FOCUSED ON APPLICATION HVAC

Unit information
Chiller Model CA2-485-4210
Width (mm) 2250
Length (mm) 11970
Height (mm) 2520
Shipping Weight (kg) 12040
Operating Weight (kg) 12240
Capacity Control Stepless Control
Starting Control Y-
Operating Range T1
Refrigerant R134a

Performance Information(Cooling Condition) Compressor Information


Cooling Capacity (TR) 485 1715 kW Type Semi-Hermetic Screw
Entering Water T 12 53.60 F° Quantity 2
Leaving Water T 7 44.60 F° Capacity Regulating Range 12.5%-100%
Water Flow (m3/h) 295 Oil Charging Volume(L) 68
Ambient T 35 95.00 F° Brand BITZER
Ambient T / Circuit 2
Input Power (kW) 510.8 Oil Model BSE170
IPLV/NPLV.SI(W/W) 4.83
COP (W/W) 3.36
Air Side Heat Exchanger Information
Type Fin-Tube
Water Side Heat Exchanger Information Fan Quantity 20
Fluid Type Fresh Water Air Flow(m3/h) 450000
Concentration / Fan Power Input(kW) 44
Nozzle Type Victaulic Couping
Water Volume(L) 304
Heat Exchanger Type Flooded Shell-and-Tube Electrical Information
Fouling Factor ((m2.K)/kW) 0.0180 Power Supply 460V~3N~60Hz
Nozzle Size(DN) 200 Rating Current (A) 711
Water Pressure Drop (kPa) 73 Max. Starting Current (A) 1260

* Resortes anti-vibratorios
*Refrigerante ecológico

1
IPLV/NPLV Points
Cooling Input Cooling Cooling Evap.
Load DBT DBT WBT WBT EEWT EEWT ELWT ELWT
capacity Power kW/Ton COP WPD
% Kw Kw KW/TON W/W kpA C° F° C° F° C° F° C° F°
100 1715 510.8 0.94 3.36 73 35.00 95.00 / / 12.00 53.6 7.00 44.6
75 1286 315.2 0.77 4.08 73 27.00 80.6 / / 10.80 51.44 7.00 44.6
50 858 158.0 0.58 5.43 73 19.00 66.2 / / 9.50 49.1 7.00 44.6
25 429 80.3 0.59 5.34 73 13.00 55.4 / / 8.30 46.94 7.00 44.6

IPLV.SI/NPLV.SI=0.01*A+0.42*B+0.45*C+0.12*D=4.832 w/w
A=EER At 100%; B=EER At 75%; C=EER At 50%; D=EER At 25%;

Soft in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Using Vapor
Compression Cycle, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Ten Points Parameters (Constant Ambient Temp.)
Cooling Input Cooling Cooling Evap.
Load DBT DBT WBT WBT EEWT EEWT ELWT ELWT
capacity Power kW/Ton COP WPD
% Kw Kw KW/TON W/W kpA C° F° C° F° C° F° C° F°
100 1715 510.8 0.94 3.36 73 35.00 95.00 / / 12.00 53.6 7.00 44.6
90 1544 434.6 0.95 3.32 73 35.00 95.00 / / 11.50 52.7 7.00 44.6
80 1372 421.2 0.97 3.26 73 35.00 95.00 / / 11.00 51.8 7.00 44.6
70 1201 380.3 1.00 3.16 73 35.00 95.00 / / 10.50 50.9 7.00 44.6
60 1029 341.9 1.05 3.01 73 35.00 95.00 / / 10.00 50 7.00 44.6
50 858 255.3 0.94 3.36 73 35.00 95.00 / / 9.50 49.1 7.00 44.6
40 686 210.6 0.97 3.26 73 35.00 95.00 / / 9.00 48.2 7.00 44.6
30 515 171 1.05 3.01 73 35.00 95.00 / / 8.50 47.3 7.00 44.6
20 343 136.5 1.26 2.51 73 35.00 95.00 / / 8.00 46.4 7.00 44.6
10 172 / / / 73 35.00 95.00 / / 7.50 45.5 7.00 44.6
For single COMP chiller, the 10% and 20% load are out of running range, so the data is only for reference;For double
COMP chiller, the 10% load are out of running range, so the data is only for reference

2
Ten Points Parameters (Variable Ambient Temp)
Cooling Input Cooling Cooling Evap.
Load DBT DBT WBT WBT EEWT EEWT ELWT ELWT
capacity Power kW/Ton COP WPD
% Kw Kw KW/TON W/W kpA C° F° C° F° C° F° C° F°
100 1715 510.8 0.94 3.36 73 35.00 95.00 / / 12.00 53.6 7.00 44.6
90 1544 421.2 0.86 3.67 73 31.80 89.24 / / 11.50 52.7 7.00 44.6
80 1372 346.7 0.80 3.96 73 28.60 83.48 / / 11.00 51.8 7.00 44.6
70 1201 284.6 0.75 4.22 73 25.40 77.72 / / 10.50 50.9 7.00 44.6
60 1029 233 0.71 4.42 73 22.20 71.96 / / 10.00 50 7.00 44.6
50 858 158 0.58 5.43 73 19.00 66.20 / / 9.50 49.1 7.00 44.6
40 686 119.2 0.55 5.76 73 15.80 60.44 / / 9.00 48.2 7.00 44.6
30 515 89.7 0.55 5.74 73 13.00 55.40 / / 8.50 47.3 7.00 44.6
20 343 71.5 0.66 4.80 73 13.00 55.40 / / 8.00 46.4 7.00 44.6
10 172 / / / 73 13.00 55.40 / / 7.50 45.5 7.00 44.6

For single COMP chiller, the 10% and 20% load are out of running range, so the data is only for reference;
For double COMP chiller,the 10% load are out of running range, so the data is only for reference

Entrada de Agua
Salida de Agua

A B C
Dimension(mm)
11970 2250 2520
NOTE:The outline drawing is only for reference.