Corrugate

RESIDENTIAL HORIZONTAL CLADDING


DETAIL LIST Revision Date
D 00 / 21 COVER SHEET
D 01 / 21 PARAPET AND BALUSTRADE CAPPING 1.0 JAN 2023
D 02 / 21 SCUPPER W/ RAINWATER HEAD 1.0 JAN 2023
D 03 / 21 SOFFIT 1.0 JAN 2023
D 04 / 21 WINDOW HEAD 1.0 JAN 2023
D 05 / 21 WINDOW SILL 1.0 JAN 2023
D 06 / 21 WINDOW JAMB 1.0 JAN 2023
D 07 / 21 METERBOX HEAD 1.0 JAN 2023
D 08 / 21 METERBOX SILL 1.0 JAN 2023
D 09 / 21 METERBOX JAMB 1.0 JAN 2023
D 10 / 21 INTERNAL CORNER 01 1.0 JAN 2023
D 11 / 21 INTERNAL CORNER 02 1.0 JAN 2023
D 12 / 21 EXTERNAL CORNER 01 1.0 JAN 2023
D 14 / 21 EXTERNAL CORNER 02 1.0 JAN 2023
D 15 / 21 SOAKER FLASHING 1.0 JAN 2023
D 16 / 21 CHANGE IN CLADDING 1.0 JAN 2023
D 17 / 21 CLADDING ABUTMENT 1.0 JAN 2023
D 18 / 21 BOTTOM OF CLADDING (FLUSH) 1.0 JAN 2023
D 19 / 21 BOTTOM OF CLADDING (RECESSED) 1.0 JAN 2023
D 20 / 21 3D WINDOW FLASHINGS 1.0 JAN 2023
D 21 / 21 3D RAINWATER HEAD 1.0 JAN 2023

Metalcraft
Roofing
RHCG www.metalcraftgroup.co.nz
AS PER E2/ASI
SITUATION 1 SITUATION 2 SITUATION 3

1. LOW, MEDIUM, HIGH W IND ZONES, 1. ALL ROOF PITCHES IN VERY HIGH 1. FOR ALL ROOF PITCHES IN EXTRA
W HERE ROOF PITCH ≥ 10° W IND ZONE HIGH W IND ZONES DPC TO PROVIDE SEPARATION OF METAL
2. LOW, MEDIUM, HIGH W IND ZONES
W HERE ROOF PITCH ≤ 10°
CAPPING AND TIMBER, SHOWN DASHED
Z MIN. 50mm MIN. 70mm MIN. 90mm

PRE-FINISHED PARAPET CAP FLASHING


AS PER MRM CODE OF PRACTICE NO FIXINGS ON TOP OF FLASHING
CATEGORY A CATEGORY B

1. NORMAL EXPOSURE 1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.
2. ROOF PITCH >10° 2. ROOF PITCH <10°

Z MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH) MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH) CONTINUOUS H3.1 TIMBER PACKING
MIN. 75mm (VERTICALLY DOWN FACE - PROFILED) MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)

MIN. 5.00°
20

15 METALCRAFT CORRUGATE
5 GAP HORIZONTAL CLADDING

BIRDS BEAK EDGE FOR


DECK SIDE OF CAPPING

Z
Z

PRE-FINISHED SELF DRILLING / TAPPING


SCREW WITH NEOPRENE WASHER PRE-FINISHED SEALED POP RIVET
OR PRE-FINISHED 8g WAFER-TEK
SCREW

PERMEABLE WALL UNDERLAY, SHOWN


DASHED 20mm CAVITY

METALCRAFT CORRUGATE WALL FRAMING


HORIZONTAL CLADDING

PARAPET AND BALUSTRADE CAPPING


Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 01 / 21
PERMEABLE WALL UNDERLAY,
PRE FINISHED SCREW WITH SHOWN DASHED
NEOPRENE WASHER
20mm CAVITY
METALCRAFT CORRUGATE
HORIZONTAL CLADDING
8g WAFER-TEK SCREW
CONTINUOUS MEMBRANE
DRESSED THROUGH BASE AND
UP SIDES OF OPENING WITH WALL FRAMING
UPPER EDGES SEALED
AGAINST CLADDING. RETURN
ALONG BACK OF RAINWATER
HEAD
RETURN MEMBRANE INTO
RAINWATER HEAD

