is lost.
3AXD50000011888 Troubleshooting 13-9
13.4 Fault Messages
Table 13-2 Fault Messages (Alphabetical by Keypad Text)
Fault Fault # Cause What to do
Measured offset of output
phase current
measurement or
Try performing the current calibration again (select Current
difference between output
Calibration 2281 measurement calibration at parameter 99.13). If the fault
phase U2 and W2 current
persists, contact your local ABB representative.
measurement is too great
(the values are updated
during current calibration).
Check motor load.
Check acceleration times in parameter group 23 Speed
reference ramp (speed control), 26 Torque reference chain
(torque control) or 28 Frequency reference chain
(frequency control). Also check parameters 46.01 Speed
scaling, 46.02 Frequency scaling and 46.03 Torque
scaling.
Output current has
Check motor and motor cable (including phasing and
Overcurrent 2310 exceeded internal fault
delta/star connection).
limit.
Check there are no contactors opening and closing in
motor cable.
Check that the start-up data in parameter group 99
corresponds to the motor rating plate.
Check that there are no power factor correction
capacitors or surge absorbers in motor cable.
Check encoder cable (including phasing).
Check there are no power factor correction capacitors or
surge absorbers in motor cable.
Check for an earth fault in motor or motor cables by
Earth leakage Drive has detected load
measuring the insulation resistances of motor and motor
unbalance typically due to
2330 cable.
Programmable fault: 31.20 earth fault in motor or
Earth fault Try running the motor in scalar control mode if allowed.
motor cable.
(See parameter 99.04 Motor control mode.)
If no earth fault can be detected, contact your local ABB
representative.
Check motor and motor cable for cabling errors.
Check there are no power factor correction capacitors or
surge absorbers in motor cable.
Short-circuit in motor
Short circuit 2340 After correcting the cause of the fault, reboot the control
cable(s) or motor
unit (using parameter 96.08 Control board boot) or by
cycling
power.
Excessive IGBT junction
Check motor cable.
to case temperature. This
Check ambient conditions.
fault protects the IGBT(s)
IGBT overload 2381 Check air flow and fan operation.
and can be activated by a
Check heatsink fins for dust pick-up.
short circuit in the motor
Check motor power against drive power.
cable.
Input phase loss Intermediate circuit DC
Check input power line fuses.
voltage is oscillating due
3130 Check for loose power cable connections.
Programmable fault: 31.21 to missing input power
Supply phase loss Check for input power supply imbalance.
line phase or blown fuse.
No acknowledgement
Charge relay lost 3180 received from charge Contact your local ABB representative.
relay.
Incorrect input power and
Cross connection motor cable connection
Programmable fault: 31.23
3181 (i.e. input power cable is Check input power connections.
Cross connection connected to drive motor
connection).
13-10 Troubleshooting 3AXD50000011888
Table 13-2 Fault Messages (Alphabetical by Keypad Text) Continued
Fault Fault # Cause What to do
Check that overvoltage control is on (parameter 30.30
Overvoltage control).
Check that the supply voltage matches the nominal input
voltage of the drive.
Excessive intermediate
DC link overvoltage 3210 Check the supply line for static or transient overvoltage.
circuit DC voltage.
Check brake chopper and resistor (if present).
Check deceleration time.
Use coast-to-stop function (if applicable).
Retrofit drive with brake chopper and brake resistor.
Intermediate circuit DC
voltage is not sufficient
DC link because of a missing
3220 Check supply cabling, fuses and switchgear.
undervoltage supply phase, blown
fuse or fault in the rectifier
bridge.
Automatic restart failed
Check the condition of the supply (voltage, cabling, fuses,
Standby timeout 3280 (see section Automatic
switchgear).
restart.
Difference in DC voltages
DC voltage between parallel-
3291 Contact your local ABB representative.
difference connected
inverter modules.
Output phase loss Motor circuit fault due to
missing motor connection
3381 Connect motor cable.
Programmable fault: 31.19 (all three phases are not
Motor phase loss
connected).
Try other autophasing modes (see parameter 21.13
Autophasing mode) if possible.
Check that the motor ID run has been successfully
Autophasing routine (see completed.
Autophasing 3385 section Autophasing has Clear parameter 98.15 Position offset user.
failed. Check that the encoder is not slipping on the motor shaft.
Check that the motor is not already turning when the
autophasing routine starts.
Check the setting of parameter 99.03 Motor type.
Calculated motor cable Check the settings of parameters 35.61 and 35.62.
Motor cable
4000 temperature has Check the dimensioning of the motor cable in regard to
overload
exceeded warning limit. required load.
Check ambient conditions.
IGBT Estimated drive IGBT Check air flow and fan operation.
4210
overtemperature temperature is excessive. Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check ambient temperature. If it exceeds 40°C (104°F),
ensure that load current does not exceed derated load
Drive module temperature capacity of drive. See appropriate Hardware Manual.
Cooling 4290
is excessive. Check drive module cooling air flow and fan operation.
Check inside of cabinet and heatsink of drive module for
dust pick-up. Clean whenever necessary.
Check ambient conditions.
Drive IGBT temperature is Check air flow and fan operation.
IGBT temperature 42F1
excessive. Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check ambient conditions.
Power unit module Check air flow and fan operation.
Excess temperature 4310
temperature is excessive. Check heatsink fins for dust pick-up.
Check motor power against drive power.
High temperature
Excess temperature difference Check the motor cabling.
4380
difference between the IGBTs of Check cooling of drive module(s).
different phases.
3AXD50000011888 Troubleshooting 13-11
Table 13-2 Fault Messages (Alphabetical by Keypad Text) Continued
Fault Fault # Cause What to do
Check the value of parameter 35.02 Measured
External temperature 1.
temperature Measured temperature 1 Check the cooling of the motor (or other equipment whose
1 4981
has exceeded fault limit. temperature is being measured).
(Editable message text) Check the value of parameter 35.12 Temperature 1 fault
limit.
Check the value of parameter 35.03 Measured
External temperature 2.
temperature Measured temperature 2 Check the cooling of the motor (or other equipment whose
2 4982
has exceeded fault limit. temperature is being measured).
(Editable message text) Check the value of parameter 35.22 Temperature 2 fault
limit.
Cooling fan stuck or
Fan 5080 Check fan operation and connection. Replace fan if faulty.
disconnected.
An auxiliary cooling fan
(connected to the fan Check auxiliary fan(s) and connection(s). Replace fan if
Auxiliary fan broken 5081 connectors on the faulty. Reboot the control unit (using parameter 96.08
control unit) is stuck or Control board boot) or by cycling power.
disconnected.
STO hardware Safe torque off hardware
5090 Contact your local ABB representative.
failure failure.
Safe torque off function is
Safe torque off active, i.e. safety circuit Check safe torque off circuit connections. For more
Programmable fault: 31.22
5091 signal(s) connected to information, see appropriate drive hardware manual and
STO indication run/stop connector XSTO is broken description of parameter 31.22 STO indication run/stop.
during start or run.
Cycle the power to the drive. If the control unit is
externally powered, also reboot the control unit (using
Power unit memory has
PU logic error 5092 parameter 96.08 Control board boot) or by cycling its
cleared.
power. If the problem persists, contact your local ABB
representative.
