SCHEDULE OF QUANTITIES

OF DL SCOPE ELECTRICAL WORKS TENDER PACKAGE FOR IT BUILDING G1, KHARADI, PUNE
Item Pay Description RATE - RS.
No. Unit Qty. SUPPLY ITC Unit Amount
Rate
(1) (2) (3) (4) (5) (6) (7) (8)

1.0 MV SWITCHGEAR & POWER PANELS:


1.1 Supply, installation, testing and commissioning of cubicle type panels
as specified and shown on drawing. The boards shall be designed and
fabricated as per general specifications, technical details,
specifications and notes as part of this tender /BOQ and relevant BIS
codes. Also, refer to General Notes and Specifications for
Panels/Boards.
GENERAL NOTES FOR ACB's & MCCB's:
a. ACB's & MCCB's shall be of 3P or 4P as called for in the BOQ.
b. Ics = Icu = 100% for the MCCB's, MPCB's & ACB's
c. MCCB's shall be with extended rotary handle.
d. Exact rating (Amps), Poles, Type/Duty, Short circuit rating of MCCB is to
be selected by the contractor as per load, fault and requirement
and
e. Protection relay testing & tripping relay coordination is in vendor's
scope.

Notes:
i Main Aluminium busbars as specified in the drawings with bar type
feeder connections & all internal wiring (with FRLS wires) and
connections.
ii Earthing all components,frame etc. to a common internal earth bar.

iii Painting all sheet metal works.


iv All accessories & supporting structure.
v Brass glands and crimping lugs for sending and receiving ends.
vi All ammeters with C.T's and voltmeter and energy meters with
necessary fuses as shown and as required.The accuracy class of all CTs in
the MLTP panel -1& 2 shall be of 0.2s.
vii All Load Managers, Power Monitors to have parameters like KW, KVA, A,
V,KWhr,Hz,PF,KVAR, Active & Reactive component of power, RS 485
port to have BMS compatibility as required & desired to complete the
system.
viii Panel components as specified.
ix MS base frame with finish as per specification.
x All switch gear to have short circuit levels as specified.
xi All Switchgear selections shall be as per manufacturer's
recommendation.
xii Contractor to submit manufacturer's selection charts for approval.

xiii Only one make of switchgear to be used in a board /panel. The


switchgear selection shall be as per manufacturer's coordination tables.
Type-2 coordination to be achieved as a minimum.
xiv All communicable meters should be looped inside the panels and this
loop has to be brought to one terminal point in the panel for
connectivity.
xv No BMS cable should be directly connected to VFD and hence these
points will have to brought on to the terminal blocks inside the panel.

xvi All energy meters shall be dual source and communicable type. "LOAD
MANAGER ACC-CL-0.2 (MODEL-EN8400+PORT (DS) CL-0.2ACC)"

xvii EMC & RFI FILTRATION FOR VFD's.


VFD’s for sensitive installations where life critical data communications
are of importance ,like Hospitals, Airports, Electronic Industry, Data
centres, Communication centres.
These installations Must have ‘C1’ category of RFI & EMC filters for 50
meters of cable length. These are applicable to all the VFD’s of AHU’s,
fans, blowers, pumps and cooling towers.
For these above mentioned critical applications, if chiller motors and
pump motors are more than 90Kw, then ‘C2’ category of filters to be
used if ‘ C1’ is not available.
VFD’s for normal buildings and others similar installations shall have
‘C3’ category of RFI & EMC filter for AHU’s , fans, blowers, pumps,
xviii THDI for VFD's between 35% and 40% .
xix All VFD's shall be IP-20, if installed inside the panels and shall be IP55 if
installed without enclosure.
xx Incomer switchgear, bus bars, supports and outgoing switchgear shall be
of same fault level withstand capacity as mentioned for the panel.

xxi All starter feeder / VFD feeder in panels means complete with starter &
VFD as the case may be as per specifications.
xxii Use separate PLC's for Load management and separate for interlocking
of breakers and bus couplers and closing of bus couplers.