RAINWATER HEAD
CAVITY CLOSER

SCUPPER TRUE ROOF LINE BEHIND

50 mm
RAINWATER HEAD

25
OVERFLOW BELOW
OPENING LEVEL,1.5 x
DOWNPIPE AREA

MEMBRANE ON ROOF SUBSTRATE


RETURN
MEMBRANE AT END
OF LIP
METALCRAFT CORRUGATE
HORIZONTAL CLADDING
PRE FINISHED SCREW WITH
NEOPRENE WASHER

SCUPPER W/ RAINWATER HEAD


Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 02 / 21
PURLIN

FIXINGS IN ACCORDANCE WITH


MRM CODE OF PRACTICE
FLY RAFTER
PRE-FINISHED SOFFIT FLASHING

INTERNAL CEILING LINING BARGE BOARD

COVER CLADDING
SOFFIT LINING

(MIN. 35mm)
SQUARE STOP CORNICE

40mm
INTERNAL WALL LINING

PRE-FINISHED SEALED POP RIVET OR PRE-FINISHED SELF DRILLING/TAPPING


PRE-FINISHED 8g WAFER-TEK SCREW SCREW WITH NEOPRENE WASHER
5mm GAP

MIN. 50mm

EXTRA NOG FOR TOP FIXING OF


WALL CLADDING

WALL FRAMING

SEPARATE BATTEN AND FLASHING AS


20mm CAVITY REQUIRED WITH DPC

PERMEABLE WALL UNDERLAY,


SHOWN DASHED METALCRAFT CORRUGATE
HORIZONTAL CLADDING

SOFFIT
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 03 / 21
METALCRAFT CORRUGATE
HORIZONTAL CLADDING
INTERNAL WALL LINING
SEPARATE BATTEN AND CLADDING
EXTRA PERMEABLE WALL UNDERLAY WITH DPC AS REQUIRED
OVER WINDOW HEAD FLASHING,
SHOWN DASHED
STOPENDS TO HEAD FLASHING,
PRE-FINISHED SELF DRILLING/TAPPING SCREW SHOWN DASHED

MIN. 75mm WITHOUT HEM EDGE


WITH NEOPRENE WASHER

MIN. 50mm COVER


PVC CAVITY CLOSER

DRIP EDGE TO CLADDING


FIXINGS IN ACCORDANCE WITH MRM
CODE OF PRACTICE

MIN. 15mm GAP


PRE-FINISHED WINDOW HEAD
FLASHING WITH 15° FALL

GAP

SUGGEST MIN. 50mm


DIMENSION TO SUIT
5mm

MIN. 10mm COVER


WINDOW LINTEL FRAMING

AIRSEAL ON BACKING ROD TO RUN


CONTINUOUSLY AROUND HEAD, SILL AND JAMB

PERMEABLE WALL UNDERLAY DRESSED


INTO OPENING WITH FLEXIBLE FLASHING WINDOW JOINERY POSITION BY OTHERS
TAPE INSTALLED OVER WRAP TO
CORNERS AT HEAD

TEMPORARY PACKER IF REQUIRED, WINDOW HEAD LINER


REMOVED AFTER FIXING

LINE OF WINDOW JAMB LINER BEHIND LINE OF JAMB FLASHING BEHIND

WINDOW HEAD
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 04 / 21
LINE OF WINDOW JAMB LINER BEHIND LINE OF JAMB FLASHING BEHIND

