Influence of Tertiary Stabilizing Windings On Zero-Sequence-Part II
Influence of Tertiary Stabilizing Windings On Zero-Sequence-Part II
a r t i c l e i n f o a b s t r a c t
Article history: This paper analyzes the influence of stabilizing windings in three-phase three-legged YNynd transformers
Received 4 October 2015 on tank overheating hazard and on the short-circuit performance of such transformers in the event
Received in revised form of unbalanced conditions involving zero-sequence currents as asymmetrical faults. It complements a
20 December 2016
previous companion paper that presented experimental zero-sequence measurements and equivalent
Accepted 2 January 2017
circuit calculations for three power transformers. Those previously calculated zero-sequence equivalent
Available online 10 January 2017
circuit parameters are used here to evaluate the comparative performance of YNynd power transformers
when the delta stabilizing winding is closed and when it is open. Additionally, it analyzes the effects of
Keywords:
Three-winding transformers
other variables, such as relative position of the stabilizing winding, presence of magnetic shunts in the
Tertiary stabilizing windings tank walls, and system grounding.
Transformer zero-sequence performance © 2017 Elsevier B.V. All rights reserved.
Short-circuit duty
Tank overheating hazard
http://dx.doi.org/10.1016/j.epsr.2017.01.003
0378-7796/© 2017 Elsevier B.V. All rights reserved.
150 A. Ramos, J.C. Burgos / Electric Power Systems Research 145 (2017) 149–156
Table 1 Table 2
Set of zero-sequence measurements taken. Characteristics of transformers subject to zero-sequence measurements.
Test number Test code HV winding LV winding Stabilizing winding Data Transformer
The most hazardous conditions for all transformers are obvi- was indicated in Section 2.1, the ampere-turn winding imbal-
ously in the HOO and LOO configurations, which represent ances offer a qualitative indication about tank heating hazard.
operating conditions when asymmetric faults or imbalances occur 3) Perform zero-sequence temperature rise tests as acceptance
in the primary (in the case of HOO) or secondary side (in the case tests in the transformer manufacturer laboratory. The number
of LOO) with transformer neutral ungrounded in the secondary and configuration of the tests must be determined according to
side (or primary in the case of LOO) and with the stabilizing wind- item 2 and they must be done with a neutral current equal (at
ing open (i.e. YN-y). In these cases (HOO and LOO), zero-sequence least) to item 1. A more detailed procedure is reported below.
ampere-turns in the energized winding are not compensated by the 4) Complementarily to zero-sequence temperature rise tests (or
other windings and so zero-sequence magnetic flux is potentially alternatively in clearly justified situations), a detailed and rig-
high, producing potentially hazardous tank currents and heating. orous finite element analysis could be carried out in order to
In other cases, under other operating conditions, tank heat- prevent tank overheating or internal hot spots in structural
ing hazard seems to be moderate or low. In authors’ opinion, parts. Desirably, this analysis should be done in early stages of
the ampere-turn winding imbalances offer a qualitative indica- transformer engineering and construction, so that a more ade-
tion about this hazard but, in order to evaluate the necessity of quate internal design or material selection could be derived.
stabilizing winding to avoid tank heating hazard, a more accurate
analysis should be complemented with zero-sequence temperature The procedure for specifying and performing zero-sequence
rise tests, as shown in the next section. temperature rise tests should be as follows:
Nonetheless, some interesting results may be derived from
Tables 3–5: - Apply a single-phase voltage source at rated frequency to HV
winding between the shorted line terminals and its neutral. LV
- In the case of transformer #1, despite what is commonly thought, winding may be open-circuited (HOO test) or shorted (HSO test).
the absence of a stabilizing winding does not eliminate ampere- In case of LOO or LSO tests, the voltage source is applied to LV
turn winding imbalances (for example, in tests HOC and HSC the winding with HV winding open-circuited or shorted, respectively.
imbalance is higher than in test HSO). - The excitation must be progressively increased up to the neu-
- Comparing Tables 3 and 4, it appears that the presence of tral current reach the maximum permitted value determined
magnetic shunts significantly reduces ampere-turn winding (see step 1 in the methodology above) and must remain constant
imbalances. throughout the test.
- The test may be ended when temperatures are stabilized (rate of
change below 1 ◦ C per hour).
