IO LIST
We reserve all rights in this document and in the information contained therein. Reproduction use or disclosure to third parties without
express authority is strictly forbidden. Copyright © by Hitachi Energy India Limited.
“Disclaimer – Unauthorized access
The offered solution may be accessed through the customer network and therefore represents a danger which poses a potential threat of
intrusion by unauthorized parties. Therefore, Hitachi Energy India Limited strongly recommends that the customer insures/implements
necessary protection measures against the possibility of such unauthorized access.
Hitachi Energy India Limited disclaims any responsibility and shall under no circumstances be liable for damages or malfunctions caused
by external intrusion of any kind whatsoever."
DOCUMENT IO LIST
CLIENT
CONTRACTOR
Revisions:
Rev. Prep. / Appr. Description Date
0 SSR / PSK First Submission 12/10/2023
SUPPLY OF CRP & SAS FOR 765/400kV BANASKANTHA S/S Extn. SSR PSK 12/10/2023
Hitachi Energy India Limited © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_INDEX REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR
ABB IEDs SCADA GENERAL SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (INDEX)
BAY IED MODEL IED SYMBOLIC NAME APPLICATION IED NAME IN SCD
REC670 R_REC670_BCU Bay Control Unit STNMB1Q01LBCU
LINE REL670 R_REL670_21M1 Main 1 Distance Protection STNMB1Q01LM1DIS
P444** R_RELAY NAME_21M2 Main 2 Distance Protection **
NOTE 1: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 2: The characters "B1" stand for Voltage level, this will be vary based on station voltage level eg. B1 for 765kV, C1 for 400kV & D1 for 220kV etc…
NOTE 3: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…
NOTE 4: ** Line Main2 Distance protection IED name will be subject to provision availability of maximum number of characters in the IED
Page 1 of 9
Doc.No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_765kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR
ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (765kV ICT BAY)
Page 2 of 9
Doc. No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_765kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR
ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (765kV ICT BAY)
REQUIRED SIGNALS FOR HV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS (765kV ICT BAY)
IED name: R_REL670_HVBUP IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 765kV STNMB1Q01ICTHBU DIRECTIONAL OVERCURRENT START SPI SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SS_BAY_HV BACKUP OC EF/OC4_1/PH3PTRC1/Str/general SS_BAY_HV BACKUP OC EF/OC4_1/PH3PTRC1/Str/general
2 765kV STNMB1Q01ICTHBU DIRECTIONAL OVERCURRENT TRIP SPI Y SS_BAY_HV BACKUP OC EF/OC4_1/OC4PTOC1/Op/general SS_BAY_HV BACKUP OC EF/OC4_1/PH3PTRC1/Op/general SS_BAY_HV BACKUP OC EF/OC4_1/PH3PTRC1/Op/general
3 765kV STNMB1Q01ICTHBU DIRECTIONAL EARTHFAULT START SPI SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTRC1/Str/general SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTRC1/Str/general
4 765kV STNMB1Q01ICTHBU DIRECTIONAL EARTHFAULT TRIP SPI Y SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTRC1/Op/general SS_BAY_HV BACKUP OC EF/EF4_1/EF4PTRC1/Op/general
5 765kV STNMB1Q01ICTHBU PT/CVT FUSE FAIL SPI Y SS_BAY_HV BACKUP OC EF/LD0/SDDRFUF1/Str/general SS_BAY_HV BACKUP OC EF/PROT/FUFSPVC1/FailVCirc/stVal
6 765kV STNMB1Q01ICTHBU GENERAL TRIP SPI Y SS_BAY_HV BACKUP OC EF/LD0/SMPPTRC1/Op/general SS_BAY_HV BACKUP OC EF/CTRL/SMPPTRC1/Op/general
Same as Ver 1.1
7 765kV STNMB1Q01ICTHBU TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_HV BACKUP OC EF/MON/SP16GAPC n/Ind n/stVal
8 765kV STNMB1Q01ICTHBU BACKUP OC/EF IED UNHEALTHY SPI Y SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SS_BAY_HV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal
Only if the IED subscriber to GOOSE