WINDOW JOINERY POSITION BY


OTHERS

MIN. 8mm PACKER STOPENDS TO SILL FLASHING,


SHOWN DASHED

AIRSEAL ON BACKING ROD TO RUN PRE-FINISHED WINDOW SILL FLASHING


CONTINUOUSLY AROUND HEAD, SILL AND JAMB

WINDOW SILL LINER

MIN. 8mm COVER


5mm GAP
WINDOW SUPPORT BAR

FLEXIBLE FLASHING TAPE OVER PERMEABLE


WALL UNDERLAY FOR FULL WIDTH/DEPTH SILL

COVER CLADDING
(MIN. 35mm)
PERMEABLE WALL UNDERLAY DRESSED

50mm
INTO OPENING WITH FLEXIBLE FLASHING
TAPE INSTALLED OVER WRAP TO
CORNERS AT SILL

PRE-FINISHED SELF DRILLING/TAPPING PRE-FINISHED SEALED POP RIVET OR


SCREW WITH NEOPRENE WASHER PRE-FINISHED 8g WAFER-TEK SCREW
5mm GAP

INTERNAL WALL LINING SEPARATE BATTEN AND FLASHING AS


REQUIRED WITH DPC

20mm CAVITY
METALCRAFT CORRUGATE HORIZONTAL
CLADDING
WALL FRAMING

WINDOW SILL
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 05 / 21
WINDOW JAMB LINER

INTERNAL WALL LINING LINE OF WINDOW SILL LINER BELOW

AIRSEAL ON BACKING ROD TO


FLEXIBLE FLASHING TAPE OVER RUN CONTINUOUSLY AROUND
PERMEABLE WALL UNDERLAY HEAD, SILL AND JAMB
FOR FULL WIDTH/DEPTH SILL
TIMBER PACKER
PRE-FINISHED SELF
DRILLING/TAPPING SCREW WITH PERMEABLE WALL UNDERLAY,
NEOPRENE WASHER SHOWN DASHED
SEPARATE BATTEN AND FLASHING
FIXINGS IN ACCORDANCE WITH AS REQUIRED WITH DPC
MRM CODE OF PRACTICE

5mm GAP
LINE OF HEAD FLASHING ABOVE

CONTINUOUS COMPRESSIBLE LINE OF SILL FLASHING BELOW


FOAM SEAL.

LINE OF HEAD FLASHING ABOVE

METALCRAFT CORRUGATE
MIN. 10mm COVER WINDOW JOINERY POSITION BY
HORIZONTAL CLADDING
OTHERS
5mm GAP
PRE-FINISHED WINDOW JAMB
PRE-FINISHED SEALED POP FLASHING
RIVET OR PRE-FINISHED 8g DIMENSION TO SUIT
WAFER-TEK SCREW
SUGGEST MIN. 50mm PRE-FINISHED SECONDARY FLASHING

WINDOW JAMB
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 06 / 21
METALCRAFT CORRUGATE
INTERNAL WALL LINING HORIZONTAL CLADDING

EXTRA PERMEABLE WALL UNDERLAY


OVER WINDOW HEAD FLASHING, SHOWN PRE-FINISHED HEAD FLASHING WITH 15°
DASHED FALL

PRE-FINISHED SELF DRILLING/TAPPING


SCREW WITH NEOPRENE WASHER

MIN.75mm WITHOUT HEM EDGE


PVC CAVITY CLOSER

MIN. 50mm COVER


STST OR GALV. FLAT HEAD NAIL FOR FLASHING

DRIP EDGE TO CLADDING


MIN. 15mm GAP
GAP
STOPENDS TO HEAD FLASHING,
SHOWN DASHED

5mm
MIN.
PERMEABLE WALL UNDERLAY DRESSED
INTO OPENING WITH FLEXIBLE FLASHING
TAPE INSTALLED OVER WRAP TO
CORNERS AT HEAD

AIRSEAL ON BACKING ROD TO RUN


CONTINUOUSLY AROUND HEAD, SILL AND JAMB
PRE-FINISHED 'U' BRACKET FIXED TO
TEMPORARY PACKER IF REQUIRED, METERBOX BEFORE INSTALLATION
REMOVED AFTER FIXING

METAL ANGLE TO BE CONTINUOUS


PRE-FINISHED SELF DRILLING/TAPPING
AROUND METER BOX SEALED.
SCREW WITH NEOPRENE WASHER

METER BOX LINE OF JAMB FLASHING BEHIND

METERBOX HEAD
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 07 / 21
METER BOX
LINE OF JAMB FLASHING BEHIND

WINDOW SILL LINER METAL ANGLE TO BE CONTINUOUS


AROUND METER BOX SEALED.