2.2. Zero-sequence temperature rise tests - Temperature probes must be installed in each transformer tank
wall and cover (medium height and at the height correspond-
In the previous section, zero-sequence ampere-turn balances ing to windings top or ending of magnetic shunts). Additional
were shown in three transformers under different operating con- probes may be installed in the transformer oil outlet and inlet
figurations, identifying the situations in which tank overheating pipes. An ambient temperature measurement must be obtained.
hazard was higher. In practice, even in such situations, the mag- The exact number and position of temperature probes should
nitude and duration of zero-sequence flux and current circulation be agreed between user and manufacturer, depending on trans-
through the tank walls is limited by grid zero-sequence impedance former design, thermal analysis, etc. Temperatures must be
and transformer protection settings. Zero-sequence currents below recorded each 5 min.
this limit value could remain undetected, causing permanent zero- - If possible, fiber optic sensors may be installed to determine tem-
sequence flux and current circulation and subsequent tank (and perature rise of internal structural parts (i.e. clamping structures,
structural part) heating. bolts, etc.).
In order to detect overheating hazards due to zero-sequence flux - Just before the end of the test, a thermographic map of tank walls
circulation in case of omission of stabilizing windings in wye–wye should be obtained (with a thermographic camera). Coherence
three-legged transformers, the authors propose to include zero- between measurements of the thermographic camera and tem-
sequence temperature rise tests as mandatory type tests in the perature probes should be checked.
technical specification for the transformer purchasing process. The - Before and after each temperature rise test, transformer oil sam-
complete methodology proposed by the authors to evaluate over- ples must be extracted for dissolved gas-in-oil analysis (H2 , CH4 ,
heating hazards in wye–wye three-legged transformers without C2 H6 , C2 H4 , C2 H2 , CO, CO2 , O2 , N2 ) in order to detect internal hot
stabilizing windings include the following steps: spots during the tests.
1) Determine the maximum permitted value for neutral current in With the objective of implementing the methodology described
the transformer. This value must be determined depending on above, several transformer manufacturers were asked to evaluate
selectivity and sensitivity of the transformer protection system. the influence of permanent zero-sequence excitation under dif-
Neutral currents above this value must be tripped out for the ferent operating conditions on three-phase three-legged YNynd
transformer protection settings (an ordinary maximum permit- transformers. In the absence of a contractual obligation, as temper-
ted value for neutral current is about 0.2–0.5 p.u.). ature rise tests require high-voltage laboratories (with a relevant
2) Identify working conditions of the transformer that may gener- cost and duration), some limitations to the complete set of tests
ate a relevant circulation of neutral current. This aspect is very were agreed. Despite these restrictions, several zero-sequence tem-
dependent on primary and secondary neutral grounding of the perature rise tests were performed with very significant results.
transformer. For example, if a transformer has its primary neu- As it was indicated in the Part I of this paper, there are three
tral directly grounded and the secondary neutral is ungrounded, internal designs that cover the vast majority construction types of
then only primary zero-sequence excitation tests would be nec- three-phase three-legged YNynd power transformers. These types
essary (i.e. HOO condition). In the case that both transformer are represented for the analyzed transformers numbered with #1,
neutrals are grounded, then different working conditions would #2 and #3. As it was shown in the previous section, the ampere-turn
be occur (i.e. HSO and LSO conditions). In this regard, it can be balance analysis offered a qualitative indication that tank overheat-
very useful to have a zero-sequence ampere-turn analysis. As it ing hazard was higher in the transformer typology #1 (i.e. with
152 A. Ramos, J.C. Burgos / Electric Power Systems Research 145 (2017) 149–156
Table 7
Zero-sequence temperature rise test results in transformer #1B. 3. Short-circuit duty of YNynd transformers
Test configuration Neutral current (p.u.) Maximum tank
temperature rise (K)
Short-circuit duty is one of the key aspects when designing and
operating power transformers, as during these regimes windings
HOO 0.3 60.2
are subject to high currents and forces. In fact, short-circuit forces
HOC 1.0 40.8
HSO 1.2 33.4 largely determine the transformer’s mechanical design. As indi-
HSC 1.2 30.3 cated in the introduction, in the particular case of three-winding
YNynd transformers, stabilizing winding design is particularly crit-
ical to short-circuit forces, as these windings are typically thermally
inner stabilizing winding and no magnetic shunts) and, especially, designed for approximately one third of the transformer’s rated
in case of HV winding zero-sequence excitation. power.
