ANDHUAN ZONE-1,GHAZIPUR BLOCK,GHAZIPUR DISTRICT,U.P.

550_12

18 GAUGE G I
4-12 # HOOPS SHEET COVER

LIGHTNING CONDUCTOR
316 - 12 # @ 100 C/C RADIALLY.
8 # @ 200 MESH
CURTAIL ALTERNATE RADIAL BARS AT 1500

100
6Ø ANCHOR FROM INNER FACE OF BEAM IN MIDDLE

80
ISA 50X50X6 4 - 12 # 6 - 16 # HOOPS
BARS 300 LONG 2550 2550 + 2 - 16 #, 2550 LONG 14 - 12 # HOOPS
ISA 50X50X6 6 - 16 # HOOPS (OVERLAP AT MID ONLY)
00 A
5
250

FLY MESH OVER EXPANDED METAL 6 - 16 # HOOPS + 2 - 16 #, 2550 LONG


A=

600
DI
8 # STR @150 C/C TOP DOME 7 ISA 50X50X6 POSTS OR

10
0
125X125 R.C.C.POSTS FOUNDATION

700
4 - 8 # HOOPS
4-12 # RING BEAM
MANHOLE ( 550 X 700 )

200
10 # STR
250
200 1200 200 125 125
5 - 16 # HOOPS A
(OVERLAP AT SUPPORTS ONLY) 5 - 16 # HOOPS
500

575
23 - 10 # 2-LEGGED STIRRUPS @ 125 C/C
DETAILS OF VENTILATOR
20 DIA M. S. BARS @ 250 C/C 8 - 10 # RINGS @ 75 C/C
R = 6950

TOP RING BEAM SECTION A - A R = 5275

ISA 50X50X6 7 - 16 # 8 # RINGS @ 190 C/C

500 450 2691.6 450


℄ OF TANK

10 # RADIALLY @ 140 C/C


4 - 8 # HOOPS
PART L - SECTION OF BOTTOM RING BEAM
STEEL LADDER 10 # HOOPS @ 140 C/C

115
R = 2250
7 - 16 #

200
8 # RINGS @ 190 C/C
1500
1675 2475 21 - 12 # HOOPS
550
4700 450 DIA COLUMNS

R = 13334
(10 NOS.)
8 - 10 # RINGS @ 75 C/C REINFORCEMENT PLAN OF ANNULAR RAFT
10 - 10 # HOOPS

575
1000 1000 1000 1000
3 - 16 # + 2 -12#

1700
3 - 16 # + 2 -12# B 3 - 16 # C 2450 LONG

80
2450 LONG 3 - 16 #

0
120

500
50

3 - 16 # + 2 -12#
250

200

302 -12 # RADIALLY @140 C/C AT TOP 3 - 16 #


16

3 - 16 # + 2 -12# B 3 - 16 # C 300 300 2450 LONG


0

250 2450 LONG

575
200
SECTION B-B SECTION C-C ℄ OF COLUMN ℄ OF TANK
9 - 8 # 2 LEGGED 9 - 8 # 2 LEGGED 5 - 8 # 2 LEGGED 9 - 8 # 2 LEGGED 9 - 8 # 2 LEGGED
STIRRUPS @ 115 C/C STIRRUPS @ 115 C/C STIRRUPS @ 160.03 C/C STIRRUPS @ 115 C/C STIRRUPS @ 115 C/C
302-12 # @ 140 C/C 920 920 800.17 920 920
R = 6515
170

MADE - UP LEVEL
450 2640.17 450

715 MM FILLING
302-12 # @ 140 C/C

L - SECTION OF BRACE
3872

3820

GL
3420

450 450
R = 5000
27 -12 # HOOPS @ 135 C/C
316 - 12 # @ 100 C/C RADIALLY.
CURTAIL ALTERNATE RADIAL BARS AT 1500
14 - 12 # HOOPS

2000
500
GRADE BEAM ( DETAILING WILL BE SAME AS BRACING) FROM INNER FACE OF BEAM IN MIDDLE

274 -12 #

250

550
10-10 # HOOPS
2692
7 - 16 # 20 - 10 # RINGS @ 75 C/C 100 MM
THICK P.C.C.
1500

1000 274 -12 # @150 C/C 300 MM THICK SAND/GANGA SAND/STONE DUST FILLING IN TWO LAYERS

1415
302-12 # @ 140 C/C 1377 21 - 12 # HOOPS
138
150

1675 550 2475 R = 2250


34 R = 6950
-1 10 # RADIALLY @ 130 C/C 4 - 12 # 2
274 - 12 # 6 23 - 12 # 2 - LEGGED STIRRUPS @ 125 C/C
# 10 # HOOPS @ 130 C/C 4-16 # HOOPS
135