The hardware of the
drive does not match the
information stored in the
Rating ID mismatch 5093 memory unit. This Cycle the power to the drive.
may occur eg. after
a firmware update or
memory unit replacement.
The way the control unit is
powered does not
Check setting of 95.04 Control board supply.
correspond
to parameter setting.
PU communication 5681
Communication errors
detected between the Check the connection between the control unit and the
drive control unit and the power unit.
power unit.
Connection between the
Check the connection between the control unit and the
Power unit lost 5682 drive control unit and the
power unit.
power unit is lost.
PU communication Internal communication
5690 Contact your local ABB representative.
internal error.
Measurement
5691 Measurement circuit fault. Contact your local ABB representative.
circuit ADC
Power unit power supply
PU board powerfail 5692 Contact your local ABB representative.
failure.
Measurement
5693 Measurement circuit fault. Contact your local ABB representative.
circuit DFF
13-12 Troubleshooting 3AXD50000011888
Table 13-2 Fault Messages (Alphabetical by Keypad Text) Continued
Fault Fault # Cause What to do
Version check cannot find
PU communication
5694 a matching power unit Contact your local ABB representative.
configuration
FPGA logic.
Check that the value of 95.13 Reduced run mode
corresponds to the number of inverter modules present.
Number of inverter Check that the modules present are powered from the
modules detected does DC bus and connected by fiber optic cables to the BCU
Reduced run 5695 not match the value of control unit.
parameter 95.13 If all modules of the inverter unit are in fact available
Reduced run mode. (eg. maintenance work has been completed), check
that parameter 95.13 is set to 0 (reduced run function
disabled).
State feedback from
PU state feedback 5696 output phases does not Contact your local ABB representative.
match control signals.
Charging feedback signal Check the feedback signal coming from the charging
Charging feedback 5697
missing. system.
Unknown power Unidentified power unit Check power unit logic and firmware compatibility.
5698
unit fault logic fault. Contact your local ABB representative.
Contact your local ABB representative.
Internal SW error 6180 Internal error. Quote the auxiliary code (check the event details in the
event log).
Firmware and FPGA file Reboot the control unit (using parameter 96.08 Control
FPGA version
6181 version in the power unit board boot) or by cycling power. If the problem persists,
incompatible
are incompatible. contact your local ABB representative.
Fieldbus adapter A
FBA A mapping file 6306 Contact your local ABB representative.
mapping file read error.
Fieldbus adapter B
FBA B mapping file 6307 Contact your local ABB representative.
mapping file read error.
Reboot the control unit (using parameter 96.08 Control
Task overload 6481 Internal fault. board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Reboot the control unit (using parameter 96.08 Control
Stack overflow 6487 Internal fault. board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Reboot the control unit (using parameter 96.08 Control
Internal file load 64A1 File read error. board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Internal record load 64A2 Internal record load error. Contact your local ABB representative.
Reboot the control unit (using parameter 96.08 Control
Application file
Application loading 64A3 board boot) or by cycling power. If the problem persists,
incompatible or corrupted.
contact your local ABB representative.
Switch off the power to the control unit and reinstall
the memory unit. In case the memory unit was not
actually removed when the fault occurred, check that
The memory unit was
Memory unit the memory unit is properly inserted into its connector
64B0 detached when the
detached and its mounting screw is tight. Reboot the control unit
control unit was powered.
(using parameter 96.08 Control board boot) or by cycling
power. If the problem persists, contact your local ABB
representative.
Reboot the control unit (using parameter 96.08 Control
Internal SSW fault 64B1 Internal fault. board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
3AXD50000011888 Troubleshooting 13-13
Table 13-2 Fault Messages (Alphabetical by Keypad Text) Continued
Fault Fault # Cause What to do
Loading of user parameter
set failed because
• requested set does
not exist Ensure that a valid user parameter set exists. Reload if
User set fault 64B2
• set is not compatible uncertain.
with control program
• drive was switched off
during loading.
Reboot the control unit (using parameter 96.08 Control
Kernel overload 64E1 Operating system error. board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Parameter load or save Try forcing a save using parameter 96.07 Parameter save
Parameter system 6581
failed. manually. Retry.
The drive does not have a
functionality requested by Check PLC programming.
FBA A parameter
65A1 PLC, or requested Check settings of parameter groups 50 Fieldbus adapter
conflict
functionality has not been (FBA) and 51 FBA A settings.
activated.
The drive does not have a
functionality requested by Check PLC programming.
FBA B parameter
65A2 PLC, or requested Check settings of parameter groups 50 Fieldbus adapter
conflict
functionality has not been (FBA) and 54 FBA B settings.
activated.
Reset the fault. Contact your local ABB representative if
Text data overflow 6881 Internal fault.
the fault persists.
Text 32-bit table Reset the fault. Contact your local ABB representative if
6882 Internal fault.
overflow the fault persists.
Text 64-bit table Reset the fault. Contact your local ABB representative if
6883 Internal fault.
overflow the fault persists.
Reset the fault. Contact your local ABB representative if
Text file overflow 6885 Internal fault.
the fault persists.
Check that all option modules are properly seated in their
Communication between slots.
Option module
7080 drive and an option Check that all option modules or slot connectors are
comm loss
module is lost. not damaged. To pinpoint the problem, try installing the
modules into different slots one at a time.
Panel port Control panel or PC tool
communication Check PC tool or control panel connection.
selected as active control
7081 Check control panel connector. Disconnect and reconnect
location for drive has
Programmable fault: 49.05 the control panel.
Communication loss action ceased communicating.
Check the event log for an auxiliary code (format XXYY
The I/O extension module
YYYY). “XX” specifies the number of the I/O extension
types specified by
module (01: parameter group 14 I/O extension module
Ext I/O comm loss 7082 parameters do not
1, 02: 15 I/O extension module 2, 03: 16 I/O extension
match the detected
module 3). “YY YYYY” indicates the problem (see actions
configuration.
for each code below).
Check that the module is properly seated in its slot.
Communication with
00 0001 Check that the module and the slot connector is not
module failed.
damaged. Try installing the module into another slot.
00 0002 Module not found.
Check the type and location settings of the modules
Configuration of module (parameters 14.01/14.02, 15.01/15.02 or 16.01/16.02).
00 0003
failed. Check that the module is properly seated in its slot.
Check that the module and the slot connector is not
Configuration of module damaged. Try installing the module into another slot.
00 0004
failed.
13-14 Troubleshooting 3AXD50000011888
Table 13-2 Fault Messages (Alphabetical by Keypad Text) Continued
Fault Fault # Cause What to do
Motor stall Motor is operating in stall
region because of e.g. Check motor load and drive ratings.
7121
Programmable fault: 31.24 excessive load or Check fault function parameters.
Stall function
insufficient motor power.
Check that a brake resistor has been connected.
Brake resistor broken or
Brake resistor 7181 Check the condition of the brake resistor.
not connected.
Check the dimensioning of the brake resistor.
Stop drive. Let resistor cool down.
Brake resistor temperature
Check resistor overload protection function settings
has exceeded fault limit
BR excess (parameter group 43 Brake chopper).
7183 defined by parameter
temperature Check fault limit setting, parameter 43.11 Brake resistor
43.11 Brake resistor
fault limit.
fault limit.