The results of the zero-sequence temperature rise tests carried The aim of this section is to analyze the magnitude of the trans-
out on a transformer of this internal design characteristics (Table 6), former currents in the case of primary or secondary single-phase
numbered #1B (similar to transformer #1), are shown below. line-to-ground faults (1LG), and to compare the short-circuit duty
Following the test procedure indicated, four zero-sequence tem- of the different transformer types under study in several grid con-
perature rise tests were performed on transformer #1B, all of them figurations.
applying the voltage source to the HV winding. In the case of the
HOO test (most hazardous configuration), the neutral current was 3.1. Transformers, scenarios and equivalent circuits considered in
limited to 0.3 p.u., but in the rest of the tests neutral currents equal simulations
or above the rated current of the transformer were applied. In all the
tests, zero-sequence excitation was maintained for several hours to For the purpose of performing quantitative assessment of short-
achieve a thermal steady state. circuit duty in three-phase three-legged YNynd transformers,
Summarized results of the tests are shown in Table 7, where neu- different simulations with various real scenarios were carried out
tral current in the energized winding is expressed in per-unit values considering the variables involved in the wye–wye transformers’
in relation to the transformer rated current, and where maximum short-circuit duty behavior.
tank temperature rise is the highest measurement above ambient Table 8 shows the variables and options considered in the sim-
temperature obtained at various points of the tank walls and cover. ulations analyzed in this paper.
The main conclusions drawn from the experimental results of Fig. 1 shows the equivalent circuits used to calculate single-
transformer #1B are as follows: phase-to-ground fault currents.
Information about the transformers’ impedance parameters is
- The results of the temperature rise tests are consistent with the reported in Part I of this paper [22], considering that the equivalent
qualitative ampere-turn balance approach (transformers #1 and circuit model used for the simulations were model B. On the other
#1 B are twin units). hand, calculation of grid impedances was based on the grid short-
Table 8
Scenarios considered in simulations.
Transformer design types 3 - 45/15 kV 25 MVA (Design type These 3 transformers represent the
#1) main three-legged transformers’
- 220/66 kV 75 MVA (Design type design types (Fig. 1 of Part I [22])
#2)
- 220/66 kV 150 MVA (Design type
#3)
Table 10
Short-circuit current results for transformer #1.
Fault type Transformer neutral grounding Stabilizing winding closed Stabilizing winding open
Table 11
Short-circuit current results for transformer #2.
Fault type Transformer neutral grounding Stabilizing winding closed Stabilizing winding open
Table 12
Short-circuit current results for transformer #3.
Fault type Transformer neutral grounding Stabilizing winding closed Stabilizing winding open
Table 13
Short-circuit voltage results for transformer #1.
Fault type Transformer neutral grounding Stabilizing winding closed Stabilizing winding open
Table 14
Short-circuit voltage results for transformer #2.
Fault type Transformer neutral grounding Stabilizing winding closed Stabilizing winding open
Table 15
Short-circuit voltage results for transformer #3.
Fault type Transformer neutral grounding Stabilizing winding closed Stabilizing winding open
during a single-phase ground fault, expressed in per-unit values currents when there the neutral is grounded on at least the faulted
referred to the rated voltage of the winding. side, as the zero-sequence impedance of the transformer is lower
As one might expect, when the stabilizing winding is open, an when the stabilizing winding is closed. Moreover, the relative posi-
increase of the temporary overvoltages occurs in the non-faulted tion of the stabilizing winding was demonstrated to have great
phases, in the case of neutral grounding at the faulted side. This importance: when the stabilizing winding is the innermost wind-
increase affects both the faulted side and the non-faulted side. ing, the increase in short-circuit currents is much higher than when
When non-faulted side is ungrounded, the increase is slightly the stabilizing winding is the outermost winding.
