User Manual: KNX Gateway For Tuya Zigbee - V2.0
User Manual: KNX Gateway For Tuya Zigbee - V2.0
wet environment;
2. Do not fall the device to the ground or make them get hard impact;
Chapter 1 Summary
KNX Gateway for Tuya ZigBee as the interface between KNX system and Tuya ZigBee system,
realizing the connection between the Tuya ZigBee ecosystem and the KNX system. Based on the
gateway, it can easily control the KNX devices with Tuya APP, and upload status information of KNX
devices to Tuya platform, for monitoring and managing the devices conveniently.
This manual provides detailed technical information about the KNX Gateway for Tuya ZigBee,
including installation and programming details, and explains how to use it in the practical examples.
After setting up KNX Gateway for Tuya ZigBee on the ETS, you can smartly manage the KNX and Zigbee
system products, add and use the devices through the supporting mobile APP——Tuya Smart.
KNX Gateway for Tuya ZigBee powered from KNX bus, and need a 12-30V DC auxiliary supply
voltage. It is available to assign the physical address and configure the parameters by engineering
As a ZigBee Gateway function, it can connect to Tuya Cloud, and add ZigBee device of
Support uploading KNX devices to Tuya platform for management, to control KNX device
Support KNX devices functions, including Switch, Dimming, Curtains, Scenes, Color and
Color temperature control, Audio control, HVAC control(Room temperature control, Air
humidity, Brightness, Gas, I/O signal and etc.), and Current, Energy Metering display
Logic functions
Support bidirectional communication between ZigBee and KNX device(only for premium
version BTMO-TY/00.3(4))
1
KNX/EIB KNX Gateway for Tuya ZigBee
Storage – 25 °C ... 55 °C
Transport – 25 °C ... 70 °C
Dimension 36 x 90 x 64mm
Weight 0.15kg
2
KNX/EIB KNX Gateway for Tuya ZigBee
3
KNX/EIB KNX Gateway for Tuya ZigBee
General function
Support to upload the KNX device to the Tuya platform for management, which to control the
device and display status. Up to support 150 devices. Each device can be customized its name with the
engineering design tools ETS, and has In operation setting to monitor whether the device is online and
upload to APP.
Top 100 device channels support the whole functions, including switch, dimming, curtain, scene
switch, color and color temperature (RGB, RGBW and color temperature), audio control, HVAC control
(Room temperature control, Air conditioner and Ventilation), multiple sensors (Air quality, humidity and
temperature, brightness, gas, I/O signal and etc.), and current, energy display.
The latter 50 device channels only support the functions, including switch, dimming, curtain, air
Note: Request each device status when the gateway power on.
4
KNX/EIB KNX Gateway for Tuya ZigBee
Support bidirectional communication between ZigBee and KNX device, for integrating Zigbee
devices into KNX system, up to 32 device data points, which can be set with name and MAC address
information on the ETS. Use the website (Tuya Zigbee Gateway Management System) to configure and
Support to control the following Zigbee devices with the KNX system:
Sensor: Air quality sensor, Temperature and humidity sensor, Brightness sensor, Gas sensor, and
Zigbee lamp: lamp, dimmable lamp, RGB bulb/strip, color temperature light and RGBCW bulb;
Electric curtain.
Up to support 10 room temperature controllers. Mainly used to control the room temperature,
Automatically and optimally cooling/heating control according to the room use or the occupants needs.
Support to manual switch to heating/cooling control, optionally three fan speeds and the auto fan
The temperature setpoint value supports the relative setting method, and is adjustable range
Ventilation controller
Support 1 ventilation controller, and fan speed can be linked to PM2.5/CO2/VOC, optionally output
Logic function
Up to support 8 channels of logic, each channel up to support 8 inputs and 1 logic result.
Logic function support functions, including AND, OR, XOR, Gate forwarding, Threshold comparator,
5
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the delay time to send to bus after the gateway power on. Options:
0..15
The setting dose not contain the gateway initialization time, and bus telegrams received during
delay time will be recorded.
This parameter is for setting the time interval when this device cycle send telegrams through the
bus to indicate this module in normal operation. When set to “0”, the object “in operation” will not send
a telegram. If the setting is not “0”, the object “In operation” will send a telegram according to the set
period time with logic “1” to the bus. Options: 0...240s, 0= inactive
As to reduce the bus load as much as possible, the maximum time interval should be selected
according to actual needs.
6
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the IP address of device, and the IP address must be unique in the
LAN, otherwise causing a conflict between IP.
Enter the address in IPv4 format, for example: 192.168.1.10
Options: 0-255.0-255.0-255.0-255
——Parameter “Default Gateway”
This parameter is for setting the default gateway. That is the default gateway of network segment
which the device connects to.
Enter the address in IPv4 format, for example: 192.168.1.1
Options: 0-255.0-255.0-255.0-255
——Parameter “Subnet Mask”
This parameter is for setting the subnet mask. That is the subnet mask of network segment which
the device connects to.
Enter the address in IPv4 format, for example: 255.255.255.0
Options: 0-255.0-255.0-255.0-255
——Parameter “DNS server”
7
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting whether to send read request telegram of status after restart device.
This parameter is visible when previous parameter is enabled. Set the interval time for sending
between request telegrams when power on. Options:
50ms
100ms
200ms
This parameter is for setting the read request period to send to query the online status of the
common device, 0 is not enable query function. Options: 0..255
The function is used to query the online status of the KNX device. Requests begin after the
gateway power-up send delay time complete.
8
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the enable KNX device. Display 10 KNX channels per page when
This parameter is for setting the KNX device setting. Display corresponding window when enabled.
9
KNX/EIB KNX Gateway for Tuya ZigBee
Parameters as follow is general setting parameters for KNX device type. Later chapters will not be
repeated.
This parameter is for setting the device type of KNX channel. Options:
Note: Channel 1~100 support all of the above function options, but channel 101~150 only
support the functions as follow:
Switch
Switch/Dimming
Curtain step/move
10
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the name description for current channel device, up to input 30
characters.
This parameter is for setting the reference type sending read request to KNX device, you can select
request for individual or common device, and optionally 10 common device requests. Options:
Common 1
...
Common 10
Individual
Always online
When select “Common ...”, common device request, apply to the device with multiple circuits. For
example, multiple channels of gateway may be multiple circuits that control the same KNX device, so
each channel can share one request.
When select “Individual”, apply to a device only is controlled by gateway single channel.
When select “Always online”, apply to the KNX device without heartbeat pack, especially scene.
That is, once configure the device, it will always online.
——Parameter “Time period for request [1..255] min”
This parameter is visible when “Individual” is selected, set the time period for the online status
request of single device. Options: 1..255
11
KNX/EIB KNX Gateway for Tuya ZigBee
This chapter explains the basic functions parameters of KNX channel, including switch, dimming,
curtain, color, color temperature, value sender and KNX scene switch.
12
KNX/EIB KNX Gateway for Tuya ZigBee
These two parameters are visible when device type is selected “Switch/Dimming”. Set the upper
and lower limit threshold value of brightness.
The lower limit threshold value options: 0..50; the upper limit threshold value options: 51..100
This parameter is visible when device type is selected “RGB dimming” or “RGBW dimming”. Set the
object datatype of RGB or RGBW dimming.
1x3byte
3x1byte
13
KNX/EIB KNX Gateway for Tuya ZigBee
1x6byte
4x1byte
These two parameters are visible when device type is selected “Color temperature”. Set the upper
and lower limit threshold value of color temperature. Options: 2000..7000
When the minimum value and maximum value are set incorrect, The selected range is the whole
range, for example the minimum value is larger than the maximum value. There is only one value when
equal.
For colour temperature, the Min. value must less than the Max., if not, if not, they can not be
This parameter is visible when device type is selected “Value sender”. Set telegram type for
sending to KNX bus when trigger calling command on the APP. Options:
1bit[On/Off]
2bit[0..3]
1byte[0..100%]
1byte[0..255]
1byte[scene control]
2byte[Float]
2byte[0..65535]
This parameter is visible when device type is selected “Value sender”, and corresponding datatype
is selected. Set the telegram value for sending to KNX bus when trigger calling command on the APP.
Options are according to the datatype:
14
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is visible when device type is selected “Scene switch”. Set the scene calling
command of KNX system to receive. Options:1..64
This chapter explains the air condition function of KNX channel, including the basic and air
conditioning control with swing. Parameters as follow are visible when “Air conditioner” or “Air
15
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the time period for read request room temperature sensor. Options:
0..255
These two parameters are for setting the adjustable range of the setpoint temperature. If the
setpoint temperature beyond the limited range, the will output the limited temperature. Options:
16°C
17°C
...
32°C
For setpoint temperature, the Min. value must less than the Max., if not, it can not be modified on
ETS.
These parameters are visible when the modes are enabled. Set the output value for switching to
each mode.
Options:0..255
16
KNX/EIB KNX Gateway for Tuya ZigBee
These parameters are visible when the modes are enabled. Set the status feedback value of each
mode.
Options:0..255
This parameter is for setting the object datatype of 1byte fan speed. Options:
These parameters are for setting the output value for switching to each fan speed, support 4 fan
speeds: auto, low, medium, high. Options are according to the object datatype of previous parameter:
0..255/0..100
These parameters are for setting the status feedback value of each fan speed, support 4 fan
speeds: auto, low, medium, high. Options are according to the object datatype of previous parameter:
0..255/0..100
Note: the out value and status value must meet the condition low<medium<high, if not, they can
not be configured on ETS, and display red box warning(Only applicable to BTMO-TY/00.1(2)), as
shown as follow:
This chapter explains the room temperature unit function of KNX channel, including the basic,
control with control mode, and with fan speed. Parameters as follow are visible when “Room
temperature unit”, “Room temperature unit(with operation mode)” or “Room temperature unit(with
operation mode & fan speed)” is selected.
17
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the time period for read request room temperature sensor. Options:
0..255
These two parameters are for setting the adjustable range of the setpoint temperature. If the
setpoint temperature beyond the limited range, the will output the limited temperature. Options:
5°C
6°C
...
40°C
18
KNX/EIB KNX Gateway for Tuya ZigBee
For setpoint temperature, the Min. value must less than the Max., if not, it can not be modified on
ETS.
This parameter is for setting temperature control mode, support 3 types: heating, cooling and
heating/cooling.
Options:
Heating
Cooling
This parameter is for setting the object datatype of 1byte fan speed. Options:
These parameters are for setting the output value for switching to each fan speed, support 3 fan
speeds: low, medium, high. Options are according to the object datatype of previous parameter:
0..255/0..100
These parameters are for setting the status feedback value of each fan speed, support 3 fan
speeds: low, medium, high. Options are according to the object datatype of previous parameter:
0..255/0..100
Note: the out value and status value must meet the condition low<medium<high, if not, they can
not be configured on ETS, and display red box warning, as shown as follow:
19
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting whether to enable the object datatype of 1bit fan speed. When
enabled, the 1 bit object of each fan speed is visible. When three objects value is 0, turn off the fan.
This parameter is visible when previous parameter is enabled. Set whether to enable the object
This chapter explains the ventilation system function of KNX channel. Parameters as follow are
visible when “Ventilation system” is selected.
20
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the initial fan speed after ventilation on. Switch status of ventilation is
read from bus after download or reset, and default as off if can not read. Options:
Low
Medium
High
Last status
Parameter “Data type of fan speed”
This parameter is for setting the data type of ventilation fan speed. Options:
1bit
1byte
This parameter is visible when fan speed datatype is selected “1byte”. Set the datatype of 1byte
fan speed object. Options:
These parameters are for setting the output value for switching to each fan speed, support 3 fan
speeds: low, medium, high. Value=0 is fan speed off. Options are according to the object datatype of
previous parameter: 0..255/0..100
These parameters are for setting the status feedback value of each fan speed, support 3 fan
speeds: low, medium, high. Value=0 is fan speed off. Options are according to the object datatype of
previous parameter: 0..255/0..100
Note: the out value and status value must meet the condition low<medium<high, if not, they can
not be configured on ETS, and display red box warning, as shown as follow:
21
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is visible when fan speed datatype is selected “1bit”. Set the control value for
switching to each fan speed and the status feedback value. support 4 fan speeds: off, low, medium,
high. Device will be update the fan speed display according to the feedback value. Options:
Low=0,Medium=0,High=0
Low=1,Medium=0,High=0
Low=0,Medium=1,High=0
Low=1,Medium=1,High=0
Low=0,Medium=0,High=1
Low=1,Medium=0,High=1
Low=0,Medium=1,High=1
Low=1,Medium=1,High=1
This parameter is visible when fan speed datatype is selected “1bit”. Set the delay time between
fan speeds switchover. Options: 0..100
Turn off fan speed before switch the fan speed, and turn on it after the delay time. When delay time
is set as 0, it will not turn off first then turn on, but switch to next fan speed directly.
