GENERAL NOTES

1. THIS DRAWING IS TO BE READ WITH ALL


RELATED ARCHITECTURAL, CIVIL, STRUCTURAL
& MEP DRAWINGS AND OTHER RELEVANT
INFORMATION, INCLUDING ALL SPECIFICATIONS,
REPORTS, CALCULATIONS AND DETAILS, AS
WELL AS THE CONDITIONS OF CONTRACT.

2. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS


STATED OTHERWISE.

3. DO NOT SCALE FROM THE DRAWINGS.

4. FIGURED DIMENSIONS ONLY ARE TO BE


CONSIDERED FROM THIS DRAWING. ALL
DIMENSIONS ARE TO BE CHECKED ON SITE.
REPORT ANY DISCREPANCIES TO THE
ENGINEER BEFORE PROCEEDING WITH THE
WORK. IF IN DOUBT ASK.

NOTE: 5. CONTRACTOR MUST VERIFY ALL JOB


1. ALL DOORS INSIDE THE "2HR" FIRE RATED WALLS MUST BE 90MINUTES FIRE 60min FIRE DIMENSIONS, DRAWINGS, DETAILS,
60min FIRE SPECIFICATIONS AND ANY OTHER RELEVANT
RATED EXCEPT IN EXIT STAIRWAYS WHICH IS 120min FIRE RATED DOOR. RATED DOOR

m
RATED DOOR

0.3
DOCUMENT. ANY DISCREPANCIES TO BE

=1
CO CO
17m
90

m
2. DISCHARGE FROM EXITS AND EGRESS CAPACITY CALCULATION (NFPA MM

EL

13
mins
MM
O EL= BROUGHT TO THE ATTENTION OF THE

AV
NP

=
101) BUILDING EXITS SHALL TERMINATE DIRECTLY AT A PUBLIC AV ON

EL
ATH

TR
TR PA

AV
OF F ENGINEER BEFORE PROCEEDING WITH WORK.

OF
HO TH

TR
ACCORDANCE WITH SECTION 7.7. TR 18m PA
T

TH
AV OF

OF
A EL=
21m ON

PA
TR

COMMON PATH OF TRAVEL= 18.6m


17m MM

TH
A C AV

ON

COMMON PATH OF TRAVEL= 20m


CO

PA
90min FIRE EL
6. ALL WORKS, COMPONENTS, SETTING OUT,

MM
3. EXIT CAPACITY =1

ON
2.4

CO
RATED DOOR

MM
A A A A A A m A A D LEVELS, MATERIALS AND FINISHES ARE TO BE

CO
COMMON PATH OF TRAVEL= 20m
EXIT CAPACITY
C INSPECTED AND APPROVED BY THE ENGINEER
SBC 201 (2018) table 1006.3.1, and Section 403.5.2
90 90min FIRE PRIOR TO COMMENCEMENT AND INSTALLATION.
MINIMUM CLEAR ACTUAL CLEAR A A
mins
RATED DOOR
EXITS A A
WIDTH (mm) WIDTH (mm) 90min FIRE 7. CONTRACTOR MUST SUBMIT ALL
BD-E1 810 1,000 39m 120min FIRE 120min FIRE 39m RATED DOOR 79m ARCHITECTURAL, CIVIL, STRUCTURAL SHOP

COM

9.5m
120 90 120

RATED DOOR
mins mins 90min FIRE mins
RATED DOOR
BD-E2 810 1,000 RATED DOOR DRAWINGS, METHOD STATEMENTS,

MON

EL=
BD-E3 810 1,000
90
90min FIRE CALCULATIONS, TEST CERTIFICATES OR ANY

V
mins

PAT

TRA
BD-E4 810 1,000 BA-E3 BB-E3 C A RATED DOOR OTHER CONSTRUCTION DOCUMENT AS
C C C C A A C A C A C

H OF
C C

H OF
BD-E5 810 1,000 VEL= 14
m 90min FIRE C REQUIRED BY THE ENGINEER AND OBTAIN

TRA

PAT
OF TRA
BD-E6 810 1,000 79m COMMO
N PATH RATED DOOR 53m APPROVAL OF THE ENGINEER PRIOR TO ANY

V
90m

MON
EL=
90

8m
mins

BD-E7 810 1,000 L= COMMENCEMENT & INSTALLATION.