Check that braking cycle meets allowed limits.
Check brake chopper and brake resistor connection.
Brake resistor short circuit
Brake resistor Ensure brake resistor is not damaged. After correcting the
7184 or brake chopper control
wiring cause of the fault, reboot the control unit (using parameter
fault.
96.08 Control board boot) or by cycling power.
Ensure brake resistor is connected and not damaged.
Check the electrical specifications of the brake resistor
Short circuit in brake against the Hardware manual.
BC short circuit 7191
chopper IGBT. Replace brake chopper (if replaceable). After correcting
the cause of the fault, reboot the control unit (using
parameter 96.08 Control board boot) or by cycling power.
Let chopper cool down.
Check for excessive ambient temperature.
Check for cooling fan failure.
Brake chopper IGBT
Check for obstructions in the air flow.
BC IGBT excess temperature has
7192 Check the dimensioning and cooling of the cabinet.
temperature exceeded internal fault
Check resistor overload protection function settings
limit.
(parameter group 43 Brake chopper).
Check that braking cycle meets allowed limits.
Check that drive supply AC voltage is not excessive.
Mechanical brake control
Mechanical brake Check mechanical brake connection.
fault.
closing failed Check mechanical brake settings in parameter group 44
Activated eg. if brake
71A2 Mechanical brake control.
acknowledgement is not
Programmable fault: 44.17 Check that acknowledgement signal matches actual
Brake fault function as expected during brake
status of brake.
closing.
Mechanical brake control
Mechanical brake Check mechanical brake connection.
fault.
opening failed Check mechanical brake settings in parameter group 44
Activated eg. if brake
71A3 Mechanical brake control.
acknowledgement is not
Programmable fault: 44.17 Check that acknowledgement signal matches actual
Brake fault function as expected during brake
status of brake.
opening.
Open conditions of
Mechanical brake mechanical brake cannot Check mechanical brake settings in parameter group 44
opening not allowed be fulfilled (for example, Mechanical brake control (especially 44.11 Keep brake
71A5 brake has been prevented closed).
Programmable fault: 44.17 from opening by Check that acknowledgement signal (if used) matches
Brake fault function
parameter 44.11 Keep actual status of brake.
brake closed).
Motor fan Check external fan (or other equipment controlled) by the
No feedback received
71B1 logic.
Programmable fault: from external fan.
35.106 DOL starter event type Check settings of parameters 35.100…35.106.
Motor speed
feedback No motor speed feedback
7301 See A7B0 Motor speed feedback.
Programmable fault: 90.45
received.
Motor feedback fault
3AXD50000011888 Troubleshooting 13-15
Table 13-2 Fault Messages (Alphabetical by Keypad Text) Continued
Fault Fault # Cause What to do
Motor is turning faster
than highest allowed
Check minimum/maximum speed settings, parameters
speed due to incorrectly
30.11 Minimum speed and 30.12 Maximum speed.
set minimum/maximum
Overspeed 7310 Check adequacy of motor braking torque.
speed, insufficient braking
Check applicability of torque control.
torque or changes in
Check need for brake chopper and resistor(s).
load when using torque
reference.
If using a control panel or the Drive composer tool,
Line side converter The supply unit has connect to the supply unit to read the fault code. Refer
7358
faulted tripped on a fault. to the firmware manual of the supply unit for instructions
related to the code.
Encoder internal 7380 Internal fault. Contact your local ABB representative.
Encoder 1 7381 Encoder feedback fault. See A7E1 Encoder 1.
Speed feedback Speed feedback
73A0 See A797 Speed feedback configuration.
configuration configuration incorrect.
Check the event log for an auxiliary code (format XXYY
ZZZZ). “XX” specifies the number of the encoder interface
Load position No load feedback module (01: 91.11/91.12, 02: 91.13/91.14), “YY” specifies
73A1
feedback received. the encoder (01: 92 Encoder 1 configuration, 02: 93
Encoder 2 configuration). “ZZZZ” indicates the problem
(see actions for each code below).
Load gear definition
0001 Check load gear settings (90.53 and 90.54).
invalid or outside limits.
Feed constant definition
0002 Check feed constant settings (90.63 and 90.64).
invalid or outside limits.
Motor/load gear definition
0003 Check motor/load gear settings (90.61 and 90.62).
invalid or outside limits.
Check encoder settings (92 Encoder 1 configuration or 93
Encoder 2 configuration).
0004 Encoder not configured.
Use parameter 91.10 Encoder parameter refresh) to
validate any changes in the settings.
0005 Encoder stopped working. Check encoder status.
Check the settings of parameters 31.32
Emergency stop did not Emergency ramp supervision and 31.33
Emergency ramp
73B0 finish within expected Emergency ramp supervision delay.
failed
time. Check the predefined ramp times (23.11…23.19 for mode
Off1, 23.23 for mode Off3).
Check status of fieldbus communication. See user
Cyclical communication
FBA A documentation of fieldbus interface.
between drive and
communication Check settings of parameter groups 50 Fieldbus adapter
fieldbus adapter module
7510 (FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A
A or between PLC and
Programmable fault: 50.02 data out.
FBA A comm loss func fieldbus adapter
Check cable connections.
module A is lost.
Check if communication master is able to communicate.
Cyclical communication Check status of fieldbus communication. See user
FBA B between drive and documentation of fieldbus interface.
communication fieldbus adapter module Check settings of parameter group 50 Fieldbus adapter
7520
Programmable fault: 50.32
B or between PLC and (FBA).
FBA B comm loss func fieldbus adapter Check cable connections.
module B is lost. Check if communication master is able to communicate.
Check status of other converter (parameters 06.36 and
FA2FA DDCS com DDCS (fiber optic)
06.39).
loss communication between
Check settings of parameter group 60 DDCS
7580 converters (for example,
communication. Check the corresponding settings in the
Programmable fault: 60.79 the inverter unit and the
INU-LSU com loss ctrl control program of the other converter.
supply unit) is lost.
Check cable connections. If necessary, replace cables.
13-16 Troubleshooting 3AXD50000011888
Table 13-2 Fault Messages (Alphabetical by Keypad Text) Continued
Fault Fault # Cause What to do
DDCS controller Check status of controller. See user documentation of
DDCS (fiber optic)
comm loss controller.
communication between
7581 Check settings of parameter group 60 DDCS
Programmable fault: 60.59 drive and external
DDCS controller comm communication.
controller is lost.
loss function Check cable connections. If necessary, replace cables.
MF comm loss Check status of other drives on the master/follower link.
Master/follower Check settings of parameter group 60 DDCS
7582
Programmable fault: 60.09 communication is lost. communication.
M/F comm loss function
Check cable connections. If necessary, replace cables.
The supply unit (or other
Line side unit converter) connected Check fault status of supply unit (or other converter).
7583
faulted to the inverter unit has Refer to the firmware manual of the supply unit.
generated a fault.
AI supervision Check signal level at the analog input.
An analog signal is
Check the wiring connected to the input.
Programmable fault: 80A0 outside the limits specified
12.03 AI supervision Check the minimum and maximum limits of the input in
for the analog input.
function parameter group 12 Standard AI.
