We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 25
BELL & GOSSETT BULLETIN NO. TEH-1275
Equipment Room
Piping Practice
Price $7.50
FLUID HANDLING I TT
TRAINING & EDUCATION DEPT.EQUIPMENT (BOTLER) ROOM PIPING PRACTT
1. GENERAL DESIGN AND APPLICATION RULES
‘The following design and application rules apply to all equipment rooms
whether intended for heating only, dual chilled and hot water, instantaneous
chilled and hot (3 or 4 pipe) or zoned chilled and hot.
1, Distribution pumps must discharge into the piping systen with the com-
pression tank connection located at the pump suction.
J+ COMPRESSION TANKS#(
AIR SEPARATORS ——|—
'
RIGHT WRONG
‘TANK AT PUMP SUCTION ‘TANK AT POMP DISCHARGE
Figure 1 - RIGHT AND WRONG PUMP LOCATION
The wrong pump location will decrease system static pressure by
an amount equal to the operating pump head. System circulation and mechan-
ical pump troubles will occur.
The properly Located pump increases system static pressure during
operation and eliminates trouble potential.
2. PUMP SELECTION
Distribution pumps should be selected to approximate curve mid-
point, using flat curved pumps.No"oRIET™
Gro oF
URVE
‘SLELCTION
Rigut! wrone / wrone!
muat CURVED WITH steep curveo— unt cORVEO—
ORIFT ABILITY (MO DRIFT ABILITY NO ORT ABILITY
Figure 2 - RIGHT AND WRONG PUMP SELECTIONS
System distribution pumps should be selected for systen needs.
‘The Large multi-circufted hydronic system needs a pump selection that
will help overcone circuit distribution problens.
3. PIPING SIZB AT PUMP SUCTION AND DISCHARGE
Pipe size at the pump suction and discharge should conform to
distribution main size; not to suction and discharge pump opening size.
BI DISTRIBUTION MAIN BITE.
5’ DISCH-R.VALVES. PIPING VALVES SIZED
ey
Sects
S"sucrioua mares WRONG /ronr pene eves
“I PUMP PIPING E VALVES: IWSTALLED TO PUMP OPEMING SIZE
Hip waorermeumon
RicuTé waive DUTY WSTALED — WeOKe/TaIPLe-DUTY mstALED
‘To busrmeuTioN ibe ste. To rome oreame te
FIGURE 3 - RIGHT AND WRONG PUMP PIPE AND VALVE SIZING
Suction and discharge piping (and valves) sized to the pump
opening works against system flow distribution needs because of unwarranted
increases in equipment room pressure drop.4, PUMP SUCTION PIPE Lenora
oO ‘The pump suction "straight" run pipe length should be at least
5 DIA. of suction pipe size to insure good pump entry conditions.
!
aun WRONG:
RIGHT: BAD PUMP ENTRY &
GogD, PUMP ENTRY “NO” PIPING SUPPORT.
FIGURE 4 - RIGHT AND WRONG PUNP ENTRY CONDITIO)
5. PUMP PIPING SUPPORT.
Pump piping support should be provided as shown in Figure 4.
The pump should not serve as a piping anchor.
6. MULTIPLE PUMP CHECK VALVES
'
) Check valves (conventional, Triple Duty or Flo Control)
should be installed at each pump discharge when more than one pump is
used in the equipment room. This applies whether the additional pumps
are for standby, parallel operation or zone pumping.
pons
Rignr/ wrone/
INSTALL CHECKS FoR = CHECKS LEFT OUT.
MULTIPLE Pumes. THIS MEANS. TROUBLE
FIGURE 5 - MULTIPLE PUMP CHECK VALVES
Trouble will develop when check valves are not installed
because of reversed flow through non-operating pumps. When these pumps
are started, they must overcome a heavy flow inertia load and will over~
load.7. ZONE PUMP STRAINERS
Zone pumps should not use a single fine mesh strainer in the
header piping. Clogging of this single strainer can lead to non-operation
and freeze up in low pump head zones.
ance
4 Seite ME Mes eae
—
Rieu! WRONG!
FING MESH STRAINERS AT FINE Mesh STEAINER
{ONE PuwP DISCHARGE; nce in Common HEADER.
