Substation Automation System

IO LIST

765/400kV BANASKANTHA S/S Extn.

M/s. POWERGRID LIMITED

We reserve all rights in this document and in the information contained therein. Reproduction use or disclosure to third parties without
express authority is strictly forbidden. Copyright © by Hitachi Energy India Limited.
“Disclaimer – Unauthorized access
The offered solution may be accessed through the customer network and therefore represents a danger which poses a potential threat of
intrusion by unauthorized parties. Therefore, Hitachi Energy India Limited strongly recommends that the customer insures/implements
necessary protection measures against the possibility of such unauthorized access.
Hitachi Energy India Limited disclaims any responsibility and shall under no circumstances be liable for damages or malfunctions caused
by external intrusion of any kind whatsoever."
DOCUMENT IO LIST

SUPPLY OF CRP & SAS FOR


PROJECT
765/400kV BANASKANTHA S/S Extn.

SUBSTATION 765/400kV BANASKANTHA S/S Extn.

CLIENT

CONTRACTOR

PO / LOA No. 21314 Dtd.: 31.10.2022

HEIL SO REF. 3100136512

Revisions:
Rev. Prep. / Appr. Description Date
0 SSR / PSK First Submission 12/10/2023

CUSTOMER DEPT. DOCUMENT ID. Rev. Lang. Page

M/s. POWERGRID LIMITED PG-GA 1MNS500836-SIOL 0 en -


PROJECT PREP. APPR. DATE

SUPPLY OF CRP & SAS FOR 765/400kV BANASKANTHA S/S Extn. SSR PSK 12/10/2023

Hitachi Energy India Limited © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_INDEX REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR

ABB IEDs SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (INDEX)

BAY IED MODEL IED SYMBOLIC NAME APPLICATION IED NAME IN SCD
REC670 R_REC670_BCU Bay Control Unit STNMB1Q01LBCU
LINE REL670 R_REL670_21M1 Main 1 Distance Protection STNMB1Q01LM1DIS
P444** R_RELAY NAME_21M2 Main 2 Distance Protection **

REC670 R_REC670_BCU Bay Control Unit STNMB1Q01ICTBCU


RET670 R_RET670_87T Differential Protection STNMB1Q01ICTDIF
RET670 R_RET670_64 Restricted Earthfault Protection STNMB1Q01ICTREF
ICT
REL670 R_REL670_HVBUP HV Backup OC/EF Protection STNMB1Q01ICTHBU
REL670 R_REL670_IVBUP LV Backup OC/EF Protection STNMB1Q01ICTLBU
TAPCON ** R_RELAY NAME_RTCC Main 2 Distance Protection **

TIE REC670 R_REC670_BCU Bay Control Unit STNMB1Q01TIEBCU


LBB REB670 R_RELAY NAME_50BFR Breaker Failure Protection STNMB1Q01BFR

NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "B1" stand for Voltage level, this will be vary based on station voltage level eg. B1 for 765kV, C1 for 400kV & D1 for 220kV etc…
NOTE 3: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…
NOTE 4: ** Line Main2 Distance protection IED name will be subject to provision availability of maximum number of characters in the IED

Page 1 of 9
Doc.No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_765kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR

ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (765kV ICT BAY)

REQUIRED SIGNALS FOR ICT DIFFERENTIAL RELAYS


IED name: R_RET670_87T IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 765kV STNMB1Q01ICTDIF OVEREXCITATION HV START SPI SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Str/general Same as Ver 1.1 SS_BAY_DIFFERENTIAL/PROT/OEXPVPH1/Str/general
2 765kV STNMB1Q01ICTDIF OVEREXCITATION HV ALARM SPI Y SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Alm/stVal SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/ExtAlm/stVal SS_BAY_DIFFERENTIAL/PROT/OEXPVPH1/Alm/stVal
3 765kV STNMB1Q01ICTDIF OVEREXCITATION HV TRIP SPI Y SS_BAY_DIFFERENTIAL/LD0/OEXPVPH1/Op/general SS_BAY_DIFFERENTIAL/PROT/OEXPVPH1/Op/general
4 765kV STNMB1Q01ICTDIF DIFFERENTIAL CURRENT ALARM SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/DifAlm/stVal SS_BAY_DIFFERENTIAL/TnW_1/TnWGAPC1/Alm1/stVal
5 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION START SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/general SS_BAY_DIFFERENTIAL/TnW_1/TnWPDIF1/Str/general
6 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION RPH START SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsA SS_BAY_DIFFERENTIAL/TnW_1/TnWPDIF1/Str/PhsA
7 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION YPH START SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsB SS_BAY_DIFFERENTIAL/TnW_1/TnWPDIF1/Str/PhsB
8 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION BPH START SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Str/PhsC SS_BAY_DIFFERENTIAL/TnW_1/TnWPDIF1/Str/PhsC
9 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION TRIP SPI Y SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Op/general SS_BAY_DIFFERENTIAL/TnW_1/TnWPDIF1/Op/general
10 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION RPH TRIP SPI Y SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SS_BAY_DIFFERENTIAL/MON/SP16GAPC n/Ind n/stVal
11 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION YPH TRIP SPI Y SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SS_BAY_DIFFERENTIAL/MON/SP16GAPC n/Ind n/stVal
12 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION BPH TRIP SPI Y SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SS_BAY_DIFFERENTIAL/MON/SP16GAPC n/Ind n/stVal
13 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION TRIP (RESTRAINED MODE) SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpRst/stVal SS_BAY_DIFFERENTIAL/TnW_1/TnWPDIF_1/Op/general
14 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION TRIP (UNRESTRAINED MODE) SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/OpUnRst/stVal SS_BAY_DIFFERENTIAL/TnW_1/TnWPDIF_2/Op/general
15 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION 2nd HARMONIC BLOCK SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk2H/stVal SS_BAY_DIFFERENTIAL/TnW_1/TnWPHAR1/Str/general
16 765kV STNMB1Q01ICTDIF DIFFERENTIAL PROTECTION 5th HARMONIC BLOCK SPI SS_BAY_DIFFERENTIAL/LD0/TnWPDIF1/Blk5H/stVal SS_BAY_DIFFERENTIAL/TnW_1/TnWPHAR2/Str/general
17 765kV STNMB1Q01ICTDIF DIFFERENTIAL RELAY GENERAL TRIP SPI Y SS_BAY_DIFFERENTIAL/LD0/SMPPTRC1/Op/general SS_BAY_DIFFERENTIAL/CTRL/SMPPTRC1/Op/general
18 765kV STNMB1Q01ICTDIF TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SS_BAY_DIFFERENTIAL/MON/SP16GAPC n/Ind n/stVal
19 765kV STNMB1Q01ICTDIF DIFFRENTIAL IED UNHEALTHY SPI Y SS_BAY_DIFFERENTIAL/LD0/LPHD1/PhyHealth/stVal SS_BAY_DIFFERENTIAL/LD0/LPHD1/PhyHealth/stVal
20 765kV STNMB1Q01ICTDIF OTI ALARM SPI Y
21 765kV STNMB1Q01ICTDIF WTI HV ALARM SPI Y
22 765kV STNMB1Q01ICTDIF WTI IV ALARM SPI Y
23 765kV STNMB1Q01ICTDIF WTI MV ALARM SPI Y
24 765kV STNMB1Q01ICTDIF BUCCHOLZ TRIP SPI Y Applicable for Three Phase Transformers
25 765kV STNMB1Q01ICTDIF OSR 1 TRIP SPI Y
26 765kV STNMB1Q01ICTDIF PRD 1 TRIP SPI Y
27 765kV STNMB1Q01ICTDIF FIRE PROTECTION OPERATED SPI Y
28 765kV STNMB1Q01ICTDIF LOW OIL LEVEL SPI Y
29 765kV STNMB1Q01ICTDIF OTI R PH ALARM SPI Y
30 765kV STNMB1Q01ICTDIF OTI Y PH ALARM SPI Y
31 765kV STNMB1Q01ICTDIF OTI B PH ALARM SPI Y
32 765kV STNMB1Q01ICTDIF OTI SPARE ICT ALARM SPI Y
33 765kV STNMB1Q01ICTDIF WTI HV R PH ALARM SPI Y
34 765kV STNMB1Q01ICTDIF WTI HV Y PH ALARM SPI Y
35 765kV STNMB1Q01ICTDIF WTI HV B PH ALARM SPI Y
36 765kV STNMB1Q01ICTDIF WTI HV SPARE ICT ALARM SPI Y
37 765kV STNMB1Q01ICTDIF WTI MV R PH ALARM SPI Y Same as Ver 1.1
38 765kV STNMB1Q01ICTDIF WTI MV Y PH ALARM SPI Y
39 765kV STNMB1Q01ICTDIF WTI MV B PH ALARM SPI Y
40 765kV STNMB1Q01ICTDIF WTI MV SPARE ICT ALARM SPI Y
41 765kV STNMB1Q01ICTDIF WTI IV R PH ALARM SPI Y
42 765kV STNMB1Q01ICTDIF WTI IV Y PH ALARM SPI Y
43 765kV STNMB1Q01ICTDIF WTI IV B PH ALARM SPI Y
44 765kV STNMB1Q01ICTDIF WTI IV SPARE ICT ALARM SPI Y
45 765kV STNMB1Q01ICTDIF BUCCHOLZ R PH TRIP SPI Y Applicable for Single Phase Transformers
SS_BAY_DIFFERENTIAL/LD0/SP16GGIO n/Ind n/stVal SS_BAY_DIFFERENTIAL/MON/SP16GAPC n/Ind n/stVal
46 765kV STNMB1Q01ICTDIF BUCCHOLZ Y PH TRIP SPI Y (If a dedicated IED is provided for spare
47 765kV STNMB1Q01ICTDIF BUCCHOLZ B PH TRIP SPI Y transformer protection, only spare phase
signals are required to be used)
48 765kV STNMB1Q01ICTDIF BUCCHOLZ SPARE ICT TRIP SPI Y
49 765kV STNMB1Q01ICTDIF OSR 1 R PH TRIP SPI Y
50 765kV STNMB1Q01ICTDIF OSR 1 Y PH TRIP SPI Y
51 765kV STNMB1Q01ICTDIF OSR 1 B PH TRIP SPI Y
52 765kV STNMB1Q01ICTDIF OSR 1 SPARE ICT TRIP SPI Y
53 765kV STNMB1Q01ICTDIF PRD 1 R PH TRIP SPI Y
54 765kV STNMB1Q01ICTDIF PRD 1 Y PH TRIP SPI Y
55 765kV STNMB1Q01ICTDIF PRD 1 B PH TRIP SPI Y
56 765kV STNMB1Q01ICTDIF PRD 1 SPARE ICT TRIP SPI Y
57 765kV STNMB1Q01ICTDIF LOW OIL LEVEL R PH SPI Y
58 765kV STNMB1Q01ICTDIF LOW OIL LEVEL Y PH SPI Y
59 765kV STNMB1Q01ICTDIF LOW OIL LEVEL B PH SPI Y
60 765kV STNMB1Q01ICTDIF LOW OIL LEVEL SPARE ICT SPI Y
61 765kV STNMB1Q01ICTDIF FIRE PROTECTION R PH OPERATED SPI Y
62 765kV STNMB1Q01ICTDIF FIRE PROTECTION Y PH OPERATED SPI Y
63 765kV STNMB1Q01ICTDIF FIRE PROTECTION B PH OPERATED SPI Y
64 765kV STNMB1Q01ICTDIF FIRE PROTECTION SPARE ICT OPERATED SPI Y
65 765kV STNMB1Q01ICTDIF TRIP RELAY 86 A HEALTHY (SUPERVISION) SPI Y
66 765kV STNMB1Q01ICTDIF TRIP RELAY 86 B HEALTHY (SUPERVISION) SPI Y
67 765kV STNMB1Q01ICTDIF GR A RELAY OPERATED SPI Y
68 765kV STNMB1Q01ICTDIF GR B RELAY OPERATED SPI Y
69 765kV STNMB1Q01ICTDIF REF RELAY FAIL SPI Y
Only if the IED subscriber to GOOSE
70 765kV STNMB1Q01ICTDIF GOOSE RECEIPT FAIL/TROUBLE SPI Y messgaes as per the scheme
ANY ADDITIONAL SIGNAL AS PER SCHEME
** It may be noted that the Body Protection alarms & trips have been Grouped into two separate relays Differential (Group A) & REF (Group B) relays. The hardwiring for same must be done accordingly and approved scheme shall be modified if required. Same is applicable for Reactor protection also.