Signal supervision
Fault generated by
(Editable message text) Check the source of the fault (parameter 32.07, 32.17 or
Programmable fault: 80B0 a signal supervision
32.06 Supervision 1 action 32.28).
32.16 Supervision 2 action
function.
32.26 Supervision 3 action
External fault 1
(Editable message text) Check the external device.
9081 Fault in external device 1.
Programmable fault: 31.01 Check setting of parameter 31.01 External event 1 source.
External event 1 source
31.02 External event 1 type
External fault 2
(Editable message text) Check the external device.
9082 Fault in external device 2.
Programmable fault: 31.03 Check setting of parameter 31.03 External event 2 source.
External event 2 source
31.04 External event 2 type
External fault 3
(Editable message text) Check the external device.
9083 Fault in external device 3.
Programmable fault: 31.05 Check setting of parameter 31.05 External event 3 source.
External event 3 source
31.06 External event 3 type
External fault 4
(Editable message text) Check the external device.
9084 Fault in external device 4.
Programmable fault: 31.07 Check setting of parameter 31.07 External event 4 source.
External event 4 source
31.08 External event 4 type
External fault 5
(Editable message text) Check the external device.
9085 Fault in external device 5.
Programmable fault: 31.09 Check setting of parameter 31.09 External event 5 source.
External event 5 source
31.10 External event 5 type
Safe torque off function is
Safe torque off 1 FA81 active, ie. STO circuit 1 is Check safety circuit connections. For more information,
broken. see appropriate drive hardware manual and description of
Safe torque off function is parameter 31.22 STO indication run/stop.
Safe torque off 2 FA82 active, ie. STO circuit 2 is
broken.
3AXD50000011888 Troubleshooting 13-17
Table 13-2 Fault Messages (Alphabetical by Keypad Text) Continued
Fault Fault # Cause What to do
Check the nominal motor values in parameter group 99
Motor data.
Check that no external control system is connected to the
drive.
Motor ID run was not Cycle the power to the drive (and its control unit, if
ID run FF61
completed successfully. powered separately).
Check that the motor shaft is not locked.
Check the event log for an auxiliary code. The second
number of the code indicates the problem (see actions for
each code below).
Check settings of parameters 99.06 Motor nominal current
and 30.17 Maximum current. Make sure that 30.17 >
Maximum current limit too
0001 99.06.
low.
Check that the drive is dimensioned correctly according to
the motor.
Check settings of parameters
• 30.11 Minimum speed
• 30.12 Maximum speed
• 99.07 Motor nominal voltage
Maximum speed limit or
• 99.08 Motor nominal frequency
0002 calculated field weakening
• 99.09 Motor nominal speed.
point too low.
Make sure that
• 30.12 > (0.55 × 99.09) > (0.50 × synchronous speed)
• 30.11 < 0, and
• supply voltage > (0.66 × 99.07).
Check settings of parameter 99.12 Motor nominal torque,
Maximum torque limit too and the torque limits in group 30 Limits.
0003
low. Make sure that the maximum torque limit in force is
greater than 100%.
Current measurement
0004 calibration did not finish Contact your local ABB representative.
within reasonable time.
0005 - 0008 Internal error. Contact your local ABB representative.
(Asynchronous motors
only) Acceleration did not
0009 Contact your local ABB representative.
finish within reasonable
time.
(Asynchronous motors
only) Deceleration did not
000A Contact your local ABB representative.
finish within reasonable
time.
(Asynchronous motors
000B only) Speed dropped to Contact your local ABB representative.
zero during ID run.
(Permanent magnet
motors only) First
000C acceleration did not Contact your local ABB representative.
finish within reasonable
time.
(Permanent magnet
motors only) Second
acceleration did
000D Contact your local ABB representative.
not finish within
reasonable
time.
000E - 0010 Internal error. Contact your local ABB representative.
A fault trip command has
FB A force trip FF81 been received through Check the fault information provided by the PLC.
fieldbus adapter A.
A fault trip command has
FB B force trip FF82 been received through Check the fault information provided by the PLC.
fieldbus adapter B.
13-18 Troubleshooting 3AXD50000011888
Appendix A
Technical Specifications
A.1 ACS880+N5350 Technical Data
Table A-1 ACS880+N5350 Technical Data
Electrical Power Network Specification
ACS880-01-xxxx-2 units: 208 … 240V AC 3-phase
+10%…-15%
ACS880-01-xxxx-3 units: 380 … 415V AC 3-phase
+10%…-15%
Voltage (U1)
ACS880-01-xxxx-5 units: 380 … 500V AC 3-phase
+10%…-15%
ACS880-01-xxxx-7 units: 525 … 690V AC 3-phase
+10%…-15%
Network Type TN (grounded) and IT (ungrounded) systems
Rated Conditional
Short-Circuit
65 kA when protected by fuses given in the fuse tables
Current (IEC
61439-1)
Short-Circuit
Current Protection
US and Canada: The drive is suitable for use on a circuit capable of delivering not more than 100kA
(UL 508C,
symmetrical amperes (rms) at 600V maximum when protected by fuses given in the fuse table
CSA C22.2
No. 14-05)
Frequency 47 to 63 Hz, maximum rate of change 17%/s
Imbalance Max. ± 3% of nominal phase to phase input voltage
Fundamental
Power Factor (cos 0.98 (at nominal load)
phi1)
Motor Connection Data
Motor Types Permanent magnet synchronous cooling tower direct drive motors
Voltage (U2) 0 to U1, 3-phase symmetrical, Umax at the field weakening point
Frequency 0…500 Hz
Current See Chapter 3 Ratings.
Switching
2.7 kHz (typically)
Frequency
For ACS880-01-xxxx-2, ACS880-01-xxxx-3 and ACS880-01-xxxx-5 frames R1 to R3 and for types
ACS880-01-07A3-7, ACS880-01-09A8-7, ACS880-01-14A2-7 and ACS880-01-018A-7: 150m (492 ft)
Maximum
Recommended For ACS880-01-xxxx-2, ACS880-01-xxxx-3 and ACS880-01-xxxx-5 frames R4 to R9 and for types
Motor Cable from ACS880-01-022A-7 to ACS880-01-271A-7: 300m (984 ft)
Length
Note: With motor cables longer than 150m (492 ft) the EMC Directive requirements may not be
fulfilled.
Control Unit (ZCU-12) Connection Data
24V (±10%) DC, 2A
Power Supply
(XPOW) Supplied from the power unit of the drive, or from an external power supply through connector
XPOW (pitch 5mm, wire size 2.5mm2)
Relay Outputs Connector pitch 5 mm, wire size 2.5mm2
RO1...RO3 250 VAC / 30 VDC, 2A
(XRO1...XRO3)
Protected by varistors
+24V Output Connector pitch 5 mm, wire size 2.5mm2
(XD24:2 and
XD24:4) Total load capacity of these outputs is 4.8W (200mA / 24V) minus the power taken by DIO1 and DIO2
3AXD50000011888 Technical Specifications A-1
Table A-1 ACS880+N5350 Technical Data Continued
Connector pitch 5 mm, wire size 2.5mm2
24V logic levels: “0” < 5V, “1” > 15V
Rin: 2.0 kohm
Digital Inputs Input type: NPN/PNP (DI1…DI5), NPN (DI6)
DI1...DI6
(XDI:1...XDI:6) Hardware filtering: 0.04ms, digital filtering up to 8ms
DI6 (XDI:6) can alternatively be used as an input for PTC sensors
“0” > 4kohm, “1” < 1.5kohm
Imax: 15mA (for DI6 5mA)
Connector pitch 5mm, wire size 2.5mm2
24V logic levels: “0” < 5V, “1” > 15V
Start Interlock
Input DIIL (XD24:1) Rin: 2.0 kohm
Input type: NPN/PNP
Hardware filtering: 0.04ms, digital filtering up to 8ms
Connector pitch 5mm, wire size 2.5mm2
Digital Inputs/ As inputs:
Outputs DIO1 and
DIO2 (XDIO:1 and 24V logic levels: “0” < 5V, “1” > 15V
XDIO:2)
Input/output Rin: 2.0 kohm
selection by
parameters. Filtering: 0.25ms
DIO1 can be As outputs:
configured as a
frequency input Total output current from +24VD is limited to 200mA.