22
KNX/EIB KNX Gateway for Tuya ZigBee
This chapter explains the audio control function of KNX channel, including the basic and audio
control with power on/off. Parameters as follow are visible when “Audio control” or “Audio control(with
on/off)” is selected.
This parameter is for setting the datatype of audio control object. Options:
These parameters are for setting the control value of each mode, including single
cycle/order/random play.
Options: 0..255
These parameters are for setting the status value of each mode, including single
cycle/order/random play. Device will be update the play mode display according to the feedback
23
KNX/EIB KNX Gateway for Tuya ZigBee
This chapter explains the sensor function of KNX channel, including air quality sensor, presence
24
KNX/EIB KNX Gateway for Tuya ZigBee
25
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is visible when device type is selected “Air quality sensor” or “PM2.5 sensor”. Set
This parameter is visible when device type is selected “Air quality sensor”. Set the object datatype
of PM10.
Options:
This parameter is visible when device type is selected “Air quality sensor” or “VOC sensor”. Set the
This parameter is visible when device type is selected “Air quality sensor” or “CO2 sensor”. Set the
object datatype of CO2. Options:
This parameter is visible when device type is selected “Presence sensor” or “Brightness sensor”.
Set the object datatype of brightness. Options:
Value in lux (DPT 7.013)
Float value in lux (DPT 9.004)
26
KNX/EIB KNX Gateway for Tuya ZigBee
This chapter explains the current metering function of KNX channel. Parameters as follow are
visible when device type is selected “Current metering”.
27
KNX/EIB KNX Gateway for Tuya ZigBee
This chapter explains the energy metering function of KNX channel. Parameters as follow are
visible when device type is selected “Energy metering”.
28
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the Zigbee device setting. Display corresponding window when
Note: Zigbee Channel function only applies to the premium version BTMO-TY/00.3(4).
29
KNX/EIB KNX Gateway for Tuya ZigBee
30
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the name description for current channel device, up to input 24
characters.
This parameter is for setting the device type of the Zigbee channel. Options:
Brightness sensor
Gas sensor
I/O signal
Switch
Switch/Dimming
RGB dimming
Color temperature
RGBCW
Curtain position
This parameter is visible when “Air quality sensor” is selected. Set the object datatype of VOC.
Options:
31
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is visible when “Air quality sensor” is selected. Set the object datatype of CO2.
Options:
This parameter is visible when “Air quality sensor” is selected. Set the object datatype of
formaldehyde.
Options:
This parameter is visible when “Brightness sensor” or “Temperature, humidity and brightness
This parameter is visible when “Gas sensor” is selected. Set the object datatype of gas
concentration.
Options:
This parameter is visible when “I/O signal” is selected. Set the object datatype of I/O signal.
Options:
32
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is visible when “Switch” or “Curtain position” is selected. Set the output channel of
Switch or Curtain.
These two parameters are visible when “Color temperature” or “RGBCW” is selected. Set the upper
When the minimum value and maximum value are set incorrect, The selected range is the whole
range, for example the minimum value is larger than the maximum value. There is only one value when
equal.
For colour temperature, the Min. value must less than the Max., if not, if not, they can not be
33
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting whether to enable the setting interface of RTC device, display
34
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the time period for read request external temperature sensor. Send
read request to external temperature sensor after the device voltage recovery or finish programming.
Options: 0..255
Parameter “Control value after temp. error[0..100]% (if 2-point control, set value '0'=0, set value
'>0'=1)”
This parameter is for setting the control value when temperature error occur. Options: 0..100
If 2-Point control, then the parameter value is 0, as well as the control value; if the parameter value
is more than 0, then the control value will be 1.
This parameter is for setting RTC control mode, support 3 types: heating, cooling and
heating/cooling.
Options:
Heating
Cooling
Heating and Cooling
Heating and Cooling: heating and cooling are available. At the same time, four parameters as
follow are visible.
——Parameter “Heating/Cooling switchover”
Via object
Automatic changeover
This parameter is for setting the heating/cooling control mode of device after download.
Options:
35
KNX/EIB KNX Gateway for Tuya ZigBee
Heating
Cooling
This parameter is for setting the heating/cooling control mode of device after voltage recovery.
Options:
Heating
Cooling
As before voltage failure: When the device is reset after power on, the control mode will recover as
before voltage failure or restart. If it is the first time the device is used or a newly enabled function page,
the control mode after the device is started is in an uncertain state, and it needs to be manually
selected at this time.
This parameter is for setting the type of RTC control system, that is, pipe types of fan coil water
inlet/outlet. Options:
2 pipes system
4 pipes system
2 pipes system: Shares an inlet and outlet pipe for heating and cooling, that is, both hot and cold water
are controlled by a valve.
4 pipes system: Has its own inlet and outlet pipes for heating and cooling, and two valves are needed to
control the entry and exit of hot water and cold water respectively.
This parameter is for setting whether to enable RTC operation mode. Options:
Disable
Enable
When enable, support 4 modes: comfort, standby, economy and frost/heat protection. Support
datatype of 1bit and 1byte, and preset a operation mode when download and voltage recovery.
Four parameters as follow are visible when RTC operation mode enabled.
——Parameter “Controller status after download”
This parameter is for setting the operation mode after download. Options:
Standby mode
Comfort mode
Economy mode
36
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the operation mode after voltage recovery. Options:
Standby mode
Comfort mode
Economy mode
Frost/heat protection
This parameter is for setting whether to enable 1 bit objects of operation mode are visible. Options:
Disable
Enable
This parameter is visible when previous parameter enabled. Set whether to enable 1 bit object of
standby mode is visible. Options:
Disable
Enable
Three parameters as follow are visible when RTC operation mode disabled.
——Parameter “ Initial setpoint temperature (°C)”
This parameter is for setting the initial value of setpoint temperature. Options:
10.0
10.5
...
35.0
When initial setpoint temperature is less than the min. setpoint temperature, display following
warning:
When initial setpoint temperature is greater than the max. setpoint temperature, display following
warning:
37
KNX/EIB KNX Gateway for Tuya ZigBee
These two parameters are visible when control mode “Heating and Cooling” is selected, and
“Automatic changeover” is selected. Setting the dead zone range of auto switchover heating/cooling.
Options:
0.5°C
1.0°C
...
10°C
Under heating control, when the actual temperature(T) greater than or equal to the setpoint
temperature + the upper dead zone, then mode heating switch to cooling;
Under cooling control, when the actual temperature(T) less than or equal to the setpoint
temperature + the upper dead zone, then mode cooling switch to heating.
This parameter is for setting whether to enable fan auto control interface is visible. Options:
Disable
Enable
This parameter is visible when operation mode enabled. Set whether to link to window contact
status.
Options:
Disable
Enable
This parameter is visible when operation mode and window contact input function are enabled. Set
the delay time to window contact detection. That is, when receive a telegram “window open”, the
controller will regard that as a valid signal and execute the behaviour after this delay time. Options:
0..65535
This parameter is visible when operation mode and window contact input function are enabled. If
38
KNX/EIB KNX Gateway for Tuya ZigBee
Economy mode
Frost/heat protection
Other control telegram receiving will be record during window is open and performed after
receiving the telegram “Close window”. If there is no telegram receiving when window is open, keep the
current mode.
This parameter is visible when operation mode enabled. Set whether to link to bus presence
Disable
Enable
If presence is detected, enter the comfort mode, and it will be restored to original mode after
leaving. If there is a telegram/manual operation to adjust the mode during the period, the telegram is
logged in the background, and it will be exited comfort mode and restored to the mode after leaving. If
there is no telegram receiving during timing, return to original mode. (If receive the presence status
cyclically, comfort mode can not be re-triggered, and only can be after leaving.)
These parameters are visible when operation mode disabled. Set to limit the adjustable range of
the setpoint temperature. If the setpoint temperature beyond the limited range, the will output the
5°C
6°C
...
40°C
These parameters are display below the parameters settings interface “Setpoint” when enable
operation mode.
For setpoint temperature, the Min. value must less than the Max., if not, it can not be modified on
ETS.
39
KNX/EIB KNX Gateway for Tuya ZigBee
Parameters of this window are visible when RTC operation mode enabled, display according to
control mode. The temperature setpoint value uses the way of absolute adjustment.
These parameters are for setting the temperature setpoint value of each mode. Options:
5°C
6°C
...
40°C
40
KNX/EIB KNX Gateway for Tuya ZigBee
When “Heating and Cooling” is selected, whether it is manual changeover, bus changeover or
automatic changeover, the heating setpoint value must be less than or equal to the cooling of the
1.When the ambient temperature is higher than the setpoint temperature of current mode, it is
changed to cooling mode; When the ambient temperature is lower than the setpoint temperature
2.In the same operation mode, the setpoint temperature difference between cooling and
heating remains constant, whether it is written on the bus or adjusted on the panel. That is, when
adjust the setpoint temperature, it need to update cooling and heating setpoint temperature of
3.When the bus is received setpoint temperature, it is still necessary to limit the value
according to the high and low thresholds, that is heating and cooling temperature neither can not
be lower than the min., or can not be higher than the max.. If parameters configuration of ETS is
When the setpoint temperature of comfort/standby/economy mode is less than the min. setpoint
When the setpoint temperature of comfort/standby/economy mode is greater than the max.
Note: for protection mode, the setpoint temperature is only configured via ETS, and not limited
with the min./max. value. When the received setpoint value from bus is different from the ETS
configuration, the value is not updated and returned to the current setpoint temperature, to update
41
KNX/EIB KNX Gateway for Tuya ZigBee
42
KNX/EIB KNX Gateway for Tuya ZigBee
Parameters of this window display according to control mode and control system(2 pipe or 4pipe).
This parameter is for setting the type of heating/cooling control. Different control types are
This parameter is for setting whether to invert control value or normal sending control value, so
that the control value will be suitable for the valve type. Options:
No
Yes
Yes: Sending the control value to the bus through objects after inverting the control value.
These two parameters are for setting the lower/upper hysteresis temperature in HVAC heating or
When the actual temperature(T) > the setting temperature + the upper hysteresis temperature,
When the actual temperature(T) < the setting temperature - the lower hysteresis temperature,
For example, the lower hysteresis temperature is 1℃, the upper hysteresis temperature is 2℃, the
setting temperature is 22℃, if T is higher than 24℃, then it will stop heating; if T is lower than 24℃,then
it will start heating; if T is between 21~24℃, then it will maintain the previous status.
43
KNX/EIB KNX Gateway for Tuya ZigBee
When the actual temperature (T) < the setting temperature -the lower hysteresis temperature,
When the actual temperature (T) > the setting temperature +the upper hysteresis temperature,
For example, the lower hysteresis temperature is 1℃, the upper hysteresis temperature is 2℃, the
setting temperature is 26℃, if T is lower than 25℃, then it will stop cooling; if T is lower than 28℃, then
it will start cooling; if T is between 28~25℃, then it will maintain the previous status.
2-point control mode is a very simple control mode. When adopting this control mode, it is
necessary to set the upper hysteresis temperature and the lower hysteresis temperature through
parameters. When setting the hysteresis temperature, the following effects need to be considered:
1. When hysteresis interval is small, the temperature range will be small, however, frequent sending
2. When hysteresis interval is large, the switch switching frequency will be low, but it is easy to
Fig.5.4.1.2(2) Effects of hysteresis on control value switch action(heating) under2-point control mode
44
KNX/EIB KNX Gateway for Tuya ZigBee
These two parameters are for setting the responding speed of heating or cooling PI controller.
Options:
User defined
Options:
User defined
These two parameters are visible when “User defined” is selected. Set the PI value of PI controller.
This parameter is only visible when the control type is “Switching PWM(use PI control)”. Set the
period of the control object cycle to send the switch value, the object sends the switch value according
to the duty cycle of the control value. For example, if the set period is 10 min and the control value is
80%, then the object will send an open telegram for 8 min. If the control value is changed, the time duty
45
KNX/EIB KNX Gateway for Tuya ZigBee
ratio of the on/ off telegram of the object will also change, but the period is still the time of parameter
setting.
Options: 1..255
The PI values of “Switching PWM (use PI control)” and “Continuous control (use PI control)” are the
same, only different in control objects, the control object of “Continuous control” output PI value(1byte)
directly, while the control value of “Switching PWM” output a “on/off” telegram according to the duty
This parameter is visible when control type is “Continuous control (use PI control)”, for setting the
changing value of the control value to be sent to the bus. Options: 0..100, 0=inactive
This parameter is for setting the period for cyclically sending the control value to the bus. Options:
0..255
In PI control mode, the predefined control parameters of each PI controller in heating or cooling
(1) Heating
46
KNX/EIB KNX Gateway for Tuya ZigBee
(2) Cooling
When the parameter“Heating/Cooling speed” is set to “User defined”, the parameter value of P
(scale factor) and I (integration time) can be set through the parameter. When adjusting the parameters,
refer to the fixed PI value mentioned in the above table. Even if the control parameters are adjusted
In addition, the integration time should be set properly. If the integration time is too long, the
adjustment will be slow, and the oscillation will not be obvious; if the integration time is too small, the
adjustment will be fast, but the oscillation will occur. 0 means the integral term is not used.