H 4-16 #
0

21 -10 # HOOPS O
30

O HOOPS
PS
(1
7
O
1377

N
EA
R= 8546

700

700
4-12 #
C
H 12 # STR
FA
C
1183

E) 0
120

100
1600

245 -12 # @170 C/C 4-16 # HOOPS


4 - 16 # HOOPS+2 - 16 #,2550 LONG 550
4 - 16 # HOOPS +2 - 16 # 2450
245 -12 # @170 C/C (OVERLAP NEAR MID SPAM) 2
2550 2550
10 - 10 # HOOPS AT TOP
SECTION 2-2
700
200

214 - 10 # RADIALLY @ 140 C/C


350

500 R = 5000 PART L - SECTION OF FOUNDATION RING BEAM


R = 4750

SECTION OF TANK

NOTES: 0 FOR APPROVAL


170
1. ALL DIMENSIONS ARE IN MILLIMETERS, LEVELS ARE IN METERS.
52

1000 2. USE M30 GRADE OF CONCRETE FOR CONTAINER AND M25 FOR STAGING REV. DATE DESCRIPTION DESIGN DRAWN CHKD APPD
3. USE HYSD BARS FE 500 CONFORMING TO IS 1786-1985.
1377 138 10
00 4. CLEAR COVER TO REINFORCEMENT SHALL BE AS FOLLOWS: PROJECT:
150

UP
· CYLINDRICAL WALL 45MM CONSTRUCTION OF WATER SUPPLY SCHEME DISTRICT-GAZIPUR WITH RELEVANT
BRACE 300X500
· COLUMNS-45MM WORKS INCLUDING COMMISSIONING AND OPERATION AND MAINTENANCE
1ST FLIGHT · DOME - 45MM
0
30

· RING BEAMS- 45MM CLIENT:


19
450 Ø DIA COLUMNS
10 NOS. · BRACE - 30 MM
EXECUTIVE DIRECTOR
47
· STAIR CASE - 15MM State Water & Sanitation Mission
1377

· FOOTING -75MM AT BOTTOM & SIDES Namami Gange & Rural Water Supply Department
1487

21
03 -50MM AT TOP Government of Uttar Pradesh
RL = 2013
B1 5. WORKMANSHIP TO CONFIRM TO IS 456-2000 Lucknow, Uttar Pradesh - 226001
6. FABRICATION OF REINFORCEMENT SHALL BE AS PER SP-34
135

0
120 7. DISCREPANCY IN THE DRAWING IF ANY SHALL BE BROUGHT TO THE NOTICE OF CONTRACTOR:
ENGINEER VSA INFRA PROJECT PVT. LTD.
302-12 # @ 140 C/C
274 -12 # @150 C/C IN CHARGE BEFORE EXECUTION OF WORK.
20

1487 8. DO NOT SCALE THE DRAWING. SMC (JV)


