0% found this document useful (0 votes)
15 views17 pages

Data Sheet 6ES7636-2EB00-0AE3: Operator Control and Monitoring

Uploaded by

pebeh32698
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views17 pages

Data Sheet 6ES7636-2EB00-0AE3: Operator Control and Monitoring

Uploaded by

pebeh32698
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

Data sheet 6ES7636-2EB00-0AE3

***Spare part*** SIMATIC C7-636 Touch, Complete unit with


integrated components: S7-300 CPU 315-2 DP and TP 270, 24 DI,
16 DO, 5 AI, 2 AO; Micro Memory Card and connector set required

Operator control and monitoring


Password protection Yes
● Password levels 10
Text elements Yes
Info texts Yes
Graphics object Yes
Process images Yes
Alarms Yes; Fault messages, operating messages
Graphics object
● Character graphics Yes
● Pixel graphics Yes
Process images
● Number of process images 300
● Number of variables per image, max. 200
● Number of variables in message text, max. 8
Operating-/fault messages
● Number of entries in operational log, max. Message archive limited by storage medium
● Number of entries in fault message buffer, max. Message archive limited by storage medium
Recipes

6ES7636-2EB00-0AE3 Subject to change without notice


Page 1/17 09/05/2019 © Copyright Siemens
● Number, max. 300
● Data records per recipe, max. 500
● Entries per data record, max. 1 000

Display
Design of display CSTN, CCFL backlit; 10.4" color (256 colors)
Resolution (pixels)
● Horizontal image resolution 640 Pixel
● Vertical image resolution 480 Pixel
Backlighting
● MTBF backlighting (at 25 °C) 60 000 h

Control elements
Touch operation
● Design as touch screen Yes

Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Digital inputs
— Rated value (DC) 24 V
— Reverse polarity protection Yes
Digital outputs
— Rated value (DC) 24 V
— Reverse polarity protection Yes
Analog outputs
— Rated value (DC) 24 V
— Reverse polarity protection Yes

Input current
Current consumption, typ. 650 mA; idling
Current consumption, max. 1.5 A
Inrush current, max. 3 A; 3 A for 10 ms, then 2 A for 70 ms
Digital inputs
● from load voltage L+ (without load), max. 70 mA
Digital outputs
● from load voltage L+, max. 20 mA; per group

Power loss

6ES7636-2EB00-0AE3 Subject to change without notice


Page 2/17 09/05/2019 © Copyright Siemens
Power loss, typ. 24 W

Memory
Micro Memory Card Yes
Work memory
● integrated 128 kbyte
● expandable No
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● with battery Yes; Option for the panel
● without battery Yes; Program and data of the CPU

Battery
Backup battery
● Backup battery (optional) Yes

CPU processing times


for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs

CPU-blocks
DB
● Number, max. 1 023; DB 0 reserved
● Size, max. 16 kbyte
FB
● Number, max. 2 048; see instruction list
● Size, max. 16 kbyte
FC
● Number, max. 2 048; see instruction list
● Size, max. 16 kbyte
OB
● Number, max. see instruction list
● Size, max. 16 kbyte
Nesting depth
● per priority class 8
● additional within an error OB 4

Counters, timers and their retentivity


S7 counter
● Number 256

6ES7636-2EB00-0AE3 Subject to change without notice


Page 3/17 09/05/2019 © Copyright Siemens
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 256
— preset Z 0 to Z 7
Counting range
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 256
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)

Data areas and their retentivity


Retentive data area (incl. timers, counters, flags), all
max.
Flag
● Number, max. 2 048 byte
● Retentivity available Yes; MB 0 to MB 255
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Local data
● per priority class, max. 1 024 byte; max. 510 bytes per block

Address area
I/O address area
● Inputs 2 kbyte
● Outputs 2 kbyte
of which distributed