9 765kV STNMB1Q01ICTHBU GOOSE RECEIPT FAIL/TROUBLE SPI Y SS_BAY_HV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_HV BACKUP OC EF/MON/SP16GAPC n/Ind n/stVal messgaes as per the scheme
Page 3 of 9
Doc. No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_765kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR
ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (765kV ICT BAY)
REQUIRED SIGNALS FOR IV DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAYS (765kV ICT BAY)
IED name: R_REL670_IVBUP IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 765kV STNMB1Q01ICTLBU DIRECTIONAL OVERCURRENT START SPI SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC1/Str/general SS_BAY_LV BACKUP OC EF/OC4_1/PH3PTRC1/Str/general SS_BAY_LV BACKUP OC EF/OC4_1/PH3PTRC1/Str/general
2 765kV STNMB1Q01ICTLBU DIRECTIONAL OVERCURRENT TRIP SPI Y SS_BAY_LV BACKUP OC EF/OC4_1/OC4PTOC1/Op/general SS_BAY_LV BACKUP OC EF/OC4_1/PH3PTRC1/Op/general SS_BAY_LV BACKUP OC EF/OC4_1/PH3PTRC1/Op/general
3 765kV STNMB1Q01ICTLBU DIRECTIONAL EARTHFAULT START SPI SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTRC1/Str/general SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTRC1/Str/general
4 765kV STNMB1Q01ICTLBU DIRECTIONAL EARTHFAULT TRIP SPI Y SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTRC1/Op/general SS_BAY_LV BACKUP OC EF/EF4_1/EF4PTRC1/Op/general
5 765kV STNMB1Q01ICTLBU PT/CVT FUSE FAIL SPI Y SS_BAY_LV BACKUP OC EF/LD0/SDDRFUF1/Str/general SS_BAY_LV BACKUP OC EF/PROT/FUFSPVC1/FailVCirc/stVal
6 765kV STNMB1Q01ICTLBU GENERAL TRIP SPI Y SS_BAY_LV BACKUP OC EF/LD0/SMPPTRC1/Op/general SS_BAY_LV BACKUP OC EF/CTRL/SMPPTRC1/Op/general
Same as Ver 1.1
7 765kV STNMB1Q01ICTLBU TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_LV BACKUP OC EF/MON/SP16GAPC n/Ind n/stVal
8 765kV STNMB1Q01ICTLBU LV BACKUP OC/EF IED UNHEALTHY SPI Y SS_BAY_LV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal SS_BAY_LV BACKUP OC EF/LD0/LPHD1/PhyHealth/stVal
Only if the IED subscriber to GOOSE
9 765kV STNMB1Q01ICTLBU GOOSE RECEIPT FAIL/TROUBLE SPI Y SS_BAY_LV BACKUP OC EF/LD0/SP16GGIO n/Ind n/stVal SS_BAY_LV BACKUP OC EF/MON/SP16GAPC n/Ind n/stVal messgaes as per the scheme
Page 4 of 9
Doc. No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_765kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR
ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (765kV ICT BAY)
Line Reactors same has been seperately
43 765kV STNMB1Q01BNMBCU BAY_89LRE_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO9/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO9/EnaOpn/stVal mentioned
44 765kV STNMB1Q01BNMBCU BAY_89LRE_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO9/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO9/EnaCls/stVal
45 765kV STNMB1Q01BNMBCU BAY_89BRS1&2_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI10/Pos/stVal SS_BAY_BCU/CTRL/SCSWI10/Pos/stVal
For Three phase BUS & Line Reactors
SS_BAY_BCU/LD0/SCSWI10Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI10/Pos/ctlOperOff for Open
46 765kV STNMB1Q01BNMBCU BAY_89BRS1&2_ISO COMMAND CMD CSWI10 may be used for 89BRS1&2, but
SS_BAY_BCU/LD0/SCSWI10/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI10/Pos/ctlOperOn for Close
for Single phase Transformers same has
47 765kV STNMB1Q01BNMBCU BAY_89BRS1&2_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO10/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO10/EnaOpn/stVal been seperately mentioned
48 765kV STNMB1Q01BNMBCU BAY_89BRS1&2_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO10/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO10/EnaCls/stVal
49 765kV STNMB1Q01BNMBCU BAY_89BRS1E_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI11/Pos/stVal SS_BAY_BCU/CTRL/SCSWI11/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI11/Pos/ctlOperOff for Open
50 765kV STNMB1Q01BNMBCU BAY_89BRS1E_ISO COMMAND CMD CSWI11 may be used for 89BRS1E, but for
SS_BAY_BCU/LD0/SCSWI11/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI11/Pos/ctlOperOn for Close
