Rectiverter 2U, 6kVA Integrated System

The Rectiverter 2U 19” Integrated System can be


used as a standalone system with bulk AC & DC
outputs in industrial applications where a 230/115 VAC
and 110 VDC backup is needed.

The total output power for both AC and DC is limited


to a total 8 kW. AC and DC output limits can be set
according to the connected load, where the limitation
for AC load is set to max 6 kVA and for DC load to
max 4,8 kW.

As additional options, the measuring and signaling


can be widely extended with the I/O Monitor or
Fleximonitor CAN nodes.

Rectiverter 2U, 6kVA Integrated System


110 VDC Systems with Smartpack2 Touch & Basic/Basic Industrial
DOC. NO: CIOR0402110.DS3, rev1

MODULAR ARCHITECTURE APPLICATIONS KEY FEATURES


RECTIVERTER MODULE POWER UTILITIES  COMPACT DESIGN AND SIMPLE
The 3 port converter simultaneously INSTALLATION
 Low & High voltage switchgear
provides power for AC and DC loads.  SINGLE PHASE 230 OR 115 VAC
During mains outage the Rectiverter feeds  Transformer & SUB stations
INPUT/OUTPUT
AC loads using energy stored in the  Power Generation & Distribution
battery.  Control & protection  110 VDC INPUT/OUTPUT
 SCADA system  HOUSE UP TO 4 RECTIVERTER
OFFSHORE AND PROCESS INDUSTRY MODULES
The modular architecture, industry-leading
efficiency, compact size, innovative design  8 KW TOTAL AC + DC OUTPUT
 Safety and Automation Systems
and comprehensive monitoring and control
(SAS)  MAX 6 kVA AC OUTPUT
features provide significant benefits over
MARINE  MAX 4,8 kW DC OUTPUT
the current industry standard.
 BULK FEED OUTPUTS AC + DC
 Communication onboard ships
 BUILT IN TRANSFER TECHNOLOGY
RAILWAY & METRO INFRASTRUCTURE
 150 % OVERLOAD CAPABILITY, 15 s
 Control & protection  600 % QUICK TRIP CURRENT, 20 ms
 Signaling  HOT PLUGGABLE
TELECOM-MOBILE/WIRELESS
 SMARTPACK2 TOUCH
 LTE/4G/WiMAX CONTROLLER
 Distributed antenna system  PROGRAMMABLE MULTIPURPOSE
 Broadband INPUTS AND OUTPUTS
Rectiverter Module

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2019 – www.eltek.com
Rectiverter Integrated 2U 19”
Doc CIOR0402110.DS3 – rev1

FRONT VIEW – RECTIVERTER INTEGRATED 2U


MODEL 110 VDC 8 kW / 4 kW
Product family CIOR0402.1xxx
INPUT DATA
Voltage range AC 185-275 / 95-140 VAC
Voltage range DC 102-145 VDC
Maximum current AC 32,8-46 A
Frequency 47-53 / 57-63 Hz
Power factor > 0,99
OUTPUT DATA
Adjustable range AC 200-240 / 100-127 VAC REAR VIEW – RECTIVERTER INTEGRATED 2U
Adjustable range DC 97-145 VDC
Max output power AC 6,0 / 3,0 kVA
Max output power DC 4,8 / 2,4 kW
Power factor 0,8
Frequency 50 Hz, 60 Hz
OTHER SPECIFICATIONS
Control unit (master) SP2 Touch
SP2 Basic or
Control unit (basic)
Basic Industrial
I/O Type 2 or
CAN node
Fleximonitor

Specifications are subject to change without notice

SINGLE LINE FOR 110 VDC WITH SMARTPACK2 TOUCH & BASIC/BASIC INDUSTRIAL

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2019 – www.eltek.com
Rectiverter Integrated 2U 19”
Doc CIOR0402110.DS3 – rev1

