Earthquake Design Q&A Guide
Earthquake Design Q&A Guide
1. What is the formula to find the load factors for plastic design of steel
structures?
Page | 1
exceed 0.1fck.
The member shall preferable have a width to depth ratio more than 0.3
Width of the member shall not be less than 200mm.
The depth D of the member shall preferably be not more than ¼ of clear span.
Decreasing the tension steel area, yield stress and strain of the tension steel
increasing the ultimate compressive strain of concrete.
Increasing the area of compression steel.
Reduction in the axial compression on the section.
Provision of effective confinement stirrups, hoops or ties such
that compressive steel does not buckle and concrete is led into three
dimensional state of stress such that its ultimate compressive strain
increases.
Page | 2
All buildings with vertical offsets fall in this category. Also, a building may have
no apparent offset, but its lateral load carrying elements may have irregularity. For
instance, shear wall length may be suddenly reduced.
When building is such that larger dimension is above the smaller dimension, it acts as
an inverted pyramid and is undesirable.
Page | 3
(b) Weak bam and strong column approach.
(c) Avoiding soft first storey effects
(d) Avoiding Non – ductile failure modes like shear, bond and axial
compression at the element level
14. Define the term symmetry in buildings. Why symmetrical forms are preferred
than unsymmetrical forms?
Symmetry denotes a geometrical property of the plan configuration, whereas the
structural symmetry means that the center of mass and the center of resistance are
located at the same point.
In asymmetrical configuration / structural system the eccentricity between the
center of mass and resistance will produce torsion and stress concentration and
therefore the symmetrical forms are preferred to the asymmetrical ones.
15. What are the factors that govern the architectural configurations?
1. Architectural design
Page | 4
2. Functional requirements
3. Urban design parameters
4. Planning considerations
5. Aesthetic appearance
6. Identity (distinctiveness)
17. List the design principles for earthquake resistant structural systems.
Structural systems should follow the design principles given below. "
1. Be simple
2. Be symmetrical
3. Not be too elongated in plan or too slender in elevation
4. Have continuous and uniform distribution of strength
5. Have horizontal members which form hinges before the vertical, members
6. Have its stiffness related to sub soil properties.
Page | 5
rotation, meaning that during a seismic event the structure would rotate about its center of
rigidity.
21. What is the design philosophy adopted for earthquake resistant structure?
The extreme loading condition caused by an earthquake and also the
low probability of such an event occurring within the expected life of a
structure, the following dual design philosophy is usually adopted
The structure is designed to resist the expected intensity of ground motion due
to a moderate earthquake so that no significant damage is caused to the basic
structure and
The structure should also be able to withstand and resist total collapse in the
unlikely event of a severe earthquake occurring during its lifetime.
24. Explain the strong column weak beam method? Nov/Dec 2008
The followings are the major aspect of the strong column and weak beam concept, as
follows:
1. The overall structure is designed so it can develop inelastic structural behavior
2. Column is designed stronger than beam it means during strong earthquake
column member remain elastic so it can provide stability and strength of the
stories above
3. The development of plastic hinge is forms at the end of beam , so the energy
dissipation is occurs in the plastic hinge
4. To ensure the perfect energy dissipation at plastic hinge, plastic hinge region
required special reinforcement detailing (confinement) to improve ductility,
energy absorption capacity and perform inelasticity
Page | 7
25. Explain two cases of design horizontal earthquake load.
(a) When the lateral resisting elements are oriented along orthogonal horizontal
direction, the structure shall be designed for the effects due to full design
earthquake load in one horizontal direction at time.
(b) When the lateral load resisting elements are not oriented along the orthogonal
horizontal directions, the structure shall be designed for the effect due to full
design earthquake load in one horizontal direction plus 30% of the design
earthquake load in the other direction.
27. Name the different methods to obtain the seismic design force
Time history method, seismic coefficient method and by response spectrum method
Page | 8
28. Define Drift
The maximum relative displacement between two successive floors due to the
design seismic force should not exceed 0.004 times the storey height. The check is
particularly necessary for buildings greater than 40m in height.