6ES7636-2EB00-0AE3 Subject to change without notice


Page 4/17 09/05/2019 © Copyright Siemens
— Inputs 2 000 byte
— Outputs 2 000 byte
Process image
● Inputs 128 byte
● Outputs 128 byte
Default addresses of the integrated channels
— Digital inputs 124.0 to 126.7
— Digital outputs 124.0 to 125.7
— Analog inputs 752
— Analog outputs 761
Digital channels
● Inputs 16 384
— of which central 992
● Outputs 16 384
— of which central 992
Analog channels
● Inputs 1 024
— of which central 248
● Outputs 1 024
— of which central 248

Hardware configuration
Number of modules per system, max. 23
Number of DP masters
● integrated 1
● via CP 1
Number of operable FMs and CPs (recommended)
● FM 8
● CP, PtP 8
● CP, LAN 10
Expansion modules
● Number of expansion modules, max. 4; max. 2 flat arrangement, max. 4 deep arrangement, max. 23 via
IM
Rack
● Racks, max. 4
● Modules per rack, max. 8; Modules in subrack 0: 4 max.; modules in subracks 1 and 2: 8
max.; modules in subrack 3: 7 max.
● Number of lines, max. 4

Time of day
Clock
● Hardware clock (real-time) Yes
● retentive and synchronizable Yes

6ES7636-2EB00-0AE3 Subject to change without notice


Page 5/17 09/05/2019 © Copyright Siemens
● Backup time 6 wk; At 40 °C ambient temperature
● Deviation per day, max. 10 s
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1h
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● in AS, master Yes

Digital inputs
Number of digital inputs 24
● of which inputs usable for technological 16
functions
Input characteristic curve in accordance with IEC Yes
61131, type 1
Number of simultaneously controllable inputs
horizontal installation
— up to 40 °C, max. 12
vertical installation
— up to 40 °C, max. 18
Input voltage
● Rated value (DC) 24 V
● for signal "0" -3 to +5V
● for signal "1" +15 to +30V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.1 / 0.3 / 3 / 15 ms
— Rated value 3 ms
for technological functions
— at "0" to "1", max. 8 µs
Cable length
● shielded, max. 1 000 m; 100 m for technological functions
● unshielded, max. 600 m
for technological functions
— shielded, max. 50 m; at maximum count frequency
— unshielded, max. not allowed

6ES7636-2EB00-0AE3 Subject to change without notice


Page 6/17 09/05/2019 © Copyright Siemens
Digital outputs
Number of digital outputs 16
● of which high-speed outputs 4
Short-circuit protection Yes; Clocked electronically
● Response threshold, typ. 1A
Limitation of inductive shutdown voltage to L+ (-48 V)
Controlling a digital input Yes
Switching capacity of the outputs
● on lamp load, max. 5W
Load resistance range
● lower limit 48 Ω
● upper limit 4 kΩ
Output voltage
● for signal "1", min. L+ (-0.8 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, min. 5 mA
● for signal "1" permissible range, max. 0.6 A
● for signal "1" permissible range for 0 to 40 °C, 0.5 A
max.
● for signal "1" permissible range for 40 to 60 °C, 0.5 A; Up to 50 °C
max.
● for signal "1" minimum load current 5 mA
● for signal "0" residual current, max. 0.5 mA
Parallel switching of two outputs
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 100 Hz
● of the pulse outputs, with resistive load, max. 2.5 kHz
Total current of the outputs (per group)
all mounting positions
— up to 40 °C, max. 3A
— up to 60 °C, max. 2 A; Up to 50 °C
horizontal installation
— up to 40 °C, max. 2A
vertical installation
— up to 40 °C, max. 3A
Cable length
● shielded, max. 1 000 m