Y: control value
47
KNX/EIB KNX Gateway for Tuya ZigBee
When the integration time is set to zero, the PI control algorithm is: Y = K (X1-X2) + Y2
K: If the scale range is too small Quick adjustment, and overshoot will occur
TN: If the integration time is too Quick adjustment, but there will be
short oscillation
TN: If the integration time is too long Slow adjustment, no obvious oscillation
48
KNX/EIB KNX Gateway for Tuya ZigBee
Parameters of this window are visible when fan auto control enabled.
This parameter is for setting the telegram value to activate automatic operation. Options:
Auto=1/Man.=0
Auto=0/Man.=1
Auto=1/Man.=0: When the object “Fan automatic operation” receives the telegram value “0”,
activate the automatic operation, when receive “1”, exit the automatic operation.
Auto=0/Man.=1: When the object “Fan automatic operation” receives the telegram value “1”,
activate the automatic operation, when receive “0”, exit the automatic operation.
This parameter is for setting the object datatype of 1 byte fan speed. Options:
These three parameters are for setting the value sent for each fan speed switchover. Fan speed off
Note: the out value and status value must meet the condition low<medium<high, if not, they can
not be configured on ETS, and display red box warning, as shown as follow:
Under 2-point control, controller will decide the fan power on/off or fan speed according to the
49
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the temperature difference between off-fan and low-level fan speeds.
Options: 1..200
If the temperature difference is greater than or equal to this setting temperature difference,
low-level fan speed will start running; if less than this setting temperature difference, the fan will be
turned off.
Define the temperature difference for switching the fan speed to medium fan speed, if the control
value is greater than or equal to this setting temperature difference, the medium fan speed will start
running.
Options: 1..200
Define the temperature difference for switching the fan speed to high fan speed, if the control
value is greater than or equal to this setting temperature difference, the high fan speed will start
This parameter is for setting the hysteresis value of the temperature difference, which can avoid
the unnecessary action of the fan when the control value fluctuates near the temperature difference.
Options: 0..50
If value is 0, no hysteresis. Fan switch to speed once control value greater than temperature
difference;
Suppose that hysteresis value is 0.5℃ and the temperature difference is 1℃, then the upper limit
temperature difference 1.5℃ (Temperature difference+Hysteresis value) and the lower limit
temperature difference 0.5℃ (Temperature difference-Hysteresis value). When the control value is
between 0.5℃~1.5℃, fan action will not be caused, and the previous status will still be maintained. Only
less than 0.5℃ or greater than or equal to 1.5℃ will change the running status of the fan.
50
KNX/EIB KNX Gateway for Tuya ZigBee
Under PI control, control value is PI operated within program, controller will power on/off fan or
switch fan speed according to the threshold range of the control values.
Define threshold value for off-fan and low-level fan speeds, options: 1..255
If the control value is greater than or equal to this setting threshold value, low-level fan speed will
start running; if the control value is less than this setting threshold value, the fan will be turned off.
Define the threshold value for switching the fan speed to medium fan speed, if the control value is
greater than or equal to this setting threshold, the medium fan speed will start running. Options: 1..255
Define the threshold for switching the fan speed to high fan speed, if the control value is greater
than or equal to this setting threshold, the high fan speed will start running. Options: 1..255
First check →OFF <->low fan speed threshold →low fan speed <->medium fan speed →medium
fan speed <->high fan speed.
The threshold of OFF <-> low fan speed is lower than that of low fan speed <-> medium fan speed,
and the threshold of low fan speed <-> medium fan speed is lower than that of medium fan speed <->
high fan speed.
This parameter is for setting the hysteresis value of the threshold value, which can avoid the
unnecessary action of the fan when the control value fluctuates near the threshold. Options: 0..50
If value is 0, no hysteresis. Fan switch to speed once control value greater than threshold value;
Suppose that hysteresis value is 10 and the threshold is 50, then the upper limit threshold 60
(Threshold value+Hysteresis value) and the lower limit threshold 40 (Threshold value-Hysteresis value).
When the control value is between 40 ~60, fan action will not be caused, and the previous status will
still be maintained. Only less than 40 or greater than or equal to 60 will change the running status of the
fan.
Defines the residence time of the fan from the current fan speed to a higher fan speed or lower fan
speed, that is, the minimum time for a fan speed operation.
51
KNX/EIB KNX Gateway for Tuya ZigBee
If you need to switch to another fan speed, you need to wait for this period of time before
switching.
If the current fan speed has been running long enough, the fan speed can be changed quickly.
Options: 0..65535
0: there is no minimum running time, but the delay switching time of fan speed still needs to be
considered.
Note: The residence time for this parameter setting is only enabled in Auto mode.
52
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting whether to enable ventilation controller, to realize the automatic
control of the fan speed, and link the fan speed to the detection value of PM2.5 or CO2, VOC.
This parameter is for setting the telegram value to activate automatic operation. Options:
Auto=1/Man.=0
Auto=0/Man.=1
Auto=1/Man.=0: When the object “Fan automatic operation” receives the telegram value “0”,
activate the automatic operation, when receive “1”, exit the automatic operation.
Auto=0/Man.=1: When the object “Fan automatic operation” receives the telegram value “1”,
activate the automatic operation, when receive “0”, exit the automatic operation.
This parameter is for setting whether to enable state of Auto.operation after startup the device.
Options:
Disable
Enable
This parameter is for setting the data type of fan speed. Options:
1bit
1byte
This parameter is visible when “1byte” is selected. Set the object datatype of 1byte fan speed.
Options:
53
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is visible when “1byte” is selected. Set the value sent for each fan speed
switchover. Fan speed off when value is 0. Options according to fan object datatype: 1..255 /1..100
Note: the out value and status value must meet the condition low<medium<high, if not, they can
not be configured on ETS, and display red box warning, as shown as follow:
This parameter is visible when 1bit” is selected. Set the value sent for each fan speed, sent by three
Low=0,Medium=0,High=0
Low=1,Medium=0,High=0
Low=0,Medium=1,High=0
Low=1,Medium=1,High=0
Low=0,Medium=0,High=1
Low=1,Medium=0,High=1
Low=0,Medium=1,High=1
Low=1,Medium=1,High=1
This parameter is visible when 1bit” is selected. Set the delay time between fan speed switchover,
Turn off fan speed before switch the fan speed, and turn on it after the delay time. When delay time
is set as 0, it will not turn off first then turn on, but switch to next fan speed directly.
54
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the reference of control value under automatic operation. Options:
PM2.5
CO2
VOC
These parameters are for setting the datatype of PM2.5/VOC. Datatype determines object type,
select it according to the docking PM2.5 or VOC sensor data type. Options:
This parameter is for setting the datatype of CO2. Datatype determines object type, select it
This parameter is for setting the time period for device to send a control value read request to
external sensor after bus recovery or finish programming (After stabilization time 2min, then read).
Options: 0..255
Parameter “The fan speed status when the control value error”
This parameter is for setting the default fan speed of ventilation system when control value is error.
Options:
Off
Low
55
KNX/EIB KNX Gateway for Tuya ZigBee
Medium
High
Define threshold value for off-fan and low-level fan speeds, options: 1..999/1..4000
If the control value is greater than or equal to this setting threshold value, low-level fan speed will
start running; if the control value is less than this setting threshold value, the fan will be turned off.
Define the threshold value for switching the fan speed to medium fan speed, if the control value is
greater than or equal to this setting threshold, the medium fan speed will start running. Options:
1..999/1..4000
Define the threshold for switching the fan speed to high fan speed, if the control value is greater
than or equal to this setting threshold, the high fan speed will start running. Options: 1..999/1..4000
First check →OFF <->low fan speed threshold →low fan speed <->medium fan speed →medium
The threshold of OFF <-> low fan speed is lower than that of low fan speed <-> medium fan speed,
and the threshold of low fan speed <-> medium fan speed is lower than that of medium fan speed <->
This parameter is for setting the hysteresis value of the threshold value, which can avoid the
unnecessary action of the fan when the control value fluctuates near the threshold. Options:
10..30/100..400
For example, the control type is CO2, the Hysteresis value is 100 and the threshold is 450, then the
upper limit threshold 550 (Threshold value+Hysteresis value) and the lower limit threshold 350
(Threshold value-Hysteresis value). When the control value is between 350 ~550, fan action will not be
caused, and the previous status will still be maintained. Only less than 350 or greater than or equal to
56
KNX/EIB KNX Gateway for Tuya ZigBee
550 will change the running status of the fan. As shown in the following figure:
Note:
When hysteresis is enabled, if the threshold overlap occurs, fan action is specified as follows:
1) Hysteresis determines the control point where Fan speed conversion occurs;
2) If Fan speed conversion occurs, new fan speed is determined by control value and threshold
Hysteresis value is 25
Fan OFF status will change at a control value of 60 (≥25+35), and new fan speed will be the
mid-fan speed (because 60 is between 55 and 75, irrespective of hysteresis at this time), so the low
The behavior of fan speed when descending from a high fan speed:
The high fan speed will change at a control value of 50 (<75-25), and new fan speed will be low
fan speed (because 50 is between 35 and 55, irrespective of hysteresis), so the fan speed is ignored.
57
KNX/EIB KNX Gateway for Tuya ZigBee
For example(2):
Hysteresis value is 10
The OFF status will be turned when the control value is 30(≥20+10)
When the control value 41 is received, the new speed will be at medium(because the hysteresis is
ignored when the value 41 is between 40 and 70), therefore the low speed is ignored.
When the control value 39 is received, the new speed will be at low (because the hysteresis is
The high speed will be turned when the control value is 60(<70-10)
When the control value 39 is received, the new speed will be at low(because the hysteresis is
ignored when the value 39 is between 20 and 40),therefore the medium speed is ignored.
3) When the control value is 0,the fan will be off at any circumstances.
Defines the residence time of the fan from the current fan speed to a higher fan speed or lower fan
speed, that is, the minimum time for a fan speed operation. Options: 0..65535
If you need to switch to another fan speed, you need to wait for this period of time before
switching.
If the current fan speed has been running long enough, the fan speed can be changed quickly.
0: there is no minimum running time, but the delay switching time of fan speed still needs to be
considered.
Note: The residence time for this parameter setting is only enabled in Auto mode.
58
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the setting interface of logic function, display corresponding logic
This parameter is for setting the logic function of the channel. Options:
AND
OR
XOR
Gate forwarding
Threshold comparator
Format convert
Gate function
Delay function
Staircase lighting
AND/OR/XOR: as the parameter is similar to the communication object (only the logic algorithm is
59
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting whether input x to calculate, whether to normally calculate or inverted
calculate.Options:
Disconnected
Normal
Inverted
Disconnected: not to calculate;
Normal: to directly calculate the input value;
Inverted: invert the input value, then to calculate. Note: not to invert the initiate value.
60
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the initial value of logic input x. Options:
0
1
Parameter “Result is inverted”
This parameter is for setting whether to invert the logic calculation result. Options:
No
Yes
No: output directly;
Yes: output after inverting.
This parameter is for setting whether to send the read request to the logic input object after device
This parameter is for setting the condition of sending logic result. Options:
Receiving a new telegram
Every change of output object
Receiving a new telegram:every time the object received a new input value will the logic result be
Every change of output object:only when logic result has changed will it be sent to the bus.
Tip: when in the first time to logic calculate, the logic result will be sent even if it has no change.
Base: None
0.1s
1s
...
10s
25s
Factor: 1..255
This parameter is for setting the delay time for sending the logic calculation result to the bus. Delay
time = Base × Factor, if option “None” of Base is selected, then there is no delay.
61
KNX/EIB KNX Gateway for Tuya ZigBee
1bit
4bit
1byte
This parameter is for setting the initial scene where logical gate forwarding can be performed by
default after device starts, which needs to be configured in the parameters. Options:1..64, 0=inactive
Note: gate scene is recommended to be selected before operating, or it will enable the initiate
scene by default.
This parameter is for setting scene number of logic gate forwarding. Up to 8 trigger scene number
62
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the output of input X (X=A/B/C/D) after gate forwarding. Options:
Output A
Output B
...
Output B,C,D
According to the options, one input can be forwarded into one or more outputs, the output value is
This parameter is for setting the threshold value data type. Options:
4bit
1byte
2byte
4byte
63
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting threshold value, the range depends on the data type. Options: 4bit
This parameter is for setting the logic result value that should be sent when threshold value Less
than, equal to, not equal to, greater than, less than or equal to the setting valve. Options:
If there is a conflict between the setting options between parameters, the base on the value that
should be sent when reach the final parameter condition. For example: parameter “If Object
value=Threshold value” is set to be “Send value “0” ”;parameter “If Object value<=Threshold value” is
set to be “Send value “1” ”;when object value is equal to the threshold value, then the logic result will
send “1”.