Whichever of these gives the more severe effect in the shear of any frame
[∑𝑛𝑖=1 𝑊𝑖 𝜙𝑖𝑘 ]2
𝑀𝑘 =
𝑔 ∑𝑛𝑖=1 𝑊𝑖 (𝜙𝑖𝑘 )2
32. Write the formula to calculate the Vertical distributions of base shear to
different floor levels of a multi storeyed building as per IS 1893 (part 1) 2002.
The design base shear (Vb) shall be distributed along the height of the building
as per the following expression
Page | 9
Qi - Design lateral force at floor,
Vb - Design base shear
Wi - Seismic weight of the building
hi - Height of floor 1 measured from base and
n - Number of storeys in the building is the number of levels at which masses are
located.
33. Write the steps to improve performance of the structure under earthquake load.
Increase redundancy is helpful to make the predetermined elements to undergo
large inelastic actions.
Prevent premature local or member buckling of design elements.
Ensure that predetermined locations of inelastic actions can sustain expected large
plastic rotations through providing good moment connections.
42. What are the factors that contribute the over strength factor?
1. Load factor on seismic and gravity load
2. Material factors
3. Member sizes/reinforcement more than required
4. Special ductile detailing
5. Redundancy
6. Strain hardening in materials
7. Higher material strength under cyclic loads
8. Strength contribution of non-structural members
Page | 13
Such movement does not have to occur during a major earthquake; slight
periodic movements called fault creep can be accompanied by micro
earthquakes too small to be felt.
The extent of earthquake vibration and subsequent damage to a region is partly
dependent on characteristics of the ground.
Page | 14
It is always desirable to avoid construction in such areas than to design the
structures following codal provisions, which may be insufficient, though ensure
effective design against vibration of structures due to shaking at the foundation
level.
Page | 15
Accordingly, reinforced concrete can be used effectively by providing proper
amount of reinforcement and correct detailing of them as they play significant
roles in the seismic resistant design of reinforced concrete structures.
Steel has the additional advantages of ductility, strength and toughness per unit
weight than concrete.
The indirect effects are Tsunamis, seiches, landslides, floods and fires are the
indirect effects of earthquakes. These may occur either alone or in combinations to add
to the damages during an earthquake
STRUCTURAL DAMAGE
Structural damage means a situation where the building's structural support has
been impaired. Structural support includes any vertical and lateral force resisting
systems, such as building frames, walls and columns.
Non-structural damage does not affect the integrity of structural system. Examples
of non-structural damage include broken windows, collapsed or rotated chimneys,
and fallen ceilings.
Structural damage is the leading cause of death and economic loss in many
earthquakes. This damage is not only to unreinforced masonry and adobe structures
but also to more modem constructions. Structures need not collapse to cause death
and damage during earthquakes.
l. Strength of shaking
Page | 16
2. Duration of shaking
4. Type of building
3. Type of subsurface conditions
l. Strength of shaking:
For small earthquakes (magnitude less than 6), the strength of shaking decreases
rapidly with distance from the epicenter of the earthquake.
In the case of a small earthquake, the center of energy release and the point where
slip begins are not far apart.
But in the case of large earthquakes, which have a significant length of fault rupture,
these two points may be hundreds of miles apart.
Thus for large earthquakes, the strength of shaking decreases in a direction away
from the fault rupture.
2. Duration of shaking:
The duration of shaking depends on how the fault breaks during the earthquake. It
usually varies from 10 see to 1 minute.
The longer the ground shakes, the greater the potential for structural damage. In
general, the higher the magnitude of an earthquake, the longer the duration of the
shaking ground.
3. Type of subsurface conditions:
Ground shaking can be increased if a site has a thick deposit of soil that is soft and
submerged.
Many other subsurface conditions can cause or contribute to structural damage.
There could be structural damage due to the liquefaction of loose submerged sands.
4. Type of building:
Certain types of buildings and other structures are especially susceptible to the side-
to-side shaking common during earthquakes.