Page 2 of 9
Doc. No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_765kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR

ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (765kV ICT BAY)

REQUIRED SIGNALS FOR ICT REF RELAYS


IED name: R_RET670_64 IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 765kV STNMB1Q01ICTREF OVEREXCITATION MV START SPI SS_BAY_REF/LD0/OEXPVPH1/Str/general Same as Ver 1.1 SS_BAY_REF/PROT/OEXPVPH1/Str/general
2 765kV STNMB1Q01ICTREF OVEREXCITATION MV ALARM SPI Y SS_BAY_REF/LD0/OEXPVPH1/Alm/stVal SS_BAY_REF/LD0/OEXPVPH1/ExtAlm/stVal SS_BAY_REF/PROT/OEXPVPH1/Alm/stVal
3 765kV STNMB1Q01ICTREF OVEREXCITATION MV TRIP SPI Y SS_BAY_REF/LD0/OEXPVPH1/Op/general SS_BAY_REF/PROT/OEXPVPH1/Op/general
4 765kV STNMB1Q01ICTREF REF ALARM SPI SS_BAY_REF/LD0/HZPDIF1/Alm/stVal SS_BAY_REF/MON/SP16GAPC n/Ind n/stVal
5 765kV STNMB1Q01ICTREF REF TRIP SPI Y SS_BAY_REF/LD0/HZPDIF1/Op/general SS_BAY_REF/PROT/HZPDIF1/Op/general
6 765kV STNMB1Q01ICTREF REF RELAY GENERAL TRIP SPI Y SS_BAY_REF/LD0/SMPPTRC1/Op/general SS_BAY_REF/CTRL/SMPPTRC1/Op/general
7 765kV STNMB1Q01ICTREF TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_REF/MON/SP16GAPC n/Ind n/stVal
8 765kV STNMB1Q01ICTREF REF IED UNHEALTHY SPI Y SS_BAY_REF/LD0/LPHD1/PhyHealth/stVal SS_BAY_REF/LD0/LPHD1/PhyHealth/stVal
9 765kV STNMB1Q01ICTREF OTI TRIP SPI Y
10 765kV STNMB1Q01ICTREF WTI HV TRIP SPI Y
11 765kV STNMB1Q01ICTREF WTI MV TRIP SPI Y
12 765kV STNMB1Q01ICTREF WTI LV TRIP SPI Y Applicable for Three Phase Transformers
13 765kV STNMB1Q01ICTREF OSR 2 TRIP SPI Y
14 765kV STNMB1Q01ICTREF PRD 2 TRIP SPI Y
15 765kV STNMB1Q01ICTREF BUCCHOLZ ALARM SPI Y
16 765kV STNMB1Q01ICTREF OTI R PH TRIP SPI Y
17 765kV STNMB1Q01ICTREF OTI Y PH TRIP SPI Y
18 765kV STNMB1Q01ICTREF OTI B PH TRIP SPI Y
19 765kV STNMB1Q01ICTREF OTI SPARE ICT TRIP SPI Y
20 765kV STNMB1Q01ICTREF WTI HV R PH TRIP SPI Y
21 765kV STNMB1Q01ICTREF WTI HV Y PH TRIP SPI Y
22 765kV STNMB1Q01ICTREF WTI HV B PH TRIP SPI Y
23 765kV STNMB1Q01ICTREF WTI HV SPARE ICT TRIP SPI Y
24 765kV STNMB1Q01ICTREF WTI MV R PH TRIP SPI Y
Same as Ver 1.1
25 765kV STNMB1Q01ICTREF WTI MV Y PH TRIP SPI Y
26 765kV STNMB1Q01ICTREF WTI MV B PH TRIP SPI Y
27 765kV STNMB1Q01ICTREF WTI MV SPARE ICT TRIP SPI Y
SS_BAY_REF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_REF/MON/SP16GAPC n/Ind n/stVal
28 765kV STNMB1Q01ICTREF WTI IV R PH TRIP SPI Y Applicable for Single Phase Transformers
29 765kV STNMB1Q01ICTREF WTI IV Y PH TRIP SPI Y (If a dedicated IED is provided for spare
30 765kV STNMB1Q01ICTREF WTI IV B PH TRIP SPI Y transformer protection, only spare phase
signals are required to be used)
31 765kV STNMB1Q01ICTREF WTI IV SPARE ICT TRIP SPI Y
32 765kV STNMB1Q01ICTREF BUCCHOLZ R PH ALARM SPI Y
33 765kV STNMB1Q01ICTREF BUCCHOLZ Y PH ALARM SPI Y
34 765kV STNMB1Q01ICTREF BUCCHOLZ B PH ALARM SPI Y
35 765kV STNMB1Q01ICTREF BUCCHOLZ SPARE ICT ALARM SPI Y
36 765kV STNMB1Q01ICTREF OSR 2 R PH TRIP SPI Y
37 765kV STNMB1Q01ICTREF OSR 2 Y PH TRIP SPI Y
38 765kV STNMB1Q01ICTREF OSR 2 B PH TRIP SPI Y
39 765kV STNMB1Q01ICTREF OSR 2 SPARE ICT TRIP SPI Y
40 765kV STNMB1Q01ICTREF PRD 2 R PH TRIP SPI Y
41 765kV STNMB1Q01ICTREF PRD 2 Y PH TRIP SPI Y
42 765kV STNMB1Q01ICTREF PRD 2 B PH TRIP SPI Y
43 765kV STNMB1Q01ICTREF PRD 2 SPARE ICT TRIP SPI Y
44 765kV STNMB1Q01ICTREF DIFFERENTIAL RELAY FAIL SPI Y
Only if the IED subscriber to GOOSE
45 765kV STNMB1Q01ICTREF GOOSE RECEIPT FAIL/TROUBLE SPI Y messgaes as per the scheme