COM
9.5m
E
R AV 90

24m FT mins

HO 90min FIRE

COMMON PATH OF TRAVEL= 14m


60

IN ACCORDANCE WITH SBC 201 (2018) TABLE 1006.3.1, AND SEXTION 403.5.2,
mins

NP
AT
RATED DOOR
LEGEND:
THE MINIMUM NUMBER OF EXITS SHALL BE 2, AS THE TOTAL OCCUPANT 60min FIRE M MO 60min FIRE
CO
90
LOAD PER STOREY IS BETWEEN 1-500, AND THE HEIGHT OF THE BUILDING
RATED DOOR 90min FIRE
mins
21m 21m A A RATED DOOR
C C A A A A A A A A A C C ESCAPE ROUTE

COMMON PATH OF TRAVEL= 10m


IS LESS THAN 128m. 4 EXITS WITH A MINIMUM CLEAR WIDTH OF 950mm A

CO M
EACH ARE PROVIDED. RATED DOOR

MO N
120min FIRE RATED WALL
90min FIRE

m
=9

PATH
4. OCCUPANT LOAD CALCULATION (SBC 801, 8.4.1.2) CAP.: 1050KG.
ELE. NO.34
CAP.: 1050KG.
ELE. NO.34

RATED DOOR 90min FIRE RATED WALL

EL
AV
A

OF T
TR
OCCUPANT COMMON PATH OF TRAVEL= 4.7m COMMON PATH OF TRAVEL= 4.7m 60min FIRE RATED WALL

OF
OCCUPANT Ex

RA V E
LOAD FACTOR 75m 45m ter 45m

TH
CAP.: 1050KG. CAP.: 1050KG.

USE AREA (m²) it


ELE. NO.35 ELE. NO.35

73m

PA
me Re
COMM

COMMON PATH
(m² / PERSON) LOAD

L= 21
ON
8 m
A 10 ote

MM
A 27m 27m ne C B
ON PA

s= C 120min FIRE RATED

m
A

CO
C A A A s A A C CAP.: 1050KG. CAP.: 1050KG.

A A ss A A C E
A
ELE. NO.36 ELE. NO.36

EXIT DOOR
te ne =
BUSINESS 9.3 10
TH OF

- -
mo 50m 8m IRE 90min FIRE RATED INDIVIDUAL ROOM EXIT DOOR
it Re ete
TRAVE

E x r
STORAGE/ 90min FIRE FIRE ESCAPE
L=

SERVICES/ RATED DOOR


26m

EQUIPMENT 28 1,477.5 52.8 50m 90min FIRE TENANT/ OFFICE AREA ZONE
RATED DOOR
ROOM r Di 60min FIRE
A A e te C A A B A ag C D COMMON AREA ZONE
C C B A C m A A B A A C A A on A C RATED DOOR
KITCHENS 8 al
18.6 - - 15 Di C CO
= st an MM FIRE RATED ZONE
ce ce
ON
BASEMENT/ an PA
ist = T HO
5.6 7,403 1,322 90min FIRE
lD
15 FT ELEVATOR RESTRICTED
MERCANTILE RATED DOOR na
8
m
RA
VE
o et L=
120min FIRE
D iag er 120min FIRE 1 9m FIRE ESCAPE ELEVATOR
PARKING 18.6 3,446 185 RATED DOOR RATED DOOR
C C C
TOTAL OCCUPANT LOAD 1,374.5 B B C C A C C KITCHEN
C A A A A
BA-E1 A A A BB-E1 A*
*PER TABLE 8.4.1.2 OF SBC 801, THE OCCUPANT LOAD IS THE MAXIMUM
90min FIRE C C 120
mins
120
mins
B STORAGE AREA/
PROBABLE NUMBER OF OCCUPANTS PRESENT AT ANY TIME BUILDING EQUIPMENT
RATED DOOR 29m 120min FIRE 120min FIRE
5. MEANS OF EGRESS REQUIREMENTS
120 120
BB-E2 BASEMENT &
RATED DOOR mins mins
RATED DOOR
90
mins
COMMON PATH OF TRAVEL= 5.2m COMMON PATH OF TRAVEL= 5.2m
29m GRADE FLOOR AREA
DEAD END COMMON PATH OF TRAVEL DISTANCE BA-E2
(m) TRAVEL (m) (m) PARKING
OCCUPANCY CAP.: 1050KG.
ELE. NO.28
10m 10m CAP.: 1050KG.
ELE. NO.28

CLASSIFICATION
MAX. PER MAX. PER 18m TRAVEL DISTANCE IN METERS
REQUIRED DESIGN REQUIRED REQUIRED
DESIGN DESIGN CAP.: 1050KG.
CAP.: 1050KG.
ELE. NO. 33
CAP.: 1050KG.
ELE. NO. 32
CAP.: 1050KG.
ELE. NO. 31
CAP.: 1050KG.
ELE. NO. 31
CAP.: 1050KG.
ELE. NO. 32
CAP.: 1050KG.
ELE. NO. 33
CAP.: 1050KG.
ELE. NO.29 ELE. NO.29

