Pa07a Difc Elg Gen SCH Gen 6005 D
Pa07a Difc Elg Gen SCH Gen 6005 D
TCL=188.93kW
ACL=177.3kW ESMDB-ME-L29-01
TDL=141.84kW
TCL=67.65kW
TDL=60.89kW
FED FROM SMDB-TN-L28-01
TCL=257.99 kW ESMDB-TN-L28-01
ESMDB-LL-L29-01
TDL=206.39 kW
LEVEL (L29)
189KW
FIRE PUMP-L13-01
FIRE PUMP CONTROL PANEL 2. LEGENDS FOR EV CHARGER PROVISION
DUTY EV-B1-XX : IN SCOPE EV CHARGER OF 7.4kW FOR OFFICE
C .. M
. *FEEDER FOR THE INTEGRATED ATS WITHIN
.. 189KW THE FIRE PUMP (EMERGENCY FEEDER)
.
.. FIRE PUMP-L13-01
STANDBY
MEP LEVEL (L13)
FIRE PUMP CONTROL PANEL
M 156 KW
L=225m S.C.=9.90kA
FIRE PUMP-P6-01
V.D.=3.15%
V.D.= 3.34%
.
..
STANDBY
PODIUM FLOOR (P6)
V.D.= 1.86%
L=40m S.C.=12.20kA V.D.= 2.33%
L=120m S.C.=5.00kA V.D.= 1.70% FED FROM SMDB-TN-L28-01
L=45m S.C.=14.80kA TCL=21.77kW, TDL=15.24kW ESMDB-TN-P5-01
2(4C,240mm²) FR6 +
2(4C,185mm²) FR6 +
1(4C,120mm²) FR6 +
1(4C,70mm²) FR6 +
1(4C,70mm²) FR6 +
1(1C,185mm²) FRE
TDL=28.01 kW
TCL=33.45 kW
TCL=35.5kW
1(1C,35mm²) FRE
1(1C,35mm²) FRE
1(1C,70mm²) FRE
SMDB-TN-P6-01 FED FROM SMDB-TN-L28-01
TDL=25.1kW TCL=21.77kW, TDL=15.24kW ESMDB-TN-P5-02
SPARE
DEWA
KILO-WATT METER CT
FED FROM SMDB-TN-L28-01
TCL=21.77kW, TDL=15.24kW ESMDB-TN-P5-03
PODIUM FLOOR (P5)
1600A,3PH+N+E,50kA,1 SEC
AMMETER 1600/5A
WITH MDI (CLASS-1)
R Y B 2A
20A
+(1C,16mm² CU/LSOH)
+(1C,16mm² CU/LSOH)
+(1C,16mm² CU/LSOH)
+(1C,16mm² CU/LSOH)
+(1C,25mm² CU/LSOH)
+(1C,25mm² CU/LSOH)
1600A,
2(4C,150mm²) FR6 +
2(4C,150mm²) FR6 +
2(4C,240mm²) FR6 +
2(4C,240mm²) FR6 +
4P
1(1C,150mm²) FRE
1(1C,150mm²) FRE
1(1C,240mm²) FRE
1(1C,240mm²) FRE
ATS
B
TD-ADDENDUM
DB-LL-GF-06
(SUBSTATION DB)
L=100m S.C.=17.40kA
S.C.=29.00kA
SPARE
V.D.= 1.34%
S.C.=22.70kA
V.D.= 1.65%
V.D.= 1.65%
V.D.=1.07%
L=110m S.C.=7.20kA
L=110m S.C.=7.20kA
V.D.= 0.97%
V.D.= 1.12%
S.C.=9.10kA
+(1C,150mm² CU/PVC) L=135m S.C.=11.40kA
(4C, 300mm² CU/XLPE/SWA/PVC) V.D.= 2.17%
CL=8.60KW
SYSTEM EM EM EM EM EM EM
2(4C, 150mm² CU/XLPE/SWA/PVC)
1600A 2500A 40A 40A 40A 40A 500A 500A 630A 630A 60A 80A 80A
+(1C,35mm² CU/PVC) L=55m
4P,PACB 4P,PACB TP TP TP TP TP TP TP TP TP TP TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
TDL=24.67 kW
TDL=24.67 kW
TCL=30.67 kW
TCL=30.67 kW
+(1C,150mm² CU/PVC)
+(1C,150mm² CU/PVC)
PROVISIONAL BREAKER
FOR HARMONIC FILTER
+(1C,300mm² CU/PVC)
+(1C,35mm² CU/PVC)
+(1C,50mm² CU/PVC)
+(1C,16mm² CU/PVC)
+(1C,10mm² CU/PVC)
4(4C, 300mm² FR6)
5000A,3PH+N+E,50kA,1 SEC
SPARE
SPARE
160A 400A 160A 500A 200A 80A 500A 1600A 630A 200A 40A 60A 60A PROJECT NO. DIFC-170 LOCATION: DUBAI-DIFC
TP TP TP TP TP TP TP TP M TP TP TP TP TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
2500A BUSDUCT 2500A BUSDUCT
(FIRE RATED) (FIRE RATED)
CLIENT:
2500A,3PH+N+E,50kA,1 SEC TO BE
EM
TO BE
EM WHOLE-BUILDING LEVEL METERS SHALL
400V, 50Hz CONNECTED TO CONNECTED TO BE PERMANENTLY INSTALLED METERS. GP GP
EMS SYSTEM EMS SYSTEM
DEWA 2400/5A AMMETER
KILO-WATT METER CT
(CLASS-1) WITH MDI
G1 G1
AMMETER 2400/5A 2A B Y R
(CLASS-1) 20A
WITH MDI GEN-GF-01 GEN-GF-02
R Y B 2A 1600KVA 1600KVA
20A
PRIME RATED GENERATOR 3Ø, PRIME RATED GENERATOR 3Ø,
OVER VOLTAGE SPD
SURGE PANEL 50Hz, 400V 50Hz, 400V
63A
PROJECT MANAGER:
2500A 2500A TOTAL CONNECTED LOAD 1610.30 kW
4P,PACB 4P,PACB ACTUAL CONNECTED LOAD 1516.38 kW
M&E INTERLOCK
TOTAL DEMAND LOAD 1108.90 kW
MDB-GF-08 2A 2A
*D.F. ON FIRE PUMP=0
TURNER CONSTRUCTION INTERNATIONAL LLC
FORM4-TYPE6 0-500V 20A 20A 0-500V P.O. BOX 13036 | DUBAI | UNITER ARAB EMIRATES
PROVISION FOR
MOBILE GENERATOR
CONSULTANT:
PROJECT SCOPE
DEWA SCOPE
FROM TRANSFORMER 07
TCL=113.94 kW
TDL=77.88 kW
ESMDB-LL-GF-01
(SERVICES)
TCL=93.33kW ESMDB-LL-B1-01
TCL=179.44 kW TDL=71.69kW
MCP-ETS-B1-01
ACL=134.43 kW (SERVICES)
BASEMENT-01 (B1) TDL=120.90 kW
A A
BASEMENT-02 (B2)
TCL=74.00 kW
SMDB-EV-B3-01
TDL=51.80 kW PROJECT TITLE:
DRAWING TITLE:
BASEMENT-03 (B3) LOW VOLTAGE SYSTEM
SCHEMATIC DIAGRAM