ANY ADDITIONAL SIGNAL AS PER SCHEME

REQUIRED SIGNALS FOR HV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS (765kV ICT BAY)
IED name: R_REL670_HVBUP IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 765kV STNMB1Q01ICTHBU DIRECTIONAL OVERCURRENT START SPI SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SS_BAY_HV BACKUP OC EF/OC4_1/PH3PTRC1/Str/general SS_BAY_HV BACKUP OC EF/OC4_1/PH3PTRC1/Str/general
2 765kV STNMB1Q01ICTHBU DIRECTIONAL OVERCURRENT TRIP SPI Y SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Op/general SS_BAY_HV BACKUP OC EF/OC4_1/PH3PTRC1/Op/general SS_BAY_HV BACKUP OC EF/OC4_1/PH3PTRC1/Op/general
3 765kV STNMB1Q01ICTHBU DIRECTIONAL EARTHFAULT START SPI SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTRC1/Str/general SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTRC1/Str/general
4 765kV STNMB1Q01ICTHBU DIRECTIONAL EARTHFAULT TRIP SPI Y SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTRC1/Op/general SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTRC1/Op/general
5 765kV STNMB1Q01ICTHBU PT/CVT FUSE FAIL SPI Y SS_BAY_HV BACKUP OC EF/LD0/SDDRFUF1/Str/general SS_BAY_HV BACKUP OC EF/PROT/FUFSPVC1/FailVCirc/stVal
6 765kV STNMB1Q01ICTHBU GENERAL TRIP SPI Y SS_BAY_HV BACKUP OC EF/LD0/SMPPTRC1/Op/general SS_BAY_HV BACKUP OC EF/CTRL/SMPPTRC1/Op/general
Same as Ver 1.1
7 765kV STNMB1Q01ICTHBU TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_HV BACKUP OC EF/MON/SP16GAPC n/Ind n/stVal
8 765kV STNMB1Q01ICTHBU BACKUP OC/EF IED UNHEALTHY SPI Y SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal
Only if the IED subscriber to GOOSE
9 765kV STNMB1Q01ICTHBU GOOSE RECEIPT FAIL/TROUBLE SPI Y SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_HV BACKUP OC EF/MON/SP16GAPC n/Ind n/stVal messgaes as per the scheme

ANY ADDITIONAL SIGNAL AS PER SCHEME

Page 3 of 9
Doc. No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_765kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR

ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (765kV ICT BAY)

REQUIRED SIGNALS FOR IV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS (765kV ICT BAY)
IED name: R_REL670_IVBUP IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 765kV STNMB1Q01ICTLBU DIRECTIONAL OVERCURRENT START SPI SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SS_BAY_LV BACKUP OC EF/OC4_1/PH3PTRC1/Str/general SS_BAY_LV BACKUP OC EF/OC4_1/PH3PTRC1/Str/general
2 765kV STNMB1Q01ICTLBU DIRECTIONAL OVERCURRENT TRIP SPI Y SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC1/Op/general SS_BAY_LV BACKUP OC EF/OC4_1/PH3PTRC1/Op/general SS_BAY_LV BACKUP OC EF/OC4_1/PH3PTRC1/Op/general
3 765kV STNMB1Q01ICTLBU DIRECTIONAL EARTHFAULT START SPI SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTRC1/Str/general SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTRC1/Str/general
4 765kV STNMB1Q01ICTLBU DIRECTIONAL EARTHFAULT TRIP SPI Y SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTRC1/Op/general SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTRC1/Op/general
5 765kV STNMB1Q01ICTLBU PT/CVT FUSE FAIL SPI Y SS_BAY_LV BACKUP OC EF/LD0/SDDRFUF1/Str/general SS_BAY_LV BACKUP OC EF/PROT/FUFSPVC1/FailVCirc/stVal
6 765kV STNMB1Q01ICTLBU GENERAL TRIP SPI Y SS_BAY_LV BACKUP OC EF/LD0/SMPPTRC1/Op/general SS_BAY_LV BACKUP OC EF/CTRL/SMPPTRC1/Op/general
Same as Ver 1.1
7 765kV STNMB1Q01ICTLBU TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_LV BACKUP OC EF/MON/SP16GAPC n/Ind n/stVal
8 765kV STNMB1Q01ICTLBU LV BACKUP OC/EF IED UNHEALTHY SPI Y SS_BAY_LV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SS_BAY_LV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal
Only if the IED subscriber to GOOSE
9 765kV STNMB1Q01ICTLBU GOOSE RECEIPT FAIL/TROUBLE SPI Y SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_LV BACKUP OC EF/MON/SP16GAPC n/Ind n/stVal messgaes as per the scheme

ANY ADDITIONAL SIGNAL AS PER SCHEME

REQUIRED SIGNALS FOR BAY CONTROL UNIT (765kV ICT BAY)


