1.

8 meter
Satellite Dish LEGEND:
@ Frequency 2250 = 10dB/30.5m
IF Amplifier, Televes, Ref 5363.
Attenuation = 10dB /30.5m (30.0m) =9.84dB
30.0m
Thus: dB Input = 92dB – 9.84dB = 82.16dB
Grounding block, DC to 3GHz

Surge protector, TSS-2400

To: 220VAC
AV Terminator, 75Ω
R 2 – Way 2 – Way 2 – Way
Splitters Splitters Splitters
5 – Way 5 – Way 5 – Way 6 – Way 5 – Way 6 – Way 5 – Way 5 – Way
Splitters Splitters Splitters Splitters Splitters Splitters Splitters Splitters
Coaxial Cable RG-11
4 – Way 4 – Way 4 – Way 4 – Way
Tap-Off, Tap-Off, Tap-Off, Tap-Off, 3.96m Coaxial Cable RG-6
16th Floor 5 – Way 24dB 5 – Way 11th Floor 5 – Way 24dB 5 – Way 7th Floor 5 – Way 24dB 5 – Way 2nd Floor
5 – Way 20dB 5 – Way
Splitters Splitters Splitters Splitters Splitters Splitters Splitters Splitters
38 Rooms 41 Rooms 41 Rooms 38 Rooms Coaxial Cable rRG-59
5 – Way 5 – Way 5 – Way 5 – Way 5 – Way 5 – Way 5 – Way 5 – Way
Splitters Splitters Splitters Splitters Splitters Splitters Splitters Splitters Grounding wire, 5.5mm2 THHN or TW
4 – Way 4 – Way 4 – Way 4 – Way
Tap-Off, Unit 1 Unit 38 Tap-Off, Unit 1 Unit 41 Tap-Off, Unit 1 Unit 41 Tap-Off, Unit 1 Unit 38
5 – Way 5 – Way 5 – Way 5 – Way 5 – Way 5 – Way
Power wire, 2.0mm2 Royal Cord 2C
20dB 20dB 20dB 5 – Way 16dB 5 – Way
Splitters Splitters Splitters Splitters Splitters Splitters Splitters Splitters

5 – Way 6 – Way 5 – Way 6 – Way 5 – Way 6 – Way NOTES:


Splitters Splitters Splitters Splitters Splitters Splitters
4 – Way 4 – Way 4 – Way
Tap-Off, Tap-Off,
1. Feeder lines should be Belden or Philflex coaxial cable RG
Tap-Off,
Grd Floor 11 in 2.0” dia. PVC conduit unless noted otherwise.
5 – Way 16dB 5 – Way 5 – Way 16dB 5 – Way 5 – Way 16dB 5 – Way
Splitters Splitters Splitters Splitters Splitters Splitters 4 – Way
3 TVS
15th Floor 10th Floor 6th Floor
Common Tap-Off, 3.96m
Area 12dB 1.1 Roof deck Conduit – Supply and Installation should
5 – Way 5 – Way 41 Rooms 5 – Way 5 – Way 41 Rooms 5 – Way 5 – Way
41 Rooms care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
Splitters Splitters Splitters Splitters Splitters Splitters
Conduit.
4 – Way 4 – Way 4 – Way
Tap-Off, Tap-Off, Tap-Off,
5 – Way 5 – Way 5 – Way 5 – Way
1.2 Riser Conduit – Cignal TV will utilize CLIENT provided
5 – Way 12dB 5 – Way Unit 1 Unit 41
12dB
Unit 1 Unit 41 12dB Unit 1 Unit 41 Unit 1 Unit 3 Cable Conduit 4 inches.
Splitters Splitters Splitters Splitters Splitters Splitters

1.3 Feeder Cable – Supply and installation should care off


5 – Way 6 – Way 5 – Way 6 – Way 5 – Way 6 – Way to Cignal TV.
Splitters Splitters Splitters Splitters Splitters Splitters
4 – Way 4 – Way 4 – Way 1.4 Terminal Panel – Cignal TV will utilize CLIENT provided
Tap-Off, Tap-Off, Tap-Off, Terminal Panel wherein the dimension is 600 x 700 x
5 – Way 24dB 5 – Way 5 – Way 24dB 5 – Way 5 – Way 24dB 5 – Way 200mm.
Splitters Splitters Splitters Splitters Splitters Splitters
9th Floor 5th Floor
14th Floor
5 – Way 5 – Way 41 Rooms
5 – Way 5 – Way
41 Rooms
5 – Way 5 – Way 2. Distribution lines should be Belden or Phil-flex coaxial
41 Rooms Splitters Splitters Splitters Splitters Splitters Splitters 3.96m cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
4 – Way 4 – Way 4 – Way shield at least 60% braiding.
Tap-Off, Tap-Off, Tap-Off,
5 – Way 20dB 5 – Way 5 – Way 20dB 5 – Way 5 – Way 20dB 5 – Way HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL
Unit 1 Unit 41 Unit 1 Unit 41 Unit 1 Unit 41
Splitters Splitters Splitters Splitters Splitters Splitters SHIELD

