DN-7070:J • A-10

NFS2-3030
Intelligent Addressable
Fire Alarm System
Intelligent Fire Alarm Control Panels

General
The NFS2-3030 is an intelligent Fire Alarm Control Panel
(FACP) designed for medium- to large-scale facilities. Fire
emergency detection and evacuation are extremely critical to
life safety, and the NFS2-3030 is ideally suited for these appli-
cations. The NFS2-3030 is part of the ONYX® Series of prod-
ucts from NOTIFIER. The NFS2-3030 is ideal for virtually any
application because it features a modular design that is config-
ured per project requirements. With one to ten Signaling Line
Circuits (SLCs), the NFS2-3030 supports up to 3,180 intelli-
gent addressable devices.
Information is critical to fire evacuation personnel, and the
NFS2-3030’s large 640-character Liquid Crystal Display (LCD)
presents vital information to operators concerning a fire situa-
tion, fire progression, and evacuation details.
A host of other options are available, including single- or multi-
channel voice; firefighter’s telephone; LED, LCD, or PC-based
graphic annunciators; networking; advanced detection prod- 7070covg.jpg

ucts for challenging environments, and many additional


options. NFS2-3030 (left)
and NFS2-3030 with DVC audio option (right)
Features
• Certified for seismic applications when used with the appro-
priate seismic mounting kit. • Advanced history filters allow sorting by event, time, date,
or address.
• Approved for Marine applications when a marine-listed ver-
sion is used with marine-listed compatible equipment (see • Alarm Verification selection per point, with automatic
DN-60688). counter.
• One to ten isolated intelligent Signaling Line Circuits (SLC) • Autoprogramming and Walk Test reports.
Style 4, 6 or 7. • Multiple central station communication options:
• Up to 159 detectors and 159 modules per SLC, 318 devices – Standard UDACT
per loop/3,180 per FACP or network node. Detectors can be – Internet
any mix of ion, photo, laser photo, thermal, or multi-sensor
– Internet/GSM
detectors; modules can be addressable pull stations, nor-
mally open contact devices, two-wire smoke detectors, • Positive Alarm Sequence (PAS) Presignal.
notification, or relay modules. • Silence Inhibit and Auto Silence timer options.
• Large 640-character LCD backlit display (16 lines x 40 char- • Field-programmable on panel or on PC, with VeriFire Tools
acters) or display-less (a node on a network). program, also check, compare.
• Network options: • Non-alarm points for lower priority functions.
– High-speed network for up to 200 nodes (NFS2-3030, • Remote ACK/Signal Silence/System Reset/Drill via monitor
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, modules.
ONYXWorks, NFS-3030, NFS-640, and NCA). • Up to 1000 powerful Boolean logic equations.
– Standard network for up to 103 nodes (NFS2-3030, • Supports SCS Series smoke control system in both HVAC
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, and FSCS modes.
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200,
• FM6320 approved Gas Detection System with FMM-4-20
AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes
module and any FM listed gas detector.
when DVC-EM is used in network paging.
• EIA-232 printer port.
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• EIA-485 annunciator port.
• VeriFire® Tools online/offline program option.
• With built-in Degraded Mode operation, the system is capa- 640-CHARACTER DISPLAY FEATURES
ble of general alarm if a fire alarm condition is present even • Backlit, 640-character display.
if the central processing unit (CPU) fails.
• Program keypad: full QWERTY keypad.
• Weekly Occupancy Schedules allow changing sensitivity by
time of day and day of week. • Up to nine users, each with a password and selectable
access levels.
• EIA-485 annunciators, including custom graphics.
• 11 LED indicators: Power; Fire Alarm; Pre-Alarm; Secu-
• History file with 4000-event capacity in nonvolatile memory, rity; Supervisory; System Trouble; Other Event; Signals
plus separate 1000-event alarm-only file. Silenced; Point Disabled; CPU Failure; Controls Active.

DN-7070:J • 06/28/2013 — Page 1 of 8


• Membrane Switch Controls: Acknowledge; Signal • Read Status displays the level of detector cleanliness.
Silence; Drill; System Reset; Lamp Test.
FSL-751 VIEW® (VERY INTELLIGENT EARLY WARNING)
• LCD Display: 640 characters (16 lines x 40 characters)
with long-life LED backlight. SMOKE DETECTION TECHNOLOGY
• Revolutionary spot laser design.
FLASHSCAN® INTELLIGENT FEATURES
• Advanced ONYX intelligent sensing algorithms differentiate
• Polls up to 318 devices on each loop in less than two between smoke and non-smoke signals (U.S. Patent
seconds. 5,831,524).
• Activates up to 159 outputs in less than five seconds. • Addressable operation pinpoints the fire location.
• Multicolor LEDs blink device address during Walk Test. • No moving parts to fail or filters to change.
• Fully digital, high-precision protocol (U.S. Patent • Early warning performance comparable to the best aspira-
5,539,389). tion systems at a fraction of the lifetime cost.
• Manual sensitivity adjustment — up to nine levels.
FAPT-851 ACCLIMATE PLUS™ LOW-PROFILE INTELLIGENT
• Pre-alarm ONYX intelligent sensing — up to nine levels.
MULTI-SENSOR
• Sensitivity levels:
• Detector automatically adjusts sensitivity levels without
– Ion – 0.5 to 2.5%/foot obscuration.
operator intervention or programming. Sensitivity increases
– Photo – 0.5 to 2.35%/foot obscuration. with heat.
– Laser (VIEW®) – 0.02 to 2.0%/foot obscuration. • Microprocessor-based technology; combination photo and
– Acclimate Plus™ – 0.5 to 4.0%/foot obscuration. thermal technology.
– IntelliQuad – 1.0 to 4.0%/foot obscuration. • Low-temperature signal at 40°F ± 5°F (4.44°C ± 2.77°C).
– IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration
FSC-851 INTELLIQUAD
• Drift compensation (U.S. Patent 5,764,142). ADVANCED MULTI-CRITERIA DETECTOR
• Multi-detector algorithm involves nearby detectors in alarm
• Detects all four major elements of a fire (smoke, heat, CO,
decision (U.S. Patent 5,627,515).
and flame).
• Automatic detector sensitivity testing (NFPA-72 compliant).
• Automatic drift compensation of smoke sensor and CO cell.
• Maintenance alert (two levels).
• High nuisance-alarm immunity.
• Self-optimizing pre-alarm.
• Six sensitivity levels.
• Programmable activation of sounder/relay bases during
alarm or pre-alarm.

Sample System Options

FAPT-851
FSL-751 NBG-12LX FMM-1 FRM-1 XP6/10 I/O
FSP-851 Modules
...etc.

CPU2-3030D
display or
CPU2-3030ND
7070blok.wmf

NFS2-3030
Shown in CAB-C4 with display
DVC-EM audio in CA-1 in second PRN Series
tier Printer
NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD2-80 in terminal mode, but not
both at the same time.