0

2ND FLIGHT
9. BOTTOM RING BEAM SHOULD BE CAST MONOLITHIC WITH BOTTOM DOME
700

10. SBC OF SOIL CONSIDERED AS 8.00 T/M TO BE CONFIRMED BEFORE GOING AHEAD 10
388

274 - 12 # B2
BASIC WIND SPEED IS CONSIDERED AS 47 M/SEC.
CONSULTANT: MATSHUI ENGINEERING
RL = 4026 11. SEISMIC ZONE CONSIDERED AS IV.
500 B1
12. ALL LAPS SHALL BE STAGGERED AND LAP LENGTH SHALL BE 50 X DIA OF BAR SERVICES PVT. LTD.
RL
=
GROUND WATER TABLE IS CONSIDERED AS NIL
13
32 13. WATER LEVEL INDICATOR AND LIGHTENING CONDUCTOR SHALL BE PROVIDED AS PER
RL = 10065 5
3RD FLIGHT THE APPROVED SPECIFICATION
245 -12 # @170 C/C CONTAINER: TITLE:
214 - 10 # RADIALLY @ 140 C/C
B1 B1 5TH FLIGHT 1. HOOP BARS IN WOLLS. RING BEAM WHERE D IS DIAMETER OF BAR: TWICE THE LAP STRUCTURAL DRAWINGOF OVER HEAD TANK (550 KL-12 m STAGING)
RL = 6039 LENGTH
4TH FLIGHT RL = 8052
2. LAPS IN ALL CIRCULAR RODS IN CONTAINER PORTION SHALL BE SO STAGGERED THAT FOR WATER SUPPLY SCHEME AT ANDHUAN ZONE-1,GHAZIPUR BLOCK,
NOT MORE THAN 1/4 OF THE TOTAL RODS ARE LAPPED IN ONE PLACE GHAZIPUR DISTRICT,U.P.
3. CONTAINER PROPER SHOULD BE KEPT DAMP DURING CONSTRUCTION TO PREVENT
245 -12 # @170 C/C 6TH FLIGHT SHRINKAGE.
10 - 10 # HOOPS AT TOP
PLAN SHOWING STAIR - CASE ARRANGEMENT
DRG. NO : SCALE- REV- SIZE- SHEET- 1/2

VSAIPPL-SMC JV 42 of 83 JJM/U.P.
ANDHUAN ZONE-1,GHAZIPUR BLOCK,GHAZIPUR DISTRICT,U.P. 550_12

2940
1000 1490 450
2640

LIGHTNING CONDUCTOR
RL = 13325

250
B B
VENTILATOR

00
ISA 50X50X6 POST 00
11

15
OR RCC POST
RL = 17447 9 - 12 #
9 - 12 #
20 DIA G.I. PIPE RAILING 9 - 12 #
9 - 12 #
14
170 R = 6515 R = 6685 0
TH
6TH FLIGHT K
FIRST FIVE FLIGHTS HAVE 200 50
3420

11 RISERS -183 0 14 TREADS OF - 250


10 B1

217.3333
1 100
10 TRADES - 264 9 - 12 # 15 RISERS OF- 217.3333
9 - 12 #

3260
RL = 13325 6Ø RINGS
9 - 12 # @ 150 C/C

1000
B
264
8 # @ 150 C/C
1377

100 Ø

183

14
500

2013
140 THK

0T

200
4-8 #
700

6TH FLIGHT

HI
BOTTOM

K
RING BEAM

1623

00
15
9 - 12 #
DETAILS OF RCC RAILING POST
8 # @ 150 C/C OR ISA 50X50X6 POST
RL = 10065

B2
3433

1 1 00
11

3 4 9 - 12 # 1000
3 - 16 # 3 - 16 # 4 - 16 #
4 - 16 #
RL = 10065 8 # @ 150 C/C

110
250
MADE UP-GL 9 - 12 #

250
350
8 # STR.@ 100 C/C 8 # STR.
500

350
2ND BRACE 2-8# @ 100 C/C

650
B1 3 - 12 # 3 3 - 12 # 4 - 12 #
250 8 # STR.
8 # STR.@ 100 C/C
4 - 12 # 4 @ 100 C/C SECTION 4-4
SECTION 3 - 3
450 1000 1400 2600 400
BEAM B1
12000