xxiii Fire Suppression System provision to be made in the desired


panels all panels as mentioned in the SLD, during panel
manufacturing.
xxiv All ACB body earthing to provided.
xxv APFC panel - MLTP Terminal to cut off APFC power while power
feed from DG source.
xxvi Door locks Zinc alloy powder painted with provision for
pad
xxvii locking. insulation: Black heat shrinkable, fire retardant, self
Busbar
extinguishing type sleeves suitable to withstand 110 degree
celcius.
xxviii Completely modular & compartmentalized, form 3B separation.
Separate adequately spaced Unit Chamber, Bus bar & cable
compartments.
xxix Gland earthing provision to be given in the panel.
All MCCBs up to 200A shall be therma magnetic without earth fault.
Rating>/= 250A shall be microprocessor based without Earth
fault.=OK but whenever specifed in sld seprate E/F reqd
xxiii GENERAL NOTES FOR TRANSIENT VOLTAGE SURGE SUPPRESSOR
(TVSS):
a. Transient Voltage Surge Suppressors (TVSS) shall be mounted out side
the panel / switch board in a sheet steel enclosure.
b. It shall be suitable for handling required (specified) surge handling
capacity, shall be 10 modes protection with noise filters. (EMI & RFI) and
with inbuilt back up fuse protection.
c. Surge suppressor shall be complete with isolating / protective device in
the form of MCB / MCCB of KA rating (breaking capacity) as of switch
board.
All panels shall be as per IEC-61439 Standard.
All equipment nomencluture as per BSC standard ( two coat of
yellow paint+Black letter)
Considered TP+100%NL for MCCB's & ACB's wherever TPN MCCB/ACB is
mentioned in SLD.
1.1.1 Each Main L.T Panel -1 as required, specified and shown on Drg.No. G1-EL- 1.00 1.00 2.00 2.00
1
SLD-01 along with ATS communication Module
Note: All the out going feeders in the Main LT panel-1 to be provided
with a pair of Potential Free contact to trip the APFCR at the
client
1.1.2 Each Main L.T Panel -2 as required, specified and shown on Drg.No. G1-EL- 1.00 1.00 2.00 2.00
1
SLD-01 along with ATS communication Module

1.1.3 Retails tenant panel specified & shown in G1-EL-SLD-01 Drg.No. G1-EL- 1.00 1.00 2.00 2.00
1
SLD-01

1.1.3 Each Transformer L.T Panel as required, specified and shown on Drg.No. G1- 1.00 1.00 2.00 2.00
1
EL-SLD-01

1.2 Kg Supply & laying of M.S chequered plate & M.S angles (2 coat of Red 1.00 1.00 2.00 7,000.00
oxide and 2 coat of Black oil paint ) to be laid on the U.G trench/
Electrical room/ floor as required. ( cutting , wedling
and Fabrication , anchor fastener cost to be included in above ) Make 3500
M/s Ishwar Ispat Industries Pvt Ltd / Shree Hanuman Loha Ltd. /
Balajee Structurals India Ltd.

Total for 1.0 7008

2.0 CONTROL CABLES & CABLE TRAYS:

The rate shall also include the following:


i Effecting adequate and proper connections at terminations.
ii Providing all fixing accessories such as clamping devices nuts, bolts and
screws.
iii Excavation for laying of cables, filling of sand, brick protection, back
filling of earth, watering, ramming and making good as approved in
directly ground burry.
iv Wherever the cables are of aluminum and bus bars of copper bimetallic
lugs shall be used.
v All cable shall be laid with one diameter gap or as specified or as called
for.
vi All cable shall be IS approved.
vii Fire retardent paint one meter on both side of wall penetration and at
termination as per specifications.
viii Burried LT cables to be laid atleast 750mm below ground.
ix All cutouts / sleeves shall be sealed with fire retardant sealent as
approved.
x Leave sufficient cable loops at both the cable ends.
xi Use Tinned copper thimbles/lugs with copper cables/copper wires.

xii Nylon cable tie is not acceptable, matelic cable tie/clamp to be consider
for cable laying.
Making necessary cutout/hole's in wall is in vendor scope
2.1 Supply, laying, testing and commissioning of the following sizes of 1.1
KV grade XLPE insulated, Extruded FR-LSH PVC inner sheath Type ST-2,
FR-LSH PVC outer sheath Type ST-2, stranded Copper conductor,
Armoured control cable in the existing pipes, channels, trays etc.
complete as required and as per specifications as per IS: 7098 Part-I.