Page 2 of 8 — DN-7070:J • 06/28/2013


FCO-851 INTELLIQUAD™ PLUS Maintenance Warnings. When the drift compensation per-
ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR formed for a detector reaches a certain level, the performance
of the detector may be compromised, and special warnings
• Detects all four major elements of a fire. are given. There are three warning levels: (1) Low Chamber
• Separate signal for life-safety CO detection. value; (2) Maintenance Alert, indicative of dust accumulation
• Optional addressable sounder base for Temp-3 (fire) or that is near but below the allowed limit; (3) Maintenance
Temp-4(CO) tone. Urgent, indicative of dust accumulation above the allowed limit.
• Automatic drift compensation of smoke sensor and CO cell. Sensitivity Adjust. Nine sensitivity levels are provided for
• High nuisance-alarm immunity. alarm detection. These levels can be set manually, or can
• Six sensitivity levels. change automatically between day and night. Nine levels of
pre-alarm sensitivity can also be selected, based on predeter-
FMM-4-20 GAS DETECTION MODULE mined levels of alarm. Pre-alarm operation can be latching or
• Interface to industry-standard linear scale 4-20 mA sensors. self-restoring, and can be used to activate special control func-
tions.
• Five programmable thresholds.
• FM Approved, Class 6320 (Stationary Gas Sensors/ Self-Optimizing Pre-Alarm. Each detector may be set for
Detectors). “Self-Optimizing” pre-alarm. In this special mode, the detector
“learns” its normal environment, measuring the peak analog
RELEASING FEATURES readings over a long period of time, and setting the pre-alarm
• Ten independent hazards. level just above these normal peaks.
• Sophisticated cross-zone (three options). Cooperating Multi-Detector Sensing. A patented feature of
• Delay timer and Discharge timers (adjustable). ONYX Intelligent Sensing is the ability of a smoke sensor to
consider readings from nearby sensors in making alarm or
• Abort (four options). pre-alarm decisions. Without statistical sacrifice in the ability to
VOICE AND TELEPHONE FEATURES resist false alarms, it allows a sensor to increase its sensitivity
to actual smoke by a factor of almost two to one.
• Up to eight channels of digital audio.
• 35 watt, 50 watt, 75 watt, and 100/125 watt digital amplifiers Field Programming Options
(DAA2/DAX series and DS series).
Autoprogram is a timesaving feature. The FACP “learns” what
• Solid state message generation.
devices are physically connected and automatically loads
• Hard-wired voice control module options. them in the program with default values for all parameters.
• Firefighter telephone option. Requiring less than one minute to run, this routine allows the
• 30- to 120-watt analog amplifiers (AA Series). user to have almost immediate fire protection in a new installa-
tion, even if only a portion of the detectors are installed.
• Backup tone generator and amplifier option.
Keypad Program Edit. The NFS2-3030, like all NOTIFIER
FlashScan® Exclusive intelligent panels, has the exclusive feature of program cre-
ation and editing capability from the front panel keypad, while
World-Leading Detector Protocol continuing to provide fire protection. The architecture of the
At the heart of the NFS2-3030 is a set of detection devices and NFS2-3030 software is such that each point entry carries its
device protocol — FlashScan (U.S. Patent 5,539,389). FlashS- own program, including control-by-event links to other points.
can is an all-digital protocol that gives superior precision and This allows the program to be entered with independent per-
high noise immunity. point segments, while the NFS2-3030 simultaneously monitors
other (already installed) points for alarm conditions.
As well as giving quick identification of an active input device,
this protocol can also activate many output devices in a frac- VERIFIRE® TOOLS
tion of the time required by competitive protocols. This high
VeriFire® Tools is an offline programming and test utility that
speed also allows the NFS2-3030 to have the largest device
can greatly reduce installation programming time, and
per loop capacity in the industry — 318 points — yet every
increase confidence in the site-specific software. It is Win-
input and output device is sampled in less than two seconds.
dows® based and provides technologically advanced capabili-
The microprocessor-based FlashScan® detectors have bicolor
ties to aid the installer. The installer may create the entire
LEDs that can be coded to provide diagnostic information,
program for the NFS2-3030 in the comfort of the office, test it,
such as device address during Walk Test.
store a backup file, then bring it to the site and download from
a laptop into the panel.
ONYX Intelligent Sensing
ONYX Intelligent Sensing is a set of software algorithms that Product Line Information
provide the NFS2-3030 with industry-leading smoke detection
• “Configuration Guidelines” on page 4
capability. These complex algorithms require many calcula-
tions on each reading of each detector, and are made possible • “Main System Components” on page 4
by the very high-speed microcomputer used by the NFS2- • “Networking Options” on page 4
3030. • “Auxiliary Power Supplies and Batteries” on page 4
Drift Compensation and Smoothing. Drift compensation • “Audio Options” on page 4
allows the detector to retain its original ability to detect actual • “Compatible Devices, EIA-232 Ports” on page 5
smoke, and resist false alarms, even as dirt accumulates. It
reduces maintenance requirements by allowing the system to • “Compatible Devices, EIA-485 Ports” on page 5
automatically perform the periodic sensitivity measurements • “Compatible Intelligent Devices” on page 5
required by NFPA 72. Smoothing filters are also provided by • “Enclosures, Chassis, and Dress Plates” on page 6
software to remove transient noise signals, usually caused by • “Other Options” on page 7
electrical interference.

DN-7070:J • 06/28/2013 — Page 3 of 8


CONFIGURATION GUIDELINES NWS-3: NOTI•FIRE•NET™ Web Server. See DN-6928.
Stand-alone and network systems require a main display. On CAP-GW: Common Alerting Protocol Gateway. See DN-
single-FACP systems (one NFS2-3030D), the display option is 60576.
the CPU2-3030D. On network systems (two or more net-
VESDA-HLI-GW: VESDAnet high-level interface gateway. See
worked fire panel nodes), at least one NCA-2, NCS, or ONYX-
DN-60753.
Works annunciation device is required. Options listed as
follows. LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic
and high-speed NOTI•FIRE•NET networks through the NFN
MAIN SYSTEM COMPONENTS Gateway. See DN-60679.
CPU2-3030D: NFS2-3030 Primary Display. CPU2-3030D OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See
ships with keypad/display installed; includes 640-character DN-60679.
backlit LCD display, QWERTY programming and control key-
pad. CPU2-3030 is a central processing unit and requires an AUXILIARY POWER SUPPLIES AND BATTERIES
AMPS-24(E) power supply. Non-English versions are avail- AMPS-24(E): One required for each NFS2-3030. Addressable
able: CPU2-3030D-FR, CPU2-3030D-HE, CPU2-3030D-KO, power supply and battery charger with two 24 VDC outputs.
CPU2-3030D-PO, CPU2-3030D-SC, CPU2-3030D-SP, CPU2- Addressable by any FlashScan® or CLIP mode FACP.
3030D-TC, and CPU2-3030D-TH. For Marine applications Charges 7 to 200 AH batteries. Occupies up to five addresses
order CPU2-3030D-M or a non-English version. on an SLC, depending on configuration. Primary input power
CPU2-3030ND: CPU2-3030 without display. Non-English ver- for panel. See DN-6883.
sions are available: CPU2-3030ND-FR, CPU2-3030ND-HE, APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes
CPU2-3030ND-KO, CPU2-3030ND-PO, CPU2-3030ND-SC, of power for peripheral devices. Includes battery input and
CPU2-3030ND-SP, CPU2-3030ND-TC. transfer relay, and overcurrent protection. Mounts on two of
LCM-320: Loop Control Module. Provides one SLC. NFS2- four positions on a CHS-4L or CHS-4 chassis. See DN-5952.
3030 supports up to five LCM-320s and five LEM-320 expand- ACPS-610: 6.0 A or 10.0 A addressable charging power sup-
ers for a total of ten SLCs. See DN-6881. ply. See DN-60244.
LEM-320: Loop Expander Module. Expands an LCM-320. See FCPS-24S6/-24S8: Remote 6 A and 8 A power supplies with
DN-6881. battery charger. See DN-6927.
SAMPLE SYSTEM: Four-loop NFS2-3030 with display: BAT Series: Batteries. AMPS-24 uses two 12 volt, 7 to 200 AH
CPU2-3030D, DP-DISP, two BMP-1s, CHS-M3, two LCM- batteries. See DN-6933.
320s, two LEM-320s, AMPS-24, SBB-A4, DR-A4, BP2-4, BB-
100, batteries. AUDIO OPTIONS
NOTE: See “Enclosures, Chassis, and Dress Plates” on page 6 for
NETWORKING OPTIONS mounting hardware.
NCA-2: Network Control Annunciator, 640 characters. An DVC-EM: Digital Voice Command, digital audio processor with
alternate primary display for CPU2-3030 can be provided by message storage for up to 32 minutes of standard quality (4
the NCA-2, NCS, or ONYXWorks. Using NCA-2 as primary minutes at high quality) digital audio. See DN-7045.
display enables non-English languages. On network systems
(two or more networked fire panel nodes), one network display DVC-RPU: Digital Voice Command Remote Paging Unit for
(either NCA-2, NCS, or ONYXWorks) is required for every sys- use with DVC-EM. Includes the keypad/display. See DN-
tem. On network systems, the NCA-2 connects (and requires) 60726.
a standard Network Communication Module or High-Speed DS-DB: Digital Series Distribution Board, provides bulk ampli-
Network Communication Module. Mounts in a row of FACP fication capabilities to the DVC-EM while retaining digital audio
node or in two annunciator positions. Mounting options include distribuition capabilities. Can be configured with up to four DS-
the DP-DISP, ADP-4B, or in an annunciator box, such as the AMPs, supplying high-level risers spread throughout an instal-
ABS-2D. In CAB-4 top-row applications, a DP-DISP and two lation. See DN-60565.
BMP-1 blank modules are required for mounting. Non-English
versions are available: NCA-2-FR, NCA-2-HE, NCA-2-KO, DVC-KD: DVC-EM keypad for local annunciation and controls;
NCA-2-PO, NCA-2-SC, NCA-2-SP, NCA-2-TC, NCA-2-TH. For status LEDs and 24 user-programmable buttons. See DN-
marine applications, order NCA-2-M or non-English version. 7045.
See DN-7047. DS-AMP/E: 125W, 25 VRMS, or 100W, 70VRMS. 70VRMS
NCM-W, NCM-F: Standard Network Communications Mod- requires DS-XF70V step-up transformer. Digital Series Ampli-
ules. Wire and multi-mode fiber versions available. See DN- fier, part of the DS-DB system. See DN-60663.
6861. DS-RFM, DS-FM, DS-SFM: Fiber conversion modules for
HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed Network DVC-EM, DS-DB distribution board, and DAA2/DAX Series
Communications Modules that can connect to two nodes. amplifiers. See DN-60633.
Wire, single-mode fiber, multi-mode fiber, and media conver- DAA2-5025(E): 50W, 25 Vrms Digital Audio Amplifier assem-
sion models are available. See DN-60454. bly with power supply; includes chassis. See DN-60556.
RPT-W, RPT-F, RPT-WF: Standard-network repeater board DAA2-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier
with wire connection (RPT-W), multi-mode fiber connection assembly with power supply; includes chassis. See DN-60556.
(RPT-F), or allowing a change in media type between wire and DAA2-7525(E): 75W, 25 Vrms digital audio amplifier assembly
fiber (RPT-WF). Not used with high-speed networks. See DN- with power supply; includes chassis. See DN-60556.
6971.
DAX-3525(E): 35W, 25 Vrms Digital Audio Amplifier assembly
ONYXWorks: UL-listed graphics PC workstation, ONYXWorks with power supply, includes chassis. See DN-60561.
GUI software, and computer hardware. See DN-7048 for spe-
cific part numbers. DAX-3570(E): 35W, 70.7 Vrms Digital Audio Amplifier assem-
bly with power supply, includes chassis. See DN-60561.
NFN-GW-EM-3: NFN Gateway, embedded. (Replaces NFN-
GW-EM.) See DN-60499.