(0…16 kHz with Figure A-1
hardware filtering
of 4 microseconds)
+24VD
for 24V level
square wave signal
(sinusoidal or other
wave form cannot
be used).
DIO2 can be DIOx
configured as a 24V
level square wave RL
frequency output.
See the firmware
manual, parameter
DIOGND
group 11.
Reference Voltage Connector pitch 5mm, wire size 2.5mm2
for Analog Inputs
+VREF and -VREF 10V ±1% and –10V ±1%, Rload 1…10kohm
(XAI:4...XAI:2)
Connector pitch 5mm, wire size 2.5mm2
Current input: –20…20mA, Rin: 100ohm
Analog Inputs AI1
and AI2 (XAI:4... Voltage input: –10…10V, Rin: > 200kohm
XAI:7) Differential inputs, common range ±30V
Current/voltage
input selection by Sampling interval per channel: 0.25ms
jumpers. Hardware filtering: 0.25ms, adjustable digital filtering up to 8ms
Resolution: 11 bit + sign bit
Inaccuracy: 1% of full scale range
A-2 Technical Specifications 3AXD50000011888
Table A-1 ACS880+N5350 Technical Data Continued
Connector pitch 5mm, wire size 2.5mm2
Analog Outputs 0…20mA, Rload < 500ohm
AO1 and AO2 Frequency range: 0…300Hz
(XAO)
Resolution: 11 bit + sign bit
Inaccuracy: 2% of full scale range
Connector pitch 5mm, wire size 2.5mm2
Drive to Drive Link
(XD2D) Physical layer: RS-485
Termination by switch
Connector pitch 5mm, wire size 2.5mm2
Safe Torque Off
Connection (XSTO) Current consumption per channel: 55mA (continuous)
For the drive to start, both connections must be closed (OUT1 to IN1 and IN2).
Control Panel / PC Connector: RJ-45
Connection Cable length < 3m
The terminals on the board fulfil the Protective Extra Low Voltage (PELV) requirements. The PELV requirements of a relay
output are not fulfilled if a voltage higher than 48V is connected to the relay output.
3AXD50000011888 Technical Specifications A-3
Figure A-2 Ground Isolation Diagram
Ground isolation diagram
XPOW
+24VI 1
GND 2
XAI
+VREF 1
-VREF 2
AGND 3
AI1+ 4
AI1- 5 Common mode voltage between
AI2+ 6 channels +30 V
AI2- 7
XAO
AO1 1
AGND 2
AO2 3
AGND 4
XD2D
B 1
A 2
BGND 3
XRO1, XRO2, XRO3
NC 1
COM 2
NO 3
NC 1
COM 2
NO 3
NC 1
COM 2
NO 3
XD24
DIIL 1
+24VD 2
DICOM 3
+24VD 4
DIOGND 5 Switch J6 settings:
XDIO
DIO1 1 All digital inputs and
DIO2 2 outputs share a
XDI J6 common ground.
DI1 1
Ground of digital
DI2 2
DI3 3 inputs DI1…DI5 and
DI4 4 DIIL (DICOM) is
DI5 5 separated from the DIO
DI6 6 signal ground (DIOGND)
XSTO (insulation voltage 50 V).
OUT1 1
SGND 2
IN1 3
IN2 4
Ground
A-4 Technical Specifications 3AXD50000011888
Table A-1 ACS880+N5350 Technical Data Continued
Efficiency
Approximately 98% at nominal power level
Protection Classes
Degree of
Protection IP21, IP55
(IEC/EN 60529)
Enclosure Types
UL Type 1, UL Type 12. For indoor use only
(UL508C)
Overvoltage
Category III
(IEC 60664-1)
Protective Class
I
(IEC/EN 61800-5-1)
Ambient Conditions
Environmental limits for the drive are given below. The drive is to be used in a heated, indoor, controlled
environment.
Operation Installed for Storage in the Transportation in the
Stationary Use Protective Package Protective Package
1. 0 to 4000m (13123 ft)
above sea level
2. 0 to 2000m (6561 ft)
above sea level - -
Installation Site Altitude Above 1000m [3281 ft]
1. For neutral-grounded TN and TT systems and non-corner grounded IT
systems
2. For corner-grounded TN, TT and IT systems
-15 to +55°C (5 to 131°F).
-40 to +70°C -40 to +70°C
Air Temperature No frost allowed. See
(-40 to +158°F) (-40 to +158°F)
Chapter 3 Ratings.
5 to 95% Max. 95% Max. 95%
Relative Humidity No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
No conductive dust allowed.
Contamination Levels Chemical gases: Chemical gases: Chemical gases:
(IEC 60721-3-3, IEC 60721-3-2, Class 3C2 Class 1C2 Class 2C2
IEC 60721-3-1) Solid particles: Solid particles: Solid particles:
Class 3S2 Class 1S3 Class 2S2
70 to 106 kPa 70 to 106 kPa 60 to 106 kPa
Atmospheric Pressure
0.7 to 1.05 atmospheres 0.7 to 1.05 atmospheres 0.6 to 1.05 atmospheres
Max. 1mm Max. 1mm Max. 3.5mm
(0.04in.) (0.04in.) (0.14in.)
(5 to 13.2 Hz), (5 to 13.2 Hz), (2 to 9 Hz),
Vibration (IEC 60068-2) max. 7m/s2 max. 7m/s2 max. 15m/s2
(23ft/s2) (23ft/s2) (49ft/s2)
(13.2 to 100 Hz) (13.2 to 100 Hz) (9 to 200 Hz)
sinusoidal sinusoidal sinusoidal
Max. 100m/s2 Max. 100m/s2
Shock (IEC 60068-2-27) Not allowed
(330 ft./s2), 11ms (330 ft./s2), 11ms
100mm (4 in.) for weight 100mm (4 in.) for weight
Free Fall Not allowed
over 100 kg (220 lb) over 100 kg (220 lb)
3AXD50000011888 Technical Specifications A-5
Table A-1 ACS880+N5350 Technical Data Continued
Materials
• PC/ABS 3 mm, color NCS1502-Y (RAL 9002 / PMS 1C Cool Grey) and RAL 9017
• PC+10%GF 3.0mm, Color RAL 9017 (in frames R1 to R3 only)
Drive Enclosure
• Hot-dip zinc coated steel sheet 1.5 to 2.5mm, thickness of coating 100 micrometers, color
NCS1502-Y
Package Plywood and cardboard. Foam cushions PP-E, bands PP.