5 – Way 6 – Way 5 – Way 6 – Way 5 – Way 5 – Way 3. Active and Passive components should be Televes Brand
Splitters Splitters Splitters Splitters Splitters Splitters with rated frequencies of 5-2400MHz.
4 – Way 4 – Way 4 – Way
Tap-Off, Tap-Off, Tap-Off, 4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”
5 – Way 16dB 5 – Way 5 – Way 16dB 5 – Way 5 – Way 16dB 5 – Way dia. PVC conduit.
Splitters Splitters Splitters Splitters Splitters Splitters
12th Floor 8th Floor 3rd Floor 5. Power receptacles for General use shall be 2 Wire, 220V,
5 – Way 5 – Way 5 – Way 5 – Way 5 – Way 5 – Way 3.96m 20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
41 Rooms 41 Rooms 39 Rooms devices manufactured by National with modern Plate or
Splitters Splitters Splitters Splitters Splitters Splitters
4 – Way 4 – Way 4 – Way approved equivalent.
Tap-Off, Tap-Off, Tap-Off,
5 – Way 12dB 5 – Way Unit 1 Unit 41 5 – Way 12dB 5 – Way Unit 1 Unit 41 5 – Way 12dB 5 – Way Unit 1 Unit 39 6. Compression connectors should be type approved, used
Splitters Splitters Splitters Splitters Splitters Splitters PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.

PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256
LEGEND:
IF Amplifier, Televes, Ref 5363.

Grounding block, DC to 3GHz

Surge protector, TSS-2400

Terminator, 75Ω

Coaxial Cable RG-11


LED TV
Coaxial Cable RG-6

Coaxial Cable rRG-59

Grounding wire, 5.5mm2 THHN or TW

Power wire, 2.0mm2 Royal Cord 2C

Coaxial Cable, RG - 6
HDMI Cable
NOTES:

1. Feeder lines should be Belden or Philflex coaxial cable RG


-
CIGNALTV STB 11 in 2.0” dia. PVC conduit unless noted otherwise.
Coaxial Cable, RG - 11

Coaxial Cable, RG - 6 1.1 Roof deck Conduit – Supply and Installation should
LED TV care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
HDMI Cable Conduit.
Coaxial Cable, RG - 11
1.2 Riser Conduit – Cignal TV will utilize CLIENT provided
Cable Conduit 4 inches.

1.3 Feeder Cable – Supply and installation should care off


to Cignal TV.

1.4 Terminal Panel – Cignal TV will utilize CLIENT provided


Terminal Panel wherein the dimension is 600 x 700 x
200mm.
HDMI Cable

2. Distribution lines should be Belden or Phil-flex coaxial


cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
- shield at least 60% braiding.
CIGNALTV STB

HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL


SHIELD

3. Active and Passive components should be Televes Brand


with rated frequencies of 5-2400MHz.

4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”


dia. PVC conduit.

5. Power receptacles for General use shall be 2 Wire, 220V,


20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
devices manufactured by National with modern Plate or
approved equivalent.

6. Compression connectors should be type approved, used


PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.
CONVENTIONAL COAX SET UP

PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256
LEGEND:
IF Amplifier, Televes, Ref 5363.

Grounding block, DC to 3GHz

Surge protector, TSS-2400

Terminator, 75Ω

Coaxial Cable RG-11

Coaxial Cable RG-6

Coaxial Cable rRG-59

Grounding wire, 5.5mm2 THHN or TW

Power wire, 2.0mm2 Royal Cord 2C

NOTES:

1. Feeder lines should be Belden or Philflex coaxial cable RG


11 in 2.0” dia. PVC conduit unless noted otherwise.

1.1 Roof deck Conduit – Supply and Installation should


care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
Conduit.

1 INCH PVC CONDUIT LAYOUT 1.2 Riser Conduit – Cignal TV will utilize CLIENT provided
Cable Conduit 4 inches.
WITH UNISTRUT CHANNEL
1.3 Feeder Cable – Supply and installation should care off
to Cignal TV.

1.4 Terminal Panel – Cignal TV will utilize CLIENT provided


Terminal Panel wherein the dimension is 600 x 700 x
200mm.

2. Distribution lines should be Belden or Phil-flex coaxial


cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
shield at least 60% braiding.
2.0 Meters Scale Reference
HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL
SHIELD

3. Active and Passive components should be Televes Brand


with rated frequencies of 5-2400MHz.

4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”


2 METERS REFERENCE dia. PVC conduit.

Basepad: 1.2 x 1.2 x 0.2m 5. Power receptacles for General use shall be 2 Wire, 220V,
20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
devices manufactured by National with modern Plate or
approved equivalent.
0.9m
6. Compression connectors should be type approved, used
PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.

PROPOSED SATELLITE DISH LOCATION, 1.8m DIAMETER TO BE FLOOR MOUNTED – OPTION 1


PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256
LEGEND:
IF Amplifier, Televes, Ref 5363.

Grounding block, DC to 3GHz

Surge protector, TSS-2400

Terminator, 75Ω

Coaxial Cable RG-11

Coaxial Cable RG-6

Coaxial Cable rRG-59

Grounding wire, 5.5mm2 THHN or TW

Power wire, 2.0mm2 Royal Cord 2C

NOTES:

1. Feeder lines should be Belden or Philflex coaxial cable RG


11 in 2.0” dia. PVC conduit unless noted otherwise.

1.1 Roof deck Conduit – Supply and Installation should


care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
Conduit.

1.2 Riser Conduit – Cignal TV will utilize CLIENT provided


Cable Conduit 4 inches.

1 INCH PVC CONDUIT LAYOUT 1.3 Feeder Cable – Supply and installation should care off
to Cignal TV.
WITH UNISTRUT CHANNEL
1.4 Terminal Panel – Cignal TV will utilize CLIENT provided
Terminal Panel wherein the dimension is 600 x 700 x
200mm.

2. Distribution lines should be Belden or Phil-flex coaxial


cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
shield at least 60% braiding.

HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL


SHIELD
2.0 Meters Scale Reference 3. Active and Passive components should be Televes Brand
with rated frequencies of 5-2400MHz.

4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”


dia. PVC conduit.

2 METERS REFERENCE 5. Power receptacles for General use shall be 2 Wire, 220V,
20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
Basepad: 1.2 x 1.2 x 0.2m devices manufactured by National with modern Plate or
approved equivalent.

6. Compression connectors should be type approved, used


PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.

PROPOSED SATELLITE DISH LOCATION, 1.8m DIAMETER TO BE FLOOR MOUNTED – OPTION 2


PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256
NOTE:

1. CLIENT SHOULD PROVIDE POWER TAPPING LEGEND:


220V, 20A OF CIRCUIT BREAKER @ 18TH IF Amplifier, Televes, Ref 5363.
FLOOR.
Grounding block, DC to 3GHz

Surge protector, TSS-2400

Terminator, 75Ω

Coaxial Cable RG-11

Coaxial Cable RG-6

Coaxial Cable rRG-59

FROM SATELLITE DISH Grounding wire, 5.5mm2 THHN or TW

GOING TO 16TH Power wire, 2.0mm2 Royal Cord 2C


FLOOR EE ROOM
GOING TO 16TH NOTES:
FLOOR EE ROOM
1. Feeder lines should be Belden or Philflex coaxial cable RG
11 in 2.0” dia. PVC conduit unless noted otherwise.

1.1 Roof deck Conduit – Supply and Installation should


care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
Conduit.

1.2 Riser Conduit – Cignal TV will utilize CLIENT provided


Cable Conduit 4 inches.

1.3 Feeder Cable – Supply and installation should care off


to Cignal TV.

1.4 Terminal Panel – Cignal TV will utilize CLIENT provided


Terminal Panel wherein the dimension is 600 x 700 x
200mm.

2. Distribution lines should be Belden or Phil-flex coaxial


cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
shield at least 60% braiding.

HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL


SHIELD

3. Active and Passive components should be Televes Brand


with rated frequencies of 5-2400MHz.

UNISTRUT 4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”


dia. PVC conduit.
CHANNEL
5. Power receptacles for General use shall be 2 Wire, 220V,
20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
devices manufactured by National with modern Plate or
approved equivalent.

