3 2 1 Key Plan:

TCL=188.93kW
ACL=177.3kW ESMDB-ME-L29-01
TDL=141.84kW
TCL=67.65kW
TDL=60.89kW
FED FROM SMDB-TN-L28-01
TCL=257.99 kW ESMDB-TN-L28-01
ESMDB-LL-L29-01
TDL=206.39 kW
LEVEL (L29)

CLUB LEVEL (L28)


TCL=74.80kW NOTES:
TDL=67.32kW
FED FROM SMDB-TN-L27-01
1. ALL THE CONTROL PANELS PROVIDED FOR MECHANICAL EQUIPMENT
ESMDB-TN-L27-01 SHALL BE PROVIDED WITH INTEGRATED DISCONNECTING
CLUB LEVEL (L27)
MEANS/ISOLATOR SWITCH AND ELECTRICAL SCOPE WILL BE LIMITED
TCL=25.52kW TO THE NECESSARY POWER TERMINATIONS TO THESE CONTROL
TDL=22.97kW PANELS ONLY. THE CABLES AND CONTAINMENT FROM CONTROL
FED FROM SMDB-TN-L26-01 PANELS TO THE MECHANICAL EQUIPMENT SHALL BE PART OF
ESMDB-TN-L26-01 MECHANICAL SCOPE.
CLUB LEVEL (L26) FIRE PUMP CONTROL PANEL

M *FEEDER FOR THE INTEGRATED ATS WITHIN


C.P CONTROL PANEL FOR MECHANICAL EQUIPMENT
THE FIRE PUMP (EMERGENCY FEEDER)

189KW
FIRE PUMP-L13-01
FIRE PUMP CONTROL PANEL 2. LEGENDS FOR EV CHARGER PROVISION
DUTY EV-B1-XX : IN SCOPE EV CHARGER OF 7.4kW FOR OFFICE
C .. M
. *FEEDER FOR THE INTEGRATED ATS WITHIN
.. 189KW THE FIRE PUMP (EMERGENCY FEEDER)

.
.. FIRE PUMP-L13-01
STANDBY
MEP LEVEL (L13)
FIRE PUMP CONTROL PANEL

FIRE PUMP CONTROL PANEL


M *FEEDER FOR THE INTEGRATED ATS WITHIN
THE FIRE PUMP (EMERGENCY FEEDER)

M 156 KW

FIRE PUMP CONTROL PANEL FIRE PUMP-P6-01


156 KW
DUTY
EFP-LL-P06-01
M
STANDBY *FEEDER FOR THE INTEGRATED ATS WITHIN

.. 156 KW THE FIRE PUMP (EMERGENCY FEEDER)

1(1C,240mm²) FRE L=215m S.C.=11.30kA


..

L=225m S.C.=9.90kA
FIRE PUMP-P6-01

V.D.=3.15%
V.D.= 3.34%
.
..
STANDBY
PODIUM FLOOR (P6)
V.D.= 1.86%
L=40m S.C.=12.20kA V.D.= 2.33%
L=120m S.C.=5.00kA V.D.= 1.70% FED FROM SMDB-TN-L28-01
L=45m S.C.=14.80kA TCL=21.77kW, TDL=15.24kW ESMDB-TN-P5-01

2(4C,240mm²) FR6 +

2(4C,185mm²) FR6 +

1(4C,120mm²) FR6 +
1(4C,70mm²) FR6 +

1(4C,70mm²) FR6 +
1(1C,185mm²) FRE

TDL=28.01 kW
TCL=33.45 kW
TCL=35.5kW

1(1C,35mm²) FRE

1(1C,35mm²) FRE

1(1C,70mm²) FRE
SMDB-TN-P6-01 FED FROM SMDB-TN-L28-01
TDL=25.1kW TCL=21.77kW, TDL=15.24kW ESMDB-TN-P5-02

SPARE
DEWA
KILO-WATT METER CT
FED FROM SMDB-TN-L28-01
TCL=21.77kW, TDL=15.24kW ESMDB-TN-P5-03
PODIUM FLOOR (P5)

PODIUM FLOOR (P3)


..
.
..
. TCL=79.86 kW SMDB-ME-P4-01
..
TDL=63.89 kW
PODIUM FLOOR (P4)
..
.
.. TCL=202.70 kW
. SMDB-P1-LL-01
..
TDL=169.60 kW
PODIUM FLOOR (P1)

630A 500A 160A 160A 225A 80A


TP TP TP TP TP TP
MCCB MCCB MCCB MCCB MCCB MCCB

1600A,3PH+N+E,50kA,1 SEC
AMMETER 1600/5A
WITH MDI (CLASS-1)
R Y B 2A
20A

TOTAL CONNECTED LOAD 738.69 kW


ACTUAL CONNECTED LOAD 725.20 kW
1600A TOTAL DEMAND LOAD 565.40kW
4P,PACB *D.F. ON FIRE PUMP=0

EMDB-LL-GF-01 2500A BUSDUCT TO

(4C, 16mm² CU/XLPE/SWA/LSOH)

(4C, 16mm² CU/XLPE/SWA/LSOH)

(4C, 16mm² CU/XLPE/SWA/LSOH)

(4C, 35mm² CU/XLPE/SWA/LSOH)

(4C, 50mm² CU/XLPE/SWA/LSOH)

(4C, 50mm² CU/XLPE/SWA/LSOH)


WORST CASE DEMAND LOAD FOR GENERATOR LOADING 565.40kW MDB-GF-07
2A
FORM4-TYPE6 0-500V 20A *CONSIDERING WORST CASE OF POWER FAILURE & FIRE SCENERIO (FIRE RATED)

+(1C,16mm² CU/LSOH)

+(1C,16mm² CU/LSOH)

+(1C,16mm² CU/LSOH)

+(1C,16mm² CU/LSOH)

+(1C,25mm² CU/LSOH)

+(1C,25mm² CU/LSOH)
1600A,

2(4C,150mm²) FR6 +

2(4C,150mm²) FR6 +

2(4C,240mm²) FR6 +

2(4C,240mm²) FR6 +
4P

1(1C,150mm²) FRE

1(1C,150mm²) FRE

1(1C,240mm²) FRE

1(1C,240mm²) FRE
ATS

B
TD-ADDENDUM
DB-LL-GF-06

(SUBSTATION DB)
L=100m S.C.=17.40kA

S.C.=29.00kA

SPARE
V.D.= 1.34%
S.C.=22.70kA

V.D.= 1.65%

V.D.= 1.65%

V.D.=1.07%
L=110m S.C.=7.20kA

L=110m S.C.=7.20kA
V.D.= 0.97%
V.D.= 1.12%
S.C.=9.10kA
+(1C,150mm² CU/PVC) L=135m S.C.=11.40kA
(4C, 300mm² CU/XLPE/SWA/PVC) V.D.= 2.17%

CL=8.60KW

POWER FACTOR 4(4C, 300mm² FR6) +


S.C.=10.50kA
(4C, 70mm² CU/XLPE/SWA/PVC) V.D.= 0.99%

CORRECTION 2(1C,300mm² FRE)


300kVAR
TO BE
CONNECTED
TO EMS
L=10m
L=60m
L=65m

SYSTEM EM EM EM EM EM EM
2(4C, 150mm² CU/XLPE/SWA/PVC)

2(4C, 150mm² CU/XLPE/SWA/PVC)

2(4C, 300mm² CU/XLPE/SWA/PVC)


(4C, 70mm² CU/XLPE/SWA/PVC)

(4C, 95mm² CU/XLPE/SWA/PVC)

(4C, 25mm² CU/XLPE/SWA/PVC)

(4C, 10mm² CU/XLPE/SWA/PVC)

1600A 2500A 40A 40A 40A 40A 500A 500A 630A 630A 60A 80A 80A
+(1C,35mm² CU/PVC) L=55m

4P,PACB 4P,PACB TP TP TP TP TP TP TP TP TP TP TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
TDL=24.67 kW

TDL=24.67 kW
TCL=30.67 kW

TCL=30.67 kW
+(1C,150mm² CU/PVC)

+(1C,150mm² CU/PVC)

PROVISIONAL BREAKER
FOR HARMONIC FILTER
+(1C,300mm² CU/PVC)
+(1C,35mm² CU/PVC)

+(1C,50mm² CU/PVC)

+(1C,16mm² CU/PVC)

D TD 25/06/2024 GENERAL REVISION K.M.