Page 4 of 8 — DN-7070:J • 06/28/2013


DAX-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly UDACT-2: Universal Digital Alarm Communicator Transmitter,
with power supply, includes chassis. See DN-60561. 636 channel. See DN-60686.
DAX-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assem- UZC-256: Programmable Universal Zone Coder provides pos-
bly with power supply, includes chassis. See DN-60561. itive non-interfering successive zone coding. Microprocessor-
TELH-1: Firefighter’s Telephone Handset for use with the controlled, field-programmable from IBM®-compatible PCs
DVC-EM when mounted in the CA-2 chassis. See DN-7045. (requires optional programming kit). Mounts on a CHS-4
series chassis within NFS2-3030.
CMIC-1: Microphone used with DVC/DVC-EM. Included with
CA-2 chassis assembly. See DN-7045. COMPATIBLE INTELLIGENT DEVICES
RM-1/RM-1SA: Remote microphone assemblies, mount on BEAMHK: Heating kit for transmitter/receiver unit of FSB-
ADP-4 (RM-1) dress panel or CAB-RM/-RMR (RM-1SA) 200(S) below. See DN-6985.
stand-alone cabinets. See DN-6728. BEAMHKR: Heating kit for use with the reflector of FSB-
AA-30: Audio Amplifier, 30 watts, 25 Vrms. Includes amplifier 200(S) below. See DN-6985.
and audio input supervision, backup input, and automatic swi- BEAMLRK: Long-range accessory kit, FSB-200(S) below.
tchover, power supply, cables. See DN-3224. See DN-6985.
AA-120/AA-100: Audio Amplifier. AA-120 is 120 watts, 25 BEAMMRK: Multi-mount kit, FSB-200(S) below. See DN-
Vrms. AA-100 is 100 watts, 70.7 Vrms. The amplifier contains 6985.
an integral chassis for mounting to a CAB-B4, -C4, or -D4
backbox (consumes one row). Includes audio input and ampli- BEAMSMK: Surface-mount kit, FSB-200(S) below. See DN-
fied output supervision, backup input, and automatic switcho- 6985.
ver to backup tone. See DN-3224. FSB-200: Intelligent beam smoke detector. See DN-6985.
DAA Series Digital Audio Amplifiers: Legacy DAA Series FSB-200S: Intelligent beam smoke detector with integral sen-
amplifiers are compatible with DVC systems running SR4.0. sitivity test. See DN-6985.
For specific information on DAA-50 series amplifiers, refer to
FSC-851: FlashScan IntelliQuad Advanced Multi-Criteria
DN-7046. For information on DAA-7525 Series, refer to DN-
Detector. See DN-60412.
60257.
FCO-851: FlashScan IntelliQuad PLUS Advanced Multi-Crite-
COMPATIBLE DEVICES, EIA-232 PORTS ria Fire/CO Detector. See DN-60689.
PRN-6: 80-column printer. See DN-6956. FSI-851: Low-profile FlashScan ionization detector. See DN-
VS4095/5: Printer, 40-column, 24 V. Order from Keltron, Inc. 6985.
See DN-3260. FSP-851: Low-profile FlashScan photoelectric detector. See
DPI-232: Direct Panel Interface, specialized modem for DN-6935.
extending serial data links to remotely located FACPs and/or FSP-851R: Low-profile intelligent photoelectric sensor, remote
peripherals. See DN-6870. test capable. For use with DNR(W). See DN-6935.
COMPATIBLE DEVICES, EIA-485 PORTS FSP-851T: Low-profile FlashScan photoelectric detector with
ACM-24AT: ONYX® Series ACS annunciator – up to 96 points 135°F (57°C) thermal. See DN-6935.
of annunciation with Alarm or Active LED, Trouble LED, and FST-851: FlashScan thermal detector 135°F (57°C). See DN-
switch per circuit. Active/Alarm LEDs can be programmed (by 6936.
powered-up switch selection) by point to be red, green, or yel-
FST-851R: FlashScan thermal detector 135°F (57°C) with
low; the Trouble LED is always yellow. See DN-6862.
rate-of-rise. See DN-6936.
AEM-24AT: Same LED and switch capabilities as ACM-24AT;
FST-851H: FlashScan 190°F (88°C) high-temperature thermal
expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.
detector. See DN-6936.
ACM-48A: ONYX® Series ACS annunciator – up to 96 points FAPT-851: FlashScan Acclimate Plus™ low-profile multi-sen-
of annunciation with Alarm or Active LED per circuit. Active/
sor detector. See DN-6937.
Alarm LEDs can be programmed (by powered-up switch selec-
tion) in groups of 24 to be red, green, or yellow. Expandable to FSL-751: FlashScan VIEW® laser photo detector. See DN-
96 points with one AEM-48A. See DN-6862. 6886.
AEM-48A: Same LED capabilities as ACM-48A; expands the DNR: InnovairFlex low-flow non-relay duct-detector housing
ACM-48A to 96 points. See DN-6862. (order FSP-851 separately). Replaces FSD-751PL/FSD-
751RPL. See DN-60429.
ACM-8R: Remote Relay Module with eight Form-C contacts.
Can be located up to 6,000 ft. (1828.8 m) from panel on four DNRW: Same as above with NEMA-4 rating, watertight. See
wires. See DN-3558. DN-60429.
LCD-160: Liquid Crystal Display annunciator, 160-character B224RB: Low-profile relay base. See DN-60054.
backlit. Can store character sets for multiple languages. Sup- B224BI: Isolator base for low-profile detectors. See DN-
ports Canadian requirements. See DN-6940. 60054.
LCD2-80: Terminal and ACS mode. 80-character, backlit LCD B210LP: Low-profile base. Standard U.S. style. Replaces
display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 B710LP. See DN-60054.
per FACP. See LCD2-80 (DN-60548).
B501: European-style, 4" (10.16 cm) base. See DN-60054.
SCS Series: Smoke control station; eight (expandable to 16)
circuits. See DN-4818. B200S: Intelligent programmable sounder base, capable of
producing a variety of tone patterns including ANSI Temporal
TM-4: Transmitter Module. Includes three reverse-polarity cir- 3. Compatible with sychronization protocol. See DN-60054.
cuits and one municipal box circuit. Mounts in panel module
position (as in single-address mode applications) or in CHS- B200SCOA: Based on B200SA, with added CO detector and
M3 position. See DN-6860. markings in English/French. For Canadian applications only.