The main parts of the drive can be recycled to preserve natural resources and energy. Product
parts and materials should be dismantled and separated.
Generally all metals, such as steel, aluminum, copper and its alloys, and precious metals can be
recycled as material. Plastics, rubber, cardboard and other packaging material can be used in
energy recovery. Printed circuit boards and DC capacitors (C1-1 to C1-x) need selective treatment
Disposal
according to IEC 62635 guidelines. To aid recycling, plastic parts are marked with an appropriate
identification code.
Contact your local ABB distributor for further information on environmental aspects and recycling
instructions for professional recyclers. End of life treatment must follow international and local
regulations.
A.2 Derating
A.2.1 Ambient Temperature Derating
IP21 (UL Type 1) drive types and other IP55 (UL Type 12) types than listed in the following subheadings
In the temperature range +40…55°C (+104…131°F), the rated output current is derated by 1% for every added 1°C (1.8°F).
The output current can be calculated by multiplying the current given in the rating table by the derating factor (k):
Figure A-3
k
1.00
0.95
0.90
0.85
0.80
-15 °C … +40 °C +50 °C +55 °C T
-59 °F +104 °F +122 °F +131 °F
A.2.2 Altitude Derating
At altitudes from 1000 to 4000m (3300 to 13123 ft) above sea level, the continuous output currents given above must be
derated 1% for every 100m (328ft). For a more accurate derating, use the DriveSize PC tool.
A.2.3 Low Noise Control Mode Derating
When low noise drive control mode is used, the motor and braking powers are derated. Contact ABB for more information.
A-6 Technical Specifications 3AXD50000011888
Appendix B
Dimensions
B.1 Dimensions, Weights and Free Space Requirements
Table B-1
IP21 UL Type 1
Frame H1 H2 W D Weight H1 H2 W D Weight
mm mm mm mm kg in. in. in. in. lb
R1 405 370 155 226 6 15.94 14.57 6.10 8.89 13
R2 405 370 155 249 8 15.94 14.57 6.10 9.80 18
R3 471 420 172 261 10 18.54 16.54 6.77 10.28 22
R4 576 490 203 274 18.5 22.70 19.30 7.99 10.80 41
R5 730 596 203 274 23 28.74 23.46 7.99 10.79 51
R6 726 569 251 357 45 28.60 22.40 9.92 14.09 99
R7 880 600 284 365 55 34.70 23.60 11.22 14.37 121
R8 963 681 300 386 70 37.90 26.82 11.81 15.21 154
R9 955 680 380 413 98 37.59 26.77 14.96 16.27 216
H1 Height with cable entry box.
H2 Height without cable entry box.
H3 Height with hood.
W Width with cable entry box.
D Depth with cable entry box.
Note: For more information on dimensions, see Dimension drawings.
200mm (7.87 in.) free space is required at top of the drive.
300mm (11.81 in.) free space (when measured from the drive base without the cable entry box) is required at bottom of the
drive.
3AXD50000011888 Dimensions B-1
Figure B-1 Frame R1 (IP21, UL Type 1)
Frame R1 (IP21, UL Type 1)
3AUA0000097621
B-2 Dimensions 3AXD50000011888
Figure B-2 Frame R2 (IP21, UL Type 1)
Frame R2 (IP21, UL Type 1)
3AUA0000097691
3AXD50000011888 Dimensions B-3
Figure B-3 Frame R3 (IP21, UL Type 1)
Frame R3 (IP21, UL Type 1)
3AUA0000097847
B-4 Dimensions 3AXD50000011888
3AXD50000011888
22[.85]
22[.85]
7 [ .26 ]
8[.32]
18[.72]
7[.28]
PLATE HOLE 22 [0.87] (3pcs.)
GROMMET UP TO 15 [0.59] CABLE DIAMETER
PLATE HOLE 44 [1.73] (3pcs.)
GROMMET UP TO 24 [0.94] CABLE DIAMETER
15 [ .57 ]
13 [ .51 ] A
203[7.99] B
74[2.90] 274[10.80] 160[6.30]
65[2.55] SUGGESTED MOUNTING HOLES 98[3.86]
A
Frame R4 (IP21, UL Type 1)
7 [ .26 ]
48[1.89]
Figure B-4 Frame R4 (IP21, UL Type 1)
124[4.86]
475[18.70]
490[19.291]
505[19.88]
WITHOUT GLAND BOX
576[22.69]
SUGGESTED MOUNTING HOLES
3AUA0000098285
Dimensions B-5
B-6 Dimensions
g p j
22[.85]
22[.85]
8[.32]
7 [ .26 ] 7 [ .26 ]
7[.28]
PLATE HOLE 29 [1.12] (2pcs.)
GROMMET UP TO 22 [0.87] CABLE DIAMETER
PLATE HOLE 51 [2.01] (3pcs.) 15 [ .57 ]
GROMMET UP TO 32 [1.26] CABLE DIAMETER
203[7.99] A B
160[6.30]
65[2.55] SUGGESTED MOUNTING HOLES
74[2.90] 274[10.77] 98[3.86] A
Frame R5 (IP21, UL Type 1)
7 [ .26 ]
48[1.88]
124[4.86]
Figure B-5 Frame R5 (IP21, UL Type 1)
596[23.46]
581[22.87]
612[24.07]
WITHOUT GLAND BOX
730[28.73]
SUGGESTED MOUNTING HOLES
3AUA0000097965
3AXD50000011888
Figure B-6 R6 (IP21, UL Type 1)
Frame R6 (IP21, UL Type 1)
3AUA0000098321
3AXD50000011888 Dimensions B-7
Figure B-7 Frame R7 (IP21, UL Type 1)
Frame R7 (IP21, UL Type 1)
3AUA0000073149
B-8 Dimensions 3AXD50000011888
Figure B-8 Frame R8 (IP21, UL Type 1)
Frame R8 (IP21, UL Type 1)
3AUA0000073150
3AXD50000011888 Dimensions B-9
Figure B-9 Frame R9 (IP21, UL Type 1)
Frame R9 (IP21, UL Type 1)
3AUA0000073151
B-10 Dimensions 3AXD50000011888
Appendix C
CE Guidelines
This section provides general information regarding recommended methods of installation for CE compliance. It is
not intended as an exhaustive guide to good practice and wiring techniques. It is assumed that the installer of the
ACS880+N5350 is sufficiently qualified to perform the task, and is aware of local regulations and requirements. ABB
products that meet the EMC directive requirements are indicated with a “CE” mark. A duly signed CE declaration of
conformity is available from ABB.
C.1 Applicable Standards
The drive complies with the following standards. The compliance with the European Low Voltage Directive is verified
according to standard EN61800-5-1.
Table C-1
Safety of machinery. Electrical equipment of machines.
Part 1: General requirements. Provisions for compliance:
EN 60204-1:2006 + A1 2009 The final assembler of the machine is responsible for installing
- emergency-stop device
- supply disconnecting device.
IEC/EN 60529:1991 + A1 2000 Degrees of protection provided by enclosures (IP code)
Insulation coordination for equipment within low-voltage systems.
