User manual

KNX Gateway for Tuya ZigBee_V2.0


BTMO-TY/00.1(2)
BTMO-TY/00.3(4)

KNX/EIB Home and Building Control System


Attentions
1. Please keep devices away from strong magnetic field, high temperature,

wet environment;

2. Do not fall the device to the ground or make them get hard impact;

3. Do not use wet cloth or volatile reagent to wipe the device;

4. Do not disassemble the devices.


Contents

Chapter 1 Summary -----------------------------------------------------------------------------------------------------1


Chapter 2 Technical Data -----------------------------------------------------------------------------------------------2
Chapter 3 Dimension and Structural Diagram ----------------------------------------------------------------------- 3
3.1 Dimension Diagram ----------------------------------------------------------------------------------------------3
3.2 Structural Diagram ---------------------------------------------------------------------------------------------- 3
Chapter 4Project Design and Programming --------------------------------------------------------------------------4
Chapter 5 Parameter setting description in the ETS ---------------------------------------------------------------- 6
5.1. Parameter window “General” ---------------------------------------------------------------------------------- 6
5.1.1. Parameter window “General setting” --------------------------------------------------------------------6
5.1.2. Parameter window “IP setting” -------------------------------------------------------------------------- 7
5.2. Parameter window “KNX Channel ” --------------------------------------------------------------------------- 8
5.2.1. Parameter window “General setting” --------------------------------------------------------------------8
5.2.2. Parameter window “KNX Channel setting” ------------------------------------------------------------- 9
5.2.3. Parameter window “Channel x”(x=1~150) ------------------------------------------------------------ 10
5.2.1.1. Parameter of basic function -----------------------------------------------------------------------12
5.2.1.2. Parameter of air condition -------------------------------------------------------------------------15
5.2.1.3. Parameter of room temperature unit -------------------------------------------------------------17
5.2.1.4. Parameter of ventilation system ------------------------------------------------------------------20
5.2.1.5. Parameter of audio control ------------------------------------------------------------------------ 23
5.2.1.6. Parameter of sensor function --------------------------------------------------------------------- 24
5.2.1.7. Parameter of current metering function --------------------------------------------------------- 27
5.2.1.8. Parameter of energy metering function ----------------------------------------------------------28
5.3. Parameter window “Zigbee Channel” ----------------------------------------------------------------------- 29
5.3.1. Parameter window “Zigbee Channel setting” ---------------------------------------------------------29
5.3.2. Parameter window “Channel x” (x=1~32) ------------------------------------------------------------- 30
5.4. Parameter window “Room temperature controller” ------------------------------------------------------- 34
5.4.1. Parameter window “RTC Channel setting” ------------------------------------------------------------ 34
5.4.2. Parameter window “RTC x”(x=1~10) ------------------------------------------------------------------ 34
5.4.1.1. Parameter window “Setpoint” ---------------------------------------------------------------------40
5.4.1.2. Parameter window “Heating/Cooling control” -------------------------------------------------- 42
5.4.1.3. Parameter window “Fan” -------------------------------------------------------------------------- 48
5.5. Parameter window “Ventilation controller” -----------------------------------------------------------------52
5.5.1. Parameter window “Control setting” ------------------------------------------------------------------ 52
5.6. Parameter window “Logic” ----------------------------------------------------------------------------------- 59
5.6.1. Parameter window “AND/OR/XOR” -------------------------------------------------------------------- 60
5.6.2. Parameter window “Gate forwarding” ----------------------------------------------------------------- 62
5.6.3. Parameter window “Threshold comparator” ----------------------------------------------------------63
5.6.4. Parameter window “Format convert” ------------------------------------------------------------------ 65
5.6.5. Parameter window “Gate function” -------------------------------------------------------------------- 66
5.6.6. Parameter window “Delay function” ------------------------------------------------------------------- 68
5.6.7. Parameter window “Staircase lighting” --------------------------------------------------------------- 68
Chapter 6 Description of Communication Object ------------------------------------------------------------------ 70
6.1. “General” Communication Object --------------------------------------------------------------------------- 70
6.2. “KNX Channel” Communication Object --------------------------------------------------------------------- 70
6.2.1. Communication Object of basic function ------------------------------------------------------------- 71
6.2.2. Communication Object of Air condition --------------------------------------------------------------- 78
6.2.3. Communication Object of Room temperature unit --------------------------------------------------- 80
6.2.4. Communication Object of Ventilation system -------------------------------------------------------- 84
6.2.5. Communication Object of Audio control -------------------------------------------------------------- 86
6.2.6. Communication Object of sensor function ------------------------------------------------------------89
6.2.7. Communication Object of current/energy metering ------------------------------------------------- 92
6.3. “Zigbee Channel” Communication Object ------------------------------------------------------------------ 93
6.4. “Room temperature controller” Communication Object -------------------------------------------------- 98
6.5. “Ventilation controller” Communication Object ---------------------------------------------------------- 101
6.6. “Logic” Communication Object -----------------------------------------------------------------------------102
6.6.1. “AND/OR/XOR” Communication Object --------------------------------------------------------------102
6.6.2. “Gate forwarding” Communication Object -----------------------------------------------------------103
6.6.3. “Threshold comparator” Communication Object --------------------------------------------------- 104
6.6.4. “Format convert” Communication Object ------------------------------------------------------------104
6.6.5. “Gate function” Communication Object --------------------------------------------------------------107
6.6.6. “Delay function” Communication Object -------------------------------------------------------------108
6.6.7. “Staircase lighting” Communication Object --------------------------------------------------------- 109
Chapter 7 UI Description for Tuya Smart APP -------------------------------------------------------------------- 110
7.1. Add device ---------------------------------------------------------------------------------------------------- 110
7.2. Device information -------------------------------------------------------------------------------------------114
7.3. Switch interface ----------------------------------------------------------------------------------------------115
7.4. Switch/Dimming interface ---------------------------------------------------------------------------------- 116
7.5. RGB Dimming interface ------------------------------------------------------------------------------------- 117
7.6. Curtain control interface ------------------------------------------------------------------------------------ 118
7.7. Value sender interface -------------------------------------------------------------------------------------- 120
7.8. KNX Scene switch interface -------------------------------------------------------------------------------- 121
7.9. Air condition interface ---------------------------------------------------------------------------------------123
7.10. Room temperature unit interface ------------------------------------------------------------------------- 124
7.11. Ventilation system interface ------------------------------------------------------------------------------ 125
7.12. Audio control interface ------------------------------------------------------------------------------------ 126
7.13. Sensor interface -------------------------------------------------------------------------------------------- 127
7.14. Current/Energy metering interface ----------------------------------------------------------------------- 129
7.15. Voice control command ----------------------------------------------------------------------------------- 130
Chapter 8 Tuya Zigbee Gateway Management System ---------------------------------------------------------- 138
8.1. Gateway information ---------------------------------------------------------------------------------------- 139
8.2. ZigBee device list -------------------------------------------------------------------------------------------- 140
8.3. ZigBee function list ------------------------------------------------------------------------------------------ 141
8.4. Linking the ZigBee device ---------------------------------------------------------------------------------- 142
Chapter 9 OTA for KNX Gateway for Tuya ZigBee ----------------------------------------------------------------146
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 1 Summary
KNX Gateway for Tuya ZigBee as the interface between KNX system and Tuya ZigBee system,

realizing the connection between the Tuya ZigBee ecosystem and the KNX system. Based on the

gateway, it can easily control the KNX devices with Tuya APP, and upload status information of KNX

devices to Tuya platform, for monitoring and managing the devices conveniently.

This manual provides detailed technical information about the KNX Gateway for Tuya ZigBee,

including installation and programming details, and explains how to use it in the practical examples.

After setting up KNX Gateway for Tuya ZigBee on the ETS, you can smartly manage the KNX and Zigbee

system products, add and use the devices through the supporting mobile APP——Tuya Smart.

KNX Gateway for Tuya ZigBee powered from KNX bus, and need a 12-30V DC auxiliary supply

voltage. It is available to assign the physical address and configure the parameters by engineering

design tools ETS with .knxprod ( support edition ETS5.7 or higher ).

The functions are summarized as followed:

 As a ZigBee Gateway function, it can connect to Tuya Cloud, and add ZigBee device of

Tuya ecosystem to the cloud

 Support uploading KNX devices to Tuya platform for management, to control KNX device

and display status

 Support KNX devices functions, including Switch, Dimming, Curtains, Scenes, Color and

Color temperature control, Audio control, HVAC control(Room temperature control, Air

conditioner and Ventilation system), multiple sensors(Air Quality,Temperature and

humidity, Brightness, Gas, I/O signal and etc.), and Current, Energy Metering display

 Logic functions

 Support bidirectional communication between ZigBee and KNX device(only for premium

version BTMO-TY/00.3(4))

1
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 2 Technical Data


Power Supply Bus voltage 21-30V DC, via the KNX bus

Bus current <4.5mA, 24V


<4mA, 30V
Bus consumption <120mW

Auxiliary Supply Voltage 12-30V DC

Current <60mA, 24V


<50mA, 30V
Consumption <1.5W

Connection KNX Bus connection terminal(Red/Black)

Auxiliary Supply Bus connection terminal(Yellow/White)

LAN RJ45 socket for 100 Mbit and 10 Mbit BaseT,


IEEE 802.3 networks
Antenna Rubber rod antenna or extension antenna (3m)

Wireless Network without barriers: >100m


communication Network with barriers: >10m ( Across two walls)
Operation and Connect button Long press 5s will disconnect gateway
display
Connect status LED On: connecting; Off: connected
Fast flashing: Tuya authorization code is
abnormal
(Unprogram)
LAN LED On: connected; Off: disconnected
Flashing: Data communication
Programming button Red on: assign physical address
and LED Green flashing: running normally
Temperature Operation – 5 °C ... 45 °C

Storage – 25 °C ... 55 °C

Transport – 25 °C ... 70 °C

Environment Humidity <93%, except dewing

Design Standard 35mm DIN rail installation

Dimension 36 x 90 x 64mm

Weight 0.15kg

2
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 3 Dimension and Structural Diagram

3.1 Dimension Diagram

3.2 Structural Diagram

①LAN connection ⑥Programming button


②Connect button ⑦Antenna interface
③Connect status LED ⑧Auxiliary supply connection terminal
④LAN LED ⑨KNX bus connection
⑤Programming LED

3
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 4Project Design and Programming


Maximum of Maximum Maximum
Application communication number of group number of
objects addresses associations
KNX Gateway for Tuya ZigBee/1.0

KNX Gateway for Tuya 3933 8000 8000


ZigBee,Premium/1.0

General function

General function includes device In operation setting and IP setting.

KNX channel function

Support to upload the KNX device to the Tuya platform for management, which to control the

device and display status. Up to support 150 devices. Each device can be customized its name with the

engineering design tools ETS, and has In operation setting to monitor whether the device is online and

upload to APP.

Top 100 device channels support the whole functions, including switch, dimming, curtain, scene

switch, color and color temperature (RGB, RGBW and color temperature), audio control, HVAC control

(Room temperature control, Air conditioner and Ventilation), multiple sensors (Air quality, humidity and

temperature, brightness, gas, I/O signal and etc.), and current, energy display.

The latter 50 device channels only support the functions, including switch, dimming, curtain, air

quality sensor and energy display.

Note: Request each device status when the gateway power on.

4
KNX/EIB KNX Gateway for Tuya ZigBee

Zigbee channel function (only for premium version BTMO-TY/00.3(4))

Support bidirectional communication between ZigBee and KNX device, for integrating Zigbee

devices into KNX system, up to 32 device data points, which can be set with name and MAC address

information on the ETS. Use the website (Tuya Zigbee Gateway Management System) to configure and

manger the linkage between Zigbee devices and KNX system.

Support to control the following Zigbee devices with the KNX system:

Sensor: Air quality sensor, Temperature and humidity sensor, Brightness sensor, Gas sensor, and

I/O signal (Switch, Boolean, Alarm, Occupancy sensor,Window/door sensor);

Zigbee lamp: lamp, dimmable lamp, RGB bulb/strip, color temperature light and RGBCW bulb;

Electric curtain.

Room temperature controller

Up to support 10 room temperature controllers. Mainly used to control the room temperature,

Automatically and optimally cooling/heating control according to the room use or the occupants needs.

Support to manual switch to heating/cooling control, optionally three fan speeds and the auto fan

speed, 4 operation modes: comfort, standby, economy and protection mode.

The temperature setpoint value supports the relative setting method, and is adjustable range

setting. Support 2 points and PI control.

Ventilation controller

Support 1 ventilation controller, and fan speed can be linked to PM2.5/CO2/VOC, optionally output

types of 1bit of 1byte.

Logic function

Up to support 8 channels of logic, each channel up to support 8 inputs and 1 logic result.

Logic function support functions, including AND, OR, XOR, Gate forwarding, Threshold comparator,

Format convert, Gate function, Delay function and Staircase lighting.

5
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 5 Parameter setting description in the ETS


5.1.Parameter window “General”
5.1.1. Parameter window “General setting”

Fig.5.1.1 “General setting” Parameter window

Parameter “Device ID”

This parameter is for setting the device ID. Options: 0…65535

Parameter “Device name”

This parameter is for setting the device name. Up to input 32 characters.

Parameter “Send delay after power on [0..15]s”

This parameter is for setting the delay time to send to bus after the gateway power on. Options:
0..15

The setting dose not contain the gateway initialization time, and bus telegrams received during
delay time will be recorded.

Parameter “Send cycle of “In operation”telegram [1...240s, 0 = inactive]”

This parameter is for setting the time interval when this device cycle send telegrams through the
bus to indicate this module in normal operation. When set to “0”, the object “in operation” will not send
a telegram. If the setting is not “0”, the object “In operation” will send a telegram according to the set
period time with logic “1” to the bus. Options: 0...240s, 0= inactive

As to reduce the bus load as much as possible, the maximum time interval should be selected
according to actual needs.

6
KNX/EIB KNX Gateway for Tuya ZigBee

5.1.2. Parameter window “IP setting”

Fig.5.1.2 “IP setting” Parameter window

Parameter “IP assignment”

This parameter is for setting the assignment of IP address. Options:


DHCP
Fixed
Fixed: the assignment of IP address is fixed, can be assigned address for device via the
parameters as follow.
DHCP: the parameters as follow are not visible when DHCP enabled, and no need to configure.
——Parameter “IP address (device)”

This parameter is for setting the IP address of device, and the IP address must be unique in the
LAN, otherwise causing a conflict between IP.
Enter the address in IPv4 format, for example: 192.168.1.10
Options: 0-255.0-255.0-255.0-255
——Parameter “Default Gateway”

This parameter is for setting the default gateway. That is the default gateway of network segment
which the device connects to.
Enter the address in IPv4 format, for example: 192.168.1.1
Options: 0-255.0-255.0-255.0-255
——Parameter “Subnet Mask”

This parameter is for setting the subnet mask. That is the subnet mask of network segment which
the device connects to.
Enter the address in IPv4 format, for example: 255.255.255.0
Options: 0-255.0-255.0-255.0-255
——Parameter “DNS server”

This parameter is for setting the DNS server of device.


Use string with IPv4 to input address, for example: 192.168.1.1
Options: 0-255.0-255.0-255.0-255

7
KNX/EIB KNX Gateway for Tuya ZigBee

5.2.Parameter window “KNX Channel ”


5.2.1. Parameter window “General setting”

Fig.5.2.1 “General setting” Parameter window

Parameter “Status object read request after restart”

This parameter is for setting whether to send read request telegram of status after restart device.

Parameter “Send request delay between status objects”

This parameter is visible when previous parameter is enabled. Set the interval time for sending
between request telegrams when power on. Options:

50ms

100ms

200ms

Device online status request setting for common x


Parameter “Time period request for common x [0..255,0=inactive] min”(x=1~10)

This parameter is for setting the read request period to send to query the online status of the
common device, 0 is not enable query function. Options: 0..255

The function is used to query the online status of the KNX device. Requests begin after the
gateway power-up send delay time complete.

8
KNX/EIB KNX Gateway for Tuya ZigBee

5.2.2. Parameter window “KNX Channel setting”

Fig.5.2.2(1) “KNX Channel setting” Parameter window

Fig.5.2.2(2) “Channel 1-10” Parameter window

Parameter “Channel 1-10/11-20/21-30/...”

This parameter is for setting the enable KNX device. Display 10 KNX channels per page when

enabled. Up to support 150 channels.

Parameter “Channel 1/2/3/...”

This parameter is for setting the KNX device setting. Display corresponding window when enabled.

9
KNX/EIB KNX Gateway for Tuya ZigBee

5.2.3. Parameter window “Channel x”(x=1~150)

Fig.5.2.3 “Channel 1” Parameter window

Parameters as follow is general setting parameters for KNX device type. Later chapters will not be
repeated.

Parameter “Device type”

This parameter is for setting the device type of KNX channel. Options:

Switch Ventilation system


Switch/Dimming Audio control
RGB dimming Audio control(with on/off)
RGBW dimming Air quality sensor
Color temperature CO2 sensor
Curtain step/move PM2.5 sensor
Roller blind step/move VOC sensor
Curtain position Presence sensor
Roller blind position Motion sensor
Venetian blind position and slat Brightness sensor
Value sender I/O signal
Scene switch Current metering
Air conditioner Energy metering
Air conditioner(with swing)
Room temperature unit
Room temperature unit(with operation mode)
Room temperature unit(with operation mode & fan
speed)

Note: Channel 1~100 support all of the above function options, but channel 101~150 only
support the functions as follow:

Switch

Switch/Dimming

Curtain step/move

Roller blind step/move

Air quality sensor


Energy metering

10
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Description (max 30char.)”

This parameter is for setting the name description for current channel device, up to input 30

characters.

Parameter “Device online status reference by”

This parameter is for setting the reference type sending read request to KNX device, you can select
request for individual or common device, and optionally 10 common device requests. Options:
Common 1
...
Common 10
Individual
Always online

When select “Common ...”, common device request, apply to the device with multiple circuits. For
example, multiple channels of gateway may be multiple circuits that control the same KNX device, so
each channel can share one request.
When select “Individual”, apply to a device only is controlled by gateway single channel.
When select “Always online”, apply to the KNX device without heartbeat pack, especially scene.
That is, once configure the device, it will always online.
——Parameter “Time period for request [1..255] min”

This parameter is visible when “Individual” is selected, set the time period for the online status
request of single device. Options: 1..255

11
KNX/EIB KNX Gateway for Tuya ZigBee

5.2.1.1. Parameter of basic function

This chapter explains the basic functions parameters of KNX channel, including switch, dimming,
curtain, color, color temperature, value sender and KNX scene switch.

Parameter setting of “Switch”

Parameter setting of “Switch/Dimming”

Parameter setting of curtain

Parameter setting of “RGB dimming”

Parameter setting of “RGBW dimming”

12
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter setting of “Color temperature”

Parameter setting of “Value sender”

Parameter setting of “Scene switch”


Fig.5.2.1.1 Parameter setting of basic function

Parameter “Min. brightness value [0..50]%”

Parameter “Max. brightness value [51..100]%”

These two parameters are visible when device type is selected “Switch/Dimming”. Set the upper
and lower limit threshold value of brightness.

The lower limit threshold value options: 0..50; the upper limit threshold value options: 51..100

Parameter “Object datatype”

This parameter is visible when device type is selected “RGB dimming” or “RGBW dimming”. Set the
object datatype of RGB or RGBW dimming.

Suitable for RGB type:

1x3byte

3x1byte

13
KNX/EIB KNX Gateway for Tuya ZigBee

Suitable for RGBW type:

1x6byte

4x1byte

Parameter “Min. color temperature [2000..7000]K”

Parameter “Max. color temperature [2000..7000]K”

These two parameters are visible when device type is selected “Color temperature”. Set the upper
and lower limit threshold value of color temperature. Options: 2000..7000

When the minimum value and maximum value are set incorrect, The selected range is the whole
range, for example the minimum value is larger than the maximum value. There is only one value when
equal.