DN-7070:J • 06/28/2013 — Page 5 of 8


B200SR: Sounder base, Temporal 3 or Continuous tone. See CA-1: Chassis, occupies one tier of a CAB-4 Series enclosure.
DN-60054. The left side accommodates one DVC-EM and a DVC-KD
FMM-1: FlashScan monitor module. See DN-6720. (optional); and the right side houses a CMIC-1 microphone
and its well (optional). See DN-7045.
FDM-1: FlashScan dual monitor module. See DN-6720.
CA-2: Chassis assembly, occupies two tiers of a CAB-4 Series
FZM-1: FlashScan two-wire detector monitor module. See DN- enclosure. The left side accommodates one DVC-EM mounted
6720. on a half-chassis and one NFS2-3030 or NCA-2 mounted on a
FMM-101: FlashScan miniature monitor module. See DN- half-chassis. The right side houses a microphone/handset
6720. well. The CA-2 assembly includes CMIC-1 microphone. ADDR
Series doors with two-tier visibility are available for use with
FMM-4-20: FlashScan 4-20 mA protocol monitor module. See the CA-2 configuration: ADDR-B4, ADDR-C4, ADDR-D4
DN-60411. (below).
FCM-1: FlashScan control module. See DN-6724. ADDR-B4: Two-tier-sized door designed for use with the CA-2
FCM-1-REL: FlashScan releasing control module. See DN- chassis configuration. ADDR Series doors are similar to CAB-
60390. 4 Series “DR” doors, but a clear window space exposes the
top two tiers of the CAB-4 enclosure. Use an SBB-B4 backbox
FTM-1: Firephone Telephone Module connects a remote fire-
with the ADDR-B4. See DN-7045, DN-6857.
fighter telephone to a centralized telephone console. Reports
status to panel. Wiring to jacks and handsets is supervised. ADDR-C4: Three-tier-sized door designed for use with the CA-
See DN-6989. 2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
FRM-1: FlashScan relay module. See DN-6724.
the top two tiers of the CAB-4 enclosure. Use an SBB-C4
FDRM-1: FlashScan dual monitor/dual relay module. See DN- backbox with the ADDR-C4. See DN-7045, DN-6857.
60709.
ADDR-D4: Four-tier-sized door designed for use with the CA-2
NBG-12LX: Manual pull station, addressable. See DN-6726. chassis configuration. ADDR Series doors are similar to CAB-
ISO-X: Isolator module. See DN-2243. 4 Series “DR” doors, but a clear window space exposes the
top two tiers of the CAB-4 enclosure. Use an SBB-D4 backbox
XP6-C: FlashScan six-circuit supervised control module. See with the ADDR-D4. See DN-7045, DN-6857.
DN-6924.
DPA-1: Dress panel, used with the CA-1 chassis when config-
XP6-MA: FlashScan six-zone interface module; connects ured with a DVC-EM, DVC-KD, and CMIC-1. See DN-7045.
intelligent alarm system to two-wire conventional detection
zone. See DN-6925. DPA-2: Dress Panel used with the CA-2 chassis assembly.
XP6-R: FlashScan six-relay (Form-C) control module. See DPA-1A4: Dress panel, used with the CA-1 chassis when the
DN-6926. CMIC-1 is not used. Provides mounting options on right two
bays for two ACS annunciators, or for blank plates. See DN-
XP10-M: FlashScan ten-input monitor module. See DN-6923. 7045.
SLC-IM: SLC integration module, for VESDAnet detectors. ADP-4B: Annunciator dress plate. Mounts in rows 2, 3 or 4 of
See DN-60755. a CAB-4 series enclosure. Used with ACS series annuncia-
ENCLOSURES, CHASSIS, AND DRESS PLATES tors.
CAB-4 Series Enclosure: NFS2-3030 mounts in a standard BMP-1: Blank module for unused module positions.
CAB-4 Series enclosure (available in four sizes, “A” through DP-1B: Blank dress panel. Provides dead-front panel for
“D”). Backbox and door ordered separately; requires BP2-4 unused tiers; covers DAA2/DAX series or AA-series amplifier.
battery plate. A trim ring option is available for semi-flush
mounting. See DN-6857. BP2-4: Battery plate, required.