6ES7636-2EB00-0AE3 Subject to change without notice


Page 7/17 09/05/2019 © Copyright Siemens
● unshielded, max. 600 m

Analog inputs
Number of analog inputs 4
● For voltage/current measurement 4
● For resistance/resistance thermometer 1
measurement
integrated channels (AI) 4; + 1 AI
permissible input voltage for current input 2.5 V; max. 2.5 V permanent; max. 24 V for short time
(destruction limit), max.
permissible input voltage for voltage input 30 V; Permanent
(destruction limit), max.
permissible input current for voltage input 0.5 mA; Permanent
(destruction limit), max.
permissible input current for current input (destruction 50 mA; Permanent
limit), max.
No-load voltage for resistance-type transmitter, typ. 2.5 V
Constant measurement current for resistance-type 1.8 to 3.3 mA
transmitter, typ.
Technical unit for temperature measurement Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
adjustable
Input ranges
● Voltage Yes
● Current Yes
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 50 Ω
● -20 mA to +20 mA Yes
● Input resistance (-20 mA to +20 mA) 50 Ω
● 4 mA to 20 mA Yes
● Input resistance (4 mA to 20 mA) 50 Ω
Input ranges (rated values), resistance thermometer
● Pt 100 Yes
● Input resistance (Pt 100) 10 MΩ
Input ranges (rated values), resistors
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 10 MΩ
Thermocouple (TC)

6ES7636-2EB00-0AE3 Subject to change without notice


Page 8/17 09/05/2019 © Copyright Siemens
Temperature compensation
— parameterizable No
Characteristic linearization
● parameterizable Yes; by software
— for resistance thermometer Pt 100
Cable length
● shielded, max. 100 m

Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 55 mA
Current output, no-load voltage, max. 17 V
Output ranges, voltage
● 0 to 10 V Yes
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes; Without compensation of the line resistances
● for voltage output four-wire connection No
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 0.1 µF
● with current outputs, max. 300 Ω
● with current outputs, inductive load, max. 0.1 mH
Destruction limits against externally applied voltages and currents
● Voltages at the outputs towards MANA 16 V; Permanent
● Current, max. 50 mA; Permanent
Cable length
● shielded, max. 200 m

Analog value generation for the inputs


Measurement principle Measurement principle momentary value encoding (successive
approximation)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), 12 bit
max.
● Integration time, parameterizable Yes; 2,5 / 16,6 / 20 ms
● Interference voltage suppression for 400 / 60 / 50 Hz
interference frequency f1 in Hz

6ES7636-2EB00-0AE3 Subject to change without notice


Page 9/17 09/05/2019 © Copyright Siemens
● permissible input frequency, max. 400 Hz
● Time constant of the input filter 0.38 ms
● Basic execution time of the module (all 1 ms
channels released)

Analog value generation for the outputs


Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), 12 bit
max.
● Conversion time (per channel) 1 ms
Settling time
● for resistive load 0.6 ms
● for capacitive load 1 ms
● for inductive load 0.5 ms

Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire 1.5 mA
sensor), max.

Errors/accuracies
Linearity error (relative to input range), (+/-) 0.06 %
Temperature error (relative to input range), (+/-) 0.006 %/K
Crosstalk between the inputs, min. 50 dB; at Ucm = 0 V
Repeat accuracy in steady state at 25 °C (relative to 0.06 %
input range), (+/-)
Output ripple (relative to output range, bandwidth 0 to 0.1 %
50 kHz), (+/-)
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.01 %/K
Crosstalk between the outputs, min. 60 dB
Repeat accuracy in steady state at 25 °C (relative to 0.06 %
output range), (+/-)
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 1%
● Current, relative to input range, (+/-) 1%
● Resistance, relative to input range, (+/-) 5%
● Voltage, relative to output range, (+/-) 1%
● Current, relative to output range, (+/-) 1%
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.7 %
● Current, relative to input range, (+/-) 0.7 %
● Resistance, relative to input range, (+/-) 3%

