Downstairs AC HVAC Installation Manual
Downstairs AC HVAC Installation Manual
SINGLE PACKAGE ®
AIR CONDITIONER/GAS HEAT
MODELS: PCG4 SERIES
2 TONS TO 5 TONS - 208/230 V - 1 PHASE
LIST OF SECTIONS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 AIRFLOW PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . 2 TYPICAL WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
LIST OF FIGURES
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Flue Vent Outlet Air Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Center of Gravity Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Bottom Duct Dimensions (in.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Measuring External Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 18
Rear Duct Dimensions (in.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Connection Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Typical Field Control Wiring Diagram for Gas Heat - AC Models . . . 7 Ladder Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 7 R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
LIST OF TABLES
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 High-Altitude Gas Orifice Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Application Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Natural Gas Application Data - PCG4 . . . . . . . . . . . . . . . . . . . . . . . 10
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Propane (LP) Gas Application Data - PCG4 . . . . . . . . . . . . . . . . . . . 11
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Airflow Performance - Side Duct Application . . . . . . . . . . . . . . . . . . 11
Unit Clearances, . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electrical Data - PCG4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Natural Gas Pipe Sizing Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Default Blower Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Propane (LP) Gas Pipe Sizing Chart . . . . . . . . . . . . . . . . . . . . . . . . . 9 Gas Rate (ft3/h) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
! WARNING ! WARNING
Before performing service or maintenance operations on unit, turn off If the information in this manual is not followed exactly, a fire or
main power switch to unit. Electrical shock could cause personal explosion may result causing property damage, personal injury, or
injury. Improper installation, adjustment, alteration, service, or main- loss of life.
tenance can cause injury or property damage. Refer to this manual. Do not store or use gasoline or other flammable vapors and liquids in
For assistance or additional information consult a qualified installer, the vicinity of this or any other appliance.
service agency, or the gas supplier. WHAT TO DO IF YOU SMELL GAS:
1. Do not try to light any appliance.
CAUTION
2. Do not touch any electrical switch; do not use any phone in
! your building.
This system uses R-410A refrigerant, which operates at higher pres- 3. Immediately call your gas supplier from a neighbor’s phone.
sures than R-22. No other refrigerant may be used in this system. Follow the gas supplier’s instructions.
Gage sets, hoses, refrigerant containers, and recovery systems must 4. If you cannot reach your gas supplier, call the fire depart-
be designed to handle R-410A. If you are unsure, consult the equip- ment.
ment manufacturer. Failure to use R-410A compatible servicing Installation and service must be performed by a qualified installer,
equipment may result in property damage or injury. service agency, or the gas supplier.
OUTDOOR COIL
(Behind Panel)
CONTROL BOARD
BLOWER MOTOR TRANSFORMER
HIGH VOLTAGE
CONTACTOR
TXV
PRESSURE SWITCH
INDOOR COIL
DRAFT INDUCER BLOWER
INDOOR BLOWER
GAS VALVE
COMPRESSOR GAS HEAT
EXCHANGER
REMOVABLE BURNER
BASE RAILS ASSEMBLY
A0297-001
LOCATION All units require particular clearances for proper operation and service.
Use the following guidelines to select a suitable location for these units: Make provisions for adequate combustion and ventilation air in accor-
dance with the following:
• The unit is designed for outdoor installation only.
• Section 5.3 of Air for Combustion and Ventilation of the National
• Outdoor coils must have an unlimited supply of air. Where a choice
Fuel Gas Code, ANSI Z223.1 - Latest Edition (in U.S.)
of location is available, position the unit on either the north or east
side of the building. • Sections 7.2, 7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 -
Latest Edition (in Canada)
• The unit is suitable for mounting on a roof curb.
• Applicable provisions of local building codes
! WARNING See Table 5 for the clearances required for combustible construction,
servicing, and proper unit operation.
Do not attach supply and return duct work to the bottom of the unit
base pan as the drain pan could be compromised. RIGGING AND HANDLING
• For ground level installation, use a level pad or slab. The thickness
and size of the pad or slab must meet local codes and support the
! CAUTION
weight of the unit. Do not tie the slab to the building foundation. All panels must be secured in place when the unit is lifted.