IED name: R_REC670_BCU IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 765kV STNMB1Q01BNMBCU BCU IN LOCAL/ REMOTE INT SS_BAY_BCU/LD0/QCBAY1/LocSwPos/stVal SS_BAY_BCU/BAY_1/LLN0/Loc/stVal
2 765kV STNMB1Q01BNMBCU CLOSE COMMAND FROM BCU FOR AUTORECLOSE SPI SS_BAY_BCU/LD0/SMBRREC1/Op/general SS_BAY_BCU/CTRL/SMBRREC1/OpCls/general
3 765kV STNMB1Q01BNMBCU BLOCK AUTORECLOSE FUNCTION SPI Y SS_BAY_BCU/LD0/SMBRREC1/BlkRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
4 765kV STNMB1Q01BNMBCU PREPARE 3PH TRIP AUTORECLOSE SPI Y SS_BAY_BCU/LD0/SMBRREC1/Prp3PhOp/stVal SS_BAY_BCU/CTRL/SMBRREC1/TrMod3Ph/stVal
For BCUs having Autoreclose function
765kV STNMB1Q01BNMBCU STATUS 1 AUTORECLOSE FUNCTION READY SS_BAY_BCU/LD0/SMBRREC1/RdyRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal inbuilt
765kV STNMB1Q01BNMBCU STATUS 2 AUTORECLOSE IN PROGRESS Y SS_BAY_BCU/LD0/SMBRREC1/ActRec/stVal SS_BAY_BCU/CTRL/SMBRREC1/ActRec/stVal
5 SPI
765kV STNMB1Q01BNMBCU STATUS 3 AUTORECLOSE SUCCESSFUL Y SS_BAY_BCU/LD0/SMBRREC1/SucRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
765kV STNMB1Q01BNMBCU STATUS 10 AUTORECLOSE UNSUCCESSFUL Y SS_BAY_BCU/LD0/SMBRREC1/UnsRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
6 765kV STNMB1Q01BNMBCU BAY_CB R PH POSITION DPI SS_BAY_BCU/LD0/SXCBR1/Pos/stVal SS_BAY_BCU/CTRL/SXCBR1/Pos/stVal
7 765kV STNMB1Q01BNMBCU BAY_CB Y PH POSITION DPI SS_BAY_BCU/LD0/SXCBR2/Pos/stVal SS_BAY_BCU/CTRL/SXCBR2/Pos/stVal
8 765kV STNMB1Q01BNMBCU BAY_CB B PH POSITION DPI SS_BAY_BCU/LD0/SXCBR3/Pos/stVal SS_BAY_BCU/CTRL/SXCBR3/Pos/stVal
9 765kV STNMB1Q01BNMBCU BAY_CB POSITION DPI SS_BAY_BCU/LD0/SCSWI1/Pos/stVal SS_BAY_BCU/CTRL/SCSWI1/Pos/stVal
SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI1/Pos/ctlOperOff for Open
10 765kV STNMB1Q01BNMBCU BAY_CB_COMMAND CMD
SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI1/Pos/ctlOperOn for Close
11 765kV STNMB1Q01BNMBCU BAY_CB_OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO1/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO1/EnaOpn/stVal
12 765kV STNMB1Q01BNMBCU BAY_CB_CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO1/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO1/EnaCls/stVal
13 765kV STNMB1Q01BNMBCU BAY_89A_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI2/Pos/stVal SS_BAY_BCU/CTRL/SCSWI2/Pos/stVal
SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI2/Pos/ctlOperOff for Open
14 765kV STNMB1Q01BNMBCU BAY_89A_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI2/Pos/ctlOperOn for Close
15 765kV STNMB1Q01BNMBCU BAY_89A_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO2/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO2/EnaOpn/stVal
16 765kV STNMB1Q01BNMBCU BAY_89A_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO2/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO2/EnaCls/stVal
17 765kV STNMB1Q01BNMBCU BAY_89AE/AE1_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI3/Pos/stVal SS_BAY_BCU/CTRL/SCSWI3/Pos/stVal
SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI3/Pos/ctlOperOff for Open
18 765kV STNMB1Q01BNMBCU BAY_89AE/AE1_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI3/Pos/ctlOperOn for Close
19 765kV STNMB1Q01BNMBCU BAY_89AE/AE1_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO3/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO3/EnaOpn/stVal
20 765kV STNMB1Q01BNMBCU BAY_89AE/AE1_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO3/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO3/EnaCls/stVal
21 765kV STNMB1Q01BNMBCU BAY_89B_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI4/Pos/stVal SS_BAY_BCU/CTRL/SCSWI4/Pos/stVal
SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI4/Pos/ctlOperOff for Open
22 765kV STNMB1Q01BNMBCU BAY_89B_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI4/Pos/ctlOperOn for Close
23 765kV STNMB1Q01BNMBCU BAY_89B_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO4/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO4/EnaOpn/stVal
24 765kV STNMB1Q01BNMBCU BAY_89B_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO4/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO4/EnaCls/stVal
25 765kV STNMB1Q01BNMBCU BAY_89BE/BE1_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI5/Pos/stVal SS_BAY_BCU/CTRL/SCSWI5/Pos/stVal
SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI5/Pos/ctlOperOff for Open
26 765kV STNMB1Q01BNMBCU BAY_89BE/BE1_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI5/Pos/ctlOperOn for Close
27 765kV STNMB1Q01BNMBCU BAY_89BE/BE1_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO5/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO5/EnaOpn/stVal
28 765kV STNMB1Q01BNMBCU BAY_89BE/BE1_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO5/EnaCls/stVal Same as Ver 1.1 SS_BAY_BCU/CTRL/SCILO5/EnaCls/stVal
29 765kV STNMB1Q01BNMBCU BAY_89L/T/BR_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI6/Pos/stVal SS_BAY_BCU/CTRL/SCSWI6/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI6/Pos/ctlOperOff for Open
30 765kV STNMB1Q01BNMBCU BAY_89L/T/BR_ISO COMMAND CMD CSWI6 may be used for 89T/BR, but for
SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI6/Pos/ctlOperOn for Close
Single phase Transformers & Reactors
31 765kV STNMB1Q01BNMBCU BAY_89L/T/BR_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO6/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO6/EnaOpn/stVal same has been seperately mentioned
32 765kV STNMB1Q01BNMBCU BAY_89L/T/BR_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO6/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO6/EnaCls/stVal
33 765kV STNMB1Q01BNMBCU BAY_89LE/TE/BRE_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI7/Pos/stVal SS_BAY_BCU/CTRL/SCSWI7/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI7/Pos/ctlOperOff for Open
34 765kV STNMB1Q01BNMBCU BAY_89LE/TE/BRE_ISO COMMAND CMD CSWI7 may be used for 89TE/BRE, but for
SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI7/Pos/ctlOperOn for Close
Single phase Transformers & Reactors
35 765kV STNMB1Q01BNMBCU BAY_89LE/TE/BRE_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO7/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO7/EnaOpn/stVal same has been seperately mentioned
36 765kV STNMB1Q01BNMBCU BAY_89LE/TE/BRE_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO7/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO7/EnaCls/stVal
37 765kV STNMB1Q01BNMBCU BAY_89LR/89C_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI8/Pos/stVal SS_BAY_BCU/CTRL/SCSWI8/Pos/stVal
For Three phase Line Reactors CSWI8 may
SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI8/Pos/ctlOperOff for Open
38 765kV STNMB1Q01BNMBCU BAY_89LR/89C_ISO COMMAND CMD be used for 89LR, but for Single phase Line
SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI8/Pos/ctlOperOn for Close
Reactors same has been seperately
39 765kV STNMB1Q01BNMBCU BAY_89LR/89C_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO8/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO8/EnaOpn/stVal mentioned
40 765kV STNMB1Q01BNMBCU BAY_89LR/89C_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO8/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO8/EnaCls/stVal
41 765kV STNMB1Q01BNMBCU BAY_89LRE_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI9/Pos/stVal SS_BAY_BCU/CTRL/SCSWI9/Pos/stVal
For Three phase Line Reactors CSWI9 may
SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI9/Pos/ctlOperOff for Open
42 765kV STNMB1Q01BNMBCU BAY_89LRE_ISO COMMAND CMD be used for 89LRE, but for Single phase
SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI9/Pos/ctlOperOn for Close
Line Reactors same has been seperately

Page 4 of 9
Doc. No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_765kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR

ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (765kV ICT BAY)
Line Reactors same has been seperately
43 765kV STNMB1Q01BNMBCU BAY_89LRE_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO9/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO9/EnaOpn/stVal mentioned
44 765kV STNMB1Q01BNMBCU BAY_89LRE_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO9/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO9/EnaCls/stVal
45 765kV STNMB1Q01BNMBCU BAY_89BRS1&2_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI10/Pos/stVal SS_BAY_BCU/CTRL/SCSWI10/Pos/stVal
For Three phase BUS & Line Reactors
SS_BAY_BCU/LD0/SCSWI10Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI10/Pos/ctlOperOff for Open
46 765kV STNMB1Q01BNMBCU BAY_89BRS1&2_ISO COMMAND CMD CSWI10 may be used for 89BRS1&2, but
SS_BAY_BCU/LD0/SCSWI10/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI10/Pos/ctlOperOn for Close
for Single phase Transformers same has
47 765kV STNMB1Q01BNMBCU BAY_89BRS1&2_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO10/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO10/EnaOpn/stVal been seperately mentioned
48 765kV STNMB1Q01BNMBCU BAY_89BRS1&2_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO10/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO10/EnaCls/stVal
49 765kV STNMB1Q01BNMBCU BAY_89BRS1E_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI11/Pos/stVal SS_BAY_BCU/CTRL/SCSWI11/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI11/Pos/ctlOperOff for Open
50 765kV STNMB1Q01BNMBCU BAY_89BRS1E_ISO COMMAND CMD CSWI11 may be used for 89BRS1E, but for
SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI11/Pos/ctlOperOn for Close
Single phase Transformers same has been
51 765kV STNMB1Q01BNMBCU BAY_89BRS1E_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO11/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO11/EnaOpn/stVal separately mentioned
52 765kV STNMB1Q01BNMBCU BAY_89BRS1E_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO11/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO11/EnaCls/stVal
53 765kV STNMB1Q01BNMBCU BAY_89AE2/BE2_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI12/Pos/stVal SS_BAY_BCU/CTRL/SCSWI12/Pos/stVal
SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI12/Pos/ctlOperOff for Open
54 765kV STNMB1Q01BNMBCU BAY_89AE2/BE2_ISO COMMAND CMD Used for BUS Earth switch of Isolator, when
SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI12/Pos/ctlOperOn for Close
Bus Earth Switch (89AE2/BE2) is provided
55 765kV STNMB1Q01BNMBCU BAY_89AE2/BE2_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO12/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO12/EnaOpn/stVal
56 765kV STNMB1Q01BNMBCU BAY_89AE2/BE2_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO12/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO12/EnaCls/stVal

The Logical node instance number (SCSWIn/SCILOn) for BUS Earth Switches, Isolator & Earthswitches for Three phase/Single phase Reactors & ITCs, e.g 89 BR, BRE, LR, LRE, RS1, RS2, RS1E, 89T,TE, 89AE2, 89BE2 may be assigned as per availability