STOPENDS TO SILL FLASHING, SHOWN


MIN. 8mm PACKER DASHED

PRE-FINISHED SECONDARY FLASHING

AIRSEAL ON BACKING ROD TO RUN


CONTINUOUSLY AROUND HEAD, SILL AND JAMB

PRE-FINISHED SELF

CO0VER CLADDING
DRILLING/TAPPING SCREW WITH
NEOPRENE WASHER

MIN. 35mm
FLEXIBLE FLASHING TAPE OVER PERMEABLE
WALL UNDERLAY FOR FULL WIDTH/DEPTH
SILL

PRE-FINISHED SELF
DRILLING/TAPPING SCREW WITH 5mm GAP
NEOPRENE WASHER PRE-FINISHED SEALED POP RIVET OR
PRE-FINISHED 8g WAFER-TEK SCREW

PERMEABLE WALL UNDERLAY, SEPARATE BATTEN AND FLASHING AS


SHOWN DASHED REQUIRED WITH DPC

METALCRAFT CORRUGATE HORIZONTAL


WALL FRAMING
CLADDING

INTERNAL WALL LINING 20mm CAVITY

METERBOX SILL
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 08 / 21
INTERNAL WALL LINING
AIRSEAL ON BACKING ROD TO RUN
CONTINUOUSLY AROUND HEAD,
SILL AND JAMB

METER BOX
PERMEABLE WALL UNDERLAY,
SHOWN DASHED

FLEXIBLE FLASHING TAPE OVER


PERMEABLE WALL UNDERLAY FOR
PRE-FINISHED SELF DRILLING/TAPPING
FULL WIDTH/DEPTH SILL
SCREW WITH NEOPRENE WASHER

TIMBER PACKER

METAL ANGLE TO BE CONTINUOUS


AROUND METER BOX SEALED.

PRE-FINISHED WINDOW JAMB


FLASHING FIXED TO METERBOX LINE OF HEAD FLASHING ABOVE
BEFORE INSTALLATION

CONTINUOUS COMPRESSIBLE FOAM LINE OF SILL FLASHING BELOW


SEAL.

LINE OF HEAD FLASHING ABOVE

METALCRAFT
CORRUGATE WEATHERSEAL ON BACKING ROD
HORIZONTAL CLADDING TO RUN CONTINUOUSLY AROUND
HEAD, SILL AND JAMB
PRE-FINISHED SEALED POP RIVET
OR PRE-FINISHED 8g WAFER-TEK PRE-FINISHED SELF
SCREW DRILLING/TAPPING SCREW WITH
NEOPRENE WASHER

METERBOX JAMB
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 09 / 21
DIMENSION TO SUIT METALCRAFT CORRUGATE
HORIZONTAL CLADDING
SUGGEST MIN. 75mm

SEPARATE BATTEN AND FLASHING


AS REQUIRED WITH DPC

PRE-FINISHED SEALED 20mm CAVITY


SUGGEST MIN. 75mm

POP RIVET OR PRE-


DIMENSION TO SUIT

FINISHED 8g WAFER-TEK
SCREW
PRE-FINISHED SECONDARY
FLASHING OR TWO J-MOULDS
PRE-FINISHED INTERNAL
CORNER FLASHING

FIXINGS IN ACCORDANCE WITH MRM


CODE OF PRACTICE

CONTINUOUS COMPRESSIBLE FOAM


SEAL.

PERMEABLE WALL UNDERLAY, SHOWN


DASHED

PRE-FINISHED SELF DRILLING/TAPPING


SCREW WITH NEOPRENE WASHER

WALL FRAMING

INTERNAL WALL LINING

INTERNAL CORNER 01
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 10 / 21
DIMENSION TO SUIT 5mm MIN

SUGGEST MIN. 100mm METALCRAFT CORRUGATE


HORIZONTAL CLADDING

SEPARATE BATTEN AND FLASHING


AS REQUIRED WITH DPC

20mm CAVITY
SUGGEST MIN. 100mm
5mm MIN DIMENSION TO SUIT

PRE-FINISHED SECONDARY
FLASHING OR TWO J-MOULDS

FIXINGS IN ACCORDANCE WITH MRM


CODE OF PRACTICE

CONTINUOUS COMPRESSIBLE FOAM


SEAL.