higher. It can be concluded that the stabilizing windings in three-phase
Nonetheless, the omission of the stabilizing winding produces three-legged YNynd transformers may be omitted when primary
temporary overvoltages that can be easily withstood for the insu- and secondary neutral are both grounded (the most frequent sit-
lation of the analyzed transformers. uation), thus reducing very significantly the severe mechanical
requirements to which the transformer is subject during asym-
4. Conclusions metric short-circuits in case of YNynd transformers, and without
tank overheating hazard. When the primary or secondary neutral
Clear understanding of the influence of stabilizing windings remains ungrounded, in the absence of the stabilizing winding tank
on tank overheating hazard and short-circuit duty in three-phase overheating hazard should be critically reviewed by manufacturer
three-legged YNynd transformers is a key factor when evaluating and user, taking protection settings into account. In such cases, uti-
the need for stabilizing windings in such transformers. lization of magnetic shunts in the tank walls should be considered
This paper presented experimental data and simulations for as a possible alternative to the stabilizing winding.
zero-sequence ampere-turn balancing, zero-sequence tempera-
ture rise tests and short-circuit duty in three-phase three-legged Acknowledgment
YNynd transformers. Special attention was paid to features such
as the relative position of the stabilizing winding, the presence of The authors would like to thank Samuel Fernandez, from Uni-
magnetic shunts and the effect of primary and secondary neutral versidad Carlos III de Madrid, for his contribution in short-circuit
grounding, which are usually underestimated or scarcely analyzed. calculations.
In a qualitative approach, ampere-turn balance analysis per-
formed on three transformers revealed that most operating Appendix A.
configurations in three-phase three-legged YNynd transformers
present moderate or low tank overheating hazard due to circulation In this section, an example of calculation of the ampere-turn
currents in tank walls. That is true with the obvious exception of the balance shown in Tables 3–5 is presented.
situation in which only the primary or secondary neutrals remain Example of calculation of test configuration HOC in transformer
ungrounded and the stabilizing winding is open, as no compensa- #1:
tion of the zero-sequence ampere-turns is achieved in this case. As reported in Table 3 of Part I of the paper [22], the measured
Additionally, measurements show that the presence of magnetic currents in the zero-sequence impedance tests were: I1 = 1.581%;
shunts reduces ampere-turn winding imbalances, as they provide a I2 = 0; I3 = 1.243%, expressed in percentage from HV rated current
circulation path for the zero-sequence flux, so no currents circulate and SW rated current respectively.
through the tank walls. Considering module (phase): I1 = 5.07 A (−83.44◦ ); I2 = 0 A;
To complete the evaluation of tank overheating hazard in the I3 = 10.361 A (+93.59◦ ).
case of omission of stabilizing windings, a complete methodology HV winding has a number of turns of N1 = 426, HV winding has a
and procedure for specifying and performing zero-sequence tem- number of turns of N2 = 152 and SW winding has a number of turns
perature rise tests have been proposed. These tests were applied of N3 = 164.
to a transformer (designed with innermost stabilizing winding and Therefore, HV Ampere-turns = 2159.8 AT (−83.44◦ ); LV Ampere-
without magnetic shunts) concluding that tank overheating hazard turns = 0 AT; SW Ampere-turns = 1699.2 AT (93.59◦ ).
is not a concern unless, in case of absence of stabilizing windings, From Eq. (1): MMF0 + (N·I)tank = 471.2 AT (−72.7◦ ).
only one of the transformer neutrals is ungrounded. The results In order to achieve a more comprehensive analysis of these
of the temperature rise tests were consistent with the qualitative results, ampere-turns in non-energized windings are expressed as
ampere-turn balance approach in a twin transformer. a percentage of ampere-turns in energized windings (i.e. ampere-
For short-circuit duty, different fault scenarios were simulated turns of the primary winding are the reference in the denominator
to evaluate the influence of the presence of the stabilizing wind- for tests HOO, HOC, HSO and HSC, and ampere-turns of the sec-
ing, internal design characteristics (stabilizing winding position ondary winding are the reference in the denominator for tests LOO,
and presence of magnetic shunts) and neutral grounding schemes. LOC, LSO and LSC). In the example:
Through such simulations, it was quantified that the presence of a (N·I)1 = 2159.8/2159.8 = 100%
closed stabilizing winding significantly increases single-phase fault (N·I)2 = 0%
156 A. Ramos, J.C. Burgos / Electric Power Systems Research 145 (2017) 149–156
(N·I)3 = 1699.2/2159.8 = 78.7% [12] A.N. Garin, Zero-phase sequence characteristics of transformers. Part II:
MMF0 + (N·I)tank = 471.2/2159.8 = 21.8% equivalent circuits for transformers, Gen. Electr. Rev. 43 (April (4)) (1940)
78–82.
