Innovative Software Solutions and Engineering Services

Installation and Configuration Manual

OPC Server
FibroLaser III

Installation and Configuration


Manual

Revision History:

Version Date Status


1.0 Sep 2015 Released.
1.1 Jan 2016 Add button to import/export zone configuration.
1.2 Feb 2016 Change the pre-alarm and fault values. The values of the
alarm, pre-alarm and fault are unique.

Property of S4S - Innovative Software Solutions and Engineering Services

We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges
these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available
to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was
delivered to him.

Innovative software solutions and Engineering IC_OPC Server FibroLaser III - Doc.n° IC-001-015 V1.2
Services Updated Feb 2016. Specifications subject to change without
S4S - Via Vespucci 6 - 20018 - Sedriano (MI) – Italy - VAT 05172500968
Tel. +39 3939505055 - Fax. +39 02 36547223 - Email: [email protected]
notice. Please visit our website for the most up-to-date product
information. www.s4s.it All Rights Reserved.
Innovative Software Solutions and Engineering Services

Table of Contents

1. Glossary ............................................................................................................................................................ 3

2. Introduction .................................................................................................................................................... 3

3. About the OPC Server FibroLaser III ...................................................................................................... 4

4. System Requirements.................................................................................................................................. 5

5. Installation guide .......................................................................................................................................... 6

5.1 Registration of the OPC Server ............................................................................................................ 6

5.2 Authentication and Permissions .......................................................................................................... 7

5.3 Licensing .................................................................................................................................................... 12

5.3.1 How to obtain a license .................................................................................................................. 12

5.3.2 Software license activation ............................................................................................................ 12

6. System Configuration............................................................................................................................... 13

6.1.1 FibroLaser IIII controller (OTS30XX) ............................................................................................ 13

6.1.2 OPC Server ........................................................................................................................................... 15

7. OPC TAGs ...................................................................................................................................................... 24

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .2
Innovative Software Solutions and Engineering Services

1. Glossary
Acronym Description
OPC OLE for Process Control
OLE Object Linking and Embedding
GUI Graphic User Interface
SCADA Supervisory Control And Data Acquisition
FibroLaser III Siemens Linear Heat Detection systems
OTS30xx Siemens Linear Heat Detection Controllers

2. Introduction
This is a User Manual for the OPC Server FibroLaser III . The Server communicates with
FibroLaser III controllers over Ethernet and supports data exchange with Client's via
Microsoft's Object Linking and Embedding (OLE) for Process Control (OPC).
S4S’s OPC Server is a software package that operates as an OPC driver of Siemens
Management stations as MM8000, Desigo CCTM and CerberusTM DMS. The OPC Server meets
the latest standard of OPC DA2.0 that allows connections to various kinds of devices and
host OPC machines.
The manual is organized to provide an overview of OPC technology, detailed information on
the configuration environment and a complete list of OPC Tag’s provided by the OPC
Server.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .3
Innovative Software Solutions and Engineering Services

3. About the OPC Server FibroLaser III


The OPC Server FibroLaser III is based on OPC Data Access, known as 'DA', which provides
real-time data from FibroLaser III controllers to management stations with OPC client drivers
as MM8000, DesigoCCTM and CerberusTM DM.
The server communicates with OTS 30xx via the LON protocol over TCP-IP
Protocol has been designed to be compatible with the previous versions of the OTS public
code protocols.
The OPC Server reads and writes data to and from FibroLaser III controllers via Ethernet.
The Server has a graphical user interface (GUI) configuration environment with an "Explorer"
look and feel. The configuration environment allows the Server to be configured with
information such as controller IP addresses and available global variables so that the Server
can communicate with these systems on behalf of Clients.