This parameter is for setting the condition of sending logic result. Options:
Receiving a new telegram: every time the object received a new input value will the logic result be
sent to the bus;
Every change of output object: only when logic result has changed will it be sent to the bus.
Tip: when in the first time to logic algorithm, the logic result will be sent even if it has no change.
64
KNX/EIB KNX Gateway for Tuya ZigBee
Base: None
0.1s
1s
...
10s
25s
Factor: 1..255
This parameter is for setting the delay time for sending the logic algorithm result to the bus. Delay
time = Base x Factor, if option “None” of Base is selected, then there is no delay.
5.6.4. Parameter window “Format convert”
Parameter “Function”
2x1bit-->1x2bit
8x1bit-->1x1byte
1x1byte-->1x2byte
2x1byte-->1x2byte
2x2byte-->1x4byte
1x1byte-->8x1bit
1x2byte-->2x1byte
1x4byte-->2x2byte
1x3byte-->3x1byte
3x1byte-->1x3byte
65
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the condition of sending logic result. Options:
Receiving a new telegram: every time the object received a new input value will the logic result be
sent to the bus;
Every change of output object: only when logic result has changed will it be sent to the bus.
Tip: when in the first time to logic algorithm, the logic result will be sent even if it has no change.
1bit[On/Off]
1byte[0..100%]
1byte[0..255]
2byte[Float]
2byte[0..65535]
This parameter is visible when “1bit[On/Off]” is selected. Set whether to filter On or Off telegram,
66
KNX/EIB KNX Gateway for Tuya ZigBee
Deactivate
On filter out
This parameter is visible when “1bit[On/Off]” is selected. Set whether to invert the value then
Normal
Inverted
This parameter is for setting whether to invert the gate object value then output it. Options:
Normal
Inverted
This parameter is for setting the gate status after power on. Options:
Disable
Enable
This parameter is for setting whether to save input signal on gate close. Options:
No
Yes
No: disable to save the input, the input values received during the gate closing period are ignored;
Yes: enable to save the input, the input values received during the gate closing period are output
when gate is open (whether the input value is changed or not).
67
KNX/EIB KNX Gateway for Tuya ZigBee
1bit[On/Off]
1byte[0..100%]
1byte[0..255]
2byte[Float]
2byte[0..65535]
This parameter is for setting the delay time that output object forwards the value when the input
68
KNX/EIB KNX Gateway for Tuya ZigBee
This parameter is for setting the telegram value of the object “Trigger value”. Options:
0 or 1
1bit
1byte
This parameter is for setting duration time of staircase lighting after the stair light power on.
Options: 10..6500
These parameters are for setting the value to send. Send value 1 when trigger, and then send value
2 after duration time. Options display according to the output object datatype.
ON
When 1 byte , options: 0..255
Parameter “Retriggering”
This parameter is for setting whether to trigger re-timing when received trigger value in delay time.
Options:
Disable
Enable
69
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is the medium to communicate other device on the bus, namely only
the communication object can communicate with the bus.
NOTE: “C” in “Flag” column in the below table means enable the communication function of the
object; “W” means value of object can be written from the bus; “R” means the value of the object can
be read by the other devices; “T” means the object has the transmission function; “U” means the value
of the object can be updated.
The communication object is used to periodically send a telegram “1” to the bus to indicate that
the device is working properly.
Table 6.1 “General” communication object table
70
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used to send the request to the bus, for common device to query the
KNX device online status, and also can receive the feedback. Telegrams:
0——Offline
1——Online
Suitable for devices with multiple circuits. For example, multiple channels of gateway may be
multiple circuits that control the same KNX device, so each channel can share one request.
310 Device online, status KNX: {{Channel 1}} 1bit C,W,T,U 1.001 switch
The communication object is used to send the request to the bus, for independent device to query
the KNX device online status, and also can receive the feedback. Telegrams:
0——Offline
1——Online
Suitable for a device that only controlled by the single channel of gateway.
The name in parentheses changes with the parameter “Description (max 30 char.)”. If description
is empty, display “...Channel x” by default. The same below.
Switch
Switch/Dimming
71
KNX/EIB KNX Gateway for Tuya ZigBee
RGB dimming
RGBW dimming(1)
RGBW dimming(2)
Color temperature
Curtain step/move
Curtain position
72
KNX/EIB KNX Gateway for Tuya ZigBee
Value sender
Scene switch
Fig.6.2.1 Basic function communication object
312 Switch, status KNX: {{Channel 1}} 1bit C,W,T,U 1.001 switch
These two communication objects apply to switch, dimming, color and color temperature control.
Telegrams:
Obj.311: Used for sending On/Off telegrams to the bus, to control the light on/off.
Obj.312: Used for receiving On/Off status responded from other bus devices, such as dimming
actuator, switch actuator.
312 Brightness dimming KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
313 Brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
Obj.312: Used for sending dimming telegrams to the bus, that is, sending the brightness value.
Obj.313: Used for receiving brightness status responded from dimming actuator.
313 Red dimming value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
317 Red brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
These two communication objects are visible when 3x1byte for the RGB object type or 4x1byte for
the RGBW object type is selected. Apply to control brightness of multi-color lamp, and also support
Obj.313 Used for sending brightness value of the control R (red) channel to the bus.
Obj.317: Used for receiving brightness value of the control R (red) channel from bus.
314 Green dimming value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
73
KNX/EIB KNX Gateway for Tuya ZigBee
318 Green brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
These two communication objects are visible when 3x1byte for the RGB object type or 4x1byte for
the RGBW object type is selected. Apply to control brightness of multi-color lamp, and also support
Obj.314: Used for sending brightness value of the control G (green) channel to the bus.
Obj.318: Used for receiving brightness value of the control G (green) channel from bus.
315 Blue dimming value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
319 Blue brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
These two communication objects are visible when 3x1byte for the RGB object type or 4x1byte for
the RGBW object type is selected. Apply to control brightness of multi-color lamp, and also support
color temperature adjustment. Telegrams: 0...100%
Obj.315: Used for sending brightness value of the control B (blue) channel to the bus.
Obj.319: Used for receiving brightness value of the control B (blue) channel from bus.
316 White dimming value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
320 White brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
These two communication objects are visible when 4x1byte for the RGBW object type is selected.
Apply to control brightness of multi-color lamp, and also support color temperature adjustment.
Telegrams: 0...100%
Obj.316: Used for sending brightness value of the control W (white) channel to the bus.
Obj.320: Used for receiving brightness value of the control W (white) channel from bus.
313 RGB dimming value KNX: {{Channel 1}} 3byte C,T 232.600 RGB value 3x(0..255)
317 RGB brightness, status KNX: {{Channel 1}} 3byte C,W,T,U 232.600 RGB value 3x(0..255)
These two communication objects are visible when 1x3byte for the RGB object type is selected.
Apply to control brightness of multi-color lamp, and also support color temperature adjustment.
Obj.313: Used for sending brightness value of RGB three-color lamp to the bus.
Obj.317: Used for receiving brightness value of RGB three-color lamp from bus.
3-Byte Code for RGB Dimming Object Data Type: U8 U8 U8, as follows:
3MSB 2 1LSB
R G B
UUUUUUUU UUUUUUUU UUUUUUUU
R: red dimming value; G: green dimming value; B: blue dimming value.
74
KNX/EIB KNX Gateway for Tuya ZigBee
313 RGBW dimming value KNX: {{Channel 1}} 6byte C,T 251.600 DPT_Colour_RGBW
317 RGBW brightness, status KNX: {{Channel 1}} 6byte C,W,T,U 251.600 DPT_Colour_RGBW
These two communication objects are visible when 1x6byte for the RGBW object type is selected.
Apply to control brightness of multi-color lamp, and also support color temperature adjustment.
6MSB 5 4 3 2 1LSB
R G B W Reserve r r r r mR mG mB mW
R: red dimming value; G: green dimming value; B: blue dimming value; W: white dimming value;
mR: determines whether the red dimming value is valid, 0 = invalid, 1 = valid;
mG: determines whether the green dimming value is valid, 0 = invalid, 1 = valid;
mB: determines whether the blue dimming value is valid, 0 = invalid, 1 = valid;
mW: Determines whether the white dimming value is valid,0 = invalid,1 =valid.
These two communication objects apply to color temperature adjustment of monochrome lamp.
Telegrams: 2000..7000 K
Obj.313: Used for sending the control telegram of the color temperature to the bus.
Obj.317: Used for receiving the control telegram of the color temperature from bus.
314 Brightness value KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
318 Brightness, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
These two communication objects apply to color temperature adjustment of monochrome lamp.
Telegrams: 0…100%
Obj.314: Used for sending the dimming telegram of the color temperature to the bus, that is,
sending the brightness value.
Obj.318: Used for receiving the brightness status responded from the dimming actuator.
75
KNX/EIB KNX Gateway for Tuya ZigBee
Curtain step/move: these two communication objects apply to open and close curtain. Support to
Obj.311: Used for sending the telegram to the bus, to control curtain open/close. Telegrams:
Roller blind step/move: these two communication objects apply to roller blind. Support to up,
down, stop.
Obj.311: Used for sending the telegram to the bus, to control blind up/down. Telegrams:
1——Move down
0——Move up
Obj.312 is the same as above.
311 Open/Close KNX: {{Channel 1}} 1bit C,T 1.009 open/close
313 Blind position KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
315 Blind position, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
Curtain position: apply to open and close curtain. Support to open, close, stop, position
adjustment and position status feedback.
Obj.311: Used for sending the telegram to the bus, to control curtain open/close. Telegrams:
Obj.312: Used for sending the telegram to the bus, to stop curtain movement. Telegrams:
1——Stop
Obj.313: Used for sending a telegram to control the position of the curtain to the bus. Telegrams:
0…100%
Obj.315: Used for receiving a curtain position status in response to the window curtain actuator
on the bus. Telegrams: 0…100%
76
KNX/EIB KNX Gateway for Tuya ZigBee
313 Blind position KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
315 Blind position, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
Roller blind position: apply to a roller blind without slat. Support to up, down, stop, position
adjustment and position status feedback.
Obj.311: Used for sending the telegram to the bus, to control blind up/down. Telegrams:
1——Move down
0——Move up
312 Stop/Slat adj. KNX: {{Channel 1}} 1bit C,T 1.007 step
313 Blind position KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
314 Slat position KNX: {{Channel 1}} 1byte C,T 5.001 percentage(0..100%)
315 Blind position, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
316 Slat position, status KNX: {{Channel 1}} 1byte C,W,T,U 5.001 percentage(0..100%)
Venetian blind position and slat: apply to a blind with slat. Support to up, down, stop, position and
Obj.312: Used for sending a telegram to the bus to stop the curtain movement or adjust the slat
angle. Telegrams:
0——Stop/Slat adj. Up
Obj.314: Used for sending a telegram to control the position of the blind to the bus. Telegrams:
0…100%
Obj.316: Used for receiving a blind position status in response to the blind actuator on the bus.
Telegrams: 0…100%
77
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used for sending a preset telegram to the bus when trigger the
calling command on the APP. Object type and value range are determined by the parameter setting
datatype.
311 Trigger scene No. KNX: {{Channel 1}} 2byte C,W 17.001 scene number
The communication object is used for receiving the scene triggered telegram from KNX system.
Telegram: 1..64
Air conditioner
78
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used to control air condition power on/off via the APP, and send the
telegram value to the bus. Telegrams:
1——On
0——Off
312 Current setpoint adjustment KNX: {{Channel 1}} 2byte C,T 9.001 temperature
The communication object is used to adjust setpoint temperature via the APP, and send telegram
value to the bus.
20.105 HVAC control
313 Control mode KNX: {{Channel 1}} 1byte C,T
mode
The communication object is used to send control telegram of each air condition mode to the
bus.
Different telegram means different control mode:
0-Auto, 1- Heating, 3-Cooling, 9-Fan, 14-Dehumidity, other reserved.
5.001 percentage
314 Fan speed KNX: {{Channel 1}} 1byte C,T
5.100 fan stage
The communication object is used to send control telegram of each fan speed to the bus.
Telegram value is determined by parameter setting datatype.
315 Vanes swing (1-swing,0-stop) KNX: {{Channel 1}} 1bit C,T 1.010 start/stop
The communication object is visible only when “Air conditioner(with swing)” is selected. Used to
send telegram controlling vanes swing to the bus. Telegrams:
1——Swing
0——Stop
317 Power on/off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
The communication object is used to receive the power on/off telegram of air condition from the
bus, and feedback to the APP display. Telegrams:
1——On
0——Off
318 Room temperature sensor KNX: {{Channel 1}} 2byte C,W,T,U 9.001 temperature
The communication object is used to receive the room temperature from the bus, and send read
request cyclically, and feedback to the APP display.