• Roof structures must be able to support the weight of the unit and The outdoor coils should be protected from rigging cable damage
its options/accessories. Install the unit on a solid, level roof curb or with plywood or other suitable material.
an appropriate angle iron frame.
CAUTION
• Maintain level tolerance to 1/8 in. across the entire width and
length of the unit. !
WARNING
If a unit is to be installed on a roof curb other than a Ducted Systems
! roof curb, gasket or sealant must be applied to all surfaces that come
in contact with the unit underside.
Excessive exposure of this unit to contaminated combustion air may
result in equipment damage or personal injury. Typical contaminates Exercise care when moving the unit. Do not remove any packaging until
include: permanent wave solution, chlorinated waxes and cleaners, the unit is near the place of installation. Rig the unit by attaching chain
chlorine based swimming pool chemicals, water softening chemicals, or cable slings to the lifting holes provided in the base rails.
carbon tetrachloride, Halogen type refrigerants, cleaning solvents
(for example, perchloroethylene), printing inks, paint removers, var- Note: Use spreader bars whose length exceeds the largest dimension
nishes, hydrochloric acid, cements and glues, anti-static fabric soft- across the unit across the top of the unit.
eners for clothes dryers, masonry acid washing materials.
CLEARANCES ! CAUTION
WARNING
Before lifting, make sure the unit weight is distributed equally on the
! rigging cables so it will lift evenly.
Do not permit overhanging structures or shrubs to obstruct outdoor Units can be moved or lifted with a forklift. Slotted openings in the base
air discharge outlet, combustion air inlet, or vent outlets. rails are provided for this purpose.
"D"
CENTER OF
GRAVITY
COMPRESSOR
"A" "C"
FRONT
OF UNIT
"B" Y
X
A0295-001
INDOOR COIL
(BEHIND PANEL) OUTDOOR COIL GUARD
HIGH VOLTAGE
OPENING 7/8"
C
HIGH VOLTAGE
COMBUSTION AIR INTAKE
OPENING 1 3/32"
HEAT EXCHANGER ACCESS PANEL
COMPRESSOR
ACCESS PANEL
FLUE EXHAUST HOOD
CONDENSATE A
DRAIN B
BLOWER
ACCESS CONTROL / HEAT LOW VOLTAGE OPENING 7/8"
PANEL ACCESS PANEL GAS SUPPLY HOLE 1 5/8" WITH
GROMMET OPENING OF 7/8" A0296-004
DUCT WORK
9,(:/22.,1*83
' ´
NOTICE
´
$7%277202)81,7
&
All units are shipped in the horizontal supply/return configuration. It is
important to reduce the possibility of any air leakage through the bot-
tom duct covers (resulting from cut, torn, or rolled gasket) due to 5(7851
improper handling or shipping processes. To ensure a good tight $ $,5'8&7
seal, it is recommended that silicone caulk and/or foil tape be applied
along the cover edges.
NOTICE
$
Model A B C D E F
Be sure to note supply and return openings. 24, 30, 36, 42 10 21.5 5 4.5 47.5 32
48, 60 14 13.5 5 3.5 47.5 42
See Figures 4 and 5 for information concerning rear and bottom supply Figure 4: Bottom Duct Dimensions (in.)
and return air duct openings.
FILTERS 127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRI
Correct filter size is very important. Always consider filter size, type, and HOHFWULFDODQGJDVOLQHV
pressure drop during duct system design.
Single-phase units are shipped without a filter or filter racks. It is the
responsibility of the installer to secure a filter in the return air ductwork
or install a filter/frame kit.
A filter rack and high-velocity filters are standard on three-phase units.
Always use filters and keep filters clean. When filters become dirt laden,
insufficient air is delivered by the blower, decreasing your unit’s effi-
ciency and increasing operating costs and wear-and-tear on the unit
and controls.
Check filters monthly. This is especially important because the unit can
be used for both heating and cooling.