Single phase Transformers same has been
51 765kV STNMB1Q01BNMBCU BAY_89BRS1E_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO11/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO11/EnaOpn/stVal separately mentioned
52 765kV STNMB1Q01BNMBCU BAY_89BRS1E_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO11/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO11/EnaCls/stVal
53 765kV STNMB1Q01BNMBCU BAY_89AE2/BE2_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI12/Pos/stVal SS_BAY_BCU/CTRL/SCSWI12/Pos/stVal
SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSWI12/Pos/ctlOperOff for Open
54 765kV STNMB1Q01BNMBCU BAY_89AE2/BE2_ISO COMMAND CMD Used for BUS Earth switch of Isolator, when
SS_BAY_BCU/LD0/SCSWI12/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSWI12/Pos/ctlOperOn for Close
Bus Earth Switch (89AE2/BE2) is provided
55 765kV STNMB1Q01BNMBCU BAY_89AE2/BE2_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO12/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO12/EnaOpn/stVal
56 765kV STNMB1Q01BNMBCU BAY_89AE2/BE2_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO12/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO12/EnaCls/stVal
The Logical node instance number (SCSWIn/SCILOn) for BUS Earth Switches, Isolator & Earthswitches for Three phase/Single phase Reactors & ITCs, e.g 89 BR, BRE, LR, LRE, RS1, RS2, RS1E, 89T,TE, 89AE2, 89BE2 may be assigned as per availability
57 765kV STNMB1Q01BNMBCU TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
Same as Ver 1.1
58 765kV STNMB1Q01BNMBCU BCU UNHEALTHY SPI Y SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal
SPI SS_BAY_BCU/SES_1/SESRSYN2/Rel/stVal SS_BAY_BCU/SES_1/SYNRSYN3/Rel/stVal SS_BAY_BCU/SYN_1/MAN1RSYN1/Rel/stVal
59 765kV STNMB1Q01BNMBCU CONDITIONS OK FOR SYNCHRONIZATION
SPI SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal Applicable for One and Half Circuit Breaker
60 765kV STNMB1Q01BNMBCU SPRING DISCHARGED SPI Y
For Spring Mechanism CBs
61 765kV STNMB1Q01BNMBCU AC MOTOR SUPPLY FAIL SPI Y
62 765kV STNMB1Q01BNMBCU SF6 GAS LOW SPI Y
63 765kV STNMB1Q01BNMBCU OPERATION LOCKED OUT SPI Y
64 765kV STNMB1Q01BNMBCU CB READY FOR AUTORECLOSURE SPI Y
65 765kV STNMB1Q01BNMBCU DC SUPPLY FAIL SPI Y
Annunciation for
66 765kV STNMB1Q01BNMBCU TC-1 FAIL SPI Y Circuit Breaker
67 765kV STNMB1Q01BNMBCU TC-2 FAIL SPI Y
68 765kV STNMB1Q01BNMBCU POLE DISCREPANCY RELAY OPTD SPI Y
69 765kV STNMB1Q01BNMBCU COMPRESSOR SUPPLY FAIL SPI Y Same as Ver 1.1
SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
70 765kV STNMB1Q01BNMBCU AIR PRESSURE LOW SPI Y For Hydraullic Mechanism CBs
71 765kV STNMB1Q01BNMBCU COMPRESSOR RUN TIME SUPERVISION SPI Y
72 765kV STNMB1Q01BNMBCU CSD FAIL SPI Y
73 765kV STNMB1Q01BNMBCU GAS COMPARTMENT n Alarm Stage n SPI Y Stage 1 to n as per scheme
74 765kV STNMB1Q01BNMBCU LCC PANEL AC SUPPLY FAIL SPI Y Annunciation for
75 765kV STNMB1Q01BNMBCU LCC PANEL DC SUPPLY FAIL SPI Y GIS bays
76 765kV STNMB1Q01BNMBCU SELECTOR SWITCH POSITION LOCAL/REMOTE SPI Y
77 765kV STNMB1Q01BNMBCU BUS VT MCB TRIP SPI Y For BCUs having BUS VT input
Only if the IED subscriber to GOOSE
78 765kV STNMB1Q01BNMBCU GOOSE RECEIPT FAIL/TROUBLE SPI Y messgaes as per the scheme
NOTE 1: The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified.
NOTE 2: If the logical nodes have been made more specific under the same logical node class by adding prefixes (n), same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1 phase High
Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
NOTE 3: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 4: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…
NOTE 5: The characters "BNM" stand for Bay Name, this will be vary based on Bay name eg. L for LINE, BR for BUSREACTOR, LR for LINEREACTOR, TIE for TIE & ICT fo ICT bay.
NOTE 6: Network Name shall be provided by M/S. NR in line with naming philosophy implemented in the existing M/S. NR SAS System.