57 765kV STNMB1Q01BNMBCU TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
Same as Ver 1.1
58 765kV STNMB1Q01BNMBCU BCU UNHEALTHY SPI Y SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal
SPI SS_BAY_BCU/SES_1/SESRSYN2/Rel/stVal SS_BAY_BCU/SES_1/SYNRSYN3/Rel/stVal SS_BAY_BCU/SYN_1/MAN1RSYN1/Rel/stVal
59 765kV STNMB1Q01BNMBCU CONDITIONS OK FOR SYNCHRONIZATION
SPI SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal Applicable for One and Half Circuit Breaker
60 765kV STNMB1Q01BNMBCU SPRING DISCHARGED SPI Y
For Spring Mechanism CBs
61 765kV STNMB1Q01BNMBCU AC MOTOR SUPPLY FAIL SPI Y
62 765kV STNMB1Q01BNMBCU SF6 GAS LOW SPI Y
63 765kV STNMB1Q01BNMBCU OPERATION LOCKED OUT SPI Y
64 765kV STNMB1Q01BNMBCU CB READY FOR AUTORECLOSURE SPI Y
65 765kV STNMB1Q01BNMBCU DC SUPPLY FAIL SPI Y
Annunciation for
66 765kV STNMB1Q01BNMBCU TC-1 FAIL SPI Y Circuit Breaker
67 765kV STNMB1Q01BNMBCU TC-2 FAIL SPI Y
68 765kV STNMB1Q01BNMBCU POLE DISCREPANCY RELAY OPTD SPI Y
69 765kV STNMB1Q01BNMBCU COMPRESSOR SUPPLY FAIL SPI Y Same as Ver 1.1
SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
70 765kV STNMB1Q01BNMBCU AIR PRESSURE LOW SPI Y For Hydraullic Mechanism CBs
71 765kV STNMB1Q01BNMBCU COMPRESSOR RUN TIME SUPERVISION SPI Y
72 765kV STNMB1Q01BNMBCU CSD FAIL SPI Y
73 765kV STNMB1Q01BNMBCU GAS COMPARTMENT n Alarm Stage n SPI Y Stage 1 to n as per scheme
74 765kV STNMB1Q01BNMBCU LCC PANEL AC SUPPLY FAIL SPI Y Annunciation for
75 765kV STNMB1Q01BNMBCU LCC PANEL DC SUPPLY FAIL SPI Y GIS bays
76 765kV STNMB1Q01BNMBCU SELECTOR SWITCH POSITION LOCAL/REMOTE SPI Y
77 765kV STNMB1Q01BNMBCU BUS VT MCB TRIP SPI Y For BCUs having BUS VT input
Only if the IED subscriber to GOOSE
78 765kV STNMB1Q01BNMBCU GOOSE RECEIPT FAIL/TROUBLE SPI Y messgaes as per the scheme

ANY ADDITIONAL SIGNAL AS PER SCHEME

NOTE 1: The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified.

NOTE 2: If the logical nodes have been made more specific under the same logical node class by adding prefixes (n), same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High
Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.

NOTE 3: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.

NOTE 4: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…

NOTE 5: The characters "BNM" stand for Bay Name, this will be vary based on Bay name eg. L for LINE, BR for BUSREACTOR, LR for LINEREACTOR, TIE for TIE & ICT fo ICT bay.

NOTE 6: Network Name shall be provided by M/S. NR in line with naming philosophy implemented in the existing M/S. NR SAS System.

Page 5 of 9
Doc. No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_400kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR

ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (400kV LINE / 400kV TIE / 400kV ICT)

REQUIRED SIGNALS FOR DISTANCE RELAYS (400kV LINE)


IED name: R_REL670_21M1 IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED NAME in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 400kV STNMC1Q01LM1DIS OVERVOLATGE STAGE 1 START SPI SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Str/general SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Str/general
2 400kV STNMC1Q01LM1DIS OVERVOLATGE STAGE 1 TRIP SPI Y SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Op/general SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV1/Op/general
3 400kV STNMC1Q01LM1DIS OVERVOLATGE STAGE 2 TRIP SPI Y SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV2/Op/general SS_BAY_M1_DISTANCE/OV2_1/OV2PTOV2/Op/general
4 400kV STNMC1Q01LM1DIS DEF START SPI SS_BAY_M1_DISTANCE/EF4_1/EF4PTRC1/Str/general Same as Ver 1.1 SS_BAY_M1_DISTANCE/EF4_1/EF4PTRC1/Str/general
5 400kV STNMC1Q01LM1DIS DEF TRIP SPI Y SS_BAY_M1_DISTANCE/EF4_1/EF4PTRC1/Op/general SS_BAY_M1_DISTANCE/EF4_1/EF4PTRC1/Op/general Applicable for One and Half CB Busbar
6 400kV STNMC1Q01LM1DIS STUB PROTECTION OPERATED SPI Y SS_BAY_M1_DISTANCE/LD0/STBPTOC1/Op/general SS_BAY_M1_DISTANCE/PROT/STBPTOC1/Op/general system
7 400kV STNMC1Q01LM1DIS SOTF OPERATED SPI Y SS_BAY_M1_DISTANCE/LD0/ZCVPSOF1/Op/general SS_BAY_M1_DISTANCE/PROT/ZCVPSOF1/Op/general
8 400kV STNMC1Q01LM1DIS START, Z1 SPI SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS1/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS1/Str/general
9 400kV STNMC1Q01LM1DIS START, Z2 SPI SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS2/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS2/Str/general
10 400kV STNMC1Q01LM1DIS START, Z2 R PH SPI SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsA SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
11 400kV STNMC1Q01LM1DIS START, Z2 Y PH SPI SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsB SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
12 400kV STNMC1Q01LM1DIS START, Z2 B PH SPI SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Str/phsC SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
13 400kV STNMC1Q01LM1DIS START, Z3 SPI SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS3/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS3/Str/general
14 400kV STNMC1Q01LM1DIS START, Z4 SPI SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS4/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS4/Str/general
15 400kV STNMC1Q01LM1DIS START, Z5 SPI SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS5/Str/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS5/Str/general
16 400kV STNMC1Q01LM1DIS GENERAL TRIP, Z1 SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS1/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS1/Op/general
17 400kV STNMC1Q01LM1DIS TRIP, Z1 R PH SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsA SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
18 400kV STNMC1Q01LM1DIS TRIP, Z1 Y PH SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsB SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
19 400kV STNMC1Q01LM1DIS TRIP, Z1 B PH SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCPDIS1/Op/phsC SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
20 400kV STNMC1Q01LM1DIS GENERAL TRIP, Z2 SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS2/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS2/Op/general
21 400kV STNMC1Q01LM1DIS TRIP, Z2 R PH SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsA SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
22 400kV STNMC1Q01LM1DIS TRIP, Z2 Y PH SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsB SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
23 400kV STNMC1Q01LM1DIS TRIP, Z2 B PH SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS2/Op/phsC SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
24 400kV STNMC1Q01LM1DIS GENERAL TRIP, Z3 SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS3/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS3/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS3/Op/general
25 400kV STNMC1Q01LM1DIS GENERAL TRIP, Z4 SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS4/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS4/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS4/Op/general
26 400kV STNMC1Q01LM1DIS GENERAL TRIP, Z5 SPI Y SS_BAY_M1_DISTANCE/LD0/ZMCAPDIS5/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS5/Op/general SS_BAY_M1_DISTANCE/ZMFC_1/ZMFPDIS5/Op/general
27 400kV STNMC1Q01LM1DIS CARRIER SEND SPI Y SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProTx/stVal SS_BAY_M1_DISTANCE/PROT/ZCPSCH1/Tx/stVal
28 400kV STNMC1Q01LM1DIS CARRIER RECEIVE SPI Y SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/ProRx/stVal SS_BAY_M1_DISTANCE/PROT/ZCPSCH1/Rx/stVal
29 400kV STNMC1Q01LM1DIS CARRIER AIDED SCHEME OPERATED SPI Y SS_BAY_M1_DISTANCE/LD0/ZCPSCH1/Op/general SS_BAY_M1_DISTANCE/PROT/ZCPSCH1/Op/general
30 400kV STNMC1Q01LM1DIS POWER SWING DETECTED SPI Y SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/Str/general SS_BAY_M1_DISTANCE/PROT/ZMRPSB1/Str/general
31 400kV STNMC1Q01LM1DIS POWER SWING BLOCKING SPI Y SS_BAY_M1_DISTANCE/LD0/ZMRPSB1/BlkZn/stVal SS_BAY_M1_DISTANCE/PROT/ZMRPSB1/BlkZn/stVal
32 400kV STNMC1Q01LM1DIS DISTANCE RELAY GENERAL TRIP SPI Y SS_BAY_M1_DISTANCE/LD0/SMPPTRC1/Op/general SS_BAY_M1_DISTANCE/CTRL/SMPPTRC1/Op/general
33 400kV STNMC1Q01LM1DIS FAULT LOCATOR DISTANCE DINT SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltDiskm/mag SS_BAY_M1_DISTANCE/MON/LMBRFLO1/FltDiskm/mag
34 400kV STNMC1Q01LM1DIS FAULT LOCATOR IMPEDANCE DINT SS_BAY_M1_DISTANCE/LD0/LMBRFLO1/FltZ/cVal.mag SS_BAY_M1_DISTANCE/MON/LMBRFLO1/FltZ/cVal/mag
35 400kV STNMC1Q01LM1DIS CVT FUSE FAIL SPI Y SS_BAY_M1_DISTANCE/LD0/SDDRFUF1/Str/general SS_BAY_M1_DISTANCE/PROT/FUFSPVC1/FailVCirc/stVal
36 400kV STNMC1Q01LM1DIS BROKEN CONDUCTOR ALARM SPI Y SS_BAY_M1_DISTANCE/LD0/BRCPTOC1/Op/general SS_BAY_M1_DISTANCE/PROT/BRCPTOC1/Op/general
37 400kV STNMC1Q01LM1DIS TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
38 400kV STNMC1Q01LM1DIS M1 IED UNHEALTHY SPI Y SS_BAY_M1_DISTANCE/LD0/LPHD1/PhyHealth/stVal SS_BAY_M1_DISTANCE/LD0/LPHD1/PhyHealth/stVal
39 400kV STNMC1Q01LM1DIS START AR SPI
40 400kV STNMC1Q01LM1DIS BLOCK AR SPI Applicable for One and Half CB Busbar
41 400kV STNMC1Q01LM1DIS LINE ISOLATOR OPEN FOR STUB ACTIVATION SPI system
42 400kV STNMC1Q01LM1DIS DT SEND CH 1 SPI Y
43 400kV STNMC1Q01LM1DIS DT SEND CH 2 SPI Y
Same as Ver 1.1
44 400kV STNMC1Q01LM1DIS DT RECEIVE CH 1 SPI Y
45 400kV STNMC1Q01LM1DIS DT RECEIVE CH 2 SPI Y
46 400kV STNMC1Q01LM1DIS TRIP RELAY 86 A HEALTHY (SUPERVISION) SPI Y
47 400kV STNMC1Q01LM1DIS TRIP RELAY 86 B HEALTHY (SUPERVISION) SPI Y
48 400kV STNMC1Q01LM1DIS GR A RELAY OPERATED SPI Y
49 400kV STNMC1Q01LM1DIS GR B RELAY OPERATED SPI Y
SS_BAY_M1_DISTANCE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_M1_DISTANCE/MON/SP16GAPC n/Ind n/stVal
50 400kV STNMC1Q01LM1DIS CARRIER RECEIVE CH-1 SPI Y
51 400kV STNMC1Q01LM1DIS CARRIER RECEIVE CH-2 SPI Y
52 400kV STNMC1Q01LM1DIS CARRIER CHANNEL 1 OUT OF SERVICE SPI Y
53 400kV STNMC1Q01LM1DIS CARRIER CHANNEL 2 OUT OF SERVICE SPI Y
54 400kV STNMC1Q01LM1DIS CARRIER CHANNEL 1 FAIL SPI Y
55 400kV STNMC1Q01LM1DIS CARRIER CHANNEL 2 FAIL SPI Y
56 400kV STNMC1Q01LM1DIS MAIN 2/1 RELAY FAIL SPI Y
57 400kV STNMC1Q01LM1DIS SOTF INITIATION SPI Y
58 400kV STNMC1Q01LM1DIS BCU RELAY FAIL SPI Y
Only if the IED subscriber to GOOSE
59 400kV STNMC1Q01LM1DIS GOOSE RECEIPT FAIL/TROUBLE SPI Y messgaes as per the scheme