MESH STRAINER IN HERDRR.
FIGURE 6 ~ STRAINER APPLICATION
Fine mesh strainers are often used to protect control valves,
etc. They are not needed for pump protection. When fine mesh steam type
strainers are used, their best application point is either at the pump
discharge or out in the systen.
It is considered good practice to remove strainers from the
water system after 2 to 3 months operation. While in use, the strainers
should be watched continually for clogging.
8. AIR SEPARATOR LOCATION
‘The air separator should be located so that full system flow
passes through it.
RisuT) WRONG /
Fou. system PLOW THRU PARTIAL SYSTEM FLOW
ROLAWTTROL AIR SEPARATOR THROUGH AIR SEPARATOR.
PIGURE 7 ~ FULL SYSTEM FLOW THROUGH SEPARATORoO
IT. EQUIPMENT OR BOTLER ROOM PIPING PRACTICE; HEATING AND/OR COOLING
AIR SEPARATION
The following illustrates a series of specific application
solutions for various Equipment Room problems:
1. FLOOR MOUNTED COMPRESSION TANK
Floor mounted compression tanks are used because of Limited
ceiling height above boilers or air separators and to eliminate special
ceiling structure design necessary for large ceiling hung tanks.
The basic problem concerning the floor mounted tank is intro-
duction of separated air from an overhead point into the tank. ‘this
problem is solved by the arrangement shown in Figure Ii-1.
SMALL Ye" TAR SECONDARY.
AIR SeeRRaToR:
FIGURE II-1 - FLOOR MOUNTED COMPRESSION TANK
In Figure II-1, main system air is liberated in the overhead
main air separating Rolairtrol. This air is then pumped down into the
small IAF type separator from which it is delivered into the bottom of
the floor mounted tank.
The small booster pump provides the driving energy head for
delivery of overhead air to the tank. ‘This pump must be selected so
that dts shut-off (no delivery) head is on the order of 2 to 3 £t.
greater than the statfe height "H" shown in Figure II-L.
‘The connecting line from the small IAF to the tank must be large
enough (at least 1") 80 that similtaneous counter passage of air into the
tank and water from the tank back to the IAF will be assured.2. MULTIPLE BOILERS CONNECTED 10 A SINGLE COMPRESSION TANK
A single tank is generally not recommended for interconnection
with multiple air separators. This is because a pressure difference
between the boiler will cause a flow in the header connection. This flow
prevents delivery of separated air to the coapression tank.
AIR BYPASSES TANK
‘AND RE-ENTERS svsTeM
THROUGH BOILER #2.
aor
* ey
jeoner” LER?
t per
WRONG!
FIGURE IL-2 - SINGLE TANK CONNECTION TO MULTIPLE BOLLERS
‘The problem can be solved by a pumped header connection as
schematically illustrated in Figure II-3.
Swan iar VALVE PRESSURE DROP
SEN ERS Aue Faccitene ation Taek,
So TANK HEADER LING Fo SMALL LAF
Aare =
t 7
RIGHT!
FIGURE IL-3 - PUMPED COMPRESSION TANK HEADER CONTAINS SMALL LAF
‘The single tank can also be floor mounted as in Figure II-4.SMALL BOOSTER
Noresre re e-|
Porpine,
sal ECrion.
FIGURE II-4 - MULTIPLE BOILERS WITH SINGLE FLOOR MOUNTED TANK; PUMPED
COMPRESSION TANK HEADER
3. MULTIPLE ZONE _ATR SEPARATION
Many larger systems are installed using multiple "reset"
zones. Flow distribution problems have occurred because use of a single
Rolairtrol or ABF does not comply with its full system flow objective
through the air separator.
FIGURE II-5 - MULITPLE ZONE RESET; FULL. FLOW DOKS NOT OCCUR THROUGH AIR
SEPARATION
A separate Rolairtrol can be placed on each zone and inter-
connected with a single tank to meet the full flow objective.IIL
Iv.