IEC 60664-1:2007
Part 1: Principles, requirements and tests.
Adjustable speed electrical power drive systems.
EN 61800-3:2004
Part 3: EMC requirements and specific test methods
Adjustable speed electrical power drive systems.
EN 61800-5-1:2007
Part 5-1: Safety requirements – electrical, thermal and energy
Adjustable speed electrical power drive systems.
EN 61800-5-2:2007
Part 5-2: Safety requirements – Functional
UL 508C:2002 UL Standard for Safety, Power Conversion Equipment, third edition
NEMA 250:2008 Enclosures for Electrical Equipment (1000 Volts Maximum)
CSA C22.2 No. 14-10 Industrial control equipment
Low-voltage switchgear and control gear assemblies.
GOST R 51321-1:2007 Part 1 - Requirements for type-tested and partially type-tested assemblies -
General technical requirements and methods of tests
C.2 CE Marking
A CE mark is attached to the drive to verify that the drive follows the provisions of the European Low Voltage, EMC and
RoHS Directives. The CE marking also verifies that the drive, in regard to its safety functions (such as Safe torque off),
conforms with the Machinery Directive as a safety component.
C.2.1 Compliance with the European Low Voltage Directive
The compliance with the European Low Voltage Directive has been verified according to standards EN 60204-1 and
EN61800-5-1.
C.2.2 Compliance with the European EMC Directive
The EMC Directive defines the requirements for immunity and emissions of electrical equipment used within the European
Union. The EMC product standard (EN61800-3:2004) covers requirements stated for drives. See section Compliance with
the EN61800-3:2004 below.
C.2.3 Compliance with the European RoHS Directive
The RoHS Directive defines the restriction of the use of certain hazardous substances in electrical and electronic equipment.
C.2.4 Compliance with the European Machinery Directive
The drive is an electronic product which is covered by the European Low Voltage Directive. However, the drive includes the
Safe torque off function and can be equipped with other safety functions for machinery which, as safety components, are in
the scope of the Machinery Directive. These functions of the drive comply with European harmonized standards such as
EN 61800-5-2. The declaration of conformity is shown below.
3AXD50000011888 CE Guidelines C-1
Figure C-1 Declaration of Conformity
C-2 CE Guidelines 3AXD50000011888
3AXD50000011888 CE Guidelines C-3
C.3 Compliance with the EN 61800-3:2004
C.3.1 Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to operate without problems
within an electromagnetic environment. Likewise, the equipment must not disturb or interfere with any other product or
system within its locality.
First environment includes establishments connected to a low-voltage network which supplies buildings used for domestic
purposes.
Second environment includes establishments connected to a network not supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000V and intended to be installed and started up only by a
professional when used in the first environment.
Note: A professional is a person or organization having necessary skills in installing and/or starting up power drive systems,
including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000V and intended for use in the second environment and not
intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000V, or rated current equal to or above 400A, or intended for
use in complex systems in the second environment.
C.3.2 Category C2
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter +E202.
2. The motor and control cables are selected as specified in the hardware manual.
3. The drive is installed according to the instructions given in the hardware manual.
4. Maximum motor cable length is 150 meters.
WARNING! The drive may cause radio interference if used in residential or domestic environment. The user
is required to take measures to prevent interference, in association to the requirements for the CE
compliance listed above, if necessary.
Note: Do not install a drive equipped with EMC filter +E202 on IT (ungrounded) systems. The supply network becomes
connected to ground potential through the EMC filter capacitors which may cause danger or damage to the unit.
C.3.3 Category C3
The drive complies with the standard with the following provisions:
1. The drive is equipped with EMC filter +E200 or +E201.
2. The motor and control cables are selected as specified in the hardware manual.
3. The drive is installed according to the instructions given in the hardware manual.
4. Maximum motor cable length is 150 meters.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public network which supplies
domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
C-4 CE Guidelines 3AXD50000011888
C.3.4 Category C4
If the provisions under Category C3 cannot be met, the requirements of the standard can be met as follows:
1. It is ensured that no excessive emission is propagated to neighboring low-voltage networks. In some cases, the inherent
suppression in transformers and cables is sufficient. If in doubt, the supply transformer with static screening between the
primary and secondary windings can be used.
Figure C-2
Medium voltage network
Supply transformer
Neighboring network
Static screen
Point of measurement
Low voltage Low voltage
Equipment
Drive
(victim)
Equipment Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available from the local ABB
representative.
3. The motor and control cables are selected as specified in the hardware manual.
4. The drive is installed according to the instructions given in the hardware manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which supplies
domestic premises. Radio frequency interference is expected if the drive is used on such a
network.
C.4 UL Marking
cULus Listed UL Type 1 (IP21) drives:
• frames R1 to R3 of voltage range 208…240V
• frames R1 to R9 of voltage ranges 380…415V and 380…500V
• frames R5 to R9 of voltage range 525…600V
cULus Listed UL Type 12 (IP55) drives:
• frames R1 to R3 of voltage range 208…240V
• frames R1 to R5 of voltage ranges 380…415V and 380…500V
• frames R5 of voltage range 525…600V
The listing is pending for the other types. The approval is valid with rated voltages.
C.4.1 UL Checklist
• The drive is to be used in a heated, indoor controlled environment. The drive must be installed in clean air according to
enclosure classification. Cooling air must be clean, free from corrosive materials and electrically conductive dust.
• The maximum ambient air temperature is 40°C (104°F) at rated current. The current is derated for 40 to 55°C (104 to
131°F).
• The drive is suitable for use in a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 600 V
maximum. The ampere rating is based on tests done according to UL508C.
• The cables located within the motor circuit must be rated for at least 75°C (167°F) in UL-compliant installations.
• The input cable must be protected with fuses. Circuit breakers must not be used without fuses in the USA. See hardware
manual for suitable IEC (class aR) fuses and UL (class T) fuses. For suitable circuit breakers, contact your local ABB
representative.
• For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical
Code (NEC) and any applicable local codes. To fulfill this requirement, use the UL classified fuses.
• For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code
and any applicable provincial codes. To fulfill this requirement, use the UL classified fuses.
• The drive provides overload protection in accordance with the National Electrical Code (NEC).
3AXD50000011888 CE Guidelines C-5
C.4.2 CSA Marking
The drives of frame sizes R1 to R3 are CSA marked. The CSA marking is pending for the other frames. The approval is valid
with rated voltages.
C.4.3 “C-tick” Marking
“C-tick” marking is required in Australia and New Zealand. A “C-tick” mark is attached to the 380…500V drives to verify
compliance with the relevant standard (IEC 61800-3:2004), mandated by the Trans-Tasman Electromagnetic Compatibility
Scheme. C-tick marking is pending for drives of voltage ranges 204…240V and 525…690V.
For fulfilling the requirements of the standard, see section Compliance with the EN61800-3:2004 in hardware manual.
C.5 GOST R Certificate of Conformity
The drive has been given a GOST R certificate of conformity.
C.6 Disclaimer
The manufacturer shall have no obligation hereunder with respect to any product which (i) has been improperly repaired
or altered; (ii) has been subjected to misuse, negligence or accident; (iii) has been used in a manner contrary to the
Manufacturer’s instructions; or (iv) has failed as a result of ordinary wear and tear.