PERMEABLE WALL UNDERLAY, SHOWN


DASHED

PRE-FINISHED SELF DRILLING/TAPPING


SCREW WITH NEOPRENE WASHER

WALL FRAMING

INTERNAL WALL LINING

INTERNAL CORNER 02
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 11 / 21
DIMENSION TO SUIT

METALCRAFT CORRUGATE HORIZONTAL SUGGEST MIN. 100mm


CLADDING PRE-FINISHED SEALED POP RIVET
OR PRE-FINISHED 8g WAFER-TEK
SCREW

PRE-FINISHED EXTERNAL
CONTINUOUS COMPRESSIBLE CORNER FLASHING
FOAM SEAL.

SUGGEST MIN. 100mm


DIMENSION TO SUIT
FIXINGS IN ACCORDANCE WITH MRM
CODE OF PRACTICE

PRE-FINISHED SELF DRILLING/TAPPING


SCREW WITH NEOPRENE WASHER

PRE-FINISHED SECONDARY
FLASHING OR TWO J-MOULDS

PERMEABLE WALL UNDERLAY, SHOWN


DASHED

WALL FRAMING

INTERNAL WALL LINING 20mm CAVITY

EXTERNAL CORNER 01
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 12 / 21
METALCRAFT CORRUGATE HORIZONTAL DIMENSION TO SUIT 10 50
CLADDING SUGGEST MIN. 100mm

PRE-FINISHED EXTERNAL
CORNER FLASHING

CONTINUOUS COMPRESSIBLE
FOAM SEAL.

50
10
FIXINGS IN ACCORDANCE WITH MRM

SUGGEST MIN. 100mm


DIMENSION TO SUIT
CODE OF PRACTICE

PRE-FINISHED SELF DRILLING/TAPPING


SCREW WITH NEOPRENE WASHER

PRE-FINISHED
SECONDARY FLASHING
OR TWO J-MOULDS

PERMEABLE WALL UNDERLAY, SHOWN


DASHED

WALL FRAMING

INTERNAL WALL LINING 20mm CAVITY

EXTERNAL CORNER 02
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 14 / 21
PRE-FINISHED SOAKER METALCRAFT CORRUGATE
FLASHING BELOW SOAKER FLASHING ONLY REQUIRED TO HORIZONTAL CLADDING
LINE UP WITH WINDOW JAMB ABOVE.
WINDOW JAMBS
REFER TO MRM CODE OF PRACTICE
VERSION 3.0 /2022 FOR REQUIRMENT.

SEPARATE BATTEN AND


FLASHING AS REQUIRED
20mm CAVITY
WITH DPC

PERMEABLE WALL
FIXINGS IN ACCORDANCE UNDERLAY, SHOWN
WITH MRM CODE OF DASHED
PRACTICE

INTERNAL WALL LINING WALL FRAMING

SOAKER FLASHING
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 15 / 21
CONTINUOUS COMPRESSIBLE PRE FINISHED
FOAM SEAL. ALUMINIUM FLASHING

SEPARATE BATTEN AND


FLASHING WITH DPC AS
REQUIRED
20mm CAVITY

FIBRE CEMENT BOARD


METALCRAFT CORRUGATE HORIZONTAL BY OTHERS
CLADDING

PRE FINISHED PERMEABLE WALL


SCREW WITH UNDERLAY, SHOWN
NEOPRENE DASHED
WASHER

CHANGE IN CLADDING
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 16 / 21
CONCRETE WALL BY
OTHERS
CONTINUOUS COMPRESSIBLE
FOAM SEAL.
PRE-FINISHED POP RIVET
BEDDED IN SILICONE

METALCRAFT CORRUGATE
HORIZONTAL CLADDING
MASTIC BEAD ON
BACKING ROD

CAVITY BATTENS
RAWLPLUG

PRE FINISHED
ALUMINIUM FLASHING

PRE-FINISHED SECONDARY
FLASHING

SEPARATE BATTEN AND


FLASHING AS REQUIRED
WITH DPC

FLEXIBLE FLASHING TAPE

WALL FRAMING

8a WAFER TEK SCREW

DPC

PERMEABLE WALL
PRE FINISHED UNDERLAY, SHOWN
SCREW WITH DASHED
NEOPRENE
WASHER

CLADDING ABUTMENT
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 17 / 21
METALCRAFT CORRUGATE
HORIZONTAL CLADDING
INTERNAL WALL LINING