2.1.1 RM 2C x 2.5 sq.mm. Cu. Ar. XLPE Cable 300 1.00 1.00 2.00 600.00
2.1.2 RM 2C x 4 sq.mm. Cu. Ar. XLPE Cable 300 1.00 1.00 2.00 600.00
2.1.3 RM 2C x 6 sq.mm. Cu. Ar. XLPE Cable 50 1.00 1.00 2.00 100.00
2.1.4 RM 4C x 2.5 sq.mm. Cu. Shielded Cable 50 1.00 1.00 2.00 100.00
2.1.5 RM 6C x 2.5 sq.mm. Cu. Ar. XLPE Cable 50 1.00 1.00 2.00 100.00
2.1.6 RM 8C x 2.5 sq.mm. Cu. Ar. XLPE Cable 50 1.00 1.00 2.00 100.00
2.1.7 RM 12C x 2.5 sq.mm. Cu. Ar. XLPE Cable 300 1.00 1.00 2.00 600.00
2.1.8 RM 16C x 2.5 sq.mm. Cu. Ar. XLPE Cable 300 1.00 1.00 2.00 600.00
2.1.9 RM 19X2.5 sqmm Cu. Ar. XLPE Cable 100 1.00 1.00 2.00 200.00
2.1.10 RM 4CX1.5 cu control cable 100 1.00 1.00 2.00 200.00
2.1.11 RM 3CX1.5 Cu shilded cable 100 1.00 1.00 2.00 200.00
2.2 Making end terminations for the following sizes of 1.1 KV grade XLPE
insulated, Extruded FR-LSH PVC inner sheath Type ST-2, FR-LSH PVC
outer sheath Type ST-2, stranded Copper conductor, Armoured control
cables including providing tinned copper terminal lugs, single
compression brass cable glands, insulation tape, effecting terminal
connections to the equipment complete as required as per IS: 7098, Part
I.
2.2.1 Nos. 2C x 2.5 sq.mm. Cu. Ar. XLPE Cable 10 1.00 1.00 2.00 20.00
2.2.2 Nos. 2C x 4 sq.mm. Cu. Ar. XLPE Cable 10 1.00 1.00 2.00 20.00
2.2.3 Nos. 2C x 6 sq.mm. Cu. Ar. XLPE Cable 5 1.00 1.00 2.00 10.00
2.2.4 Nos. 4C x 2.5 sq.mm. Cu. Shielded Cable 5 1.00 1.00 2.00 10.00
2.2.5 Nos. 6C x 2.5 sq.mm. Cu. Ar. XLPE Cable 5 1.00 1.00 2.00 10.00
2.2.6 Nos. 8C x 2.5 sq.mm. Cu. Ar. XLPE Cable 4 1.00 1.00 2.00 8.00
2.2.7 Nos. 12C x 2.5 sq.mm. Cu. Ar. XLPE Cable 10 1.00 1.00 2.00 20.00
2.2.8 Nos. 16C x 2.5 sq.mm. Cu. Ar. XLPE Cable 10 1.00 1.00 2.00 20.00
2.2.9 Nos. 19X2.5 sqmm Cu. Ar. XLPE Cable 10 1.00 1.00 2.00 20.00
2.2.10 Nos. 4CX1.5 Cu. Ar. XLPE Cable 10 1.00 1.00 2.00 20.00
2.2.11 Nos. 3CX1.5 Cu shilded cable 10 1.00 1.00 2.00 20.00
2.3 Supply, fabrication and installation of Hot dip galvanised factory built
perforated type cable trays complete with all bends, tees, elbows,
reducers, supports & fixing arrangement etc. of various widths in single
tier/two tier/ three tier/ five tier fashion either on one side of the wall
or on two sides of the wall or ceiling/wall/floor. (All bends & tees shall
be of factory built of same make as that of tray). Cable tray supports
are supposed to be included in the rate of the trays. Nothing extra to be
paid for cable tray supports. Cable trays and supports shall be as per
specifications. Cable tray supports shall also be MS for indoor
installation & GI for outdoor installation Hot dip galvanised. Use
modular factory fabricated cable tray supporting system as per
specifications. Contractor to be responsible for the design and execution
of a failsafe cable supporting system.
Cable tray supports shall be included in cost of cable tray. Support to be 0
considered as MS for indoor installation & GI for outdoor installation.

