TEST CERTIFICATE

Name of Party: ALIM AKRAM

SITE: HASANPUR PWSS, KARIMGANJ PHE DIVISION, JAL JEEVAN MISSION, ASSAM

Product Name : AMITEX GRP PANEL TANK As Per IS-14399 (Part 1 & 2 ) (With All Accessories)

P.O. NO: As per your P.O.

Size and Cap. 5x4x2 (40000 Ltr)–– 01 No

Ref. No : QT/ASM/GU/1573,, Date of Inspection : 17/Jan/2024

MATERIAL SUPPLIED THROUGH OUR AUTHORISED DEALER: AJAY TRADERS

SN Parameter Testing as per IS-14399 Test Value / Remarks


O (Part 1: 1996) Observation

1 Tensile Strength 70 MPa (Min) 87.2 Confirm

Bending Strength
2 100 MPa (Min) 112.6 Confirm
(Cross- Breaking)

3 Elastic Modulus in Bend 6000 MPa (Min) 6200 Confirm

4 Glass Content % 25 Percent (Min) 30.1 Confirm

5 Barcoal Hardness 50 BHU (Min) 56 Confirm

6 Water Absorption % 0.5 Percent (Max) 0.28 Confirm

Thickness of Panel:
1) Type-‘A’ – 3mm Min Found Much more
7 Dimension of the Panel 2)Type-‘B’ – 4mm Min than the Tolerance Confirm
3)Type-‘C’ –5mm Min Limit
Testing as per IS- Test Value / Remarks
8 Visual Inspection of Panel 14399 (Part 1: 1996) Observation

a) Small pits appearing on the surface No No Such Observation Confirm

Poor Impregnation of Fibreglass


b) No No Such Observation Confirm
with Resin

Cuts, Cracks and Scratches


c) No No Such Observation Confirm
exposing the glass reinforcement.
Sharp projections, exposed fibres
d) or glass reinforcement too close to No No Such Observation Confirm
the surface.
Surface and non-structural
structural repair
e) No No Such Observation Confirm
marks

Blister on the surface caused by air


f) No No Such Observation Confirm
pockets.

Testing as per IS- Test Value / Remarks


9 Description 14399 (Part 2: 1996) Observation

RUBBER/SILICON
a) SEALENT RUBBER YES
RUBBER

SHOULD NOT BE
b) BOLTS / NUTS 10X45MM YES
LESS THEN 10MM

c) SUPPORT SYSTEM UPVC / GRP UPVC YES

SHOULD BE 450MM
d) MANHOLE 450MM YES
MINIMUM

ALUMINIUM ALLOY
e) LADDER ALUMMIUM ALLOY YES
OR GRP
GRP / PVC
f) AIRVENT PVC YES

Inspected By: Verified By:-


By: