Module 2 Upload
Module 2 Upload
• Maximum demand registered during the month, which is measured in preset time inter-
vals (say of 30 minute duration) and this is reset at the end of every billing cycle.
• Active energy in kWh during billing cycle
• Reactive energy in kVArh during billing cycle and
• Apparent energy in kVAh during billing cycle
It is important to note that while maximum demand is recorded, it is not the instantaneous
demand drawn, as is often misunderstood, but the time integrated demand over the predefined
recording cycle.
As example, in an industry, if the drawl over a recording cycle of 30 minutes is :
2500 kVA for 4 minutes
3600 kVA for 12 minutes
4100 kVA for 6 minutes
3800 kVA for 8 minutes
The MD recorder will be computing MD as:
(2500 x 4) + (3600 x 12) + (4100 x 6) + (3800 x 8) = 3606.7 kVA
30
The month’s maximum demand will be the highest among such demand values recorded
over the month. The meter registers only if the value exceeds the previous maximum demand
value and thus, even if, average maximum demand is low, the industry / facility has to pay for
the maximum demand charges for the highest value registered during the month, even if it
occurs for just one recording cycle duration i.e., 30 minutes during whole of the month. A
typical demand curve is shown in Figure 1.4.
Jan.
Feb.
…….
…….
…….
Dec.
*Some utilities charge Maximum Demand on the basis of minimum billing demand, which may be between 75 to 100% of the contract demand
or actual recorded demand whichever is higher
1. Rescheduling of Loads
Rescheduling of large electric loads and equipment operations, in different shifts can be planned
and implemented to minimize the simultaneous maximum demand. For this purpose, it is advis-
able to prepare an operation flow chart and a process chart. Analyzing these charts and with an
integrated approach, it would be possible to reschedule the operations and running equipment in
such a way as to improve the load factor which in turn reduces the maximum demand.
2. Storage of Products/in process material/ process utilities like refrigeration
It is possible to reduce the maximum demand by building up storage capacity of products/ materi-
als, water, chilled water / hot water, using electricity during off peak periods. Off peak hour oper-
ations also help to save energy due to favorable conditions such as lower ambient temperature etc.
Example: Ice bank system is used in milk & dairy industry. Ice is made in lean period and
used in peak load period and thus maximum demand is reduced.
3. Shedding of Non-Essential Loads
When the maximum demand tends to reach preset limit, shedding some of non-essential loads
temporarily can help to reduce it. It is possible to install direct demand monitoring systems,
which will switch off non-essential loads when a preset demand is reached. Simple systems give
an alarm, and the loads are shed manually. Sophisticated microprocessor controlled systems are
also available, which provide a wide variety of control options like:
Accurate prediction of demand
Graphical display of present load, available load, demand limit
Visual and audible alarm
Automatic load shedding in a predetermined sequence
Automatic restoration of load
Recording and metering
4. Operation of Captive Generation and Diesel Generation Sets
When diesel generation sets are used to supplement the power supplied by the electric utilities,
it is advisable to connect the D.G. sets for durations when demand reaches the peak value. This
would reduce the load demand to a considerable extent and minimize the demand charges.
5. Reactive Power Compensation
The maximum demand can also be reduced at the plant level by using capacitor banks and
maintaining the optimum power factor. Capacitor banks are available with microprocessor based
control systems. These systems switch on and off the capacitor banks to maintain the desired
Power factor of system and optimize maximum demand thereby.
Typical inductive loads are A.C. Motors, induction furnaces, transformers and ballast-type
lighting. Inductive loads require two kinds of power: a) active (or working) power to perform the
work and b) reactive power to create and maintain electro-magnetic fields.
Active power is measured in kW (Kilo Watts). Reactive power is measured in kVAr (Kilo
Volt-Amperes Reactive).
The vector sum of the active power and reactive power make up the total (or apparent) power
used. This is the power generated by the SEBs for the user to perform a given amount of work.
Total Power is measured in kVA (Kilo Volts-Amperes) (See Figure 1.6).
The active power (shaft power required or true power required) in kW and the reactive power
required (kVAr) are 90° apart vectorically in a pure inductive circuit i.e., reactive power kVAr
lagging the active kW. The vector sum of the two is called the apparent power or kVA, as
illustrated above and the kVA reflects the actual electrical load on distribution system.
The ratio of kW to kVA is called the power factor, which is always less than or equal to unity.
Theoretically, when electric utilities supply power, if all loads have unity power factor,
maximum power can be transferred for the same distribution system capacity. However, as the
loads are inductive in nature, with the power factor ranging from 0.2 to 0.9, the electrical dis-
tribution network is stressed for capacity at low power factors.
Voltage Control
Voltage alone can be used as a source of intelligence when the switched capacitors are
applied at point where the circuit voltage decreases as circuit load increases. Generally, where
they are applied the voltage should decrease as circuit load increases and the drop in voltage
should be around 4 – 5 % with increasing load.
Voltage is the most common type of intelligence used in substation applications, when
maintaining a particular voltage is of prime importance. This type of control is independent of
load cycle. During light load time and low source voltage, this may give leading PF at the sub-
station, which is to be taken note of.
KILOVAR Control
Kilovar sensitive controls (see Figure 10.2) are used at loca- tions where the voltage level
is closely regulated and not avail- able as a control variable. The capacitors can be
switched to respond to a decreasing power factor as a result of change insystem loading.
This type ofcontrol can also be used to avoid penalty on low power factor by adding
capacitors in steps as the system power factor begins to lag behind the desired value.
Kilovar control requires two inputs - current and voltage from the incoming feeder, which
arefed to the PF correction mecha- nism, either the microprocessoror the relay.
It controls the power factor of the installation by giving signals to switch on or off power fac-
tor correction capacitors. Relay is the brain of control circuit and needs contactors of appropri-
ate rating for switching on/off the capacitors.
There is a built-in power factor transducer, which measures the power factor ofthe
installation and converts it to a DC voltage of appropriate polarity. This is compared with a
reference voltage, which can be set by means of a knob calibrated in terms of power fac- tor.
When the power factor falls below setting, the capacitors are switched on in sequence. The
relays are provided with First in First out (FIFO) and First in Last Out (FILO) sequence. The
capacitors controlled by the relay must be of the same rating and they are switched on/off in lin-
ear sequence. To prevent over correction hunting, a dead band is provided. This setting deter-
mines the range of phase angle over which the relay does not respond; only when the PF goes
beyond this range, the relay acts. When the load is low, the effect of the capacitors is more pro-
nounced and may lead to hunting. Under current blocking (low current cut out) shuts off the
relay, switching off all capacitors one by one in sequence, when load current is below setting.
Special timing sequences ensure that capacitors are fully discharged before they are switched
in. This avoids dangerous over voltage transient. The solid state indicating lamps (LEDS) dis-
play various functions that the operator should know and also and indicate each capacitor
switching stage.
Intelligent Power Factor Controller (IPFC)
This controller determines the rating of capacitance connected in each step during the first hour
of its operation and stores them in memory. Based on this measurement, the IPFC switches on
the most appropriate steps, thus eliminating the hunting problems normally associated with
capacitor switching.
Thus energy-efficient electric motors reduce energy losses through improved design, better
materials, and improved manu-facturing techniques. Replacing a motor may be justifiable solely
on the electricity cost savings derived from an energy-efficient replacement. This is true if the
motor runs continuously, power rates are high, the motoris oversized for the application, or its
nomi- nal efficiency has been reduced by damage orprevious rewinds. Efficiency comparison for
standard and high efficiency motors is shownin Figure 10.4
Technical aspects of Energy EfficientMotors
Energy-efficient motors last longer, and may require less maintenance. At lower
temperatures, bearing grease lasts longer; required time between re-greasing increases.
Lower temperatures translate to long lasting insulation. Generally, motor life doubles for each
10°C reduction in operating temperature.