79
KNX/EIB KNX Gateway for Tuya ZigBee
319 Current temperature setpoint, status KNX: {{Channel 1}} 2byte C,W,U 9.001 temperature
The communication object is used to receive the current setpoint temperature from the bus, and
feedback to the APP display.
320 Control mode, status KNX: {{Channel 1}} 1byte C,W 20.105 HVAC control mode
The communication object is used to receive the current control mode from the bus, and
feedback to the APP display. Different telegram means different control mode:
The communication object is used to receive the current fan speed from the bus, and feedback to
the APP display. Telegram value is determined by parameter setting datatype.
322 Vanes swing (1-swing,0-stop), status KNX: {{Channel 1}} 1bit C,W 1.010 start/stop
The communication object is visible only when “Air conditioner(with swing)” is selected. Used to
receive vanes swing status from the bus. Telegrams:
1——Swing
0——Stop
80
KNX/EIB KNX Gateway for Tuya ZigBee
311 Power on/off KNX: {{Channel 1}} 1bit C,T 1.001 switch
The communication object is used to control RTC power on/off via the APP, and send the
telegram value to the bus. Telegrams:
1——On
0——Off
312 Current setpoint adjustment KNX: {{Channel 1}} 2byte C,T 9.001 temperature
The communication object is used to adjust setpoint temperature via the APP, and send telegram
value to the bus.
313 Heating/Cooling mode KNX: {{Channel 1}} 1bit C,T 1.100 cooling/heating
The communication object is used to send telegram for switching cooling and heating functions
to the bus. Telegrams:
1——Heating
0——Cooling
314 Operation mode KNX: {{Channel 1}} 1byte C,T 20.102 HVAC mode
The communication object is used to send the telegram of the room operation mode to the bus.
320 Fan speed low KNX: {{Channel 1}} 1bit C,T 1.001 switch
81
KNX/EIB KNX Gateway for Tuya ZigBee
321 Fan speed medium KNX: {{Channel 1}} 1bit C,T 1.001 switch
322 Fan speed high KNX: {{Channel 1}} 1bit C,T 1.001 switch
323 Fan speed off KNX: {{Channel 1}} 1bit C,T 1.001 switch
These communication objects are used to control fan speed via the APP, and send telegrams to
the bus.
Only the corresponding object sends telegram “1” when switch to a certain fan speed. When
1bit-off object is not enable, all objects send telegrams “0” when switch to fan speed off (The situation
apply to connect with fan actuator of GVS);
When 1bit-off object is enable, only 1bit-off object send telegram “1” (The situation apply to
connect with fan actuator of other manufacturers).
1byte: the corresponding telegram value of each fan speed is defined by the parameter. Activate
the corresponding fan speed on the APP, and object 319 sends the corresponding telegram value of
the fan speed to the bus.
324 Fan automatic operation KNX: {{Channel 1}} 1bit C,T 1.003 enable
The communication object is used to send the telegram of fan automatic control to the bus.
Telegrams:
1——Auto
0——Exit auto
325 Power on/off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
The communication object is used to receive the power on/off telegram of RTC from the bus, and
feedback to the APP display. Telegrams:
1——On
0——Off
326 Room temperature sensor KNX: {{Channel 1}} 2byte C,W,T,U 9.001 temperature
The communication object is used to receive the room temperature from the bus, and send read
request cyclically, and feedback to the APP display.
82
KNX/EIB KNX Gateway for Tuya ZigBee
327 Current temperature setpoint, status KNX: {{Channel 1}} 2byte C,W,U 9.001 temperature
The communication object is used to receive the current setpoint temperature from the bus, and
feedback to the APP display.
328 Heating/Cooling mode, status KNX: {{Channel 1}} 1bit C,W 1.100 cooling/heating
The communication object is used for receiving the status of heating and cooling from the bus,
and feedback to the APP display. Telegrams:
1 ——Heating
0 ——Cooling
329 Operation mode, status KNX: {{Channel 1}} 1byte C,W 20.102 HVAC mode
The communication object is used for receiving the telegram of RTC operation mode from the
bus.
Different telegram means different control mode:
1-Comfort, 2-Standby, 3-Economy, 4-Protection, other reserved.
5.001 percentage
334 Fan speed, status KNX: {{Channel 1}} 1byte C,W
5.100 fan stage
335 Fan speed low, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
336 Fan speed medium, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
337 Fan speed high, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
338 Fan speed off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
These communication objects are used to receive status feedback to control fan speed via four
1bit objects or a 1byte object.
1bit :
Object 335——Low fan speed
Object 336——Medium fan speed
Object 337——High fan speed
Object 338——Fan speed off
The object receives telegram “1”, activate corresponding fan speed, and and feedback to the APP
display. When 1bit-off object is not enable, fan speed off when telegram values of low/medium/high
fan speed are “0”;
When 1bit-off object is enable, fan speed off when 1bit-off object receives telegram “1”, and fan
speed also off when telegram values of low/medium/high fan speed are “0”
1byte: the corresponding telegram value of each fan speed is defined by the parameter. When
object 334 receives the corresponding value, update the fan speed status on the APP display.
83
KNX/EIB KNX Gateway for Tuya ZigBee
339 Fan automatic operation, status KNX: {{Channel 1}} 1bit C,W 1.003 enable
The communication object is used to receive feedback status of fan automatic control.
Telegrams:
1——Automatic
0——Cancel automatic
Table 6.2.3 Room temperature unit function communication object table
Ventilation system
Fig.6.2.4 Ventilation system function communication object
NO. Object Function Name Data Type Flag DPT
311 Power on/off KNX: {{Channel 1}} 1bit C,T 1.001 switch
The communication object is used to control ventilation power on/off via the APP, and send the
telegram value to the bus. Telegrams:
1——On
0——Off
5.001 percentage
312 Fan speed KNX: {{Channel 1}} 1byte C,T
5.100 fan stage
313 Fan speed low KNX: {{Channel 1}} 1bit C,T 1.001 switch
314 Fan speed medium KNX: {{Channel 1}} 1bit C,T 1.001 switch
315 Fan speed high KNX: {{Channel 1}} 1bit C,T 1.001 switch
These communication objects are used to send the control telegrams of fan speed to the bus.
1byte: the corresponding telegram value of each fan speed is defined by the parameter. Activate
the corresponding fan speed on the APP, and object 312 sends the corresponding telegram value of
the fan speed to the bus.
1bit:
Object 313——Low fan speed
Object 314——Medium fan speed
Object 315——High fan speed
The corresponding object sends telegram “1” to activate corresponding fan speed on the APP.
Turn off fan speed when send telegram “0”.
84
KNX/EIB KNX Gateway for Tuya ZigBee
316 Fan automatic operation KNX: {{Channel 1}} 1bit C,T 1.003 enable
The communication object is used to send the telegram of fan automatic control to the bus.
Telegrams:
1——Auto
0——Exit auto
317 Heat recovery KNX: {{Channel 1}} 1bit C,T 1.003 enable
The communication object is used to control heat recovery mode via the APP, and send telegram
1——Active
0——Inactive
318 Power on/off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
The communication object is used to receive the power on/off telegram of ventilation from the
bus, and feedback to the APP display. Telegrams:
1——On
0——Off
5.001 percentage
319 Fan speed, status KNX: {{Channel 1}} 1byte C,W
5.100 fan stage
320 Fan speed low, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
321 Fan speed medium, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
322 Fan speed high, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
These communication objects are used to receive status feedback to control fan speed via three
1bit objects or a 1byte object.
1byte: the corresponding telegram value of each fan speed is defined by the parameter. When
object 319 receives the corresponding value, update the fan speed status on the APP display.
1bit :
The object receives telegram “1”, activate corresponding fan speed, and and feedback to the APP
display. All telegram values of fan speed should be 0 when turn off fan speed;
85
KNX/EIB KNX Gateway for Tuya ZigBee
323 Fan automatic operation, status KNX: {{Channel 1}} 1bit C,W 1.003 enable
The communication object is used to receive feedback status of fan automatic control.
Telegrams:
1——Automatic
0——Cancel automatic
324 Heat recovery, status KNX: {{Channel 1}} 1bit C,W 1.003 enable
The communication object is used to receive status of heat recovery mode, and feedback to the
APP display. Telegrams:
1——Active
0——Inactive
325 Filter alarm, status KNX: {{Channel 1}} 1bit C,W 1.005 alarm
The communication object is used to receive filter status from the bus, and feedback to the APP
display. Telegrams:
1——In normal use
0——Replace alarm
Table 6.2.4 Ventilation system function communication object table
Audio control
the object no need to send read request telegram. If “Audio control” is selected, the object needs to
86
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object only applies to the audio control with power on/off. Used to to control
the audio power on/off via the APP, and send the telegram to the bus. Telegrams:
1——On
0——Off
The communication object is used to play/stop the music in the audio module via the APP.
Telegrams:
1——Play music
313 Next track=1/Previous track=0 KNX: {{Channel 1}} 1bit C,T 1.007 step
The communication object is used to switch the playing song of the audio module via the APP, to
switch the previous song/the next song. Telegrams:
5.001 percentage
315 Absolute volume KNX: {{Channel 1}} 1byte C,T
5.004 percentage
The communication object is used to adjust volume of the audio module via the APP. Telegram
value is determined by different object datatype.
1 bit object, telegrams:
1——Increase volume
0——Decrease volume
1 byte object only applies to the audio control function without power on/off. Telegram value is
according to object type: 0..100 / 0..255
The communication object only applies to the audio control function without power on/off, used
to control mute of the audio module via the APP. Telegrams:
1——Mute
0——Cancel mute
87
KNX/EIB KNX Gateway for Tuya ZigBee
317 Play mode KNX: {{Channel 1}} 1byte C,T 5.010 counter pulses
The communication object is used to send control telegram of the audio module play mode,
different mode telegrams are preset by parameters.
318 Power on/off, status KNX: {{Channel 1}} 1bit C,W 1.001 switch
The communication object only applies to the audio control function with power on/off. Used to
receive the power on/off telegram of the audio module from the bus.
C,W
319 Play=1/Pause=0, status KNX: {{Channel 1}} 1bit 1.010 start/stop
C,W,T,U
The communication object is used to receive the music play/stop status from the bus.
When the audio control function with power on/off, the object flag is C,W; And without power
on/off, the object flag is C,W,T,U.
Volume adjustment function, 1byte object only applies to the audio control function without power
on/off. Used to receive the volume status of audio control.
Telegram value is according to object type: 0..100 / 0..255
321 Mute, status KNX: {{Channel 1}} 1bit C,W,T,U 1.003 enable
The communication object only applies to the audio control function without power on/off. Used
to receive the mute status of audio control.
1byt C,W
322 Play mode, status KNX: {{Channel 1}} 5.010 counter pulses
e C,W,T,U
The communication object is used to receive the play mode status of the audio module from the
bus, different mode telegrams are preset by parameters.
When the audio control function with power on/off, the object flag is C,W; And without power
on/off, the object flag is C,W,T,U.
Table 6.2.5 Audio control function communication object table
88
KNX/EIB KNX Gateway for Tuya ZigBee
CO2 sensor
PM2.5 sensor
VOC sensor
Presence sensor
Motion sensor
Brightness sensor
I/O signal
Fig.6.2.6 Sensor function communication object
89
KNX/EIB KNX Gateway for Tuya ZigBee
concentration(ug/m3)
The communication object is used to receive the input of the PM2.5 value and get the
corresponding value from the bus to be updated to the APP display in ug/m3.
concentration(ug/m3)
The communication object is used to receive the input of the PM10 value and get the
corresponding value from the bus to be updated to the APP display in ug/m3.
7.001 pulse
concentration(ug/m3)
The communication object is used to receive the input of the VOC value and get the
corresponding value from the bus to be updated to the APP display in ug/m3.
The communication object is used to receive the input of the CO2 value and get the
corresponding value from the bus to be updated to the APP display in ppm.
Range: 0...4000ppm
316 AQI value KNX: {{Channel 1}} 2byte C,W,T,U 7.001 pulses
The communication object is used to receive the input of the AQI value and get the corresponding
value from the bus to be updated to the APP display. Range: 0...500
317 Temperature value KNX: {{Channel 1}} 2byte C,W,T,U 9.001 temperature
The communication object is used to receive the input of the temperature value and get the
corresponding value from the temperature sensor on bus to be updated to the APP display. Range:
-40...40℃
90
KNX/EIB KNX Gateway for Tuya ZigBee
311 Humidity value KNX: {{Channel 1}} 2byte C,W,T,U 9.007 humidity
The communication object is used to receive the input of the humidity value and get the
corresponding value from the humidity sensor on bus to be updated to the APP display. Range:
0...100%
7.013 brightness(lux)
312 Brightness value(lux) KNX: {{Channel 1}} 2byte C,W,T,U
9.004 lux(lux)
The communication object is used to receive the input of the brightness value and get the
corresponding value from the bus to be updated to the APP display in lux.