Application Name : OPC-FibroLaserIII.exe


OPC NAME : "S4S.OPC-FibroLaser III" (Can be configured in xml file)

OPC DESCRIPTION : "OPC Server – FibroLaser III" (Can be configured in xml file)

OPC GUID : {4DA870F2-A36A-46FF-BD36-A21511B9FF80}

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .4
Innovative Software Solutions and Engineering Services

4. System Requirements
The OPC Server FibroLaser III application runs on any hardware which supports Windows
Server 2003/2008/2012, Windows XP, Windows 7 or Windows 8 with DCOM, Visual C++
2010 Redistributable Packages and .NET Framework 4 Installed.
The system must have 10 Mb of free disk space to install the program and 1 Gb of free
memory is required to load and run the application. All systems information is stored in the
server’s disk. For configuration purpose a monitor connected to the computer is required.
The OPC server is a 32 bit application which runs on both 32/64 bit operating systems.

Hardware characteristics recommended

- CPU i5 high-end (for example INTEL Core i5 4690K) or i7 mid-range (for example
Intel Core i7-4770K)
- RAM : 8GB

Checks on the network

Since the Server communicates with the FibroLaser OTS 30XX over TCP-IP, an Ethernet
network must be in place. The network itself should be fully tested and be known to operate
before attaching the controllers and the Server computers. Contact your system
administrator for assistance or consult instructional documentation and manuals to setting
up the network. It is beyond the scope of this Users Manual to discuss networking topics in
any detail.
Once the network is in place and the Server computers and controllers are attached, check
connectivity using available network testing tools and programs such as ping command.

Note: When the OTS 30XX configuration is modified, a re-start of the LON Protocol is
carried out and a disconnection on communication is detected.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .5
Innovative Software Solutions and Engineering Services

5. Installation guide
Before installation of the OPC server, make sure it is installed the Visual C++ 2010
Redistributable Packages, if not please let install it on your computer.
The OPC Server FibroLaser III is provided with own specific setup. The setup includes all the
dependencies (ex. WtOPCSvr.DLL - OPC server library) in order to ensure the proper
functioning of the application.

 S4S_OPC_Library.dll
 S4SGenCodeInfo.dll
 S4SGenCodeInfoLibrary.dll
 S4SObjectListView.dll
 WtOPCSvr.dll
 SysInfo.dll

Two security issues require attention:

 Installation needs Administrator rights;


 Windows Firewall must be configured;
 DCOM security settings must be configured. This guide describes how to make the
necessary settings.

5.1 Registration of the OPC Server

Image 1 Register and UnRegister

 To register the Server, you must click 'Register' in the menu 'Server'.
 To unregister the OPC Server, you must click 'UnRegister' in the menu 'Server'.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .6
Innovative Software Solutions and Engineering Services

5.2 Authentication and Permissions


After OPC Server registration the COM security has to be enabled, so OPC Client can
automatically call the OPC Server.
Below are showed all steps needed to enable the security COM, using ‘DCOMCNFG1’:
1. Verify that the DCOM security registration was executed successfully;
2. Run DCOMCNFG (Only the administrator can run ‘Dcomcnfg.exe’). To use ‘RUN
Command Windows’ or ‘Command Prompt’ , to open DCOMCNFG program;

Image 2 DCOMCNFG - Run

3. Locate the My Computer item by expanding the following nodes: Component


Services > Computers;
4. Right-click My Computer and select Properties.

Image 3 Component Services Property

1
Dcomcnfg.exe provides a user interface for modifying certain settings in the registry. By using Dcomcnfg.exe, you can
enable security either on a computer-wide or a process-wide basis. You can enable security for a particular computer so that
when a process does not provide its own security settings, either programmatically or through registry values, the values set by
Dcomcnfg.exe will be used. Or you can use Dcomcnfg.exe to enable security for a particular application only.
Note:You must be an administrator to run Dcomcnfg.exe.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .7
Innovative Software Solutions and Engineering Services

5. Go to the COM Security tab. Edit the default settings to Access Permission, hereby
adding ‘ANONYMOUS LOGON’ and ‘Everyone’ and giving all access permissions to
that group of users. Repeat the setup for the limit settings.

Image 4 COM Security Access Permissions

6. Now edit the default settings for Launch and Activation Permissions, hereby adding
‘ANONYMOUS LOGON’ and ‘Everyone‘ and giving all access permissions to that
group of users. Repeat the setup for the limit settings.