SMALL IAF
Fu FLOW
ae
Srarator.
f
|<}
FIGURE 11-6 - MULTIPLE ZONE RESET; FULL, FLOW THROUGH EACH ZONE AIR SEPARATOR
The small Booster pump must have a shut-off head greater than
height "H". Its head must also be greater than the three-way valve
pressure drop.
See note on page 23
ZONE PIPING APPLICATIONS
1. MULTIPLE ZONE HEATING APPLICATION
‘The multiple zone heating application has led to many operating
problems because of improper application.
‘One of the common problems is illustrated by an attempt to reduce
cost by using a single return main for a nunber of zones; each zone having
several circuits and several returns for each zone.
UNWANTEO.
FLOW in TONE,
—}
WRONG /
@
PIGURE IV-1 ~ MULTIPLE ZONES, VALVE CONTROLLED, EACH ZONE WITH MORE THAN ONE
‘RETURN,ty
®
UNWANTEO.
Flow im ZONE
WRONG /
FIGURE IV-2 - MULTIPLE ZONES, PUMP CONTROLLED, EACH ZONE WITH NORE THAN
ONE _RETURN
@
In both Figures IV-1 and IV-2, the operating zone causes flow
rate in the return main. Pressure drop in the return (as at A and B) in
turn causes unwanted flow in the non-operating cone with an associated lack
of control.
On already installed systems, the only solution ib to install
check valve in the zone circuit returns as required.
The uncontrolled flow problems can be overcome during design
by combining all zone circuit returns into a common zone return before
entry into the main return.
TONE CIRCUIT RETURN
One ren TONE
RIGHT /
FIGURE IV-3 - MULTIPLE ZONE, ONLY ONE RETURN PER ZONEV. EQUIPMENT OR BOELER ROOM PIPING PRACTICE; HEATING
1. BOILER SHOCK PROTECTION
“Boiler Shock" is a term that has been very loosely defined. In
general, it refers to sudden thermal changes inside the boiler causing
vapid and uneven contractions; in turn, tending to loosen boiler tubes
with a final necessity for boiler retubing.
Water tube and cast iron type boilers have, in general, a high
resistance to boiler"shock". Larger fire tube type are generally more
susceptible.
Boiler shock frequently occurs in large systems waere week-end
or might shut-down takes place.
The sudden introduction of massive amounts of cold water into the
hot boiler during start-up often causes trouble.
Boiler shock can also occur in the conbination heating and
cooling system when switching from chilled to hot operation.
Reduced to fundamentals, control against "boiler shock"
involves control of incoming "cold" water flow rate so that boiler
temperatures are changed slowly.
‘SWAY TIMED To OPEN SLOWLY
SWAY VeLVE CONTROLS
ONLY ayaa nin never on START UR
WRONG! 3 WAY OPENS IMMEDIATELY ON START UR Rieu
FIGURE V-1 - 3-WAY OPENS FIGURE V-2 - 3-WAY OPENING 10
INMEDIATELY ON START-UP RESET REQUIREMENTS OVER-RIDDEN
BY "TDM" OPENING CYCLE
10One of the methods used for "shock" protection employs a timed
3eway valve so that the boiler circuit is opened slowly to incoming cold
system water. The timed cycle is generally on the order of 20 to 30
minutes from closed to fully open.
A more sophisticated arrangement provides for continuous
automatic protection against boiler "shock" by separate circulation of the
boiler.
sont
FIGURE V-3 - SEPARATELY PUMPED BOILER; 3-WAY OPENING TO RESET OVER-RIDDEN
‘BY TEMPERATURE DIFFERENTIAL CONTROL ACROSS BOILER
In Figure V-3, the boiler is continuously circulated at a constant
flow rate. The flow rate corresponding to 20° to 40°AT at the maximum load
draw condition. On a cold start, the boiler temperature differential controls
3-way valve opening; admitting controlled amounts of "cold" system water
into the boiler circuit. As the system heats up, the 3-way opens more to
the system until final controlling reset is obtained.
2, RESET METHODS
Reset control can be obtained by valves alone, pumps alone or
‘by use of valves and pumps in combination.
ntRIGHT /
PICURE V-4 - CONVENTIONAL 3-WAY VALVE RESE!