Range: 0...65535lux, object datatype is determined by the parameter setting.
311 Motion detector KNX: {{Channel 1}} 1bit C,W,T,U 1.018 Occupancy
The communication object is used to receive the input of the 1bit presence signal. Telegram:
0——No one
1——Some one
311 I/O signal value KNX: {{Channel 1}} 1bit C,W,T,U 1.001 switch
The communication object is used to receive the input of the 1bit I/O signal. Telegram:
0——Open
1——Close
Table 6.2.6 Sensor function communication object table
91
KNX/EIB KNX Gateway for Tuya ZigBee
Current metering
Energy metering
Fig.6.2.7 Current/Energy metering function communication object
The communication object is used to receive the current value from the bus, updated to the APP
display. Object datatype is determined by the parameter setting.
When 2byte int is selected, display range: 0...65535mA, step value is 1mA.
When 2byte float is selected, display range: -670760...670760mA, step value is 0.01mA.
The communication object is used to receive the voltage value from the bus, updated to the APP
display. Object datatype is determined by the parameter setting.
The communication object is used to receive the power value from the bus, updated to the APP
display. Object datatype is determined by the parameter setting.
92
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used to receive the energy value from the bus, updated to the APP
display. Object datatype is determined by the parameter setting.
Brightness sensor
Gas sensor
I/O signal
Switch
Switch/Dimming
93
KNX/EIB KNX Gateway for Tuya ZigBee
RGB dimming
Color temperature
RGBCW
Curtain position
The communication object applies to air quality sensor, is used to send the VOC value in ug/m3 to
the KNX bus. Range: 0...999ug/m3, object datatype is determined by the parameter setting.
7.001 pulse
3713 CO2 value Zigbee: {{Channel 1}} 2byte C,R,T
9.008 parts/million(ppm)
The communication object applies to air quality sensor, is used to send the CO2 value in ppm to the
KNX bus.
Range: 0...4000ppm
7.001 pulse
3714 Formaldehyde value Zigbee: {{Channel 1}} 2byte C,R,T
9.030 concentration(ug/m3)
The communication object applies to air quality sensor, is used to send the formaldehyde value in
ug/m3 to the KNX bus.Range: 0...1000ug/m3
94
KNX/EIB KNX Gateway for Tuya ZigBee
3715 Temperature value Zigbee: {{Channel 1}} 2byte C,R,T 9.001 temperature
The communication object applies to temperature sensor, and temperature, humidity and brightness
sensor, is used to send the temperature value in °C to the KNX bus. Range: -50...99°C
3716 Humidity value Zigbee: {{Channel 1}} 2byte C,R,T 9.007 humidity
The communication object applies to humidity sensor, and temperature, humidity and brightness
sensor, air quality sensor, is used to send the humidity value in % to the KNX bus. Range: 0...100%
7.013 brightness(lux)
3710 Brightness(lux) value Zigbee: {{Channel 1}} 2byte C,R,T
9.004 lux(lux)
The communication object applies to brightness sensor, and temperature, humidity and brightness
sensor, air quality sensor, is used to send the brightness value to the KNX bus. Range: 0...65535lux,
object datatype is determined by the parameter setting.
7.001 pulse
3710 Gas concentration value Zigbee: {{Channel 1}} 2byte C,R,T 9.008 parts/million(ppm)
9.030 concentration(ug/m3)
The communication object applies to gas sensor, air quality sensor, gas measurement, is used to
send the gas concentration value to the KNX bus. For example VOC, CO2 or formaldehyde detection
value.
1.001 switch
3710 Binary value Zigbee: {{Channel 1}} 1bit C,R,T
1.002 boolean
3710 Alarm detect Zigbee: {{Channel 1}} 1bit C,R,T 1.005 alarm
3710 Presence detect Zigbee: {{Channel 1}} 1bit C,R,T 1.018 occupancy
3710 Window/door detect Zigbee: {{Channel 1}} 1bit C,R,T 1.019 window/door
The communication object applies to I/O type sensor, is used to send the I/O signal to the KNX bus.
Object datatype is determined by the parameter setting. Telegram value:
0——Open/No alarm/Not occupied/Close window
1——Close/Alarm/Occupied/Open window
3710/.
C,W
./ Switch Zigbee: {{Channel 1}} 1bit 1.001 switch
C,W,R,T,U
3712
3713/.
3715
95
KNX/EIB KNX Gateway for Tuya ZigBee
These communication objects apply to switch, dimming, RGB, color temperature and RGBCW
control, are used for KNX system to control Zigbee lamps, including lamp, dimmable lamp, RGB
bulb/strip, color temperature light and RGBCW bulb.
When “Switch” is selected, object name is “Zigbee: {{Channel 1}}-x”, and set the number of channels
for the switch by parameter, up to 3 channels, x=1/2/3.
Telegram value:
3712 Brightness value Zigbee: {{Channel 1}} 1byte C,W 5.001 percentage(0..100%)
3715 Brightness, status Zigbee: {{Channel 1}} 1byte C,R,T 5.001 percentage(0..100%)
These two communication objects apply to color temperature and RGBCW control, are used for KNX
system to control Zigbee lamps, including RGB bulb/strip and RGBCW bulb. Telegrams: 0…100%
Obj.3712: Used for receiving the brightness value from KNX bus, to control the brightness of the
lamp.
3712 RGB dimming value Zigbee: {{Channel 1}} 3byte C,W 232.600 RGB value 3x(0..255)
3715 RGB brightness, status Zigbee: {{Channel 1}} 3byte C,R,T 232.600 RGB value 3x(0..255)
These two communication objects apply to RGB and RGBCW control, are used for KNX system to
control Zigbee lamps, including RGB bulb/strip and RGBCW bulb.
Obj.3712: Used for receiving the brightness value of RGB three-color lamp from KNX bus, to control
the color of the lamp.
Obj.3715: Used for sending the brightness status of RGB three-color lamp to the KNX bus.
3-Byte Code for RGB Dimming Object Data Type: U8 U8 U8, as follows:
3MSB 2 1LSB
R G B
3711 Color temperature value Zigbee: {{Channel 1}} 2byte C,W 7.600 absolute color
temperature
96
KNX/EIB KNX Gateway for Tuya ZigBee
3714 Color temperature, Zigbee: {{Channel 1}} 2byte C,R,T 7.600 absolute color
status temperature
These two communication objects apply to color temperature and RGBCW control, are used for KNX
system to control Zigbee lamps, including color temperature light and RGBCW bulb. Telegrams:
2000..7000K
Obj.3711: Used for receiving the color temperature control value form the bus, to control the color
temperature of the lamp.
Obj.3714: Used for sending the color temperature status to the KNX bus.
3710/
Open/Close Zigbee: {{Channel 1}}-x 1bit C,W 1.009 open/close
3713
3711/
Stop Zigbee: {{Channel 1}}-x 1bit C,W 1.007 step
3714
These communication objects apply to curtain step/move, are used for KNX system to control
Zigbee electric curtain. Set the number of channels for the curtain by parameter, up to 2 channels, x=1/2.
Obj.3710/3713: Used for receiving the telegrams from KNX bus to control curtain open/close.
Telegrams:
1——Close the curtain
0——Open the curtain
Obj.3711/3714: Used for receiving the telegrams from KNX bus to stop curtain movement.
Telegrams:
1——Stop
Obj.3712/3715: Used for receiving the telegrams from KNX bus to control curtain position, and
97
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used to receive the telegram value of control RTC power on/off from
the bus. Telegrams:
1——On
0——Off
The communication object is used to receive the room temperature from the bus, and send read
The communication object is used to modify the current setpoint value of temperature. Telegrams:
0..65535
The communication object is used to switch heating/cooling mode via the bus. Telegrams:
1——Heating
0——Cooling
98
KNX/EIB KNX Gateway for Tuya ZigBee
These communication objects are used to control RTC operation mode via the bus.
1byte: object 78 is visible. Telegrams: 1-comfort, 2-standby, 3-economy, 4-protection, other
reserved.
1bit:
Object 79——Comfort mode
Object 80——Economy mode
Object 81——Protection mode
Object 82——Standby mode
Activate corresponding mode when receive a telegram “1”. When 1bit standby mode is not enable,
and objects value of comfort, economy and protection are all 0, it is standby mode. When 1bit standby
mode is enable, the 1bit standby object receives 1 is standby mode, and telegram “0” will be ignored.
The communication object is used to activate fan automatic control via the bus. Telegrams:
1——Auto
0——Exit auto
The communication object is used to receive the switch status of window contact. Telegrams:
1——Open window
0——Close window
The communication object is used to receive the room occupancy status from presence detector.
Telegrams:
1——Occupied
0——Not occupied
Current temperature setpoint,
86 RTC 1 2byte C,R,T 9.001 temperature
status
The communication object is used to send the current setpoint temperature of RTC to the bus.
Telegrams: 0..65535
99
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used to feedback the telegram to the bus for switching heating and
cooling function.
These communication objects are used to send RTC operation mode status to the bus.
When 1 byte: object 88 is visible, telegrams: 1-comfort, 2-standby, 3-economy, 4-protection, other
reserved.
When 1bit:
Object 89—— Comfort mode
Object 90—— Economy mode
Object 91—— Protection mode
Object 92—— Standby mode
When a mode is activated, the corresponding object only sends telegram “1”. When 1 bit standby
object is not enable, activate standby mode when comfort, economy, protection objects send telegram
0 together. When 1 bit standby object is enable, activate standby mode only when standby object send
1.
Note: no requirement to send mode status to the bus when switchover via bus. The same is fan
speed and other operation.
1bit 1.001 switch
93 Heating control value, status RTC 1 C,R,T
1byte 5.001 percentage
These communication objects are used to send control status of heating or cooling function to the
bus. Object datatype is according to parameter setting.
5.001 percentage
94 Fan speed, status RTC 1 1byte C,T
5.100 fan stage
The communication object is used to send the status of fan speed to the bus. The corresponding
telegram value of each fan speed is defined by the parameter.
Table 6.4 “Room temperature controller” communication object table
100
KNX/EIB KNX Gateway for Tuya ZigBee
294 Fan automatic operation Ventilation controller 1bit C,W 1.003 enable
The communication object is used to activate fan automatic control via the bus. Telegrams:
1——Auto
0——Exit auto
PM 2.5 value 7.001 pulse
The communication object is used to receive the input value of PM2.5/VOC/CO2, and get the
corresponding value from the bus and update it to the display, the corresponding object datatype is
defined by the parameter. Unit is ug/m3 or ppm. Range: 0~999ug/m3 or 0...4000ppm
For example, Control value of automatic operation is PM2.5, that is, under the automation, the
ventilation system can adjust the fan speed automatically according to PM2.5 concentration.
5.001 percentage
296 Fan speed, status Ventilation controller 1byte C,T
5.100 fan stage
297 Fan speed low, status Ventilation controller 1bit C,T 1.001 switch
299 Fan speed high, status Ventilation controller 1bit C,T 1.001 switch
These communication objects are used to send control telegrams of the fan speed to the bus.
1byte: the corresponding telegram value of each fan speed is defined by the parameter. Object 296
sends the corresponding telegram value of the fan speed to the bus.
1bit:
Object 297——Low fan speed
Object 298——Medium fan speed
Object 299——High fan speed
The corresponding object sends telegram “1” to the bus, and sends telegram “0” is turn off fan
speed.
Table 6.5 “Ventilation controller” communication object table
101
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used to receive the value of logical input Input x.
10 Logic result 1st /.../8th Logic 1bit C,T 1.002 boolean
102
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used to select the scene of logical gate forwarding.
1.001 switch
1bit
3.007 dimming control
3/.../6 Input x 1st /.../8th Logic 4bit C,W
5.010 counter
1byte
pulses(0..255)
The communication object is used to receive the value of the logic gate input Input x.
1.001 switch
1bit
7/../1 3.007 dimming control
Output x 1st /.../8th Logic 4bit C,T
0 5.010 counter
1byte
pulses(0..255)
The communication object is used to output the value forwarded by the logic gate. The output
value is the same as the input value, but one input can be forwarded into one or more outputs, set by
parameters.
Table 6.6.2 “Gate forwarding” communication object table
103
KNX/EIB KNX Gateway for Tuya ZigBee
2byte pulses(0..255)
The communication object is used to send the results of logical operation. That is, the value that
should be sent after the object input threshold is compared with the setting threshold value.
“2x1bit --> 1x2bit”function: converts two 1bit values to a 2bit value, such as Input bit1=1, bit0=0-->
Output 2bit=2
“8x1bit --> 1x1byte”function: converts eight 1bit values to a 1byte value, such as Input bit2=1, bit1=1,
bit0=1,other bits are 0--> Output 1byte=7
104
KNX/EIB KNX Gateway for Tuya ZigBee
“1x1byte --> 1x2byte”function: converts one 1byte values to a 2byte value, such as Input 1byte=125-->
Output 2byte=125.Although the value remains the same, the data type of the value is different.