For colour temperature, the Min. value must less than the Max., if not, if not, they can not be

modified on ETS, and display red box warning, as shown as follow:

Parameter “Output object datatype for trigger”

This parameter is visible when device type is selected “Value sender”. Set telegram type for
sending to KNX bus when trigger calling command on the APP. Options:

1bit[On/Off]

2bit[0..3]

1byte[0..100%]

1byte[0..255]

1byte[scene control]

2byte[Float]

2byte[0..65535]

Parameter “Output value”

This parameter is visible when device type is selected “Value sender”, and corresponding datatype
is selected. Set the telegram value for sending to KNX bus when trigger calling command on the APP.
Options are according to the datatype:

OFF ON(1bit) / 0..3(2bit) / 0..100(1byte) / 0..255(1byte) / 1..64(1byte) /

-671 088.64..670 760.96(2byte) / 0..65535(2byte)

14
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Trigger scene No. from KNX”

This parameter is visible when device type is selected “Scene switch”. Set the scene calling
command of KNX system to receive. Options:1..64

5.2.1.2. Parameter of air condition

This chapter explains the air condition function of KNX channel, including the basic and air

conditioning control with swing. Parameters as follow are visible when “Air conditioner” or “Air

conditioner(with swing)” is selected.

Fig.5.2.1.2(1) Parameter setting of air condition function

15
KNX/EIB KNX Gateway for Tuya ZigBee

Fig.5.2.1.2(2) Parameter setting of air condition function

Parameter “Time period for request room temperature sensor [0...255]min”

This parameter is for setting the time period for read request room temperature sensor. Options:
0..255

Send read request as default when the device voltage recovery.

Parameter “Min./Max. setpoint temperature [16..32]°C”

These two parameters are for setting the adjustable range of the setpoint temperature. If the
setpoint temperature beyond the limited range, the will output the limited temperature. Options:

16°C

17°C

...

32°C

For setpoint temperature, the Min. value must less than the Max., if not, it can not be modified on
ETS.

Control mode setting


Parameter “Auto/Heating/Cooling/Fan/Dehumidification mode”

Corresponding mode setting is visible when these parameters are enabled.

——Parameter “Output value for auto/heating/cooling/fan/dehumidification [0..255]”

These parameters are visible when the modes are enabled. Set the output value for switching to
each mode.

Options:0..255

16
KNX/EIB KNX Gateway for Tuya ZigBee

——Parameter “Status value for auto/heating/cooling/fan/dehumidification [0..255]”

These parameters are visible when the modes are enabled. Set the status feedback value of each
mode.

Options:0..255

Parameter “Object datatype of 1byte fan speed”

This parameter is for setting the object datatype of 1byte fan speed. Options:

Fan stage (DPT 5.100)

Percentage (DPT 5.001)

Output value for fan speed

——Parameter “Output value for fan speed auto/low/medium/high”

These parameters are for setting the output value for switching to each fan speed, support 4 fan
speeds: auto, low, medium, high. Options are according to the object datatype of previous parameter:
0..255/0..100

Status feedback for fan speed

——Parameter “Status value for fan speed auto/low/medium/high”

These parameters are for setting the status feedback value of each fan speed, support 4 fan
speeds: auto, low, medium, high. Options are according to the object datatype of previous parameter:
0..255/0..100

Note: the out value and status value must meet the condition low<medium<high, if not, they can
not be configured on ETS, and display red box warning(Only applicable to BTMO-TY/00.1(2)), as
shown as follow:

5.2.1.3. Parameter of room temperature unit

This chapter explains the room temperature unit function of KNX channel, including the basic,
control with control mode, and with fan speed. Parameters as follow are visible when “Room
temperature unit”, “Room temperature unit(with operation mode)” or “Room temperature unit(with
operation mode & fan speed)” is selected.

17
KNX/EIB KNX Gateway for Tuya ZigBee

Fig.5.2.1.3 Parameter setting of room temperature unit

Parameter “Time period for request room temperature sensor [0...255]min”

This parameter is for setting the time period for read request room temperature sensor. Options:
0..255

Send read request as default when the device voltage recovery.

Parameter “Min./Max. setpoint temperature [5..40]°C”

These two parameters are for setting the adjustable range of the setpoint temperature. If the
setpoint temperature beyond the limited range, the will output the limited temperature. Options:

5°C

6°C

...

40°C

18
KNX/EIB KNX Gateway for Tuya ZigBee

For setpoint temperature, the Min. value must less than the Max., if not, it can not be modified on
ETS.

Parameter “Control mode”

This parameter is for setting temperature control mode, support 3 types: heating, cooling and
heating/cooling.

Options:

Heating

Cooling

Heating and Cooling

Fan speed setting


This setting is visible when “Room temperature unit(with operation mode & fan speed)”
is selected
Parameter “Object datatype of 1byte fan speed”

This parameter is for setting the object datatype of 1byte fan speed. Options:

Fan stage (DPT 5.100)

Percentage (DPT 5.001)

Output value for fan speed

——Parameter “Output value for fan speed low/medium/high”

These parameters are for setting the output value for switching to each fan speed, support 3 fan
speeds: low, medium, high. Options are according to the object datatype of previous parameter:
0..255/0..100

Status feedback for fan speed

——Parameter “Status value for fan speed low/medium/high”

These parameters are for setting the status feedback value of each fan speed, support 3 fan
speeds: low, medium, high. Options are according to the object datatype of previous parameter:
0..255/0..100

Note: the out value and status value must meet the condition low<medium<high, if not, they can
not be configured on ETS, and display red box warning, as shown as follow:

19
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “1 bit object function for fan speed”

This parameter is for setting whether to enable the object datatype of 1bit fan speed. When
enabled, the 1 bit object of each fan speed is visible. When three objects value is 0, turn off the fan.

——Parameter “1 bit object for fan speed off ”

This parameter is visible when previous parameter is enabled. Set whether to enable the object

“1bit fan speed off” to visible.

5.2.1.4. Parameter of ventilation system

This chapter explains the ventilation system function of KNX channel. Parameters as follow are
visible when “Ventilation system” is selected.

Fig.5.2.1.4 Parameter setting of ventilation system

20
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Default fan speed after ventilation on”

This parameter is for setting the initial fan speed after ventilation on. Switch status of ventilation is
read from bus after download or reset, and default as off if can not read. Options:
Low
Medium
High
Last status
Parameter “Data type of fan speed”

This parameter is for setting the data type of ventilation fan speed. Options:

1bit

1byte

——Parameter “Object datatype of 1byte fan speed”

This parameter is visible when fan speed datatype is selected “1byte”. Set the datatype of 1byte
fan speed object. Options:

Fan stage (DPT 5.100)

Percentage (DPT 5.001)

Output value for fan speed


——Parameter “Output value for fan speed low/medium/high”

These parameters are for setting the output value for switching to each fan speed, support 3 fan
speeds: low, medium, high. Value=0 is fan speed off. Options are according to the object datatype of
previous parameter: 0..255/0..100

Status feedback for fan speed


——Parameter “Status value for fan speed low/medium/high”

These parameters are for setting the status feedback value of each fan speed, support 3 fan
speeds: low, medium, high. Value=0 is fan speed off. Options are according to the object datatype of
previous parameter: 0..255/0..100

Note: the out value and status value must meet the condition low<medium<high, if not, they can
not be configured on ETS, and display red box warning, as shown as follow:

21
KNX/EIB KNX Gateway for Tuya ZigBee

——Parameter “Object value of fan speed off/low/medium/high”

This parameter is visible when fan speed datatype is selected “1bit”. Set the control value for
switching to each fan speed and the status feedback value. support 4 fan speeds: off, low, medium,
high. Device will be update the fan speed display according to the feedback value. Options:

Low=0,Medium=0,High=0

Low=1,Medium=0,High=0

Low=0,Medium=1,High=0

Low=1,Medium=1,High=0

Low=0,Medium=0,High=1

Low=1,Medium=0,High=1

Low=0,Medium=1,High=1

Low=1,Medium=1,High=1

——Parameter “Delay between fan speed switch [0..100]*50ms ”

This parameter is visible when fan speed datatype is selected “1bit”. Set the delay time between
fan speeds switchover. Options: 0..100

Turn off fan speed before switch the fan speed, and turn on it after the delay time. When delay time
is set as 0, it will not turn off first then turn on, but switch to next fan speed directly.

22
KNX/EIB KNX Gateway for Tuya ZigBee

5.2.1.5. Parameter of audio control

This chapter explains the audio control function of KNX channel, including the basic and audio
control with power on/off. Parameters as follow are visible when “Audio control” or “Audio control(with
on/off)” is selected.

Fig.5.2.1.5 Parameter setting of audio control

Parameter “Object datatype of absolute volume”

This parameter is for setting the datatype of audio control object. Options:

Percentage (DPT 5.001)

Percentage (DPT 5.004)

Output value for play mode

——Parameter “Output value for play in single cycle/order/random”

These parameters are for setting the control value of each mode, including single

cycle/order/random play.

Options: 0..255

Status feedback for play mode

——Parameter “Status value for for play in single cycle/order/random”

These parameters are for setting the status value of each mode, including single

cycle/order/random play. Device will be update the play mode display according to the feedback

value. Options: 0..255

23
KNX/EIB KNX Gateway for Tuya ZigBee

5.2.1.6. Parameter of sensor function

This chapter explains the sensor function of KNX channel, including air quality sensor, presence

sensor, motion sensor, brightness sensor, I/O sensor and etc.

Parameter setting of “Air quality sensor”

Parameter setting of “CO2 sensor”

Parameter setting of “PM2.5 sensor”

24
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter setting of “VOC sensor”

Parameter setting of “Presence sensor”

Parameter setting of “Motion sensor”

Parameter setting of “Brightness sensor”

Parameter setting of “I/O signal”


Fig.5.2.1.6 Parameter setting of sensor function

25
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Object datatype of PM2.5”

This parameter is visible when device type is selected “Air quality sensor” or “PM2.5 sensor”. Set

the object datatype of PM2.5. Options:

Value in ug/m3 (DPT 7.001)

Float value in ug/m3 (DPT 9.030)

Parameter “Object datatype of PM10”

This parameter is visible when device type is selected “Air quality sensor”. Set the object datatype
of PM10.

Options:

Value in ug/m3 (DPT 7.001)

Float value in ug/m3 (DPT 9.030)

Parameter “Object datatype of VOC”

This parameter is visible when device type is selected “Air quality sensor” or “VOC sensor”. Set the

object datatype of VOC. Options:

Value in ug/m3 (DPT 7.001)

Float value in ug/m3 (DPT 9.030)

Parameter “Object datatype of CO2”

This parameter is visible when device type is selected “Air quality sensor” or “CO2 sensor”. Set the
object datatype of CO2. Options:

Value in ppm (DPT 7.001)

Float value in ppm (DPT 9.008)

Parameter “Object datatype of brightness(lux)”

This parameter is visible when device type is selected “Presence sensor” or “Brightness sensor”.
Set the object datatype of brightness. Options:
Value in lux (DPT 7.013)
Float value in lux (DPT 9.004)

26
KNX/EIB KNX Gateway for Tuya ZigBee

5.2.1.7. Parameter of current metering function

This chapter explains the current metering function of KNX channel. Parameters as follow are
visible when device type is selected “Current metering”.

Fig.5.2.1.7 Parameter setting of current metering function

Parameter “Object datatype of current”

This parameter is for setting the object datatype of current. Options:

Value in mA (DPT 7.012)

Float value in mA (DPT 9.021)

Float value in A (DPT 14.019)

Parameter “Object datatype of power”

This parameter is for setting the object datatype of power. Options:


Float value in kW (DPT 9.024)
Float value in W (DPT 14.056)

27
KNX/EIB KNX Gateway for Tuya ZigBee

5.2.1.8. Parameter of energy metering function

This chapter explains the energy metering function of KNX channel. Parameters as follow are
visible when device type is selected “Energy metering”.

Fig.5.2.1.8 Parameter setting of energy metering function

Parameter “Object datatype of current”

This parameter is for setting the object datatype of current. Options:

Value in mA (DPT 7.012)

Float value in mA (DPT 9.021)

Float value in A (DPT 14.019)

Parameter “Object datatype of voltage”

This parameter is for setting the object datatype of voltage. Options:

Float value in mV (DPT 9.020)

Float value in V (DPT 14.027)

Parameter “Object datatype of power”

This parameter is for setting the object datatype of power. Options:

Float value in kW (DPT 9.024)

Float value in W (DPT 14.056)

Parameter “Object datatype of energy”

This parameter is for setting the object datatype of energy. Options:

Value in Wh (DPT 13.010)

Value in kWh (DPT 13.013)

28
KNX/EIB KNX Gateway for Tuya ZigBee

5.3.Parameter window “Zigbee Channel”

5.3.1. Parameter window “Zigbee Channel setting”

Fig.5.3.1 “Zigbee Channel setting” Parameter window

Parameter “Channel 1/2/3/...”

This parameter is for setting the Zigbee device setting. Display corresponding window when

enabled. Up to support 32 channels.

Note: Zigbee Channel function only applies to the premium version BTMO-TY/00.3(4).

29
KNX/EIB KNX Gateway for Tuya ZigBee

5.3.2. Parameter window “Channel x” (x=1~32)

30
KNX/EIB KNX Gateway for Tuya ZigBee

Fig.5.3.2 “Channel setting” Parameter window

Parameter “Description (max 24char.)”

This parameter is for setting the name description for current channel device, up to input 24

characters.

Parameter “Preset Mac address of zigbee device”

This parameter is for presetting MAC address of the current channel.

Parameter “Device type”

This parameter is for setting the device type of the Zigbee channel. Options:

Air quality sensor

Temperature and humidity sensor

Brightness sensor

Gas sensor

I/O signal

Switch

Switch/Dimming

RGB dimming

Color temperature

RGBCW

Curtain position

Temperature, humidity and brightness sensor

Parameter “Object datatype of VOC”

This parameter is visible when “Air quality sensor” is selected. Set the object datatype of VOC.

Options:

Value in ug/m3 (DPT 7.001)

Float value in ug/m3 (DPT 9.030)

31
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Object datatype of CO2”

This parameter is visible when “Air quality sensor” is selected. Set the object datatype of CO2.

Options:

Value in ppm (DPT 7.001)

Float value in ppm (DPT 9.008)

Parameter “Object datatype of formaldehyde”

This parameter is visible when “Air quality sensor” is selected. Set the object datatype of

formaldehyde.

Options:

Value in ppm (DPT 7.001)

Float value in ppm (DPT 9.008)

Parameter “Object datatype of brightness(lux)”

This parameter is visible when “Brightness sensor” or “Temperature, humidity and brightness

sensor” is selected. Set the object datatype of brightness. Options:

Value in lux (DPT 7.013)

Float value in lux (DPT 9.004)

Parameter “Object datatype of gas concentration”

This parameter is visible when “Gas sensor” is selected. Set the object datatype of gas

concentration.

Options:

Value in ug/m3 (DPT 7.001)

Float value in ppm (DPT 9.008)

Float value in ug/m3 (DPT 9.030)

Parameter “Object datatype of I/O signal”

This parameter is visible when “I/O signal” is selected. Set the object datatype of I/O signal.

Options:

Switch (DPT 1.001)

Boolean (DPT 1.002)

32
KNX/EIB KNX Gateway for Tuya ZigBee

Alarm (DPT 1.005)

Occupancy (DPT 1.018)

Window/door (DPT 1.019)

Parameter “Number of output”

This parameter is visible when “Switch” or “Curtain position” is selected. Set the output channel of

Switch or Curtain.

Options for switch output: 1 / 2 / 3

Options for curtain output: 1 / 2

Parameter “Min. color temperature [2000..7000]K”

Parameter “Max. color temperature [2000..7000]K”

These two parameters are visible when “Color temperature” or “RGBCW” is selected. Set the upper

and lower limit threshold value of color temperature. Options: 2000..7000

When the minimum value and maximum value are set incorrect, The selected range is the whole

range, for example the minimum value is larger than the maximum value. There is only one value when

equal.

For colour temperature, the Min. value must less than the Max., if not, if not, they can not be

modified on ETS, and display red box warning, as shown as follow:

33
KNX/EIB KNX Gateway for Tuya ZigBee

5.4. Parameter window “Room temperature controller”

5.4.1. Parameter window “RTC Channel setting”

Fig.5.4.1 “RTC Channel setting” Parameter window

Parameter “Room temperature controller 1/2/3/...”

This parameter is for setting whether to enable the setting interface of RTC device, display

corresponding interface. Up to enable 10 channels.

5.4.2. Parameter window “RTC x”(x=1~10)

Fig.5.4.2(1) “RTC 1” parameter window

34
KNX/EIB KNX Gateway for Tuya ZigBee

Fig.5.4.2(2) “RTC 1” parameter window

Parameter “Time period for request room temperature sensor [0...255]min”

This parameter is for setting the time period for read request external temperature sensor. Send
read request to external temperature sensor after the device voltage recovery or finish programming.
Options: 0..255

Parameter “Control value after temp. error[0..100]% (if 2-point control, set value '0'=0, set value

'>0'=1)”

This parameter is for setting the control value when temperature error occur. Options: 0..100

If 2-Point control, then the parameter value is 0, as well as the control value; if the parameter value
is more than 0, then the control value will be 1.

Parameter “Room temperature control mode”

This parameter is for setting RTC control mode, support 3 types: heating, cooling and
heating/cooling.
Options:
Heating
Cooling
Heating and Cooling
Heating and Cooling: heating and cooling are available. At the same time, four parameters as
follow are visible.
——Parameter “Heating/Cooling switchover”

This parameter is for setting the switchover way of Heating/Cooling. Options:

Via object

Automatic changeover

——Parameter “Heating/Cooling status after download”

This parameter is for setting the heating/cooling control mode of device after download.

Options:

35
KNX/EIB KNX Gateway for Tuya ZigBee

Heating

Cooling

——Parameter “Heating/Cooling status after power on”

This parameter is for setting the heating/cooling control mode of device after voltage recovery.
Options:

Heating

Cooling

As before power off

As before voltage failure: When the device is reset after power on, the control mode will recover as
before voltage failure or restart. If it is the first time the device is used or a newly enabled function page,
the control mode after the device is started is in an uncertain state, and it needs to be manually
selected at this time.

——Parameter “Room temperature control system”

This parameter is for setting the type of RTC control system, that is, pipe types of fan coil water
inlet/outlet. Options:

2 pipes system

4 pipes system

2 pipes system: Shares an inlet and outlet pipe for heating and cooling, that is, both hot and cold water
are controlled by a valve.

4 pipes system: Has its own inlet and outlet pipes for heating and cooling, and two valves are needed to
control the entry and exit of hot water and cold water respectively.

Parameter “Operation mode”

This parameter is for setting whether to enable RTC operation mode. Options:

Disable

Enable

When enable, support 4 modes: comfort, standby, economy and frost/heat protection. Support
datatype of 1bit and 1byte, and preset a operation mode when download and voltage recovery.

Four parameters as follow are visible when RTC operation mode enabled.
——Parameter “Controller status after download”

This parameter is for setting the operation mode after download. Options:

Standby mode

Comfort mode

Economy mode

36
KNX/EIB KNX Gateway for Tuya ZigBee

——Parameter “Controller status after power on”

This parameter is for setting the operation mode after voltage recovery. Options:

Standby mode

Comfort mode

Economy mode

Frost/heat protection

As before power off

——Parameter “1 bit object function for operation mode”

This parameter is for setting whether to enable 1 bit objects of operation mode are visible. Options:

Disable

Enable

——Parameter “1 bit object for standby mode”

This parameter is visible when previous parameter enabled. Set whether to enable 1 bit object of
standby mode is visible. Options:

Disable

Enable

Three parameters as follow are visible when RTC operation mode disabled.
——Parameter “ Initial setpoint temperature (°C)”

This parameter is for setting the initial value of setpoint temperature. Options:

10.0

10.5

...

