1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1:500
2" ADDITIONAL LEAK
DEDICATED AREA
(AREA 5.0mx5.0m)
NOTES:
DETECTION PIPE 0° 1. PLANT SURVEY INFORMATION:
2x4" DIA. PVC CONDUIT SCH.40 GLOBAL COORDINATES: UMT/WGS 84 - 38 NORTH
FOR ANODE FEEDER CABLES

PLANT NORTH
360° 0° 1x2" DIA. PVC CONDUIT SCH.40 LOCAL COORDINATE ORIGIN:
A A

TRU
REFERENCE ELECTRODE CABLES SEE X= 0.00 - E: 685 400.000
DETAIL - B GROOVE FOR CLEAN DEDICATED AREA
OUTDOOR 2" ADDITIONAL LEAK (AREA 5.0mx5.0m) Y= 0.00 - N: 2 710 350.000

EN
DETECTION PIPE 0°
2x4" DIA. PVC CONDUIT SCH.40 ALL PLANT LEVELS SHOWN ARE LOCAL PLANT LEVELS.
360° 0°

OR
2" ADDITIONAL LEAK FOR ANODE FEEDER CABLES STATION PLATFORM ZERO (0.00) = 574.60 masl

5.71°
DETECTION PIPE 45° 1x2" DIA. PVC CONDUIT SCH.40 ALL UNITS ARE IN METERS IF NOTHING ELSE MENTIONED.

TH
E 15 DER
REFERENCE ELECTRODE CABLES SEE

OVERFLOW 35
2" ADDITIONAL LEAK OUTLET

.00°
DETECTION PIPE 315° DETAIL - B 2. DRAWING DIMENSIONING AND LEVEL INDICATION:

A
SPARE

R HE
Dr

°
ALL UNITS IN mm IF NOTHING ELSE MENTIONED.

.00
ain

31
ABL
AND UIT FO
ALL LEVELS IN METERS IF NOTHING ELSE IS MENTIONED.

32
2" ADDITIONAL LEAK

5.71°
ain
9.0
2" ADDITIONAL LEAK DETECTION PIPE 45°

RE C

Dr

DETECTION PIPE 315° 3. SUBSTRUCTURE AND FOUNDATIONS:

FLUSH TYPE CLEAN OUT

ABL HEADER
OVERFLOW 35
D
PV OUTLET

CON

.00°
B C
PI SPARE BEARING CAPACITY, SETTLEMENT AND DIFFERENTIAL B

Dr

E 15
PE

°
SETTLEMENTS HAVE TO BE PROVEN IN A SEPARATE DOCUMENT.

.00
ain
31

31
İN

AND UIT FO
5.

32
L
00

FITTING 0.00°
ET

ain
9.0
PI ° 4. CONCRETE:

RE C
PE

Dr
LOCAL STATION


30 0°

D
0.0 COORDINATE ORIGIN LEAN CONCRETE MIN. CHARACTERISTIC STRENGTH 15NM/m²

PV
4.2

CON
6

C
9° IP E X = 0.00

PI
CP Y = 0.00 MIN. CEMENT CONTENT 150 kg/m³

PE
PV WGS-84, ZONE 38N

31
İN STRUCTURAL CONCRETE GRADE A

5.
LE E: 685 400.000

00
T MINIMUM CHARACTERISTIC STRENGTH 50 MN/m² (CUBE)

°
PI N: 2 710 350.000
2" ADDITIONAL LEAK PE
°
DETECTION PIPE 270° 30
4 0 .00 MINIMUM CEMENT CONTENT 350 kg/m³
COORDINATE CENTER .29 E6
OF TANK ST - 01 ° ° PIP MAXIMUM CEMENT CONTENT 420 kg/m³
D PIP E 80.00 C
PV
C 2" S LOTTE WATER/CEMENT RATIO 0,40 C
Drain 272.00°
''3'' 2" ADDITIONAL LEAK CONCRETE IN CONTACT WITH SOIL OR WATER
270° PUMP OUT 88.50°
90° DETECTION PIPE 270° COORDINATE CENTER
PUMP OUT 268.50°
0° Drain 92.00° MUST BE WATERPROOF (SEE NOTE ABOVE)
E 260.0 OF TANK ST - 02
IPE 80.00°
TT ED PIP 2" ADDITIONAL LEAK TTED P
2" SLO 2" SLO 5. TYPE OF CEMENT:
m R) (A DETECTION PIPE 90°
. 0 0 0m METE NN PORTLAND CEMENT TYPE 1 ACCORDING TO ASTM C150
106 ER DIA E R)
UL
AR 1 Drain 272.00°
IN N m E T TANK ST - 01 PL 06.2 270° PUMP OUT 88.50°
90°
TYPE V FOR PLAIN CONCRETE
NK 8m IAM AT 38 PUMP OUT 268.50°
(TA 0 8 170.000 m³ E I mm IPE 260
.00° Drain 92.00° ALL UNDERGROUND CONCRETE STRUCTURES SHALL CONTAIN
6. R D NN TTED P 2" ADDITIONAL LEAK
10 UTE D = 106.00 m ER PV 2" SLO
R) (A
MICRO-SILICA OF 7.0% BY WEIGHT OF CEMENT.
m DETECTION PIPE 90°
D LO DIA CP
IPE
0 0 0m METE NN MICROSILICA SHALL COMPLY WITH THE ADDITIONAL REQUIREMENTS D
H EL ME 115 .
106 ER DIA R)
UL
A
(S TE
R)
.00
°
I N N m E TE TANK ST - 02 R P 106 ACCORDING TO SPECIFICATION C07, 2.3 (SILICA FUME).
NK m LA .23
O (TA 88 DIAM 170.000 m³ TE 8m 6. FORMWORK:
U . 0 IN m
TL 6 R NE
ET 10 UTE SMOOTH FORMWORK FOR ALL VISIBLE SURFACES AND
FLUSH TYPE CLEAN OUT

D = 106.00 m RD PV
PI
CP
INLET PE 11
(6NoS.) 2 DIA. PVC CONDUIT SCH.40 LO IA IPE ESPECIALLY FOR ALL WATER COVERED SURFACES
13 ACCESS TUBE (TYP.) H EL ME 115
SPARE (S TE .00 ACCORDING TO ASTM A185.
5. R) °
00
FITTING 180.00°

°
SEE DETAIL C 7. REINFORCING STEEL:

O
Dra

U
°
.00

.00°

TL
REINFORCING STEEL GRADE 60 ACCORDING TO ASTM A615
in 1

E
11

T
2" ADDITIONAL LEAK
200

PI
49
n2

PE
DETECTION PIPE 225°
.00

INLET 8. CONCRETE COVER OF REINFORCING STEEL:


ai

13
Dr

PIP

E E
°

SPARE

5.
FOUNDATION IN CONTACT WITH SOIL 70 mm

00
PVC

°
2" ADDITIONAL LEAK DUCTILITY CLASS B fy ≥ 420 N/mm²
11
(6NoS.) 2 DIA. PVC CONDUIT SCH.40

Dra

2" ADDITIONAL LEAK DETECTION PIPE 135°

184.29°

ACCESS TUBE (TYP.)

1.0

in 1
2" ADDITIONAL LEAK

00.0
DECTION PIPE 180°
''2''

21
DETECTION PIPE 225° SEE DETAIL C

49
E2
ain

.00
OVERFLOW
Dr

PIP

°
PVC
2" ADDITIONAL LEAK
2" ADDITIONAL LEAK DETECTION PIPE 135°
GROOVE FOR CLEAN
OUTDOOR
180° ''1'' DECTION PIPE 180° LEGEND :
STRUCTURE:
F EARTH PLAIN CONCRETE GRADE D F
180°
REINFORCED CONCRETE GRADE A COMPACTED FILL
PLAN VIEW STEEL TANK FROM NR. ST - 01 CLEAN WASHED SAND
1:500 1:500
REFERENCE DOCUMENTS
42-QP10-P-001 TGSE STATION GENERAL PLOT PLAN

42-YB70-S-011 GENERAL ASSEMBLY AND DETAIL DRAWINGS FOR 170.000 M3 STEEL STORAGE TANK

G 42-QB14-R-801 TGSE STATION GEOTECHNICAL INVESTIGATION REPORT G


42-QB14-R-802 TGSE STATION ENDORSEMENT OF GEOTECHNICAL INVESTIGATION REPORT

42-QP10-P-004 TGSE STATION PLATFORM GRADING AND SOIL BALANCE DRAWINGS

±0.00 +0.30
+0.30 ±0.00
ENGINEER'S STICKER: CONTRACTOR'S STICKER:

PROTECTION PIT GEO - TEXTILE SOCK SURROUNDING


FOR SLOTTED PIPE COUPLING 400 mm CLEAN WASHED SAND
2" SLOTTED PIPE
H (See Detail) 500 mm WELL COMPACTED SELECTED FILL H
2" NON - SLOTTED PIPE SHOULD
DURING POURING CONCRETE
ON RING WALL SECTION A - A
SECTIONAL ELEVATION OF SLOTTED PIPE INSTALLATION
1:200

I B ISSUE FOR APPROVAL Z.H. A.Y. D.E.K. 09.09.2024 I


A ISSUE FOR APPROVAL Z.H. A.Y. D.E.K. 05.06.2024
‫جيقنت‬ ‫جأرررحت‬ ‫اهدعأ‬ ‫ةطساوب جدقدت‬ ‫وقعشومقا‬ ‫وقرأرنا‬
REV. ISSUED FOR BY CHECKED APPROVED DATE
FLUSH TYPE CLEAN OUT

GROOVE FOR CLEAN OUTDOOR TANK FOUNDATION ‫لوااملا لوعـيـلللا لوـلللللعلمـللللا‬


STEEL COURSE
FITTING 0.00° (ST-02)

(RING BEAM) KINGDOM OF SAUDI ARABIA


GROOVE FOR CLEAN OUTDOOR ‫هايقتا تاقنقتو لقن ةـرا‬
ANNULAR PLATE
ANNULAR PLATE WATER TRANSMISSION AND TECHNOLOGIES CO
J Project No. J
300mm CLEAN WASHED SAND
BOTTOM PLATE 20 mm (or 2x10 mm) ‫مقر عورشم‬ SOUTHERN RING WATER TRANSMISSION SYSTEM
FILLER BOARD 5536 FOR THE CITY OF RIYADH
+0.30
Package C

400 mm CLEAN WASHED SAND


±0.00
‫لوانهمل‬
KHATIB & ALAMI
HDPE LINER, 0.75 mm THICK ENGINEER

500 mm WELL COMPACTED


K SELECTED FILL K
‫لواقملا‬ MAPA CONSTRUCTION & TRADE CO. INC.
WATERPROOFING AND
CONCRETE PROTECTION CONTRACTOR

ORIGINAL DRAWING SIZE: A1


SCALE TGSE STRATEGIC TANKS TANK FOUNDATION 170.000m³
1:500 GUIDE DRAWINGS
1:200, 1:25
BOTTOM REINFORCING PLATE
DOCUMENT NO: Sheet Rev
GROOVE FOR CLEAN OUTDOOR
4 2 - Z G 2 7 - S - 0 0 1 1 of 2 B
L L
DETAIL ''1'' SECTION B - B SECTION C - C
1:25 SUB-CONTRACTOR
1:25 1:25 PROJECT DEVELOPMENT / ENGINEERING MANAGEMENT

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

STEEL COURSE NOTES:


20 mm (or 2x10 mm) FILLER BOARD 1. PLANT SURVEY INFORMATION:
GLOBAL COORDINATES: UMT/WGS 84 - 38 NORTH
STEEL COURSE LOCAL COORDINATE ORIGIN:
A X= 0.00 - E: 685 400.000 A
20 mm (or 2x10 mm) FILLER BOARD Y= 0.00 - N: 2 710 350.000
2" NON - SLOTTED PIPE ALL PLANT LEVELS SHOWN ARE LOCAL PLANT LEVELS.
ANNULAR PLATE ANNULAR PLATE
STATION PLATFORM ZERO (0.00) = 574.60 masl
A A PROTECTION PIT FOR ALL UNITS ARE IN METERS IF NOTHING ELSE MENTIONED.
SLOPE MIN %1 2" SLOTTED PIPE SLOPE MIN %1
+0.30 SLOTTED PIPE +0.30 2. DRAWING DIMENSIONING AND LEVEL INDICATION:
400 mm CLEAN WASHED SAND 400 mm CLEAN WASHED SAND ALL UNITS IN mm IF NOTHING ELSE MENTIONED.
±0.00 ±0.00 ALL LEVELS IN METERS IF NOTHING ELSE IS MENTIONED.
3. SUBSTRUCTURE AND FOUNDATIONS:
B BEARING CAPACITY, SETTLEMENT AND DIFFERENTIAL B
HDPE LINER, 0.75mm THICK HDPE LINER, 0.75 mm THICK SETTLEMENTS HAVE TO BE PROVEN IN A SEPARATE DOCUMENT.