6833/< 5(7851
$,5'8&7 $,5'8&7
$ % $
$
Model A B
24, 30, 36, 42 9.6 22
48, 60 13.6 14
Figure 5: Rear Duct Dimensions (in.)
! CAUTION G
GREEN
WARNING
BLUE
! C
This system uses R-410A refrigerant, which operates at higher pres- Table 8: Natural Gas Pipe Sizing Chart1
sures than R-22. No other refrigerant may be used in this system. Length Nominal Inches Iron Pipe Size
The compressor uses polyolester (POE) oil, Mobil 3MA POE. This oil is (ft) 1/2 in. 3/4 in. 1 in. 1 1/4 in.
extremely hygroscopic, meaning it absorbs water readily. POE oil can 10 132 278 520 1,050
absorb 15 times as much water as other oils designed for HCFC and 20 92 190 350 730
CFC refrigerants. If the refrigerant circuit is opened, take all necessary 30 73 152 285 590
precautions to avoid exposure of the oil to the atmosphere.
40 63 130 245 500
CAUTION
50 56 115 215 440
! 60 50 105 195 400
Do not leave the system open to the atmosphere. Unit damage could 70 46 96 180 370
occur due to moisture being absorbed by the POE oil in the system. 80 43 90 170 350
This type of oil is highly susceptible to moisture absorption.
90 40 84 160 320
POE compressor lubricants are known to cause long-term damage to 100 38 79 150 305
some synthetic roofing materials.
1. Maximum capacity of pipe in cubic feet of gas per hour (based upon a pressure
drop of 0.3 in. W.C. and 0.6 specific gravity gas).
! CAUTION Table 9: Propane (LP) Gas Pipe Sizing Chart1
Exposure to compressor oil, even if immediately cleaned up, may
Length Nominal Inches Iron Pipe Size
cause embrittlement (leading to cracking) to occur in one year or
more. When performing any service that may risk exposure of com- (ft) 1/2 in. 3/4 in. 1 in. 1 1/4 in.
pressor oil to the roof, take precautions to protect roofing. 10 275 567 1071 2,205
20 189 393 732 1496
Procedures that risk oil leakage include but are not limited to the follow-
ing: 30 152 315 590 1212
40 129 267 504 1039
• Replacing the compressor
50 114 237 448 913
• Repairing refrigerant leaks
60 103 217 409 834
• Replacing refrigerant components, for example, filter drier, pres-
sure switch, metering device, or coil 70 96 196 378 771
80 89 185 346 724
! CAUTION 90
100
83
78
173
162
322
307
677
630
Do not loosen compressor mounting bolts.
1. Maximum capacity of pipe in thousands of BTU per hour (based upon a pres-
Units are shipped with compressor mountings, which are factory- sure drop of 0.5 in. W.C.).
adjusted and ready for operation.
NOTICE
RectorSeal No. 5 or equivalent compounds may be used.
• Isolate the unit from the gas supply piping system by closing its
! WARNING individual manual shut-off valve before conducting any pressure
testing of the gas supply piping system at test pressures equal to
FIRE OR EXPLOSION HAZARD or less than 1/2 psig (3.48 kPa).
Failure to follow the safety warning exactly could result in serious
injury, death, or property damage. HIGH-ALTITUDE GAS CONVERSION
Never test for gas leaks with an open flame. Use a commercially
The furnace is constructed at the factory for natural gas-fired operation
available soap solution made specifically for the detection of leaks to
check all connections. A fire or explosion may result causing property at altitudes up to 2,000 ft above sea level. For installations located
damage, personal injury, or loss of life. above 2,000 ft, reduce the gas input rate to the burners by 4% per
1,000 ft above sea level. It may be necessary to change to smaller ori-
• Disconnect the unit and its equipment shutoff valve from the gas fices at high altitude. See Table 10 for the correct orifice size to use.
supply system during any pressure testing of that system at test
pressures in excess of 1/2 psig (3.48 kPa).
! WARNING
Flue hood surfaces may be hot. AIR INTAKE HOOD
The flue vent hood and air intake hoods are shipped loose. Install these Figure 8: Flue Vent Outlet Air Hood
hoods to ensure proper unit operation. Fasten the hoods to the outside
of the side gas control/electrical compartment with the screws provided.