Page 5 of 9
Doc. No.- 1MNS500836-SIOL © 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_400kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR
ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (400kV LINE / 400kV TIE / 400kV ICT)
Page 6 of 9
Doc. No.- 1MNS500836-SIOL
© 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_400kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR
ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (400kV LINE / 400kV TIE / 400kV ICT)
REQUIRED SIGNALS FOR BREAKER FAILURE PROTECTION RELAY PROTECTION RELAY (400kV TIE)
R_RELAY
IED name: NAME_50BFR IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 400kV STNMC1Q01BFR BREAKER FAILURE PROTECTION START SPI Y SS_BAY_BREAKER FAILURE/LD0/GGIO n/ST/ Ind n SS_BAY_BREAKER FAILURE/MON/SP16GAPC n/Ind n/stVal
2 400kV STNMC1Q01BFR BREAKER FAILURE TRIP SPI Y SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpEx/general SS_BAY_BREAKER FAILURE/PROT/CCRBRF n/OpEx/general CCRBRF-Three Phase & CCSRBRF -
3 400kV STNMC1Q01BFR BREAKER FAILURE RETRIP SPI Y SS_BAY_BREAKER FAILURE/LD0/CCRBRF1/OpIn/general SS_BAY_BREAKER FAILURE/PROT/CCRBRF n/OpIn/general Single Phase Variant
4 400kV STNMC1Q01BFR TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal Same as Ver 1.1 SS_BAY_BREAKER FAILURE/MON/SP16GAPC n/Ind n/stVal Only If standalone Breaker Failure is used
5 400kV STNMC1Q01BFR BFP IED UNHEALTHY SPI Y SS_BAY_BREAKER FAILURE/LD0/LPHD1/PhyHealth/stVal SS_BAY_BREAKER FAILURE/LD0/LPHD1/PhyHealth/stVal
Only if the IED subscriber to GOOSE
6 400kV STNMC1Q01BFR GOOSE RECEIPT FAIL/TROUBLE SPI Y SS_BAY_BREAKER FAILURE/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BREAKER FAILURE/MON/SP16GAPC n/Ind n/stVal messgaes as per the scheme
REQUIRED SIGNALS FOR BAY CONTROL UNIT (400kV LINE / 400kV TIE / 400kV ICT)
IED name: R_REC670_BCU IEC61850 Edition-1 IEC61850 Edition-2
SL. Voltage WHETHER ALARM ADDITIONAL
NO. Level IED name in SCD EVENT/ALARM NAME TYPE TO BE GENERATED IEC 61850 ADDRESS (REx670 ver 1.1) IEC 61850 ADDRESS (REx670 ver 2.x) IEC 61850 ADDRESS (REx670 ver 2.x) REMARKS REMARKS
1 400kV STNMC1Q01BNMBCU BCU IN LOCAL/ REMOTE INT SS_BAY_BCU/LD0/QCBAY1/LocSwPos/stVal SS_BAY_BCU/BAY_1/LLN0/Loc/stVal
2 400kV STNMC1Q01BNMBCU CLOSE COMMAND FROM BCU FOR AUTORECLOSE SPI SS_BAY_BCU/LD0/SMBRREC1/Op/general SS_BAY_BCU/CTRL/SMBRREC1/OpCls/general
3 400kV STNMC1Q01BNMBCU BLOCK AUTORECLOSE FUNCTION SPI Y SS_BAY_BCU/LD0/SMBRREC1/BlkRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
4 400kV STNMC1Q01BNMBCU PREPARE 3PH TRIP AUTORECLOSE SPI Y SS_BAY_BCU/LD0/SMBRREC1/Prp3PhOp/stVal SS_BAY_BCU/CTRL/SMBRREC1/TrMod3Ph/stVal
For BCUs having Autoreclose function
400kV STNMC1Q01BNMBCU STATUS 1 AUTORECLOSE FUNCTION READY SS_BAY_BCU/LD0/SMBRREC1/RdyRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal inbuilt
400kV STNMC1Q01BNMBCU STATUS 2 AUTORECLOSE IN PROGRESS Y SS_BAY_BCU/LD0/SMBRREC1/ActRec/stVal SS_BAY_BCU/CTRL/SMBRREC1/ActRec/stVal
5 SPI
400kV STNMC1Q01BNMBCU STATUS 3 AUTORECLOSE SUCCESSFUL Y SS_BAY_BCU/LD0/SMBRREC1/SucRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
400kV STNMC1Q01BNMBCU STATUS 10 AUTORECLOSE UNSUCCESSFUL Y SS_BAY_BCU/LD0/SMBRREC1/UnsRec/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
6 400kV STNMC1Q01BNMBCU BAY_CB R PH POSITION DPI SS_BAY_BCU/LD0/SXCBR1/Pos/stVal SS_BAY_BCU/CTRL/SXCBR1/Pos/stVal
7 400kV STNMC1Q01BNMBCU BAY_CB Y PH POSITION DPI SS_BAY_BCU/LD0/SXCBR2/Pos/stVal SS_BAY_BCU/CTRL/SXCBR2/Pos/stVal
8 400kV STNMC1Q01BNMBCU BAY_CB B PH POSITION DPI SS_BAY_BCU/LD0/SXCBR3/Pos/stVal SS_BAY_BCU/CTRL/SXCBR3/Pos/stVal
9 400kV STNMC1Q01BNMBCU BAY_CB POSITION DPI SS_BAY_BCU/LD0/SCSWI1/Pos/stVal SS_BAY_BCU/CTRL/SCSW I1/Pos/stVal
SS_BAY_BCU/LD0/SCSW I1/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I1/Pos/ctlOperOff for Open
10 400kV STNMC1Q01BNMBCU BAY_CB_COMMAND CMD
SS_BAY_BCU/LD0/SCSWI1/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I1/Pos/ctlOperOn for Close
11 400kV STNMC1Q01BNMBCU BAY_CB_OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO1/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO1/EnaOpn/stVal
12 400kV STNMC1Q01BNMBCU BAY_CB_CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO1/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO1/EnaCls/stVal
13 400kV STNMC1Q01BNMBCU BAY_89A_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI2/Pos/stVal SS_BAY_BCU/CTRL/SCSW I2/Pos/stVal