EQ Series Cabinets: EQ series cabinets will house amplifiers, CHS-4L: Low-profile four-position Chassis. Mounts two AA-30
power supplies, battery chargers and control modules. EQ amplifiers.
cabinets are available in three sizes, “B” through “D”. See DN- CHS-4N: Chassis for mounting up to four APS-6Rs.
60229.
CHS-6: Chassis used with the XP6 and XP10 Multi-Modules.
CAB-BM Marine System: Protects equipment in shipboard Mounts up to six modules in any CAB-4 series row.
and waterfront applications. Order CPU2-3030D-M or a non-
BB-100: Backbox for batteries and power supplies. The BB-
English version. Also order BB-MB for systems using 100 AH
100 is used to mount up to two 100 AH batteries and power
batteries. For a full list of required and optional equipment, see
supply, if needed. 30" (76.20 cm) wide x 25" (63.50 cm) high x
DN-60688.
7.5" (19.05 cm) deep; depth includes door.
CHS-M3: Mounting chassis for CPU2-3030. One required for
BB-200: Backbox for batteries and power supplies. Holds up
each CPU2-3030D/3030ND.
to four 100 AH batteries (200 AH capacity) and power supply.
CA-2: Chassis for FACP control panel when DVC-EM is used 30" (76.20 cm) wide x 36" (91.44 cm) high x 7.5" (19.05 cm)
with firefighter's telephone. Mounts in the top two rows of a deep; depth includes door.
CAB-4 series enclosure.
NFS-LBB: Battery Box. The NFS-LBB is used to mount up to
DP-DISP: Dress panel for top row in cabinet with CPU2- two 55 AH batteries. Dimensions: Box: 24" (610 mm) wide x
3030D installed. 14" (356 mm) high x 7.75" (197 mm) deep. Door: 24.125" (613
DP-1B: Blank dress panel. Provides dead-front panel for mm) wide x 14.25" (362 mm) high; door adds 0.0625" (approx.
unused tiers; covers DAA2/DAX series or AA-series amplifier. 1.6 mm) to depth.
See DN-7046. BB-UZC: Backbox for housing the UZC-256 for applications
CHS-BH1: Battery chassis; holds two 12.0 AH batteries. where the UZC will not fit in panel enclosure. Black; for red,
Mounts on the left side of DAA2 chassis. See DN-7046. order BB-UZC-R. See DN-3404.