Select energy-efficient motors with a 1.15 service factor, and design for operation at 85% of the
rated motor load.
Electrical power problems, especially poor incoming power quality can affect the operation of
energy-efficient motors.
Speed control is crucial in some applications. In polyphase induction motors, slip is a measure
of motor winding losses. The lower the slip, the higher the efficiency. Less slippage in energy
efficient motors results in speeds about 1% faster than in standard counterparts.
Starting torque for efficient motors may be lower than for standard motors. Facility managersshould be
careful when applying efficient motors to high torque applications.
Soft Starter
When starting, AC Induction motor develops more torque than is required at full speed. This
stress is transferred to the mechanical trans- mission system resulting in excessive wear and
premature failure of chains, belts, gears, mechanical seals, etc. Additionally, rapid accelera-tion
also has a massive impact on electricity supply charges with high inrush currents drawing +600%
of the normal run current.
The use of Star Delta only provides a partial solution to the problem. Should the motor slow
down during the transition period,the high peaks can be repeated and can even exceed direct on
line current.
Figure 10.6 Soft Starter: Starting current, Stress profile during starting
Fan Characteristics
Fan characteristics can be represented in form of fan curve(s). The fan curve is a performance
curve for the particular fan under a specific set of conditions. The fan curve is a graphical rep-
resentation of a number of inter-related parameters. Typically a curve will be developed for a
given set of conditions usually including: fan volume, system static pressure, fan speed, and
brake horsepower required to drive the fan under the stated conditions. Some fan curves will
also include an efficiency curve so that a system designer will know where on that curve the fan
will be operating under the chosen conditions (see Figure 5.6). In the many curves shown in the
Figure, the curve static pressure (SP) vs. flow is especially important.
The intersection of the system curve and the static pressure curve defines the operating
point. When the system resistance changes, the operating point also changes. Once the operat-
ing point is fixed, the power required could be found by following a vertical line that passes
through the operating point to an intersection with the power (BHP) curve. A horizontal line
drawn through the intersection with the power curve will lead to the required power on the right
vertical axis. In the depicted curves, the fan efficiency curve is also presented.
System Characteristics and Fan Curves
In any fan system, the resistance to air flow (pressure) increases when the flow of air is
increased. As mentioned before, it varies as the square of the flow. The pressure required by a
system over a range of flows can be determined and a "system performance curve" can be
developed (shown as SC) (see Figure 5.7).
This system curve can then be plotted on the fan curve to show the fan's actual operating
point at "A" where the two curves (N1 and SC1) intersect. This operating point is at air flow Q1
delivered against pressure P1.
A fan operates along a performance given by the manufacturer for a particular fan speed. (The
fan performance chart shows performance curves for a series of fan speeds.) At fan speedN1, the
fan will operate along the N1 performance curve as shown in Figure 5.7. The fan's actual
operating point on this curve will depend on the system resistance; fan's operating point at "A" is
flow (Q1) against pressure (P1).
Figure 5.7 System Curve
Fan Laws
The fans operate under a predictable set of laws concerning speed, power and pressure. A
change in speed (RPM) of any fan will predictably change the pressure rise and power neces-
sary to operate it at the new RPM.
11
Damper Controls
Some fans are designed with damper controls (see Figure 5.11). Damperscan be located at inlet or
outlet. Dampers provide a means of changing air volume by adding or removing system resistance.
This resistance forces the fan to move up or down along its characteristic curve, gener- ating more or
less air without changing fan speed. However, dampers provide a limited amount of adjustment, and
they are not particularly energy efficient.
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air flowing
through the duct. The velocity pressure is used to calculate air velocity.
Total pressure
Total pressure is the sum of the static and velocity pressure. Velocity pressure and static pres- sure
can change as the air flows though different size ducts, accelerating and decelerating the velocity.
The total pressure stays constant, changing only with friction losses. The illustration that follows
shows how the total pressure changes in a system.