Page | 17
For example, sites located near (about 16 km) the epicenter or location of fault
rupture are generally subjected to rough, jerky, high-frequency seismic waves that
are often more capable of causing short buildings to vibrate vigorously.
For sites located at greater distance, the seismic waves often develop into longer
period waves that are more capable of causing high-rise buildings and buildings
with large floor areas to vibrate vigorously.
Page | 18
Therefore, the earthquake resistant capacity at the first story tends to be smaller than
upper stories, and the first story collapse is very common during any earthquakes.
3) Damage to Mid-Storey
During the Earthquake, several buildings suffered from mid-story collapse, which is
rather rare earthquake damage.
The reason of the damage is considered that those buildings were designed using an
old seismic code, in which the distribution of seismic forces had not been properly
considered, and also there was structural discontinuity along the height of the
buildings, i.e. the steel frame reinforced concrete for lower stories and reinforced
concrete for upper stories
Page | 19
In many earthquakes, damage to structural elements may be minor, but roof tiles,
exterior finishing, concrete block fences, etc are extensively damaged even by
moderate earthquakes.
Overturning of furniture may injure people, hinder evacuation, cause fires, etc. The
damage to non-structural elements may occur even during minor earthquakes, and
cannot be ignored from an economical point of View.
Page | 20
2. Briefly describe the type of plan irregularities and vertical irregularities of
buildings with neat sketches? May/June 2013
PLAN IRREGULARITIES
However, in agreement with the experiences in past and recent earthquakes, most of
the damages are related to architectonic and structural configuration in plant and
elevation and site ground effects.
Page | 21
The effects that cause seismic action in irregular structures were observed in many
recent earthquakes.
Most of literature describes the effects only qualitative, and the codes used some
percentages that limited the structural performance, but not necessary are obtained
with large and deep investigation.
Page | 22
VERTICAL IRREGULARITIES
Irregular buildings constitute a large portion of the modern urban infrastructure. The
group of people involved in constructing the building facilities, including owner,
architect, structural engineer, contractor and local authorities, contribute to the
overall planning, selection of structural system, and to its configuration.
A base case structure is developed, and cases that represent irregular structures are
defined by modifying the vertical distribution of mass, stiffness or strength of the
base case.
Page | 24
Page | 25
3. Write the step by step procedure for seismic analysis of RC buildings as per IS
1893: 2002? May/June 2013
Where,
h= height of the building in ‘m’,
d= base dimension of building in ‘m’
Page | 26
Figure 2: Seismic zones of India [Fig. 1, IS-1893 (2002)]
Page | 27
Table 2: Importance factor (I) [Table 6, IS-1893 (2002)]
Figure 3: Response spectra for rock and soil sites for 5% damping [Fig. 2, IS-1893 (2002)]
Page | 28
Table 4: Response reduction factor (R) for building systems [Table 7, IS-1893
(2002)]
Page | 29
Step: 4 Determination of design vertical seismic coefficient
Design vertical seismic coefficient is equal to two-third of the design horizontal
seismic coefficient.
VB =Ah.W
where
1. Static analysis
For the purpose of determining seismic forces, the country is classified into four
seismic zones. Such as Zone II, III,IV,V
The design horizontal seismic coefficient Ah for a structure shall be determined by the
following expression
Page | 30
Provided that for any structure with T< 0.1 s, the value of Ah will not be taken less
than Z/2 whatever be the value of I/R
Where,
Z = Zone factor given in Table 2, is for the Maximum Considered Earthquake (MCE)
and service life of structure in a zone. The factor 2 in the denominator of Z is
used so as to reduce the Maximum Considered Earthquake (MCE) zone factor to
the factor for Design Basis Earthquake (DBE).
Sa /g = Average response acceleration coefficient of srock or soil site as given the fig.
Seismic Weight
Seismic Weight of Floors
The seismic weight of each floor is its full dead load plus appropriate amount of
imposed load, as specified in 7.3.1 and 7.3.2. While computing the seismic weight of
such floor, the weight of columns and walls in any storey shall be equally distributed to
the floors above and below the storey.