35.0

When initial setpoint temperature is less than the min. setpoint temperature, display following
warning:

When initial setpoint temperature is greater than the max. setpoint temperature, display following

warning:

37
KNX/EIB KNX Gateway for Tuya ZigBee

Automatic H/C mode changeover dead zone

——Parameter “ Upper/Lower dead zone”

These two parameters are visible when control mode “Heating and Cooling” is selected, and
“Automatic changeover” is selected. Setting the dead zone range of auto switchover heating/cooling.
Options:

0.5°C

1.0°C

...

10°C

Under heating control, when the actual temperature(T) greater than or equal to the setpoint
temperature + the upper dead zone, then mode heating switch to cooling;

Under cooling control, when the actual temperature(T) less than or equal to the setpoint
temperature + the upper dead zone, then mode cooling switch to heating.

Parameter “Fan speed auto.control function”

This parameter is for setting whether to enable fan auto control interface is visible. Options:

Disable

Enable

Parameter “Window contact input function”

This parameter is visible when operation mode enabled. Set whether to link to window contact

status.

Options:

Disable

Enable

——Parameter “Delay for window contact [0..65535]s”

This parameter is visible when operation mode and window contact input function are enabled. Set

the delay time to window contact detection. That is, when receive a telegram “window open”, the

controller will regard that as a valid signal and execute the behaviour after this delay time. Options:

0..65535

——Parameter “Controller mode for open window”

This parameter is visible when operation mode and window contact input function are enabled. If

window status is open, perform corresponding operation according to configuration. Options:

38
KNX/EIB KNX Gateway for Tuya ZigBee

Economy mode

Frost/heat protection

Other control telegram receiving will be record during window is open and performed after

receiving the telegram “Close window”. If there is no telegram receiving when window is open, keep the

current mode.

Parameter “Bus presence detector function”

This parameter is visible when operation mode enabled. Set whether to link to bus presence

detector status. Options:

Disable

Enable

If presence is detected, enter the comfort mode, and it will be restored to original mode after

leaving. If there is a telegram/manual operation to adjust the mode during the period, the telegram is

logged in the background, and it will be exited comfort mode and restored to the mode after leaving. If

there is no telegram receiving during timing, return to original mode. (If receive the presence status

cyclically, comfort mode can not be re-triggered, and only can be after leaving.)

Parameter “Min./Max. setpoint temperature [5..40]°C”

These parameters are visible when operation mode disabled. Set to limit the adjustable range of

the setpoint temperature. If the setpoint temperature beyond the limited range, the will output the

limited temperature. Options:

5°C

6°C

...

40°C

These parameters are display below the parameters settings interface “Setpoint” when enable

operation mode.
For setpoint temperature, the Min. value must less than the Max., if not, it can not be modified on
ETS.

39
KNX/EIB KNX Gateway for Tuya ZigBee

5.4.1.1. Parameter window “Setpoint”

Fig.5.4.1.1 “Setpoint” parameter window

Parameters of this window are visible when RTC operation mode enabled, display according to

control mode. The temperature setpoint value uses the way of absolute adjustment.

Parameter “Setpoint temperature in comfort mode [5...40]°C”

Parameter “Setpoint temperature in standby mode [5...40]°C”

Parameter “Setpoint temperature in economy mode [5...40]°C”

Parameter “Setpoint temperature in frost protection mode [5...40]°C”(for heating)

Parameter “Setpoint temperature in heat protection mode [5...40]°C”(for cooling)

These parameters are for setting the temperature setpoint value of each mode. Options:

5°C

6°C

...

40°C

40
KNX/EIB KNX Gateway for Tuya ZigBee

When “Heating and Cooling” is selected, whether it is manual changeover, bus changeover or

automatic changeover, the heating setpoint value must be less than or equal to the cooling of the

same operation mode, if not, it can not be configured on ETS.

1.When the ambient temperature is higher than the setpoint temperature of current mode, it is

changed to cooling mode; When the ambient temperature is lower than the setpoint temperature

of current mode, it is changed to heating mode.

2.In the same operation mode, the setpoint temperature difference between cooling and

heating remains constant, whether it is written on the bus or adjusted on the panel. That is, when

adjust the setpoint temperature, it need to update cooling and heating setpoint temperature of

current operation mode at the same time.

3.When the bus is received setpoint temperature, it is still necessary to limit the value

according to the high and low thresholds, that is heating and cooling temperature neither can not

be lower than the min., or can not be higher than the max.. If parameters configuration of ETS is

not met the condition, it will be noted warnings:

When the setpoint temperature of comfort/standby/economy mode is less than the min. setpoint

temperature, display following warning:

When the setpoint temperature of comfort/standby/economy mode is greater than the max.

setpoint temperature, display following warning:

Note: for protection mode, the setpoint temperature is only configured via ETS, and not limited

with the min./max. value. When the received setpoint value from bus is different from the ETS

configuration, the value is not updated and returned to the current setpoint temperature, to update

synchronously to other devices on the bus.

41
KNX/EIB KNX Gateway for Tuya ZigBee

5.4.1.2. Parameter window “Heating/Cooling control”

Parameter setting of “Switching on/off(use 2-point control)”

Parameter setting of “Switching PWM(use PI control)”

Parameter setting of “Continuous control(use PI control)”


Fig.5.4.1.2(1) “Heating/Cooling control” parameter window

42
KNX/EIB KNX Gateway for Tuya ZigBee

Parameters of this window display according to control mode and control system(2 pipe or 4pipe).

Parameter “Type of heating/cooling control”

This parameter is for setting the type of heating/cooling control. Different control types are

suitable for controlling different temperature controllers. Options:

Switching on/off(use 2-point control)

Switching PWM(use PI control)

Continuous control(use PI control)

Parameter “Invert control value”

This parameter is for setting whether to invert control value or normal sending control value, so

that the control value will be suitable for the valve type. Options:

No

Yes

Yes: Sending the control value to the bus through objects after inverting the control value.

Two parameters as follow are suitable for 2 point control:


——Parameter “Lower Hysteresis [0...200]*0.1°C ”

——Parameter “Upper Hysteresis [0...200]*0.1°C ”

These two parameters are for setting the lower/upper hysteresis temperature in HVAC heating or

cooling. Options: 0..200

Under heating control,

When the actual temperature(T) > the setting temperature + the upper hysteresis temperature,

then will stop heating;

When the actual temperature(T) < the setting temperature - the lower hysteresis temperature,

then will start heating.

For example, the lower hysteresis temperature is 1℃, the upper hysteresis temperature is 2℃, the

setting temperature is 22℃, if T is higher than 24℃, then it will stop heating; if T is lower than 24℃,then

it will start heating; if T is between 21~24℃, then it will maintain the previous status.

43
KNX/EIB KNX Gateway for Tuya ZigBee

Under the cooling control,

When the actual temperature (T) < the setting temperature -the lower hysteresis temperature,

then will stop cooling;

When the actual temperature (T) > the setting temperature +the upper hysteresis temperature,

then will start cooling.

For example, the lower hysteresis temperature is 1℃, the upper hysteresis temperature is 2℃, the

setting temperature is 26℃, if T is lower than 25℃, then it will stop cooling; if T is lower than 28℃, then

it will start cooling; if T is between 28~25℃, then it will maintain the previous status.

2-point control mode is a very simple control mode. When adopting this control mode, it is

necessary to set the upper hysteresis temperature and the lower hysteresis temperature through

parameters. When setting the hysteresis temperature, the following effects need to be considered:

1. When hysteresis interval is small, the temperature range will be small, however, frequent sending

of control value will bring large load to the bus;

2. When hysteresis interval is large, the switch switching frequency will be low, but it is easy to

cause uncomfortable temperature change.

Fig.5.4.1.2(2) Effects of hysteresis on control value switch action(heating) under2-point control mode

44
KNX/EIB KNX Gateway for Tuya ZigBee

Two parameters as follow are suitable for PI control:


——Parameter “Heating speed ”

——Parameter “Cooling speed”

These two parameters are for setting the responding speed of heating or cooling PI controller.

Different responding speeds are suitable for different environments.

Options:

Hot water heating (5K/150min)

Underfloor heating (5K/240 min)

Electrical heating (4K/100min)

Split unit (4K/90min)

Fan coil unit (4K/90min)

User defined

Options:

Cooling ceiling (5K/240min)

Split unit (4K/90min)

Fan coil unit(4K/90min)

User defined

——Parameter “Proportional range [10..100]*0.1°C”(P value)

——Parameter “Reset time [0..255]min”(I value)

These two parameters are visible when “User defined” is selected. Set the PI value of PI controller.

Options: 10..100 (P value)

Options: 0..255 (I value)

——Parameter “PWM cycle time [1...255]min”

This parameter is only visible when the control type is “Switching PWM(use PI control)”. Set the

period of the control object cycle to send the switch value, the object sends the switch value according

to the duty cycle of the control value. For example, if the set period is 10 min and the control value is

80%, then the object will send an open telegram for 8 min. If the control value is changed, the time duty

45
KNX/EIB KNX Gateway for Tuya ZigBee

ratio of the on/ off telegram of the object will also change, but the period is still the time of parameter

setting.

Options: 1..255

The PI values of “Switching PWM (use PI control)” and “Continuous control (use PI control)” are the

same, only different in control objects, the control object of “Continuous control” output PI value(1byte)

directly, while the control value of “Switching PWM” output a “on/off” telegram according to the duty

cycle of the control value.

——Parameter “Send control value on change by [0...100,0=inactive]%”

This parameter is visible when control type is “Continuous control (use PI control)”, for setting the

changing value of the control value to be sent to the bus. Options: 0..100, 0=inactive

Parameter “Cyclically send control value [0...255]min”

This parameter is for setting the period for cyclically sending the control value to the bus. Options:

0..255

In PI control mode, the predefined control parameters of each PI controller in heating or cooling

system are recommended as follows:

(1) Heating

Heating type P value I value(integration Recommended Recommended PWM

time) PI control type period

Hot water Heating 5K 150min Continuous/PWM 15min

Underfloor heating 5K 240min PWM 15-20min

Electrical heating 4K 100min PWM 10-15min

Split unit 4K 90min PWM 10-15min

Fan coil unit 4K 90min Continuous --

46
KNX/EIB KNX Gateway for Tuya ZigBee

(2) Cooling

Cooling type P value I value(integration Recommended Recommended PWM

time) PI control type period

Cooling ceiling 5K 240min PWM 15-20mIn

Split unit 4K 90min PWM 10-15min

Fan coil unit 4K 90min Continuous --

(3) User defined

When the parameter“Heating/Cooling speed” is set to “User defined”, the parameter value of P

(scale factor) and I (integration time) can be set through the parameter. When adjusting the parameters,

refer to the fixed PI value mentioned in the above table. Even if the control parameters are adjusted

slightly, the control behavior will be significantly different.

In addition, the integration time should be set properly. If the integration time is too long, the

adjustment will be slow, and the oscillation will not be obvious; if the integration time is too small, the

adjustment will be fast, but the oscillation will occur. 0 means the integral term is not used.

Fig.5.4.3 (7) control value of PI control mode

Y: control value

Y1: last control value

X1: temperature deviation = set temperature - actual temperature

X2: last temperature deviation = set temperature - actual temperature

TN: integration time

K: scale factor (the scale factor is not zero)

PI control algorithm: Y = K * (X1-X2) + X1 * K * t / TN + Y1

47
KNX/EIB KNX Gateway for Tuya ZigBee

When the integration time is set to zero, the PI control algorithm is: Y = K (X1-X2) + Y2

Setting and influence of user-defined parameters:

Parameter setting Effect

K: If the scale range is too small Quick adjustment, and overshoot will occur

K: If the scale range is too small Slow adjustment, but no overshoot

TN: If the integration time is too Quick adjustment, but there will be
short oscillation
TN: If the integration time is too long Slow adjustment, no obvious oscillation

5.4.1.3. Parameter window “Fan”

Fig.5.4.1.3 “Fan” parameter window

48
KNX/EIB KNX Gateway for Tuya ZigBee

Parameters of this window are visible when fan auto control enabled.

Parameter “Auto. operation on object value”

This parameter is for setting the telegram value to activate automatic operation. Options:

Auto=1/Man.=0

Auto=0/Man.=1

Auto=1/Man.=0: When the object “Fan automatic operation” receives the telegram value “0”,

activate the automatic operation, when receive “1”, exit the automatic operation.

Auto=0/Man.=1: When the object “Fan automatic operation” receives the telegram value “1”,

activate the automatic operation, when receive “0”, exit the automatic operation.

After power-on, automatic operation is not activated by default.

Fan speed output setting


Parameter “Object datatype of 1byte fan speed”

This parameter is for setting the object datatype of 1 byte fan speed. Options:

Fan stage (DPT 5.100)

Percentage (DPT 5.001)

——Parameter “Output value for fan speed low/medium/high”

These three parameters are for setting the value sent for each fan speed switchover. Fan speed off

when value is 0. Options according to fan object datatype: 1..255 /1..100

Note: the out value and status value must meet the condition low<medium<high, if not, they can

not be configured on ETS, and display red box warning, as shown as follow:

Fan speed control setting


Condition setting for using 2-point control

Under 2-point control, controller will decide the fan power on/off or fan speed according to the

temperature difference between the actual temperature and setpoint temperature.

Cooling: Temperature difference = actual temperature - setpoint temperature;

Heating: Temperature difference = setpoint temperature - actual temperature.

49
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Temperature difference speed OFF<-->low [1..200] *0.1°C”

This parameter is for setting the temperature difference between off-fan and low-level fan speeds.

Options: 1..200

If the temperature difference is greater than or equal to this setting temperature difference,

low-level fan speed will start running; if less than this setting temperature difference, the fan will be

turned off.

Parameter “Temperature difference speed low<-->medium [1..200]*0.1°C”

Define the temperature difference for switching the fan speed to medium fan speed, if the control

value is greater than or equal to this setting temperature difference, the medium fan speed will start

running.

Options: 1..200

Parameter “Temperature difference speed medium<-->high [1..200]*0.1°C”

Define the temperature difference for switching the fan speed to high fan speed, if the control

value is greater than or equal to this setting temperature difference, the high fan speed will start

running. Options: 1..200

Parameter “Hysteresis temperature difference in [0..50] *0.1°C”

This parameter is for setting the hysteresis value of the temperature difference, which can avoid

the unnecessary action of the fan when the control value fluctuates near the temperature difference.

Options: 0..50

If value is 0, no hysteresis. Fan switch to speed once control value greater than temperature

difference;

Suppose that hysteresis value is 0.5℃ and the temperature difference is 1℃, then the upper limit

temperature difference 1.5℃ (Temperature difference+Hysteresis value) and the lower limit

temperature difference 0.5℃ (Temperature difference-Hysteresis value). When the control value is

between 0.5℃~1.5℃, fan action will not be caused, and the previous status will still be maintained. Only

less than 0.5℃ or greater than or equal to 1.5℃ will change the running status of the fan.

50
KNX/EIB KNX Gateway for Tuya ZigBee

Condition setting for using PI control

Under PI control, control value is PI operated within program, controller will power on/off fan or

switch fan speed according to the threshold range of the control values.

Parameter “Threshold value speed OFF<-->low [1..255]”

Define threshold value for off-fan and low-level fan speeds, options: 1..255

If the control value is greater than or equal to this setting threshold value, low-level fan speed will

start running; if the control value is less than this setting threshold value, the fan will be turned off.

Parameter “Threshold value speed low<-->medium [1..255]”

Define the threshold value for switching the fan speed to medium fan speed, if the control value is

greater than or equal to this setting threshold, the medium fan speed will start running. Options: 1..255

Parameter “Threshold value speed medium<-->high [1..255]”

Define the threshold for switching the fan speed to high fan speed, if the control value is greater
than or equal to this setting threshold, the high fan speed will start running. Options: 1..255

Tip: The controller evaluates the threshold in ascending order.

First check →OFF <->low fan speed threshold →low fan speed <->medium fan speed →medium
fan speed <->high fan speed.

The correctness of functional execution is guaranteed only in this case:

The threshold of OFF <-> low fan speed is lower than that of low fan speed <-> medium fan speed,
and the threshold of low fan speed <-> medium fan speed is lower than that of medium fan speed <->
high fan speed.

Parameter “Hysteresis threshold value in +/-[0..50]”

This parameter is for setting the hysteresis value of the threshold value, which can avoid the
unnecessary action of the fan when the control value fluctuates near the threshold. Options: 0..50

If value is 0, no hysteresis. Fan switch to speed once control value greater than threshold value;

Suppose that hysteresis value is 10 and the threshold is 50, then the upper limit threshold 60
(Threshold value+Hysteresis value) and the lower limit threshold 40 (Threshold value-Hysteresis value).
When the control value is between 40 ~60, fan action will not be caused, and the previous status will
still be maintained. Only less than 40 or greater than or equal to 60 will change the running status of the
fan.

Parameter “Minimum time in fan speed [0..65535]s”

Defines the residence time of the fan from the current fan speed to a higher fan speed or lower fan
speed, that is, the minimum time for a fan speed operation.

51
KNX/EIB KNX Gateway for Tuya ZigBee

If you need to switch to another fan speed, you need to wait for this period of time before
switching.

If the current fan speed has been running long enough, the fan speed can be changed quickly.

Options: 0..65535

0: there is no minimum running time, but the delay switching time of fan speed still needs to be
considered.

Note: The residence time for this parameter setting is only enabled in Auto mode.

5.5.Parameter window “Ventilation controller”

5.5.1. Parameter window “Control setting”

Fig.5.5.1 “Control setting” parameter window

52
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Ventilation controller”

This parameter is for setting whether to enable ventilation controller, to realize the automatic

control of the fan speed, and link the fan speed to the detection value of PM2.5 or CO2, VOC.

Parameters as follow are visible when enabled.

Parameter “Auto. operation on object value”

This parameter is for setting the telegram value to activate automatic operation. Options:

Auto=1/Man.=0

Auto=0/Man.=1

Auto=1/Man.=0: When the object “Fan automatic operation” receives the telegram value “0”,

activate the automatic operation, when receive “1”, exit the automatic operation.

Auto=0/Man.=1: When the object “Fan automatic operation” receives the telegram value “1”,

activate the automatic operation, when receive “0”, exit the automatic operation.

After power-on, automatic operation is not activated by default.

Parameter “State of Auto.operation after startup”

This parameter is for setting whether to enable state of Auto.operation after startup the device.

Options:

Disable

Enable

Fan speed output setting


Parameter “Data type of fan speed”

This parameter is for setting the data type of fan speed. Options:

1bit

1byte

——Parameter “Object datatype of 1byte fan speed”

This parameter is visible when “1byte” is selected. Set the object datatype of 1byte fan speed.

Options:

Fan stage (DPT 5.100)

Percentage (DPT 5.001)

53
KNX/EIB KNX Gateway for Tuya ZigBee

——Parameter “Output value for fan speed low/medium/high”

This parameter is visible when “1byte” is selected. Set the value sent for each fan speed

switchover. Fan speed off when value is 0. Options according to fan object datatype: 1..255 /1..100

Note: the out value and status value must meet the condition low<medium<high, if not, they can

not be configured on ETS, and display red box warning, as shown as follow:

——Parameter “Object value of fan speed off/low/medium/high”

This parameter is visible when 1bit” is selected. Set the value sent for each fan speed, sent by three

1 bit objects at the same time. Options:

Low=0,Medium=0,High=0

Low=1,Medium=0,High=0

Low=0,Medium=1,High=0

Low=1,Medium=1,High=0

Low=0,Medium=0,High=1

Low=1,Medium=0,High=1

Low=0,Medium=1,High=1

Low=1,Medium=1,High=1

——Parameter “Delay between fan speed switch [0..100]*50ms”

This parameter is visible when 1bit” is selected. Set the delay time between fan speed switchover,

and consider it according to the fan technical characters. Options: 0..100

Turn off fan speed before switch the fan speed, and turn on it after the delay time. When delay time

is set as 0, it will not turn off first then turn on, but switch to next fan speed directly.