A A
A A A C B C A A A A* C A* A A A A A A FIRE EXIT POINT
BUSINESS 15 m NO 30 m 16.4 m 91 m 79 m
72m C 60m
DEAD END COMMON PATH OF TRAVEL= 7.2m X
COMMON PATH OF TRAVEL= 7.2m
CAP.: 1050KG.
ELE. NO.30
C C CAP.: 1050KG.
ELE. NO.30

ASSEMBLY 6.1 m NO 23 m 20.7m 76 m 58 m


DEAD END
90min FIRE REFUGE POINT
MERCANTILE 15 m NO 30 m 15 m 76 m 30 RATED DOOR
DEAD END 90
mins

LOW HAZARD 30 m 16m 30 m 28 122 m 98 A A EXIT SIGN, SINGLE SIDED, SURFACED MOUNTED, WITH
A A A C A A A C A A A A C A A A C C C A A A A A A 1x8W FLOURESCENT LAMP, 127V, 60HZ, WITH BUILT-IN
A BATTERY AND CHARGER, AUTONOMY= 3Hrs, WITH
*As per SBC 201 (2018) section 1006.2.1, the common path travel distance in
OPAL DIFFUSER
the building shall not exceed 30 meters.
EXIT SIGN, DOUBLE SIDED, SURFACED MOUNTED, WITH
As per SBC 201 (2018) section 1020.4, the dead-end corridor shall not exceed 1x8W FLOURESCENT LAMP, 127V, 60HZ, WITH BUILT-IN
BATTERY AND CHARGER, AUTONOMY= 3Hrs, WITH
15 meters, given that the building shall be equipped with a sprinkler system
OPAL DIFFUSER
throughout.

A C A A
In accordance with SBC 201 (2018) section 1017.2, the maximum travel distance B C A A C A A A C A A A C A A A C A A A A
to an exit in a building shall be no more than 90 meters, provided that the building is
equipped with a sprinkler system throughout.
A A C
42m 90min FIRE
6. MINIMUM FIRE PROTECTION RATINGS FOR WALLS & DOORS
RATED DOOR
B
90

SPACE WALL RATING DOOR RATING


mins B
120min FIRE B 120min FIRE
C A B
RATED DOOR B B A C A A A A C A A A A A C A A A A RATED DOOR
EXIT STAIRS, ELEVATORS, SHAFTS,
BB-E4
120 MINUTES 120 MINUTES C A
.6m

TRANSFORMERS & GENERATOR


L= 22

21.6m
JANITOR , PANTRY & KITCHEN 60 MINUTES 60 MINUTES

m
RAVE

120

L= 30

L=
53m 53m mins

AVE
MECHANICAL AND STORES,
OF T

55m 55m

RAVE
COMM, ELECT ROOMS. 90 MINUTES 90 MINUTES

R
BA-E4

OF T
PATH

OF T
90
ASSEMBLY: PRAYER 60 MINUTES 60 MINUTES

PATH
mins
90 90min FIRE
A C
MON

PATH
90min FIRE mins
C A RATED DOOR
48m C A A A A A C A A A A A C A A A A 48m

MON
RATED DOOR
COM

90min FIRE

MON
7. FOR EXIT LIGHTS ACTUAL ARRANGEMENT, THE APPOINTED CONTRACTOR 90min FIRE 90min FIRE

COM
IS TO PERFORM TESTING AND COMMISSIONING OF EXISTING EXIT SIGNS, RATED DOOR RATED DOOR RATED DOOR

COM
AND DIRECTIONAL EXIT SIGNS TO FIND THE BATTERY LIFE, LUX
REQUIREMENTS (11 LUX) AND THE LOCATION AND CONDITION OF EXISTING A A 90
mins
FIXTURES. THE CONTRACTOR SHOULD SHARE THE RESULTS WITH THE 90
DESIGN TEAM TO INCORPORATE THE ACTUAL SITE CONDITION ON THE mins

DRAWING. BASED ON THE TESTING AND COMMISSIONING, THE DESIGN 32m 32m

VVV
23m 60min FIRE 60min FIRE 23m
REQUIREMENTS WILL BE VERIFIED AND CONFIRMED FOR THE ADDITIONAL COMMON PATH OF TRAVEL= 5.2m
RATED DOOR RATED DOOR
46m COMMON PATH OF TRAVEL= 5.2m
32m
REQUIREMENTS AS PER SBC-401 & SBC-801.
m
8. FIRE ESCAPE ELEVATOR SHALL BE AS PER SBC REQUIREMENTS. L = 19.7 60min FIRE
RAVE COM
THE CONTRACTOR TO VERIFY SBC REQUIREMENTS REGARDING FIRE OF T CAP.: 1050KG. CAP.: 1050KG. CAP.: 1050KG.