Since there is discrepancy between thickness of tray mentioned in 0


specification & BOQ description, so the thickness of tray shall be 2mm
for 600mm and below sizes and 2.5mm for 750mm & above sizes.

Cable tray accessories such as HORIZONTAL BEND, VERTICAL BEND, TEE


BEND and ELBOW you can considered as site fabricated with
proper
2.3.1 mtr 150mm wide tray 150 1.00 1.00 2.00 300.00
2.3.2 mtr 300mm wide tray x 75MM 90 1.00 1.00 2.00 180.00
2.3.3 mtr 450mm wide tray x 75MM 80 1.00 1.00 2.00 160.00
2.3.4 mtr 600mm wide tray x 75MM 25 1.00 1.00 2.00 50.00
2.3.5 mtr 1000mm wide tray x100MM 25 1.00 1.00 2.00 50.00
2.3.5 PITC OF GI TRUNKING with cover 100X100X1.5 mm pre 1.00 1.00 2.00 78.00
galvanised,complete with all bends, tees, elbows, reducers, Junction
box , nockout punch supports & fixing arrangement etc. of various
widths in single tier/two tier/ three tier/ five tier fashion either on
one side of the wall or on two sides of the wall or ceiling/wall/floor,
supports to be included in the rate of the trunking . Nothing extra to
RM
be paid for trunking supports. trunking and supports shall be as per
specifications. trunking supports shall also be pre galvanised. Use
modular factory fabricated trunking supporting system as per
specifications. Contractor to be responsible for the design and
execution of a failsafe trunking supporting system.
39
2.3.6 PITC OF GI TRUNKING with cover 100X50X1.5 mm pre 1.00 1.00 2.00 60.00
galvanised,complete with all bends, tees, elbows, reducers, Junction
box , nockout punch supports & fixing arrangement etc. of various
widths in single tier/two tier/ three tier/ five tier fashion either on
one side of the wall or on two sides of the wall or ceiling/wall/floor,
supports to be included in the rate of the trunking . Nothing extra to
RM
be paid for trunking supports. trunking and supports shall be as per
specifications. trunking supports shall also be pre galvanised. Use
modular factory fabricated trunking supporting system as per
specifications. Contractor to be responsible for the design and
execution of a failsafe trunking supporting system.
30
2.3.7 PITC OF GI TRUNKING with cover 200X50X1.5 mm pre 1.00 1.00 2.00 60.00
galvanised,complete with all bends, tees, elbows, reducers, Junction
box , nockout punch supports & fixing arrangement etc. of various
widths in single tier/two tier/ three tier/ five tier fashion either on
one side of the wall or on two sides of the wall or ceiling/wall/floor,
supports to be included in the rate of the trunking . Nothing extra to
RM
be paid for trunking supports. trunking and supports shall be as per
specifications. trunking supports shall also be pre galvanised. Use
modular factory fabricated trunking supporting system as per
specifications. Contractor to be responsible for the design and
execution of a failsafe trunking supporting system.
30
0
2.4 CABLE TAGGING 0
Nos. Supply & fixing of Al. cable tags as approved. 100 1.00 1.00 2.00 200.00
Total for 2.0 4716

3.0 EARTHING:

3.1 Plate Earthing Stations


Each Providing Plate earthing stations for equipment earthing with 600 x 600
x 3 mm copper plate as specified and required and in IS 3043 -1988 R0
complete with:
a. Excavation in hard murram
b. Electrode with disconnecting link arrangement.
c. Watering pipe.
d. Brick masonary chamber with Heavy Duty RCC frame and covers with 40
T passing capacity
e. Charcoal & salt fill.

3.2 ASHLOK Earthing Stations


3.2.1 Each Type T 39 Providing Pipe earthing stations for equipment earthing with 1.00 1.00 2.00 6.00
3mtr length, dia of pipe 40mm inner, 80mm outer G.I. pipe as specified 3
and required and in IS 3043 -1987 complete with:
a. Excavation in hard murram
b. Electrode with disconnecting link arrangement.
c. Inner pipe. With (200-250 microns)
d. outer pipe G.I. pipe plated with 80-70 microns
e. back fill compound -moisture retaining compound having 13 times more
(hygroscopic) water retaining capacity then its dry volume.