SS_BAY_BCU/LD0/SCSW I2/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I2/Pos/ctlOperOff for Open
14 400kV STNMC1Q01BNMBCU BAY_89A_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI2/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I2/Pos/ctlOperOn for Close
15 400kV STNMC1Q01BNMBCU BAY_89A_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO2/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO2/EnaOpn/stVal
16 400kV STNMC1Q01BNMBCU BAY_89A_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO2/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO2/EnaCls/stVal
17 400kV STNMC1Q01BNMBCU BAY_89AE/AE1_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI3/Pos/stVal SS_BAY_BCU/CTRL/SCSW I3/Pos/stVal
SS_BAY_BCU/LD0/SCSW I3/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I3/Pos/ctlOperOff for Open
18 400kV STNMC1Q01BNMBCU BAY_89AE/AE1_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI3/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I3/Pos/ctlOperOn for Close
19 400kV STNMC1Q01BNMBCU BAY_89AE/AE1_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO3/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO3/EnaOpn/stVal
20 400kV STNMC1Q01BNMBCU BAY_89AE/AE1_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO3/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO3/EnaCls/stVal
21 400kV STNMC1Q01BNMBCU BAY_89B_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI4/Pos/stVal SS_BAY_BCU/CTRL/SCSW I4/Pos/stVal
SS_BAY_BCU/LD0/SCSW I4/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I4/Pos/ctlOperOff for Open
22 400kV STNMC1Q01BNMBCU BAY_89B_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI4/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I4/Pos/ctlOperOn for Close
23 400kV STNMC1Q01BNMBCU BAY_89B_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO4/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO4/EnaOpn/stVal
24 400kV STNMC1Q01BNMBCU BAY_89B_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO4/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO4/EnaCls/stVal
25 400kV STNMC1Q01BNMBCU BAY_89BE/BE1_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI5/Pos/stVal SS_BAY_BCU/CTRL/SCSW I5/Pos/stVal
SS_BAY_BCU/LD0/SCSW I5/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I5/Pos/ctlOperOff for Open
26 400kV STNMC1Q01BNMBCU BAY_89BE/BE1_ISO COMMAND CMD
SS_BAY_BCU/LD0/SCSWI5/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I5/Pos/ctlOperOn for Close
27 400kV STNMC1Q01BNMBCU BAY_89BE/BE1_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO5/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO5/EnaOpn/stVal
28 400kV STNMC1Q01BNMBCU BAY_89BE/BE1_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO5/EnaCls/stVal Same as Ver 1.1 SS_BAY_BCU/CTRL/SCILO5/EnaCls/stVal
29 400kV STNMC1Q01BNMBCU BAY_89L/T/BR_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI6/Pos/stVal SS_BAY_BCU/CTRL/SCSW I6/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSW I6/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I6/Pos/ctlOperOff for Open
30 400kV STNMC1Q01BNMBCU BAY_89L/T/BR_ISO COMMAND CMD CSW I6 may be used for 89T/BR, but for
SS_BAY_BCU/LD0/SCSWI6/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I6/Pos/ctlOperOn for Close
Single phase Transformers & Reactors
31 400kV STNMC1Q01BNMBCU BAY_89L/T/BR_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO6/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO6/EnaOpn/stVal same has been seperately mentioned
32 400kV STNMC1Q01BNMBCU BAY_89L/T/BR_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO6/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO6/EnaCls/stVal
33 400kV STNMC1Q01BNMBCU BAY_89LE/TE/BRE_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI7/Pos/stVal SS_BAY_BCU/CTRL/SCSW I7/Pos/stVal
For Three phase Transformers & Reactors
SS_BAY_BCU/LD0/SCSW I7/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I7/Pos/ctlOperOff for Open
34 400kV STNMC1Q01BNMBCU BAY_89LE/TE/BRE_ISO COMMAND CMD CSW I7 may be used for 89TE/BRE, but for
SS_BAY_BCU/LD0/SCSWI7/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I7/Pos/ctlOperOn for Close
Single phase Transformers & Reactors
35 400kV STNMC1Q01BNMBCU BAY_89LE/TE/BRE_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO7/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO7/EnaOpn/stVal same has been seperately mentioned
36 400kV STNMC1Q01BNMBCU BAY_89LE/TE/BRE_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO7/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO7/EnaCls/stVal