The fan flow is measured using pitot tube manometer combination, or a flow sensor (differential
pressure instrument) or an accurate anemometer. Care needs to be taken regardingnumber of traverse
points, straight length section (to avoid turbulent flow regimes of measurement) up stream and
downstream of measurement location. The measurements can be on the suction or discharge side of
the fan andpreferably both where feasible.
Velocity calculation
Once the air density and velocity pressure have been established, the velocity can be determined
from the equation:
Fan efficiency
Fan manufacturers generally use two ways to mention fan efficiency: mechanical
efficiency (sometimes called the total efficiency) and static efficiency. Both measure how
well the fan con- verts horsepower into flow and pressure.
The equation for determining mechanical efficiency is:
x
100
The static efficiency equation is the same except that the outlet velocity pressure is not
added to the fan static pressure
x 100
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate. The cen-
trifugal pump has a curve where the head falls gradually with increasing flow. This is called the
pump characteristic curve (Head - Flow curve) -see Figure 6.8.
If the actual system curve is different in reality to that calculated, the pump will operate at
a flow and head different to that expected.
For a centrifugal pump, an increasing system resistance will reduce the flow, eventually to zero, but the
maximum head is limited as shown. Even so, this condition is only acceptable fora short period without
causing problems. An error in the system curve calculation is also likelyto lead to a centrifugal pump
selection, which is less than optimal for the actual system head losses. Adding safety margins to the calculated
system curve to ensure that a sufficiently large pumpis selected will generally result in installing an
oversized pump, which will operate at an excessive flow rate or in a throttled condition, which increases
energy usage and reduces pump life.
Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they produce
and the pressure (H) at which the flow is delivered. Pump efficiency varies with flow and pres-
sure, and it is highest at one particular flow rate.
The Figure 6.10 below shows a typical vendor-supplied head-flow curve for a centrifugal
pump. Pump head-flow curves are typically given for clear water. The choice of pump for a
given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump.
Figure 6.16 Example for the Effect of Pump Speed Change with a System with High Static Head.
It is relevant to note that flow control by speed regulation is always more efficient than by
control valve. In addition to energy savings there could be other benefits of lower speed. The
hydraulic forces on the impeller, created by the pressure profile inside the pump casing, reduce
approximately with the square of speed. These forces are carried by the pump bearings and so
reducing speed increases bearing life. It can be shown that for a centrifugal pump, bearing life
is inversely proportional to the 7th power of speed. In addition, vibration and noise are reduced
and seal life is increased providing the duty point remains within the allowable operating range.
The corollary to this is that small increases in the speed of a pump significantly increase
power absorbed, shaft stress and bearing loads. It should be remembered that the pump and
motor must be sized for the maximum speed at which the pump set will operate. At higher speed
the noise and vibration from both pump and motor will increase, although for small increases
the change will be small. If the liquid contains abrasive particles, increasing speed will give a
corresponding increase in surface wear in the pump and pipework.
The effect on the mechanical seal of the change in seal chamber pressure, should be reviewed
with the pump or seal manufacturer, if the speed increase is large. Conventional mechanical
seals operate satisfactorily at very low speeds and generally there is no requirement for a
minimum speed to be specified, however due to their method of operation, gas seals require a
minimum peripheral speed of 5 m/s.
Figure 6.18 Typical Head-Flow Curves for Pumps in Parallel, With System Curve Illustrated.
Stop/start control
In this control method, the flow is controlled by switching pumps on or off. It is necessary to
have a storage capacity in the system e.g. a wet well, an elevated tank or an accumulator type
pressure vessel. The storage can provide a steady flow to the system with an intermittent oper-
ating pump. When the pump runs, it does so at the chosen (presumably optimum) duty point and
when it is off, there is no energy consumption. If intermittent flow, stop/start operation and the
storage facility are acceptable, this is an effective approach to minimise energy consumption.
The stop/start operation causes additional loads on the power transmission components and
increased heating in the motor. The frequency of the stop/start cycle should be within the motor
design criteria and checked with the pump manufacturer.