See Figure 8.
GAS VALVE FAULT Rapid Amber Flash: Indicates the flame sense current is below 1.5
VDC. Do the following:
If the main valve output is sensed as energized for more than 1 s when
• Check and clean the flame sensor.
commanded to be off, the control board de-energizes the induced draft
motor (if the flame is not present) to attempt to open the pressure • Check for proper gas flow.
switch to de-energize the gas valve. If the main gas valve is still sensed • Verify that the current is greater than 1.5 VDC at the flame current
as energized after the inducer has been off for 10 s, the control board test pad.
re-energizes the inducer to vent the unburned gas. The control board 4 Amber Flashes: Indicates the control board is receiving a Y signal
enters a hard lockout, and the LED on the control board emits 10 red from the thermostat without a G signal. The furnace operates normally
flashes. during heating and cooling, but this fault code is displayed to alert the
The only way to recover from a hard lockout is to remove and reapply user that there is a wiring problem. Verify that the G wire from the ther-
24-VAC power to the control board. mostat is connected properly.
1 Red Flash: Indicates the flame was sensed when there was no call 9 Red Flashes: Indicates reversed line voltage polarity, a grounding
for heat. The control board turns on both the induced draft motor and problem, or reversed low-voltage transformer wires. Do the following:
supply air blower. Check for a leaking or slow-closing gas valve. • Check the polarity at the furnace and branch.
2 Red Flashes: Indicates the pressure switch is closed when it should • Check the furnace grounding.
be open. The control board confirms the pressure switch contacts are
• Check that the flame probe is not shorted to the chassis.
open at the beginning of each heat cycle. The control board prevents
the ignition sequence from continuing if the pressure switch contacts The furnace does not start the ignition sequence until the problem is
are closed when they should be open. Check for a faulty pressure corrected.
switch or miswiring. 10 Red Flashes: Indicates the gas valve is energized with no call for
3 Red Flashes: Indicates the pressure switch contacts are open when heat. The main blower and inducer blower run and no ignition sequence
they should be closed. Check for the following: starts as long as this condition exists. Check the gas valve and gas
valve wiring.
• Faulty inducer
• Blocked vent 11 Red Flashes: Indicates the limit circuit has remained open for more
than 5 min and less than 15 min. This condition is usually caused by a
• Broken pressure switch hose
failed blower motor or blower wheel. The control board enters a hard
• Disconnected pressure switch or inducer wires lockout. When the problem is corrected, you must turn off the power to
• Faulty pressure switch the unit and turn on the power to the unit again to reset the control
4 Red Flashes: Indicates the high-temperature limit switch or rollout board.
switch has opened its contacts, which are normally closed. The control Soft Lockout: The control includes a soft lockout that resets automati-
board turns on the supply air blower and inducer. Check for the follow- cally after 1 h. This provides protection for an unoccupied structure if a
ing: temporary condition causes a furnace malfunction, for example, if a
• Dirty filter temporary interruption in gas supply prevents the furnace from lighting.
• Incorrectly sized duct system The control board keeps trying to light each hour and resumes normal
• Incorrect blower speed setting operation if the gas supply is restored.
• Incorrect firing rate Hard Lockout: Some fault conditions cause a hard lockout, and you
• Loose high-temperature limit switch or rollout switch wiring must turn off the power to the unit and turn on the power to the unit
again to reset the control board. The control board does not automati-
• Faulty blower motor
cally restart.
If the high-temperature limit switch does not close within 5 min, the con-
trol board operates as if the blower is not functioning. The control board COOLING SEQUENCE OF OPERATIONS
starts a hard lockout and the LED on the control board emits 11 red When the thermostat calls for COOL, the thermostat terminals G and Y
flashes. If the high-temperature limit switch does not close after 15 min, are energized, which signals the compressor, outdoor fan, and indoor
the control board operates as if a manual reset rollout switch has blower to run.
opened, and the LED on the control board emits 5 red flashes. See the With a call for Y, the indoor circulating blower is energized at cooling
5 Red Flashes and 11 Red Flashes descriptions below. If the high-tem- speed.
perature limit switch opens five times within a call for heat, the LED on
When the thermostat is satisfied, terminals G and Y are de-energized,
the control board emits 4 red flashes, and the control board enters a 1-h
de-energizing the compressor and outdoor fan.
soft lockout.