Page | 31
Seismic Weight of Building
The seismic weight of the whole building is the sum of the seismic weights of all
the floors
Design Seismic Base Shear
The total design lateral force or design seismic base shear (VB) along any principal
direction shall be determined by the following expression.
H = Height of building, in m,
d = Base dimension of the building at the plinth level, in m, along the considered
direction of the lateral force.
The design base shear (VB) computed in 7.5.3 shall be distributed along the height of the
building as per the following expression:
Page | 33
Calculation of Design Seismic Force by Static Analysis Method
Problem Statement:
Seismic Weights:
Page | 34
The floor area is 15×20=300 sq. m. Since the live load class is 4kN/sq.m, only
50% of the live load is lumped at the floors. At roof, no live load is to be lumped. Hence,
the total seismic weight on the floors and the roof is:
Floors :
W1 W2 W3 300 (12 0.5 4)
4200 kN
Roof :
W4 300 10
3000
(clause 7.3.1, Table 8 of IS : 1893 Part 1)
Fundamental Period:
Lateral load resistance is provided by moment resisting frames infilled with brick
masonry panels. Hence, approximate fundamental natural period:(Clause 7.6.2. of IS:
1893 Part 1)
EL in X-Direction:
0.09h
T
d
0.09 13.8
20
0.28sec
ZI S a
Ah
2R g
0.36 1.0
2.5
25
0.09 (Clause 6.4.2 of IS 1893 Part I)
Page | 35
Design base shear
VB AhW
0.09 15600
1440kN (Clause 7.5.3 of IS :1893 Part1)
EL in Y-Direction:
0.09h
T
d
0.09 13.8
15
0.32sec
Sa
2.5
g
Ah 0.09
Therefore, for this building the design seismic force in Y-direction is same as that
in the X-direction. Fig. 1.2(b) shows the design seismic force on the building in the Y-
direction.
Table 1.1 – Lateral Load Distribution with Height by the Static Method
Lateral Force at
Wi hi 2
Storey Wi(kN Wi hi 2 (1000) ith Level for EL in
hi (m) Wi hi 2
Level ) direction (kN)
X Y
4 3000 13.8 571.3 0.424 611 611
3 4200 10.6 471.9 0.350 504 504
2 4200 7.4 230.0 0.171 246 246
1 4200 4.2 74.1 0.055 79 79
1347.3 1000 1440 1440
Page | 36
Figure 1.2 – Design seismic force on the building for (a) X – direction, and (b) Y –
direction
Page | 37
Solution: Analysis considering stiffness of infill masonry
2) Beams:
Self weight of beam per unit length = 0.25 x 0.4 x 25 = 2.5 kN/m
Total length = 4x22.5x2 = 180 m
DL due to self weight of beams = (2.5 x 22.5) x 4 x 2 = 450 kN
3) Columns:
Self weight of column per unit length = 0.45 x 0.45 x 25 = 5.0625 kN/m
DL due to self weight of columns (16 No.s) = 16 x 5.0625 x 3.0 = 243 kN
4) Walls:
Self weight of wall per unit length = 0.12 x 3 x 20 = 7.2 kN/m
Total length = 4x22.5x2 = 180 m
DL due to self weight of Walls = 7.2 x 22.5 x 4 = 648 Kn
Page | 38
5) Live Load [Imposed load] (25 %) = (0.25 x 3) x 22.5 x 22.5 = 380 kN
Load on all floors:
W1=W2=W3= 1898 + 380 + 450 + 243 + 648 = 3619 kN
Load on roof slab (Live load on slab is zero)
W4 = 1898 + 0+450 + (243/2) + (648/2) = 2793.5 kN
Total Seismic weight, W = (3619 x 3) + 2793.5 = 13650.5 kN
Page | 39
Page | 40
Page | 41
6. For a four storeyed RCC office buildings located in zone V and resting on hard
rock, compute the seismic forces as per IS – 1893 2002 equivalent static procedure.