[13] F. Descans, Transformateurs à couplage étoile-étoile. Revue ACEC-Charleroi,
References 1969.
[14] T. Ngnegueu, M. Mailhot, A. Munar, Zero-phase impedance and tank heating
[1] M.A. Tsili, S.A. Papathanassiou, Analysis of a three-limb core power model for three-phase three-leg core type transformers coupling magnetic
transformer under earth fault, in: Proceedings of 16th International field and electric circuit equations in a finite element software, IEEE Trans.
Conference on Electrical Machines (ICEM), Cracow, Poland, September, 2004. Magn. 31 (May (3)) (1995) 2068–2071.
[2] L.F. Blume, Influence of transformers connections on operation, AIEE Trans. 33 [15] P. Penabad-Duran, C. Alvarez-Marino, X.M. Lopez-Fernandez, Transformer
(May) (1914) 753–770. tertiary stabilizing windings. Part II: overheating hazard on tank walls, XXth
[3] J.F. Peters, Harmonics in transformer magnetizing currents, AIEE Trans. 34 International Conference on Electrical Machines (ICEM) 31 (May (3)) (2012)
(September) (1915) 2157–2182. 2369–2374.
[4] L.N. Robinson, Phenomena accompanying transmission with some types of [16] IEC 60076-8, Power Transformers. Part 8: Application Guide, 1997.
star transformer connections, AIEE Trans. 34 (September) (1915) 2183–2195. [17] IEEE Std. C57.105, Guide for Application of Transformer Connections in
[5] J.F. Peters, M.E. Skinner, Transformers for interconnecting high-voltage Three-Phase Distribution Systems, 1978 (Reaffirmed 2008).
transmission systems for feeding synchronous condensers from a tertiary [18] U.S. Patent 1,173, 094 by L.F. Blume, Tertiary Winding, United States Patent
winding, AIEE Trans. 40 (June) (1921) 1181–1199. Office, February 1916.
[6] J. Mini Jr., L.J. Moore, R. Wilkins, Performance of auto transformers with [19] R.M. Charley, Recent progress in large transformers, J. Inst. Electr. Eng. 69
tertiaries under short-circuit conditions, AIEE Trans. 42 (October) (1923) (October (418)) (1931) 1189–1207.
1060–1068. [20] P. Penabad-Duran, X.M. Lopez-Fernandez, C. Alvarez-Marino, Transformer
[7] K.E. Gould, Instability in transformer banks, AIEE Trans. 46 (May) (1927) Tertiary Stabilizing Windings. Part I: Apparent Power Rating, XXth
676–682. International Conference on Electrical Machines (ICEM) (2012) 2369–2374.
[8] A. Boyajian, Inversion currents and voltages in auto-transformers, AIEE Trans. [21] G. Bertagnolli, L. Bergonzi, G. Cannavale, G. Caprio, F. Iliceto, B. Dilli, O.
49 (January) (1930) 810–818. Gülyyesil, Power Transmission Reliability. Technical and Economic Issues
[9] A. Boyajian, B.A. Cogbill, The Whys of the Wyes. The Behavior of Transformer Relating to the Short-Circuit Performance of Power Transformers. Paper no.
Y Connections, Publication General Electric Company GEA-6605/GET-3388B, 12-207, CIGRE Session, 2000.
1957. [22] A. Ramos, J.C. Burgos, Influence of stabilizing windings on zero-sequence
[10] B.A. Cogbill, Are stabilizing windings necessary in all Y-connected performance of three-phase three-legged YNynd transformers Part I:
transformers? AIEE Trans. Power Appar. Syst. 78 (October (3)) (1959) equivalent circuit models, Electr. Power Syst. Res. 144 (2017) 32–40.
963–970. [23] A. Ramos, Consideraciones Acerca de la Utilización de Arrollamientos de
[11] O.T. Farry, Tertiary windings in autotransformers, AIEE Trans. Power Appar. Estabilización en Transformadores Estrella-Estrella (Pd. D. Dissertation),
Syst. 80 (April (3)) (1961) 78–82. Universidad Carlos III de Madrid, 2016, January (in Spanish).