54
KNX/EIB KNX Gateway for Tuya ZigBee

Fan speed control setting


Parameter “Control value reference from”

This parameter is for setting the reference of control value under automatic operation. Options:

PM2.5

CO2

VOC

——Parameter “Object datatype of PM2.5/VOC”

These parameters are for setting the datatype of PM2.5/VOC. Datatype determines object type,

select it according to the docking PM2.5 or VOC sensor data type. Options:

Value in ug/m3(DPT 7.001)

Float value in ug/m3(DPT 9.030)


DPT_7.001: Suitable for integrated value.
DPT_9.030: Suitable for float value.
——Parameter “Object datatype of CO2”

This parameter is for setting the datatype of CO2. Datatype determines object type, select it

according to the docking CO2 sensor data type. Options:

Value in ppm(DPT 7.001)

Float value in ppm(DPT 9.008)

DPT_7.001: Suitable for integrated value.

DPT_9.008: Suitable for float value.

Parameter “Time period for request control value [0...255]min”

This parameter is for setting the time period for device to send a control value read request to

external sensor after bus recovery or finish programming (After stabilization time 2min, then read).

Options: 0..255

Parameter “The fan speed status when the control value error”

This parameter is for setting the default fan speed of ventilation system when control value is error.

Options:

Off

Low

55
KNX/EIB KNX Gateway for Tuya ZigBee

Medium

High

Parameter “Threshold value speed OFF<-->low [1..999]/ [1…4000]”

Define threshold value for off-fan and low-level fan speeds, options: 1..999/1..4000

If the control value is greater than or equal to this setting threshold value, low-level fan speed will

start running; if the control value is less than this setting threshold value, the fan will be turned off.

Parameter “Threshold value speed low<-->medium [1..999]/ [1…4000]”

Define the threshold value for switching the fan speed to medium fan speed, if the control value is

greater than or equal to this setting threshold, the medium fan speed will start running. Options:

1..999/1..4000

Parameter “Threshold value speed medium<-->high [1..999]/ [1…4000]”

Define the threshold for switching the fan speed to high fan speed, if the control value is greater

than or equal to this setting threshold, the high fan speed will start running. Options: 1..999/1..4000

Tip: The controller evaluates the threshold in ascending order.

First check →OFF <->low fan speed threshold →low fan speed <->medium fan speed →medium

fan speed <->high fan speed.

The correctness of functional execution is guaranteed only in this case:

The threshold of OFF <-> low fan speed is lower than that of low fan speed <-> medium fan speed,

and the threshold of low fan speed <-> medium fan speed is lower than that of medium fan speed <->

high fan speed.

Parameter “Hysteresis threshold value in +/- [10…30]/[100..400]”

This parameter is for setting the hysteresis value of the threshold value, which can avoid the

unnecessary action of the fan when the control value fluctuates near the threshold. Options:

10..30/100..400

For example, the control type is CO2, the Hysteresis value is 100 and the threshold is 450, then the

upper limit threshold 550 (Threshold value+Hysteresis value) and the lower limit threshold 350

(Threshold value-Hysteresis value). When the control value is between 350 ~550, fan action will not be

caused, and the previous status will still be maintained. Only less than 350 or greater than or equal to

56
KNX/EIB KNX Gateway for Tuya ZigBee

550 will change the running status of the fan. As shown in the following figure:

Note:

When hysteresis is enabled, if the threshold overlap occurs, fan action is specified as follows:

1) Hysteresis determines the control point where Fan speed conversion occurs;

2) If Fan speed conversion occurs, new fan speed is determined by control value and threshold

value, irrespective of hysteresis.

For example (1):

Take PM2.5 as an example

OFF <-> Low fan speed threshold value is 35

Low fan speed <->Medium fan speed threshold value is 55

Medium fan speed <-> High fan speed threshold value is 75

Hysteresis value is 25

The fan speed of the fan turbine increases from OFF:

Fan OFF status will change at a control value of 60 (≥25+35), and new fan speed will be the

mid-fan speed (because 60 is between 55 and 75, irrespective of hysteresis at this time), so the low

fan speed is ignored;

The behavior of fan speed when descending from a high fan speed:

The high fan speed will change at a control value of 50 (<75-25), and new fan speed will be low

fan speed (because 50 is between 35 and 55, irrespective of hysteresis), so the fan speed is ignored.

57
KNX/EIB KNX Gateway for Tuya ZigBee

For example(2):

Take PM2.5 as an example

OFF <-> Low fan speed threshold value is 20

Low fan speed <->Medium fan speed threshold value is 40

Medium fan speed <-> High fan speed threshold value is 70

Hysteresis value is 10

When fan speed is increasing from OFF:

The OFF status will be turned when the control value is 30(≥20+10)

When the control value 41 is received, the new speed will be at medium(because the hysteresis is

ignored when the value 41 is between 40 and 70), therefore the low speed is ignored.

When the control value 39 is received, the new speed will be at low (because the hysteresis is

ignored when the value 39 is between 20 and 40)

When Fan Speed decreasing from high:

The high speed will be turned when the control value is 60(<70-10)

When the control value 39 is received, the new speed will be at low(because the hysteresis is

ignored when the value 39 is between 20 and 40),therefore the medium speed is ignored.

3) When the control value is 0,the fan will be off at any circumstances.

Parameter “Minimum time in fan speed [0..65535]s”

Defines the residence time of the fan from the current fan speed to a higher fan speed or lower fan

speed, that is, the minimum time for a fan speed operation. Options: 0..65535

If you need to switch to another fan speed, you need to wait for this period of time before

switching.

If the current fan speed has been running long enough, the fan speed can be changed quickly.

0: there is no minimum running time, but the delay switching time of fan speed still needs to be

considered.

Note: The residence time for this parameter setting is only enabled in Auto mode.

58
KNX/EIB KNX Gateway for Tuya ZigBee

5.6.Parameter window “Logic”

Fig.5.6 “Logic function setting” Parameter window

Parameter “1st/2nd/3rd... Logic function”

This parameter is for setting the setting interface of logic function, display corresponding logic

function page when select. Up to enable 8 logic functions.

Parameter “Function of channel”

This parameter is for setting the logic function of the channel. Options:

AND

OR

XOR

Gate forwarding

Threshold comparator

Format convert

Gate function

Delay function

Staircase lighting

AND/OR/XOR: as the parameter is similar to the communication object (only the logic algorithm is

different), the following parameters taking one options for example.

59
KNX/EIB KNX Gateway for Tuya ZigBee

5.6.1. Parameter window “AND/OR/XOR”

Fig.5.6.1 “AND/OR/XOR” parameter window

Parameter “Input a/b/c/d/e/f/g//h”

This parameter is for setting whether input x to calculate, whether to normally calculate or inverted

calculate.Options:
Disconnected
Normal
Inverted
Disconnected: not to calculate;
Normal: to directly calculate the input value;
Inverted: invert the input value, then to calculate. Note: not to invert the initiate value.

60
KNX/EIB KNX Gateway for Tuya ZigBee

——Parameter “Default value”

This parameter is for setting the initial value of logic input x. Options:
0
1
Parameter “Result is inverted”

This parameter is for setting whether to invert the logic calculation result. Options:
No
Yes
No: output directly;
Yes: output after inverting.

Parameter “Read input object value after bus voltage recovery”

This parameter is for setting whether to send the read request to the logic input object after device

voltage recovery or finish programming. Options:


No
Yes
Parameter “Output send when”

This parameter is for setting the condition of sending logic result. Options:
Receiving a new telegram
Every change of output object

Receiving a new telegram:every time the object received a new input value will the logic result be

sent to the bus;

Every change of output object:only when logic result has changed will it be sent to the bus.

Tip: when in the first time to logic calculate, the logic result will be sent even if it has no change.

Parameter “Send delay time”

Base: None
0.1s
1s
...
10s
25s
Factor: 1..255

This parameter is for setting the delay time for sending the logic calculation result to the bus. Delay
time = Base × Factor, if option “None” of Base is selected, then there is no delay.

61
KNX/EIB KNX Gateway for Tuya ZigBee

5.6.2. Parameter window “Gate forwarding”

Fig.5.6.2 “Gate forwarding” parameter window

Parameter “Object type of Input/Output”

This parameter is for setting the object type of input/output. Options:

1bit

4bit

1byte

Parameter “Default scene NO. of Gate after startup [1~64,0=inactive]”

This parameter is for setting the initial scene where logical gate forwarding can be performed by

default after device starts, which needs to be configured in the parameters. Options:1..64, 0=inactive

Note: gate scene is recommended to be selected before operating, or it will enable the initiate

scene by default.

Parameter “z->Gate trigger scene NO. is [1~64,0=inactive]”(z=1~8)

This parameter is for setting scene number of logic gate forwarding. Up to 8 trigger scene number

can be set for each logic. Options: 1..64, 0=inactive

62
KNX/EIB KNX Gateway for Tuya ZigBee

——Parameter “Input A/B/C/D send on”

This parameter is for setting the output of input X (X=A/B/C/D) after gate forwarding. Options:

Output A

Output B

...

Output B,C,D

According to the options, one input can be forwarded into one or more outputs, the output value is

the same as the input value.

5.6.3. Parameter window “Threshold comparator”

Fig.5.6.3 “Threshold comparator” parameter window

Parameter “Threshold value data type”

This parameter is for setting the threshold value data type. Options:
4bit

1byte

2byte

4byte

63
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Threshold value 0..255”

This parameter is for setting threshold value, the range depends on the data type. Options: 4bit

0..15/1byte 0..255/ 2byte 0..65535 /4byte 0..4294967295

Parameter “If Object value<Threshold value”

Parameter “If Object value!=Threshold value”

Parameter “If Object value<Threshold value”

Parameter “If Object value<Threshold value”

Parameter “If Object value<Threshold value”

This parameter is for setting the logic result value that should be sent when threshold value Less

than, equal to, not equal to, greater than, less than or equal to the setting valve. Options:

Do not send telegram

Send value "0"

Send value "1"

Do not send telegram: not consider to select this option;

Send value “0”/“1”: when condition is satisfied, send telegram 0 or1.

If there is a conflict between the setting options between parameters, the base on the value that

should be sent when reach the final parameter condition. For example: parameter “If Object

value=Threshold value” is set to be “Send value “0” ”;parameter “If Object value<=Threshold value” is

set to be “Send value “1” ”;when object value is equal to the threshold value, then the logic result will

send “1”.

Parameter “Output send when”

This parameter is for setting the condition of sending logic result. Options:

Receiving a new telegram

Every change of output object

Receiving a new telegram: every time the object received a new input value will the logic result be
sent to the bus;

Every change of output object: only when logic result has changed will it be sent to the bus.

Tip: when in the first time to logic algorithm, the logic result will be sent even if it has no change.

64
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Send delay time”

Base: None

0.1s

1s

...

10s

25s

Factor: 1..255

This parameter is for setting the delay time for sending the logic algorithm result to the bus. Delay
time = Base x Factor, if option “None” of Base is selected, then there is no delay.
5.6.4. Parameter window “Format convert”

Fig.5.6.4 “Format convert” parameter window

Parameter “Function”

This parameter is for setting the format convert type. Options:

2x1bit-->1x2bit

8x1bit-->1x1byte

1x1byte-->1x2byte

2x1byte-->1x2byte

2x2byte-->1x4byte

1x1byte-->8x1bit

1x2byte-->2x1byte

1x4byte-->2x2byte

1x3byte-->3x1byte

3x1byte-->1x3byte

65
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Output send when”

This parameter is for setting the condition of sending logic result. Options:

Receiving a new telegram

Every change of output object

Receiving a new telegram: every time the object received a new input value will the logic result be
sent to the bus;

Every change of output object: only when logic result has changed will it be sent to the bus.

Tip: when in the first time to logic algorithm, the logic result will be sent even if it has no change.

5.6.5. Parameter window “Gate function”

Fig.5.6.5 “Gate function” parameter window

Parameter “Object type of Input/Output”

This parameter is for setting the object type of input/output. Options:

1bit[On/Off]

1byte[0..100%]

1byte[0..255]

2byte[Float]

2byte[0..65535]

——Parameter “Filter function”

This parameter is visible when “1bit[On/Off]” is selected. Set whether to filter On or Off telegram,

only pass one of them or pass all. Options:

66
KNX/EIB KNX Gateway for Tuya ZigBee

Deactivate

On filter out

Off filter out

Deactivate: Do not filter the On or Off telegrams;

On filter out: Off can pass, On cannot pass;

Off filter out: On can pass, Off cannot pass.

——Parameter “Value output”

This parameter is visible when “1bit[On/Off]” is selected. Set whether to invert the value then

output it. Options:

Normal

Inverted

Parameter “Gate object value”

This parameter is for setting whether to invert the gate object value then output it. Options:

Normal

Inverted

Parameter “Gate status after power on”

This parameter is for setting the gate status after power on. Options:

Disable

Enable

Parameter “Save input signal when gate close”

This parameter is for setting whether to save input signal on gate close. Options:

No

Yes

No: disable to save the input, the input values received during the gate closing period are ignored;

Yes: enable to save the input, the input values received during the gate closing period are output
when gate is open (whether the input value is changed or not).

67
KNX/EIB KNX Gateway for Tuya ZigBee

5.6.6. Parameter window “Delay function”

Fig.5.6.6 “Delay function” parameter window

Parameter “Object type of Input/Output”

This parameter is for setting the object type of input/output. Options:

1bit[On/Off]

1byte[0..100%]

1byte[0..255]

2byte[Float]

2byte[0..65535]

——Parameter “Delay time [0..6500]s”

This parameter is for setting the delay time that output object forwards the value when the input

object receives the telegram. Options: 0..6500

Note: Receive telegram again in delay time, re-timing.

5.6.7. Parameter window “Staircase lighting”

Fig.5.6.7 “Staircase lighting” parameter window

68
KNX/EIB KNX Gateway for Tuya ZigBee

Parameter “Trigger value”

This parameter is for setting the telegram value of the object “Trigger value”. Options:

0 or 1

Parameter “Object type of output”

This parameter is for setting the object type of output. Options:

1bit

1byte

Parameter “Duration time of staircase lighting[10..6500]s”

This parameter is for setting duration time of staircase lighting after the stair light power on.

Options: 10..6500

——Parameter “Send value 1 when trigger”

——Parameter “Send value 2 after duration time”

These parameters are for setting the value to send. Send value 1 when trigger, and then send value

2 after duration time. Options display according to the output object datatype.

When 1 bit, options:


OFF

ON
When 1 byte , options: 0..255

Parameter “Retriggering”

This parameter is for setting whether to trigger re-timing when received trigger value in delay time.

Options:

Disable

Enable

69
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 6 Description of Communication Object

The communication object is the medium to communicate other device on the bus, namely only
the communication object can communicate with the bus.

NOTE: “C” in “Flag” column in the below table means enable the communication function of the
object; “W” means value of object can be written from the bus; “R” means the value of the object can
be read by the other devices; “T” means the object has the transmission function; “U” means the value
of the object can be updated.

6.1.“General” Communication Object

Fig.6.1 “General” Communication Object


NO. Object Function Name Data Flag DPT
Type
1 In operation General 1bit C,R,T 1.001 switch

The communication object is used to periodically send a telegram “1” to the bus to indicate that
the device is working properly.
Table 6.1 “General” communication object table

6.2.“KNX Channel” Communication Object

Fig.6.2 KNX general communication Object

70
KNX/EIB KNX Gateway for Tuya ZigBee

NO. Object Function Name Data Flag DPT


Type
Device online common x,
300/.../309 KNX General 1bit C,W,T,U 1.001 switch
status

The communication object is used to send the request to the bus, for common device to query the
KNX device online status, and also can receive the feedback. Telegrams:

0——Offline
1——Online

Suitable for devices with multiple circuits. For example, multiple channels of gateway may be
multiple circuits that control the same KNX device, so each channel can share one request.

310 Device online, status KNX: {{Channel 1}} 1bit C,W,T,U 1.001 switch

The communication object is used to send the request to the bus, for independent device to query
the KNX device online status, and also can receive the feedback. Telegrams:
0——Offline
1——Online

Suitable for a device that only controlled by the single channel of gateway.

The name in parentheses changes with the parameter “Description (max 30 char.)”. If description
is empty, display “...Channel x” by default. The same below.

Table 6.2 KNX general communication object table

6.2.1. Communication Object of basic function

Switch

Switch/Dimming

71
KNX/EIB KNX Gateway for Tuya ZigBee

RGB dimming

RGBW dimming(1)

RGBW dimming(2)

Color temperature

Curtain step/move

Roller blind step/move

Curtain position

Roller blind position

Venetian blind position and slat

72
KNX/EIB KNX Gateway for Tuya ZigBee

Value sender

Scene switch
Fig.6.2.1 Basic function communication object

NO. Object Function Name Data Type Flag DPT


311 Switch KNX: {{Channel 1}} 1bit C,T 1.001 switch

312 Switch, status KNX: {{Channel 1}} 1bit C,W,T,U 1.001 switch

These two communication objects apply to switch, dimming, color and color temperature control.
Telegrams:

0——Turn off the light

1——Turn on the light

Obj.311: Used for sending On/Off telegrams to the bus, to control the light on/off.
Obj.312: Used for receiving On/Off status responded from other bus devices, such as dimming
actuator, switch actuator.

312 Brightness dimming KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

313 Brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

These two communication objects apply to brightness dimming. Telegrams: 0~100%

Obj.312: Used for sending dimming telegrams to the bus, that is, sending the brightness value.

Obj.313: Used for receiving brightness status responded from dimming actuator.

313 Red dimming value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

317 Red brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

These two communication objects are visible when 3x1byte for the RGB object type or 4x1byte for

the RGBW object type is selected. Apply to control brightness of multi-color lamp, and also support

color temperature adjustment. Telegrams: 0...100%

Obj.313 Used for sending brightness value of the control R (red) channel to the bus.

Obj.317: Used for receiving brightness value of the control R (red) channel from bus.

314 Green dimming value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

73
KNX/EIB KNX Gateway for Tuya ZigBee

318 Green brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

These two communication objects are visible when 3x1byte for the RGB object type or 4x1byte for

the RGBW object type is selected. Apply to control brightness of multi-color lamp, and also support

color temperature adjustment. Telegrams: 0...100%

Obj.314: Used for sending brightness value of the control G (green) channel to the bus.

Obj.318: Used for receiving brightness value of the control G (green) channel from bus.

315 Blue dimming value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

319 Blue brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

These two communication objects are visible when 3x1byte for the RGB object type or 4x1byte for
the RGBW object type is selected. Apply to control brightness of multi-color lamp, and also support
color temperature adjustment. Telegrams: 0...100%

Obj.315: Used for sending brightness value of the control B (blue) channel to the bus.

Obj.319: Used for receiving brightness value of the control B (blue) channel from bus.

316 White dimming value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

320 White brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

These two communication objects are visible when 4x1byte for the RGBW object type is selected.

Apply to control brightness of multi-color lamp, and also support color temperature adjustment.

Telegrams: 0...100%

Obj.316: Used for sending brightness value of the control W (white) channel to the bus.

Obj.320: Used for receiving brightness value of the control W (white) channel from bus.

313 RGB dimming value KNX: {{Channel 1}} 3byte C,T 232.600 RGB value 3x(0..255)

317 RGB brightness, status KNX: {{Channel 1}} 3byte C,W,T,U 232.600 RGB value 3x(0..255)

These two communication objects are visible when 1x3byte for the RGB object type is selected.
Apply to control brightness of multi-color lamp, and also support color temperature adjustment.

Obj.313: Used for sending brightness value of RGB three-color lamp to the bus.

Obj.317: Used for receiving brightness value of RGB three-color lamp from bus.

3-Byte Code for RGB Dimming Object Data Type: U8 U8 U8, as follows:
3MSB 2 1LSB
R G B
UUUUUUUU UUUUUUUU UUUUUUUU
R: red dimming value; G: green dimming value; B: blue dimming value.