After a cool fan off delay timing of 30 s, the indoor circulating blower is
5 Red Flashes: Indicates the limit circuit has been open for more than de-energized.
15 min, usually meaning that a manual reset rollout switch has opened.
Check for the following: Safety Controls
• Proper combustion air The control circuit includes the following safety control:
• Correct inducer operation • High-pressure switch - This switch protects against excessive dis-
charge pressures due to a blocked outdoor coil or an outdoor
• Primary heat exchanger failure
motor failure (opens at 650 ± 25 psig and closes at 450 ± 25 psig).
• Burner problem
The high-pressure switch is specifically designed to operate with
The control board enters a hard lockout. When the problem is cor- R-410A systems. Do not use R-22 pressure switches as replacements
rected, you must turn off the power to the unit and turn on the power to for R-410A pressure switches.
the unit again to reset the control.
6 Red Flashes: Indicates that while the unit was operating, the pres-
sure switch opened four times during the call for heat. Check for a faulty
! WARNING
inducer, blocked vent, or faulty pressure switch. The furnace locks out The ability to properly perform maintenance on this equipment
for 1 h and then restarts. requires certain expertise, mechanical skills, tools, and equipment. If
you do not possess these, do not attempt to perform any mainte-
7 Red Flashes: Indicates the flame could not be established during
nance other than those procedures recommended in this Installation
three attempts for ignition. Check that the gas valve switch is in the ON
Manual. Failure to heed this warning could result in serious injury
position. Check for the following: and possible damage to this equipment.
• Low gas pressure or no gas pressure
• Faulty gas valve INDOOR CIRCULATING BLOWER
• Dirty or faulty flame sensor When the thermostat calls for FAN, the thermostat terminal G is ener-
• Faulty hot surface ignitor gized, signaling the indoor circulating blower to run at the G-speed air-
flow.
• Loose wires
• Burner problem If a call for COOL occurs (Y), the indoor circulating blower switches to
run at the Y-speed airflow.
The furnace locks out for 1 h and then restarts.
If a call for HEAT occurs (W), the indoor circulating blower switches to
8 Red Flashes: Indicates the flame has been lost five times (four recy- run at the W-speed airflow after a 30-s delay.
cles) during the heating cycle. Check for low gas pressure, a dirty or
When the thermostat ends the call for FAN, the thermostat terminal G is
faulty flame sensor, or a faulty gas valve. The furnace locks out for 1 h
de-energized, de-energizing the indoor circulating blower.
and then restarts.
AIRFLOW SETTINGS
NOTICE Cooling Airflow Settings
The regulated outlet pressure has been calibrated at the factory. The unit is equipped with a five-speed blower motor. Select the required
Additional pressure adjustment should not be necessary. If adjust- cooling airflow by connecting the required motor speed tap wire to the
ment is necessary, set to the following specifications. After adjust- yellow COOL speed wire coming from the control board. Select the
ment, check for gas leakage. speed to deliver approximately 350 CFM to 400 CFM per ton of A/C
cooling capacity. Use of airflow outside of this range may cause dimin-
3. See Figure 9 for the location of the pressure regulator adjustment
ished air conditioning performance, lower overall energy efficiency, and
cap and adjustment screws on the main gas valve.
higher electric utility bills. See Table 17 for default cooling blower set-
4. Turn on gas and electrical supplies and follow the operating instruc-
tings.
tions to place the unit back in operation.
5. Adjust the manifold pressure by adjusting the gas valve regulator Table 17: Default Blower Speeds
screw for the appropriate gas per Table 16.
