Safety Relief Valve HON 832
product information
serving the gas industry
worldwide
Safety relief valve HON 832
Application, characteristics, technical data
Application
• As leak gas SRV with internal vent connection (function class B in accordance with DIN 33821)
• Variant as proportional SRV with autonomous vent connection (function class A in accordance
with DIN 33821)
• For systems in municipal applications and industrial operations
• Leak gas SRV type “B”, e. g. for blowing off gas leakages downstream of gas pressure regulators to prevent
the SSV from tripping by accident in the event of gas pressure regulator leaks due to consumer zero droop
2 • Can be used for gases in accordance with DVGW Worksheet G 260 and neutral, non-aggressive gases;
other gases on request
Characteristics
• Simple, compact design
• Position-independent installation
• Safe operation
• High actuating accuracy
• Integrated vent line for use as leak gas SRV (type “B“)
Device-specific operating instructions, maintenance instructions, spare parts drawings, and spare parts lists are
provided in the brochure “Operating and Maintenance Manual / Spare Parts List 832.20”.
Safety relief valve HON 832
Application, properties, technical data
Technical data
Max. permissible pressure PS 100 bar
Max. operating pressure pmax 100 bar
Setpoint spring Specific pressure range Accuracy class AC
No. Colour Wire Ø Wus in bar
Specific pressure range Wus 1 grey 5 0.5 to 2 5/2.5 3
and accuracy class AC 2 yellow 5.6 1 to 4 2.5/1
3 brown 6.3 2 to 8 2.5/1
4 red 7 4 to 16 2.5/1
5 green 8/7* 12 to 30 2.5/1
Valve seat diameter 8 mm
Valve flow rate coefficient KG: 32 m3/(h · bar)
Pipe connections according to DIN EN ISO 8434-1 (DIN 2353), PN 100
Connection for pipe outer diameters:
Inlet: 12 mm Outlet: 16 mm, 20 mm, 25 mm, 28 mm
– Leak gas SRV Internal via vent line
Spring compartment type “B”
venting – Proportional SRV Autonomous vent connection with pipe outer diameter 12 mm
type “A”
Main valve body Aluminium alloy
Spring housing Aluminium alloy
Material
Measuring diaphragm NBR (Perbunan)
Valve trim FKM
Weight Approx. 3 kg
Temperature range – 20 °C to + 60 °C
CE mark in accordance with PED
8
Function and strength In accordance with DIN 33821
The mechanical components of the device do not have any potential ignition
ATEX sources, and thus are not subject to ATEX 95 (94/9/EC). Electronic components
attached on the device satisfy the ATEX requirements.
*) = vertical cross section
Safety relief valve HON 832
Dimensions
Dimensions
145
65
70
28
4
E 12
E 20
95
250
E 12
(external vent connection
for SRV type “A”,
in accordance with
DIN 33821)
Note: internal venting
sealed
Safety relief valve HON 832
Structure and mode of operation
A safety relief valve (SRV) has the task of autonomously releasing a gas flow from a pressurised line, as soon as
the pressure in the system to be safeguarded reaches the set response pressure through increasing increments.
The SRV closes again when the pressure in the system to be safeguarded drops below the closing pressure.
The Safety relief valve HON 832 is a directly acting device (works without auxiliary energy) with spring loading.
The safety device is designed in two variants: as leak gas SRV and as proportional SRV.
When the device is used as a leak gas SRV (type “B” in accordance with 33821) the spring space is vented in-
ternally via the vent line. When the device is used as a proportional SRV (type “A” in accordance with DIN 33821)
on the spring housing a connection piece is arranged for the autonomous vent line to the free atmosphere. 5
The pressure to be monitored on the inlet side (actual value) is switched internally and compared with the
specified force of the adjustable setpoint spring. If the pressure in the system to be safeguarded exceeds the
set response pressure, the main valve opens and allows the excess gas to flow off via the outlet line. The safety
relief valve closes again automatically when the pressure of the system to be safeguarded drops below the
response pressure of the SRV.
The lateral forces that occur due to the setpoint spring are dissipated directly to the housing via the guide bush.
This ensures a high reproducible response accuracy.
The valve piston of the main valve is force-relieved through a control spring. Through this measure the valve trim
is protected against impermissible stress. The measuring diaphragm is formed as a bead-moulded diaphragm.
This means that the high actuating accuracy of the device is also ensured at lower operating temperatures.
Safety relief valve HON 832
Structure and mode of operation
Leak gas quantity SRV (type “B” it accordance with DIN 33821)
Inlet line
Internal venting Outlet line
Measuring diaphragm Valve seat
Valve disc
with sealing ring
Setpoint spring Spindle bush
Setpoint adjuster
Cover cap
Autonomous vent
connection for
proportional SRV
(Type “A” in accordance
with DIN 33821)
Note: internal
venting sealed
Safety relief valve HON 832
Device designation
Device description (example) HON 832 - B - E12 / E20 - 1
Device designation
Type
HON 832
Function class
7
Leak gas SRV (type “B” in accordance with DIN 33821) B
Connection, inlet
E12
Connection, outlet
E16
E20
E25
E28
Specific pressure range Wus in bar Spring no.
0.5 to 2 1
1 to 4 2
2 to 8 3
4 to 16 4
12 to 30 5
*Optionally with internal and external vent connection
For More Information
To learn more about Honeywell’s
Advanced Gas Solutions, visit
www.honeywellprocess.com or contact
your Honeywell account manager
GERMANY
Honeywell Process Solutions
Honeywell Gas Technologies GmbH
Osterholzstrasse 45
34123 Kassel, Deutschland
Tel: +49 (0)561 5007-0 HON 832.00
2017-01