6ES7636-2EB00-0AE3 Subject to change without notice


Page 10/17 09/05/2019 © Copyright Siemens
● Resistance thermometer, relative to input 3%
range, (+/-)
● Voltage, relative to output range, (+/-) 0.7 %
● Current, relative to output range, (+/-) 0.7 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of 30 dB
interference < rated value of input range), min.
● Common mode interference, min. 40 dB

Interfaces
Number of printer interfaces 1; serial, USB for panel
MPI
● Cable length, max. 50 m; without repeater

1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Protocols
● MPI Yes
● PROFIBUS DP master No
● PROFIBUS DP slave No
MPI
● Number of connections 16
● Transmission rate, max. 187.5 kbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client Yes; Via CP and loadable FB
— S7 communication, as server Yes

2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Number of connection resources 16
Protocols
● MPI No
● PROFIBUS DP master Yes

6ES7636-2EB00-0AE3 Subject to change without notice


Page 11/17 09/05/2019 © Copyright Siemens
● PROFIBUS DP slave Yes
PROFIBUS DP master
● Number of connections, max. 16; For PG/OP communication
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 125
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication No
— S7 communication, as client No
— S7 communication, as server No
— Equidistance Yes
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Direct data exchange (slave-to-slave Yes
communication)
Address area
— Inputs, max. 244 byte
— Outputs, max. 244 byte
PROFIBUS DP slave
● Number of connections 16
● Transmission rate, max. 12 Mbit/s
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication No
— Direct data exchange (slave-to-slave Yes
communication)
— DPV1 Yes
Transfer memory
— Inputs 244 byte
— Outputs 244 byte

Communication functions
Global data communication
● Number of GD packets, max. 8

6ES7636-2EB00-0AE3 Subject to change without notice


Page 12/17 09/05/2019 © Copyright Siemens
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with
X_PUT or X_GET as server)
S7 communication
● as server Yes
● as client Yes; Via CP and loadable FB
● User data per job, max. 180 byte; With PUT/GET
● User data per job (of which consistent), max. 64 byte
S5 compatible communication
● supported Yes; via CP and loadable FC
Standard communication (FMS)
● supported No
Number of connections
● overall 16
● usable for PG communication 15
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 15
● usable for OP communication 15
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 15
● usable for S7 basic communication 12
— reserved for S7 basic communication 12
— adjustable for S7 basic communication, 0
min.
— adjustable for S7 basic communication, 12
max.

S7 message functions
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40

Test commissioning functions


Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes

6ES7636-2EB00-0AE3 Subject to change without notice


Page 13/17 09/05/2019 © Copyright Siemens
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
— of which status variables, max. 30
— of which control variables, max. 14
Forcing
● Forcing Yes
● Forcing, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— adjustable No

Interrupts/diagnostics/status information
Alarms Yes; No interrupts when used as standard I/O; when using the
technological functions, see the manual S7-300 Programmable
Controller, CPU31xC Technological Functions
Diagnostics function No; No interrupts when used as standard I/O; when using the
technological functions, see the manual S7-300 Programmable
Controller, CPU31xC Technological Functions

Integrated Functions
Number of counters 4; 4 channels in total
Counting frequency (counter) max. 60 kHz
Frequency measurement Yes
Number of frequency meters 4; 4 channels in total
controlled positioning Yes
integrated function blocks (closed-loop control) Yes
PID controller Yes
Number of pulse outputs 4; 4 channels in total
Limit frequency (pulse) 2.5 kHz

Potential separation
Potential separation digital inputs
● Potential separation digital inputs Yes
● between the channels No
● between the channels and backplane bus Yes
Potential separation digital outputs
● Potential separation digital outputs Yes
● between the channels Yes
● between the channels, in groups of 8
● between the channels and backplane bus Yes
Potential separation analog inputs
● Potential separation analog inputs Yes
● between the channels No

6ES7636-2EB00-0AE3 Subject to change without notice


Page 14/17 09/05/2019 © Copyright Siemens
● between the channels and backplane bus Yes
Potential separation analog outputs
● Potential separation analog outputs Yes
● between the channels No
● between the channels and backplane bus Yes

Permissible potential difference


between different circuits 75 V DC/60 V AC
Between the inputs and MANA (UCM) 8 V DC
between MANA and M internally (UISO) 75 V DC/60 V AC

Isolation
Isolation tested with 500 V DC

EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes; ±6 kV contact discharge acc. to IEC 61000-4-2, ESD; ±8 kV
static electricity acc. to IEC 61000-4-2 air discharge acc. to IEC 61000-4-2, ESD
Interference immunity against high-frequency electromagnetic fields
● Interference immunity against high-frequency Yes; 10 V/m, with 80% amplitude modulation at 1 kHz, 80 MHz to
radiation acc. to IEC 61000-4-3 1 GHz (to IEC 61000-4-3); 10 V/m, pulse-modulated 50% duty
cycle at 900 MHz and 1.89 GHz (to IEC61000-4-3)
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to Yes; ±2 kV acc. to IEC 61000-4-4, burst; surge measurements
IEC 61000-4-4 with additional protective elements
● Interference immunity on signal cables acc. to Yes
IEC 61000-4-4
Interference immunity against voltage surge
● on the supply lines acc. to IEC 61000-4-5 Yes; ±1 kV acc. to IEC 61000-4-5, µs pulse/line to line; ±2 kV acc.
to IEC 61000-4-5, µs pulse/line to ground
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency Yes; 10 V/m, with 80% amplitude modulation at 1 kHz
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes

Degree and class of protection


Degree of protection acc. to EN 60529
● IP20 Yes; Housing
● IP65 Yes; Front

Standards, approvals, certificates


CSA approval Yes
UL approval Yes
FM approval Yes

Ambient conditions

6ES7636-2EB00-0AE3 Subject to change without notice


Page 15/17 09/05/2019 © Copyright Siemens
Suited for outdoor use No
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 40 °C
● vertical installation, min. 0 °C
● vertical installation, max. 50 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
● permissible range, lower limit 795 hPa
● permissible range, upper limit 1 080 hPa
Relative humidity
● Operation, min. 5%
● Operation, max. 85 %; at <40 °C (no condensation)
● Storage, max. 85 %; at <40 °C (no condensation)
● Transportation, max. 85 %; at <40 °C (no condensation)
Vibrations
● Operation, tested according to IEC 60068-2-6 Yes; Operation 10 Hz to 58 Hz, amplitude 0.075 mm; 58 Hz to
150 Hz, acceleration 9.8 m/s²
● Transport, tested acc. to IEC 60068-2-6 Yes; 5 to 9 Hz: Amplitude 3.5 mm; 9 to 500 Hz: Acceleration 9.8
m/s2
Shock testing
● tested according to IEC 60068-2-29 Yes; Half-sine: 150 m/s2 (15 g), 11 ms, 18 shocks

Operating systems
pre-installed operating system
● Windows CE Yes

Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1 HSP or higher
● ProTool Yes; as of V6.0 SP3 with Setup C7-636
● ProTool/Lite Yes; as of version 6.0 SP3 and setup C7-636
● ProTool/Pro Yes; as of version 6.0 SP3 and setup C7-636
● WinCC flexible Compact Yes
● WinCC flexible Standard Yes
● WinCC flexible Advanced Yes
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list

6ES7636-2EB00-0AE3 Subject to change without notice


Page 16/17 09/05/2019 © Copyright Siemens
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes

Languages
Online languages
● Number of online/runtime languages 5

Dimensions
Width 335 mm
Height 275 mm
Depth 100 mm
Mounting cutout, width 310 mm; Tolerance: +1 mm
Mounting cutout, height 248 mm; Tolerance: +1 mm

Weights
Weight, approx. 3 980 g

last modified: 09/04/2019

6ES7636-2EB00-0AE3 Subject to change without notice


Page 17/17 09/05/2019 © Copyright Siemens