Default Blower Speeds
Table 16: Nominal Manifold Pressure Model Number Heat Cool Continuous Fan
Nominal Manifold Pressure (White Wire) (Yellow Wire) (Red Wire)
Natural Gas 3.5 in. W.C. (0.87 kPa) PCG4A24050 Medium Low (2) High (5) Low (1)
Propane (LP) Gas 10.0 in. W.C. (2.488 kPa) PCG4A24075 Medium High (4) High (5) Low (1)
PCG4A30050 Low (1) High (5) Low (1)
OUTLET PCG4A30075 Medium Low (2) High (5) Low (1)
PRESSURE PCG4A36050 Low (1) High (5) Low (1)
PORT VENT PORT
PCG4A36075 Medium Low (2) High (5) Low (1)
PCG4A36100 Medium (3) High (5) Low (1)
INLET OUTLET
PCG4A42075 Medium Low (2) High (5) Low (1)
FF PCG4A42100 Medium Low (2) High (5) Low (1)
WRENCH O
BOSS PCG4B48065 Low (1) High (5) Low (1)
INLET N MAIN REGULATOR
O
PRESSURE ADJUSTMENT PCG4B48100 Medium Low (2) High (5) Low (1)
ON/OFF SWITCH
PORT PCG4B48125 Medium Low (2) High (5) Low (1)
(Shown in ON position) A0226-001
PCG4B60065 Low (1) High (5) Low (1)
Figure 9: Gas Valve
PCG4B60100 Medium Low (2) High (5) Low (1)
PCG4B60125 Medium Low (2) High (5) Low (1)
IMPORTANT: If gas valve regulator is turned in (clockwise), manifold
pressure increases. If the screw is turned out (counterclockwise), Continuous Fan Airflow Settings
manifold pressure decreases.
The default blower speed for continuous fan operation is Low speed. To
6. When the manifold pressure has been adjusted, re-calculate the operate the furnace in continuous fan mode, set the wall thermostat fan
furnace input to make sure you have not exceeded the specified switch to ON. To select the required continuous fan airflow, connect the
input on the rating plate. See Natural Gas in the CHECKING GAS required motor speed tap wire to the red FAN speed wire coming from
HEAT INPUT section. the control board.
7. When the correct BTU (kW) input has been established, turn the The default position is with the red (Low) blower speed wire connected
gas valve to OFF and turn the electrical supply switch to OFF.
to the red FAN speed wire coming from the control board. In certain cir-
Remove the flexible tubing from the gas valve pressure tap and
cumstances, it may be necessary to move the continuous fan speed to
tighten the pressure tap plug using the 3/32 in. (2.4 mm) hex head
wrench. a different speed tap. However, this is not best practice because it
causes higher electrical energy usage and higher electric utility bills.
8. Turn on the electrical and gas supplies, and with the burners in
operation, check for gas leakage around the gas valve pressure Gas Heating Airflow Settings
port using an approved non-corrosive gas leak detection fluid or See Table 17 for the default heating blower speed. The unit is equipped
other non-flammable leak detection methods.
with a five-speed blower motor. See Table 17 for the default heating
MANIFOLD PRESSURE U-TUBE CONNECTION blower speed for each model.
287/(7
In certain circumstances, it may be necessary to move the heating
35(6685(3257 blower speed to a different motor speed tap.
*$69$/9(
´78%,1* Note: Not all of the five motor speeds are appropriate for gas heating
operation.
)/$0( 0$1,)2/'
6(1625 3,3( The use of heating airflow at a speed other than the default speed
causes diminished heating performance and may cause the furnace
temperature limit controls to shut down the furnace.
,1
:$7(5
&2/801
*$6
*$6 35(6685(
%851(56 878%( 6+2:1
0$120(7(5
$
INCHES OF WATER
HI PORT
LO PORT
RETURN AIR
DUCT
SUPPLY AIR
DUCT
A0435-002
NOTICE 28
30
64
60
129
120
To find the BTU input, multiply the number of cubic feet of gas con- 32 56 113
sumed per hour by the BTU content of the gas in your particular 34 53 106
locality. Contact your gas company for this information since it varies 36 50 100
widely from city to city. 38 47 95
40 45 90
42 43 86
44 41 82
46 39 78
48 37 75
50 36 72
52 35 69
54 34 67
56 32 64
58 31 62
60 30 60
1. Example: By actual measurement, it takes 38 s for the hand on the 1 ft3 dial to
make a revolution with just a 100,000 BTUH furnace running. Using this infor-
mation, locate 38 s in the first column of Table 18. Read across to the 1 ft3 col-
umn, where you see that 95 ft3/h of gas are consumed by the furnace at that
rate. Multiply 95 x 1050 (or the BTU rating of the gas obtained from the local
gas company). The result is 99,750 BTUH, which is close to the 100,000 BTUH
rating of the unit.