It may also be used to benefit from "off peak" energy tariffs by arranging the run times dur-
ing the low tariff periods.
To minimise energy consumption with stop start control it is better to pump at as low flow
rate as the process permits. This minimises friction losses in the pipe and an appropriately small
pump can be installed. For example, pumping at half the flow rate for twice as long can reduce
energy consumption to a quarter.
Flow control valve
With this control method, the pump runs continuously and a valve in the pump discharge line
is opened or closed to adjust the flow to the required value.
Figure 6.19 Control of Pump Flow by Changing System Resistance Using a Valve.
To understand how the flow rate is controlled, see Figure 6.19. With the valve fully open,
the pump operates at "Flow 1". When the valve is partially closed it introduces an additional
friction loss in the system, which is proportional to flow squared. The new system curve cuts
the pump curve at "Flow 2", which is the new operating point. The head difference between the
two curves is the pressure drop across the valve.
It is usual practice with valve control to have the valve 10% shut even at maximum flow.
Energy is therefore wasted overcoming the resistance through the valve at all flow conditions.
There is some reduction in pump power absorbed at the lower flow rate (see Figure 6.19), but
the flow multiplied by the head drop across the valve, is wasted energy. It should also be noted
that, while the pump will accommodate changes in its operating point as far as it is able within
its performance range, it can be forced to operate high on the curve, where its efficiency is low,
and its reliability is affected.
Maintenance cost of control valves can be high, particularly on corrosive and solids-con-
taining liquids. Therefore, the lifetime cost could be unnecessarily high.
By-pass control
With this control approach, the pump runs continuously at the maximum process demand duty,
with a permanent by-pass line attached to the outlet. When a lower flow is required the surplus
liquid is bypassed and returned to the supply source.
An alternative configuration may have a tank supplying a varying process demand, which
is kept full by a fixed duty pump running at the peak flow rate. Most of the time the tank over-
flows and recycles back to the pump suction. This is even less energy efficient than a control
valve because there is no reduction in power consumption with reduced process demand.
The small by-pass line sometimes installed to prevent a pump running at zero flow is not a
means of flow control, but required for the safe operation of the pump.
Q = flow
H = head
BHP = brake horsepower of the pump motor
Subscript 1 = original pump,
Subscript 2 = pump after impeller trimming
D = Diameter
Trimming an impeller changes its operating efficiency, and the non-linearities of the Affinity
Laws with respect to impeller machining complicate the prediction of pump perfor- mance.
Consequently, impeller diameters are rarely reduced below 70 percent of their original size.
Electronic Ballast
Role of Ballast
In an electric circuit the ballast acts as a stabilizer. Fluorescent lamp is an electric discharge
lamp. The two electrodes are separated inside a tube with no apparent connection between them.
When sufficient voltage is impressed on these electrodes, electrons are driven from one electrode
and attracted to the other. The current flow takes place through an atmosphere of low-pressure
mercury vapour.
Since the fluorescent lamps cannot produce light by direct connection to the power source,
they need an ancillary circuit and device to get started and remain illuminated. The auxillary
circuit housed in a casing is known as ballast.
One of largest advantages of an electronic ballast is the enormous energy savings it pro-
vides. This is achieved in two ways. The first is its amazingly low internal core loss, quite unlike
old fashioned magnetic ballasts. And second is increased light output due to the excita- tion of
the lamp phosphors with high frequency. If the period of frequency of excitation is smaller than
the light retention time constant for the gas in the lamp, the gas will stay ionized and, therefore,
produce light continuously. This phenomenon along with continued persistenceof the phosphors
at high frequency will improve light output from 8–12 percent. This is possi- ble only with high
frequency electronic ballast.
Localized Switching
Localized switching should be used in applications which contain large spaces. Local switches
give individual occupants control over their visual environment and also facilitate energy savings.
By using localized switching it is possible to turn off artificial lighting in specific areas, while still
operating it in other areas where it is required, a situation which is impossible if the lighting for an
entire space is controlled from a single switch