Cost of Brick masonary chamber not in Electrical vendor scope


3.2.2 Each Type T 39 Providing Pipe earthing stations for equipment earthing with 1.00 1.00 2.00 6.00
3mtr length, dia of pipe 40mm inner, 80mm outer CU. pipe as specified 3
and required and in IS 3043 -1987 complete with:
a. Excavation in hard murram
b. Electrode with disconnecting link arrangement.
c. Inner pipe. With (200-250 microns)
d. outer pipe Cu. pipe plated with 80-70 microns
e. back fill compound -moisture retaining compound having 13 times more
(hygroscopic) water retaining capacity then its dry volume.

Cost of Brick masonary chamber not in Electrical vendor scope


3.2.3 Each SITC 40 TON capacity FRP cover exclusive of civil works. 2 1.00 1.00 2.00 4.00
3.2.4 Each SITC 20 TON capacity FRP cover exclusive of civil works. 2 1.00 1.00 2.00 4.00
3.2.5 Each SITC 5 TON capacity FRP cover exclusive of civil works. 2 1.00 1.00 2.00 4.00

3.3 Earth wire/strips


Supply & laying Cu/G.I. earthing strips for interconnecting the earthing
stations, panels, DB's etc. in built-up trenches, on walls/ceiling, buried in
ground, generally as specified & shown on drawings complete with:

a. Fixing accessories.
b. Corrosion protection of buried conductors with bituminous coating and
covered with PVC tapes.

GI Strips:
3.3.1 mtr 75 x 10 mm G.I. Strip 100 1.00 1.00 2.00 200.00
3.3.2 mtr 75 x 6 mm G.I. Strip 50 1.00 1.00 2.00 100.00
3.3.3 mtr 50 x 10 mm G.I. Strip 200 1.00 1.00 2.00 400.00
3.3.4 mtr 50 x 6 mm G.I. Strip 100 1.00 1.00 2.00 200.00
3.3.5 mtr 40 x 10 mm G.I. Strip 200 1.00 1.00 2.00 400.00
3.3.6 mtr 40 x 6 mm G.I. Strip 75 1.00 1.00 2.00 150.00
3.3.7 mtr 32 x 10 mm G.I. Strip 25 1.00 1.00 2.00 50.00
3.3.8 mtr 32 x 6 mm G.I. Strip 100 1.00 1.00 2.00 200.00
3.3.9 mtr 25 x 10 mm G.I. Strip 250 1.00 1.00 2.00 500.00
3.3.10 mtr 25 x 6 mm G.I. Strip 150 1.00 1.00 2.00 300.00
3.3.11 mtr 25 x 3 mm G.I. Strip 50 1.00 1.00 2.00 100.00
Copper Strips:
3.3.11 mtr 50 x 10 mm Cu. Strip 50 1.00 1.00 2.00 100.00
3.3.12 mtr 50 x 6 mm Cu. Strip 100 1.00 1.00 2.00 200.00
3.3.13 mtr 40 x 10 mm Cu. Strip 50 1.00 1.00 2.00 100.00
3.3.14 mtr 40 x 6 mm Cu. Strip 100 1.00 1.00 2.00 200.00
3.3.15 mtr 32 x 10 mm Cu. Strip 25 1.00 1.00 2.00 50.00
3.3.16 mtr 32 x 6 mm Cu. Strip 50 1.00 1.00 2.00 100.00
3.3.17 mtr 25 x 10 mm Cu. Strip 25 1.00 1.00 2.00 50.00
3.3.18 mtr 25 x 6 mm Cu. Strip 95 1.00 1.00 2.00 190.00
3.3.19 mtr 25 x 3 mm Cu. Strip
Total for 3.0 3614