RATED DOOR CAP.: 1050KG. CAP.: 1050KG. CAP.: 1050KG.


MON
ATH
ELE. NO. 27 ELE. NO. 26 ELE. NO. 25 ELE. NO. 25 ELE. NO. 26 ELE. NO. 27

PATH
ESCAPE ELEVATOR AND THE SCOPE OF WORK & CAUSE & EFFECT MATRIX ON P A C B OF T
C OMM A A A A A A A A A RAVE
SHALL BE UPDATED ACCORDINGLY. A L= 21
m
90min FIRE 90min FIRE
CO RATED DOOR RATED DOOR COM
MO m
MM N PAT 8.5
ON
HO L=
PA F TR A VE
TH AVE TR
OF
T
L= 9
.2m OF
RA TH
VEL PA
=8 ON
.5m 60min FIRE MM
CO
RATED DOOR
90min FIRE
90min FIRE RATED DOOR 35m 90min FIRE
RATED DOOR 35m RATED DOOR
m CO
8.5 90min FIRE 90min FIRE MM
L= BC-E5 ON
VE RATED DOOR RATED DOOR PA
RA TH
T .2m
OF L= 9 OF
TH 120min FIRE AVE TR
PA F TR AV
ON RATED DOOR HO EL
PAT =
MM MM
ON 8.5
m
CO CO 60min FIRE
ELE. NO.49
CAP.: 1050KG

RATED DOOR
COM A A A A A A A A A A A A 1m
MON EL= 2
PATH
OF T F TRAV
R AVEL 90min FIRE PA TH O
= 21m
ELE. NO. 27
CAP.: 1050KG.
ELE. NO. 26
CAP.: 1050KG.
ELE. NO. 25
CAP.: 1050KG.
60min FIRE ELE. NO. 25
CAP.: 1050KG.
ELE. NO. 26
CAP.: 1050KG.
ELE. NO. 27
CAP.: 1050KG.

MON
RATED DOOR COM
90min FIRE RATED DOOR 90min FIRE
RATED DOOR RATED DOOR
32m COMMON PATH OF TRAVEL= 5.2m 60min FIRE 60min FIRE 46m COMMON PATH OF TRAVEL= 5.2m 32m
32m 23m 23m 32m
RATED DOOR RATED DOOR 90
90 mins
mins

90
A A
mins

COMMON PATH OF TRAVEL= 17.6m

COM
A

COM
MON
A A A A C A A A C A A C A A A A A C
90min FIRE 90min FIRE

MON
PATH
RATED DOOR 48m
C
A 48m RATED DOOR

PATH
OF T
90
mins

OF T
RAVE
55m 55m

RAV
L= 30
53m 53m

EL=
120
mins

21.6m
19

A C C A C
BD-E4 B B A A A A A A A C A A C A A A A A BC-E4

90min FIRE 120min FIRE


B B 120min FIRE 90min FIRE
RATED DOOR RATED DOOR RATED DOOR RATED DOOR
C

C C A A C
B A A A A A A C A A A C A A A C A A A A A A

C A
A A A A A A A A C A A A A A A A C A A A A A A A A

C C
Rev Date Description Checked
ELE. NO.30
CAP.: 1050KG.
C C B A
ELE. NO.30
CAP.: 1050KG.

COMMON PATH OF TRAVEL= 7.2m A A COMMON PATH OF TRAVEL= 7.2m


A A A A A A A A A* A*
X

A A A A A
60m 60m
ELE. NO.29
CAP.: 1050KG.
C C
ELE. NO.29
CAP.: 1050KG.
DESIGN STAGE: DETAILED DESIGN
ELE. NO. 33 ELE. NO. 32 ELE. NO. 31 ELE. NO. 31 ELE. NO. 32 ELE. NO. 33
CAP.: 1050KG. CAP.: 1050KG. CAP.: 1050KG. CAP.: 1050KG. CAP.: 1050KG. CAP.: 1050KG.

90min FIRE
ELE. NO.28 ELE. NO.28 RATED DOOR
PURPOSE of ISSUE: FOR REVIEW
C
CAP.: 1050KG. CAP.: 1050KG.