6. Compression connectors should be type approved, used


PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.

FROM SATELLITE DISH GOING TO 16TH FLOOR EE ROOM

PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256
LEGEND:
IF Amplifier, Televes, Ref 5363.

Grounding block, DC to 3GHz

Surge protector, TSS-2400

Terminator, 75Ω

RG6 SCHNEIDER DUAL SHIELD


Coaxial Cable RG-11
UTILIZE 4 INCHES PVC RISER
Coaxial Cable RG-6
CONDUIT.
Coaxial Cable rRG-59

Grounding wire, 5.5mm2 THHN or TW

Power wire, 2.0mm2 Royal Cord 2C


UTILIZING 2 INCHES IMC
CONDUIT
NOTES:
UTILIZE TERMINAL PANEL 1. Feeder lines should be Belden or Philflex coaxial cable RG
11 in 2.0” dia. PVC conduit unless noted otherwise.
WITH DIMENSION OF 600 X
700 X 200mm.
1.1 Roof deck Conduit – Supply and Installation should
care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
Conduit.
OR UTILIZING CABLE UTILIZE TERMINAL PANEL 1.2 Riser Conduit – Cignal TV will utilize CLIENT provided
RACEWAY WITH DIMENSION OF 600 X Cable Conduit 4 inches.

700 X 200mm. 1.3 Feeder Cable – Supply and installation should care off
to Cignal TV.

1.4 Terminal Panel – Cignal TV will utilize CLIENT provided


Terminal Panel wherein the dimension is 600 x 700 x
200mm.

2. Distribution lines should be Belden or Phil-flex coaxial


cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
shield at least 60% braiding.

HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL


SHIELD

3. Active and Passive components should be Televes Brand


UTILIZE 4 INCHES PVC RISER with rated frequencies of 5-2400MHz.
CONDUIT. 4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”
dia. PVC conduit.

5. Power receptacles for General use shall be 2 Wire, 220V,


20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
devices manufactured by National with modern Plate or
approved equivalent.

6. Compression connectors should be type approved, used


PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.
TERMINAL PANEL SET UP

PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256
LEGEND:
IF Amplifier, Televes, Ref 5363.

Grounding block, DC to 3GHz

Surge protector, TSS-2400

Terminator, 75Ω
F TYPE CONNECTOR
Coaxial Cable RG-11

Coaxial Cable RG-6

Coaxial Cable rRG-59

Grounding wire, 5.5mm2 THHN or TW

Power wire, 2.0mm2 Royal Cord 2C

NOTES:

1. Feeder lines should be Belden or Philflex coaxial cable RG


11 in 2.0” dia. PVC conduit unless noted otherwise.

NOTE: 1.1 Roof deck Conduit – Supply and Installation should


care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
Conduit.
• CLIENT SHOULD PROVIDE 1.2 Riser Conduit – Cignal TV will utilize CLIENT provided
POWER OUTLET FOR SET TOP Cable Conduit 4 inches.

BOX. 1.3 Feeder Cable – Supply and installation should care off
• INSTALLING L TYPE ADAPTER to Cignal TV.

FOR STB PLUG. 1.4 Terminal Panel – Cignal TV will utilize CLIENT provided
Terminal Panel wherein the dimension is 600 x 700 x
200mm.

2. Distribution lines should be Belden or Phil-flex coaxial


cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
shield at least 60% braiding.

HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL


SHIELD

3. Active and Passive components should be Televes Brand


NOTE FOR HORIZONTAL CABLE: with rated frequencies of 5-2400MHz.

1. ANY HORIZONTAL CABLE THAT IS NOT A TYPE APPROVED OF CIGNALTV IS SUBJECT TO RECTIFY BY 4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”
dia. PVC conduit.
CLIENT.
5. Power receptacles for General use shall be 2 Wire, 220V,
2. HORIZONTAL CABLE SHOULD BE 1:1 CONNECTION. 20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
devices manufactured by National with modern Plate or
approved equivalent.
3. HORIZONTAL CABLE SHOULD BE RG6 CABLE WITH RATED FREQUENCIES OF 5-2400 MHz.
6. Compression connectors should be type approved, used
4. AVOID SWAN CABLE PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.
HORIZONTAL CABLE INSTALLED FACEPLATES, CONNECTOR AND L TYPE ADAPTER

PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256
NOTE: LEGEND:
IF Amplifier, Televes, Ref 5363.
• CLIENT SHOULD PROVIDE
POWER OUTLET FOR SET TOP Grounding block, DC to 3GHz
BOX.
• INSTALLING L TYPE ADAPTER Surge protector, TSS-2400
FOR STB PLUG.
Terminator, 75Ω

Coaxial Cable RG-11

Coaxial Cable RG-6

Coaxial Cable rRG-59

Grounding wire, 5.5mm2 THHN or TW

Power wire, 2.0mm2 Royal Cord 2C

CAFETERIA TV NOTES:

1. Feeder lines should be Belden or Philflex coaxial cable RG


11 in 2.0” dia. PVC conduit unless noted otherwise.