74
KNX/EIB KNX Gateway for Tuya ZigBee

313 RGBW dimming value KNX: {{Channel 1}} 6byte C,T 251.600 DPT_Colour_RGBW

317 RGBW brightness, status KNX: {{Channel 1}} 6byte C,W,T,U 251.600 DPT_Colour_RGBW

These two communication objects are visible when 1x6byte for the RGBW object type is selected.

Apply to control brightness of multi-color lamp, and also support color temperature adjustment.

6MSB 5 4 3 2 1LSB

R G B W Reserve r r r r mR mG mB mW

UUUUUUUU UUUUUUUU UUUUUUUU UUUUUUUU 0000000 0000BBBB

R: red dimming value; G: green dimming value; B: blue dimming value; W: white dimming value;

mR: determines whether the red dimming value is valid, 0 = invalid, 1 = valid;

mG: determines whether the green dimming value is valid, 0 = invalid, 1 = valid;

mB: determines whether the blue dimming value is valid, 0 = invalid, 1 = valid;

mW: Determines whether the white dimming value is valid,0 = invalid,1 =valid.

7.600 absolute color


313 Color temperature value KNX: {{Channel 1}} 2byte C,T
temperature

7.600 absolute color


317 Color temperature, status KNX: {{Channel 1}} 2byte C,W,T,U
temperature

These two communication objects apply to color temperature adjustment of monochrome lamp.

Telegrams: 2000..7000 K

Obj.313: Used for sending the control telegram of the color temperature to the bus.

Obj.317: Used for receiving the control telegram of the color temperature from bus.

314 Brightness value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

318 Brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

These two communication objects apply to color temperature adjustment of monochrome lamp.
Telegrams: 0…100%

Obj.314: Used for sending the dimming telegram of the color temperature to the bus, that is,
sending the brightness value.

Obj.318: Used for receiving the brightness status responded from the dimming actuator.

75
KNX/EIB KNX Gateway for Tuya ZigBee

311 Open/Close KNX: {{Channel 1}} 1bit C,T 1.009 open/close

312 Stop KNX: {{Channel 1}} 1bit C,T 1.007 step

Curtain step/move: these two communication objects apply to open and close curtain. Support to

open, close, stop.

Obj.311: Used for sending the telegram to the bus, to control curtain open/close. Telegrams:

1——Close the curtain


0——Open the curtain
Obj.312: Used for sending the telegram to the bus, to stop curtain movement. Telegrams:
1——Stop
311 Up/Down KNX: {{Channel 1}} 1bit C,T 1.008 up/down

312 Stop KNX: {{Channel 1}} 1bit C,T 1.007 step

Roller blind step/move: these two communication objects apply to roller blind. Support to up,
down, stop.
Obj.311: Used for sending the telegram to the bus, to control blind up/down. Telegrams:
1——Move down
0——Move up
Obj.312 is the same as above.
311 Open/Close KNX: {{Channel 1}} 1bit C,T 1.009 open/close

312 Stop KNX: {{Channel 1}} 1bit C,T 1.007 step

313 Blind position KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

315 Blind position, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

Curtain position: apply to open and close curtain. Support to open, close, stop, position
adjustment and position status feedback.

Obj.311: Used for sending the telegram to the bus, to control curtain open/close. Telegrams:

1——Close the curtain

0——Open the curtain

Obj.312: Used for sending the telegram to the bus, to stop curtain movement. Telegrams:

1——Stop

Obj.313: Used for sending a telegram to control the position of the curtain to the bus. Telegrams:
0…100%

Obj.315: Used for receiving a curtain position status in response to the window curtain actuator
on the bus. Telegrams: 0…100%

76
KNX/EIB KNX Gateway for Tuya ZigBee

311 Up/Down KNX: {{Channel 1}} 1bit C,T 1.008 up/down

312 Stop KNX: {{Channel 1}} 1bit C,T 1.007 step

313 Blind position KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

315 Blind position, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

Roller blind position: apply to a roller blind without slat. Support to up, down, stop, position
adjustment and position status feedback.

Obj.311: Used for sending the telegram to the bus, to control blind up/down. Telegrams:

1——Move down

0——Move up

Obj.312, Obj.313, Obj.315 are the same as above.

311 Up/Down KNX: {{Channel 1}} 1bit C,T 1.008 up/down

312 Stop/Slat adj. KNX: {{Channel 1}} 1bit C,T 1.007 step

313 Blind position KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

314 Slat position KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)

315 Blind position, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

316 Slat position, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)

Venetian blind position and slat: apply to a blind with slat. Support to up, down, stop, position and

slat adjustment, position and slat status feedback.

Obj.311、Obj.313 and Obj.315 are same as above.

Obj.312: Used for sending a telegram to the bus to stop the curtain movement or adjust the slat

angle. Telegrams:

1——Stop/Slat adj. Down

0——Stop/Slat adj. Up

Obj.314: Used for sending a telegram to control the position of the blind to the bus. Telegrams:

0…100%

Obj.316: Used for receiving a blind position status in response to the blind actuator on the bus.

Telegrams: 0…100%

77
KNX/EIB KNX Gateway for Tuya ZigBee

1bit on/off 1.001 switch


Send 1bit value
2bit 0..3 2.001 switch control
Send 2bit value
1byte 0..100% 5.001
Send 1byte percent value
1byte 0..255 percentage(0..100%)
311 Send 1byte unsigned value KNX: {{Channel 1}} C,T
1byte 1..64 5.010 counter pulses
Recall scene No.
2byte 17.001 scene number
Send 2byte float value
-671088.64..670760.96 9.x float value
Send 2byte unsigned value
2byte 0..65535 7.001 pulses

The communication object is used for sending a preset telegram to the bus when trigger the
calling command on the APP. Object type and value range are determined by the parameter setting
datatype.

311 Trigger scene No. KNX: {{Channel 1}} 2byte C,W 17.001 scene number

The communication object is used for receiving the scene triggered telegram from KNX system.

Telegram: 1..64

Table 6.2.1 Basic function communication object table

6.2.2. Communication Object of Air condition

Air conditioner

Air conditioner(with swing)


Fig.6.2.2 Air condition function communication object

78
KNX/EIB KNX Gateway for Tuya ZigBee

NO. Object Function Name Data Flag DPT


Type
311 Power on/off KNX: {{Channel 1}} 1bit C,T 1.001 switch

The communication object is used to control air condition power on/off via the APP, and send the
telegram value to the bus. Telegrams:
1——On
0——Off
312 Current setpoint adjustment KNX: {{Channel 1}} 2byte C,T 9.001 temperature

The communication object is used to adjust setpoint temperature via the APP, and send telegram
value to the bus.
20.105 HVAC control
313 Control mode KNX: {{Channel 1}} 1byte C,T
mode

The communication object is used to send control telegram of each air condition mode to the
bus.
Different telegram means different control mode:
0-Auto, 1- Heating, 3-Cooling, 9-Fan, 14-Dehumidity, other reserved.
5.001 percentage
314 Fan speed KNX: {{Channel 1}} 1byte C,T
5.100 fan stage

The communication object is used to send control telegram of each fan speed to the bus.
Telegram value is determined by parameter setting datatype.
315 Vanes swing (1-swing,0-stop) KNX: {{Channel 1}} 1bit C,T 1.010 start/stop

The communication object is visible only when “Air conditioner(with swing)” is selected. Used to
send telegram controlling vanes swing to the bus. Telegrams:
1——Swing
0——Stop

317 Power on/off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

The communication object is used to receive the power on/off telegram of air condition from the
bus, and feedback to the APP display. Telegrams:

1——On

0——Off

318 Room temperature sensor KNX: {{Channel 1}} 2byte C,W,T,U 9.001 temperature

The communication object is used to receive the room temperature from the bus, and send read
request cyclically, and feedback to the APP display.

79
KNX/EIB KNX Gateway for Tuya ZigBee

319 Current temperature setpoint, status KNX: {{Channel 1}} 2byte C,W,U 9.001 temperature

The communication object is used to receive the current setpoint temperature from the bus, and
feedback to the APP display.

320 Control mode, status KNX: {{Channel 1}} 1byte C,W 20.105 HVAC control mode

The communication object is used to receive the current control mode from the bus, and
feedback to the APP display. Different telegram means different control mode:

0-Auto, 1- Heating, 3-Cooling, 9-Fan, 14-Dehumidity, other reserved.


5.001 percentage
321 Fan speed, status KNX: {{Channel 1}} 1byte C,W
5.100 fan stage

The communication object is used to receive the current fan speed from the bus, and feedback to
the APP display. Telegram value is determined by parameter setting datatype.

322 Vanes swing (1-swing,0-stop), status KNX: {{Channel 1}} 1bit C,W 1.010 start/stop

The communication object is visible only when “Air conditioner(with swing)” is selected. Used to
receive vanes swing status from the bus. Telegrams:

1——Swing

0——Stop

Table 6.2.2 Air condition function communication object table

6.2.3. Communication Object of Room temperature unit

Room temperature unit

Room temperature unit(with operation mode)

80
KNX/EIB KNX Gateway for Tuya ZigBee

Room temperature unit(with operation mode & fan speed)


Fig.6.2.3 Room temperature unit function communication Object
NO. Object Function Name Data Type Flag DPT

311 Power on/off KNX: {{Channel 1}} 1bit C,T 1.001 switch

The communication object is used to control RTC power on/off via the APP, and send the
telegram value to the bus. Telegrams:

1——On

0——Off

312 Current setpoint adjustment KNX: {{Channel 1}} 2byte C,T 9.001 temperature

The communication object is used to adjust setpoint temperature via the APP, and send telegram
value to the bus.

313 Heating/Cooling mode KNX: {{Channel 1}} 1bit C,T 1.100 cooling/heating

The communication object is used to send telegram for switching cooling and heating functions
to the bus. Telegrams:

1——Heating

0——Cooling

314 Operation mode KNX: {{Channel 1}} 1byte C,T 20.102 HVAC mode

The communication object is used to send the telegram of the room operation mode to the bus.

Different telegram means different control mode:

1-Comfort, 2-Standby, 3-Economy, 4-Protection, other reserved.


5.001 percentage
319 Fan speed KNX: {{Channel 1}} 1byte C,T
5.100 fan stage

320 Fan speed low KNX: {{Channel 1}} 1bit C,T 1.001 switch

81
KNX/EIB KNX Gateway for Tuya ZigBee

321 Fan speed medium KNX: {{Channel 1}} 1bit C,T 1.001 switch

322 Fan speed high KNX: {{Channel 1}} 1bit C,T 1.001 switch

323 Fan speed off KNX: {{Channel 1}} 1bit C,T 1.001 switch

These communication objects are used to control fan speed via the APP, and send telegrams to
the bus.

1bit object is visible according to the parameter setting :

Object 320——Low fan speed

Object 321——Medium fan speed

Object 322——High fan speed

Object 323——Fan speed off

Only the corresponding object sends telegram “1” when switch to a certain fan speed. When
1bit-off object is not enable, all objects send telegrams “0” when switch to fan speed off (The situation
apply to connect with fan actuator of GVS);

When 1bit-off object is enable, only 1bit-off object send telegram “1” (The situation apply to
connect with fan actuator of other manufacturers).

1byte: the corresponding telegram value of each fan speed is defined by the parameter. Activate
the corresponding fan speed on the APP, and object 319 sends the corresponding telegram value of
the fan speed to the bus.

324 Fan automatic operation KNX: {{Channel 1}} 1bit C,T 1.003 enable

The communication object is used to send the telegram of fan automatic control to the bus.
Telegrams:

1——Auto

0——Exit auto

325 Power on/off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

The communication object is used to receive the power on/off telegram of RTC from the bus, and
feedback to the APP display. Telegrams:

1——On

0——Off

326 Room temperature sensor KNX: {{Channel 1}} 2byte C,W,T,U 9.001 temperature

The communication object is used to receive the room temperature from the bus, and send read
request cyclically, and feedback to the APP display.

82
KNX/EIB KNX Gateway for Tuya ZigBee

327 Current temperature setpoint, status KNX: {{Channel 1}} 2byte C,W,U 9.001 temperature

The communication object is used to receive the current setpoint temperature from the bus, and
feedback to the APP display.

328 Heating/Cooling mode, status KNX: {{Channel 1}} 1bit C,W 1.100 cooling/heating

The communication object is used for receiving the status of heating and cooling from the bus,
and feedback to the APP display. Telegrams:
1 ——Heating
0 ——Cooling

329 Operation mode, status KNX: {{Channel 1}} 1byte C,W 20.102 HVAC mode

The communication object is used for receiving the telegram of RTC operation mode from the
bus.
Different telegram means different control mode:
1-Comfort, 2-Standby, 3-Economy, 4-Protection, other reserved.
5.001 percentage
334 Fan speed, status KNX: {{Channel 1}} 1byte C,W
5.100 fan stage

335 Fan speed low, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

336 Fan speed medium, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

337 Fan speed high, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

338 Fan speed off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

These communication objects are used to receive status feedback to control fan speed via four
1bit objects or a 1byte object.

1bit :
Object 335——Low fan speed
Object 336——Medium fan speed
Object 337——High fan speed
Object 338——Fan speed off
The object receives telegram “1”, activate corresponding fan speed, and and feedback to the APP
display. When 1bit-off object is not enable, fan speed off when telegram values of low/medium/high
fan speed are “0”;

When 1bit-off object is enable, fan speed off when 1bit-off object receives telegram “1”, and fan

speed also off when telegram values of low/medium/high fan speed are “0”

1byte: the corresponding telegram value of each fan speed is defined by the parameter. When
object 334 receives the corresponding value, update the fan speed status on the APP display.

83
KNX/EIB KNX Gateway for Tuya ZigBee

339 Fan automatic operation, status KNX: {{Channel 1}} 1bit C,W 1.003 enable

The communication object is used to receive feedback status of fan automatic control.
Telegrams:
1——Automatic
0——Cancel automatic
Table 6.2.3 Room temperature unit function communication object table

6.2.4. Communication Object of Ventilation system

Ventilation system
Fig.6.2.4 Ventilation system function communication object
NO. Object Function Name Data Type Flag DPT

311 Power on/off KNX: {{Channel 1}} 1bit C,T 1.001 switch

The communication object is used to control ventilation power on/off via the APP, and send the
telegram value to the bus. Telegrams:
1——On
0——Off
5.001 percentage
312 Fan speed KNX: {{Channel 1}} 1byte C,T
5.100 fan stage
313 Fan speed low KNX: {{Channel 1}} 1bit C,T 1.001 switch
314 Fan speed medium KNX: {{Channel 1}} 1bit C,T 1.001 switch
315 Fan speed high KNX: {{Channel 1}} 1bit C,T 1.001 switch
These communication objects are used to send the control telegrams of fan speed to the bus.
1byte: the corresponding telegram value of each fan speed is defined by the parameter. Activate
the corresponding fan speed on the APP, and object 312 sends the corresponding telegram value of
the fan speed to the bus.
1bit:
Object 313——Low fan speed
Object 314——Medium fan speed
Object 315——High fan speed
The corresponding object sends telegram “1” to activate corresponding fan speed on the APP.
Turn off fan speed when send telegram “0”.

84
KNX/EIB KNX Gateway for Tuya ZigBee

316 Fan automatic operation KNX: {{Channel 1}} 1bit C,T 1.003 enable

The communication object is used to send the telegram of fan automatic control to the bus.
Telegrams:

1——Auto

0——Exit auto

317 Heat recovery KNX: {{Channel 1}} 1bit C,T 1.003 enable

The communication object is used to control heat recovery mode via the APP, and send telegram

to the bus. Telegrams:

1——Active

0——Inactive

318 Power on/off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

The communication object is used to receive the power on/off telegram of ventilation from the
bus, and feedback to the APP display. Telegrams:

1——On

0——Off
5.001 percentage
319 Fan speed, status KNX: {{Channel 1}} 1byte C,W
5.100 fan stage

320 Fan speed low, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

321 Fan speed medium, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

322 Fan speed high, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

These communication objects are used to receive status feedback to control fan speed via three
1bit objects or a 1byte object.

1byte: the corresponding telegram value of each fan speed is defined by the parameter. When
object 319 receives the corresponding value, update the fan speed status on the APP display.

1bit :

Object 320——Low fan speed

Object 321——Medium fan speed

Object 322——High fan speed

The object receives telegram “1”, activate corresponding fan speed, and and feedback to the APP
display. All telegram values of fan speed should be 0 when turn off fan speed;

85
KNX/EIB KNX Gateway for Tuya ZigBee

323 Fan automatic operation, status KNX: {{Channel 1}} 1bit C,W 1.003 enable

The communication object is used to receive feedback status of fan automatic control.
Telegrams:
1——Automatic
0——Cancel automatic

324 Heat recovery, status KNX: {{Channel 1}} 1bit C,W 1.003 enable

The communication object is used to receive status of heat recovery mode, and feedback to the
APP display. Telegrams:
1——Active
0——Inactive

325 Filter alarm, status KNX: {{Channel 1}} 1bit C,W 1.005 alarm

The communication object is used to receive filter status from the bus, and feedback to the APP
display. Telegrams:
1——In normal use
0——Replace alarm
Table 6.2.4 Ventilation system function communication object table

6.2.5. Communication Object of Audio control

Audio control

Audio control(with on/off)


Fig.6.2.5 Audio control function communication object
Note: If “Audio control(with on/off)” is selected, default as power off when voltage recovery, and

the object no need to send read request telegram. If “Audio control” is selected, the object needs to

send read request telegram when voltage recovery.

86
KNX/EIB KNX Gateway for Tuya ZigBee

NO. Object Function Name Data Type Flag DPT


311 Power on/off KNX: {{Channel 1}} 1bit C,T 1.001 switch

The communication object only applies to the audio control with power on/off. Used to to control
the audio power on/off via the APP, and send the telegram to the bus. Telegrams:

1——On
0——Off

312 Play=1/Pause=0 KNX: {{Channel 1}} 1bit C,T 1.010 start/stop

The communication object is used to play/stop the music in the audio module via the APP.

Telegrams:

1——Play music

0——Pause playing music

313 Next track=1/Previous track=0 KNX: {{Channel 1}} 1bit C,T 1.007 step

The communication object is used to switch the playing song of the audio module via the APP, to
switch the previous song/the next song. Telegrams:

1——Play the next song

0——Play the previous song

314 Volume+=1/Volume-=0 KNX: {{Channel 1}} 1bit C,T 1.007 step

5.001 percentage
315 Absolute volume KNX: {{Channel 1}} 1byte C,T
5.004 percentage

The communication object is used to adjust volume of the audio module via the APP. Telegram
value is determined by different object datatype.
1 bit object, telegrams:
1——Increase volume
0——Decrease volume
1 byte object only applies to the audio control function without power on/off. Telegram value is
according to object type: 0..100 / 0..255

316 Mute KNX: {{Channel 1}} 1bit C,T 1.003 enable

The communication object only applies to the audio control function without power on/off, used
to control mute of the audio module via the APP. Telegrams:
1——Mute
0——Cancel mute

87
KNX/EIB KNX Gateway for Tuya ZigBee

317 Play mode KNX: {{Channel 1}} 1byte C,T 5.010 counter pulses

The communication object is used to send control telegram of the audio module play mode,
different mode telegrams are preset by parameters.

318 Power on/off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch

The communication object only applies to the audio control function with power on/off. Used to
receive the power on/off telegram of the audio module from the bus.

C,W
319 Play=1/Pause=0, status KNX: {{Channel 1}} 1bit 1.010 start/stop
C,W,T,U

The communication object is used to receive the music play/stop status from the bus.
When the audio control function with power on/off, the object flag is C,W; And without power
on/off, the object flag is C,W,T,U.

1byt 5.001 percentage


320 Absolute volume, status KNX: {{Channel 1}} C,W,T,U
e 5.004 percentage

Volume adjustment function, 1byte object only applies to the audio control function without power
on/off. Used to receive the volume status of audio control.
Telegram value is according to object type: 0..100 / 0..255

321 Mute, status KNX: {{Channel 1}} 1bit C,W,T,U 1.003 enable

The communication object only applies to the audio control function without power on/off. Used
to receive the mute status of audio control.