Image 5 COM Security Launch and Activation Permissions

The new settings will take effect when the OPC Client has been restarted. Therefore, close
the Component Services (dcomcnfg program) and restart the OPC Client application.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .8
Innovative Software Solutions and Engineering Services

7. Using tree view DCOMCMFG to check the all DCOM registered.

Image 6 DCOMCMFG

Select the 'Component Services' item, than 'Computers', than 'My Computer' and 'DCOM
Config' item;
Find the OPC Server name registered in the DCOM list, it must be the same as configured in
the xml file.

Xml file example:

<OPC_PROTOCOL Delimiter="." OPC_name=”OPC-SERVER" OPC_description="OPC Server - Fibro Laser" …>

OPC Server name is registered: “OPC-Fibro Laser”, for this example the name is
“OPC-SERVER”.

Image 7 DCOMCNFG - Find OPC Server

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .9
Innovative Software Solutions and Engineering Services

8. OPC Server Configuration Permissions. Select the ‘OPC-SERVER’ registration then the
properties (pushing the right button) and then select the ‘security’ tab:

a. Select ‘Customize’ in the 'Configuration Permissions’ and then click the ‘Edit’
button.

Image 8 DCOMCNFG – Configuration Permissions

b. Select ‘Add’ button to add a new user and then, in the new form, select the
‘Advanced’ button.

c. Click the ‘Find’ button to search the ‘everyone’ and then ‘ANONYMOUS
LOGON ‘ users.

Image 9 DCOMCNFG – Find User

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .10
Innovative Software Solutions and Engineering Services

d. Add ‘everyone’ and ‘ANONYMOUS LOGON ‘ user;

Image 10 DCOMCNFG - Add users

e. Provide all permission to added users.

9. Set OPC Server identity. Select the ‘identity’ tab:

Set ‘This user’ and insert User and Password used to access MM8000.

Image 11 DCOMCNFG – Identity

Note: The demo version runs only with Launching or Interactive User. A different user from
Launching or Interactive can be used ONLY if the OPC-Server runs with a registered PAK.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .11
Innovative Software Solutions and Engineering Services

5.3 Licensing
To run the OPC Server without any time restriction a regularly software license has to be
purchased from S4S.
A software license defines the maximum configuration managed by the OPC Server in terms
of:
- N° of FibroLaser III controllers (OTS30xx)
- N° of channels per OTS30xx (Optic fibers)
- Length of Optic Fiber (1,2,4,6,10 Km) per OTS30xx

Without the software license the OPC Server FibroLaser III runs in demo mode with full
functionality for two hours. The demo mode runs only with Launching or Interactive User
(see OPC Server identity 9).

5.3.1 How to obtain a license


A software license must be obtained from S4S and the request has to be done from the
computer where is installed the OPC Server. From the its User Interface selecting “?” then
“Information about OPC Server FibroLaser III” then “View license” then “Product activation”.

In the 'Product Activation' the following fields have to be filled :

 Customer installation data


o User name,
o Organization,
o Email,

 OTS 30XX configuration in terms of: numbers of FibroLaser III controllers, numbers of
channels for controller and fiber length per channel;

 Code generation (via the 'Generate new user code' button);

 Save the code and directly send it to '[email protected] ' or send it via 'Send' button if it
is configured a mail box on the computer.

A PAK (Program Authorization Key) code will be generated for that specific configuration
and for the PC from which has been requested the software license.

5.3.2 Software license activation


To activate your license you must access to the 'Product Activation' dialog and through the
'Load New License' button you load the license file released by S4S.
A dialog will appear for feedback at the end of loading to indicate the outcome of
activation.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .12
Innovative Software Solutions and Engineering Services

6. System Configuration
The purpose of this section is to provide the necessary information for configuring the
FibroLaser III controller and the OPC Server.

6.2.1 FibroLaser IIII controller (OTS30XX)


To enable the communication with the OPC-Server, the OTS30xx has to be configured
setting connection parameters and enabling the LON protocol.