REINFORCEMENT DETAILS FOR


3433

FIRST FIVE FLIGHTS


7-16 #
1 1
10/8 # RINGS
@ 75/190 C/C REINFORCEMENT DETAILS FOR 6TH FLIGHT AND BEAM - B2
500

1ST BRACE

200 250 5
250 1740
1200 BALCONY 6
1000

450
3433

3510 5
BEAM - B
6
1 1 SECTION 1 - 1
3-16 # 2940

250
RL = 0.00
B
MADE UP GL
RL = 13325
2255
500

GRADE BEAM
3-16 #

2500
300X500 8 # STR.@100 C/C 250

GL SECTION 5-5
715 MM FILLING
1200

150 8 # STR.
2000

@ 100 C/C
1000 1140 800
R=
600
700

700 3-16 # AT TOP


CUT-O 302-12 # @ 140 C/C 8 # @ 200 MESH
U
6TH F T FOR 3-16 # AT BOTTOM

250
L
300 MM THICK SAND/GANGA SAND/STONE DUST FILLING IN TWO LAYERS
2040X IGHT 274 - 12 # B

150
1000
100

4700 R=2250 21 -10 # HOOPS 250


R= 6950
SECTION 6-6
HALF SECTION HALF ELEVATION BALCONY

10 # HOOPS @ 140 C/C 3-16 #


3-16 # AT TOP
AT BO
10 # RADIALLY @ 140 C/C TTOM

PLAN AT BALCONY LEVEL


450 DIA COLUMNS
10 NOS.
SHOWING CUT OUT IN LANDING SLAB

BRACE 300X500 10 - 10 # HOOPS NOTES: 0 FOR APPROVAL


AT TOP
1. ALL DIMENSIONS ARE IN MILLIMETERS, LEVELS ARE IN METERS.
302 -12 # RADIALLY @140 C/C REV. DATE DESCRIPTION DESIGN DRAWN CHKD APPD
2. USE M30 GRADE OF CONCRETE FOR CONTAINER AND M25 FOR STAGING
PART PLAN OF TOP DOME REINFORCEMENT 3. USE HYSD BARS FE 500 CONFORMING TO IS 1786-1985.
4. CLEAR COVER TO REINFORCEMENT SHALL BE AS FOLLOWS: PROJECT:
· CYLINDRICAL WALL 45MM CONSTRUCTION OF WATER SUPPLY SCHEME DISTRICT-GAZIPUR WITH RELEVANT
· COLUMNS-45MM WORKS INCLUDING COMMISSIONING AND OPERATION AND MAINTENANCE
167 · DOME - 45MM
5 3 - 12 # BARS HAVE TO GO RING BEAMS- 45MM
550
ACROSS THE CROWN
· CLIENT: EXECUTIVE DIRECTOR
247
· BRACE - 30 MM State Water & Sanitation Mission
5 500 1200 · STAIR CASE - 15MM
Namami Gange & Rural Water Supply Department
36°

225 · FOOTING -75MM AT BOTTOM & SIDES


0 2640 -50MM AT TOP Government of Uttar Pradesh
5. WORKMANSHIP TO CONFIRM TO IS 456-2000 Lucknow, Uttar Pradesh - 226001
1635 6. FABRICATION OF REINFORCEMENT SHALL BE AS PER SP-34
7. DISCREPANCY IN THE DRAWING IF ANY SHALL BE BROUGHT TO THE NOTICE OF CONTRACTOR:
ENGINEER
VSA INFRA PROJECT PVT. LTD.
0

IN CHARGE BEFORE EXECUTION OF WORK.


309

8. DO NOT SCALE THE DRAWING. SMC (JV)


9. BOTTOM RING BEAM SHOULD BE CAST MONOLITHIC WITH BOTTOM DOME
10. SBC OF SOIL CONSIDERED AS 8.00 T/M TO BE CONFIRMED BEFORE GOING AHEAD 10
BASIC WIND SPEED IS CONSIDERED AS 47 M/SEC.
CONSULTANT: MATSHUI ENGINEERING
11. SEISMIC ZONE CONSIDERED AS IV.
12. ALL LAPS SHALL BE STAGGERED AND LAP LENGTH SHALL BE 50 X DIA OF BAR SERVICES PVT. LTD.
10 # HOOPS @ 130 C/C GROUND WATER TABLE IS CONSIDERED AS NIL
10 # RADIALLY @ 130 C/C 13. WATER LEVEL INDICATOR AND LIGHTENING CONDUCTOR SHALL BE PROVIDED AS PER
10 - 10 # HOOPS THE APPROVED SPECIFICATION
AT TOP CONTAINER: TITLE:
214 - 10 # RADIALLY @ 140 C/C 1. HOOP BARS IN WOLLS. RING BEAM WHERE D IS DIAMETER OF BAR: TWICE THE LAP STRUCTURAL DRAWINGOF OVER HEAD TANK (550 KL-12 m STAGING)
R = 6950 R= 5000 LENGTH FOR WATER SUPPLY SCHEME AT ANDHUAN ZONE-1,GHAZIPUR BLOCK,
2. LAPS IN ALL CIRCULAR RODS IN CONTAINER PORTION SHALL BE SO STAGGERED THAT
NOT MORE THAN 1/4 OF THE TOTAL RODS ARE LAPPED IN ONE PLACE GHAZIPUR DISTRICT,U.P.
3. CONTAINER PROPER SHOULD BE KEPT DAMP DURING CONSTRUCTION TO PREVENT
PART PLAN OF BOTTOM DOME REINFORCEMENT SHRINKAGE.
HALF FOUNDATION PLAN HALF PLAN AT BRACE LEVEL
DRG. NO : SCALE- REV- SIZE- SHEET- 2/2

VSAIPPL-SMC JV 43 of 83 JJM/U.P.