1byt C,W
322 Play mode, status KNX: {{Channel 1}} 5.010 counter pulses
e C,W,T,U

The communication object is used to receive the play mode status of the audio module from the
bus, different mode telegrams are preset by parameters.

When the audio control function with power on/off, the object flag is C,W; And without power
on/off, the object flag is C,W,T,U.
Table 6.2.5 Audio control function communication object table

88
KNX/EIB KNX Gateway for Tuya ZigBee

6.2.6. Communication Object of sensor function

Air quality sensor

CO2 sensor

PM2.5 sensor

VOC sensor

Presence sensor

Motion sensor

Brightness sensor

I/O signal
Fig.6.2.6 Sensor function communication object

89
KNX/EIB KNX Gateway for Tuya ZigBee

NO. Object Function Name Data Type Flag DPT


7.001 pulse

311 PM2.5 value KNX: {{Channel 1}} 2byte C,W,T,U 9.030

concentration(ug/m3)

The communication object is used to receive the input of the PM2.5 value and get the
corresponding value from the bus to be updated to the APP display in ug/m3.

Range: 0~999ug/m3, object datatype is determined by the parameter setting.


7.001 pulse

312 PM10 value KNX: {{Channel 1}} 2byte C,W,T,U 9.030

concentration(ug/m3)

The communication object is used to receive the input of the PM10 value and get the
corresponding value from the bus to be updated to the APP display in ug/m3.

Range: 0~999ug/m3, object datatype is determined by the parameter setting.

7.001 pulse

313 VOC value KNX: {{Channel 1}} 2byte C,W,T,U 9.030

concentration(ug/m3)

The communication object is used to receive the input of the VOC value and get the
corresponding value from the bus to be updated to the APP display in ug/m3.

Range: 0~999ug/m3, object datatype is determined by the parameter setting.


7.001 pulse
314 CO2 value KNX: {{Channel 1}} 2byte C,W,T,U
9.008 parts/million(ppm)

The communication object is used to receive the input of the CO2 value and get the
corresponding value from the bus to be updated to the APP display in ppm.

Range: 0...4000ppm

316 AQI value KNX: {{Channel 1}} 2byte C,W,T,U 7.001 pulses

The communication object is used to receive the input of the AQI value and get the corresponding
value from the bus to be updated to the APP display. Range: 0...500

317 Temperature value KNX: {{Channel 1}} 2byte C,W,T,U 9.001 temperature

The communication object is used to receive the input of the temperature value and get the
corresponding value from the temperature sensor on bus to be updated to the APP display. Range:
-40...40℃

90
KNX/EIB KNX Gateway for Tuya ZigBee

311 Humidity value KNX: {{Channel 1}} 2byte C,W,T,U 9.007 humidity

The communication object is used to receive the input of the humidity value and get the
corresponding value from the humidity sensor on bus to be updated to the APP display. Range:
0...100%
7.013 brightness(lux)
312 Brightness value(lux) KNX: {{Channel 1}} 2byte C,W,T,U
9.004 lux(lux)

The communication object is used to receive the input of the brightness value and get the
corresponding value from the bus to be updated to the APP display in lux.
Range: 0...65535lux, object datatype is determined by the parameter setting.

311 Motion detector KNX: {{Channel 1}} 1bit C,W,T,U 1.018 Occupancy

The communication object is used to receive the input of the 1bit presence signal. Telegram:
0——No one
1——Some one

311 I/O signal value KNX: {{Channel 1}} 1bit C,W,T,U 1.001 switch

The communication object is used to receive the input of the 1bit I/O signal. Telegram:
0——Open
1——Close
Table 6.2.6 Sensor function communication object table

91
KNX/EIB KNX Gateway for Tuya ZigBee

6.2.7. Communication Object of current/energy metering

Current metering

Energy metering
Fig.6.2.7 Current/Energy metering function communication object

NO. Object Function Name Data Type Flag DPT


7.012 current(mA)
2byte
311 Current value KNX: {{Channel 1}} C,W,T,U 9.021 current(mA)
4byte
14.019 electric current(A)

The communication object is used to receive the current value from the bus, updated to the APP
display. Object datatype is determined by the parameter setting.

When 2byte int is selected, display range: 0...65535mA, step value is 1mA.

When 2byte float is selected, display range: -670760...670760mA, step value is 0.01mA.

When 4byte is selected, display range: -99999999.9...99999999.9A, step value is 0.1A.

2byte 9.020 voltage(mV)


312 Voltage value KNX: {{Channel 1}} C,W,T,U
4byte 14.027 electric potential(V)

The communication object is used to receive the voltage value from the bus, updated to the APP
display. Object datatype is determined by the parameter setting.

When 2byte is selected, display range: -670760mV...670760mV, step value is 0.01mV.

When 4byte is selected, display range: -99999999.9...99999999.9V, step value is 0.1V.

2byte 9.024 power(kW)


313 Power value KNX: {{Channel 1}} C,W,T,U
4byte 14.056 power(W)

The communication object is used to receive the power value from the bus, updated to the APP
display. Object datatype is determined by the parameter setting.

When 2byte is selected, display range: -670760kW...670760kW, step value is 0.01kW.

When 4byte is selected, display range: -99999999.9...99999999.9W, step value is 0.1W.

92
KNX/EIB KNX Gateway for Tuya ZigBee

13.010 active energy(Wh)


314 Energy value KNX: {{Channel 1}} 4byte C,W,T,U
13.013 active energy(kWh)

The communication object is used to receive the energy value from the bus, updated to the APP
display. Object datatype is determined by the parameter setting.

Display range: -2147483648...2147483647Wh, step value is 1Wh.

Display range: -2147483648...2147483647kWh, step value is 1kWh.


Table 6.2.7 Current/Energy metering function communication object table

6.3.“Zigbee Channel” Communication Object

Air quality sensor

Temperature and humidity sensor

Brightness sensor

Gas sensor

I/O signal

Switch

Switch/Dimming

93
KNX/EIB KNX Gateway for Tuya ZigBee

RGB dimming

Color temperature

RGBCW

Curtain position

Temperature, humidity and brightness sensor


Fig.6.3 “Zigbee Channel” communication object

NO. Object Function Name Data Flag DPT


Type
7.001 pulse
3712 VOC value Zigbee: {{Channel 1}} 2byte C,R,T
9.030 concentration(ug/m3)

The communication object applies to air quality sensor, is used to send the VOC value in ug/m3 to
the KNX bus. Range: 0...999ug/m3, object datatype is determined by the parameter setting.
7.001 pulse
3713 CO2 value Zigbee: {{Channel 1}} 2byte C,R,T
9.008 parts/million(ppm)

The communication object applies to air quality sensor, is used to send the CO2 value in ppm to the
KNX bus.

Range: 0...4000ppm

7.001 pulse
3714 Formaldehyde value Zigbee: {{Channel 1}} 2byte C,R,T
9.030 concentration(ug/m3)

The communication object applies to air quality sensor, is used to send the formaldehyde value in
ug/m3 to the KNX bus.Range: 0...1000ug/m3

94
KNX/EIB KNX Gateway for Tuya ZigBee

3715 Temperature value Zigbee: {{Channel 1}} 2byte C,R,T 9.001 temperature

The communication object applies to temperature sensor, and temperature, humidity and brightness
sensor, is used to send the temperature value in °C to the KNX bus. Range: -50...99°C

3716 Humidity value Zigbee: {{Channel 1}} 2byte C,R,T 9.007 humidity

The communication object applies to humidity sensor, and temperature, humidity and brightness
sensor, air quality sensor, is used to send the humidity value in % to the KNX bus. Range: 0...100%
7.013 brightness(lux)
3710 Brightness(lux) value Zigbee: {{Channel 1}} 2byte C,R,T
9.004 lux(lux)

The communication object applies to brightness sensor, and temperature, humidity and brightness
sensor, air quality sensor, is used to send the brightness value to the KNX bus. Range: 0...65535lux,
object datatype is determined by the parameter setting.
7.001 pulse

3710 Gas concentration value Zigbee: {{Channel 1}} 2byte C,R,T 9.008 parts/million(ppm)

9.030 concentration(ug/m3)

The communication object applies to gas sensor, air quality sensor, gas measurement, is used to
send the gas concentration value to the KNX bus. For example VOC, CO2 or formaldehyde detection
value.
1.001 switch
3710 Binary value Zigbee: {{Channel 1}} 1bit C,R,T
1.002 boolean

3710 Alarm detect Zigbee: {{Channel 1}} 1bit C,R,T 1.005 alarm

3710 Presence detect Zigbee: {{Channel 1}} 1bit C,R,T 1.018 occupancy

3710 Window/door detect Zigbee: {{Channel 1}} 1bit C,R,T 1.019 window/door

The communication object applies to I/O type sensor, is used to send the I/O signal to the KNX bus.
Object datatype is determined by the parameter setting. Telegram value:
0——Open/No alarm/Not occupied/Close window
1——Close/Alarm/Occupied/Open window

3710/.
C,W
./ Switch Zigbee: {{Channel 1}} 1bit 1.001 switch
C,W,R,T,U
3712

3713/.

./ Switch, status Zigbee: {{Channel 1}} 1bit C,R,T 1.001 switch

3715

95
KNX/EIB KNX Gateway for Tuya ZigBee

These communication objects apply to switch, dimming, RGB, color temperature and RGBCW
control, are used for KNX system to control Zigbee lamps, including lamp, dimmable lamp, RGB
bulb/strip, color temperature light and RGBCW bulb.
When “Switch” is selected, object name is “Zigbee: {{Channel 1}}-x”, and set the number of channels
for the switch by parameter, up to 3 channels, x=1/2/3.
Telegram value:

0——Turn off the light


1——Turn on the light
Obj.3710/../3712: Used for receiving On/Off telegram from KNX bus, to control the light on/off.
When “RGBCW” is selected, object flag is C,W,R,T,U; while other selections, the object flag is C,W.
Obj.3713/../3715: Used for sending On/Off status to the bus.

3712 Brightness value Zigbee: {{Channel 1}} 1byte C,W 5.001 percentage(0..100%)

3715 Brightness, status Zigbee: {{Channel 1}} 1byte C,R,T 5.001 percentage(0..100%)

These two communication objects apply to color temperature and RGBCW control, are used for KNX
system to control Zigbee lamps, including RGB bulb/strip and RGBCW bulb. Telegrams: 0…100%

Obj.3712: Used for receiving the brightness value from KNX bus, to control the brightness of the
lamp.

Obj.3715: Used for sending the brightness status to KNX bus.

3712 RGB dimming value Zigbee: {{Channel 1}} 3byte C,W 232.600 RGB value 3x(0..255)

3715 RGB brightness, status Zigbee: {{Channel 1}} 3byte C,R,T 232.600 RGB value 3x(0..255)

These two communication objects apply to RGB and RGBCW control, are used for KNX system to
control Zigbee lamps, including RGB bulb/strip and RGBCW bulb.
Obj.3712: Used for receiving the brightness value of RGB three-color lamp from KNX bus, to control
the color of the lamp.
Obj.3715: Used for sending the brightness status of RGB three-color lamp to the KNX bus.
3-Byte Code for RGB Dimming Object Data Type: U8 U8 U8, as follows:

3MSB 2 1LSB

R G B

UUUUUUUU UUUUUUUU UUUUUUUU

R: red dimming value; G: green dimming value; B: blue dimming value.

3711 Color temperature value Zigbee: {{Channel 1}} 2byte C,W 7.600 absolute color

temperature

96
KNX/EIB KNX Gateway for Tuya ZigBee

3714 Color temperature, Zigbee: {{Channel 1}} 2byte C,R,T 7.600 absolute color

status temperature

These two communication objects apply to color temperature and RGBCW control, are used for KNX
system to control Zigbee lamps, including color temperature light and RGBCW bulb. Telegrams:
2000..7000K

Obj.3711: Used for receiving the color temperature control value form the bus, to control the color
temperature of the lamp.

Obj.3714: Used for sending the color temperature status to the KNX bus.
3710/
Open/Close Zigbee: {{Channel 1}}-x 1bit C,W 1.009 open/close
3713

3711/
Stop Zigbee: {{Channel 1}}-x 1bit C,W 1.007 step
3714

3712/ Curtain position &


Zigbee: {{Channel 1}}-x 1byte C,W,R,T 5.001 percentage
3715 status

These communication objects apply to curtain step/move, are used for KNX system to control

Zigbee electric curtain. Set the number of channels for the curtain by parameter, up to 2 channels, x=1/2.

Obj.3710/3713: Used for receiving the telegrams from KNX bus to control curtain open/close.

Telegrams:
1——Close the curtain
0——Open the curtain
Obj.3711/3714: Used for receiving the telegrams from KNX bus to stop curtain movement.

Telegrams:
1——Stop
Obj.3712/3715: Used for receiving the telegrams from KNX bus to control curtain position, and

return the status to bus. Telegrams: 0..100%

Table 6.3 “Zigbee Channel” communication object table

97
KNX/EIB KNX Gateway for Tuya ZigBee

6.4.“Room temperature controller” Communication Object

Fig.6.4 “Room temperature controller” communication object

Object Function Name Data Type Flag DPT


NO.
74 Power on/off RTC 1 1bit C,W 1.001 switch

The communication object is used to receive the telegram value of control RTC power on/off from
the bus. Telegrams:
1——On
0——Off

75 Room temperature sensor RTC 1 2byte C,W,T,U 9.001 temperature

The communication object is used to receive the room temperature from the bus, and send read

request cyclically, and also receive feedback.

76 Current setpoint adjustment RTC 1 2byte C,W 9.001 temperature

The communication object is used to modify the current setpoint value of temperature. Telegrams:

0..65535

77 Heating/Cooling mode RTC 1 1bit C,W 1.100 cooling/heating

The communication object is used to switch heating/cooling mode via the bus. Telegrams:

1——Heating

0——Cooling

98
KNX/EIB KNX Gateway for Tuya ZigBee

78 Operation mode RTC 1 1byte C,W 20.102 HVAC mode

79 Comfort mode RTC 1 1bit C,W 1.003 enable

80 Economy mode RTC 1 1bit C,W 1.003 enable

81 Frost/Heat protection mode RTC 1 1bit C,W 1.003 enable

82 Standby mode RTC 1 1bit C,W 1.003 enable

These communication objects are used to control RTC operation mode via the bus.
1byte: object 78 is visible. Telegrams: 1-comfort, 2-standby, 3-economy, 4-protection, other
reserved.
1bit:
Object 79——Comfort mode
Object 80——Economy mode
Object 81——Protection mode
Object 82——Standby mode
Activate corresponding mode when receive a telegram “1”. When 1bit standby mode is not enable,
and objects value of comfort, economy and protection are all 0, it is standby mode. When 1bit standby
mode is enable, the 1bit standby object receives 1 is standby mode, and telegram “0” will be ignored.

83 Fan automatic operation RTC 1 1bit C,W 1.003 enable

The communication object is used to activate fan automatic control via the bus. Telegrams:

1——Auto

0——Exit auto

84 Window contact RTC 1 1bit C,W,U 1.019 Window/door

The communication object is used to receive the switch status of window contact. Telegrams:
1——Open window
0——Close window

85 Presence detector RTC 1 1bit C,W,U 1.018 occupancy

The communication object is used to receive the room occupancy status from presence detector.
Telegrams:
1——Occupied
0——Not occupied
Current temperature setpoint,
86 RTC 1 2byte C,R,T 9.001 temperature
status

The communication object is used to send the current setpoint temperature of RTC to the bus.

Telegrams: 0..65535

99
KNX/EIB KNX Gateway for Tuya ZigBee

87 Heating/Cooling mode, status RTC 1 1bit C,R,T 1.100 cooling/heating

The communication object is used to feedback the telegram to the bus for switching heating and
cooling function.

88 Operation mode, status RTC 1 1byte C,R,T 20.102 HVAC mode

89 Comfort mode, status RTC 1 1bit C,R,T 1.003 enable

90 Economy mode, status RTC 1 1bit C,R,T 1.003 enable

Frost/Heat protection mode,


91 RTC 1 1bit C,R,T 1.003 enable
status

92 Standby mode, status RTC 1 1bit C,R,T 1.003 enable

These communication objects are used to send RTC operation mode status to the bus.
When 1 byte: object 88 is visible, telegrams: 1-comfort, 2-standby, 3-economy, 4-protection, other
reserved.
When 1bit:
Object 89—— Comfort mode
Object 90—— Economy mode
Object 91—— Protection mode
Object 92—— Standby mode
When a mode is activated, the corresponding object only sends telegram “1”. When 1 bit standby
object is not enable, activate standby mode when comfort, economy, protection objects send telegram
0 together. When 1 bit standby object is enable, activate standby mode only when standby object send
1.
Note: no requirement to send mode status to the bus when switchover via bus. The same is fan
speed and other operation.
1bit 1.001 switch
93 Heating control value, status RTC 1 C,R,T
1byte 5.001 percentage

1bit 1.001 switch


94 Cooling control value, status RTC 1 C,R,T
1byte 5.001 percentage

These communication objects are used to send control status of heating or cooling function to the
bus. Object datatype is according to parameter setting.
5.001 percentage
94 Fan speed, status RTC 1 1byte C,T
5.100 fan stage

The communication object is used to send the status of fan speed to the bus. The corresponding
telegram value of each fan speed is defined by the parameter.
Table 6.4 “Room temperature controller” communication object table

100
KNX/EIB KNX Gateway for Tuya ZigBee

6.5.“Ventilation controller” Communication Object

Fig.6.5 “Ventilation controller” communication object


NO. Object Function Name Data Type Flag DPT

294 Fan automatic operation Ventilation controller 1bit C,W 1.003 enable

The communication object is used to activate fan automatic control via the bus. Telegrams:
1——Auto
0——Exit auto
PM 2.5 value 7.001 pulse

295 VOC value Ventilation controller 2byte C,W,T,U 9.030 concentration(ug/m3)

CO2 value 9.008 parts/million(ppm)

The communication object is used to receive the input value of PM2.5/VOC/CO2, and get the
corresponding value from the bus and update it to the display, the corresponding object datatype is
defined by the parameter. Unit is ug/m3 or ppm. Range: 0~999ug/m3 or 0...4000ppm
For example, Control value of automatic operation is PM2.5, that is, under the automation, the
ventilation system can adjust the fan speed automatically according to PM2.5 concentration.
5.001 percentage
296 Fan speed, status Ventilation controller 1byte C,T
5.100 fan stage

297 Fan speed low, status Ventilation controller 1bit C,T 1.001 switch

Fan speed medium,


298 Ventilation controller 1bit C,T 1.001 switch
status

299 Fan speed high, status Ventilation controller 1bit C,T 1.001 switch

These communication objects are used to send control telegrams of the fan speed to the bus.
1byte: the corresponding telegram value of each fan speed is defined by the parameter. Object 296
sends the corresponding telegram value of the fan speed to the bus.
1bit:
Object 297——Low fan speed
Object 298——Medium fan speed
Object 299——High fan speed
The corresponding object sends telegram “1” to the bus, and sends telegram “0” is turn off fan
speed.
Table 6.5 “Ventilation controller” communication object table

101
KNX/EIB KNX Gateway for Tuya ZigBee

6.6.“Logic” Communication Object

6.6.1. “AND/OR/XOR” Communication Object

Fig.6.6.1 “AND/OR/XOR” Communication Object

NO. Object Function Name Data Type Flag DPT


2/... Input x 1st /.../8th Logic 1bit C,W,T,U 1.002 boolean

The communication object is used to receive the value of logical input Input x.
10 Logic result 1st /.../8th Logic 1bit C,T 1.002 boolean

The communication object is used to send the results of logical operation.