WALL FRAMING
20mm CAVITY

PERMEABLE WALL UNDERLAY,


SHOWN DASHED

PRE-FINISHED SELF FIXINGS IN ACCORDANCE WITH


DRILLING/TAPPING SCREW WITH MRM CODE OF PRACTICE
NEOPRENE WASHER

PRE-PRIMED SKIRTING PRE-FINISHED NON-PERFORATED


CLOSURE FLASHING WITH 10° FALL
DPC
PVC CAVITY CLOSER
CONCRETE SLAB

MIN. 50mm LAP


MIN. 15mm DRIP EDGE
GAP
GROUND CLEARANCE IS NECESSARY BETW EEN BOTTOM OF

ATION
3-5mm
PROFILED METAL CLADDING AND LARGE FLAT SURFACES

APPLICATION

VENTIL
25mm CLEARANCE AT GARAGE DOOR
SHELTERED AREAS OR CLADDING ABUTTING A
35mm DECK
75mm UNLINED BUILDINGS
LINED BUILDINGS AND DWELLINGS. STONE CHIP
100mm
GROUND SURFACE
150mm KEPT LAWN GROUND SURFACE
175mm PASTURE GROUND SURFACE

BOTTOM OF CLADDING (FLUSH)


Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 18 / 21
METALCRAFT CORRUGATE
INTERNAL WALL LINING HORIZONTAL CLADDING

WALL FRAMING
20mm CAVITY

PERMEABLE WALL UNDERLAY OVER


FLASHING, SHOWN DASHED
PRE-FINISHED SELF
PVC CAVITY CLOSER DRILLING/TAPPING SCREW WITH
NEOPRENE WASHER
FIXINGS IN ACCORDANCE WITH MRM 20
CODE OF PRACTICE

MIN. 75mm COVER


PRE-FINISHED NON-PERFORATED 15
CLOSURE FLASHING WITH 10° FALL
5 GAP
PRE-PRIMED SKIRTING

DPC ALTERNATIVE OPTION

GAP
BIRDS BEAK EDGE
CONCRETE SLAB

mm

TION
3-5

TILA

MIN. 50mm LAP


VEN
GROUND CLEARANCE IS NECESSARY BETW EEN BOTTOM OF
PROFILED METAL CLADDING AND LARGE FLAT SURFACES

APPLICATION
25mm CLEARANCE AT GARAGE DOOR
SHELTERED AREAS OR CLADDING ABUTTING A
35mm DECK
75mm UNLINED BUILDINGS
LINED BUILDINGS AND DWELLINGS. STONE CHIP
100mm
GROUND SURFACE
150mm KEPT LAWN GROUND SURFACE
175mm PASTURE GROUND SURFACE

BOTTOM OF CLADDING (RECESSED)


Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale 1:2 Sheet D 19 / 21
HEAD FLASHING

METALCRAFT
CORRUGATE OR
HORIZONTAL
CLADDING

SECONDARY
DEFENCE SOAKERS
ALUMINIUM WHEN REQUIRED
WINDOW
JOINERY

JAMB FLASHING

INDICATIVE

SILL FLASHING

3D WINDOW FLASHINGS
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale Sheet D 20 / 21
N
MI METALCRAFT CORRUGATE HORIZONTAL
0 mm ING CLADDING
20 PEN
O
N
MI
mm SIDE
50 HER
EIT

LIP OF DISCHARGE AT LOWEST


POINT OF ROOF
75 mm MIN
OPENING

OVERFLOW BELOW OPENING LEVEL, 1.


CROSS-SECTION AREA OF DOWNPIPE

DOWNPIPE

3D RAINWATER HEAD
Metalcraft
Roofing
DISCLAIMER:
All details are to be used for indicative purposes only and the designer should consult both the MRM
code of practice version 3.0 / 2022, E2 and all other relevant building codes
Details of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is
Corrugate Rev. 1.0 RESIDENTIAL HORIZONTAL CLADDING

www.metalcraftgroup.co.nz
the responsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed
as a single line for simplicity and is indicative only. Building paper type and method of installation should
comply with underlay manufacturers recommendations and NZBC regulations.
Reference RHCG Date JAN 2023 Scale Sheet D 21 / 21