“2x1byte --> 1x2byte”function: converts two 1byte values to a 2byte value, such as Input 1byte-low
= 255 ($FF), Input 1byte-high = 100 ($64) --> Output 2byte = 25855 ($64 FF)
“2x2byte --> 1x4byte”function: converts two 2 byte values to a 4byte value, such as Input 2byte-low =
65530 ($FF FA), Input 2byte-high = 32768 ($80 00)--> Output 2byte = 2147549178 ($80 00 FF FA)
“1x1byte --> 8x1bit” function: converts one 1byte values to eight 1but value, such as Input 1byte=200 -->
Output bit0=0, bit1=0, bit2=0, bit3=1, bit4=0, bit5=0, bit6=1, bit7=1
“1x2byte --> 2x1byte”function: converts one 2byte values to two 2byte value, such as Input 2byte =
55500 ($D8 CC) --> Output 1byte-low = 204 ($CC), Output 1byte-high =216 ($D8)
“1x4byte --> 2x2byte”function: converts one 4byte values to two 2byte value, such asInput 4byte =
78009500 ($04 A6 54 9C) --> Output 2byte-low = 21660 ($54 9C), Output 2byte-high =1190 ($04 A6)
105
KNX/EIB KNX Gateway for Tuya ZigBee
“1x3byte --> 3x1byte”function: converts one 3byte values to three 1byte value, such as Input 3byte = $78
64 C8--> Output 1byte-low = 200 ($C8) , Output 1byte-middle = 100 ($64) , Output 1byte-high =120 ($78)
“3x1byte --> 1x3byte”function: converts three 1byte values to a 3byte value, such as Input 1byte-low =
150 ($96), Input 1byte-middle = 100 ($64), Input 1byte-high = 50 ($32)--> Output 3byte = $32 64 96
Fig.6.6.4 “Format convert” Communication Object
106
KNX/EIB KNX Gateway for Tuya ZigBee
Input/Output - 1bit[On/Off]
Input/Output - 1byte[0..100%]
Input/Output - 1byte[0..255]
Input/Output - 2byte[Float]
Input/Output - 2byte[0..65535]
Fig.6.6.5 “Gate function” Communication Object
NO. Object Function Name Data Type Flag DPT
1.001 switch
7.001 pulses
The communication object is used to input a value that needs to gate filter.
The communication object is used to control the switch status of gate input. Input signal is
allowed to pass when gate open, then output, and the current input status is still sent if there is a
change; Can not pass when gate close.
1.001 switch
7.001 pulses
The communication object is used to output the value after gate filtering. Only when gate input
status is open, output is available, defined by the object “Gate input”.
107
KNX/EIB KNX Gateway for Tuya ZigBee
Input/Output - 1bit[On/Off]
Input/Output - 1byte[0..100%]
Input/Output - 1byte[0..255]
Input/Output - 2byte[Float]
Input/Output - 2byte[0..65535]
Fig.6.6.6 “Delay function” Communication Object
NO. Object Function Name Data Type Flag DPT
1.001 switch
7.001 pulses
7.001 pulses
The communication object is used to output that needs to delay converted value, delay time is
108
KNX/EIB KNX Gateway for Tuya ZigBee
The communication object is used to receive the value to trigger staircase lighting.
3 Light-on duration time 1st /.../8th Logic 2byte C,W 7.005 time(s)
The communication object is used to modify the staircase light-on duration time, the modified
range is referenced from the range defined by the parameter, take the limit value if exceeded.
The communication object is used to output value 1 when trigger, and send value 2 after duration
109
KNX/EIB KNX Gateway for Tuya ZigBee
This chapter detail UI use for Tuya Smart APP in functional blocks. Please make sure the database
is downloaded to KNX Gateway for Tuya ZigBee before operating APP. Once the database is
downloaded, you can add gateways and other devices on the APP.
7.1.Add device
Click icon on the mobile phone desk to start up Tuya Smart APP, register or login the account.
Click the icon in the upper right corner of homepage to add device after login successfully. Take
KNX Gateway for Tuya ZigBee as an example to explain the operation of adding a device.
Other devices are added in similar ways to the gateway, and no longer repeat in this chapter.
1. Select corresponding device type, KNX Gateway for Tuya ZigBee selects the Gateway in
Gateway Control. You can select to add it manually(Step 2~5), or select to click icon to auto scan,
please ensure that the device has entered paring mode, click blue word in the follow picture to go to the
details of “Auto Scan”. If failed to auto add device, you can select to Try again or Add Manually.
110
KNX/EIB KNX Gateway for Tuya ZigBee
Note: Please ensure to turn on Bluetooth, Wi-Fi and Location services, otherwise the APP cannot
2. Click device icon, you can see the device connection steps. If the device is not reset, please
perform net pairing as prompted. If it has been reset, ignore step 3. Please note the LED indication
3. Reset device. Long press ZigBee connect button on the gateway for 5s, to remove the gateway
from the cloud, triggered to flash after manually operating the connect button, and flashing 5 times to
enter the waiting connection status. LED indication effect of gateway as follow:
——Always on after gateway network is connected OK, flashing when there is a data
communication.
111
KNX/EIB KNX Gateway for Tuya ZigBee
4. Make sure the device reset is successful, and your phone and the gateway are under the same
network. Then make sure the device LED is indicated correctly. The gateway confirms that the two
green lights(Connect status LED and LAN LED) are always on, then click Next to enter the status for
connecting device.
5. Add device. When scan the “KNXGateway”, click the icon to complete the addition.
Note: For Android systems, if the gateway fails to connect several times, it need to clear cache.
Click icon in the upper right corner of【Me】interface to enter the settings page, select【Clear
Cache】.
112
KNX/EIB KNX Gateway for Tuya ZigBee
6. After completing the above steps, display setting page of the device, and displays a list of the
As below, the interactive use of KNX channel devices will be described in detail.
113
KNX/EIB KNX Gateway for Tuya ZigBee
Click the icon to check the Gateway information, which is shown in the figure below. The last
If you want to use IP address, when IP assignment is set as Fixed mode, IP address is assigned
from the parameters on ETS; while IP assignment is DHCP mode, at first, you should enter the
background of the router which is connected to the gateway, then you can see IP address of the
gateway. (The ways to enter the router background are different, detail please refer to the router
manual.)
114
KNX/EIB KNX Gateway for Tuya ZigBee
7.3.Switch interface
①
②
④
Fig.7.2(1) Switch interface Fig.7.2(2) Device basic settings Fig.7.2(3) Info editing interface
②Device name, shown it above the interface. Click icon to go to figure7.2(2), you can view, change
Device basic settings as shown in figure 7.2 (2), including Device Information, Tap-to-Run and
Automation, Other settings, and Remove Device. Set the Tap-to-Run and Automation via KNX scene
Click ④ to go to figure7.2(3), you can edit current device name, icon and location.
③Switch button, gray indicates status off, bright color indicates status on. Used for switching of switch
status.
115
KNX/EIB KNX Gateway for Tuya ZigBee
7.4.Switch/Dimming interface
①
②
②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
③B: brightness adjustment. Adjust brightness by sliding this slider, range: 0..100%
④LED switch button, gray indicates status off, bright color indicates status on. Used for switching of
switch status. When brightness value is not 0, touch this button to close brightness, and value is 0.
116
KNX/EIB KNX Gateway for Tuya ZigBee
①
②
④
③
⑤
②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
There are 3 control types of RGB dimming function: RGB, RGBW, Color Temperature. Among them,
RGB is suitable for adjusting RGB lamp; RGBW is suitable for controlling RGBW strip; Color Temperature
③RGB value adjustment. Adjust brightness by sliding R/G/B slider, range: 0..255
④RGBW value adjustment. Adjust brightness by sliding R/G/B/W slider, range: 0..255
⑤B: brightness adjustment. Adjust brightness by sliding this slider, range: 0..100%
CW: color temperature adjustment. Adjust color temperature by sliding this slider, range:
2000..7000K
⑥LED switch button, gray indicates status off, bright color indicates status on. When current value is
117
KNX/EIB KNX Gateway for Tuya ZigBee
①
②
⑤
④
③
⑥
⑦
⑨
⑧ ⑩
②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
③Curtain step/move:
1)Touch icon , open curtain. Device sends out a telegram with the object(Open/Close) value of 0;
2)Touch icon , stop curtain. Device sends out a telegram with the object(Stop) value of 1;
3)Touch icon , close curtain. Device sends out a telegram with the object(Open/Close) value of
1;
118
KNX/EIB KNX Gateway for Tuya ZigBee
⑤⑥Curtain position:
1)By sliding the slider⑤ to adjust the position of curtain;
2) Operation of Open/Close/Stop are the same as above.
119
KNX/EIB KNX Gateway for Tuya ZigBee
①
②
Fig.7.6Value sender
120
KNX/EIB KNX Gateway for Tuya ZigBee
①
②
APP to perform action set in scene setting, link the KNX device functions to the ZigBee on the APP.
Configure specific associated devices and trigger responses for scene on the APP before operation.
⑧
⑨
Fig.7.7(2) Scene switch setting Fig.7.7(3) Create Smart Fig.7.7(4) Add task
②Click to save the setting and return to the previous interface after scene switch setting.
121
KNX/EIB KNX Gateway for Tuya ZigBee
⑥Click to save the setting and return to the previous interface after creating smart.
⑦Click plus icon to create“Tap-To-Run” task, the window⑨ is pop up below, you can select required
setting, including: all devices, smart scenes, notification and the action delay. Task is shown in figure
⑧Set the task name, display style, and whether to show on home page.
③ ⑥ ⑦
①
④
⑤
②
①Click three-point icon, display drop-down window, you can select 【Manage】 or 【Logs】, shown as
figure 7.7(5). Click【Manage】to go to manage interface, shown as figure 7.7(6). Long press icon④ to
slide, to adjust the order of scene tasks; click icon⑤ to delete the scene task.
②Click three-point icon, go to the scene edit interface, shown as 7.7(7), operation in the interface: add
task, change the task name and display style, whether to show on home page, and delete the scene.
Click on the rest of the control to perform the scene immediately.
Operate the edit interface also can be via the single device, such as figure 7.2 (2) device basic setting,
to click Tap-to-Run and Automation.
③Click to save and return to previous interface after task management.
⑥Click to cancel edit, and return to previous interface.
⑦Click to save and return to previous interface after editing.
122
KNX/EIB KNX Gateway for Tuya ZigBee
①
②
④
⑤
⑦
Fig.7.8(1) Air condition interface Fig.7.8(2) Air condition (with swing) interface
②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
③Ring slider is used to adjust the setpoint temperature, the performed adjustment step is 1℃. When
temperature unit is set to degrees Celsius (℃), adjustment range of setpoint temperature is default as
16 ~ 32℃; Current temperature display according the parameter configuration, you can configure to
④Click this icon to switch Air condition control mode, update the mode status via the object: Heat ,
⑤Click this icon to switch fan speed, the current fan speed is cyclically switched in this order--Low
⑦Air condition switch button, gray indicates status off, bright color indicates status on. When power off,
except for the status of power on/off, the other icon status can not be updated via the bus or manually
controlled. Click this icon, device sends a telegram of value 1/0 (On/Off) via the object Power on/off.
123
KNX/EIB KNX Gateway for Tuya ZigBee
①
②
④ ⑤
②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
③Ring slider is used to adjust the setpoint temperature, the performed adjustment step is 1℃. When
temperature unit is set to degrees Celsius (℃), adjustment range of setpoint temperature is default as
5 ~ 40℃; Current temperature display according the parameter configuration, you can configure to
124
KNX/EIB KNX Gateway for Tuya ZigBee
④Click this icon to switch control mode, update the mode status via the object: Heating ,
cooling. .
You can switch the mode via touch or telegram when the database sets the RTC control mode to
⑤Click this icon to switch operation mode: comfort , standby , economy , protection
⑥Click this icon to switch fan speed, the current fan speed is cyclically switched in this order--Low
⑦RTC switch button, gray indicates status off, bright color indicates status on. When power off, except
for the status of power on/off, the other icon status can not be updated via the bus or manually
controlled. Click this icon, device sends a telegram of value 1/0 (On/Off) via the object Power on/off.
④
⑤
125
KNX/EIB KNX Gateway for Tuya ZigBee
②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
④Click this icon to switch fan speed, the current fan speed is cyclically switched in this order--Low
⑥Ventilation switch button, gray indicates status off, bright color indicates status on. When power off,
except for the status of power on/off, the other icon status can not be updated via the bus or manually
controlled. Click this icon, device sends a telegram of value 1/0 (On/Off) via the object Power on/off.