4.0 SUPPLY & INSTALLATION OF BUS DUCT:

4.1 BUS DUCT - INDOOR (AT CEILING LEVEL) IP:55, 50kA


Supply, Installation, Testing, and Commissioning of Sandwich
Busway
1100 volts system Busduct with cooling Fins, 4bar - 3P & 1N,
aluminum conductor with body / enclosure acting as earth, as per
specifications, suitable for 3ph 4wire 50HZ, 50 KA short circuit fault
withstand capacity for 1 Sec. The Busway shall have a system of single
bolt double head section jointing system. The bus duct suspension
system shall be complete with steel rods, GI angle supports and dash
fasteners etc. at required intervals for safe installation of bus ducts.
Supporting system shall be fail proof even in earth quake situations, as
per Sesmic requirement at site.
Necessary flexible joints to be provided for building expansion joints and
for thermal expansion as may be required.
Insulation Class- class F can withstand a maximum temperature of 155
deg C, whereas class B can withstand a maximum temperature of 130
deg C. So Class F is a superior insulation over class B and bus duct life
will be longer. But class B may also be considered as per IEC 61439-6
temp rise clause
Steel supports used for installation of bus ducts shall be measured
separately under kg item.
Cost to include in straight run of bus duct for 2runs of 50 x 6 GI earthing
strips.
The Rising main shall be measured on the center line which includes 2
runs of earting strips.
All equipment nomencluture as per BSC standard ( two coat of
yellow paint+Black letter)
Making necessary cutout/hole in wall is in vendor scope
4.1.1 3200 AMP, 4P, 50kA BUS DUCT
FROM TRANSFORMER-1 TO L.T. KIOSK-1
(I) Set Tinned copper flexible connection at Transformer-1. 1 1.00 1.00 2.00 2.00
(II) Set Tinned copper flexible connection at L.T. Kiosk-1. 1 1.00 1.00 2.00 2.00
(III) Straight Run. Inclusive of End flange at Transformer end,LT Kiosk,vertical 1.00 1.00 2.00 30.00
RM bend,horizontal bens, off set & phase crossover 15

4.1.2 3200 AMP, 4P, 50kA BUS DUCT


FROM TRANSFORMER-2 TO TO L.T. KIOSK-2
(I) Set Tinned copper flexible connection at Transformer-2. 1 1.00 1.00 2.00 2.00
(II) Set Tinned copper flexible connection at Transformer L.T. Panel end. 1 1.00 1.00 2.00 2.00
(III) Straight Run. Inclusive of End flange at Transformer end,LT Kiosk,vertical 1.00 1.00 2.00 30.00
RM bend,horizontal bens, off set & phase crossover 15
4.1.3 3200 AMP, 4P, 50kA BUS DUCT
FROM TRANSFORMER-3 TO L.T. KIOSK-3
(I) Set Tinned copper flexible connection at Transformer-3. 1 1.00 1.00 2.00 2.00
(II) Set Tinned copper flexible connection at L.T. Kiosk-3. 1 1.00 1.00 2.00 2.00
(III) Straight Run. Inclusive of End flange at Transformer end,LT Kiosk,vertical 1.00 1.00 2.00 30.00
RM bend,horizontal bens, off set & phase crossover 15

4.1.4 3200 AMP, 4P, 50kA BUS DUCT


FROM L.T. KIOSK-1 TO MAIN L.T. PANEL-1_SECTION-1
(I) Set Tinned copper flexible connection at L.T. Isolator/Kiosk-1. 1 1.00 1.00 2.00 2.00
(II) Set Tinned copper flexible connection at Main L.T. Panel-1_Section-1. 1 1.00 1.00 2.00 2.00
(III) Straight Run. Inclusive of End flange at Transformer end,LT Kiosk,vertical 1.00 1.00 2.00 140.00
RM bend,horizontal bens, off set & phase crossover 70

4.1.5 3200 AMP, 4P, 50kA BUS DUCT


FROM L.T. KIOSK-2 TO MAIN L.T. PANEL-1_SECTION-2 & MAIN L.T.
PANEL-2_SECTION-2
(I) Set Tinned copper flexible connection at Transformer L.T. Panel. 2 1.00 1.00 2.00 4.00
(II) Set Tinned copper flexible connection at Main L.T. Panel-1_Section-2. 2 1.00 1.00 2.00 4.00
(III) Straight Run. Inclusive of End flange at Transformer end,LT Kiosk,vertical 1.00 1.00 2.00 260.00
RM bend,horizontal bens, off set & phase crossover 130

4.1.6 3200 AMP, 4P, 50kA BUS DUCT


FROM L.T. KIOSK-3 TO MAIN L.T. PANEL-2_SECTION-1
(I) Set Tinned copper flexible connection at Transformer L.T. Panel. 1 1.00 1.00 2.00 2.00
(II) Set Tinned copper flexible connection at Main L.T. Panel-2_Section-1. 1 1.00 1.00 2.00 2.00
(III) Straight Run. Inclusive of End flange at Transformer end,LT Kiosk,vertical 1.00 1.00 2.00 140.00
RM bend,horizontal bens, off set & phase crossover 70