Height of first is 4.2m and the remaining three stories are of height 3.2m each. Plan
dimensions (length and width) of the structure are 15mx20m. The RCC frames are
infilled with brick masonry.
Dead load on floor 12kN/m2 on floors and 10kN/m2 on roof. Live = 4kN/ m2 on floors
and 1.5kN/ m2 on roof.
Also compute the base shear, neglecting the stiffness of infill walls. Compare the base
shears for the two cases and comment on the result.
Solution
Given data
On roof = 10 kN/m2
Note: Only 50% of the live load is lumped at the floors. At roof, no live load is to
be lumped
Zone V, Z = 0.36
Page | 42
Total seismic weight:
Page | 43
Page | 44
7. Determine the design horizontal seismic coefficient for an ordinary reinforcement
concrete moment resisting frame hospital building without infill panels for a
damping of 5:1, zone III resting on hard soil. Height of the building is 22m and it is
resting on hard soil.
b. For a natural period of 0.76s, the value of sa/g from Fig. is = 1.35
For Zone III Z = 0.16 (from code book)
I = 1.5 (from code book)
R = 3 (from code book)
Ah 0.054
Page | 45
8. A three storeyed symmetrical reinforced concrete school building in zone V with
plan dimensions 7m, storey height of 3.5m. Total weight of beams in a storey is
130kN and total weight of slab in a storey 250kN. Total weight of columns in a
storey is 50kN and total weight of walls in the storey is 530kN. Live load = 130kN,
weight of terrace floor is 655kN resting on hard rock. Damping = 5% determine the
base shear and lateral loads of each floor by seismic coefficient method.
Solution:
1) Natural period
0.09h 0.09 X 10.5
T 0.357sec
d 7
2) For T = 0.357s, damping, sa/g = 2.5 (from code book)
Z = 0.36, I = 1.5, R=5
ZISa
3) Design horizontal seismic coefficient h
2 Rg
0.35 X 1.5 X 2.5
h 0.135
2X 5
4) Seismic weight
Weight of one storey = total weight of beams + columns + slabs + live load
= 130 + 50 + 250 + 530 + 130 kN
= 1090 kN
Weight of terrace = 655 kN
Total weight of building = weight of I + II floor + 655
= 2 X 1090 + 655
= 2835 kN
5) Base shear
Vb AhXW
= 0.135 X 2835
= 382.725 kN
Page | 46
6) Equivalent lateral load
Wihi 2
Qi Vb X
nj 1Wihj 2
655 X 3.52
382.725 2
655 X 3.5 1090 X 7 1090 X 10.5
2 2
16.91kN
1090 X 72
Q2 382.725 2
655 X 3.5 1090 X 7 1090 X 10.5
2 2
38112.56kN
1090 X 10.52
Q3 382.725 2
655 X 3.5 1090 X 7 1090 X 10.5
2 2
253.21kN
The shear distribution of three storeyed building is shown in fig.
9. Briefly explain about the Design and detailing as per IS:13920 – 1993
Page | 47
Structures situated in high seismic zones require special ductile design and
detailing, Under severe earthquake shaking, it is ensured that the structure designed
should exhibit good ductility, a large lateral deformation and vibrations will be induced,
which results in the formation of plastic hinges at a predetermined locations in the
frames. Ductility is the ability of the structure to undergo large displacements without
collapse, even after the yielding has occurred.
Ductility is the capacity of the building materials, systems or structures to absorb
seismic energy by deforming in the inelastic range. The safety of the building from
collapse is ensured by absorbing energy rather than resisting seismic forces IS 13920 -
1993 gives provisions for ductile detailing of reinforced concrete structures subjected to
seismic forces.
Page | 48
Page | 49
10. Explain the Methods of introducing ductility in Reinforced Concrete structure
The main structural elements and their connections shall be designed to have a ductile
failure. This will enable the structure to absorb energy during earthquake, to avoid
sudden collapse of the structure. Providing reinforcing steel in masonry at critical
sections will not only increase strength and stability but also ductility.