500 mm WELL COMPACTED 500 mm WELL COMPACTED 4. CONCRETE:


SELECTED FILL SELECTED FILL LEAN CONCRETE MIN. CHARACTERISTIC STRENGTH 15NM/m²
MIN. CEMENT CONTENT 150 kg/m³
WATERPROOFING AND WATERPROOFING AND STRUCTURAL CONCRETE GRADE A
CONCRETE PROTECTION CONCRETE PROTECTION MINIMUM CHARACTERISTIC STRENGTH 50 MN/m² (CUBE)
2 x 4" DIA. PVC CONDUIT SCH.40
MINIMUM CEMENT CONTENT 350 kg/m³
FOR ANODE FEEDER CABLES
1 x 2" DIA. PVC CONDUIT SCH.40 MAXIMUM CEMENT CONTENT 420 kg/m³
C FOR REFERENCE ELECTRODE CABLES WATER/CEMENT RATIO 0,40 C
CONCRETE IN CONTACT WITH SOIL OR WATER
MUST BE WATERPROOF (SEE NOTE ABOVE)
DETAIL OF CONDUIT DETAIL OF SLOTTED PIPE INSTALLATION
5. TYPE OF CEMENT:
1:25 1:25 PORTLAND CEMENT TYPE 1 ACCORDING TO ASTM C150
TYPE V FOR PLAIN CONCRETE
ALL UNDERGROUND CONCRETE STRUCTURES SHALL CONTAIN
MICRO-SILICA OF 7.0% BY WEIGHT OF CEMENT.
D STEEL COURSE PROTECTION PIT FOR MICROSILICA SHALL COMPLY WITH THE ADDITIONAL REQUIREMENTS D
SLOTTED PIPE ACCORDING TO SPECIFICATION C07, 2.3 (SILICA FUME).
20 mm (or 2x10 mm) FILLER BOARD
PROTECTION PIT FOR
6. FORMWORK:
38.1 MM DIA. PVC PIPE WITH
CAP THROUGH RING BEAM SLOTTED PIPE SMOOTH FORMWORK FOR ALL VISIBLE SURFACES AND
INTO BASE SAND PAD (6x) ESPECIALLY FOR ALL WATER COVERED SURFACES
ANNULAR PLATE ACCORDING TO ASTM A185.
LID / COVER
7. REINFORCING STEEL:
A
+0.30 REINFORCING STEEL GRADE 60 ACCORDING TO ASTM A615
400 mm CLEAN WASHED SAND 8. CONCRETE COVER OF REINFORCING STEEL:
E ±0.00 FOUNDATION IN CONTACT WITH SOIL 70 mm E
DUCTILITY CLASS B fy ≥ 420 N/mm²
±0.00
HDPE LINER, 0.75 mm THICK

500 mm WELL COMPACTED


2" SLOTTED
SELECTED FILL
UPVC PIPE LEGEND :
HOLE SUITABLE FOR
WATERPROOFING AND STRUCTURE:
F
CONCRETE PROTECTION SECTION VIEW 2" SLOTTED UPVC PIPE
F
EARTH PLAIN CONCRETE GRADE D
TOP VIEW 1:25
LID / COVER
1:25 REINFORCED CONCRETE GRADE A COMPACTED FILL

CLEAN WASHED SAND

DETAIL C DETAIL OF PROTECTION PIT FOR


REFERENCE DOCUMENTS
2" SLOTTED PIPE
DETAIL OF ACCESS TUBE 42-QP10-P-001 TGSE STATION GENERAL PLOT PLAN

1:25 1:25 42-YB70-S-011 GENERAL ASSEMBLY AND DETAIL DRAWINGS FOR 170.000 M3 STEEL STORAGE TANK

G CL CONDUIT FOR HEADER


AND RE CABLE 15.00°
42-QB14-R-801 TGSE STATION GEOTECHNICAL INVESTIGATION REPORT G
42-QB14-R-802 TGSE STATION ENDORSEMENT OF GEOTECHNICAL INVESTIGATION REPORT
+0.30
42-QP10-P-004 TGSE STATION PLATFORM GRADING AND SOIL BALANCE DRAWINGS
PIT
MP
SU
AIN