Table 6.6.1 “AND/OR/XOR” communication object table

102
KNX/EIB KNX Gateway for Tuya ZigBee

6.6.2. “Gate forwarding” Communication Object

Fig.6.6.2 “Gate forwarding” Communication Object


NO. Object Function Name Data Type Flag DPT
2 Gate value select 1st /.../8th Logic 1byte C,W 17.001 scene number

The communication object is used to select the scene of logical gate forwarding.
1.001 switch
1bit
3.007 dimming control
3/.../6 Input x 1st /.../8th Logic 4bit C,W
5.010 counter
1byte
pulses(0..255)

The communication object is used to receive the value of the logic gate input Input x.
1.001 switch
1bit
7/../1 3.007 dimming control
Output x 1st /.../8th Logic 4bit C,T
0 5.010 counter
1byte
pulses(0..255)

The communication object is used to output the value forwarded by the logic gate. The output
value is the same as the input value, but one input can be forwarded into one or more outputs, set by
parameters.
Table 6.6.2 “Gate forwarding” communication object table

103
KNX/EIB KNX Gateway for Tuya ZigBee

6.6.3. “Threshold comparator” Communication Object

Fig.6.6.3 “Threshold comparator” Communication Object

NO. Object Function Name Data Flag DPT


Type
2 Threshold value input 1st /.../8th Logic 4bit C,W, U 3.007 dimming control

1byte 5.010 counter

2byte pulses(0..255)

4byte 7.001 pulses

12.001 counter pulses

The communication object is used to input threshold value.

10 Logic result 1st /.../8th Logic 1bit C,T 1.002 boolean

The communication object is used to send the results of logical operation. That is, the value that
should be sent after the object input threshold is compared with the setting threshold value.

Table 6.6.3 “Threshold comparator” communication object table

6.6.4. “Format convert” Communication Object

“2x1bit --> 1x2bit”function: converts two 1bit values to a 2bit value, such as Input bit1=1, bit0=0-->
Output 2bit=2

“8x1bit --> 1x1byte”function: converts eight 1bit values to a 1byte value, such as Input bit2=1, bit1=1,
bit0=1,other bits are 0--> Output 1byte=7

104
KNX/EIB KNX Gateway for Tuya ZigBee

“1x1byte --> 1x2byte”function: converts one 1byte values to a 2byte value, such as Input 1byte=125-->
Output 2byte=125.Although the value remains the same, the data type of the value is different.

“2x1byte --> 1x2byte”function: converts two 1byte values to a 2byte value, such as Input 1byte-low
= 255 ($FF), Input 1byte-high = 100 ($64) --> Output 2byte = 25855 ($64 FF)

“2x2byte --> 1x4byte”function: converts two 2 byte values to a 4byte value, such as Input 2byte-low =
65530 ($FF FA), Input 2byte-high = 32768 ($80 00)--> Output 2byte = 2147549178 ($80 00 FF FA)

“1x1byte --> 8x1bit” function: converts one 1byte values to eight 1but value, such as Input 1byte=200 -->
Output bit0=0, bit1=0, bit2=0, bit3=1, bit4=0, bit5=0, bit6=1, bit7=1

“1x2byte --> 2x1byte”function: converts one 2byte values to two 2byte value, such as Input 2byte =
55500 ($D8 CC) --> Output 1byte-low = 204 ($CC), Output 1byte-high =216 ($D8)

“1x4byte --> 2x2byte”function: converts one 4byte values to two 2byte value, such asInput 4byte =
78009500 ($04 A6 54 9C) --> Output 2byte-low = 21660 ($54 9C), Output 2byte-high =1190 ($04 A6)

105
KNX/EIB KNX Gateway for Tuya ZigBee

“1x3byte --> 3x1byte”function: converts one 3byte values to three 1byte value, such as Input 3byte = $78
64 C8--> Output 1byte-low = 200 ($C8) , Output 1byte-middle = 100 ($64) , Output 1byte-high =120 ($78)

“3x1byte --> 1x3byte”function: converts three 1byte values to a 3byte value, such as Input 1byte-low =
150 ($96), Input 1byte-middle = 100 ($64), Input 1byte-high = 50 ($32)--> Output 3byte = $32 64 96
Fig.6.6.4 “Format convert” Communication Object

NO. Object Function Name Data Flag DPT


Type
1bit 1.001 switch

1byte 5.010 counter pulses(0..255)

2 Input ... 1st /.../8th Logic 2byte C,W,U 7.001 pulses

3byte 232.600 RGB value 3x(0..255)

4byte 12.001 counter pulses

The communication object is used to input a value that needs to be converted.


1bit 1.001 switch

2bit 2.001 switch control

1byte 5.010 counter pulses(0..255)


10 Output ... 1st /.../8th Logic C,T
2byte 7.001 pulses

3byte 232.600 RGB value 3x(0..255)

4byte 12.001 counter pulses

The communication object is used to output the converted value.


Table 6.6.4 “Format convert” communication object table

106
KNX/EIB KNX Gateway for Tuya ZigBee

6.6.5. “Gate function” Communication Object

Input/Output - 1bit[On/Off]

Input/Output - 1byte[0..100%]

Input/Output - 1byte[0..255]

Input/Output - 2byte[Float]

Input/Output - 2byte[0..65535]
Fig.6.6.5 “Gate function” Communication Object
NO. Object Function Name Data Type Flag DPT
1.001 switch

1bit 5.001 percentage

2 Input 1st /.../8th Logic 1byte C,W 5.010 counter pulses

2byte 9.001 temperature

7.001 pulses

The communication object is used to input a value that needs to gate filter.

3 Gate input 1st /.../8th Logic 1bit C,W 1.002 boolean

The communication object is used to control the switch status of gate input. Input signal is
allowed to pass when gate open, then output, and the current input status is still sent if there is a
change; Can not pass when gate close.
1.001 switch

bit 5.001 percentage

10 Output 1st /.../8th Logic 1byte C,T 5.010 counter pulses

2byte 9.001 temperature

7.001 pulses

The communication object is used to output the value after gate filtering. Only when gate input
status is open, output is available, defined by the object “Gate input”.

Table 6.6.5 “Gate function” communication object table

107
KNX/EIB KNX Gateway for Tuya ZigBee

6.6.6. “Delay function” Communication Object

Input/Output - 1bit[On/Off]

Input/Output - 1byte[0..100%]

Input/Output - 1byte[0..255]

Input/Output - 2byte[Float]

Input/Output - 2byte[0..65535]
Fig.6.6.6 “Delay function” Communication Object
NO. Object Function Name Data Type Flag DPT
1.001 switch

1bit 5.001 percentage

2 Input 1st /.../8th Logic 1byte C,W 5.010 counter pulses

2byte 9.001 temperature

7.001 pulses

The communication object is used to input a value that needs to delay.


1.001 switch

1bit 5.001 percentage

10 Output 1st /.../8th Logic 1byte C,T 5.010 counter pulses

2byte 9.001 temperature

7.001 pulses

The communication object is used to output that needs to delay converted value, delay time is

defined by the parameter.

Table 6.6.6 “Delay function” communication object table

108
KNX/EIB KNX Gateway for Tuya ZigBee

6.6.7. “Staircase lighting” Communication Object

Fig.6.6.7 “Staircase lighting” Communication Object

NO. Object Function Name Data Type Flag DPT

2 Trigger value 1st /.../8th Logic 1bit C,W 1.017 trigger

The communication object is used to receive the value to trigger staircase lighting.

3 Light-on duration time 1st /.../8th Logic 2byte C,W 7.005 time(s)

The communication object is used to modify the staircase light-on duration time, the modified

range is referenced from the range defined by the parameter, take the limit value if exceeded.

1bit 1.001 switch


10 Output 1st /.../8th Logic C,T
1byte 5.010 counter pulses

The communication object is used to output value 1 when trigger, and send value 2 after duration

time. Telegram value is determined by the parameter setting datatype.

Table 6.6.7 “Staircase lighting” communication object table

109
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 7 UI Description for Tuya Smart APP

This chapter detail UI use for Tuya Smart APP in functional blocks. Please make sure the database

is downloaded to KNX Gateway for Tuya ZigBee before operating APP. Once the database is

downloaded, you can add gateways and other devices on the APP.

7.1.Add device

Click icon on the mobile phone desk to start up Tuya Smart APP, register or login the account.

Click the icon in the upper right corner of homepage to add device after login successfully. Take

KNX Gateway for Tuya ZigBee as an example to explain the operation of adding a device.

Other devices are added in similar ways to the gateway, and no longer repeat in this chapter.

1. Select corresponding device type, KNX Gateway for Tuya ZigBee selects the Gateway in

Gateway Control. You can select to add it manually(Step 2~5), or select to click icon to auto scan,

please ensure that the device has entered paring mode, click blue word in the follow picture to go to the

details of “Auto Scan”. If failed to auto add device, you can select to Try again or Add Manually.

110
KNX/EIB KNX Gateway for Tuya ZigBee

Note: Please ensure to turn on Bluetooth, Wi-Fi and Location services, otherwise the APP cannot

search the device, and display the following prompt:

2. Click device icon, you can see the device connection steps. If the device is not reset, please

perform net pairing as prompted. If it has been reset, ignore step 3. Please note the LED indication

status on the gateway.

3. Reset device. Long press ZigBee connect button on the gateway for 5s, to remove the gateway

from the cloud, triggered to flash after manually operating the connect button, and flashing 5 times to

enter the waiting connection status. LED indication effect of gateway as follow:

LAN LED—Green LED:

——Always on after gateway network is connected OK, flashing when there is a data

communication.

Connect status LED—Green LED:

——Off when gateway is connected to cloud;

——Always on when connection is waiting to connect;

——Always flashing when Tuya authorization code is abnormal(Unprogram).

111
KNX/EIB KNX Gateway for Tuya ZigBee

4. Make sure the device reset is successful, and your phone and the gateway are under the same

network. Then make sure the device LED is indicated correctly. The gateway confirms that the two

green lights(Connect status LED and LAN LED) are always on, then click Next to enter the status for

connecting device.

5. Add device. When scan the “KNXGateway”, click the icon to complete the addition.

Note: For Android systems, if the gateway fails to connect several times, it need to clear cache.

Click icon in the upper right corner of【Me】interface to enter the settings page, select【Clear

Cache】.

112
KNX/EIB KNX Gateway for Tuya ZigBee

6. After completing the above steps, display setting page of the device, and displays a list of the

added subdevices. Click “Add subdevice” to search device for addition.

As below, the interactive use of KNX channel devices will be described in detail.

113
KNX/EIB KNX Gateway for Tuya ZigBee

7.2. Device information

Click the icon to check the Gateway information, which is shown in the figure below. The last

bit is hidden from the IP address.

If you want to use IP address, when IP assignment is set as Fixed mode, IP address is assigned

from the parameters on ETS; while IP assignment is DHCP mode, at first, you should enter the

background of the router which is connected to the gateway, then you can see IP address of the

gateway. (The ways to enter the router background are different, detail please refer to the router

manual.)

114
KNX/EIB KNX Gateway for Tuya ZigBee

7.3.Switch interface



Fig.7.2(1) Switch interface Fig.7.2(2) Device basic settings Fig.7.2(3) Info editing interface

①Return to the previous interface.

②Device name, shown it above the interface. Click icon to go to figure7.2(2), you can view, change

device settings, and remove devices.

Device basic settings as shown in figure 7.2 (2), including Device Information, Tap-to-Run and

Automation, Other settings, and Remove Device. Set the Tap-to-Run and Automation via KNX scene

switch, details in chapter 7.7.

Click ④ to go to figure7.2(3), you can edit current device name, icon and location.

③Switch button, gray indicates status off, bright color indicates status on. Used for switching of switch

status.

115
KNX/EIB KNX Gateway for Tuya ZigBee

7.4.Switch/Dimming interface

Fig.7.3(1) Switch/Dimming interface

①Return to the previous interface.

②Device name, shown it above the interface. Click icon , you can view, change device settings, and

remove devices.

③B: brightness adjustment. Adjust brightness by sliding this slider, range: 0..100%

④LED switch button, gray indicates status off, bright color indicates status on. Used for switching of

switch status. When brightness value is not 0, touch this button to close brightness, and value is 0.

116
KNX/EIB KNX Gateway for Tuya ZigBee

7.5.RGB Dimming interface




Fig.7.4(1) RGB dimming interface Fig.7.4(2)RGBW dimming interface Fig.7.4(3)Color temperature


interface

①Return to the previous interface.

②Device name, shown it above the interface. Click icon , you can view, change device settings, and

remove devices.

There are 3 control types of RGB dimming function: RGB, RGBW, Color Temperature. Among them,

RGB is suitable for adjusting RGB lamp; RGBW is suitable for controlling RGBW strip; Color Temperature

is suitable for color temperature control. Shown as figure7.4(1)(2)(3).

③RGB value adjustment. Adjust brightness by sliding R/G/B slider, range: 0..255

④RGBW value adjustment. Adjust brightness by sliding R/G/B/W slider, range: 0..255

⑤B: brightness adjustment. Adjust brightness by sliding this slider, range: 0..100%

CW: color temperature adjustment. Adjust color temperature by sliding this slider, range:

2000..7000K

⑥LED switch button, gray indicates status off, bright color indicates status on. When current value is

not 0, touch this button to close R/G/B/W or B/CW, and value is 0.

117
KNX/EIB KNX Gateway for Tuya ZigBee

7.6.Curtain control interface





Fig.7.5(1)Curtain step/move Fig.7.5(2)Roller blind step/move Fig.7.5(3)Curtain


position


⑧ ⑩

Fig.7.5(4)Roller blind position Fig.7.5(5)Venetian blind position and slat


①Return to the previous interface.

②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.

③Curtain step/move:
1)Touch icon , open curtain. Device sends out a telegram with the object(Open/Close) value of 0;
2)Touch icon , stop curtain. Device sends out a telegram with the object(Stop) value of 1;
3)Touch icon , close curtain. Device sends out a telegram with the object(Open/Close) value of
1;

118
KNX/EIB KNX Gateway for Tuya ZigBee

④Roller blind step/move:


1)Touch icon , move up blind. Device sends out a telegram with the object(Up/Down) value of 0;
2)Touch icon , stop blind. Device sends out a telegram with the object(Stop) value of 1;
3)Touch icon , move down blind. Device sends out a telegram with the object(Up/Down) value of
1;

⑤⑥Curtain position:
1)By sliding the slider⑤ to adjust the position of curtain;
2) Operation of Open/Close/Stop are the same as above.

⑦⑧Roller blind position:


1)By sliding the slider⑦ to adjust the position of blind;
2) Operation of Up/Down/Stop are the same as above.

⑨⑩Venetian blind position and slat:


1)By sliding the slider⑨ to adjust the position and louver angle of venetian blind;
2) Operation of Up/Down/Stop are the same as above.

119
KNX/EIB KNX Gateway for Tuya ZigBee

7.7.Value sender interface


Fig.7.6Value sender

①Return to the previous interface.


②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
③Touch icon, send telegram to KNX bus. Only used to trigger calling command on the APP, with only
button operation.
There are 8 value types sent: 1bit[On/Off], 2bit[0..3], 1byte[0..255], 1byte[0..100%], 1byte[scene
control], 2byte[-671 088.64..670 760.96], 2byte[0..65535].

120
KNX/EIB KNX Gateway for Tuya ZigBee

7.8.KNX Scene switch interface


Fig.7.7(1) Scene switch interface


①Return to the previous interface.
②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
③Long press to enter the scene setting, receive KNX scene calling command, or short press on the

APP to perform action set in scene setting, link the KNX device functions to the ZigBee on the APP.

Configure specific associated devices and trigger responses for scene on the APP before operation.

Add scene setting:


① ⑤
② ⑥



Fig.7.7(2) Scene switch setting Fig.7.7(3) Create Smart Fig.7.7(4) Add task

①⑤Return to the previous interface.

②Click to save the setting and return to the previous interface after scene switch setting.

121
KNX/EIB KNX Gateway for Tuya ZigBee

③Click to modify scene icon.

④Click to go to the interface Create Smart, shown as figure7.7(3).

⑥Click to save the setting and return to the previous interface after creating smart.

⑦Click plus icon to create“Tap-To-Run” task, the window⑨ is pop up below, you can select required

setting, including: all devices, smart scenes, notification and the action delay. Task is shown in figure

7.7(3) after creating successfully.

⑧Set the task name, display style, and whether to show on home page.

Manage scene setting:

③ ⑥ ⑦



Fig.7.7(5) Smart interface Fig.7.7(6) Manage interface Fig.7.7(7) Edit interface

①Click three-point icon, display drop-down window, you can select 【Manage】 or 【Logs】, shown as
figure 7.7(5). Click【Manage】to go to manage interface, shown as figure 7.7(6). Long press icon④ to
slide, to adjust the order of scene tasks; click icon⑤ to delete the scene task.
②Click three-point icon, go to the scene edit interface, shown as 7.7(7), operation in the interface: add
task, change the task name and display style, whether to show on home page, and delete the scene.
Click on the rest of the control to perform the scene immediately.
Operate the edit interface also can be via the single device, such as figure 7.2 (2) device basic setting,
to click Tap-to-Run and Automation.
③Click to save and return to previous interface after task management.
⑥Click to cancel edit, and return to previous interface.
⑦Click to save and return to previous interface after editing.

122
KNX/EIB KNX Gateway for Tuya ZigBee

7.9.Air condition interface




Fig.7.8(1) Air condition interface Fig.7.8(2) Air condition (with swing) interface

①Return to the previous interface.

②Device name, shown it above the interface. Click icon , you can view, change device settings, and

remove devices.

③Ring slider is used to adjust the setpoint temperature, the performed adjustment step is 1℃. When

temperature unit is set to degrees Celsius (℃), adjustment range of setpoint temperature is default as

16 ~ 32℃; Current temperature display according the parameter configuration, you can configure to

show detected temperature of internal senor or external sensor.

④Click this icon to switch Air condition control mode, update the mode status via the object: Heat ,

Cool , Dehumidification , Fan , Auto .

⑤Click this icon to switch fan speed, the current fan speed is cyclically switched in this order--Low

speed...AUTO...Low speed: Low speed , Medium speed , High speed , Auto .

⑥Click this icon switch swing control: swing , stop .

⑦Air condition switch button, gray indicates status off, bright color indicates status on. When power off,

except for the status of power on/off, the other icon status can not be updated via the bus or manually

controlled. Click this icon, device sends a telegram of value 1/0 (On/Off) via the object Power on/off.

123
KNX/EIB KNX Gateway for Tuya ZigBee

7.10. Room temperature unit interface


④ ⑤

Fig.7.8(1) RTC interface Fig.7.8(2) RTC (with operation mode) interface

Fig.7.8(3) RTC (with operation mode&fan)

①Return to the previous interface.

②Device name, shown it above the interface. Click icon , you can view, change device settings, and

remove devices.

③Ring slider is used to adjust the setpoint temperature, the performed adjustment step is 1℃. When

temperature unit is set to degrees Celsius (℃), adjustment range of setpoint temperature is default as

5 ~ 40℃; Current temperature display according the parameter configuration, you can configure to

124
KNX/EIB KNX Gateway for Tuya ZigBee

show detected temperature of internal senor or external sensor.

④Click this icon to switch control mode, update the mode status via the object: Heating ,

cooling. .

You can switch the mode via touch or telegram when the database sets the RTC control mode to

“Heating and Cooling”.

⑤Click this icon to switch operation mode: comfort , standby , economy , protection

⑥Click this icon to switch fan speed, the current fan speed is cyclically switched in this order--Low

speed...AUTO...Low speed: Low speed , Medium speed , High speed , Auto .

⑦RTC switch button, gray indicates status off, bright color indicates status on. When power off, except

for the status of power on/off, the other icon status can not be updated via the bus or manually

controlled. Click this icon, device sends a telegram of value 1/0 (On/Off) via the object Power on/off.

7.11. Ventilation system interface




Fig. 7.10 Ventilation system control interface

125
KNX/EIB KNX Gateway for Tuya ZigBee

①Return to the previous interface.

②Device name, shown it above the interface. Click icon , you can view, change device settings, and

remove devices.