+2(1C,300mm² FRE)

+(1C,10mm² CU/PVC)
4(4C, 300mm² FR6)

5000A,3PH+N+E,50kA,1 SEC
SPARE

SPARE

2500A 2500A C TD 07/06/2024 APPROVED ISSUE K.M.


4P,PACB 4P,PACB
B DD 25/04/2024 APPROVED ISSUE K.M.
GEN. SYNC. PANEL A SD 06/02/2024 APPROVED ISSUE K.M.
Rev Phase Date Description Appr

160A 400A 160A 500A 200A 80A 500A 1600A 630A 200A 40A 60A 60A PROJECT NO. DIFC-170 LOCATION: DUBAI-DIFC
TP TP TP TP TP TP TP TP M TP TP TP TP TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
2500A BUSDUCT 2500A BUSDUCT
(FIRE RATED) (FIRE RATED)
CLIENT:
2500A,3PH+N+E,50kA,1 SEC TO BE
EM
TO BE
EM WHOLE-BUILDING LEVEL METERS SHALL
400V, 50Hz CONNECTED TO CONNECTED TO BE PERMANENTLY INSTALLED METERS. GP GP
EMS SYSTEM EMS SYSTEM
DEWA 2400/5A AMMETER
KILO-WATT METER CT
(CLASS-1) WITH MDI
G1 G1
AMMETER 2400/5A 2A B Y R
(CLASS-1) 20A
WITH MDI GEN-GF-01 GEN-GF-02
R Y B 2A 1600KVA 1600KVA
20A
PRIME RATED GENERATOR 3Ø, PRIME RATED GENERATOR 3Ø,
OVER VOLTAGE SPD
SURGE PANEL 50Hz, 400V 50Hz, 400V
63A
PROJECT MANAGER:
2500A 2500A TOTAL CONNECTED LOAD 1610.30 kW
4P,PACB 4P,PACB ACTUAL CONNECTED LOAD 1516.38 kW
M&E INTERLOCK
TOTAL DEMAND LOAD 1108.90 kW

MDB-GF-08 2A 2A
*D.F. ON FIRE PUMP=0
TURNER CONSTRUCTION INTERNATIONAL LLC
FORM4-TYPE6 0-500V 20A 20A 0-500V P.O. BOX 13036 | DUBAI | UNITER ARAB EMIRATES

PROVISION FOR
MOBILE GENERATOR
CONSULTANT:

PROJECT SCOPE
DEWA SCOPE
FROM TRANSFORMER 07
TCL=113.94 kW
TDL=77.88 kW
ESMDB-LL-GF-01
(SERVICES)

GROUND FLOOR (GF)


TCL=49.50 kW
TCL=74.16 KW EMCP-ETS-B1-01
SMDB-EV-B1-01 TDL=39.60 kW
TDL=51.91 kW

TCL=93.33kW ESMDB-LL-B1-01
TCL=179.44 kW TDL=71.69kW
MCP-ETS-B1-01
ACL=134.43 kW (SERVICES)
BASEMENT-01 (B1) TDL=120.90 kW

A A

BASEMENT-02 (B2)

TCL=74.00 kW
SMDB-EV-B3-01
TDL=51.80 kW PROJECT TITLE:

IMMERSIVE TOWER by DIFC


DESIGN PACKAGE
Plot No. PA07A DIFC, Dubai, UAE

DRAWING TITLE:
BASEMENT-03 (B3) LOW VOLTAGE SYSTEM
SCHEMATIC DIAGRAM

SCALE DRAWN CHECKED AUTHORIZED SIZE


V.S. A.K./S.G. K.M.
N.T.S.
A1

DWG No. PA07A-DIFC-ELG-GEN-SCH-GEN-6005-D


3 2