ANY ADDITIONAL SIGNAL AS PER SCHEME

Page 6 of 9
Doc. No.- 1MNS500836-SIOL
© 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_400kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR

ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (400kV LINE / 400kV TIE / 400kV ICT)

REQUIRED SIGNALS FOR BREAKER FAILURE PROTECTION RELAY PROTECTION RELAY (400kV TIE)
R_RELAY
IED name: NAME_50BFR IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 400kV STNMC1Q01BFR BREAKER FAILURE PROTECTION START SPI Y SS_BAY_BREAKER FAILURE/LD0/GGIO n/ST/ Ind n SS_BAY_BREAKER FAILURE/MON/SP16GAPC n/Ind n/stVal
2 400kV STNMC1Q01BFR BREAKER FAILURE TRIP SPI Y SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpEx/general SS_BAY_BREAKER FAILURE/PROT/CCRBRF n/OpEx/general CCRBRF-Three Phase & CCSRBRF -
3 400kV STNMC1Q01BFR BREAKER FAILURE RETRIP SPI Y SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/general SS_BAY_BREAKER FAILURE/PROT/CCRBRF n/OpIn/general Single Phase Variant
4 400kV STNMC1Q01BFR TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal Same as Ver 1.1 SS_BAY_BREAKER FAILURE/MON/SP16GAPC n/Ind n/stVal Only If standalone Breaker Failure is used
5 400kV STNMC1Q01BFR BFP IED UNHEALTHY SPI Y SS_BAY_BREAKER FAILURE/LD0/LPHD1/PhyHealth/stVal SS_BAY_BREAKER FAILURE/LD0/LPHD1/PhyHealth/stVal
Only if the IED subscriber to GOOSE
6 400kV STNMC1Q01BFR GOOSE RECEIPT FAIL/TROUBLE SPI Y SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BREAKER FAILURE/MON/SP16GAPC n/Ind n/stVal messgaes as per the scheme