GND
BLK 6
GRN 44
COIL
BLK/WHT 12
DUAL
BLU 43 CAPACITOR
FAN
HI PRESS RED 45
YEL 18 YEL 17
HERM C
1 BLK
RED 7
BLU 42
2
BRN/WHT 13 3 BRN
W 4 OD FAN
MOTOR
Y GRN 10 5 GRN
BLOWER RED
O DELAY RED 9 6
R 180
LOW
VOLTAGE C BLK 5
BOX 120
C BLU 23 C 90
R RED 22 R
60
O
PUR 2
Y YEL 21 Y CONTROL
W WHT 20 W
BOARD (CONTINUOUS FAN) (LOW) 1
G GRN 19 G RED 32
PUR 26
THERMOSTAT RED 34 RED/GRN 36 2 N
(LOW/MED) 1
ROLLOUT LIMIT (HEATING SPEED) (MED) 3 BLOWER G
WHT 33 MOTOR 2 GRN 4
3 2 1
RED/BLK 35 (COOLING SPEED) (MED/HIGH) 4 L
BLK
YEL 31 3
YEL 38 6 5 4
SHARED TAP
5 SEE NOTE 7 C
GRN 40 9 8 7 (HIGH) 4
YEL 38
ORG 37 FLAME
GAS IGNITOR SENSOR
VALVE ORG 39
PRESSURE
W SPD
SPARK
G SPD TRANSFORMER
CONTROL BOARD SETTINGS:
L1 IND FS
Y SPD COMBUSTION BLOWER POST PURGE: 60 SEC
1 2 3 ORG
24V COM INDOOR BLOWER HEAT ON DELAY: 30 SEC
INDOOR BLOWER COOL OFF DELAY: 60 SEC
RED 28 INDOOR BLOWER HEAT OFF DELAY: FIELD SELECT
BRN
DRAFT CAP
MOTOR
WHT 27 YEL LINE VOLTAGE
BLU 30
LOW VOLTAGE
Operational Fault Codes 2. CAUTION : LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
Flashes Fault Condition CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION. IF ANY OF THE WIRING, AS SUPPLIED WITH THE UNIT, MUST
None Power Off or open fuse BE REMOVED, IT MUST BE REPLACED WITH TYPE 105 C. 600 VOLT
Slow Green Flashes Normal Operation WIRE OR EQUIVALENT CLEARLY RENUMBERED FOR IDENTIFICATION.
Slow Amber Flashes Normal Operation with call for heat VERIFY PROPER OPERATION AFTER SERVICING.
Rapid Amber Flashes Low flame sense current 3. FACTORY WIRED FOR 230 VOLT SUPPLY POWER. FOR 208 VOLT, MOVE
4 Amber Flashes No G from thermostat with Y call BLACK WIRES FROM THE 230 TO THE 208 VOLT TAP ON THE TRANSFORMER.
Steady on Red Control Failure 4. MOTORS ARE INHERENTLY PROTECTED.
1 Red Flash Flame present with gas off
2 Red Flashes Check pressure switch wiring 5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE
AND MINIMUM CIRCUIT AMPACITY.
3 Red Flashes Vent OR termination problem
4 Red Flashes Airflow problem 6. SELECT INDOOR BLOWER SPEED TO REMAIN WITHIN THE TEMPERATURE
RISE RANGE ON THE NAMEPLATE IN HEATING AND TO OBTAIN APPROX.