37 400kV STNMC1Q01BNMBCU BAY_89LR/89C_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI8/Pos/stVal SS_BAY_BCU/CTRL/SCSW I8/Pos/stVal
For Three phase Line Reactors CSW I8
SS_BAY_BCU/LD0/SCSW I8/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I8/Pos/ctlOperOff for Open
38 400kV STNMC1Q01BNMBCU BAY_89LR/89C_ISO COMMAND CMD may be used for 89LR, but for Single
SS_BAY_BCU/LD0/SCSWI8/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I8/Pos/ctlOperOn for Close
phase Line Reactors same has been
39 400kV STNMC1Q01BNMBCU BAY_89LR/89C_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO8/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO8/EnaOpn/stVal seperately mentioned
40 400kV STNMC1Q01BNMBCU BAY_89LR/89C_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO8/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO8/EnaCls/stVal
41 400kV STNMC1Q01BNMBCU BAY_89LRE_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI9/Pos/stVal SS_BAY_BCU/CTRL/SCSW I9/Pos/stVal
For Three phase Line Reactors CSW I9
SS_BAY_BCU/LD0/SCSW I9/Pos/ctlOperOff for Open SS_BAY_BCU/CTRL/SCSW I9/Pos/ctlOperOff for Open
42 400kV STNMC1Q01BNMBCU BAY_89LRE_ISO COMMAND CMD may be used for 89LRE, but for Single
SS_BAY_BCU/LD0/SCSWI9/Pos/ctlOperOn for Close SS_BAY_BCU/CTRL/SCSW I9/Pos/ctlOperOn for Close
phase Line Reactors same has been
43 400kV STNMC1Q01BNMBCU BAY_89LRE_ISO OPEN PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO9/EnaOpn/stVal SS_BAY_BCU/CTRL/SCILO9/EnaOpn/stVal seperately mentioned
44 400kV STNMC1Q01BNMBCU BAY_89LRE_ISO CLOSE PERMITTED OR ENABLED SPI SS_BAY_BCU/LD0/SCILO9/EnaCls/stVal SS_BAY_BCU/CTRL/SCILO9/EnaCls/stVal
45 400kV STNMC1Q01BNMBCU BAY_89BRS1&2_ISOLATOR POSITION DPI SS_BAY_BCU/LD0/SCSWI10/Pos/stVal SS_BAY_BCU/CTRL/SCSW I10/Pos/stVal
For Three phase BUS & Line Reactors
Page 7 of 9
Doc. No.- 1MNS500836-SIOL
© 2023 Hitachi Energy. All rights reserved.
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_400kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. PREPARED BY: SSR
ABB IEDs SCADA SIGNAL LIST FOR VARIOUS PROTECTION & CONTROL SIGNALS - REV04 (400kV LINE / 400kV TIE / 400kV ICT)
The Logical node instance number (SCSWIn/SCILOn) for BUS Earth Switches, Isolator & Earthswitches for Three phase/Single phase ICTsmay be assigned as per availability
57 400kV STNMC1Q01BNMBCU TIME SYNCHRONIZATION ERROR SPI Y SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
Same as Ver 1.1
58 400kV STNMC1Q01BNMBCU BCU UNHEALTHY SPI Y SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal SS_BAY_BCU/LD0/LPHD1/PhyHealth/stVal
STNMC1Q01BNMBCU SPI SS_BAY_BCU/SES_1/SESRSYN2/Rel/stVal SS_BAY_BCU/SES_1/SYNRSYN3/Rel/stVal SS_BAY_BCU/SYN_1/MAN1RSYN1/Rel/stVal
59 400kV CONDITIONS OK FOR SYNCHRONIZATION
STNMC1Q01BNMBCU SPI SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal Applicable for One and Half Circuit Breaker
60 400kV STNMC1Q01BNMBCU SPRING DISCHARGED SPI Y
For Spring Mechanism CBs
61 400kV STNMC1Q01BNMBCU AC MOTOR SUPPLY FAIL SPI Y
62 400kV STNMC1Q01BNMBCU SF6 GAS LOW SPI Y
63 400kV STNMC1Q01BNMBCU OPERATION LOCKED OUT SPI Y
64 400kV STNMC1Q01BNMBCU CB READY FOR AUTORECLOSURE SPI Y
65 400kV STNMC1Q01BNMBCU DC SUPPLY FAIL SPI Y
Annunciation for
66 400kV STNMC1Q01BNMBCU TC-1 FAIL SPI Y Circuit Breaker
67 400kV STNMC1Q01BNMBCU TC-2 FAIL SPI Y
68 400kV STNMC1Q01BNMBCU POLE DISCREPANCY RELAY OPTD SPI Y
69 400kV STNMC1Q01BNMBCU COMPRESSOR SUPPLY FAIL SPI Y Same as Ver 1.1
SS_BAY_BCU/LD0/SP16GGIO n/Ind n/stVal SS_BAY_BCU/MON/SP16GAPC n/Ind n/stVal
70 400kV STNMC1Q01BNMBCU AIR PRESSURE LOW SPI Y For Hydraullic Mechanism CBs
71 400kV STNMC1Q01BNMBCU COMPRESSOR RUN TIME SUPERVISION SPI Y
72 400kV STNMC1Q01BNMBCU CSD FAIL SPI Y
73 400kV STNMC1Q01BNMBCU GAS COMPARTMENT n Alarm Stage n SPI Y Stage 1 to n as per scheme
74 400kV STNMC1Q01BNMBCU LCC PANEL AC SUPPLY FAIL SPI Y Annunciation for
75 400kV STNMC1Q01BNMBCU LCC PANEL DC SUPPLY FAIL SPI Y GIS bays
76 400kV STNMC1Q01BNMBCU SELECTOR SW ITCH POSITION LOCAL/REMOTE SPI Y
77 400kV STNMC1Q01BNMBCU BUS VT MCB TRIP SPI Y For BCUs having BUS VT input
Only if the IED subscriber to GOOSE
78 400kV STNMC1Q01BNMBCU GOOSE RECEIPT FAIL/TROUBLE SPI Y messgaes as per the scheme
NOTE 1: The Logical Device LD is for reference only and vendors may use the same as per their own stndardized way, however the logical nodes used are to be used only as specified.