The following screen shows how to configure the OTS30XX via Fibro Manager windows
application.

Image 12 - FibroLaser III Communication Settings

In the Network Settings section it is possible to set the OTS30XX IP address. This IP address
will be used by the OPC Server configuration tool to connect the FibroLaser III controller
.

Image 13 FibroLaser III Network Settings

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .13
Innovative Software Solutions and Engineering Services

In the LON Protocol section, to enable the LON Protocol, select the check-box "Use TCP"
and then set the communication Port.
The value of the Port will be set in the OPC Server to connect the OTS30xx.
In the transmitted data section is possible to define which data type the OTS30XX has to
be transmitted: Notices, Alarms, Alarm locations, Zone Minimum temperature, Zone
Maximum temperature, Zone Mean temperature, Temperature data and backscattering
data.
For MM8000 (Danger Management System) is sufficient to enable the following data:
Notices, Alarms and Alarm locations, for system as Desigo CCTM, CerberusTM DMS, WinCC
and SCADA, can be enabled the following data : Notices, Alarms, Alarm locations, Zone
Minimum temperature, Zone Maximum temperature, Zone Mean temperature, Temperature
data

Transmitted data setting for MM8000 :

Image 14 FibroLaser LON Protocol Transmitted data setting for MM8000

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .14
Innovative Software Solutions and Engineering Services

Transmitted data setting for DesigoCC, Desigo Insight, SCADA :

Image 15 FibroLaser LON Protocol Transmitted data setting for DesigoCC

6.2.2 OPC Server

After a successful installation, the OPC Server has to be configured in order to communicate
with the OTS 30xx and acquire data from it.
The OPC Server FibroLaser III configuration tool consists of two sections: Settings and
Subsystems.

 SETTINGS: Is the section where to define the OPC Server general parameters;

 SUBSYSTEMS: Is the section where to configure the subsystems (FibroLaser III


controllers) that the OPC Server has to connect.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .15
Innovative Software Solutions and Engineering Services

SETTINGS

The SETTINGS section allows configuring the OPC Server name and description and the
main operating parameters:

Image 16 OPC Server – SETTINGS

OPC Server

After entering the OPC Server name and description you must register the application with
the command "Register". In case you want to change the name and description you must
first unregister it then register it again with the new name.

Operating Parameters

 OPC Quality behavior


Enables or disables the management of the quality property in accordance with the
standard OPC. Default is : Enabled
 System Status Update (s):
Polling delay in seconds for updating the OTS 30xx status. Range Value: 1-3600 [s]
Default value: 3 [s].

 Level Log Detail :


Defines the level of detail of OPC LOGs presented on the screen.
Three levels are supported : LOW, MEDIUM and HIGH

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .16
Innovative Software Solutions and Engineering Services

- LOW - [Default value] – Presents the system diagnostics and commands received
from an OPC client .
- MEDIUM – Presents all OPC transactions (change of status, commands, diagnostics).
- HIGH - Presents all OPC transactions (change of status, commands, diagnostics)
with the native messages sent by the OTS. \). The detail level is verbose and can slow
down the application. Normally used only for Debug.

All logs are saved on a File.txt (C:\OPC- FibroLaser \LOG.

 Number Retry Msg


Number of polling messages sent to the OTS30xx, without any response, before to
set the communication status to disconnected. Range Value: 1-50 - Default value: 5

 Default Value TAG


Default value assigned when the OPC Server does not know the real value of TAGs,
for example at the start-up of the OPC. Default value is : -1.