Page | 50
3. Shape of cross section
The presence of an enlarged compression flange in T beam reduces the depth of
the compression zone at collapse and thus increases the ductility.
4. Lateral reinforcement
Lateral reinforcement tends to improve the ductility by preventing shear failures
and by confining the compression zone, thus increasing deformation capability of a
reinforced concrete beam.
Longitudinal Reinforcement
1. At least two bars throughout the member length at top and bottom.
2. Positive steel at a joint face must be at least equal to 1/2 the negative steel at that
face
3. Steel provided at each of the top and bottom face of the member at any section
along its length should be at least equal to 1/4 of the maximum negative moment
steel provided at the face of either joint.
The longitudinal bars should be spliced, only if hoops are provided over the entire
splice length, at spacing not exceeding 150mm. For confining the concrete and to support
longitudinal bars
Page | 51
1. The lap length should not be less than the bar development length in tension
2. Lap splices shall not be provided
a. within a joint
b. Within a distance of 2d from joint face.
3. Within a quarter length of the member where flexural yielding may generally
occur under the effect of earthquake forces.
4. Not more than 50% of the bars shall be spliced at one section and the lap spice in
beam is shown in Fig.
Beam Reinforcement
The spacing of hoops over a length of 2 x d at either end of a beam shall not
exceed
1. d/4
2. 8 times the diameter of the smallest longitudinal bar (It must not be less
than 100mm) shown Fig.
Page | 52
Fig: Beam reinforcement
Transverse reinforcement
Transverse reinforcement for circular columns shall consist of spiral or circular hoops.
In rectangular columns, rectangular hoops are used.
A rectangular hoop is a closed stirrup having a 1350 hook with a 10 diameter
extension (but not less than 75mm) at each end, that is embedded in the confined core.
The parallel legs of rectangular hoop shall be spaced not more than 300mm centre to
centre. If the length of any side of the hoop exceeds 300mm a crosstie shall be
provided as shown in Fig. Alternatively, a pair of overlapping hoops may be provided
within the columns.
The hoops shall engage peripheral longitudinal bars.
Page | 53
Fig: Transverse reinforcement in column
Page | 54
Fig: column and joint detailing
1. Larger lateral dimension of the member at the section where yielding occurs.
2. 1/6 of clear span of the member and
3. 450mm
Page | 55
Fig: Special Confining Reinforcement in Footings
Columns supporting reactions from discontinued stiff members such as walls,
shall be provided with special confining reinforcement over their full height shown in
Fig.
Page | 56
Fig: Special Confining Reinforcement for Column under Discontinued Walls
This variation in stiffness may result due to the presence of bracing, a mezzanine
floor or a RCC wall on either side of the column that extends only over a part of the
column height as shown in Fig
The spacing of hoops used as special confining reinforcement shall not exceed 'l4
of minimum member dimension but need not be less than 75mm nor more than 100mm.
Page | 57
Subject Code/Name: CE 2403 / Basics of Dynamics and Aseismic Design
Page | 58
Unit-5 Important Sixteen Mark Questions
7. 17. Determine the design horizontal seismic coefficient for an ordinary reinforcement
concrete moment resisting frame hospital building without infill panels for a damping
Page | 59
of 5:1, zone III resting on hard soil. Height of the building is 22m and it is resting on
hard soil.
8. A three storeyed symmetrical reinforced concrete school building in zone V with plan
dimensions 7m, storey height of 3.5m. Total weight of beams in a storey is 130kN and
total weight of slab in a storey 250kN. Total weight of columns in a storey is 50kN
and total weight of walls in the storey is 530kN. Live load = 130kN, weight of terrace
floor is 655kN resting on hard rock. Damping = 5% determine the base shear and
lateral loads of each floor by seismic coefficient method.
9. Briefly explain about the Design and detailing as per IS:13920 – 1993
10. Methods of introducing ductility in Reinforced Concrete structure
Page | 60
Page | 61
Page | 62
Page | 63
Page | 64