1.1 Roof deck Conduit – Supply and Installation should


care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
Conduit.

1.2 Riser Conduit – Cignal TV will utilize CLIENT provided


Cable Conduit 4 inches.

1.3 Feeder Cable – Supply and installation should care off


to Cignal TV.

1.4 Terminal Panel – Cignal TV will utilize CLIENT provided


Terminal Panel wherein the dimension is 600 x 700 x
200mm.

2. Distribution lines should be Belden or Phil-flex coaxial


cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
shield at least 60% braiding.

HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL


SHIELD

3. Active and Passive components should be Televes Brand


with rated frequencies of 5-2400MHz.

4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”


dia. PVC conduit.

5. Power receptacles for General use shall be 2 Wire, 220V,


20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
devices manufactured by National with modern Plate or
approved equivalent.
LOBBY TV OFFICE TV
6. Compression connectors should be type approved, used
PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.
TVs AT COMMON AREAS AT GROUND FLOOR

PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256
LEGEND:
IF Amplifier, Televes, Ref 5363.

Grounding block, DC to 3GHz

OPTION 1 Surge protector, TSS-2400


W E
Terminator, 75Ω
Satellite Dish
location

Satellite Dish Coaxial Cable RG-11


Direction W E OPTION 2
S Coaxial Cable RG-6
Satellite Dish
location Coaxial Cable rRG-59
Satellite Dish
Direction Grounding wire, 5.5mm2 THHN or TW
S
Power wire, 2.0mm2 Royal Cord 2C

NOTES:

1. Feeder lines should be Belden or Philflex coaxial cable RG


11 in 2.0” dia. PVC conduit unless noted otherwise.

1.1 Roof deck Conduit – Supply and Installation should


care off to CIGNAL TV. Sizes should be 3/4” dia. EMT
Conduit.

1.2 Riser Conduit – Cignal TV will utilize CLIENT provided


Cable Conduit 4 inches.

1.3 Feeder Cable – Supply and installation should care off


to Cignal TV.

1.4 Terminal Panel – Cignal TV will utilize CLIENT provided


Terminal Panel wherein the dimension is 600 x 700 x
200mm.

2. Distribution lines should be Belden or Phil-flex coaxial


cable RG 6 in ½” dia. PVC Conduit. Cables should be tri
shield at least 60% braiding.

HORIZONTAL CABLE INSTALLED – RG6 PHILFLEX DUAL


SHIELD

3. Active and Passive components should be Televes Brand


with rated frequencies of 5-2400MHz.

4. Grounding wire shall be 5.5mm² THHN or TW wire in 1/2”


dia. PVC conduit.

5. Power receptacles for General use shall be 2 Wire, 220V,


20A respectively, wire shall be 2.0mm² Royal Cord 2C, all
devices manufactured by National with modern Plate or
approved equivalent.

6. Compression connectors should be type approved, used


PCT, PPC or Gilbert brand.

7. All materials to be used shall be brand new and with the


approved type.

SATELLITE DISH DIRECTION REFERENCE


PROJECT TITLE OWNER SBDD ENGINEERING PREPARED BY PRE SALES 15/01/2024

Prepared by: Checked by: Approved by: Approved by: APPROVED BY ENG’G 01/19/2024
HOTEL 101 MANILA PROPOSED CIGNAL FACILITIES DOUBLE DRAGON
CIGNAL TV INC. RELEASED TO INSTI 01/19/2024
5th Floor Launchpad SHEET CONTENT LOCATION
REVISED DATE1
Reliance cor Sheridan Street DTHTV SINGLE LINE DIAGRAM
ONMandaluyong
CITY City PASAY CITY M. M. BOBIER A. E. CASTAÑEDA R. G. TINUMPIT R. J. NAGUA
REVISED DATE2
CONVENTIONAL COAX (FINAL DESIGN)
927 2256