 Path logo image :


Defines the logo to be presented on top of the application. Defaul value : S4S logo

 Alarm-Prealarm behavior :
Defines how to handle the zone alarm and prealarm OPC tags :
- FibroLaserIII : The alarm and pre-alarm value are aligned with the value sent by
the FibroLaserIII, so you can have both alarm and pre-alarm active
- Alarm-Prealarm : In this case when a zone alarm tag is set to a value active the
pre-alarm tag of the same zone is set to a value no-active.
Default value: FibroLaserIII

 Ack-Reset behavior :
Defines how to handle the event status of an OPC tag value :
- FibroLaserIII : The OPC tag value takes the value sent by the FibroLaserIII (0=no
active, 1 = active).
- Ack-Reset : The OPC tag value is set in accordance to the Ack and Reset
commands sent to the OTS. Es. 0 = event not-active, 1= event active, 2=event
silenced (Ack command sent) and ready to be reset. After the command reset the
value return to the value = 0.
Default value: FibroLaserIII

 Delimiter Export CSV file :


Defines the delimiter character used in the CSV file. Default value: ;

 Export full CSV file :

Whether NOT checked the CSV export file contains the following data;

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .17
Innovative Software Solutions and Engineering Services

Full Tag name Tag description text OPC Class


SUBSYSTEM_1.FIBRO_CHANNEL_1.Connection Connection 1
SUBSYSTEM_1.FIBRO_CHANNEL_1.FibreBreak FibreBreak 5
SUBSYSTEM_1.FIBRO_CHANNEL_1.Alarm Alarm 2
SUBSYSTEM_1.FIBRO_CHANNEL_1.FibreAlarmPositions FibreAlarmPositions 8
SUBSYSTEM_1.FIBRO_CHANNEL_1.FireMagnitude FireMagnitude 0
SUBSYSTEM_1.FIBRO_CHANNEL_1.FireDirection FireDirection 0
SUBSYSTEM_1.FIBRO_CHANNEL_1.ConfigurationAligned ConfigurationAligned 7
SUBSYSTEM_1.FIBRO_CHANNEL_1.Command Command 0
SUBSYSTEM_1.FIBRO_CHANNEL_1.ZONE_UKNOWN.Name Name 0
SUBSYSTEM_1.FIBRO_CHANNEL_1.ZONE_UKNOWN.Alarm Alarm 2
SUBSYSTEM_1.FIBRO_CHANNEL_1.ZONE_UKNOWN.Prealarm Prealarm 3
SUBSYSTEM_1.FIBRO_CHANNEL_1.ZONE_UKNOWN.Fault Fault 4

Whether is checked the CSV export file contains the following data (for DesigoCC);

SUBSYSTEM

The SUBSYSTEM section allows to define the number and properties of the subsystems
(OTS 30xx) to be connected to the OPC Server.

The “Add New” button is used to add new subsystem while the button “Remove” remove it.
The arrow buttons allow selecting the subsystem to configure. The number on the left
represents the subsystem to be configured while the number on the right represents the
maximum number of subsystems defined with the “Add” and “Remove” buttons.
For each subsystem (OTS) you must fill out the section “connection” and the section “Zone”

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .18
Innovative Software Solutions and Engineering Services

Connection

The connection section allows configuring information regarding the OTS30xx


communication parameters

Image 17 Configuration - SUBSYSTEM Connection

 Description
Is the description of the subsystem (OTS). At the sturt-up the OPC Server creates by
default one subsystem which description is set to “EXAMPLE”. The description can
be freely modified.
 TAG Name
The TAG name is used to identify the subsystem OPC TAG. The default value is
'SUBSYSTEM_(ID).
 Ethernet
- IP Address
IP address of the OTS30xx to be connected. The default is 127.0.0.1 (localhost).

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .19
Innovative Software Solutions and Engineering Services

- Port
Port number of the OTS30xx to be connected. The default is 1234.

 Serial Interface

- Port Name
Port Name of the OTS30xx to be connected. The default is COM1;

- Baud Rate
Baud Rate of the OTS30xx to be connected. The default is 19200;

- Data Bits
Data Bits of the OTS30xx to be connected. The default is 8;

- DTR Enable
DTR Enable of the OTS30xx to be connected. The default is true;

- Flow
Flow of the OTS30xx to be connected. The default is None;

- Parity
Prity of the OTS30xx to be connected. The default is None;

- Stop Bits
Stop Bits of the OTS30xx to be connected. The default is One;

 LON ID
The LON addresses are used to identify the OTS controllers in a network structure.
Note that each LON address MUST be unique in each network segment. Range

