Declaration
AV Automatic Fire Alarm System
Advanced Electronics Ltd declares that the MX-5000 CIE provided with optional functions as listed in Annex 1 and
comprising of system components as listed in Annex 2 meets the requirements of:
EN54-13:2005 Fire detection and fire alarm systems – Compatibility assessment of system components
This declaration is prepared based on the results detailed in the test reports listed in Annex 3.
Authorised by:
D Wilson
Engineering Manager
Total number of pages: 08 Revision: 02 Date Issued: 2013-10-09
www.advancedco.com
Annex 1 Options with requirements
Optional function with requirements EN54-2 Clause
Output to fire alarm devices 7.8
Output to fire alarm routing equipment 7.9
Output to fire protection equipment 7.10
Delays to outputs 7.11
Coincidence detection, Type B dependency 7.12.2
Coincidence detection, Type C dependency 7.12.3
Alarm Counter 7.13
Fault signals from points 8.3
Output to fault warning routing equipment 8.9
Disablement of addressable points 9.5
Test condition 10
Standardised interface 11
www.advancedco.com
Annex 2 System Components
1
Type / Part Number Description Certificate Type
Control and Indicating Equipment
MX-5101V Control and indicating equipment – 1 Loop 0786-CPD-20952 1
Enclosures S, M, L, D, R
MX-5201V – MX-5202V Control and indicating equipment – 1-2 Loop 0786-CPD-20952 1
Enclosures M, L, D, R
MX-5401V – MX-5404V Control and indicating equipment – 1-4 Loop 0786-CPD-20952 1
Enclosures M, L, D, E, R
MX-5030/FT Control and indicating equipment – RCT G210022 1
2
System Components - Optional
MXP-501 Battery Temperature Sensor G210022 1
3
MXP-502 Loop Interface Card G210022 1
MXP-505 Alarm Circuit Active EOL G210022 1
MXP-506 Routing / Protection Standardised Termination G210022 1
MXP-507 Relay Card – 2-Way G210022 1
MXP-509 Network Interface Card – FT G210022 1
MXP-510/FT Network BMS Interface G210022 1
MXP-512 Printer G210022 2
4
MXP-513-XXX LED Indicators G210022 1
MXP-514 AC Filter Card G210022 1
MXP-532 PBUS Module – Routing / Protection Interface G210022 1
MXP-536 PBUS Module – 8-Way Zone Interface G210022 1
MXP-537 PBUS Module – 10-Way Input G210022 1
MXP-538 PBUS Module – 16-Way Switch / 48-LED G210022 1
MXP-539 PBUS Module – 16-Way Input / 48-Output G210022 1
MXP-547 Pager Interface G210022 1
MXP-554/FT Network LAN Interface G210022 1
MXP-034 PBUS Module – 4-Way Sounder G210022 1
MXP-035 PBUS Module – 4-Way Relay G210022 1
MXP-045/FT Network 50-Way I/O G210022 1
MXS-051 PSE Module 5A G210022 1
1
Component Types are listed in accordance with the categories in EN54-13 – Type 1 compatible and Type 2 connectable.
2
Tested as part of the control and indicating system and listed in the report.
3
A minimum of one loop driver is installed in each panel.
4
Covers variants -050RD, -050RY, -050YL, -100RD, -100RY, -100YL, -050CRY, -050CRYG and -200RY
www.advancedco.com
Type / Part Number Description Certificate Type
Loop Devices
20-V100-ADV Detector – Optical Smoke 0832-CPD-1123 1
20-V200-ADV Detector – Multi-criteria, Optical Smoke / Heat 0832-CPD-1124 1
20-V350-ADV Detector – Heat 0832-CPD-1122 1
20-LV100-ADV Detector – Optical Smoke 0832-CPD-1118 1
20-LV200-ADV Detector – Multi-criteria, Optical Smoke / Heat 0832-CPD-1119 1
20-LV350-ADV Detector – Heat 0832-CPD-1120 1
5
20-VB100-ADV Detector Mounting Base N/A 1
5
20-VDBS100-ADV Detector Mounting Base – Deep N/A 1
5
20-VBLR100-ADV Detector Mounting Base – Relay N/A 1
20-VCP100-ADV Manual Call Point – Red 0832-CPD-1117 1
20-VCP100-B-ADV Manual Call Point – Blue 0832-CPD-1117 1
20-VCP100-G-ADV Manual Call Point – Green 0832-CPD-1117 1
20-VCP100-W-ADV Manual Call Point – White 0832-CPD-1117 1
20-VCP100-Y-ADV Manual Call Point – Yellow 0832-CPD-1117 1
20-VMI100-ADV Monitored Input Module 0786-CPD-21190 1
20-VMMI100-ADV Monitored Input Module – Mini 0786-CPD-21210 1
20-VMC100-ADV Monitored Output Module 0786-CPD-21188 1
20-VMMC100-ADV Monitored Output Module – Mini 0786-CPD-21211 1
20-VMC120-ADV Relay Output Module 0786-CPD-21186 1
20-VMMC120-ADV Relay Output Module – Mini 0786-CPD-21213 1
20-VMIC100-ADV Monitored Input / Monitored Output Module 0786-CPD-21189 1
20-VMMIC100-ADV Monitored Input / Monitored Output Module - Mini 0786-CPD-21212 1
20-VMIC120-ADV Monitored Input / Relay Output Module 0786-CPD-21187 1
20-VMMIC120-ADV Monitored Input / Relay Output Module – Mini 0786-CPD-21214 1
6
20-MB100-ADV Mounting Box for Modules N/A
6
20-DMB100-ADV Mounting Box for Modules – Deep N/A
20-VMIC404-ADV Monitored 4 Input / 4 Relay Output Module 0051-CPD-0335 1
20-VMIC602-ADV Monitored 6 Input / 2 Relay Output Module 0051-CPD-0336 1
20-VMIC422-ADV Monitored 4 Input / 2 Relay Output / 2 Monitored Output 0051-CPD-0334 1
Module
20-VLS100-ADV Wall Sounder 0832-CPD-1121 1
20-VLS100H-ADV Wall Sounder (Slow Whoop) – Red 0832-CPD-1064 1
20-VLS100HW-ADV Wall Sounder (Slow Whoop) – White 0832-CPD-1064 1
20-VW2W100-ADV Wireless Translator Module 0832-CPD-1071 1
5
Detector bases are covered on the detector certificates.