C-6 CE Guidelines 3AXD50000011888
Appendix D
Mechanical Installation
This chapter gives a description of the mechanical installation of the drive.
D.1 Safety
WARNING: For frame sizes R6 to R9: Use the lifting eyes of the drive when you lift the drive. Do not tilt the drive. The drive
is heavy and its center of gravity is high. An overturning drive can cause physical injury.
Figure D-1
D.2 Examining the Installation Site
The drive must be installed in an upright position with the cooling section against a wall. All IP21 (UL Type 1) and IP55 drives
and UL Type 12 drives of frames R1 to R3 can be installed tightly side by side. For UL Type 12 drives of frames R4 to R9,
leave 100mm (4 in) between the hoods.
Make sure that the installation site agrees with these requirements:
• The installation site has sufficient ventilation to prevent overheating of the drive. See section Losses, cooling data and
noise.
• The operation conditions of the drive agree with the specifications in section Ambient conditions.
• The wall is vertical, not flammable and strong enough to hold the weight of the drive.
• The material below the installation is not flammable.
• There is enough free space above and below the drive for cooling air flow, service and maintenance. There is enough free
space in front of the drive for operation, service and maintenance.
Figure D-2
200 mm (7.87 in.)
300 mm (11.81 in.)
3AXD50000011888 Mechanical Installation D-1
D.3 Necessary Tools
• Drill and drill bits
• Screwdriver and/or wrench with bits. The drive cover has Torx screws.
D.4 Moving the Drive
Move the transport package by pallet truck to the installation site.
D.5 Unpacking and Examining the Delivery (Frames R1 to R5)
This illustration shows the layout of the transport package. Examine that all items are present and there are no signs of
damage. Read the data on the type designation label of the drive to make sure that the drive is of the correct type.
Figure D-3
77 11
22
66
33
12 11
10
10
55
99
88
44
Table D-1
Item Description Item Description
1 Drive with factory installed options. 5 Cardboard sleeve
Control cable grounding shelf. Romex
connectors in IP21 frames R1 to R3
in a plastic bag inside the cable entry
box.
2 Manuals CD 6 - 9 Cushions
3 Printed quick guides and manuals, 10 PET straps
multilingual residual voltage warning
sticker
4 Cardboard tray 11 Top cardboard cover
- - 12 Hood included with option +B056
To unpack:
• Cut the straps (10).
• Remove the top cardboard cover (11) and cushions (6 - 9).
• Lift the cardboard sleeve (5).
• Lift the drive.
D-2 Mechanical Installation 3AXD50000011888
D.5.1 Frame R5 Cable Entry Box (IP21, UL Type 1)
This illustration shows the contents of the cable entry box package. The package also includes an assembly drawing which
shows how to install the cable entry box to the drive module frame.
Figure D-4
3AXD50000011888 Mechanical Installation D-3
D.6 Unpacking and Examining the Delivery (Frames R6 to R9)
This illustration shows the layout of the transport package. Examine that all items are present and there are no signs of
damage. Read the data on the type designation label of the drive to make sure that the drive is of the correct type.
Figure D-5
6
7
1
2
Table D-2
Item Description Item Description
1 Cable entry box. Power and control 5 Cardboard sleeve
cable grounding shelves in a plastic
bag, assembly drawing. Note: The
cable entry box is mounted to a IP55
drive module frame at the factory.
2 Drive with factory installed options 6 Straps
3 Top cardboard cover 7 Printed quick guides and manuals
CD and multilingual residual
valtage warning sticker
4 Cushion 8 Pallet tray
To unpack:
• Cut the straps (6).
• Remove the top cardboard cover (3) and cushion (4).
• Lift the cardboard sleeve (5).
• Attach lifting hooks to the lifting eyes of the drive. Lift the drive with a hoist.
D-4 Mechanical Installation 3AXD50000011888
D.6.1 Frame R6 Cable Entry Box (IP21, UL Type 1)
This illustration shows the contents of the cable entry box package. The package also includes an assembly drawing which
shows how to install the cable entry box to the drive module frame.
Figure D-6
3AXD50000011888 Mechanical Installation D-5
D.6.2 Frame R7 Cable Entry Box (IP21, UL Type 1)
This illustration shows the contents of the cable entry box package. The package also includes an assembly drawing which
shows how to install the cable entry box to the drive module frame.
Figure D-7
D-6 Mechanical Installation 3AXD50000011888
D.6.3 Frame R8 Cable Entry Box (IP21, UL Type 1)
This illustration shows the contents of the cable entry box package. There is also an assembly drawing which shows how to
install the cable entry box to the drive module frame.
Figure D-8
3AXD50000011888 Mechanical Installation D-7
D.6.4 Frame R9 Cable Entry Box (IP21, UL Type 1)
This illustration shows the contents of the cable entry box package. The package also includes an assembly drawing which
shows how to install the cable entry box to the drive module frame.
Figure D-9
D-8 Mechanical Installation 3AXD50000011888
D.7 Installing the Drive
These instructions are for drives without vibration dampers. For drives with vibration dampers (option +C131), see the
additional instructions (included with the dampers and on the manuals CD).
D.7.1 Frames R1 to R4
1. See the dimensions in chapter Dimension drawings. Mark the locations for the four mounting holes.
2. Drill the mounting holes.
3. Start the screws or bolts into the mounting holes.
4. Position the drive onto the screws on the wall.
5. Tighten the screws in the wall securely.
Figure D-10
1 2 3
×4
×4
×4
×4 Screw size
R1 M5
R2 M5
R3 M5
R4 M5
4
3AXD50000011888 Mechanical Installation D-9
D.7.2 Frames R4 and R7 (UL Type 12)
1. Position the drive onto the screws on the wall as shown in section Frames R5 to R9 without vibration dampers on page
50.
2. Put the hood onto the upper screws.
3. Tighten the upper screws in the wall securely.
4. Tighten the lower screws in the wall securely.
Note: Do not open or remove the cable entry box for easier installation. The gaskets do not fulfill the degree of protection if
the box is opened.
Figure D-11
D.7.3 Frames R5 and R9 without Vibration Dampers
1. See the dimensions in chapter Dimension drawings. Mark the locations for the four or six mounting holes.
2. Drill the mounting holes.
3. Start the screws or bolts into the mounting holes.
4. Remove the front cover.
5. For IP21 units: Attach the cable entry box to the drive frame. For instructions, see the assembly drawing in the cable
entry box. A view of frame R5 is shown below.
6. Position the drive onto the screws on the wall.
7. Tighten the accessible screws in the wall securely.
Note: If you use the lower mounting screws, you can replace the drive module without unfastening the cable entry box.
D-10 Mechanical Installation 3AXD50000011888
Figure D-12
200 mm
(7.87”)
Screw size
R5 M5
R6 M8
R7 M8
R8 M8
3
R9 M8
1 2 3
300 mm
(11.81”)
3AXD50000011888 Mechanical Installation D-11
D.8 Cabinet Installation
See ACS880-01 cabinet installation supplement (3AUA0000145446 [English]).
D-12 Mechanical Installation 3AXD50000011888
Local Sales Offices
NOTES
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
Contact Us
www.abb.com/drives
www.abb.com/drivespartners
3AXD50000011888 Rev C (EN) 2016-5-01