Ø300 (12") PIPE


Ø300 (12") ELBOW ENGINEER'S STICKER: CONTRACTOR'S STICKER:
E

DR
RS
OU
LC

H +0.30 H
ST NK
EE
TA

BOTTOM PLATE
UPN 160

ANNULAR PLATE

I B ISSUE FOR APPROVAL Z.H. A.Y. D.E.K. 09.09.2024 I


VORTEX BREAKER A ISSUE FOR APPROVAL Z.H. A.Y. D.E.K. 05.06.2024
21 .00°

DETAIL A ‫جيقنت‬

HDPE LINER, 0.75 mm THICK ‫جأرررحت‬ ‫اهدعأ‬ ‫ةطساوب جدقدت‬ ‫وقعشومقا‬ ‫وقرأرنا‬
9
0.0
Dr in 14

REV. ISSUED FOR BY CHECKED APPROVED DATE


400 mm CLEAN WASHED SAND
1:10
a
ain
Dr

WATERPROOFING AND ‫لوااملا لوعـيـلللا لوـلللللعلمـللللا‬


DETAIL 2 CONCRETE PROTECTION WORK
HDPE LINER, 0.75mm THICK KINGDOM OF SAUDI ARABIA
1:50 PUMP-OUT NOZZLE SUMP SIDE VIEW 2 x 4" DIA. PVC CONDUIT SCH.40
DETAIL B ‫هايقتا تاقنقتو لقن ةـرا‬
FOR ANODE FEEDER CABLES
1:25 1 x 2" DIA. PVC CONDUIT SCH.40 1:10 Project No. WATER TRANSMISSION AND TECHNOLOGIES CO
J FOR REFERENCE ELECTRODE CABLES
J
‫مقر عورشم‬ SOUTHERN RING WATER TRANSMISSION SYSTEM
TANK 5536 FOR THE CITY OF RIYADH
STEEL COURSE Package C
ALL CONCRETE STRUCTURES WITH A FLOOR LEVEL
270° L 170.000-m3 TANK
C
Ø100 (4") PIPE
BELOW PERMANENT GRADE SHALL HAVE THE
Ø100 (4") ELBOW TANKING: UNDERGROUND PART COMPLETELY ENCASED IN A
TANKING MADE FROM PREFABRICATED HEAVY DUTY
‫لوانهمل‬
KHATIB & ALAMI
WATER PROOFING MEMBRANE OF MODIFIED BITUMEN,
TANKING DETAIL: MINIMUM 4MM THICK AND WITH A POLYESTER ENGINEER
UPN 80 CONCRETE OVERLAY 50mm NON-WOVEN FABRIC BASE. THE TANKING ON THE SIDES
AND THE OPS OF THE STRUCTURES SHALL BE FULLY
K TORCH-APPLIED ON A BITUMEN-PRIMED SURFACE. THE
K
‫لواقملا‬ MAPA CONSTRUCTION & TRADE CO. INC.
PUMP OUT SUMP PIT ANNULAR PLATE PROTECTION MATERIAL SHALL CONTINUE TO A LEVEL
PUMP OUT 268.50° TANKING NOT LESS THAN 0.2M ABOVE FINAL GRADE (STATION CONTRACTOR
PUMP OUT 88.50° LEAN CONCRETE 100mm ELEVATION).

ORIGINAL DRAWING SIZE: A1


PE SHEET THE TANKING UNDER THE STRUCTURES SHALL BE LAID TGSE STRATEGIC TANKS TANK FOUNDATION 170.000m³
SCALE
ON A CONCRETE BLINDING AND POTECTED BY A
1:500, 1:50 GUIDE DRAWINGS
CONCRETE OVERLAY OF MINIMUM 50MM THICKNESS. ALL
1:25, 1:10
OVERLAPS SHALL BE MINIMUM 100 mm AND FULLY
TORCH-WELDED. PROTECTION MEMBRANE FOR DOCUMENT NO: Sheet Rev

DETAIL 3 VERTICAL ELEMENTS TO BE USED. 300 MICRON PE


SHEET SHALL BE LAID BENEATH THE LEAN CONCRETE.
4 2 - Z G 2 7 - S - 0 0 1 2 of 2 B
L 1:50 RAIN NOZZLE SUMP SIDE VIEW L
1:25 SUB-CONTRACTOR
PROJECT DEVELOPMENT / ENGINEERING MANAGEMENT