APPLIED 10 HEATING ONLY SYSTEM
Conventional 3-way valve reset is best used for the heating only
system where, under full load, the entire system flow passes through the
boiler. Under these conditions, the valve is sized to the flow it is
controlling; 1.e, flow from the boiler into the distribution main.
The conventional 3-vay reset control is often mis-applied to
combination heating and cooling systems. The mis-application concerns
a fundamental proposition; that the control valve be sized to the flow
it is controlling.
WRONG!
FIGURE V-5 - CONVENTIONAL 3-WAY RESET APPLIED T0 HEAT/COOL CHANGE -OVER;
VALVE SIZED 10 DISTRIBUTION MAIN PIPE SIZE
In Figure V-5, the 3-vay is sized to the main distribution pipe
size, but is controlling the side branch boiler cireuit flow. Since the
boiler ctreuit flow requirement at full load reset is only 18% (Nain AT
or Boller AT Jijg=134 ) of the main flow rate. ‘the valve is obviously
over-sized; it is sized to control, as an exanple, 300 GPM main flow,
2)
but is used to control approximately 60 GPM boiler input flow.
The situation can be corrected with a resultant saving in valve
and boiler pipe sizing as in Figure V-6.
USED To FORCE FLOW THROUGH
tom sean nares ye
Sehncane
Ricut!
Figure V-6 - THREE WAY RESET APPLIED TO HEAT/COOL
CHANGE-OVER; VALVE SIZED TO FULL LOAD
BOILER CIRCUIT FLOW RATE.
Injection pumps are often used in a Primary-Secondayy Boiler con-
nection for reset.
Figure V-7 - INJECTION PUMP "RESET"
The injection pump can be used for either heating only or for
hheat/cool application. Injection pumps are sometimes used in multiples for
boiler shock protection, When used in multiples, one pump is used for light
load, and other pumpa are sequenced in as load increases. This particular
arrangement is applied by Homer Bird, Consultant in Minneapolis, Minnesota.
13Reser
MULTIPLE INUBCTION PUMP RESET.
Figure V-8 - MULTIPLE INJECTION
PUMP RESET
On cold start up, the pumps are gradually sequenced in until reset
conditions are reached,
Multiple sual boilers are also used for reset control. This partic-
ular method has the advantage of reducing boiler standby loss during light
loads.
Figure V-9 - MULTIPLE BOILER RESET
In multiple boiler reset, only the operating boilers are at
temperature, Standby loss is eliminated for the non-operating boilers
resulting in lower operating cost. During light Load, only one boiler is
“on as load or reset temperature requirements increase additional boilers
axe sequenced “on.
Boiler circuit pumps are often used to provide constant boiler
flow, reduce control valve size and provide against boiler "shock."
“reser
Figure V-10 - SEPARATELY CIRCULATED BOLLER
WITH "RESEI"; BOILER SHOCK
OVERRIDE NOT SHOWN (see Fig. V-3)
3. MEDIUM TEMPERATURE (250° to 300°) BOLLER ROOM APPLICATION
‘The medium temperature system requires special consideration for
its boiler room application; standard low temperature (less than 250°) piping
‘) configurations should not be used.
250 To 300" sone
TaneeraTone,
WRone!
Figure V-11 - STD, L1W ARRANGEMENT SHOULD NOT
BE _USED FOR MIW APPLICATION
In MEW application, the main distribution pump is placed on the
system return in order to reduce temperatures entering the pump.SYSTEM PRESSURIZATION
UMAIN DISTRIBUTION PUMP
g—_peot To 300°
iin seraranon
RiguT.
Figure V-12 - MIW BOTLER ROOM ARRANGEMENT;
WATER TUBE TYPE BOILER
SEPARATELY CIRCULATED
In this arrangenent, the main distribution pump is placed at the
system return discharging into the water tube boiler. Constant flow is
maintained in the boiler to help prevent tube burn-out.
System pressurization is set to a minimum "fill" pressure equal
to a saturation pressure corresponding to 25° above maximum leaving supply
temperature; 300° supply establishes 325° saturation or about 85 psig min-
imum £111 pressure.
The boiler maximum operating pressure will be:
Minimum Fill plus system pressure rise plus pump head.