Models 8 kW, 230 VAC 4 kW, 115 VAC


Product family CIOR0402.1xxx CIOR0402.1xxx
AC OUTPUT DATA
Voltage (default) / (adjustable range) 1) 230 VAC / 200-240 VAC 115 VAC / 100-127 VAC
Frequency (inverter mode – default) 50 Hz (adaptive) 60 Hz (adaptive)
Frequency (inverter mode – settable) 50 Hz, 60 Hz or last synced 50 / 60 Hz (adaptive)
Power maximum (continuous / overload <15s) 4800 W (6000 VA) / 8000 VA 2400 W (3000 VA) / 4000 VA
Current maximum (continuous / overload <15s) 26 ARMS / 34,8 ARMS
Current (maximum) quick trip (20ms) 128 A (6 x nominal)
Hold up (Voltage dips) (before switching to
5 ms 5 ms
battery)
THD < 1,5 % at resistive load
Protection Fuse in L, Hot pluggable, Varistor
DC OUTPUT DATA
Voltage (default) / (adjustable range) 122,5 VDC / 97-145 VDC
Power (maximum @nominal input) 4800 W 2) 2400 W 2)
2)
Current (maximum @VOUT ≤ 108 VDC) 44,4 A 22,2 A 2)
Current sharing (10 - 100% load) ±5 % of maximum current from 10 to 100 % load
Protection Short circuit proof, Over voltage shutdown, Reversed polarity and Fuse
INPUT DATA
AC Mains Input Voltage (range / LV disconnect) 185-275 VAC / 170 VAC 95-140 VAC / 85 VAC
3)
AC Current (maximum - depends on module type) 32,8-46 ARMS 36,8-45,2 ARMS 3)
Frequency (default: sync range) 47-53 & 57-63 Hz 57-63 & 47-53 Hz
Frequency (settable: sync range) 47-53 Hz, 57-63 Hz or both (adaptive)
Power Factor / THD > 0,99 at 70% load or more / < 3,5 %
DC Voltage nominal / extended range 4) 102-145 VDC / 90-102 VDC
DC Current (maximum) 50 A / 72 A during overload (15 s) 25,2 A / 36 A during overload (15 s)
Fuse in L and N, Hot pluggable, Varistor
Input features
AC input individual screw terminals 4 mm 2 for L, N & PE (4x single phase)
OPTIONS
Control and Monitoring (master unit) Smartpack2 Touch
Control and Monitoring (basic unit) Smartpack2 Basic or Basic Industrial
Controller CAN node I/O Monitor T2 or Fleximonitor (with Relay box)
AC distribution AC output individual screw terminals 10 mm2 for L, N & PE (1x single phase)
DC distribution DC bulk connection on 2x M6 bolt
OTHER SPECIFICATION
Efficiency > 96 % (mains mode), > 95 % (inverter mode) > 93 % (mains mode), > 92 % (inverter mode)
Operating temperature -40 to +55 °C (-40 to +131 °F), humidity 5-95 % RH non-condensing
Storage temperature -40 to +85 °C (-40 to +185 °F), humidity 0-99 % RH non-condensing
Dimensions [W x D x H] 5) 482 x 400 x 89 mm (2U) (19 x 15,7 x 3,5 inch)
Weight 9,4-9,9 kg (20,7-21,8 lbs)
DESIGN STANDARDS
Electrical safety EN 60950-1, EN 62040-1 UPS safety
ETSI EN 300 386 V2.1.1, FCC CFR 47 Part 15
EMC EN 62040-2
EN 61000-6-1/-2/-3/-4/-5
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
Normal operating conditions as per IEC 62040-3:2011 clause 4.2. Other operating conditions as
Environment
per IEC 62040-3:2011 clause 4.3, must be advised
RoHS 3 (2015/863/EU) and WEEE (2008/98/EC) compliant
1) Output voltage ranges configured in factory and have individual 2) AC load has priority. Maximum available DC output power and current is dependent on instant AC load and AC input voltage;
keying in top chassis i.e. maximum 3200 W / 29,6 A at full AC power and nominal input for 230 V AC.
4) Reduced performance - no over load support, and for 200-240 VAC output THD will increased and maximum output power de-
3) If DC port is overloaded pulling the voltage below 97 V the input rates (to 970 W for 230 VAC @ 90 VDC)
current may increase above this level. 5) The system is 40 mm (0,4 inch) deeper in case of variant with Basic Industrial control unit

Specifications are subject to change without notice

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2019 – www.eltek.com