4.1.7 PITC Adaptor box along with necessary extension of bus bar for 1.00 1.00 2.00 8.00
transformer/DG 4
Total for 4.0 666

5.0 TRANSFORMERS:
5.1 Loading, unloading alongwith Mathadi charges and shifting to
transformer room, Installation, testing & commissioning of of
22KV/0.433 KV, 2000kVA continuous duty cycle, 22kV/433V, 3 phase,
50Hz, Dyn-11 vector group, step down, indoor type, copper strip wound,
dry type - Resin Casted transformer complete with vacuum type OLTC,
RTCC & AVR and with all accessories, including winding temperature
scanner with alarm and trip contact, fittings and conforming to
specifications. Tap changing range shall be +15% to -15% in steps of
2.5%. Transformer shall have cable box for 22kV XPLE cable on HT side
& LV Busduct box on 433V voltage side. One set of 22KV surge
suppressor at 22KV and one set of 433V surge suppressor at 433V side.
Control wiring for from trafo. to RTCC and AVR shall be included in the
cost. Transformer shall meet latest ECBC code of India on NO LOAD &
ON LOAD power losses. Transformer to be as per technical specifications
and any deviation to be submitted with quotation. All the tools, tackles
and Machineries shall be part of vendor scope.

All equipment nomencluture as per BSC standard ( two coat of 0


yellow paint+Black letter)
i Installing, testing & commissioning generally as specified and shown on 0
drawings.
ii Termination of incoming/outgoing cables or bus ducts as required and 0
or as specified including the necessary cu Bus Bar extension
chambers,adopter box etc.,
iii Required Foundation for Mounting Transformers
iv Inspection of the above by Electricity Supply Board and getting the
approval at site of installation.
v with all required structural supports/frames.

5.2 Each Installation, testing & commissioning of 2000 KVA Dry Type 1.00 1.00 2.00 6.00
3
Transformers as described above.

5.3 Each Supply, installation, testing & commisioning of LT kiosk breaker of rating 1.00 1.00 2.00 4.00
3200A 4P MDO, ACB, 50kA in GI enclosure(IP:55) including all the
2
structural supports/frames as required, specified and shown on
drawings (Indoor Type)

5.4 Each Supply of Transfomer Protection Panel for 4 Nos TR with ANN and TR 1.00 1.00 2.00 2.00
1
Aux Relay
5.5 Each 24V DC 6A power pack for the RTCC Panel 3 1.00 1.00 2.00 6.00

Total for 5.0 18

6.0 H.T. SWITCHGEAR:

6.1 CONSUMER HT PANEL


'22KV/750 MVA, Motorised HT Breaker
Seven Panel, (Two incomers & five outgoings) RMU Type consisting of
22KV SF-6 Gas Insulated vacuum circuit breaker for 'incomers and
outgoings complete. Motorised Spring charging Mechanism shall be 24V
DC, closing & trip coil shall be 24V DC.
Each Incomer & Outgoing module shall be with 230V/24V DC power
pack.

Each Incomer & Outgoing module shall be with suitable dual core cast
resin CT's for metering & protection, IDMT relay & digital ammeter. CT's
shall be of suitable class & burden.
HT Switchgears in 'Stainless Steel Tank of SS 304 Grade, Thickness 2.5
mm with robotic welding (Prototype inspection), 'Bushing shall site
detachable/ site replacing, 'Boot shall inclusive, seprate battery charger
for operation ( 24V BATTERY charger with battery bank),
CT class 0.2S PS

Incomer Module shall have suitable PT's, cast resin type of suitable
burden, BMS compatible MFM with RS 485 port having parameters like
KW, KVA, A, V, KWhr, Hz, PF, KVAR, Active & Reactive component
of power RS 485 port to have BMS compatiblility. Metering & PT's shall
be