Location of the pump; discharging into boiler helps prevent boiler
tube burnout.
Steam to water exchangers are often used as a heat source for
MIW application.
Bish,
Figure V-13 - MIW BOILER ROOM ARRANGEMENT
STEAM TO WATER EXCHANGER
16VI. EQUIPMENT OR BOILER ROOM PIPING PRACTICE - CHILLER
CONSTANT CHILLER FLOW
It is important, for most chillers, that a fairly constant chiller
Elow rate be established for good chiller load control. Unless precautions
are taken chiller "short cycle” can occur with resulting chiller problems.
Changing chiller flow rates will occur with 2 way valve system
control.
2 war
VALVES
CHILLER CONTROL:
Figure VI-1 - TWO WAY VALVE CONTROL CAUSES
CHILLER FLOW CHANGE
‘The chiller control is tenperature sensitive only and will go
into the sane load control regardless of flow rate. For a system design
to full load at 300 GPM, the temperature control will load the chiller
properly only at 300 GPM. At 100 GPM flow past the chiller control point,
only 1/3 load is required for any given load temperature signal. The
chiller control cannot recognize the change in load caused by flow change,
however, and chiller load control is upset.
The solution is to provide a relatively constant flow rate past
the chiller temperature load registration point. This can be accomplished
by either of two methods.
1. Separate chiller pump
2. Differential pressure controlled bypass valve.
acircum mens
PRESSURE oreaas
2 way
Vvauwe
conto.
CHILLER LonD conTROL
Figure VI-2 - DIFFERENTIAL PRESSURE CONTROL
‘ACROSS CHILLER OPENS BYPASS
FOR CONSTANT CHILLER FLOM,
In Figure VI-1, a constant chiller flow rate is established by
differential pressure control activation of a two way bypass valve.
pressure differential controller is set to maintain a relatively constant
pressure drop (constant flow).
The differential pressure control is often taken across a cali-
brated orfice meter, rather than the chiller itself.
The separate chiller pump is also employed
chiller flow regardless of system flow change.
IM DISTRIBUTION PUMP,
RS COMMON FIPING BYPASS
YS
2 way
CHILLER RETURN: CHILLER DISCHARGE CONTROL
ConsTANT
Chiccer’
row
CHILLER Loa CONTROL
Rieut/
Figure VI-3. - CONSTANT CHTLLER FLOW ESTABLISHED
BY_SEPARATE CHILEER PONP.
to provide constant‘The separate chiller pump provides constant flow rate through the
chiller regardless of system flow rate.
When system flow rate reduces to less than chiller flow rate, bypass
flow from chiller discharge to chiller return occurs through the common piping
A mixture of system return with chiller discharge water occurs so that a true
load statement is made to the chiller control device in terms of entering
chiller temperature,
‘The separate chiller pump removes chiller P.D. from system pumping
considerations. Removal of the chiller P,D. increases 2 way valve control
effectiveness because of a reduction in the main distribution pump head.
‘The separately circulated chiller, with slight modification, per-
mits use of the chiller to "cool down" hot distribution mains while controlling
inlet chiller water temperatures.
2, Inmediate "cool down" of hot distribution main, Primary-Secondary-Separate
Chiller Pump.
A conmon operational problem with combination heating-cooling
systems concerns switch over from heating to cooling when residual system
water temperatures are too high (over 90°) to permit instant chiller start up.
‘The separately circulated chiller can be used to "cool down" the
hot system water by mixing of chiller discharge water with main system water
to provide allowable chiller entry temperatures.
Either of two methods can be used:
1, Gonstant chiller flow; reduced main flow.
2. Constant chiller flow; constant system flow with
controlled "bleed" flow.
19Teo
Siig
uncer
uray
Sinrer
SamucTURE oF
Rov arstem
wins coun,
Gucae otscungee)
cutter
Figure VI-4 - TIMED 3 WAY VALVE APPLIED
TO SYSTEM COOL DOWN
In this arrangement, often applied by Barber Colman, a three way
valve is time cycled to open from full open bypass to bypass closed in about
20 Min. (time dependent on system water volume and temp.)
SWOT" SYSTEM WATER,
COLD DISCHARGE WaTHE
Pigure VI-5 - THREE WAY VALVE, CONTROLLED FROM
‘SHILLER INLET TEMPERATURE
In figure VI-5, the three way valve is set so as to open to bypass
when inlet temperatures are over 90° and to close to bypass when inlet
temperature is less then 80°,
The three way would be controlled by master, sub naster controllers
50 arranged so as to decrease bypass flow and increase system "bleed" flow
as system water temperature is decreased by chiller operation.