NOTE 2: If the logical nodes have been made more specific under the same logical node class by adding prefixes (n), same can be used as per the application. For example, PDIFF has been specified for all types of differential functions, but if some vendor, under the same logical node class, made the function more specific by adding prefix HZD1PDIFF for 1
phase High Impedance Differential function & T3WPDIFF for 3 winding Low Impedance differential protection, same may be used.
NOTE 3: The characters "STNM" stand for Substation Name with maximum 4 characters, this code will be given by POWERGRID for each project.
NOTE 4: The characters "Q01" stand for Bay Number, this will be vary based on Bay number eg. Q01 for BAY01, Q02 for BAY02 etc…
NOTE 5: The characters "BNM" stand for Bay Name, this will be vary based on Bay name eg. L for LINE, TIE for TIE & ICT fo ICT bay.
NOTE 6: Network Name shall be provided by M/S. NR in line with naming philosophy implemented in the existing M/S. NR SAS System.
Page 8 of 9
Doc. No.- 1MNS500836-SIOL
© 2023 Hitachi Energy. All rights reserved.
Type (SPS=Single/DP
CUSTOMER- POWERGRID CORPORATION OF INDIA LIMITED SIGNAL LIST_400kV (2) REV 04
PROJECT- 765/400kV BANASKANTHA S/S Extn. GE_400_P444_21.2 PREPARED BY: SSR
(IEC: LD;LN)
IEC Address
IEC Address
Single : Text
Single : Text
Attribute;CD
Short Name
Short Name
Short Name
Short Name
Object;Data
at electrical
at electrical
at electrical
at electrical
Long name
Dual : Text
Dual : Text
state = 10
state = 01
(16 char)
(16 char)
(16 char)
(35 char)
(16 char)
Multiple :
Multiple :
state = 1
state = 0
FC;Data
Voltage
Module
Part 2
Part 1
Level
(IEC:
Bay
C)
SPS 400kV R401_P444_21M2 PROTECTION TIME SYNCHRONISATION ERROR Alarm Normal NL_AL_TIME SYNC System;LLN0 ST;SyncSt;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION CVT FUSE Alarm Normal RS_OP_VT-FUSE System;AlmGGIO1 ST;Alm6;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION BROKEN CONDUCTOR Alarm Normal RS_OP_BRKN CND System;AlmGGIO1 ST;Alm31;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION GOOSE RECEIPT FAIL/TROUBLE Alarm Normal NL_AL_GOOSE RECP System;GosGGIO2 ST;Ind15;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM GROUP A TRIP RELAY Operated Reset RS_OP_GRP-A System;OptGGIO1 ST;Ind4;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CARRIER CHANNEL-1 Healthy Unhealthy RS_set_CARr1 System;OptGGIO1 ST;Ind5;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM LINE ISO OPEN FOR STUB PROTN Set Reset RS_ST_ISO_OE_STU System;OptGGIO1 ST;Ind6;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CB CLOSE CMD SOTF INITIATION Set Reset RS_ST_SOTF System;OptGGIO1 ST;Ind7;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CARRIER CHANNEL-2 Received Not Received NR_RV_CAR_R_CH2 System;OptGGIO1 ST;Ind8;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM MAIN-2 RELAY Healthy Faulty FL_HL_M2_RLY System;OptGGIO1 ST;Ind9;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CARRIER CHANNEL-1 Received Not Received NR_RV_CARR CH1 System;OptGGIO1 ST;Ind10;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM CARRIER CHANNEL-2 Healthy Unhealthy RS_set_CARr2 System;OptGGIO1 ST;Ind11;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM DIRECT TRIP RECEIVED CH-1 Received Not Received NR_RV_DT_REV_CH1 System;OptGGIO1 ST;Ind12;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM DIRECT TRIP RECEIVED CH-2 Received Not Received NR_RV_DT_REV_CH2 System;OptGGIO1 ST;Ind13;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM GROUP B TRIP RELAY Operated Reset RS_OP_GRP-B System;OptGGIO1 ST;Ind17;stVal;SPS