As per specification and equipment data sheet and drawing including


the following:
i. Supply, loading & unloading at site of installation.
ii Installation, testing & commissioning generally as specified and shown
on drawings.
iii Inspection of the above by Electricity Supply Board and getting the
approval at site of installation.
Termination of incoming/outgoing cables as required and or as specified
including the necessary Bus Bar extension chambers etc.,
iv
Earthing all components,frame etc. to a common internal earth bar.
v
vi Painting all sheet metal works.
All accessories & supporting structures, MS base frame with finish as per
vii specification.
viii Panel components as specified.
ix with all required exhaust/SA fans as per requirement.
with required short circuit rating re-engineered as per requirement but
x not less than shown in the dwg.
All equipment nomencluture as per BSC standard ( two coat of
yellow paint+Black letter)
Consumer HT Panel '22KV/750 MVA, Motorised HT Breaker as described 1.00 1.00 2.00 2.00
1
Set above

6.2 No. Design, manufacturing and supply of 22kV HT load break switch, 22kV,
RO
750MVA, TP HT switch with fuses.

Total for 6.0 2

7.0 H.T. CABLE:

7.1 Supply, laying & testing of 22KV 3C XLPE armoured aluminium cables
including all accessories, supports, clamps, structural angles etc., as
required and as specifed in complete.
7.1.1 RM 3C x 300 Sqmm 550 1.00 1.00 2.00 1,100.00

7.2 Making cable end terminations with glands, lugs, compound etc. as
specified for the above XLPE cables.
7.2.1 NO 3C x 300 Sqmm indoor termination kit 14 1.00 1.00 2.00 28.00

7.2.2 No 3Cx300 sqmm Touch proof termination Kit 8 1.00 1.00 2.00 16.00

7.3 Supply & Installation of following voltage grade rubber mat (2mtr x 1
mtr)
7.3.1 Each 22 KV Grade 1.00 1.00 2.00 100.00
50
7.3.2 Each 1.1 KV Grade 1.00 1.00 2.00 100.00
50

Total for 7.0 1344

8 SAFETY AND TESTING EQUIPMENTS:


Supplying and erection of the following equipment at suitable place in
the sub-station building as required.
8.1 M.S. buckets 5 nos. of 20 litres capacity painted with red oxide paint & 1.00 1.00 2.00 4.00
lettered as ‘Fire’ with White and mounted on free standing stand, as
Set required including filling with dry sand. 2
8.2 First aid box as approved by St. John Ambulance Brigade /Indian Red 1.00 1.00 2.00 4.00
Nos Cross society conforming to IS : 2217 - 1963. 2
8.3 Shock treatment chart duly mounted on a wooden frame with glass on, 1.00 1.00 2.00 4.00
Nos. as required in 2 languages (Hindi & English). 2
8.4 Providing and fixing High Voltage danger notice plate 250 mm. x 200 1.00 1.00 2.00 8.00
mm. made of M.S. 2 mm. thick and vitreous enamelled white on both
sides and with inscription in signal red colour on front side as required.
Nos. 4
8.5 Providing and fixing Medium Voltage Danger Notice Plate 200 mm. x 1.00 1.00 2.00 8.00
200 mm. made of MS 2 mm. thick and vitreous enamelled white on both
sides and with inscription in signal red 'colour on front side as required.
Nos 4
8.6 Elastomer mat 1000 mm. wide, 3mm thick, for above 11kV and upto 1.00 1.00 2.00 200.00
65kV grade as per Latest BIS Codes (IS: 15652/2006). (Vendor to check
the thickness of the mat as per latest IS code & Quoe accordingly and
RM also mention the thickness provided). 100
8.7 Elastomer mat 1000 mm. wide, 2mm thick, for upto 3.3kV grade 1.00 1.00 2.00 600.00
as per Latest BIS Codes (IS: 15652/2006). (Vendor to check the
thickness of the mat as per latest IS code & Quoe accordingly and
RM also mention the thickness prov ided). 300
8.8 Pairs Rubber gloves of 22kV grade as per per Latest BIS Codes 2 1.00 1.00 2.00 4.00

Total for 8 832

9.0 APPROVALS:

9.1 INSTALLATION APPROVAL CHARGES:


Carrying out the necessary works including liaison with the local Chief 1.00 1.00 2.00 2.00
Electrical Inspectorate's Office and organising site tests/inspection
by the state's inspectorate and obtaining the certificate/approval for 1
safe installation. All the official fees for approval charges shall be
reimbursed by the owner on producing the govt. receipt.
Lot

Total for9.0 2