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .20
Innovative Software Solutions and Engineering Services

value: 1-255 (LON address 1, which has been used to identify Charon3 is not used
for OTS3/LHD3 system).
Default value: 2
 Fibro Channels
Number of the OTS30xx Fibro Channels configured by the Fibro Manager. Range
value : 1-48
Deafult value : 1
 Outputs
Number of Outputs configured in the OTS30xx by the Fibro Manager. Range value :
0-112.
Default value : 10.
 Inputs
Number of Inputs configured in the OTS30xx by the Fibro Manager. Range value: 0-
112.
Default value: 4.
 Temperature data
Whether checked enables the reading of temperature data transmitted by the
OTS30xx. Temperature date can be visualized in a chart that can be activated by the
User Interface menu.
OPC Server generates a number of TAGs OPC as the number of measurement points
sent from OTS30xx (the number of points is in relation to the OTS30xx resolution).
The OPC TAG name is defined according to the position (in meters) of measurement,
while the OPC TAG value shows the temperature measured in that instant.
The OPC path is: TEMPERATURE_DATA.Meter_{value} where {value} is the position in
meter (ex. TEMPERATURE_DATA.Meter_10_5 = 10,5 meter )

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .21
Innovative Software Solutions and Engineering Services

Zones

Image 18 Configuration - SUBSYSTEM Zone

This section allows to configure the zones for each fiber connected to the OTS30xx.
In the upper part of the section it’s possible to select the fibro channell using the left/right
arrow. Once selected the fibro channell proceed defining the associated zones.

The zones can be configured in two different ways:

Automatically: Zones are generated automatically by the system on the basis of the
following data provided by the Fibro Manager :

- Fiber length (mt) : is the length of the optic fiber cable defined by the Fibro Manager
in the section : Zone configuration – “effective fiber length” (see the right upper part
of the screen)
- Number of zones or Length of zones : These data comes always from the Fibro
Manager section “Generate Zones”

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .22
Innovative Software Solutions and Engineering Services

All zones generated by automattically configuration have the same length, if there are zones
with different lengths from other, you must configure them manually.

Manually: This configuration allows to manually configure the length of all zones. In this
mode is possible have zones with different lengths. The steps are:

- Automatically generate zones according to their number;

- Export the configuration via "Export" button;

- Open the csv file generated and edit fields:

 ZONE_NAME: description of the zone;


 ZONE_START: start position of the zone, expressed in meters (eg. 100,00);
 ZONE_END: end position of the zone, expressed in meters (eg. 200,00).

Important: FIBRO_CHANNEL, ALARM_ID and FAULT_ID should not be changed


and no zone should be overlaid with other.

Image 19 Manual Configuration - CSV Zone

- Import the csv file via "Import" button.

Once the zone configuration for each fibro channel is complited, select the “Download”
button to make active the new configuration.
Selecting the button “Close” without carrying out the command “Download”, data is lost.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .23
Innovative Software Solutions and Engineering Services

7. OPC TAGs
The following list introduces each tags in the OPC structure with a brief description.

PROPERTY

VALUE
TYPE
TAG DESCRIPTION VALUE DESCRIPTION

OPC Server FibroLaser III

SETTINGS

Default value: 2[s]


.System_status_update[s] System Status in seconds Int32 R/W 1-3600

Date last upload configuration data


.Date_XML_Upload String R DD/MM/YYYY hh:mm:ss
(xml file)

-1 Unknown
Indicates the status of the license. If
the license is installed but covers 0 Demo Version starting
.License_State fewer tags than configured, tags Int16 R 1 Demo Version running
unlicensed assume the default value 2 Demo Version Expired
(-100)
3 Licensed