ANY ADDITIONAL SIGNAL AS PER SCHEME

REQUIRED SIGNALS FOR BAY CONTROL UNIT (400kV LINE / 400kV TIE / 400kV ICT)
IED name: R_REC670_BCU IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 400kV STNMC1Q01BNMBCU BCU IN LOCAL/ REMOTE INT SS_BAY_BCU/LD0/QCBAY1/LocSwPos/stVal SS_BAY_BCU/BAY_1/LLN0/Loc/stVal
2 400kV STNMC1Q01BNMBCU CLOSE COMMAND FROM BCU FOR AUTORECLOSE SPI SS_BAY_BCU/LD0/SMBRREC1/Op/general SS_BAY_BCU/CTRL/SMBRREC1/OpCls/general
3 400kV STNMC1Q01BNMBCU BLOCK AUTORECLOSE FUNCTION SPI Y SS_BAY_BCU/LD0/SMBRREC1/BlkRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
4 400kV STNMC1Q01BNMBCU PREPARE 3PH TRIP AUTORECLOSE SPI Y SS_BAY_BCU/LD0/SMBRREC1/Prp3PhOp/stVal SS_BAY_BCU/CTRL/SMBRREC1/TrMod3Ph/stVal
For BCUs having Autoreclose function
400kV STNMC1Q01BNMBCU STATUS 1 AUTORECLOSE FUNCTION READY SS_BAY_BCU/LD0/SMBRREC1/RdyRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal inbuilt
400kV STNMC1Q01BNMBCU STATUS 2 AUTORECLOSE IN PROGRESS Y SS_BAY_BCU/LD0/SMBRREC1/ActRec/stVal SS_BAY_BCU/CTRL/SMBRREC1/ActRec/stVal
5 SPI
400kV STNMC1Q01BNMBCU STATUS 3 AUTORECLOSE SUCCESSFUL Y SS_BAY_BCU/LD0/SMBRREC1/SucRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
400kV STNMC1Q01BNMBCU STATUS 10 AUTORECLOSE UNSUCCESSFUL Y SS_BAY_BCU/LD0/SMBRREC1/UnsRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
6 400kV STNMC1Q01BNMBCU BAY_CB R PH POSITION DPI SS_BAY_BCU/LD0/SXCBR1/Pos/stVal SS_BAY_BCU/CTRL/SXCBR1/Pos/stVal
7 400kV STNMC1Q01BNMBCU BAY_CB Y PH POSITION DPI SS_BAY_BCU/LD0/SXCBR2/Pos/stVal SS_BAY_BCU/CTRL/SXCBR2/Pos/stVal
8 400kV STNMC1Q01BNMBCU BAY_CB B PH POSITION DPI SS_BAY_BCU/LD0/SXCBR3/Pos/stVal SS_BAY_BCU/CTRL/SXCBR3/Pos/stVal
9 400kV STNMC1Q01BNMBCU BAY_CB POSITION DPI SS_BAY_BCU/LD0/SCSWI1/Pos/stVal SS_BAY_BCU/CTRL/SCSW I1/Pos/stVal
SS_BAY_BCU/LD0/SCSW I1/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I1/Pos/ctlOperOff for Open
10 400kV STNMC1Q01BNMBCU BAY_CB_COMMAND CMD
SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I1/Pos/ctlOperOn for Close
11 400kV STNMC1Q01BNMBCU BAY_CB_OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO1/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO1/EnaOpn/stVal
12 400kV STNMC1Q01BNMBCU BAY_CB_CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO1/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO1/EnaCls/stVal
13 400kV STNMC1Q01BNMBCU BAY_89A_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI2/Pos/stVal SS_BAY_BCU/CTRL/SCSW I2/Pos/stVal
SS_BAY_BCU/LD0/SCSW I2/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I2/Pos/ctlOperOff for Open
14 400kV STNMC1Q01BNMBCU BAY_89A_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I2/Pos/ctlOperOn for Close
15 400kV STNMC1Q01BNMBCU BAY_89A_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO2/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO2/EnaOpn/stVal
16 400kV STNMC1Q01BNMBCU BAY_89A_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO2/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO2/EnaCls/stVal
17 400kV STNMC1Q01BNMBCU BAY_89AE/AE1_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI3/Pos/stVal SS_BAY_BCU/CTRL/SCSW I3/Pos/stVal
SS_BAY_BCU/LD0/SCSW I3/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I3/Pos/ctlOperOff for Open
18 400kV STNMC1Q01BNMBCU BAY_89AE/AE1_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I3/Pos/ctlOperOn for Close
19 400kV STNMC1Q01BNMBCU BAY_89AE/AE1_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO3/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO3/EnaOpn/stVal
20 400kV STNMC1Q01BNMBCU BAY_89AE/AE1_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO3/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO3/EnaCls/stVal
21 400kV STNMC1Q01BNMBCU BAY_89B_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI4/Pos/stVal SS_BAY_BCU/CTRL/SCSW I4/Pos/stVal
SS_BAY_BCU/LD0/SCSW I4/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I4/Pos/ctlOperOff for Open
22 400kV STNMC1Q01BNMBCU BAY_89B_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I4/Pos/ctlOperOn for Close
23 400kV STNMC1Q01BNMBCU BAY_89B_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO4/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO4/EnaOpn/stVal
24 400kV STNMC1Q01BNMBCU BAY_89B_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO4/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO4/EnaCls/stVal
25 400kV STNMC1Q01BNMBCU BAY_89BE/BE1_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI5/Pos/stVal SS_BAY_BCU/CTRL/SCSW I5/Pos/stVal
SS_BAY_BCU/LD0/SCSW I5/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I5/Pos/ctlOperOff for Open
26 400kV STNMC1Q01BNMBCU BAY_89BE/BE1_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I5/Pos/ctlOperOn for Close
27 400kV STNMC1Q01BNMBCU BAY_89BE/BE1_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO5/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO5/EnaOpn/stVal
28 400kV STNMC1Q01BNMBCU BAY_89BE/BE1_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO5/EnaCls/stVal Same as Ver 1.1 SS_BAY_BCU/CTRL/SCILO5/EnaCls/stVal
29 400kV STNMC1Q01BNMBCU BAY_89L/T/BR_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI6/Pos/stVal SS_BAY_BCU/CTRL/SCSW I6/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSW I6/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I6/Pos/ctlOperOff for Open
30 400kV STNMC1Q01BNMBCU BAY_89L/T/BR_ISO COMMAND CMD CSW I6 may be used for 89T/BR, but for
SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I6/Pos/ctlOperOn for Close
Single phase Transformers & Reactors
31 400kV STNMC1Q01BNMBCU BAY_89L/T/BR_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO6/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO6/EnaOpn/stVal same has been seperately mentioned
32 400kV STNMC1Q01BNMBCU BAY_89L/T/BR_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO6/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO6/EnaCls/stVal
33 400kV STNMC1Q01BNMBCU BAY_89LE/TE/BRE_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI7/Pos/stVal SS_BAY_BCU/CTRL/SCSW I7/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSW I7/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I7/Pos/ctlOperOff for Open
34 400kV STNMC1Q01BNMBCU BAY_89LE/TE/BRE_ISO COMMAND CMD CSW I7 may be used for 89TE/BRE, but for
SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I7/Pos/ctlOperOn for Close
Single phase Transformers & Reactors
35 400kV STNMC1Q01BNMBCU BAY_89LE/TE/BRE_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO7/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO7/EnaOpn/stVal same has been seperately mentioned
36 400kV STNMC1Q01BNMBCU BAY_89LE/TE/BRE_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO7/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO7/EnaCls/stVal
37 400kV STNMC1Q01BNMBCU BAY_89LR/89C_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI8/Pos/stVal SS_BAY_BCU/CTRL/SCSW I8/Pos/stVal
For Three phase Line Reactors CSW I8
SS_BAY_BCU/LD0/SCSW I8/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I8/Pos/ctlOperOff for Open
38 400kV STNMC1Q01BNMBCU BAY_89LR/89C_ISO COMMAND CMD may be used for 89LR, but for Single
SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I8/Pos/ctlOperOn for Close
phase Line Reactors same has been
39 400kV STNMC1Q01BNMBCU BAY_89LR/89C_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO8/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO8/EnaOpn/stVal seperately mentioned
40 400kV STNMC1Q01BNMBCU BAY_89LR/89C_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO8/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO8/EnaCls/stVal
41 400kV STNMC1Q01BNMBCU BAY_89LRE_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI9/Pos/stVal SS_BAY_BCU/CTRL/SCSW I9/Pos/stVal
For Three phase Line Reactors CSW I9
SS_BAY_BCU/LD0/SCSW I9/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I9/Pos/ctlOperOff for Open
42 400kV STNMC1Q01BNMBCU BAY_89LRE_ISO COMMAND CMD may be used for 89LRE, but for Single
SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I9/Pos/ctlOperOn for Close
phase Line Reactors same has been
43 400kV STNMC1Q01BNMBCU BAY_89LRE_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO9/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO9/EnaOpn/stVal seperately mentioned
44 400kV STNMC1Q01BNMBCU BAY_89LRE_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO9/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO9/EnaCls/stVal
45 400kV STNMC1Q01BNMBCU BAY_89BRS1&2_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI10/Pos/stVal SS_BAY_BCU/CTRL/SCSW I10/Pos/stVal
For Three phase BUS & Line Reactors

Page 7 of 9
Doc. No.- 1MNS500836-SIOL
© 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_400kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR

ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (400kV LINE / 400kV TIE / 400kV ICT)

For Three phase BUS & Line Reactors


SS_BAY_BCU/LD0/SCSW I10Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I10/Pos/ctlOperOff for Open
46 400kV STNMC1Q01BNMBCU BAY_89BRS1&2_ISO COMMAND CMD CSWI10 may be used for 89BRS1&2, but
SS_BAY_BCU/LD0/SCSWI10/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I10/Pos/ctlOperOn for Close
for Single phase Transformers same has
47 400kV STNMC1Q01BNMBCU BAY_89BRS1&2_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO10/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO10/EnaOpn/stVal been seperately mentioned
48 400kV STNMC1Q01BNMBCU BAY_89BRS1&2_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO10/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO10/EnaCls/stVal
49 400kV STNMC1Q01BNMBCU BAY_89BRS1E_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI11/Pos/stVal SS_BAY_BCU/CTRL/SCSW I11/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSW I11/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I11/Pos/ctlOperOff for Open
50 400kV STNMC1Q01BNMBCU BAY_89BRS1E_ISO COMMAND CMD CSWI11 may be used for 89BRS1E, but
SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I11/Pos/ctlOperOn for Close
for Single phase Transformers same has
51 400kV STNMC1Q01BNMBCU BAY_89BRS1E_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO11/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO11/EnaOpn/stVal been separately mentioned
52 400kV STNMC1Q01BNMBCU BAY_89BRS1E_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO11/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO11/EnaCls/stVal
53 400kV STNMC1Q01BNMBCU BAY_89AE2/BE2_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI12/Pos/stVal SS_BAY_BCU/CTRL/SCSW I12/Pos/stVal
SS_BAY_BCU/LD0/SCSW I12/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I12/Pos/ctlOperOff for Open Used for BUS Earth switch of Isolator,
54 400kV STNMC1Q01BNMBCU BAY_89AE2/BE2_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I12/Pos/ctlOperOn for Close when Bus Earth Switch (89AE2/BE2) is
55 400kV STNMC1Q01BNMBCU BAY_89AE2/BE2_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO12/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO12/EnaOpn/stVal provided
56 400kV STNMC1Q01BNMBCU BAY_89AE2/BE2_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO12/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO12/EnaCls/stVal