When system water temperature is reduced to less than 80°, the
valve closes completely to bypass and normal system operation occurs.
Another, and very simple arrangement, makes use of a small change-
over distribution pump applied in parallel with the main distribution pump.MAIN PUMP DISTRIBUTION
MAIN DISTRIBUTION PUMP, CONTROL
SorR"@ TEMP OVER 90%
“on” @ TEMP UNDER 90°
sveass
over
Sani cunnce ove CHILLER,
IMP CONTROL OM AT
‘Tene over 30% 0F# at
TENR UNDER 90!
Figure VI-6 - CHANGEOVER PUMP; OPERATION CON-
TROLLED FROM SYSTEM WATER TEMPERATURE
The changeover punp illustration above will generally be a small
booster pump providing a system flow rate less than chiller flow rate.
Since system flow rate is less than chiller flow, a continuous
bypass flow oceura in the Primary-Secondary bypass mixing with system water
to provide mixed chiller entry water that is less than 90°.
When system water temperature decreases to 90°, the main distri-
bution pump is energized and normal system operation takes place.
VII. EQUIPMENT ROOM PUMPING HEATING/COOLING
1, Standby Pump Provision
Most Large heating-cooling systems have standby pump provision,
A common standby method is illustrated below:
Figure VII-1 - COMMON STANDBY; STANDBY SERVES
BOTH TOWER AND SYSTEM DISTRIBUTION
aO
The common standby pump is selected to the greater flow requirement;
usually tower pump and is checked against distribution head requirement by
use of system curve analysis for actual standby system distribution flov.
2. Paralleled Chiller; Each Chiller with its own Pump
On some larger systems, chillers are placed in parallel; each
chiller having its own circulation pump, which is also applied to system
distribution. As load increases chillers are placed on the line, as load
decreases chillers and their pumps are cut off.
CHMLER
‘CAUTION IN PUMP SELECTION 0
system system
CHAR
Figure VII-2 - PARALLEL CHILLERS; EACH
CHILLER WITH PUMP
Caution must be applied in pump selection and operation for this
arrangement. The pump selection can be easily made for full load operation;
with both ehillers and their pumps in operation. As an example:
Pump selection is to be made for parallel chillers; each with its
own pump. Bach chiller has 20 ft. P.D, at 200 GPM. ‘The piping system, ex-
clusive of the chillers, has 80 ft. P.D. at 400 GPM.
The selection point for each pump is then 100 £t. head at 200 GPM.
A "system curve" can be struck for each pump using the "point" 100 ft.
@ 200 GPM.TIL
When only a single chiller is in operation, however, a new set
of circumstances is faced by the single operating pump. The revised
“system curve" for single pump operation can be developed by referencing
piping system P.D. (P.D. exclusive of chiller) to single chiller flow and
adding piping system P.D, and chiller P.D. at a common flow rate; usually
design chiller flow rate, In this case:
Reference to both Chillers; System Piping P.D. = 80' @ 400 G.P.M.
Reference to single Chiller; System Piping P.D. = 20' @ 200 G.P.M.
‘The total revised system curve for the single pump and chiller will then
be:
Chiller P.D. = 20° @ 200 G.P.M.
Piping P.D. = 20' @ 200 G.P.M,
Total System = 40' @ 200 G.P.M. ,
A system curve developed through 40' @ 200 G.P.M, will yield re-
quired information for operation of the single chiller.
EQUIPMENT OR BOILER ROOM PRESSURIZATION
PROBLEMS; HEATING AND/OR COOLING
Note (to be added in Appendix)
BFLUID HANDLING
TRAINING & EDUCATION DEPT
INTED IN UB, 968 Fr eUUis TRANSEen CIMISION