SUBSYSTEM*
Subsystem Configured in xml file. If
the subsystem is configured implies 0 Configured
that opc tags are not updated. To
. Configured Int16 R
configure a subsystem you need to
change the description and do not 1 Not Configured
let 'EXAMPLE'
.ID OTS30xx ID Int16 R 1-N
.Description OTS30xx Description String R
0 Open
.PortState TCP Port State Int16 R
1 Close
0 Connected
.ConnectionState OTS30xx Connection State Int16 R
1 Disconnected
.SoftwareVersion OTS30xx S Software version String R Version.Revision.Release Code
.ControllerAddress OTS30xx LON Address Int16 R 2-255
0 Device is measuring
.MeasurementState measurement state Int16 R
1 Device is NOT measuring
None of the fibres involved in the
active measurement sequence
0
including spares exhibits a fibre
.NoFibreBreak break.
General Fibre Break state Int16 R
There is one or more fibres
involved in the active
1
measurement sequence including
spares exhibits a fibre break.
0 Inactive
.Output_[0-n] Output State Int16 R
1 Active
0 Inactive
.Input_[0-m] Input State Int16 R
1 Active
Systems without explosion
0
.ExplosionProtection protection option
Explosion protection state Int16 R
Explosion protection circuit is
1
installed

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .24
Innovative Software Solutions and Engineering Services

0 Normal
.KeySwitch Key switch state Int16 R
1 Test Mode position
0 No system fault
5 System fault
Silenced: defined only if "Ack-Reset
behavior" is setted to ''Ack-Reset",
6 otherwise it is never set. This value
is set when you send the command
Acknowledge on zone in Fault.
.SystemFault System fault state Int16 R/W COMMANDS
Acknowledge: if "Ack-Reset
behavior" is setted to ''Ack-Reset",
30
set zone value to Silenced,
otherwise not set a value.
Reset all: if "Ack-Reset behavior" is
setted to ''Ack-Reset", set zone
31
value to Normal, otherwise not set
a value.
0 No alarm
1 Alarm
Silenced: defined only if "Ack-Reset
behavior" is setted to ''Ack-Reset",
2 otherwise it is never set. This value
is set when you send the command
Acknowledge on zone in alarm.
.CommonAlarm Common alarm state Int16 R/W COMMANDS
Acknowledge: if "Ack-Reset
behavior" is setted to ''Ack-Reset",
30
set zone value to Silenced,
otherwise not set a value.
Reset all: if "Ack-Reset behavior" is
setted to ''Ack-Reset", set zone
31
value to Normal, otherwise not set
a value.
.InternalDeviceTemperature Internal device temperature in °C Float R
If the device is not equipped with
.InternalDeviceHumidity Internal device humidity in % rel.
Float R an internal humidity sensor, the
humidity
value is always Unknown
.PowerSupplyDCinputVoltag Power supply DC input voltage in
Float R
Volt
0 No synchronised with NTP server
.ClockSynchronised State of controller's clock Int16 R
1 Synchronised with NTP server
.LastUpdate Data Last Update String R
COMMANDS:
Alarm Triggering Locations
10
Request
11 Alarms Request
12 Software Version Request
13 Attendance Check Request
.Command Command SUBSYSTEM Int16 R/W
14 Controller Address Request
15 Device Status Request
16 Date And Time Request
30 Acknowledge
31 Reset all
SUBSYSTEM*.FIBRE_CHANNEL [1-48]
0 Connected
.Connection Connection State Int16 R
1 Disconnected
.NoFibreBreak Fibre Break state Int16 R 0 Normal

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .25
Innovative Software Solutions and Engineering Services