6
Boxes are covered on the device certificates.
www.advancedco.com
Type / Part Number Description Certificate Type
20-SG100-ADV Wireless Detector – Optical Smoke 0832-CPD-1069 1
20-SG200-ADV Wireless Detector – Optical Smoke / Heat Enhanced 0832-CPD-1070 1
20-SG350-ADV Wireless Detector – Heat 0832-CPD-1068 1
20-SGRS100-ADV Wireless Wall Sounder 0832-CPD-1686 1
20-SGRS100W-ADV Wireless Wall Sounder – White 0832-CPD-1686 1
20-SGRS100-H-ADV Wireless Wall Sounder (Slow Whoop) 0832-CPD-1688 1
20-SGRS100-HW- Wireless Wall Sounder (Slow Whoop) – White 0832-CPD-1688 1
ADV
7
20-SGRS100-AV-ADV Wireless Sounder Beacon 0832-CPD-1687 1
7
20-SGRS100-AV/W- Wireless Sounder Beacon – White 0832-CPD-1687 1
ADV
7
Note: The date of compliance to CPD/CPR EN54-23 is 2013-12. The devices listed remain compatible but compliance with the CPD/CPR is
not assured beyond the date of compliance or unless this declaration is updated. Beacons can be used as Type 2 devices.
www.advancedco.com
Type / Part Number Description Certificate Type
8
Conventional Detector Devices
20-S1000-ADV Detector – Optical Smoke 0832-CPD-1421 1
20-S2000-ADV Detector – Multi-criteria, Optical Smoke / Heat -- 1
20-S3500-ADV Detector – Heat 0832-CPD-1425 1
08-RP-RS-01 Manual Call Point – Red – Type A -- 1
08-RP-RS1-01 Manual Call Point – Red – Type A -- 1
08-RP-RF-01 Manual Call Point – Red – Type A -- 1
08-RP-YS-01 Manual Call Point – Yellow – Type A -- 2
08-RP-YS1-01 Manual Call Point – Yellow – Type A -- 2
08-RP-YF-01 Manual Call Point – Yellow – Type A -- 2
HFM/3/11/02 LST Manual Call Point – Red – Type B 0786-CPD-20350 1
HM/3/11/01/02 LST Manual Call Point – Red – Type B 0786-CPD-20350 1
HM/1/11/17/02 LST Manual Call Point – Yellow – Type B 0786-CPD-20251 2
HM/5/11/02/02 LST Manual Call Point – Blue – Type B 0786-CPD-20363 2
HM/5/11/18/02 LST Manual Call Point – Blue – Type B 0786-CPD-20363 2
8
Connected via the MXP-536 Interface.
www.advancedco.com
Type / Part Number Description Certificate Type
9
Conventional Alarm Devices
18-980542 Klaxon Nexus Sounder (105dB) 0832-CPD-0617 1
18-980620 Klaxon Nexus Sounder Beacon (105dB) 0832-CPD-0615 1
9
Any conventional sounder / beacon may be connected if the device operating voltage range is: 15V ≤ V ≥ 28V. The number of devices that can
be connected depends on the loading. The sounder circuit current rating (1A) must not be exceeded.
www.advancedco.com
Annex 3 Test documentation
Accredited Laboratory Report Number Date
VdS Schadenverhütung (DAT PL-016/92) BMA 10001 2010-02-24
VdS Schadenverhütung (DAT PL-016/92) BMA 10029 2010-03-03
BSI Product Services (UKAS 0135) 2244/7756376 2012-04-27
VdS Schadenverhütung (DAkkS D-PL-11149-01-01) BMA 13004 2013-02-25
VdS Schadenverhütung (DAkkS D-PL-11149-01-01) BMA 13015 2013-03-01
www.advancedco.com