The approved document has a date entered in the "Approved"-fie
1 2 3 4 5 6 7 8
This document is issued by means of a computerized system.
The digitally stored original is electronically approved.
611 Bushing Data: END SHIELD DRAW ROD SYSTEM / OUTER TERMINAL
Rated Voltage 800 kV D2
A Phase to-earth Voltage 485 kV R533 Outer terminal A
Dry Lightning Impulse 1,2/50µs2550 kV Threaded hole M8
H2
Wet Switching Impulse 1675 kV for pulling wire
150
Dry switching impulse 1760 kV
A manual signature is not required.
Routine test 1min dry 50Hz 1075 kV
Rated Current 2500 A
420
Creepage Distance 25720 mm
290
Mass 3500 kg
Ordering Data:
B 565 BUSHING COLOUR AIR INSULATOR B
1ZSC902800-AAA BROWN Upper
draw rod
OUTER TERMINAL R44 R25
8051 63
8051 63
Max. Rated H2 D2
Current (A)(mm) (mm)
LF170 073-ACCu/Sn 2500 125 42 TERMINAL PLATE
END-SHIELD 45 (3x)
6690
LF170 046-XPINSULATED WITH 6 mm PRESSBOARD
DRAW ROD SYSTEM 17.5
LF170 059-DRLOWER DRAW ROD WITH N1=4 13
C (8x C
LF170 057-BYUPPER DRAW ROD )
TERMINAL PLATE
LF170 077-B Cu/Sn
235
665
25
125
20
45
28
For stud 42 Lower
Tan 0.4%
60
We reserve all rights in this document and in the information contained therein.
draw rod
D D
Max. test load Imin 12200 N 170
Reproduction, use or disclosure to third parties without express authority
605
640
215
Max. permissible load in
Additional
1955 5
opration at mounting angel joint on
request
1955 5
Earthed
H1 min260
0 $ 6100 N
layer 30 $ 2900 N
30 $
58
39
Earthing hole
M12 Position of
E E
is strictly forbidden. © 2022 Hitachi Energy.
test tap N1=4
48
528
780
90 $
N1=Number of holes M12, equipped with
thread insert with screw lock,
711
depth 20, for cable lugs.
DOCUMENT KIND APPROVED TITLE / SUPPLEMENTARY TITLE
Dimension Drawing 2023-10-11 GOE 2550-1675-2500-0.6
F Position of oil
RESPONSIBLE DEPARTMENT F
12 Mounting GOE 2550-1675-2500-0.6
sample valve holes n 32 SEABB-9AAE300824
A-A RESPONSIBLE COMPANY DOCUMENT ID STATUS REVISION SHEET
Hitachi Energy Sweden AB 1ZSC026186-AYD Released B 1/1
1 2 3 4 5 6 7 8
DRAWING SHEET ISO 5457:1999-A3T