1 Fibre Break
0 Normal
1 Alarm
Silenced: defined only if "Ack-Reset
behavior" is setted to ''Ack-Reset",
2 otherwise it is never set. This value
is set when you send the command
Acknowledge on zone in alarm.
.Alarm
Alarm state Int16 R/W COMMANDS
Acknowledge: if "Ack-Reset
behavior" is setted to ''Ack-Reset",
30
set zone value to Silenced,
otherwise not set a value.
Reset all: if "Ack-Reset behavior" is
setted to ''Ack-Reset", set zone
31
value to Normal, otherwise not set
a value.
List of meter positions of alarm
triggering locations along the
sensor fibre. In order to reduce the
amount of data, adjacent triggering
.FibreAlarmPositions Alarm Triggering Locations String R
locations are transmitted only as
start and end position. In that case,
the end position is transmitted as a
negative number
1 Normal
2 Low
. FireMagnitude Fire magnitude state Int16 R 3 Medium
4 High
5 Very High
0 Fire static
. FireDirection Fire direction state Int16 R 1 Fire moving towards fiber end
2 Fire moving towards controller
COMMANDS
Avarage Zone Temperature
20
Request
.Command Command Int16 R/W Maximum Zone Temperatures
21
Request
Minimum Zone Temperatures
22
Request
SUBSYSTEM*.FIBRE_CHANNEL*.ZONE [0-1000]
.Index Int16 R 1-1000
.Name Zone Name String R
Starting position of the zone in
.Start Float R
meters
.End End position of the zone in meters Float R
.TemperatureMaximum Maximum zone temperatures in °C Float
.TemperatureAverage Average zone temperature in °C Float
.TemperatureMinimum Minimum zone temperature in °C Float
0 Normal
1 Alarm
Silenced: defined only if "Ack-Reset
behavior" is setted to ''Ack-Reset",
.Alarm 2 otherwise it is never set. This value
Alarm state Int16 R/W
is set when you send the command
Acknowledge on zone in alarm.
COMMANDS
Acknowledge: if "Ack-Reset
30
behavior" is setted to ''Ack-Reset",

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .26
Innovative Software Solutions and Engineering Services

set zone value to Silenced,


otherwise not set a value.
Reset all: if "Ack-Reset behavior" is
setted to ''Ack-Reset", set zone
31
value to Normal, otherwise not set
a value.
0 Normal
3 Prelarm
Silenced: defined only if "Ack-Reset
behavior" is setted to ''Ack-Reset",
4 otherwise it is never set. This value
is set when you send the command
Acknowledge on zone in Prealarm.
.Prealarm
Prealarm state Int16 R/W COMMANDS
Acknowledge: if "Ack-Reset
behavior" is setted to ''Ack-Reset",
30
set zone value to Silenced,
otherwise not set a value.
Reset all: if "Ack-Reset behavior" is
setted to ''Ack-Reset", set zone
31
value to Normal, otherwise not set
a value.
0 Normal
5 Fault
Silenced: defined only if "Ack-Reset
behavior" is setted to ''Ack-Reset",
6 otherwise it is never set. This value
is set when you send the command
Acknowledge on zone in Fault.
.Fault
Fault state Int16 R/W COMMANDS
Acknowledge: if "Ack-Reset
behavior" is setted to ''Ack-Reset",
30
set zone value to Silenced,
otherwise not set a value.
Reset all: if "Ack-Reset behavior" is
setted to ''Ack-Reset", set zone
31
value to Normal, otherwise not set
a value.
List of meter positions of alarm
triggering locations along the zone.
In order to reduce the amount of
.ZoneAlarmPositions data, adjacent
Alarm Triggering Locations String R
triggering locations are transmitted
only as start and end position. In
that case, the end position is
transmitted as a negative number
SUBSYSTEM*.TEMPERATURE_DATA
The temperature_data tags are created
only if is enabled the feature "Date
Temperatures" in settings panel.

The number of measurement


points (expressed in meters) is
defined by OTS30xx and depends
on its resolution.

There will be many temperature_data


Current temperature in °C on the tags how many will be the
. Meter_ [meter] Float R
fibre position. measuring points, each tag will be
differentiated by its position in the
optical fiber.

The position is expressed in meters


[meter].

Example: ".Meter_100_5" is
relative to the temperature
measurement position in the
optical fibre to the 100,5 meter.

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .27
Innovative Software Solutions and Engineering Services

LICENSE NOTE:
If the license is installed but covers fewer tags than configured, tags unlicensed assume the
default value (-100).

UNKNOWN VALUE:
If OPC-Server does not receive the state of one tag set the tag value with 'Default Value
TAG' defined in Settings configuration if the type tag is a integer else if the type is a string
set value with "".

OPC Server FibroLaser III Installation and Configuration Manual V1.2 Pag .28