5 Red Flashes Flame Rollout 400 CFM/TON IN COOLING.
6 Red Flashes Repeated pressure switch cycles
7 Red Flashes Failed to light burners 7. BLOWER MOTOR SPEED CONNECTIONS SHOWN ARE TYPICAL,
BUT MAY VARY BY MODEL AND APPLICATION.
8 Red Flashes Loss of flame during call for heat
9 Red Flashes Incorrect polarity OR Don't have neutral
10 Red Flashes Gas valve shorted "ON"
11 Red Flashes Check blower motor/wiring
1174285-UWD-C-0519
Refer to Installation Manual for more detailed information.
L1 L2
NOTES:
R RED
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR
NATIONAL CODES IN EFFECT AT THE TIME OF INSTALLATION OF THE UNIT. L1 T1 BLK C COMPRES
BRN
S
VERIFY PROPER OPERATION AFTER SERVICING.
T2
BRN/WHT
L2
3. FACTORY WIRED FOR 230 VOLT SUPPLY POWER. FOR 208 VOLT, MOVE DUAL
BLACK WIRES FROM THE 230 TO THE 208 VOLT TAP ON THE TRANSFORMER. CAPACITOR
H C F
4. MOTORS ARE INHERENTLY PROTECTED. RED
5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE
AND MINIMUM CIRCUIT AMPACITY.
G
7. BLOWER MOTOR SPEED CONNECTIONS SHOWN ARE TYPICAL,
CONTROL
BUT MAY VARY BY MODEL AND APPLICATION. BOARD
RELAY DRAFT
PUR WHT MOTOR BLK
L1 IND
R-410A refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
R-410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400, or DOT BW400.
Recovery equipment must be rated for R-410A.
DO NOT use R-410A service equipment on R-22 systems. All hoses, gages, recovery cylinders, charging
cylinders and recovery equipment must be dedicated for use on R-410A systems only.
Manifold sets must be at least 700 psig high side, and 180 psig low side, with 550 psig retard.
All hoses must have a service pressure rating of 800 psig.
Leak detectors must be designed to detect HFC refrigerants.
Systems must be charged with liquid refrigerant. Use a commercial type metering device
in the manifold hose.
R-410A can only be used with POE type oils.
POE type oils rapidly absorb moisture from the atmosphere.
Vacuum pumps will not remove moisture from R-410A refrigerant oils.
Do not use liquid line driers with a rated working pressure rating less than 600 psig.
Do not install suction line driers in the liquid line.
A liquid line drier is required on every unit.
Do not use a R-22 TXV. If a TXV is to be used, it must be a R-410A TXV.
Never open system to atmosphere when under a vacuum.
If system must be opened for service, evacuate system then break the vacuum with dry nitrogen
and replace all filter driers.
Owner Information
Name Address Daytime Phone
Equipment Data
Unit Model # Unit Serial #
Filters
Filters installed Number of filters Filter size Filter located inside Filter located outside
Line voltage present at disconnect Measured voltage "L1 to L2" "L2 to L3" "L1 to L3"
Compressor amperes "L1" "L2" "L3" Total amperes "L1" "L2" "L3"
Supply static (inches of water column) Supply air dry bulb temperature Outside air dry bulb temperature
Return static (inches of water column) Return air dry bulb temperature Return air wet bulb temperature
Total external static pressure Temperature drop Supply air wet bulb temperature
Gas Heat
Single Stage Two Stage Natural Gas Propane LP (Requires LP Conversion Kit)
LP Gas Conversion Kit # LP Conversion Kit Installed By Inlet Gas Pressure (w.c.")
Manifold Pressure at 100% Firing Rate (w.c.") Measured BTU/H (Clock Gas Meter Nat Gas) Rated BTU/H
Manifold Pressure / Low Fire Rate (w.c.") Return Air Dry Bulb Temp Supply Air Dry Bulb Temp Temp Rise
Burner Flame Inspection - Blue flames extending directly into the primary heat exchanger cells
Owner Education
Provide owner with the owner's manual
Explain operation of system to equipment owner
Explain thermostat use and programming (if applicable) to owner
Explain the importance of regular filter replacement and equipment maintenance