The Logical node instance number (SCSWIn/SCILOn) for BUS Earth Switches, Isolator & Earthswitches for Three phase/Single phase ICTsmay be assigned as per availability

57 400kV STNMC1Q01BNMBCU TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
Same as Ver 1.1
58 400kV STNMC1Q01BNMBCU BCU UNHEALTHY SPI Y SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal
STNMC1Q01BNMBCU SPI SS_BAY_BCU/SES_1/SESRSYN2/Rel/stVal SS_BAY_BCU/SES_1/SYNRSYN3/Rel/stVal SS_BAY_BCU/SYN_1/MAN1RSYN1/Rel/stVal
59 400kV CONDITIONS OK FOR SYNCHRONIZATION
STNMC1Q01BNMBCU SPI SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal Applicable for One and Half Circuit Breaker
60 400kV STNMC1Q01BNMBCU SPRING DISCHARGED SPI Y
For Spring Mechanism CBs
61 400kV STNMC1Q01BNMBCU AC MOTOR SUPPLY FAIL SPI Y
62 400kV STNMC1Q01BNMBCU SF6 GAS LOW SPI Y
63 400kV STNMC1Q01BNMBCU OPERATION LOCKED OUT SPI Y
64 400kV STNMC1Q01BNMBCU CB READY FOR AUTORECLOSURE SPI Y
65 400kV STNMC1Q01BNMBCU DC SUPPLY FAIL SPI Y
Annunciation for
66 400kV STNMC1Q01BNMBCU TC-1 FAIL SPI Y Circuit Breaker
67 400kV STNMC1Q01BNMBCU TC-2 FAIL SPI Y
68 400kV STNMC1Q01BNMBCU POLE DISCREPANCY RELAY OPTD SPI Y
69 400kV STNMC1Q01BNMBCU COMPRESSOR SUPPLY FAIL SPI Y Same as Ver 1.1
SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
70 400kV STNMC1Q01BNMBCU AIR PRESSURE LOW SPI Y For Hydraullic Mechanism CBs
71 400kV STNMC1Q01BNMBCU COMPRESSOR RUN TIME SUPERVISION SPI Y
72 400kV STNMC1Q01BNMBCU CSD FAIL SPI Y
73 400kV STNMC1Q01BNMBCU GAS COMPARTMENT n Alarm Stage n SPI Y Stage 1 to n as per scheme
74 400kV STNMC1Q01BNMBCU LCC PANEL AC SUPPLY FAIL SPI Y Annunciation for
75 400kV STNMC1Q01BNMBCU LCC PANEL DC SUPPLY FAIL SPI Y GIS bays
76 400kV STNMC1Q01BNMBCU SELECTOR SW ITCH POSITION LOCAL/REMOTE SPI Y
77 400kV STNMC1Q01BNMBCU BUS VT MCB TRIP SPI Y For BCUs having BUS VT input
Only if the IED subscriber to GOOSE
78 400kV STNMC1Q01BNMBCU GOOSE RECEIPT FAIL/TROUBLE SPI Y messgaes as per the scheme

ANY ADDITIONAL SIGNAL AS PER SCHEME

NOTE 1: The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified.

NOTE 2: If the logical nodes have been made more specific under the same logical node class by adding prefixes (n), same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1
phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.

NOTE 3: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.

NOTE 4: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…

NOTE 5: The characters "BNM" stand for Bay Name, this will be vary based on Bay name eg. L for LINE, TIE for TIE & ICT fo ICT bay.

NOTE 6: Network Name shall be provided by M/S. NR in line with naming philosophy implemented in the existing M/S. NR SAS System.

Page 8 of 9
Doc. No.- 1MNS500836-SIOL
© 2023 Hitachi Energy. All rights reserved.
Type (SPS=Single/DP
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_400kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. GE_400_P444_21.2 PREPARED BY: SSR

Description Labels / States Description IEC Interface

(IEC: LD;LN)
IEC Address

IEC Address
Single : Text

Single : Text

Attribute;CD
Short Name

Short Name

Short Name

Short Name

Object;Data
at electrical

at electrical

at electrical

at electrical
Long name

Dual : Text

Dual : Text
state = 10

state = 01
(16 char)

(16 char)

(16 char)

(35 char)

(16 char)
Multiple :

Multiple :
state = 1

state = 0

FC;Data
Voltage

Module

Part 2
Part 1
Level

(IEC:
Bay

C)
SPS 400kV R401_P444_21M2 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION CVT FUSE Alarm Normal RS_OP_VT-FUSE System;AlmGGIO1 ST;Alm6;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRKN CND System;AlmGGIO1 ST;Alm31;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind15;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM GROUP A TRIP RELAY Operated Reset RS_OP_GRP-A System;OptGGIO1 ST;Ind4;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CARRIER CHANNEL-1 Healthy Unhealthy RS_set_CARr1 System;OptGGIO1 ST;Ind5;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM LINE ISO OPEN FOR STUB PROTN Set Reset RS_ST_ISO_OE_STU System;OptGGIO1 ST;Ind6;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CB CLOSE CMD SOTF INITIATION Set Reset RS_ST_SOTF System;OptGGIO1 ST;Ind7;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RV_CAR_R_CH2 System;OptGGIO1 ST;Ind8;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM MAIN-2 RELAY Healthy Faulty FL_HL_M2_RLY System;OptGGIO1 ST;Ind9;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RV_CARR CH1 System;OptGGIO1 ST;Ind10;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy RS_set_CARr2 System;OptGGIO1 ST;Ind11;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM DIRECT TRIP RECEIVED CH-1 Received Not Received NR_RV_DT_REV_CH1 System;OptGGIO1 ST;Ind12;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM DIRECT TRIP RECEIVED CH-2 Received Not Received NR_RV_DT_REV_CH2 System;OptGGIO1 ST;Ind13;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM GROUP B TRIP RELAY Operated Reset RS_OP_GRP-B System;OptGGIO1 ST;Ind17;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM TRIP RELAY 86A SUPERVISION Healthy Unhealthy RS_ST_86A SUPV System;OptGGIO1 ST;Ind24;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION POWER SWING DETECTED Set Reset RS_AL_PSB_STR Control;PsbRPSB3 ST;Str;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Control;PsbRPSB3 ST;BlkZn;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Protection;PTRC1 ST;Tr;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-1 R-PH Operated Reset RS_OP_Z1R-PH Protection;DisPDIS1 ST;Op;phsA;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-1 Y-PH Operated Reset RS_OP_Z1Y-PH Protection;DisPDIS1 ST;Op;phsB;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-1 B-PH Operated Reset RS_OP_Z1B-PH Protection;DisPDIS1 ST;Op;phsC;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-1 Operated Reset RS_OP_ZONE-1 Protection;DisPDIS1 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Protection;DisPDIS1 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-2 Operated Reset RS_OP_ZONE-2 Protection;DisPDIS2 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_DIS S Z2_R Protection;DisPDIS2 ST;Str;phsA;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_DIS S Z2_Y Protection;DisPDIS2 ST;Str;phsB;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_DIS S Z2_B Protection;DisPDIS2 ST;Str;phsC;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Protection;DisPDIS2 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-3 Operated Reset RS_OP_ZONE-3 Protection;DisPDIS3 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Protection;DisPDIS3 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-4 Operated Reset RS_OP_ZONE-4 Protection;DisPDIS4 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Protection;DisPDIS4 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-5 Operated Reset RS_OP_ZONE-5 Protection;DisPDIS5 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Protection;DisPDIS5 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Protection;DisPSCH1 ST;CarRx;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Protection;DisPSCH1 ST;ProRx;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Protection;DisPSCH1 ST;ProTx;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Protection;EfdPTOC1 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DEF Protection;EfdPTOC1 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION SOTF Operated Reset RS_OP_SOTF Protection;SofPSOF1 ST;Op;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V-I Protection;VtpPhsPTOV1 ST;Op;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Protection;VtpPhsPTOV1 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V-II Protection;VtpPhsPTOV2 ST;Op;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB System;GosGGIO2 ST;Ind19;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 R-PH Operated Reset RS_OP_DIS Z1 R Protection;DisPDIS2 ST;Op;phsA;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 Y-PH Operated Reset RS_OP_DIS Z1 Y Protection;DisPDIS2 ST;Op;phsB;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 B-PH Operated Reset RS_OP_DIS Z1 B Protection;DisPDIS2 ST;Op;phsC;general;ACT
Z 400kV R401_P444_21M2 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Records;PriRFLO1 MX;FltZ;cVal;CMV
Km 400kV R401_P444_21M2 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Records;PriRFLO1 MX;FltDiskm;mag;MV

Page 9 of 9