③It is used to display the switch status of filter.

④Click this icon to switch fan speed, the current fan speed is cyclically switched in this order--Low

speed...AUTO...Low speed: Low speed , Medium speed , High speed , Auto .

⑤Click the icon to turn on or off heat recovery function.

⑥Ventilation switch button, gray indicates status off, bright color indicates status on. When power off,

except for the status of power on/off, the other icon status can not be updated via the bus or manually

controlled. Click this icon, device sends a telegram of value 1/0 (On/Off) via the object Power on/off.

7.12. Audio control interface



Fig.7.11(1) Audio control interface Fig.7.11(2) Audio control (with on/off) interface
①Return to the previous interface.

②Device name, shown it above the interface. Click icon , you can view, change device settings, and

remove devices.

③Click the icon to adjust the volume in increasing or decreasing increments.

④Slide the slider to adjust the volume decrease/increase.

126
KNX/EIB KNX Gateway for Tuya ZigBee

⑤Click the icon to mute/exit mute: mute , exit mute .

⑥Click the button to switch the audio play mode. Update the status via the object: single loop , list

play , random play .

⑦Click the icon to select previous song or next song.

⑧Click the icon to play or stop music. And update the status via the object.

⑨Audio control switch button, gray indicates status off, bright color indicates status on. When power

off, except for the status of power on/off, the other icon status can not be updated via the bus or

manually controlled. Click this icon, device sends a telegram of value 1/0 (On/Off) via the object Power

on/off.

7.13. Sensor interface

Air quality sensor interface CO2 sensor interface PM2.5 sensor interface VOC sensor
interface

Air quality sensor displays 7 reference values, independently is: CO2, PM2.5, PM10, VOC,

Temperature, Humidity, AQI. What displays can be configured through the database. The CO2, PM2.5

and VOC have separate detectors, and all can show the internal temperature and humidity on the

interface.

The ring on the interface and the reference values of corresponding devices. The update of the

display value can be achieved by rewriting the object via the bus.

Detection range of AQI: 0..500

127
KNX/EIB KNX Gateway for Tuya ZigBee

Detection range of CO2: 0..4000ppm

Detection range of PM2.5: 0..999ug/m3

Detection range of VOC: 0..999ug/m3

Detection range of temperature: -50...90℃

Detection range of humidity: 0..100%

Presence sensor interface Motion sensor interface Brightness sensor interface I/O signal interface

Presence sensor can detect PIR state, and illuminance, detection range: 0...65535lux

Motion sensor can detect PIR state.

Brightness sensor can detect the illuminance, detection range: 0...65535lux

I/O signal can detect the device switch status.

128
KNX/EIB KNX Gateway for Tuya ZigBee

7.14. Current/Energy metering interface

Current metering Energy metering

Current metering detects the current and power, and display the changing status in real-time, the

values unit and resolution can be rewrite via the object on the bus.

Energy metering detects the current, power, voltage and energy, and display the changing status in

real-time, the values unit and resolution can be rewrite via the object on the bus.

129
KNX/EIB KNX Gateway for Tuya ZigBee

7.15. Voice control command

This chapter mainly list the voice control commands for Tuya Smart APP. You can find the

command of ETS function to voice control. Note: Currently , only the devices listed below are

supported.

Voice control command


Note: the specific content in < > is determined by the name edited on the
ETS functions
APP. Only support English. The same as below.
Amazon Alexa Google Assistant
Alexa, turn on <device name> OK Google, turn on <device name>
Switch
Alexa, turn off <device name> OK Google, turn off <device name>

Switch: Switch:

Alexa, turn on <device name> OK Google, turn on <device name>

Alexa, turn off <device name> OK Google, turn off <device name>

Dimming: Dimming:

Alexa, set the bedroom light to fifty percent OK Google, what is the brightness level of
Switch/Dimming
Alexa, brighten <device name> <device name>?

Alexa, dim <device name> OK Google, adjust <device name> to 65%

brightness

OK Google, brighten the <device name>

OK Google, dim the <device name>


Switch: Switch:

RGB Dimming Alexa, turn on <device name> OK Google, turn on <device name>

Alexa, turn off <device name> OK Google, turn off <device name>
Switch: Switch:

RGBW Dimming Alexa, turn on <device name> OK Google, turn on <device name>

Alexa, turn off <device name> OK Google, turn off <device name>

Switch: Switch:

Alexa, turn on <device name> OK Google, turn on <device name>

Alexa, turn off <device name> OK Google, turn off <device name>
Color
Dimming:
Temperature
Alexa, set the bedroom light to fifty percent

Alexa, brighten <device name>

Alexa, dim <device name>

130
KNX/EIB KNX Gateway for Tuya ZigBee

Voice control command


ETS functions
Amazon Alexa Google Assistant

Color temperature: Dimming:

Alexa, make the living room lights warmer OK Google, what is the brightness level
Alexa, set the dining room lights cooler of <device name>?
Alexa, set the dining room softer OK Google, adjust <device name> to
Alexa, make the living room light whiter 65% brightness
Color
Alexa, make the living room light warm OK Google, brighten the <device name>
Temperature
white OK Google, dim the <device name>
Alexa, set the kitchen to daylight Color temperature:

OK Google, set the <device name> to


cool white

Curtain switch: Curtain switch:

Alexa, turn on <device name> OK Google, turn on <device name>


Curtain Alexa, turn off <device name> OK Google, turn off <device name>
step/move Work status:
OK Google, pause <device name>
OK Google, resume <device name>
Curtain switch: Curtain switch:

Alexa, turn on <device name> OK Google, turn on <device name>


Roller blind Alexa, turn off <device name> OK Google, turn off <device name>
step/move Work status:
OK Google, pause <device name>
OK Google, resume <device name>
Curtain switch: Curtain switch:

Alexa, turn on <device name> OK Google, turn on <device name>


Alexa, turn off <device name> OK Google, turn off <device name>
Percentage position: Work status:
Alexa, set the <device name> to thirty OK Google, pause <device name>
Curtain position
percent OK Google, resume <device name>
Alexa, increase <device name> by ten Percentage position:
percent OK Google, open <device name>
Alexa, decrease <device name> by twenty OK Google, close <device name>
percent

131
KNX/EIB KNX Gateway for Tuya ZigBee

Voice control command


ETS functions
Amazon Alexa Google Assistant

Curtain switch: Curtain switch:


Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Percentage position: Work status:
Roller blind Alexa, set the <device name> to thirty OK Google, pause <device name>
position percent OK Google, resume <device name>
Alexa, increase <device name> by ten Percentage position:
percent OK Google, open <device name>
Alexa, decrease <device name> by twenty OK Google, close <device name>
percent
Curtain switch: Curtain switch:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Venetian blind
Work status: Work status:
position and slat
Alexa, pause device OK Google, start the washing machine
Alexa, resume device OK Google, stop <device name>
Value sender Alexa, turn on <device name> OK Google, turn on <device name>
/Scene switch Alexa, turn off <device name> OK Google, turn off <device name>

Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Control mode: Control mode:
Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
name> to <mode value> value>
Temperature: Temperature:
Alexa, make it warmer in here OK Google, set the <device name> to
Alexa, make it cooler in here 350 degrees
Air conditioner Alexa, what is the target temperature of the Check actual temperature:
<device name>? OK Google, what is the current device
Alexa, set <device name> to twenty temperature?
Alexa, set <device name> to N Fan speed level:
Check actual temperature: OK Google, set the <device name> to
Alexa, what is the temperature of <device low
name> OK Google, set the <device name> to
Fan speed level: high
Alexa, set the fan speed on the <device
name> to <mode value>

132
KNX/EIB KNX Gateway for Tuya ZigBee

ETS Voice control command

functions Amazon Alexa Google Assistant

Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Control mode: Control mode:
Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
name> to <mode value> value>
Temperature: Temperature:
Alexa, make it warmer in here OK Google, set the <device name> to 350
Alexa, make it cooler in here degrees
Alexa, what is the target temperature of the Check actual temperature:
<device name>? OK Google, what is the current device
Air condition Alexa, set <device name> to twenty temperature?
(with swing) Alexa, set <device name> to N Fan speed level:
Check actual temperature: OK Google, set the <device name> to low
Alexa, what is the temperature of <device OK Google, set the <device name> to
name> high
Fan speed level: Swing:
Alexa, set the fan speed on the <device Turn on/off <device name>
name> to <mode value>
Swing:
Alexa, turn on horizontal swing on <device
name>
Alexa, turn off horizontal swing on <device
name>

133
KNX/EIB KNX Gateway for Tuya ZigBee

ETS Voice control command

functions Amazon Alexa Google Assistant

Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Control mode: Control mode:

Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
name> to <mode name> value>
Temperature: Temperature:
Room
Alexa, make it warmer in here OK Google, set the <device name> to 350
temperature
Alexa, make it cooler in here degrees
unit
Alexa, what is the target temperature of the Check actual temperature:

<device name>? OK Google, what is the current device


Alexa, set <device name> to twenty temperature?
Alexa, set <device name> to N
Check actual temperature:

Alexa, what is the temperature of <device


name>
Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Operation/Control mode: Operation/Control mode:

Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
name> to <mode name> value>
Room
Temperature: Temperature:
temperature
Alexa, make it warmer in here OK Google, set the <device name> to 350
unit
Alexa, make it cooler in here degrees
(with operation
Alexa, what is the target temperature of the Check actual temperature:
mode)
<device name>? OK Google, what is the current device
Alexa, set <device name> to twenty temperature?
Alexa, set <device name> to N
Check actual temperature:
Alexa, what is the temperature of <device
name>

134
KNX/EIB KNX Gateway for Tuya ZigBee

Voice control command


ETS
functions
Amazon Alexa Google Assistant

Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>

Alexa, turn off <device name> OK Google, turn off <device name>
Operation/Control mode: Operation/Control mode:

Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode

name> to <mode name> value>


Temperature: Temperature:
Room
Alexa, make it warmer in here OK Google, set the <device name> to 350
temperature
Alexa, make it cooler in here degrees
unit
Alexa, what is the target temperature of the Check actual temperature:
(with
<device name>? OK Google, what is the current device
operation
Alexa, set <device name> to twenty temperature?
mode & fan
Alexa, set <device name> to N Fan speed level:
speed)
Check actual temperature: OK Google, set the <device name> to low

Alexa, what is the temperature of <device OK Google, set the <device name> to high

name>
Fan speed level:

Alexa, set the fan speed on the <device


name> to <mode value>

Power:
Alexa, turn on <device name>

Alexa, turn off <device name>


Ventilation Fan speed level:

system Alexa, set the fan speed on the <device


name> to <mode value>

135
KNX/EIB KNX Gateway for Tuya ZigBee

ETS Voice control command

functions Amazon Alexa Google Assistant

Volume: Volume:
Alexa, set the volume of the speakers to OK Google, make the <device name> a
fifty little quieter
Alexa, turn the volume down on the stereo OK Google, mute <device name>
by twenty Mute mode:

Alexa, turn the volume down on Living Turn on <device name>


Audio control
Room TV Turn off <device name>
Alexa, mute speakers
Alexa, unmute speakers
Track change:
Alexa, previous on device
Alexa, next song/video/photo on device
Power: Power:
Alexa, open <device name> OK Google, turn on <device name>
Alexa, close <device name> OK Google, turn off <device name>
Audio Play/pause:
control(with Alexa, pause device
on/off) Alexa, resume device
Track change:
Alexa, previous on device
Alexa, next song/video/photo on device
Temperature check: Temperature check:
Alexa, what is the temperature of <device OK Google, what is the current device
name> temperature?
Humidity check: Humidity check:
Alexa, what is the bedroom humidity? OK Google, what humidity does my
Air quality CO2 check: humidifier show?
sensor Alexa, what's the <device name> <range CO2 check:
name>? OK Google, is the <sensor name>
detecting carbon dioxide
OK Google, Is carbon dioxide detected
OK Google, do you detect carbon
dioxide in the room

136
KNX/EIB KNX Gateway for Tuya ZigBee

ETS Voice control command

functions Amazon Alexa Google Assistant

Alexa, what's the <device name> <range OK Google, is the <sensor name>
name>? detecting carbon dioxide
CO2 sensor OK Google, Is carbon dioxide detected
OK Google, do you detect carbon
dioxide in the room
Presence Alexa, what's the <device name> <range
sensor name>?
Brightness Alexa, what's the <device name> <range
sensor name>?

137
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 8 Tuya Zigbee Gateway Management System

Tuya Zigbee Gateway Management System only apply to KNX Gateway for Tuya ZigBee,Premium,

use web to configure and manage the links between ZigBee devices and KNX system. Before enter to

the system, please ensure that the gateway is connected to LAN correctly, then configure IP address

and Zigbee channel via ETS. This management system only makes secondary configuration for the

devices.

Ensure the computer and mobile phone is in the same LAN, then enter IP address of the gateway in

the browser to enter Management System. The system operation and ZigBee device linking will be

explained in the following chapters.

138
KNX/EIB KNX Gateway for Tuya ZigBee

8.1.Gateway information

In the system, you can see the based information of the gateway, including the IP address, MAC

address, default gateway address, Tuya license account and password, and firmware version.

Click the upper right corner of the webpage to switch languages : Chinese; English.

Note: if description of ZigBee channel is set as Chinese character, please set the codepage of

project to UTF-8 at first, or that will display abnormally on the Management System after download the

ETS. The setting of codepage as shown as following:

139
KNX/EIB KNX Gateway for Tuya ZigBee

8.2.ZigBee device list

Click “ZigBee device list”, you can view the information of ZigBee devices that are linked/to be

linked. As follow:

Virtual ID Assigned automatically by the system.

Name Display ZigBee device name. User can customize the name, if it is not

defined, it will be empty.

MAC MAC address of the device.

Status Online/Offline

KNX Name The name configured in ETS.

ZigBee Channel Display the bound ZigBee channel number, corresponding to the ETS

setting, number is 1~32.

Operation DVC: use to link the ZigBee device to corresponding ZigBee channel.

setting FUN: use to link the ZigBee device to corresponding ZigBee function.

EDIT: use to change ZigBee device name.

DEL: use to delete the linking information of ZigBee device.

Note: If the device is already linked, the DVC button is not operable. If

the device is not linked, FUN/DEL buttons are not operable.

140
KNX/EIB KNX Gateway for Tuya ZigBee

8.3.ZigBee function list

Click “ZigBee function list”, you can view the information of ZigBee functions that are already

linked. The detail operation you can refer to chapter 8.4.

Device Display device name, you can change it in “Operation setting” of “ZigBee

device list”.

MAC Display MAC address of the device.

Fun.ID Display the function ID number that is linked.

Data mode Display the data transmission mode of the device. There are 3 modes:

Status: ZigBee device only uploads the current status value to the

management system or KNX;

Control: ZigBee device only receives the control command from other

terminals (such as APP and KNX).

Status/Control: ZigBee device not only can upload the current status

value, but also can receive the control command.

Status value Display the status value fed back from ZigBee device to KNX bus.

Note: data with decimal point is displayed as an integer, for example, the

value is 26.7, and the system displays 267; The value is 77%, and the

system displays 766.

Device type Display the ZigBee device type, according to the linked channel and

function.

Linking Display the linked ZigBee function, you can change it in “Operation

setting” of “ZigBee device list”.

141
KNX/EIB KNX Gateway for Tuya ZigBee

8.4.Linking the ZigBee device

Operation of linking the ZigBee device is as follow:

(1)Firstly, configure ZigBee channel in ETS, including name, MAC address, device type and etc..

Then download to the gateway, add the gateway and sub devices to Tuya Smart APP according to

chapter 7.1. Enter the gateway IP address in the browser into Tuya Zigbee Gateway Management

System, it displays ZigBee devices that are linked/to be linked, as shown as follow:

(2)Link KNX function. View the MAC address on the APP firstly, each ZigBee device has

corresponding unique MAC address. Click the DVC button in “ZigBee device list” page, pop-up the

setting page, then click on the “Function selection” drop-down box, select the corresponding function to

link, and then display the KNX name, which is configured in ETS and can not change. “ZigBee Device

Name” is customized by the user. Click “Submit” after completion.

(3)After completing the last step, auto return to “ZigBee device list” page, when the column of the

“ZigBee Channel” has number displayed, the device is linked to the ZigBee channel. At this time, the

DVC button can no longer be operated.

142
KNX/EIB KNX Gateway for Tuya ZigBee

Note:

The same ZigBee channel can not be linked to multiple ZigBee devices, or it will pop-up the

prompt to change channel.

If preset MAC address in ETS, as shown as follow, the gateway will assign the channel linking

automatically to the ZigBee device with this MAC address. There is no need to do steps (2) and (3) on

the system and DVC button is not operable at this time, it only need to operate step (4) to link the

ZigBee function.

MAC address can be obtained from Device information in Tuya Smart APP. View the device MAC

address as follow:

If not preset MAC address, system displays the ZigBee devices scanned by the gateway , follow

the steps to link the ZigBee channel and function.

(4)Link the ZigBee function. When the device is linked the ZigBee channel, click the FUN button in

the “ZigBee device list” page, pop-up the setting page, setting as follow:

143
KNX/EIB KNX Gateway for Tuya ZigBee

Fun.ID Display the ZigBee function number.

Type Display the function type (bool, value, enumeration, character and etc.).

Data mode Display the data mode of the function , there are 3 modes: Status; Control;

Status/Control.

Status value Display status value of the conrresponding function.

Note: data with decimal point is displayed as an integer, for example, the value

is 77%, and the system displays 766.

Linking Display the linked ZigBee function.

Operation Operate ZigBee device function on the APP, if the status value in the setting

setting page changes and is similar to the status information on the APP (If there are

no changes, please refresh the system), then click on the “Function selection”

drop-down box, select the corresponding function to link.

e.g: The dimming device with the MAC address bc33acfffe452684 is linked to

the ZigBee channel on the system, then operate the device on the APP,

Function ID1=1 and ID2=766 is corresponding to dimmer ON and brightness

value 77% on the APP, as shown as above figure. Click the “Function selection”

drop-down box according to the status value and select the corresponding

function to link.

ZigBee function linking for other devices can be analogized.

(5)After completing the function linking, display the configured ZigBee device on the “ZigBee

function list” page.

144
KNX/EIB KNX Gateway for Tuya ZigBee

(6)After completing the above steps, you can control ZigBee devices via KNX or Tuya Smart APP,

and also can upload the current status of the ZigBee device to the cloud or KNX.

(7)Edit the device name. Click EDIT button on the “ZigBee device list” page, pop-up the setting page,

enter the custom name in “Device Name” input box, click “OK”, then the device name can be replaced.

(8)Remove the device linking. Click DEL button on the “ZigBee device list” page, pop-up the page to

select whether to delete, click “OK”, then clean the linking information of the ZigBee device. As shown

as follow.

Note: After deletion, the item will be automatically arranged at the last of the list, and the FUN /

DEL button are inoperable at this time.

145
KNX/EIB KNX Gateway for Tuya ZigBee

Chapter 9 OTA for KNX Gateway for Tuya ZigBee

KNX Gateway for Tuya ZigBee upgrades new firmware remotely (OTA) via Tuya Smart APP.

Operation as follow:

(1)Enter the gateway home page, if there is a new device firmware released, the page will pop up

the update reminder. If the new firmware is released but you do not receive the update, please contact

GVS technical support.

(2)Click “Update Now” to enter the Device Update page, which notes the Main Module New Version

and the update content. Then click “Update”, pup up the update reminder, please ensure that the power

supply for gateway is normal during updating, and it will be unavailable during the update, then click

“Start update”.

146
KNX/EIB KNX Gateway for Tuya ZigBee

User can set the gateway to update automatically. But some key device features still need to be

confirmed to update.

(4) After entering the update status, the page is shown in the figure below, please do not do

anything at this time. Wait about 1 minute, the APP prompt update success.

(5) Check the device update. Click the icon in the gateway home page to enter management

page, click “Device Update”, if upgraded, it will show “No updates available” and Main Module

version; if there is a new update, you can follow these steps above to update.