SPS 400kV R401_P444_21M2 SYSTEM TRIP RELAY 86A SUPERVISION Healthy Unhealthy RS_ST_86A SUPV System;OptGGIO1 ST;Ind24;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION POWER SWING DETECTED Set Reset RS_AL_PSB_STR Control;PsbRPSB3 ST;Str;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION POWER SWING BLOCKING Set Reset RS_OP_PWR SW BLK Control;PsbRPSB3 ST;BlkZn;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION GENERAL TRIP Operated Reset RS_OP_GEN TRIP Protection;PTRC1 ST;Tr;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-1 R-PH Operated Reset RS_OP_Z1R-PH Protection;DisPDIS1 ST;Op;phsA;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-1 Y-PH Operated Reset RS_OP_Z1Y-PH Protection;DisPDIS1 ST;Op;phsB;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-1 B-PH Operated Reset RS_OP_Z1B-PH Protection;DisPDIS1 ST;Op;phsC;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-1 Operated Reset RS_OP_ZONE-1 Protection;DisPDIS1 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-1 START Set Reset RS_OP_DIS S Z1 Protection;DisPDIS1 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-2 Operated Reset RS_OP_ZONE-2 Protection;DisPDIS2 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 START R-PH Set Reset RS_OP_DIS S Z2_R Protection;DisPDIS2 ST;Str;phsA;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 START Y-PH Set Reset RS_OP_DIS S Z2_Y Protection;DisPDIS2 ST;Str;phsB;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 START B-PH Set Reset RS_OP_DIS S Z2_B Protection;DisPDIS2 ST;Str;phsC;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 START Set Reset RS_OP_DIS S Z2 Protection;DisPDIS2 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-3 Operated Reset RS_OP_ZONE-3 Protection;DisPDIS3 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-3 START Set Reset RS_OP_DIS S Z3 Protection;DisPDIS3 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-4 Operated Reset RS_OP_ZONE-4 Protection;DisPDIS4 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-4 START Set Reset RS_OP_DIS S Z4 Protection;DisPDIS4 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE PROTN ZONE-5 Operated Reset RS_OP_ZONE-5 Protection;DisPDIS5 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-5 START Set Reset RS_OP_DIS S Z5 Protection;DisPDIS5 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION CARRIER AIDED SCHEME Operated Reset RS_ST_CARR_AIDED Protection;DisPSCH1 ST;CarRx;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION CARRIER RECEIVE Set Reset RS_ST_CARR REC Protection;DisPSCH1 ST;ProRx;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION CARRIER SEND Set Reset RS_ST_CARR SEND Protection;DisPSCH1 ST;ProTx;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION DIRECTIONAL E/F START Set Reset RS_OP_DIR E/F S Protection;EfdPTOC1 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION DIRECTIONAL E/F Operated Reset RS_OP_DEF Protection;EfdPTOC1 ST;Op;general;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION SOTF Operated Reset RS_OP_SOTF Protection;SofPSOF1 ST;Op;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION OVERVOLTAGE STAGE-1 Operated Reset RS_OP_O/V-I Protection;VtpPhsPTOV1 ST;Op;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION OVERVOLTAGE STAGE-1 START Set Reset RS_OP_O/V STG1 S Protection;VtpPhsPTOV1 ST;Str;general;general;ACD
SPS 400kV R401_P444_21M2 PROTECTION OVERVOLTAGE STAGE-2 Operated Reset RS_OP_O/V-II Protection;VtpPhsPTOV2 ST;Op;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION STUB PROTECTION Operated Reset RS_OP_STUB System;GosGGIO2 ST;Ind19;stVal;SPS
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 R-PH Operated Reset RS_OP_DIS Z1 R Protection;DisPDIS2 ST;Op;phsA;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 Y-PH Operated Reset RS_OP_DIS Z1 Y Protection;DisPDIS2 ST;Op;phsB;general;ACT
SPS 400kV R401_P444_21M2 PROTECTION DISTANCE ZONE-2 B-PH Operated Reset RS_OP_DIS Z1 B Protection;DisPDIS2 ST;Op;phsC;general;ACT
Z 400kV R401_P444_21M2 PROTECTION FAULT IMPEDANCE -100.0 100.0 Fltz Records;PriRFLO1 MX;FltZ;cVal;CMV
Km 400kV R401_P444_21M2 PROTECTION FAULT DISTANCE 0.0 1000.0 FltDiskm Records;PriRFLO1 MX;FltDiskm;mag;MV
Page 9 of 9