①
②
④
⑤
Fig.7.11(1) Audio control interface Fig.7.11(2) Audio control (with on/off) interface
①Return to the previous interface.
②Device name, shown it above the interface. Click icon , you can view, change device settings, and
remove devices.
126
KNX/EIB KNX Gateway for Tuya ZigBee
⑥Click the button to switch the audio play mode. Update the status via the object: single loop , list
⑧Click the icon to play or stop music. And update the status via the object.
⑨Audio control switch button, gray indicates status off, bright color indicates status on. When power
off, except for the status of power on/off, the other icon status can not be updated via the bus or
manually controlled. Click this icon, device sends a telegram of value 1/0 (On/Off) via the object Power
on/off.
Air quality sensor interface CO2 sensor interface PM2.5 sensor interface VOC sensor
interface
Air quality sensor displays 7 reference values, independently is: CO2, PM2.5, PM10, VOC,
Temperature, Humidity, AQI. What displays can be configured through the database. The CO2, PM2.5
and VOC have separate detectors, and all can show the internal temperature and humidity on the
interface.
The ring on the interface and the reference values of corresponding devices. The update of the
display value can be achieved by rewriting the object via the bus.
127
KNX/EIB KNX Gateway for Tuya ZigBee
Presence sensor interface Motion sensor interface Brightness sensor interface I/O signal interface
Presence sensor can detect PIR state, and illuminance, detection range: 0...65535lux
128
KNX/EIB KNX Gateway for Tuya ZigBee
Current metering detects the current and power, and display the changing status in real-time, the
values unit and resolution can be rewrite via the object on the bus.
Energy metering detects the current, power, voltage and energy, and display the changing status in
real-time, the values unit and resolution can be rewrite via the object on the bus.
129
KNX/EIB KNX Gateway for Tuya ZigBee
This chapter mainly list the voice control commands for Tuya Smart APP. You can find the
command of ETS function to voice control. Note: Currently , only the devices listed below are
supported.
Switch: Switch:
Alexa, turn off <device name> OK Google, turn off <device name>
Dimming: Dimming:
Alexa, set the bedroom light to fifty percent OK Google, what is the brightness level of
Switch/Dimming
Alexa, brighten <device name> <device name>?
brightness
RGB Dimming Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Switch: Switch:
RGBW Dimming Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Switch: Switch:
Alexa, turn off <device name> OK Google, turn off <device name>
Color
Dimming:
Temperature
Alexa, set the bedroom light to fifty percent
130
KNX/EIB KNX Gateway for Tuya ZigBee
Alexa, make the living room lights warmer OK Google, what is the brightness level
Alexa, set the dining room lights cooler of <device name>?
Alexa, set the dining room softer OK Google, adjust <device name> to
Alexa, make the living room light whiter 65% brightness
Color
Alexa, make the living room light warm OK Google, brighten the <device name>
Temperature
white OK Google, dim the <device name>
Alexa, set the kitchen to daylight Color temperature:
131
KNX/EIB KNX Gateway for Tuya ZigBee
Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Control mode: Control mode:
Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
name> to <mode value> value>
Temperature: Temperature:
Alexa, make it warmer in here OK Google, set the <device name> to
Alexa, make it cooler in here 350 degrees
Air conditioner Alexa, what is the target temperature of the Check actual temperature:
<device name>? OK Google, what is the current device
Alexa, set <device name> to twenty temperature?
Alexa, set <device name> to N Fan speed level:
Check actual temperature: OK Google, set the <device name> to
Alexa, what is the temperature of <device low
name> OK Google, set the <device name> to
Fan speed level: high
Alexa, set the fan speed on the <device
name> to <mode value>
132
KNX/EIB KNX Gateway for Tuya ZigBee
Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Control mode: Control mode:
Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
name> to <mode value> value>
Temperature: Temperature:
Alexa, make it warmer in here OK Google, set the <device name> to 350
Alexa, make it cooler in here degrees
Alexa, what is the target temperature of the Check actual temperature:
<device name>? OK Google, what is the current device
Air condition Alexa, set <device name> to twenty temperature?
(with swing) Alexa, set <device name> to N Fan speed level:
Check actual temperature: OK Google, set the <device name> to low
Alexa, what is the temperature of <device OK Google, set the <device name> to
name> high
Fan speed level: Swing:
Alexa, set the fan speed on the <device Turn on/off <device name>
name> to <mode value>
Swing:
Alexa, turn on horizontal swing on <device
name>
Alexa, turn off horizontal swing on <device
name>
133
KNX/EIB KNX Gateway for Tuya ZigBee
Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Control mode: Control mode:
Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
name> to <mode name> value>
Temperature: Temperature:
Room
Alexa, make it warmer in here OK Google, set the <device name> to 350
temperature
Alexa, make it cooler in here degrees
unit
Alexa, what is the target temperature of the Check actual temperature:
Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
name> to <mode name> value>
Room
Temperature: Temperature:
temperature
Alexa, make it warmer in here OK Google, set the <device name> to 350
unit
Alexa, make it cooler in here degrees
(with operation
Alexa, what is the target temperature of the Check actual temperature:
mode)
<device name>? OK Google, what is the current device
Alexa, set <device name> to twenty temperature?
Alexa, set <device name> to N
Check actual temperature:
Alexa, what is the temperature of <device
name>
134
KNX/EIB KNX Gateway for Tuya ZigBee
Power: Power:
Alexa, turn on <device name> OK Google, turn on <device name>
Alexa, turn off <device name> OK Google, turn off <device name>
Operation/Control mode: Operation/Control mode:
Alexa, set the <mode name> on the <device OK Google, set <device name> to <mode
Alexa, what is the temperature of <device OK Google, set the <device name> to high
name>
Fan speed level:
Power:
Alexa, turn on <device name>
135
KNX/EIB KNX Gateway for Tuya ZigBee
Volume: Volume:
Alexa, set the volume of the speakers to OK Google, make the <device name> a
fifty little quieter
Alexa, turn the volume down on the stereo OK Google, mute <device name>
by twenty Mute mode:
136
KNX/EIB KNX Gateway for Tuya ZigBee
Alexa, what's the <device name> <range OK Google, is the <sensor name>
name>? detecting carbon dioxide
CO2 sensor OK Google, Is carbon dioxide detected
OK Google, do you detect carbon
dioxide in the room
Presence Alexa, what's the <device name> <range
sensor name>?
Brightness Alexa, what's the <device name> <range
sensor name>?
137
KNX/EIB KNX Gateway for Tuya ZigBee
Tuya Zigbee Gateway Management System only apply to KNX Gateway for Tuya ZigBee,Premium,
use web to configure and manage the links between ZigBee devices and KNX system. Before enter to
the system, please ensure that the gateway is connected to LAN correctly, then configure IP address
and Zigbee channel via ETS. This management system only makes secondary configuration for the
devices.
Ensure the computer and mobile phone is in the same LAN, then enter IP address of the gateway in
the browser to enter Management System. The system operation and ZigBee device linking will be
138
KNX/EIB KNX Gateway for Tuya ZigBee
8.1.Gateway information
In the system, you can see the based information of the gateway, including the IP address, MAC
address, default gateway address, Tuya license account and password, and firmware version.
Click the upper right corner of the webpage to switch languages : Chinese; English.
Note: if description of ZigBee channel is set as Chinese character, please set the codepage of
project to UTF-8 at first, or that will display abnormally on the Management System after download the
139
KNX/EIB KNX Gateway for Tuya ZigBee
Click “ZigBee device list”, you can view the information of ZigBee devices that are linked/to be
linked. As follow:
Name Display ZigBee device name. User can customize the name, if it is not
Status Online/Offline
ZigBee Channel Display the bound ZigBee channel number, corresponding to the ETS
Operation DVC: use to link the ZigBee device to corresponding ZigBee channel.
setting FUN: use to link the ZigBee device to corresponding ZigBee function.
Note: If the device is already linked, the DVC button is not operable. If
140
KNX/EIB KNX Gateway for Tuya ZigBee
Click “ZigBee function list”, you can view the information of ZigBee functions that are already
Device Display device name, you can change it in “Operation setting” of “ZigBee
device list”.
Data mode Display the data transmission mode of the device. There are 3 modes:
Status: ZigBee device only uploads the current status value to the
Control: ZigBee device only receives the control command from other
Status/Control: ZigBee device not only can upload the current status
Status value Display the status value fed back from ZigBee device to KNX bus.
Note: data with decimal point is displayed as an integer, for example, the
value is 26.7, and the system displays 267; The value is 77%, and the
Device type Display the ZigBee device type, according to the linked channel and
function.
Linking Display the linked ZigBee function, you can change it in “Operation
141
KNX/EIB KNX Gateway for Tuya ZigBee
(1)Firstly, configure ZigBee channel in ETS, including name, MAC address, device type and etc..
Then download to the gateway, add the gateway and sub devices to Tuya Smart APP according to
chapter 7.1. Enter the gateway IP address in the browser into Tuya Zigbee Gateway Management
System, it displays ZigBee devices that are linked/to be linked, as shown as follow:
(2)Link KNX function. View the MAC address on the APP firstly, each ZigBee device has
corresponding unique MAC address. Click the DVC button in “ZigBee device list” page, pop-up the
setting page, then click on the “Function selection” drop-down box, select the corresponding function to
link, and then display the KNX name, which is configured in ETS and can not change. “ZigBee Device
(3)After completing the last step, auto return to “ZigBee device list” page, when the column of the
“ZigBee Channel” has number displayed, the device is linked to the ZigBee channel. At this time, the
142
KNX/EIB KNX Gateway for Tuya ZigBee
Note:
The same ZigBee channel can not be linked to multiple ZigBee devices, or it will pop-up the
If preset MAC address in ETS, as shown as follow, the gateway will assign the channel linking
automatically to the ZigBee device with this MAC address. There is no need to do steps (2) and (3) on
the system and DVC button is not operable at this time, it only need to operate step (4) to link the
ZigBee function.
MAC address can be obtained from Device information in Tuya Smart APP. View the device MAC
address as follow:
If not preset MAC address, system displays the ZigBee devices scanned by the gateway , follow
(4)Link the ZigBee function. When the device is linked the ZigBee channel, click the FUN button in
the “ZigBee device list” page, pop-up the setting page, setting as follow:
143
KNX/EIB KNX Gateway for Tuya ZigBee
Type Display the function type (bool, value, enumeration, character and etc.).
Data mode Display the data mode of the function , there are 3 modes: Status; Control;
Status/Control.
Note: data with decimal point is displayed as an integer, for example, the value
Operation Operate ZigBee device function on the APP, if the status value in the setting
setting page changes and is similar to the status information on the APP (If there are
no changes, please refresh the system), then click on the “Function selection”
e.g: The dimming device with the MAC address bc33acfffe452684 is linked to
the ZigBee channel on the system, then operate the device on the APP,
value 77% on the APP, as shown as above figure. Click the “Function selection”
drop-down box according to the status value and select the corresponding
function to link.
(5)After completing the function linking, display the configured ZigBee device on the “ZigBee
144
KNX/EIB KNX Gateway for Tuya ZigBee
(6)After completing the above steps, you can control ZigBee devices via KNX or Tuya Smart APP,
and also can upload the current status of the ZigBee device to the cloud or KNX.
(7)Edit the device name. Click EDIT button on the “ZigBee device list” page, pop-up the setting page,
enter the custom name in “Device Name” input box, click “OK”, then the device name can be replaced.
(8)Remove the device linking. Click DEL button on the “ZigBee device list” page, pop-up the page to
select whether to delete, click “OK”, then clean the linking information of the ZigBee device. As shown
as follow.
Note: After deletion, the item will be automatically arranged at the last of the list, and the FUN /
145
KNX/EIB KNX Gateway for Tuya ZigBee
KNX Gateway for Tuya ZigBee upgrades new firmware remotely (OTA) via Tuya Smart APP.
Operation as follow:
(1)Enter the gateway home page, if there is a new device firmware released, the page will pop up
the update reminder. If the new firmware is released but you do not receive the update, please contact
(2)Click “Update Now” to enter the Device Update page, which notes the Main Module New Version
and the update content. Then click “Update”, pup up the update reminder, please ensure that the power
supply for gateway is normal during updating, and it will be unavailable during the update, then click
“Start update”.
146
KNX/EIB KNX Gateway for Tuya ZigBee
User can set the gateway to update automatically. But some key device features still need to be
confirmed to update.
(4) After entering the update status, the page is shown in the figure below, please do not do
anything at this time. Wait about 1 minute, the APP prompt update success.
(5) Check the device update. Click the icon in the gateway home page to enter management
page, click “Device Update”, if upgraded, it will show “No updates available” and Main Module
version; if there is a new update, you can follow these steps above to update.
147
KNX/EIB KNX Gateway for Tuya ZigBee
If you have any questions about the latest version, please contact GVS technical support.
148