10m 10m
BD-E2
COMMON PATH OF TRAVEL= 5.2m COMMON PATH OF TRAVEL= 5.2m C 90min FIRE
RATED DOOR
A1 B1
29m 120
BC-E2 29m
C mins
120
mins 120min FIRE
90min FIRE
BC-E1 RATED DOOR
120 A RATED DOOR C
C
C B B C mins

A120min FIRE B BD-E1


A A A A A A A C A C B
A*
A2 BLOCK A BLOCK B
120min FIRE RATED DOOR 90min FIRE B 120min FIRE
RATED DOOR RATED DOOR RATED DOOR
CO Di
MM ag er 19
m
ON on et EL=
PA al m AV
TH 8 R
OF Di
sta 15 O FT
T RA = TH
VE nc
e n ce N PA
L=
19 = sta MO
Di
15 A B C A A M
m C C C A A CO

21m
90min FIRE A 8
m A A A A A A n al A C C
et go

RAVEL=
RATED DOOR C er a
Di
D2 BLOCK D BLOCK C C2

H OF T
C 46m 90min FIRE 90min FIRE

ON PAT
27m RATED DOOR RATED DOOR
90min FIRE 52m Ex r
it ete

COMM
RATED DOOR Re
C
A A
mo
ten A A
A C 50m
A A =
1 08
m
A A C
KEYPLAN: D1 C1
C es s
s= ELE. NO.36 ELE. NO.36

C A es PROJECT NAME:
8.8m

CAP.: 1050KG. CAP.: 1050KG.

27m n
10 ote
COMMON PATH OF TRAVEL= 9.5m

8m em
EL= 1

73m ete it R 75m


45m r Ex 45m
TRAV

ELE. NO.35 ELE. NO.35


CAP.: 1050KG. CAP.: 1050KG.
COMMON PATH OF TRAVEL= 14m

COMMON PATH OF TRAVEL= 4.7m COMMON PATH OF TRAVEL= 4.7m


TH OF

ELE. NO.34
CAP.: 1050KG.
ELE. NO.34
CAP.: 1050KG.
90m Osool Integrated Real Estate Company
ON PA

90min FIRE
C A A RATED DOOR A A C
A A A A
COMM

A A
90min FIRE
RATED DOOR CO
MM
21m 90min FIRE 90min FIRE
LOCATION:
90min FIRE ON
PA
RATED DOOR RATED DOOR
90 RATED DOOR TH
mins OF 90
TR
22m AV
mins

Riyadh, KSA
9.5m

COM
EL
=8
90 m

MON
EL=

mins

60m COMMO 90min FIRE 90min FIRE 60m


RAV

B C C N PATH B

PAT
C OF TRAV
EL= 14m RATED DOOR RATED DOOR
C B C
C A C A A A A C C C C
OF T

H OF
CLIENT:
BC-E3
H

BD-E3 B

TRA
PAT

VEL
MON

=
83m
COM

9.5m
78m
COMMON PATH OF TRAVEL= 18.6m

COMMON PATH OF TRAVEL= 18.6m

120
120min FIRE mins 120min FIRE 120
mins

A A 39m RATED DOOR RATED DOOR 31m A A


90min FIRE
90min FIRE RATED DOOR OSOOL
RATED DOOR 90min FIRE C C A
C C RATED DOOR A
A A A COMMON PATH OF TRAVEL= 20m
60
mins
90min FIRE COMMON PATH OF TRAVEL= 20m
A A A A A A
CO
A A RATED DOOR MM
90min FIRE A 8.5m 90 90min FIRE ON
L= mins
A PA
RATED DOOR 17m AVE RATED DOOR TH
OF
EL= TR
RA
V H OF TR
CONSULTANT:
=8
.6m
= 13.2
m FT 18m 18m 90
mins
PAT COMM
ON P
AV
EL
VEL AVEL T HO M ON ATH O = 8.2
TRA F TR PA OM F TRA m
F ATH O ON C VEL=
HO ON P 90
MM 1
PAT COMM 3.2m
mins
CO 90min FIRE
ON
MM RATED DOOR
CO
90min FIRE
RATED DOOR
HOUSE OF CONSULTING OFFICE

Drawing Title
FIRE LIFE SAFETY
BASEMENT 2 FLOOR PLAN
FLS LAYOUT- OVERALL

1 BASEMENT 2 FLOOR PLAN FIRE LIFE SAFETY LAYOUT- OA Drawing No. 2023072-OA-B2-PL-FLS-200
FLS-200 SCALE 1:300 NZ ND 1:300 / A0
Designed Drawn Scale & Size
Rev.
MF SS NOV 2023
Checked Approved Date
01