Page 6 of 8 — DN-7070:J • 06/28/2013


SEISKIT-CAB: Seismic mounting kit. Required for seismic- Battery charger range: 7 AH – 200 AH. Use separate cabinet
certified applications with NFS2-3030 and other equipment for batteries over 26 AH.
mounted in CAB-4 Series Enclosures. Includes battery bracket Float Rate: 27.6 V.
for two 26 AH batteries.
SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery SHIPPING WEIGHT
bracket for two 55 AH batteries. • CPU2-3030D: 5.95 lb (2.70 kg).
• CPU2-3030ND: 2.90 lb (1.32 kg).
OTHER OPTIONS
411: Slave digital alarm communicator. See DN-6619. TEMPERATURE AND HUMIDITY RANGES
411UDAC: Digital alarm communicator. See DN-6746. This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
IPDACT-2, IPDACT Internet Monitoring Module: Connects
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
to primary and secondary DACT telephone output ports for
useful life of the system's standby batteries and the electronic
internet communications over customer-provided Ethernet
components may be adversely affected by extreme tempera-
connection. Requires compatible Teldat VisorALARM Central
ture ranges and humidity. Therefore, it is recommended that
Station Receiver. Can use DHCP or static IP. See DN-60408.
this system and its peripherals be installed in an environment
IPCHSKIT: IP Communicator Chassis Mounting Kit. For with a normal room temperature of 15 – 27°C/60 – 80°F.
mounting an IPDACT-2/2UD onto the panel chassis or CHS-4
series chassis. Use IPENC for external mounting applications. AGENCY LISTINGS AND APPROVALS
IPSPLT: Y-adapter option allow connection of both panel dialer These listings and approvals apply to the modules specified in
outputs to one IPDACT-2/2UD cable input. this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
IPENC: External enclosure for IPDACT, includes IPBRKT be in process. Consult factory for latest listing status.
mounting bracket; Red; for black, order IPENC-B.
• UL Listed: S635.
IPGSM-DP: Internet and Digital Cellular Fire Alarm Communi-
• ULC Listed: S635.
cator. Provides selectable configurable paths: cellular only, IP
only, or IP primary with cellular backup. Connects to the primary • MEA: 232-06-E.
and secondary ports of a DACT. Replaces IPGSM-COM. See • FDNY: COA#6114.
DH-60695. • CSFM: 7165-0028:0224 (Commercial).
NOTE: For other options including compatibility with retrofit equip- • FM Approved.
ment, refer to the panel's installation manual, the SLC manual, and
the Device Compatibility Document. • FM6320 Approved. Class 6320 for Gas Detection.
• City of Chicago.
System Specifications • City of Denver.
• Singapore Productivity and Standards Board (PSB).
SYSTEM CAPACITY
• CCCF listed.
• Intelligent Signaling Line Circuits ...........1 expandable to 10
• Fire Services Department (Hong Kong).
• Intelligent detectors .......................................... 159 per loop
Marine Applications: Marine approved systems must be con-
• Addressable monitor/control modules .............. 159 per loop
figured using components itemized in this document. (See
• Programmable software zones ............................. over 2000 Main System Components, in “Product Line Information.) Spe-
• ACS annunciators cific connections and requirements for those components are
per CPU2-3030 .......................32 address x 64 or 96 points described in the installation document, PN 54756. When these
NOTE: The CPU2-3030 can support up to 96 annunciator requirements are followed, systems are approved by the fol-
address points per ACM-24AT/-48A. lowing agencies:
• US Coast Guard 161.002/55/0 (Standard 46 CFR and
SPECIFICATIONS
161.002).
Primary Input Power: • Lloyd's Register 11/600013 (ENV 3 category).
– AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum. • American Bureau of Shipping (ABS) Type Approval.
– AMPS-24E: 240 VAC, 50/60 Hz, 2.25 A maximum. NOTE: For information on marine applications, see DN-60688.
DC Output:
STANDARDS
– Main 24 VDC: Up to 5.0 A The NFS2-3030 complies with the following UL Standards and
– Aux 24 VDC: Up to 5.0 A NFPA 72, International Building Code (IBC), and California
– 5 VDC: Up to 0.15 A. Building Code (CBC) Fire Alarm Systems requirements:
Current draw (Standby/Alarm): • UL 864 (Fire).
– CPU2-3030D board: 0.340 A. • UL 1076 (Burglary).
– CPU2-3030ND board: 0.120 A. • LOCAL (Automatic, Manual, Waterflow and Sprinkler
– LCM-320: 0.130 A. Supervisory).
– LEM-320: 0.100 A. • AUXILIARY (Automatic, Manual and Waterflow) (requires
TM-4).
– AMPS-24(E)*: 0.13 A.
(Draws power from secondary power source only.) • REMOTE STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory) (requires TM-4).
NOTE: See AMPS-24(E) Manual 51907 for a complete current
draw calculation sheet and details of input and output values. • PROPRIETARY (Automatic, Manual, Waterflow and Sprin-
kler Supervisory). Not applicable for FM.
• EMERGENCY VOICE/ALARM.

DN-7070:J • 06/28/2013 — Page 7 of 8


• OT, PSDN (Other Technologies, Packet-switched Data Net-
work).
• IBC 2000, IBC 2003, IBC 2006, IBC2009 (Seismic).
• CBC 2007 (Seismic).

IntelliQuad™ and NOTI•FIRE•NET™ are all trademarks; and Acclimate®


Plus™, FlashScan®, NOTIFIER®, ONYX®, VeriFire®, and VIEW® are all
registered trademarks of Honeywell International Inc.
©2013 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.